socomec MASTERYS BC 60 kVA, MASTERYS BC 80 Installation And Operating Manual

MASTERYS BC
60-80 kVA
Installations- und bedienungsanleitung
DE
Installation and operating manual
EN
ES
Paigaldus- ja kasutusjuhend
ET
Asennus- ja käyttöohje
FI
Manuel d’installation et d’utilisation
FR
Manuale di installazione e uso
IT
Installatie– en bedieningshandleiding
NL
Dokumentacja Techniczno-Ruchowa
PL
Manual de instalação e funcionamento
PT
Manual de instalare şi utilizare
RO
Руководство по установке и эксплуатации
RU
Navodila za priključitev in uporabo
SL
Installations- och användarhandbok
SV
Kurulum ve kullanım kılavuzu
TR
安装及操作手册
ZH
2
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
This SOCOMEC continuous power system is guaranteed against any manufacturing or material defects. The warranty is valid for 12 (twelve) months from the commission date, provided activation is carried out by SOCOMEC person-
nel or personnel from a support centre authorised by SOCOMEC, and no more than 15 (fifteen) months from being shipped from SOCOMEC.
The warranty is valid throughout national territory. If the UPS is exported abroad, the warranty will only cover the parts used to repair faults.
The warranty is valid ex-works and covers labour and parts used to repair the faults.
The warranty shall not apply in the following cases:
• Failure due to unforeseen circumstances or force majeure (lightning, floods, etc.);
• Failure due to negligence or improper use (use outside limits: temperature, humidity, ventilation, electric power supply, applied load, batteries);
• Insufficient or inappropriate maintenance;
• When maintenance, repairs or modifications have not been carried out by SOCOMEC personnel, or personnel from a support centre authorised by SOCOMEC.
• If the battery has not been recharged in accordance with the terms indicated on the packaging and in the manual, in the event of long periods of storage or UPS inactivity.
SOCOMEC may, at its own discretion, opt for the repair of the product or the replacement of faulty or defective parts with new parts, or with used parts of equivalent quality to new parts with regard to function and performance.
Defective or faulty parts replaced free of charge must be made available to SOCOMEC, which becomes the sole owner. Replacement or repair of parts, or any modifications to the product during the warranty period, will not extend the duration of the
warranty. SOCOMEC will not be responsible for damages under any circumstances (including, without limitations, damage for loss of earnings,
interruption of activity, loss of information or other financial losses) arising from the use of the product. These conditions are subject to Italian law. Any disputes fall under the jurisdiction of the Court of Vicenza.
CERTIFICATE AND CONDITIONS OF WARRANTY
SOCOMEC retains the full and exclusive ownership rights to this document. Only a personal entitlement to use the document for the application indicated by SOCOMEC is granted to the recipient of this document. The reproduction, modification, distribution of this document, either partially or wholly and in any manner, is strictly prohibited except upon Socomec’s express prior written consent.
This document is not a specification. SOCOMEC reserves the right to make any changes to the information provided without prior notice.
3
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
SUMMARY
ENGLISH
1. SAFETY STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.1. IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.2.
DESCRIPTION OF SYMBOLS USED ON LABELS ATTACHED TO THE UNIT
. .5
2. UNPACKING AND INSTALLATION OF THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.1. SHIPPING AND MOVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.2. ENVIRONMENTAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.3. ELECTRICAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.4. INSTALLATION PROCEDURES AND INSTRUCTIONS . . . . . . . . . . . . . . .8
2.5. GENERATOR CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
2.6. EXTERNAL ESD CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
2.7. UPS PARALLEL CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.8. CONTROL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.9. EXTERNAL BATTERY CABINET CONNECTION . . . . . . . . . . . . . . . . . .14
3. MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.1. ON LINE OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.2. OPERATION IN HIGH EFFICIENCY MODE . . . . . . . . . . . . . . . . . . . . . .15
3.3. OPERATION WITH MANUAL MAINTENANCE BYPASS. . . . . . . . . . . . .15
3.4. OPERATION WITH EXTERNAL MANUAL BYPASS (OPTIONAL) . . . . . .16
4. ACCESS TO CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
4.1. IDENTIFYING SWITCHES AND INTERFACES . . . . . . . . . . . . . . . . . . . .17
4.2. SWITCH FUNCTIONS FOR THE 60-80 KVA RANGE . . . . . . . . . . . . . .18
5. MIMIC PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
5.1. BASIC MIMIC PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
6. OPERATING PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
7. CONNECTIVITY AND COMMUNICATION OPTIONS . . . . . . . . . . . . . . . . . . . . . . .28
7.1. MULTI-LEVEL COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
7.2. ADC CARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
7.3. REMOTE MIMIC PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
7.4. NET VISION LAN/WEB INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . .30
7.5. PROFIBUS INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
7.6. SOFTWARE OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
8. TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
8.1. SYSTEM ALARMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
8.2. UPS ALARMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
8.3. PREVENTIVE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
9. ELECTRICAL OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
9.1. INSULATION CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
9.2. EXTERNAL MAINTENANCE BYPASS . . . . . . . . . . . . . . . . . . . . . . . . . .34
9.3. ACS PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
9.4. SEPARATE AUXILIARY POWER SUPPLY . . . . . . . . . . . . . . . . . . . . . . .34
9.5. EXTERNAL BACKFEED PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . .34
9.6.
PROTECTION ON MAINS SUPPLY AND ON AUXILIARY MAINS SUPPLY
. .35
9.7. PROTECTION ON A UPS WITHOUT AUXILIARY MAINS SUPPLY . . . . .35
10. TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
4
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
1.1. IMPORTANT
• This document provides important instructions for the safe use, movement and connection of the MASTERYS BC uninterrupt­ible power system (UPS).
• SOCOMEC retains the full and exclusive ownership rights over this document. Only a personal right to use the document for the application indicated by SOCOMEC is granted to the recipient of the document. The reproduction, modifi cation, distribution of this document either partially or wholly, and in any way, is strictly prohibited except upon Socomec’s express prior written consent.
• This document is not a specifi cation. SOCOMEC reserves the right to make any changes to information provided without prior notice.
• The unit must only be installed and activated by qualifi ed technical personnel who have been authorised by SOCOMEC.
The UPS MUST only be moved by two people at least. They MUST take position at the sides of the UPS with respect to the direction of movement.
• The unit must remain in a vertical position at all times.
• Connect the PE ground conductor fi rst before making any other connection.
• Do not expose the UPS to rain or liquids in general. Do not insert foreign bodies.
The installer is responsible for implementing the backfeed protection with the use of AC input line isolation devices external to the UPS (see section 2.4.1).
Before working on this circuit
- Isolate the Uninterruptible Power System (UPS)
- Then check for Hazardous Voltage between all terminals including the protective earth
Risk of Voltage Backfeed
• For the purpose of warning electrical technicians against backfeed situations not caused by the UPS, which may arise when a particular load fault is present while the UPS is operating in stored energy mode, or while unbalanced loads are supplied through a particular power distribution system e.g. an impedance grounded IT system, the installer must attach the labels provided to all primary power isolators installed remotely from the UPS area and on external access points, if present, between the said isolators and the UPS. In particular the label must be attached to the external AC input line isolation service (backfeed insulation).
• Keep this manual in a convenient place for future consultation.
• If the unit fails, it must only be repaired by authorised technicians who have been specially trained for this purpose.
• This equipment complies with European Community directives for industrial equipment and bears the approval mark
• The UPS requires three-phase plus neutral input connections (3P+N).
• Do not connect the output neutral to ground. The UPS does not modify the neutral setup of the system; the use of an isolation transformer is required should it be necessary to modify the neutral setup downstream of the UPS.
• Before connecting any external battery cabinets, ensure they are fully compatible with the UPS model used.
• The use of external battery cabinets not supplied by the manufacturer is not recommended.
• Switch o and isolate the UPS and wait for 5 minutes before removing the protection panels in order to carry out work on parts under dangerous voltage.
• Risk of explosion if batteries are replaced with others of the wrong type.
• Used batteries must be disposed of at authorised waste disposal centres.
It is very dangerous to touch any part of the batteries as there is no insulation between the batteries and the mains power source.
The product you have chosen is designed for commercial and industrial use only. If used for particular critical applications such as life support systems, medical applications, commercial transportation, nuclear facilities or any other application or systems where product failure is likely to cause substantial harm to people or property, the products may have to be adapted.
For such use please contact SOCOMEC beforehand to check if these products to meet the required level of safety, performance, reliability and comply with applicable laws, regulations and specifi cations.
WARNING! This is a product for commercial and industrial application in the second environment - installation restrictions or additional measures may be needed to prevent disturbances.
1. SAFETY STANDARDS
5
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
ENGLISH
1. SAFETY STANDARD
1.2. DESCRIPTION OF SYMBOLS USED ON LABELS ATTACHED TO THE UNIT
All precautions and warnings on labels and plates inside and outside the equipment should be observed.
DANGER! HIGH VOLTAGE (BLACK/YELLOW)
GROUND TERMINAL
READ THE USER MANUAL BEFORE USING THE UNIT
6
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
The packaging guarantees the stability of the UPS during shipping and physical transfer. Carry the packaged unit as close as possible to the installation site.
When moving the unit on even slightly sloping surfaces, use the blocking equipment and braking devices to ensure that the unit does not fall over.
2.1. SHIPPING AND MOVING
• The UPS must remain in a vertical position during all shipping and moving operations.
• The unit has wheels that can be used to move it for short distances.
• Ensure the floor is strong enough to support the weight of the UPS and battery cabinet, if used.
Avoid pressing on the front panels when moving the unit.
The UPS MUST only be moved by two people at least. They MUST take position at the sides of the UPS with respect to the direction of movement.
CAUTION IF DAMAGED NON-SPILLABLE BATTERIES If packaging is crushed, ripped or open such that the inner contents are revealed, the equipment should be kept in
an isolated area and inspected by a qualified person. If the packaging cannot be shipped the contents should be collected promptly, kept apart, and the sender or recipient should be contacted.
All packaging must be recycled in compliance with existing legislation in the country where the system is installed.
2. UNPACKING AND INSTALLATION OF THE UNIT
2.2. ENVIRONMENTAL REQUIREMENTS
The recommended operating temperature, humidity and altitude values are listed in the technical specifications table (see chapter 10). Cooling systems may be required to maintain these values.
Avoid dusty environments or areas where there is dust from conductive or corrosive materials (e.g. metal dust or chemical solutions).
• The UPS is not designed for outdoor use.
• Do not expose the UPS to direct sunlight or sources of excessive heat.
• A space of at least 40 cm must be left at the back for adequate ventilation (see figure 2.2-1).
• The UPS switches are accessed from the front; however, a space of at least 1.5 metres should be left at the front of the UPS for maintenance purposes. It is also advisable to ensure that the cable connections are sufficiently long and flexible so that the unit can be extracted during maintenance (see figure 2.2-2).
• If it is not possible to leave sufficient space at the front, adequate access must be ensured from both sides.
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS
40 cm1,5 m
UPS
40 cm1,5 m
20 cm20 cm
2.2-1 2.2-2
7
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
ENGLISH
2. UNPACKING AND INSTALLATION OF THE UNIT
2.3. ELECTRICAL REQUIREMENTS
The installation and system must comply with national plant regulations. The electrical distribution panel must have a protection and sectioning system installed for the input mains and the auxiliary mains.
If a differential switch is installed on the mains power switch (optional), it must be inserted upstream from the distribution panel. The table below shows the size of the input protection devices recommended for correct installation.
Size of the input protection devices
UPS
Magneto-thermal
input
(1)
Magneto-thermal
Aux Mains
(1)
Di erential
input
(5)
Input/Output cable
core size
Battery cable
core size
Battery
protection
(4)
(kVA) (A) (A) (A) (mm2) (mm2) (A)
single parallel
(2)
single parallel
(2)
selective type
(5)
Min Max
(3)
Min Max
(3)
60 3/3 125 160 125 160 0.5 35 50 50 95 200 aR 80 3/3 160 200 160 200 0.5 50 50 70 95 200 aR
1. Magneto-thermal switch recommended: four poles with intervention threshold ≥10 In (curve C). It is necessary to use a D curve selective breaker if an optional external transformer is used.
2. In systems with two or more UPSs operating in a redundant or power parallel confi guration.
3. Determined by the size of the terminals.
4. Protection on the external battery cabinet (preferably 2 bipolar protection devices or one quadripolar).
5. Caution! Use selective type di erentials. Load leakage currents are added to those generated by the UPS and during transitory phases (power failure and power return) short current peaks may occur. If loads with high leakage current are present, adjust the di erential protec­tion. It is advisable in all cases to carry out a preliminary check on the earth current leakage with the UPS installed and operational with the defi nitive load, so as to prevent the sudden activation of the above switches.
6. Use 2500 aR for a battery cabinet with capacity exceeding 90 A.
This unit has been designed for connection to an ordinary AC power supply, i.e. with transient voltage in overvol­tage II category. Should it be necessary to connect the UPS to a higher overvoltage category (e.g. at the beginning of the installation, or to primary distribution circuits), or should the UPS risk being exposed to higher transient overvoltages, adequate external protection devices must be installed.
GENSET must support load variations from 0 to 100%.
In the event of three-phase distorting loads connected in output, the current on the neutral conductor may have a value that is 1.5 - 2 times the phase value (also for the input bypass). In this case, size the neutral cables and the input/output protection adequately.
WARNING! This is a product for commercial and industrial application in an industrial environment - installation restrictions or additional measures may be needed to prevent interference.
IMPORTANT! Protective earthing conductor (PE) must have sufficient current-carrying capacity. The PE cable core size must be chosen according to the PROTECTIVE CURRENT RATING of the earth circuit which depends on the provision and location of protective overcurrent devices.
8
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
2. UNPACKING AND INSTALLATION OF THE UNIT
2.3.1. Backfeed protection
If the UPS does not have an automatic protection device against current backfeed, the operator/installer must add a warning label to all the mains power disconnecting switches installed at a distance from the UPS area. This serves to remind technicians of the fact that the circuit is connected to a UPS (see the SAFETY section in paragraph 1 of this manual and paragraph 4.7.3 of the EN62040-1 2009-05 standard).
The label is supplied with the system. The backfeed protection device may be built into the system (only on specific request), or an electromechanical switch may be
installed externally in the input of the UPS.
• If the UPS incorporates this protection, proceed with the connections as described in paragraph 2.5 of this manual.
• To install the external backfeed protection it is necessary to use the BKF card and an external electromechanical switch that should be installed as close as possible to the UPS. For further information on the connection and the type of remote switch, please read paragraph 9.7 of this manual.
WARNING The neutral is not disconnected as, even in the event of a single fault on the UPS, it never has high potential when the mains and/or auxiliary power supplies are disconnected upstream. This is to prevent transformation of the power source to the UPS every time there is a power failure. Should the neutral potential be very high due to certain error conditions or due to installations downstream (e.g. ground fault not detected and protected, high dispersion of a phase, or the IT system), it will be necessary to install either devices that disconnect the Neutral or alternatively a system that detects, signals and protects against high neutral/ground potential that could lead to UPS failure.
NOTE For equipment with separate Emergency Mains, it must be possible to make the neutral of the Emergency Mains line electrically common with the neutral of the main input feed line.
2.4. INSTALLATION PROCEDURES AND INSTRUCTIONS
The procedure below should be followed closely for correct installation:
2.4-1 Set switches Q2/Q4, Q3, Q5 to position 0, open the switches of any external battery cabinets.
Switch off the UPS, remove the power, open the switches of any external battery cabinets, isolate the system and wait for 5 minutes before working on the terminal board or any internal UPS parts.
2.4-2 Open the terminal board protection panel at the back of the UPS by removing the four fastening screws A.
The terminal board shown is the most complete version including all options. On basic models or models with inter­nal batteries the terminal board has fewer terminals. Refer to the names of each terminal to identify it during connection. After connection secure the cables with bands C (figure 2.4-3) to couplings B as shown in the figure 2.4-6.
2.4-3 Connect the ground lead to the terminal with the corresponding symbol. Connect the input cables to the terminals labelled
MAINS SUPPLY L1, L2, L3, N (observing the phase cycle direction).
2.4-1
Q2 Q4
Q5
Q3
2.4-2
A
2.4-3
OUTPUT
L12
L22
L32
N2
EXTE
R
+B2
AUX MAINS SUPPLY
L11
L21
L31
N1
MAINS SUPPLY
L1
L2
L3
N
8 cm max
C
9
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
2. UNPACKING AND INSTALLATION OF THE UNIT
2.4-5 Connect the cables of the separate auxiliary power supply (if present) to the terminals labelled AUX MAINS SUPPLY L11, L21, L31, N1 (observing the phase cycle direction).
2.4-6 Connect the output cables to the terminals labelled OUTPUT L12, L22, L32, N2.
2.4-7 Connect the external battery cables (if present) to the terminals labelled EXTERNAL BATTERY +B2, -B2, -B1, +B1 (refer
to paragraph 2.9).
2.4-8 Guide any control cables from the front (RS232, signalling relay contacts, etc.) into the appropriate side cable run A.
2.4-4
2.4-7
2.4-5
2.4-8
2.4-6
B
N2
EXTERNAL BATTERY
+B2
–B2
–B1
+B1
AUX MAINS SUPPLY
L11
L21
L31
N1
MAINS SUPPLY
L1L2L3
N
OUTPUT
L12
L22
L32
N2
AU
X
L11
MAINS SUPPLY
L1
L2
L3
N
EXTERNAL BATTERY
+B2
–B2
–B1
+B1
AUX MAINS SUPPLY
L11
L21
L31
N1
LY
N
A
10
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
2. UNPACKING AND INSTALLATION OF THE UNIT
2.4-9 Remove the pre-cut element C and curved elements B to feed the cables through.
Secure the cables to the couplings D located on the rack as shown in picture 2.4-10, ensuring the air vents are not obstructed in any way.
2.4-11 Once cabling has been completed secure the terminal board cover with the four screws A.
Once cabling has been carried out secure the UPS with the fixing feet E as shown in figure 2.4-12.
2.4-13 If the system is installed on a raised floor (such as in a data processing room):
- leave a space of at least 20 cm between the power and the control cables;
- avoid parallel channelling over long distances; choose cables crossing at 90° instead.
2.4-9
2.4-12
2.4-10
2.4-13
2.4-11
E
E
A. power cables B. control cables
20 cm
90°
A A
B
B
D
A
C
B
2.5. GENERATOR CONNECTION
If your system uses a generator, connect the ‘generator set ready’ no-potential contact to connector IN 2 on the optional ADC PCB configured in standard or power safe mode (see paragraph 7.2). This automatically extends the voltage and frequency value range when power is supplied by the generator set.
2.6. EXTERNAL ESD CONNECTION
A remote emergency shutdown system (ESD) can be installed by means of the optional ADC PCB; see paragraph 7.2. Connect a normally closed zero-potential contact to terminals IN1+ and IN1- of the ADC PCB.
11
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
ENGLISH
2. UNPACKING AND INSTALLATION OF THE UNIT
2.7. UPS PARALLEL CONFIGURATION
2.7.1. General
Parallel connection enhances UPS system reliability, performance and power. All MASTERYS BC models can be installed in parallel configuration provided they have the special parallel kit that can be installed
in the factory or later by specialist personnel. UPS modules for parallel operation are identical to standard UPS modules, as a result safety, shipping and installation recommen-
dations in chapters 1 and 2 also apply.
2.7.2. Installation
UPS units operating in parallel are interconnected using control cables B (fig. 2.7.3-1) and are configured differently depending on the position they are assigned.
For this reason the units have a position label C (Fig. 2.8-1):
• The LEFT label means that the unit must be positioned to the left.
• The RIGHT label means that the unit must be positioned to the right.
The control cables supplied allow a maximum distance of about 3 metres between the UPS units. This gives enough room for an external battery cabinet to be inserted beside each UPS.
2.7.3. Power connections
• The power supply to each unit must be protected as indicated in the table in paragraph 2.3.
• The cross section and length of the input and output cables must be identical for all the units.
• The phase rotation must be the same for each unit connected in parallel and also on any external manual bypass line.
• Cables of the same length and cross section must be used for the connection between the general power switch A, the switches
C and the respective UPS units. The length of the cables from A to each UPS module must not exceed 25 metres (Fig. 2.7.3-1).
• The cables from the UPS module to switch F must be of the same length (max. 7.5 metres) with multi-core cables.
• If a differential switch is installed on the mains power switch (optional), it must be inserted upstream from the distribution panel
(see fig. 2.7.3-1, detail H), it must be a selective type and the trigger value must be 0.5 A multiplied by the number of UPSs connected in parallel.
Only activate switch D after carrying out the procedure for switching onto the maintenance bypass.
Only activate switch E after turning off the UPS.
12
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
2. UNPACKING AND INSTALLATION OF THE UNIT
25 m max
7.5 m max
H
A
C C
B
L
R
E
E
F
G
2.7.3-1
Recommended parallel confi guration
Key A System input switch B Parallel bus cable C
Single UPS magneto-thermal switch (if a separate auxiliary power source is used, add a magneto-thermal switch for each UPS)
D Ext. bypass magneto-thermal switch
E
(1)
Output switch (connect signal status to
the parallel board)
F
(1)
System shutdown switch
G Distribution H
Main di erential magneto-thermal switch
Max 2 units in parallel
(1). To avoid unwanted tripping, do not use the magneto-thermal switch.
13
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
2.8-1
2. UNPACKING AND INSTALLATION OF THE UNIT
2.8. CONTROL CONNECTIONS
In order for units connected in a parallel confi guration to operate correctly, control cables are required to exchange data between the various UPS units making up the parallel system, for management of correct load sharing and synchronisation logic. The cables in question are supplied with the UPS in the case of standard parallel setups or are attached to the parallel kit in the case of a later system upgrade. Parallel confi guration must only be activated by SOCOMEC qualifi ed personnel; in each case arrange the control cables in the relevant cable run as shown in fi gure 2.8-1, leaving the connector(s) unconnected (in the central UPS one incoming and one outgoing control cable must be used).
A
B
C
Key A Control cable run B Parallel bus cable; leave approx. 20cm cable length at the exit of the cable run C Label for unit positioning
14
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
2. UNPACKING AND INSTALLATION OF THE UNIT
2.9. EXTERNAL BATTERY CABINET CONNECTION
Position the battery cabinet next to the UPS.
Before carrying out any operations ensure that:
• the battery fuses located inside the battery cabinet are open;
• the UPS is not live;
• all mains or battery switches are open;
• the switches upstream of the UPS are open.
• Remove the terminal board protection.
• Connect the ground cable (figure 2.9-1).
• Connect the cables between the UPS terminals and the battery cabinet terminals, strictly observing the polarity of each individual string (figure 2.9-1) and the cross-sections indicated in table 2.3.
Use double insulated cables or the cables supplied with the unit to connect the UPS to the battery cabinet.
Cabling errors with inversion of battery polarity may cause permanent damage to the equipment.
• Replace the terminal board protection.
If using cabinets not supplied by the UPS manufacturers, it is the installer’s responsibility to check electrical compa­tibility and the presence of appropriate protection devices between the UPS and the battery cabinet (fuses and switches of sufficient capacity to protect the cables from the UPS to the battery cabinet). As soon as the UPS is switched on (before closing the battery switches) the battery parameters must be verified accordingly (voltage, capa­city, number of elements, etc.) on the mimic panel menu. If the values indicated on the battery cabinet data plate are different from those shown on the mimic panel use the SERVICE > CONFIGURATIONS menu to correct the settings.
UPS
BATTERY CABINET
2.9-1
OUTPUT
L12
N2
EXTERNAL BATTERY
+B2
B2
B1
+B1
EXTERNAL BATTERY
+B2
B2
B1
+B1
L11A = L11 N1A = N1
AUX MAINS
SUPPLY
L11A
N1A
L11
N1
MAINS SUPPLY
L1
L2
L3
N
15
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
ENGLISH
3. MODES OF OPERATION
3.1. ON LINE OPERATION
A special feature of the MASTERYS BC series is the ON LINE double conversion feature in conjunction with low distortion mains power absorption. With ON LINE mode the UPS is able to supply a voltage that is fully stabilised in frequency and amplitude, regardless of any interference in the mains power supply within the most stringent classification of UPS regulations.
ON LINE operation provides three operating modes according to mains and load conditions:
• Normal mode
This is the most frequent operating condition: the energy is drawn from the primary mains power supply and is converted and used by the inverter to generate the output voltage to power the loads connected.
The inverter is constantly synchronised in frequency with the auxiliary mains to enable load transfer (due to an overload or inverter shutdown) without any break in the power supply to the load.
The battery charger supplies the energy required to maintain or recharge the battery.
• Bypass mode
In the event of inverter failure the load is automatically transferred onto the auxiliary mains without any interruption in the power supply. This procedure may occur in the following situations:
- in the event of a temporary overload the inverter continues to power the load. If the condition persists the UPS output is switched on to the auxiliary mains via the automatic bypass. Normal operation, which is from the inverter, returns automatically a few seconds after the overload disappears.
- when the voltage generated by the inverter goes outside the limits due to a major overload or fault on the inverter.
- when the internal temperature exceeds the maximum value allowed.
• Battery mode
In the event of a mains failure (micro interruptions or extended power cuts), the UPS continues to power the load using the energy stored in the battery. The Expert Battery System keeps the user constantly informed on battery status and back-up time available.
3.2. OPERATION IN HIGH EFFICIENCY MODE
The UPS allows the selection of a programmable ‘economy’ operating mode that can increase overall efficiency by up to 98% for energy saving purposes. With this mode of operation, specific daily or weekly time intervals can be selected and programmed to power the applications directly from the auxiliary mains. If the power supply fails the UPS will automatically switch onto the inverter and continue to supply power to the load by drawing energy from the battery.
This mode does not provide perfect stability in frequency and voltage like the ON LINE mode. Thus the use of this mode should be carefully evaluated according to the level of protection required by the application.
The Eco Mode operation provides very high efficiency, since the application is powered directly from the auxiliary mains via the automatic bypass in normal operating conditions.
3.3. OPERATION WITH MANUAL MAINTENANCE BYPASS
If the maintenance bypass is activated using the appropriate procedure the load is powered directly from the maintenance bypass, while the UPS is separated from the power supply and can be switched off.
This operating mode can be selected for maintenance to be carried out on the system so that the necessary actions can be perfor­med by service personnel without having to disconnect the power supply to the load.
16
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
3. MODES OF OPERATION
3.4. OPERATION WITH EXTERNAL MANUAL BYPASS (optional)
The external maintenance bypass may be placed on the general distribution panel when the UPS is installed, or by installing the bypass panel that is supplied on request.
If the UPS has an input for the auxiliary power supply the Q2 switch must be connected to this input and the main power supply input must be disconnected on the control panel.
If the maintenance bypass is activated with the appropriate procedure the load is powered directly from the maintenance bypass, while the UPS is separated from the power supply and can be switched off.
This operating mode can be selected for maintenance to be carried out on the system so that the necessary actions can be perfor­med by service personnel without having to disconnect the power supply to the load.
3.4-1
3-phase input/3-phase output for UPS 3/3
3.4-2
3-phase input/1-phase output for UPS 3/1
Key Q1 Bypass switch Q2 Mains power switch Q3 Output switch
Bypass panel connection diagram
Mains
L3
L2
L1
L3
L2
L1
L1
N
N
Load
IN
UPS
N
L1 L2 L2 L3 L3
N
OUT
Q1
Q2
Q3
Mains
L3
L2
L1
L3
L2
L1
Lo
N
N
Load
IN
UPS
N
Lo
N
OUT
Q1
Q2
Q3
17
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
4.1-1
4. ACCESS TO CONTROLS
4.1. IDENTIFYING SWITCHES AND INTERFACES
Key C1 Serial connector RS232/485 S Mimic panel S1 Options slot 1 S2 Options slot 2 Q2 Input switch Q3 Output inverter switch Q4 Auxiliary mains Input switch Q5 Output maintenance bypass switch
Q3
S2
S1
S
C1
Q5
Q2/Q4
MAINS OUT
B
Confi guration with common mains
OUT
B
MAINS
AUX
MAINS
Confi guration with separate mains
Q2 Q3
Q5
Q3
Q5
Q2/Q4
18
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
4.2. SWITCH FUNCTIONS FOR THE 60-80 kVA RANGE
With common mains input:
• Input switch Q2:
- The input switch provides the primary power supply to the UPS.
- In normal operating conditions this should be in position 1 ON.
- The position 0 OFF will cause the batteries to discharge.
With separate mains inputs:
• Input switch Q4:
- The switch provides the power supply to the automatic bypass line.
- In normal operating conditions this should be in position 1 ON.
WARNING! in this configuration the mains power supply to the rectifier cannot be isolated inside the UPS, only via external protection devices.
• Output switches Q3 and Q5:
- These are used to manage UPS output. Q3 connects the UPS output to the inverter (continuous power supply). Q5 connects the output directly to the auxiliary mains input (manual bypass).
- Positions Q3 closed (1) and Q5 open (0): this is the position for normal operation of the UPS for a continuous power supply to the load.
- Position MANUAL BYPASS Q3 open (0) and Q5 closed (1): this position should only be selected for standard or special main­tenance operations (manual bypass); the load is connected directly to the auxiliary mains. It may be used in the event of a UPS failure to power applications from the auxiliary mains while awaiting the intervention of technical personnel. Refer to the relevant procedure described below on how to activate the bypass; see chapter 6.
- Positions OFF Q3 open (0) and Q5 closed (0): this completely isolates the UPS output by removing the voltage from the appli­cations in any operating conditions. It is used for the emergency shutdown of the system (internal ESD).
3. ACESS TO CONTROLS
19
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
5. MIMIC PANEL
5.1. BASIC MIMIC PANEL
The LCD mimic panel (figure 5.1-1) located on the upper part of the UPS provides all the information on operating status, electrical measurements, access to controls and configuration parameters.
The information is grouped into four sections:
A. LEDs that identify the subsets and the energy flow; B. Multicoloured light bar that identifies the condition of the power supply to the load; C. Alphanumeric information that uses a menu layout to provide details on any alarms that may occur and on the measurements,
controls and parameters.
D. Use of the buttons:
· ESC: exits from the current menu/parameter/action;
·
: scrolls the available menus/values upwards. It increases the value each time it is pressed when changing a parameter;
· : scrolls the available menus/values downwards. It decreases the value each time it is pressed when changing a parameter;
· ENTER: enters the menu displayed on the screen to confirm the choice/changes made.
5.1-1
A
B
C
D
20
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
Meaning of LEDs
LED L1 L2 L3 L4 L5 L6 L7
COLOUR GREEN YELLOW GREEN GREEN YELLOW GREEN RED
ON
Rectifi er and Battery char­ger on
Operation from battery­battery test
Inverter on Auxiliary input
mains present and Ok
Output on automatic bypass mode
Output pow­ered
Activation code alarm­Maintenance
FLASHING
Rectifi er alarm
Battery sec­tion alarm
Inverter failure or fault
Auxiliary input mains out of tolerance
General bypass alarm
Bypass gen­eral alarm Inverter failure or fault
General alarm
OFF
No input mains present
Battery charged
Inverter o or power supply from auto­matic bypass
Auxiliary input mains not present
Power supply from inverter
Load not powered
No alarms
5.1.1. Meaning of LEDs
5.1.1-1
L2L1 L3
L4 L5
L6
L7
5.1.2. Meaning of light bar status
The light bar B (figure 5.1-1) provides immediate indication of the condition of the power supply to the load:
• Red: power supply not present or shutdown imminent.
• Yellow: power supply present but unstable or temporary.
• Green: power supply stable and regular.
5. MIMIC PANEL
Meaning of light bar status
Colour Condition displayed
RED fl ashing Imminent shutdown alarm (the load will be disconnected in a few minutes) RED Load not powered or battery circuit open YELLOW fl ashing Alarm requesting standard maintenance after over 25,000-30,000 hours of operation according to
conditions of use (type of load, temperature), (L7 fl ashing and alarm A44) UPS on standby YELLOW Load on battery or battery discharging if LED 2 is on continuously YELLOW On automatic bypass if LED 5 is on continuously YELLOW End of fi rst maintenance period (10,000 hours) UPS in maintenance mode GREEN fl ashing Battery Test in progress GREEN Load powered by the inverter or in high e ciency mode
21
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
5. MIMIC PANEL
5.1.3. Display menu
This paragraph describes the menus available on the mimic panel and their functions. The displays are organised into menus and submenus as shown in the diagram:
• to access a menu press the ENTER key.
• To return to the higher level press ESC key.
• Use the and keys to scroll the information available at a particular level.
FIRST LEVEL SECOND LEVEL THIRD LEVEL
MAIN ALARMS
MEASUREMENTS COMMANDS IMMEDIATE COMMANDS
EXTENDED COMMANDS PARAMETERS UPS CURRENT DATA SERVICE UPS SETTING
CIM ALARMS CODE
WARRANTY CODE
22
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
5. MIMIC PANEL
5.1.4. Alarms menu
This menu displays all alarms that are active at the time of access. The alarms menu is activated automatically when an alarm condition occurs.
ALARMS menu
Code Mimic panel message Description
A00 GENERAL ALARM At least one alarm is present A01 BATTERY ALARM Battery circuit failure or faulty operation A02 OUT OVERLOAD Power required in output over the limits A06 VAUX OUT OF TOL
The voltage or frequency limits accepted by the bypass have been exceeded A07 OVER TEMPERATURE Temperature excessive or ventilation problems A08 MAINTEN. BYPASS Active bypass procedure A17 IMPROPER USE Improper conditions of use verifi ed (load, mains, temperature) A18 OVERLOAD OFF INV Inverter shutdown due to overload A20 WRONG CONFIG.
Error in the confi guration parameters (e.g. di erent between several UPS units in parallel) A22 MAINS OUT OF TOL
The voltage or frequency limits accepted by the rectifi er have been exceeded A23 RECTIFIER ALARM Rectifi er fault A25 INVERTER ALARM Inverter fault A26 BATT CHARGER ALM Battery charger fault A29 BYPASS ALARM Bypass fault A30 OVERLOAD STOP The duration of the overload has inhibited the bypass A38 EXTERNAL ALARM1 Signalling from ADC input A39 EXTERNAL ALARM2 Signalling from ADC input A40 EXTERNAL ALARM3 Signalling from ADC input A41 EXTERNAL ALARM4 Signalling from ADC input
A42 REMOTE SERVICE ALARM
This alarm indicates that a critical anomaly has occurred on the UPS.
Where a maintenance contract with the Remote Monitoring option is in
place, the procedure for analysing the UPS via remote connection will be
automatically activated by your service centre provider.
A43 REDOUNDANCY LOST
The power required by the load no longer allows the preset redundancy
N+x (signalling for UPS units in parallel) to be maintained A44 SERVICE CHECK Notifi cation that the routine service check is overdue A49 BATT. DISCHARGED The energy available in the battery has been depleted A51 OPT. BOARD ALM Fault in the optional cards in the slots A58 ESD ACTIVATED The remote emergency shutdown command has been activated A59 BATT.CIRC. OPEN The battery switch is open A60 FAN FAILURE Fans faulty or blocked A61 PHASE ROT. FAULT Wrong phase cycle direction
23
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
5. MIMIC PANEL
5.1.5. Measurements menu
This menu is used to display all measurements relating to UPS input, output, and the battery. For models with single phase input or output, the voltage and current displays are adjusted automatically.
MEASUREMENTS menu
Type of measurements Value Value Value Note
OUTPUT VOLTAGE ___ V ___ V ___ V Output voltage OUTPUT LOAD __ % __ % __ % Output load percentage OUT ACTIVE PWR __._ kW Output active power OUTPUT FREQNCY __._ Hz Output frequency AUX VOLTAGE ___ V ___ V ___ V Auxiliary mains voltage AUX FREQUENCY __._ Hz Auxiliary mains frequency INPUT VOLTAGE ___ V ___ V ___ V Input mains voltage INPUT FREQUENCY __._ Hz Input mains frequency BATTERY VOLTAGE B+___ V B+___ V Battery voltage CAPACITY __ % Battery capacity percentage during charging BACKUP INFO T___MIN Backup time during battery discharge INTERNAL TEMP. __ °C Internal temperature
5.1.6. Commands menu
This is used to send immediate commands for start-up/shutdown/reset alarms to the UPS and to select the operating mode. Commands can also be sent for diagnostic purposes by means of the extended commands menu (if enabled in the configurations menu). The command is activated by selecting it with the and keys, press ENTER, confirm YES or NO, then press ENTER.
IMMEDIATE COMMANDS menu
Command Description
START PROCEDURE UPS start-up command STOP PROCEDURE UPS shutdown command HIGH EFF. MODE High e ciency mode: activates the energy saving feature NORMAL MODE Activates normal double conversion operation ALARMS RESET Resets all the alarms LEDS TEST Performs test on mimic panel LEDs
EXTENDED COMMANDS menu
Command Description
BATTERY TEST Activates the battery test to check battery e ciency BATT.COMMISSION Activates forming charging for the battery CHECK-UP DISAB. Disables the regular maintenance message
5.1.7. Parameters menu
Displays the UPS parameters set.
UPS CURRENT DATA menu
Message Description
MASTERYS 3/3 30 KVA SN. 0000000000
Displays the size, input and output phase confi guration and UPS serial number
UC FW. REVISION RV 000 CKS: 0000
Identifi es the microprocessor software release
DSP FW. REVISION RV 000 CKS: 0000
Identifi es DSP software release
24
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
5. MIMIC PANEL
5.1.8. Service menu
This is used to change the configuration parameters, insert the warranty activation code and display the service code.
5.1.9. UPS SETTINGS menu
This is used to change the configuration parameters. Access is via the password MAST which is keyed in by using the and
keys and ENTER to go on to the next letter.
UPS SETTINGS menu
Parameter Description Allowed values
SET LANGUAGE Sets the required language English, Français, Italiano,
Deutsch, Español SET OUTPUT VOLTAGE Sets the required output voltage value 208/220/230/240 V SET OUTPUT FREQUENCY Sets the required output frequency value 50/60 Hz SET MODE CONVERTER Sets whether or not the UPS has to operate as a
frequency converter
WARNING! Set only on UPS with mains power (MAINS) and auxiliary mains (AUX MAINS) sepa­rated and with the auxiliary mains (AUX MAINS) disconnected! Do not set on UPS with common mains lines as it could damage the load!
YES/NO
SET MODE AUTORESTART Sets whether or not the UPS has to restart automatically
after shutdown due to minimum battery
YES/NO
SET BATTERY AVAILABLE Set if battery is present YES/NO if YES:
- SET BATTERY TYPE Selects the type of batteries used Sealed
- SET BATTERY CAPACITY Sets the battery capacity in Ah 9.5 – 1000 Ah
- SET CHARGER TYPE Selects the type of recharge required Auto, Float, int.
- SET BATTERY ELEMENTS Set the number of battery elements 120-132
- SET BATT_TEST PERIOD Sets the frequency rate of the battery test in days 0, 30, 60, 90, 120,150,180 (zero
do not perform the test) in days SET BACKFEED Sets the type of backfeed protection Disable,
2.ByPass-Input alone,
3.ByPass-Input common
SERIAL LINK Inserts the serial communication parameters:
- Serial Link Baud Rate
- Serial Link Parity
- Serial Link Bit Number
- Serial Link Stop Bits When the data is confi rmed, the serial connection automatically
changes the confi guration without having to switch o the UPS.
1200/2400/4800/9600/14.4
odd/even/none
8-9
0-1
JBUS SETTING SLAVE NR. Sets the mimic panel jbus node
When the data is confi rmed, the serial connection au­tomatically changes the confi guration without having to switch o the UPS.
1/32
DATE SETUP Sets the date DD/MM/YY TIME SETUP Sets the time HH:MM SYN EXT CMDS ENABLED Enables/Disables the mimic panel extended commands YES/NO REMOTE CMDS ENABLED
Enables the transmission of commands from external systems
YES/NO SET BUZZER ENABLED Enables/Disables the buzzer YES/NO
25
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
5. MIMIC PANEL
CIM Alarms Code menu
This displays the service code to be sent to the support service to make an accurate and rapid diagnosis of the possible failure. In the event of a fault, select the menu SERVICE > CIM ALARMS CODE and inform the support centre of the code displayed.
ALARMS CODE 1/2
1) 0000 2) 0000
ALARMS CODE 2/2
3) 0000 4) 0000
Warranty Code menu
During equipment commissioning, a warranty activation code, comprising four characters, is required to complete the start-up procedure.
5.3 WARRANTY CODE
COMMISSIONING
The activation code is provided directly by the reference Support Centre upon communication of the equipment serial number which is displayed in the next message by pressing ENTER.
WARRANTY CODE
SN: 0000000000
Inserting the code does not limit the availability of equipment functionality. When the Support Centre is contacted for the activation code, detailed information can be obtained on the UPS functions available
and regular routine maintenance programmes. Once the code is obtained, enter it by pressing ENTER to activate the entry (two asterisks will appear). Select the first character
with the
and keys and confirm with ENTER to accept the character. Then move on to the next character. Pressing the
ENTER key after selecting the fourth character activates the code.
WARRANTY CODE
CODE - - - -
An error message is displayed if the code is incorrect. Check that the code displayed corresponds to the code provided by the Support Centre and repeat the procedure.
26
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
6. OPERATING PROCEDURES
This chapter defines the operating procedures to be followed to activate and manage the UPS.
For UPSs in parallel: Carry out the procedures on all the UPSs before going on to the next operation. Each procedure should be carried out on all the UPSs within 30 seconds. The mimic panel operations are carried out on the concentrator.
6.1.1. Start-up in normal mode
• Set the external battery switches to position 1 (battery circuit closed).
• Apply voltage to the UPS.
• Set switch Q4/Q2 to position 1.
• Wait for the mimic panel to start up.
• Activate the start procedure from the commands menu on the mimic panel.
• Set switch Q3 to position 1 (inverter in output ON).
• The load is now powered by the UPS.
6.1.2. Shutdown
Shutdown interrupts the power supply to the load and stops the UPS and the battery charger.
• Activate the stop procedure from the commands menu on the mimic panel, wait approx. 2 minutes for shutdown (the controlled shutdown of any servers is managed via shutdown software).
• Set switch Q3 to position 0 (inverter in output OFF).
• Set the battery switches to position 0 (battery circuit open).
• Set switch Q4/Q2 to position 0 (input mains OFF).
6.1.3. Extended out of service
In the event of an extended period of UPS inactivity the batteries must be recharged regularly. Recharging should be carried out every three months.
• Put the external battery switches to position 1 (battery circuit closed).
• Apply voltage to the UPS.
• Set switch Q4/Q2 to position 1 (input mains ON).
• Set or keep switches Q3 and Q5 to position 0 (inverter in output OFF and bypass OFF).
• The battery must be charged for at least ten hours.
• After ten hours:
• Set the battery switches to position 0 (battery circuit open).
• Set switch Q4/Q2 to position 0 (input mains OFF).
• The UPS can be switched off.
6.1-1
Q5
Q3
Q2/Q4
27
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
6. OPERATING PROCEDURES
6.1.4. Switching onto manual bypass
Switching onto the manual bypass creates a direct connection between the UPS input and output, completely excluding the equipment control element.
This operation is performed in the event of standard maintenance on the equipment, so as not to remove the power supply from the load, or in the event of a serious failure while waiting for the equipment to be repaired.
• From the mimic panel set the HIGH EFFICIENCY MODE command from the COMMANDS > IMMEDIATE COMMANDS menu.
• Wait for the command to be executed (bypass line on the M1 display on). If this does not take place, suspend the operation (the auxiliary mains is not suitable for the load).
• Set switch Q5 to position 1 (bypass on load) and then put switch Q3 to position 0 (inverter in output OFF).
• Set the battery switches to position 0 (battery circuit open).
• Open the switch Q4/Q2.
• In the event of a separate input mains disconnect the UPS primary input mains.
If there is an external manual bypass, carry out the procedure described above before activating this switch.
6.1.5. Return to normal mode
• Set switch Q4/Q2 to position 1 (input mains ON).
• Set the external battery switches to position 1 (battery circuit closed).
• Activate the start procedure from the commands menu on the mimic panel.
• From the mimic panel set the HIGH EFFICIENCY MODE command from the COMMANDS > IMMEDIATE COMMANDS menu.
• Set switch Q3 to position 1 (inverter in output ON).
• Check that alarm A06 is not present (if the alarm is present resolve the problem before continuing).
• Set switch Q5 to position 0.
If there is an external manual bypass, put the switch to position OFF.
• From the mimic panel set the NORMAL OPERATION command from the COMMANDS > IMMEDIATE COMMANDS menu.
6.1.6. Emergency shutdown
Should it be necessary to interrupt the continuous power supply provided by the UPS quickly (emergency shutdown), this can be done by putting switch Q3 to position 0 or, where applicable, by activating the emergency button/switch connected to the ADC
PCB.
The UPS output can only be electrically disconnected by means of Q3. If the UPS is operating from the manual bypass (Q5 in position 1) with mains present, the emergency shutdown does not interrupt the power supply to the load. In emergency conditions all the power supplies upstream of the UPS must be disconnected.
28
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
7. CONNECTIVITY AND COMMUNICATION OPTIONS
As each channel is independent, simultaneous connections can be made to satisfy the different levels of signalling and remote monitoring.
See the options paragraph to access the detailed functions of the cards installed in the slots.
Key for pin RS232/485 C1
1 Not connected 2 RX for RS232 3 TX for RS232 4 Data + 5 GND for RS232
6 Data − 7 Reserved 8 Not connected 9 +12 V
7.1-1
7.1-2
Key C1 Serial connector RS232/485 S1 Options slot 1 S2 Options slot 2
S2
S1
C1
34521
8976
7.1. MULTI-LEVEL COMMUNICATION
MASTERYS BC can manage a variety of serial, contact and Ethernet communication channels simultaneously. The various cards and signalling accessories are inserted in the two standard communication slots. This gives MASTERYS BC
immediate interfacing and integration flexibility as soon as the unit is installed with no need for trained personnel.
29
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
7. CONNECTIVITY AND COMMUNICATION OPTIONS
ENVIRONMENTAL confi guration DIP1: ON - DIP2: ON
IN/OUT Description Filter level
OUT 1 General Alarm 2 OUT 2 Overheating 2 OUT 3 Overload / Loss of redundancy 2 OUT 4 External alarm In2 2
IN 1
(1)
ESD 1
IN 2 External alarm A39 2
IN 3
(2)
External alarm A40 2
POWER SAFE confi guration DIP1: ON - DIP2: OFF
IN/OUT Description Filter level
OUT 1 General Alarm 2 OUT 2 Power safe plug 1 2 OUT 3 Power safe plug 2 2 OUT 4 Power safe plug 3 2
IN 1
(1)
ESD 1
IN 2 Supply from GenSet 1
IN 3
(2)
Management of energy consuption
1
STANDARD confi guration (default) DIP1: OFF - DIP2: OFF
IN/OUT Description Filter level
OUT 1 General alarm 2 OUT 2 Battery discharging 3 OUT 3 Battery low or imminent stop 2 OUT 4 UPS on bypass 2
IN 1
(1)
ESD 1
IN 2 Supply from GenSet 1
IN 3
(2)
Insulation controller 2
(1) If the external ESD button is not used always insert a jumper to short circuit input IN 1.
(2) The IN3 input on the ADC card with temperature sensor is for the external battery temperature sensor.
The fi lter level indicates the activation delay: 1 immediate activation (1 second minimum communication time), 2 10 s delay, 3 30 s delay.
SAFETY confi guration DIP1: OFF - DIP2: ON
IN/OUT Description Filter level
OUT 1 General Alarm 2 OUT 2 ESD activation 1 OUT 3 Battery low or imminent stop 2 OUT 4 ESD activation 1
IN 1
(1)
ESD 1
IN 2 External alarm A39 2
IN 3
(2)
External alarm A40 2
7.2. ADC CARD
To be installed in one of the two slots available, these cards can be used to manage up to four normally closed or normally open outputs, and up to three digital inputs in confi gurable mode. If more than one ADC card is used simultaneously, the dip switch confi gurations must be di erent. Secure the card with the appropriate screws.
This card can be confi gured to control up to four outputs that can be set as normally closed or normally open and up to three digital in­puts. The card is inserted in one of two slots provided. Up to four operating modes can be selected using the two DIP switches 1 or 2.
• Electrical data
- Permitted Nominal current and voltage of NO or NC contacts: 2 A 250 Vac depending on the terminal used.
- Inputs are activated on loop closing.
• Connection of the generator
If your system uses a generator connect the ‘generator set ready’ no-potential contact to connector IN 2 on the optional ADC card confi gured in standard or power safe mode. This automatically extends the voltage and frequency value range when power is supplied by the generator set.
• External ESD connection
A remote emergency shutdown system (ESD) can be installed by means of the optional ADC card. Connect a normally closed zero-potential contact to terminals IN1+ and IN1- of the ADC card.
OUT2
IN3
OUT3
OUT1
IN1
IN2
OUT4
DIP2
DIP1
30
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
7. CONNECTIVITY AND COMMUNICATION OPTIONS
Intervention of the ESD input switches off the UPS output. To restore the UPS to operation:
• Close the ESD contact on ‘In 1’ on the ADC board.
• Send the Alarms Reset command.
• Run the Automatic Start Procedure
7.3. REMOTE MIMIC PANEL
This device monitors and interacts with the UPS through a serial link RS 485 (maximum distance of 175 m) 25 m cable supplied as standard and 50 m cable available as an option.
7.4. NET VISION LAN/WEB INTERFACE
NET VISION is a communication and management interface to be installed in the UPS slot designed for business networks. The
UPS behaves exactly like a networked peripheral, it can be managed remotely and allows the shutdown of network workstations. NET VISION allows a direct interface between the UPS and LAN network avoiding dependence on the server and support SMTP,
SNMP, DMCP and many other protocols. It interacts via the Web browser.
Please note that two Net Vision cards cannot be connected simultaneously.
7.5. PROFIBUS INTERFACE
The externally mounted PROFIBUS adapter allows UPS models to be connected to a Profibus network.
7.6. SOFTWARE OPTIONS
A large number of SW solutions can be adopted on MASTERYS BC thanks to its advanced communication facilities. These solu­tions have been specially designed for the efficient management of power protection devices.
Visit www.socomec.com and click on DOWNLOAD then SOFTWARE to find the communication software which is suitable for your requirements.
Description of signals
Message on the mimic panel Description
General Alarm ‘General Alarm’ contact output
No alarm
C1
NO1
NC1
‘General Alarm’ active
C1
NO1
NC1
Battery Low or Imminent stop Battery low voltage and imminent shutdown contact output Supply from GenSet Generator ready signal input Power safe plug 1 Non privileged load 1 command output activated by overload or loss of redundancy Power safe plug 2 Non privileged load 1 command output activated by battery discharging Power safe plug 3 Non privileged load 1 command output activated by low battery Management of energy consumption Input for the battery to help providing energy in the event of peak consumption ESD activation Shutdown for ESD contact outpu Overheating Internal overheating contact output Overload/Loss of redundancy Overload / loss of redundancy contact output
31
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
ENGLISH
8. TROUBLESHOOTING
The alarm messages displayed enable immediate diagnosis. Alarms are divided into two categories:
• alarms related to the UPS external circuits, (input mains, output mains, temperature and environment).
• alarms related to the UPS internal circuits. In this case, corrective actions will be carried out by the After Sales Department.
8.1. SYSTEM ALARMS
• A02: OUT OVERLOAD
The power required by the loads is higher than the power available. Check that the load is well balanced on the three phases by checking the measurements on the display. If necessary disconnect
any loads that do not need uninterruptible power.
Important! The accepted overload time limit is defined in the technical specifications. When this time limit is exceeded the loads will no longer be powered by the inverter.
• A06: VAUX OUT OF TOL
The auxiliary mains supply exceeds the acceptable tolerance values. Possible causes are:
- No voltage or frequency present or voltage and frequency outside acceptable values (see the technical specifications).
- The frequency is subject to continuous variations (typical with power supplied from an incorrectly sized GE).
• A07: OVER TEMPERATURE
The technical plant temperature is higher than the maximum value recommended. Check the ventilation or air conditioning system in the UPS room.
• A08: MAINTEN. BYPASS
The output disconnecting switch Q3 is in position 2 (maintenance bypass). The load is therefore powered directly by mains power supply.
• A17: IMPROPER USE
This alarm does not indicate a malfunction or failure of the UPS, but an incorrect use/sizing of the system. It is activated in the event of:
- Operation for long periods at high temperatures (battery deterioration)
- High number of overloads (wrong sizing)
- Continuous battery discharging (mains not stable)
- High number of switches onto the bypass (high impulsive loads).
• A22: MAINS OUT OF TOL
The input mains is not present or not sufficient (voltage and/or frequency values incorrect with reference to the technical data); if there is no input mains outage check that no protection devices upstream of the UPS have tripped.
Check the voltage applied and frequency values are in compliance with the values set on the mimic panel.
• A38, A39, A40, A41: EXTERNAL ALARM 1, 2, 3, 4
One of the ADC card inputs has been activated; check the status of the devices connected to this card.
• A61: PHASE ROT. FAULT
The phase cycle sequence is incorrect. In this case invert two phases of the input mains. For a UPS with separate auxiliary mains exchange the two phases of the auxiliary mains only.
32
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
8. TROUBLESHOOTING
8.2. UPS ALARMS
• A01: BATTERY ALARM
Failure or problem on the battery circuit. Check the battery switch is closed.
• A18: OVERLOAD OFF INV
Reduce the load rate applied to the UPS and reset the alarms.
• A20: WRONG CONFIG.
Error in the configuration parameters; contact the support service.
• A30: OVERLOAD STOP
Reduce the load rate applied to the UPS and reset the alarms.
• A42:REMOTE SERVICE ALARM
This alarm indicates that a critical anomaly has occurred on the UPS. Where a maintenance contract with the Remote Monitoring option is in place, the procedure for analysing the UPS via remote connection will be automatically activated by your service centre provider.
• A44: SERVICE CHECK
The equipment has to undergo regular checks by the support service in order to ensure optimum performance and efficiency. If the Scheduled Inspection signal appears on the mimic panel, the equipment should be inspected by a suitably trained technician.
• A59: BATT.CIRC. OPEN
Battery switch open.
• A60: FAN FAILURE
Fault in the ventilation system; check the air inlet at the front and the air outlet at the back of the UPS are not obstructed.
8.3. PREVENTIVE MAINTENANCE
Please note that specialist regular maintenance (annually) is recommended for the MASTERYS BC to provide optimum operating efficiency and avoid equipment downtime.
It is strongly advisable to give due consideration to any instructions to perform preventive maintenance displayed automatically with alarm message M29 (refer to chapter 5).
All operations on the equipment must only be carried out by SOCOMEC personnel or authorised support personnel. Maintenance consists of accurate functional checks on electronic and mechanical parts with replacement of parts subject to wear
if necessary (typically batteries, fans and capacitors).
8.3.1. Batteries
The condition of the battery is fundamental to UPS operation. Thanks to the Expert Battery System, the information relating to the battery status and conditions of use are processed in real
time and recharging and discharging procedures are selected automatically in order to optimise battery life expectancy and offer maximum performance.
Furthermore, during the operating life of the battery, MASTERYS BC stores statistics on the conditions of use of the battery for analysis.
Since the expected lifetime of the batteries is very much dependent on operating conditions (number of charging and discharging cycles, load rate, temperature), a regular check by authorised personnel is recommended.
When replacing the batteries use the same type and configuration by placing them in appropriate containers to avoid the risk of acid leakage. Used batteries must be disposed of at authorised recycling and disposal centres. Do not open the plastic cover of the batteries as they contain harmful substances.
33
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
ENGLISH
8. TROUBLESHOOTING
8.3.2. Fans
The lifetime of the fans used to cool the power parts is dependent on usage and environmental conditions (temperature, dust). Preventive replacement by an authorised technician is recommended within four years (in normal operating conditions).
When necessary fans should be replaced as per specifications by SOCOMEC.
8.3.3. Capacitors
The equipment houses electrolytic capacitors (used in the rectifier and inverter section) and filtering capacitors (used in the output section), the lifetime of which is dependent on usage and environmental conditions.
The average expected life of these components is shown below:
• Electrolytic capacitors: 5 years;
• Filtering capacitors: 7 years.
Component status is however verified during preventive maintenance.
34
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
9. ELECTRICAL OPTIONS
9.1. INSULATION CONTROLLER
This device continually checks transformer insulation, displaying an alarm message on the mimic panel.
9.2. EXTERNAL MAINTENANCE BYPASS
This device will electrically exclude and isolate the UPS (e.g. for maintenance operations) without interrupting the power supplied to the load (see paragraph 3.4).
9.3. ACS PCB
Synchronises UPS output with an external power source (another UPS, even of a different brand, generator or transformer).
9.4. SEPARATE AUXILIARY POWER SUPPLY
This allows the use of an auxiliary energy source other than the primary mains power supply in the event of outage.
9.5. EXTERNAL BACKFEED PROTECTION
External devices can be installed to protect against the backfeed of dangerous currents, both on the MAINS SUPPLY and on the AUX MAINS SUPPLY. These devices are controlled by the BKF PCB shown in figure 9.5-1.
The BKF PCB is installed in the position shown in figure 9.5-2. Refer to the following paragraphs for details on electrical connections and activating the chosen protection.
9.5-1
9.5-2
XC1
XB1
XB3
XB2
OUTPUT
L12
L22
L32
N2
EXTERNAL BATTERY
+B2
–B2
–B1
+B1
AUX MAINS SUPPLY
L11
L21
L31
N1
MAINS SUPPLY
L1L2L3
N
XC1
XB2 XB1
35
ENGLISH
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
ENGLISH
9. ELECTRICAL OPTIONS
9.6. PROTECTION ON MAINS SUPPLY AND ON AUXILIARY MAINS SUPPLY
Activating UPS protection on the mimic panel: access the SERVICE menu on the mimic panel (see the SERVICE menu sec- tion) and set the SET BACKFEED parameter to 2.BYPASS-INPUT Alone.
Cable and trunk schematic
9.6-1
UPS 3/3 with separate auxiliary supply
A UPS
L11
Q2
L21
L31
N1
T2
B
M2
L11
L21
L31
N1
XB1
XB2
BKF card
L1
Q1
L2
L3
N
T1
B
M1
L1
L2
L3
N
Key A Distribution panel B Remote coil switch L1-L2-L3-N Input power source L11-L21-L31-N1 Backup power source M1 Input power terminal board M2 Backup power terminal board T1 Remote switch
1
T2 Remote switch
1
Q1 Input power switch Q2 Backup power switch XB1 Connector on BKF PCB XB2 Connector on BKF PCB
1
Remote switches - rated current
Model T1 T2
60 3/3 125 A AC1 125 A AC1 80 3/3 140 A AC1 140 A AC1
9.7. PROTECTION ON A UPS WITHOUT AUXILIARY MAINS SUPPLY
Activating UPS protection on the mimic panel: access the SERVICE menu on the mimic panel (see the SERVICE menu section) and set the SET BACKFEED parameter to 3.BYPASS-INPUT Common.
Cable and trunk schematic
9.7-1
UPS 3/3 without separate auxiliary supply
A UPS
L1
Q1
L2
L3
N
T1
B
M1
L1
L2
L3
N
XB1
BKF card
Key A Distribution panel B Remote coil switch L1-L2-L3-N Input power source M1 Input power terminal board Q1 Input power switch T1 Remote switch
1
XB1 Connector on BKF PCB
1
Remote switches - rated current
Model T1
60 3/3 125 A AC1 80 3/3 140 A AC1
WARNING The neutral connections on the UPS input or output are identical. Consequently there is no risk of high potential when the input power supply is absent. However, depending on the type of system connected to the output or in some failure conditions (earth leakage, significant phase dispersion or in the case of non-insulated neutral systems), high potential can be detected. It would therefore be necessary to install either adequate neutral switching or a protection system.
36
MASTERYS BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
1. 360 V with Pout = 90% Pn.
2. Initial Condition Pout ≤ 80% Pn
3. @ Battery Fully Discharged. Call SOCOMEC support service.
4. @ Battery Fully Charged. Call SOCOMEC support service.
Models 60 80 Input/Output phases 3/3 3/3
Electrical specifications - Input
Mains voltage Vin 3Ph+N 400 V -10% +20% (up to -40% @50% of nominal load) Input frequency Hz 50-60 ±10% Input power factor > 0.99 THDI < 3%
Electrical specifications - External battery
Battery voltage range V bat from from ±1983 up to ±360
4
Electrical specifications - Output
Output voltage (three phase + neutral)
V 400 V three phase (selectable 360/380/400/415 V) ±1%
1
Frequency Hz 50-60 Hz ±2% (from 1% to 8% if generator is used)
Automatic bypass
nominal output voltage ±15%
(from 10% to 20% selectable if generator is used) Nominal power kW 54 72 Overload
(@ 25 °C; Vin > 380; Vbat > 216)
2
• 10 minutes
• 1 minute
kW
67,5
81
90
108
Crest factor ≥ 2.7 Voltage distortion 1% with linear load
Environment
Operating temperature °C 0÷35 (15÷25 recommended for longer battery life) Storage temperature °C -5÷45 Relative humidity % 0÷95% condensation-free Max. altitude m 1.000 without derating; 3.000 max Acoustic noise dBA < 62 < 62 Required cooling capacity m
3
/h 1330 1330 Dissipated power max W 5341 7121 Dissipated power max BTU/h 18,234 24,312
Standards
Safety EN 62040-1/A1, EN 60950-1 Type and performance EN 62040-3 (VFI-SS-111) EMC EN 62040-2 (Category C3) Product certifi cation CE - TÜV-SÜD Protection level IP20, IP21 on request
Mechanical characteristics with standard batteries
Dimensions (LxPxH) mm 444 x 795 x 1400 444 x 795 x 1400 Weight kg 200
1
210
1
10. TECHNICAL SPECIFICATIONS
www.socomec.com
HEAD OFFICE
SOCOMEC GROUP
S.A. SOCOMEC capital 10 816 800€ R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE Tel. +33 3 88 57 41 41 Fax +33 3 88 74 08 00 info.scp.isd@socomec.com
Socomec worldwide
BELGIUM
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +32 2 340 02 30 Fax +32 2 346 28 99 info.be@socomec.com
FRANCE
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +33 1 45 14 63 00 Fax +33 1 48 67 31 12 dcm.ups.fr@socomec.com
GERMANY
Power Control & Energy Efficiency
Tel. +49 7243 65292 0 Fax +49 7243 65292 13 info.scp.de@socomec.com
UPS
Tel. +49 621 71 68 40 Fax +49 621 71 68 444 info.ups.de@socomec.com
ITALY
Power Control & Energy Efficiency
Tel.+39 02 98 49 821 Fax +39 02 98 24 33 10 info.scp.it@socomec.com
Solar
Tel. +39 0444 598611 Fax +39 0444 598627 info.solar.it@socomec.com
UPS
Tel.+39 02 98 242 942 Fax +39 02 98 240 723 info.ups.it@socomec.com
NETHERLANDS
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +31 30 760 0900 Fax +31 30 637 2166 info.nl@socomec.com
POLAND
Power Control & Energy Efficiency
Tel. +48 91 442 64 11 Fax +48 91 442 64 19 info.scp.pl@socomec.com
UPS
Tel. +48 22 825 73 60 Fax. +48 22 825 73 60 info.ups.pl@socomec.com
PORTUGAL
UPS / Solar
Tel.+351 261 812 599 Fax +351 261 812 570 info.ups.pt@socomec.com
ROMANIA
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +40 21 319 36 88 Fax +40 21 319 36 89 info.ro@socomec.com
RUSSIA
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +7 495 775 19 85 Fax +7 495 775 19 85 info.ru@socomec.com
SLOVENIA
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +386 1 5807 860 Fax +386 1 561 11 73 info.si@socomec.com
SPAIN
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +34 93 540 75 75 Fax +34 93 540 75 76 info.es@socomec.com
UNITED KINGDOM
Power Control & Energy Efficiency
Tel. +44 1462 440 033 Fax +44 1462 431 143 info.scp.uk@socomec.com
UPS
Tel.+44 1285 863 300 Fax+44 1285 862 304 info.ups.uk@socomec.com
TURKEY
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +90 216 540 71 20-21-22 Fax +90 216 540 71 27 info.tr@socomec.com
YOUR DISTRIBUTOR
IN ASIA PACIFIC
AUSTRALIA
UPS
Tel. +61 2 9325 3900 Fax +61 2 9888 9544 info.ups.au@socomec.com
CHINA
UPS / Power Control & Energy Efficiency
Tel. +86 21 52 98 95 55 Fax +86 21 62 28 34 68 info.cn@socomec.com
INDIA
Power Control & Energy Efficiency
Tel. +91 124 4027210 Fax +91 124 4562738 info.scp.in@socomec.com
836}6RODU
Tel. +91 44 39215400 Fax +91 44 39215450 & 51 info.ups.in@socomec.com info.solar.in@socomec.com
SINGAPORE
UPS / Power Control & Energy Efficiency
Tel.+65 6506 7600 Fax +65 64 58 7377 info.sg@socomec.com
THAILAND
UPS
Tel. +66 2 941 1644 7 Fax +66 2 941 1650 info.ups.th@socomec.com
VIETNAM
UPS
Tel. +84 8 3559 1220 Fax +84 8 3559 1221 info.ups.vn@socomec.com
IN MIDDLE EAST
UNITED ARAB EMIRATES
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel.+971 4 29 98 441 Fax +971 4 29 98 449 info.ae@socomec.com
IN AMERICA
USA, CANADA & MEXICO
Power Control & Energy Efficiency
Tel. +1 617 245 0447 Fax +1 617 245 0437 info.us@socomec.com
OTHER COUNTRIES
NORTH AFRICA
Algeria / Morocco / Tunisia
info.naf@socomec.com
AFRICA
Other countries
info.africa@socomec.com
SOUTH EUROPE
Cyprus / Greece / Israel / Malta
info.se@socomec.com
SOUTH AMERICA
Tel. +34 93 540 75 75 info.es@socomec.com
MORE DETAILS
www.socomec.com/worldwide
IN EUROPE
*IOMMASBCXX06-EN 06*
IOMMASBCXX06-EN 06 12.2016
Loading...