socomec Modulys GP Green Power 2.0 Series, M4-S-125-HCA0, M4-S-100-HCA0 Installation And Operating Manual

Page 1
MODULYS GP
INSTALLATION AND OPERATING
MANUAL
Green Power 2.0 range
100 kW UL
EN
www.socomec.com
Page 2
Page 3
CONTENTS
1. SAFETY STANDARDS 5
1.1 IMPORTANT SAFETY INSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 DESCRIPTION OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3 BBREVIATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2. ENVIRONMENTAL REQUIREMENTS AND HANDLING 8
2.1 ENVIRONMENTAL REQUIREMENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 HANDLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3. ELECTRICAL INSTALLATION 10
3.1 ELECTRICAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2 CABLE POSITIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4. OVERVIEW 13
5. CONNECTIONS 15
5.1 EXTERNAL BATTERY CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.2 POWER AND BYPASS MODULE INSERTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6. CONTROL PANEL 23
7. DISPLAY OPERATION 26
7.1 DISPLAY DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
7.2 MENU ARCHITECTURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7.3 FUNCTIONING MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.4 STATUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.4.1 STATUS PAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.5 ALARMS MANAGEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.5.1 ALARM REPORT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.5.2 ALARM POPUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.5.3 ALARM PAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.6 SYNOPTIC ANIMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
7.6.1 ADDITIONAL ICONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.7 EVENT LOG PAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.8 MENU FUNCTION DESCRIPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.8.1 ENTERING PASSWORDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.8.2 MONITORING MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.8.3 EVENTS LOG MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.8.4 MEASUREMENTS MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.8.5 CONTROLS MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.8.6 UPS CONFIGURATION MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.8.7 USER PARAMETERS MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.8.8 SERVICE MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.9 ADDITIONAL USER FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.9.1 PHASE COLOR MODIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
8. OPERATING PROCEDURES 41
8.1 SWITCHING ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.2 SWITCHING OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.3 BYPASS OPERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.4 EXTENDED OUT OF SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
8.5 EMERGENCY SHUTDOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
9. OPERATING MODES 43
9.1 ON LINE MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
9.2 HIGH EFFICIENCY MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
9.3 OPERATION WITH MOTOR GENERATOR (GENSET) . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10. STANDARD FEATURES AND OPTIONS 44
10.1 ADC+SL CARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
10.1.1 TEMPERATURE SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
10.2 NET VISION CARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10.2.1 EMD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10.3 LI-ION BATTERY INTERACTIVITY KIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10.4 TOP AIR EXHAUSTED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
10.5 TOP ENTRY CABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
11. PREVENTIVE MAINTENANCE 51
11.1 BATTERIES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
11.2 FANS & CAPACITORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
12. SAFEGUARDING THE ENVIRONMENT 52
13. TECHNICAL SPECIFICATIONS 53
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 4
SOCOMEC retains the full and exclusive ownership rights to this document. Only a personal entitlement to use the document for the application indicated by SOCOMEC is granted to the recipient of this document. The reproduction, modification, distribution of this document, either partially or wholly and in any manner, is strictly prohibited except upon Socomec’s express prior written consent.
This document is not a specification. SOCOMEC reserves the right to make any changes to the information provided without prior notice.
4 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 5
1. SAFETY STANDARDS
1.1 IMPORTANT SAFETY INSTRUCTION
SAVE THIS INSTRUCTION - This manual contains important instructions for models M4-S-100-HCA0, M4-S-125­HCA0 and options, that should be followed during installation and maintenance of the UPS and batteries.
This manual should be kept carefully in a safe place near the UPS, so that it can be consulted by the operator at any time for any information that may be needed regarding correct use of the unit. Read the manual carefully before connecting the unit to the a.c. mains supply and to the downstream appliances. Before the UPS is put into commis­sion, the user must be perfectly familiar with its operation, with the position of all the controls and with the technical and functional characteristics of the unit, so as to ensure there will be no risk to any persons or to the appliance itself.
NOTE! Any work carried out on the equipment must be performed by skilled, qualified technicians.
DANGER! Failure to observe safety standards could result in fatal accidents or serious injury, and damage equipment or the environment.
CAUTION! If the unit is found to be damaged externally or internally, or any of the accessories are damaged or missing, contact SOCOMEC. Do not operate the unit if it has suffered a violent mechanical shock of any kind.
NOTE! Install the unit in accordance with clearances in order to prevent access to handling devices and guarantee sufficient ventilation (refer to 'Environmental requirements' chapter).
NOTE! Only use accessories recommended or sold by the manufacturer.
NOTE! When the equipment is transferred from a cold to a warm place wait approx. two hours before putting the unit into operation.
Avoid exposing the UPS to contact with water or any liquids generally. Do not insert foreign objects into the cabinet.
WARNING! Connect the protective earth (PE) conductor before making any other connections.
The wiring methods in accordance with the National Electrical Code, ANSI/NFPA 70 and Canadian Electric Code (CEC) are to be used. All national standards applicable to batteries must be observed.
CAUTION! To reduce the risk of fire, connect only to a circuit provided with 200 amperes maximum branch­circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70.
DANGER! RISK OF ELECTRIC SHOCK! Before carrying out any operations on the unit (cleaning and maintenance performances, connec­tion of appliances, etc.) disconnect all power sources.
DANGER! RISK OF ELECTRIC SHOCK! After disconnecting all power sources wait approx. 5 minutes for the complete discharge of the unit.
NOTE! Any use other than the specified purpose will be considered improper. The manufacturer/supplier shall not be held responsible for damage resulting from this. Risk and responsibility lies with the system manager.
• Use the UPS in accordance with the technical specifications indicated in this manual (chapter 'Operating modes').
• A specific input with remote EPO (Emergency Power Off) is available.
• In the event that the equipment has no automatic backfeed protection contactor device, make certain that:
- the user/installer attaches warning labels to all mains isolating switches located remotely from the area where the UPS is sited, in order to inform service personnel that the circuit is connected to a UPS.
- an external isolating device is installed.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 6
CAUTION The user is cautioned that any changes or modifications not expressly approved by Socomec could void the user’s authority to operate the equipment.
IMPORTANT!: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reason­able protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
NOTE! The product you have chosen is designed for commercial and industrial use only. In order to be used for particular critical applications such as life support systems, medical applications, commercial transportation, nuclear facilities or any other application or system where product failure is likely to cause substantial harm to people or prop­erty, the products may have to be adapted. For such uses we would advise you to contact SOCOMEC beforehand to confirm the ability of these products to meet the requested level of safety, performance, reliability and compliance with applicable laws, regulations and specifications.
1.2 DESCRIPTION OF SYMBOLS
All interior and exterior precautions and warnings on labels and plates on the equipment should be complied with.
5 min.
UL 1778; CSA-C22.2 NO.107.3-05; MET file E114654
Waiting time before operating
The electrolyte corrodes metals and burns the skin and all parts of the human body.
WARNING! Risk of explosion! Avoid short circuits! Never place tools or metal objects on the accumu­lators.
DANGER! High voltage (black/yellow) Wear safety goggles and suitable clothing.
Protective earth terminal (PE) Read the user instructions carefully.
Read the user manual before performing any operations.
Read the user manual before using the unit Wear protective gloves and clothing.
It is forbidden for non-qualified personnel to work on the batteries.
In the event of contact with the eyes, wash immediately with plenty water and call a doctor. Call a doctor immediately in the event of accidents or illness.
Do not smoke, use naked flames or generate sparks in the vicinity of the accu-
The unit MUST be handled by at least two people.
mulators.
Accumulators are heavy! Use suitable trans­port and lifting equipment to work safely.
Batteries and related parts contain lead. Lead is dangerous to health if ingested. Wash hands after handling!
Connecting accumulators in series creates hazardous voltages.
We advise you to contact SOCOMEC beforehand to confirm the ability of these products to meet the required level of safety, performance, reliability and compliance with applicable laws, regulations and specifications.
6 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 7
1.3 BBREVIATIONS
For the purpose of this document, the following abbreviations are used:
BMS Battery Management System EMC Electro Magnetic Compatibility HMI Human Machine Interface IEC International Electrotechnical Commission IMD Insulation Monitoring Device LIB Li-Ion battery MBMS Master BMS PE Protective Earth SOC State of Charge SOH State of Health SPD Surge Protection Device THDI Total Harmonic Distortion in Current THDV Total Harmonic Distortion in Voltage UPS Uninterruptible Power Supply
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 8
2. ENVIRONMENTAL REQUIREMENTS AND HANDLING
NOTE! Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
2.1 ENVIRONMENTAL REQUIREMENTS
The room must be:
• of a suitable size
• free from conductive, inflammable and corrosive items;
• not exposed directly to sunlight.
The floor must support the weight of the unit and guarantee its stability. The unit is designed for indoor installation only.
• Check that the UPS will not be installed in a dusty environment.
ROOM POSITIONING
UPS OR
OTHER
CABINET
(1)
UPS
≥ 5 ft
130°
UPS OR
OTHER
CABINET
door
UPS OR OTHER
CABINET
free area
Top view: rear air outlet Top view: top air outlet
free area
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS
≥ 5 ft
≥ 1.25 ft
130°
UPS OR
OTHER
CABINET
door
UPS OR
OTHER
CABINET
free area
UPS OR
OTHER
CABINET
Front view: rear or top air outlet
free area
≥ 0.5 ft
UPS OR
OTHER
CABINET
1. This configuration is possible only with top air-exhaust option. See 'Standard features and options' chapter.
UPS OR
OTHER
CABINET
UPS
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
8 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 9
IN-ROW CONFIGURATION
Top view Front view
free areahot aisle
≥ 1.25 ft
SERVER
OR OTHER
CABINET
SERVER
OR OTHER
CABINET
≥ 5 ft
UPS
130°
SERVER
OR OTHER
CABINET
door
SERVER
OR OTHER
CABINET
free areacold aisle
SERVER
OR OTHER
CABINET
SERVER
OR OTHER
CABINET
UPS
2.2 HANDLING
• The packaging guarantees the stability of the unit during shipping and physical transfer.
• The unit must remain in a vertical position during all shipping and handling operations.
• Ensure that the floor is strong enough to support the weight of the unit.
• Carry the packaged unit as close as possible to the installation site.
WARNING! HEAVY WEIGHT! Move the unit using a fork lift truck taking the utmost caution at all times.
The unit MUST be handled by at least two people. The people MUST take position at the sides of the UPS with respect to the direction of movement.
SERVER
OR OTHER
CABINET
SERVER
OR OTHER
CABINET
Do not move the unit by putting pressure on the front door.
When moving the unit on even slightly sloping surfaces, use the locking equipment and braking devices to ensure that the unit does not fall over.
WARNING! The following instructions must be carried out prior to moving the unit (after initial positioning). Failure to heed this warning could result in the unit falling over, equipment damage, injury and even death
WARNING! RISK OF TIPPING OVER! The six feet must be secured evenly to ensure the unit is stable.
Ø43/64"
25"3/32
Tightening torque 450 lb.in
Recommended diameter of screws 5/8"
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
15"17/32 15"17/32
2"3/4
Page 10
3. ELECTRICAL INSTALLATION
NOTE! Before carrying out any operations on the unit read the 'Safety standards' chapter carefully
3.1 ELECTRICAL REQUIREMENTS
The installation and system must comply with national plant regulations.
The electrical distribution panel must have a sectioning and protection system installed for input mains.
If a RCD is required a B-type should be used.
The short circuit current (Icw) according to UL1778 is 10kA rms.
Size of input protection devices
Model rat-
ing
(kVA) (A) (A) (mm
100 200 0.5 1/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG
1. Circuit breaker switch recommended with magnetic intervention threshold 10 In (curve D). The min value depends on the size of the power cables in the installation, while the max value is limited by the UPS cabinet.
2. Caution! Use type B four-pole selective (S) residual current detectors. Load leakage currents are to be added to those generated by the UPS and during transitory phases (power failures and power returns) short current peaks may occur. If loads with high leakage current are present, adjust the residual current protection. It is advisable in all cases to carry out a preliminary check on the earth current leakage with the UPS installed and operational with the definitive load, so as to prevent the RCD tipping over.
3. Use tin plated copper lugs.
Breaker
(1)
Input
Max Min Min Max Min Max
RCD
input
Input/Output cable size Battery cable core size
(2)
2
) (mm2)
Type of
cable
AWG,
90°C
(2)
Tightening
torque
180 lb-in
(20.3 Nm)
CAUTION! To reduce the risk of fire, connect only to a circuit provided with 200 A maximum branch circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1.
The UPS is designed for transient overvoltages in category II installations. If the UPS is part of the building’s electrical circuit, or is likely to be subject to transient overvoltages in category III installa­tions, additional external protection must be provided, either on the UPS or in the AC power supply network powering the UPS.
WARNING! Protective earthing conductor (PE) must have sufficient current-carrying capacity. The PE cable core size must be chosen according to the PROTECTIVE CURRENT RATING of the earth circuit which depends on the provision and location of protective overcurrent devices.
10 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 11
BACKFEED PROTECTION
The UPS is set up for the installation of external protection devices against the backfeed of dangerous voltages on the auxiliary backup mains power supply line (AUX MAINS SUPPLY). The current rating of the switching device has to follow the instruction outlined in chapter 'Electrical requirements'.
DANGER! RISK OF ELECTRIC SHOCK! The installer must attach the warning label in order to warn electrical technicians about dangerous backfeed situations (not caused by the UPS)
Warning label (supplied with the equipment) Backfeed electrical diagram
Before working on this circuit
- Isolate the Uninterruptible Power System (UPS)
- Then check for Hazardous Voltage between all terminals including the protective earth
Risk of Voltage Backfeed
Backfeed card
L1 L2 L3
N
UPS output
voltage
max
250V
Backfeed Card
Dry Contact
B
NOTE! Use a 220-240 V release coil with integrated travel limit contact to pilot the input protection systems. If a trip coil without an integrated end-of-travel contact is used, an early auxiliary contact must be added (see figure). Electrical data of the contacts: 2 A 250 Vac.
Function Detail
BKF AUX COM1
(Connector name)
- NO1
(XB1)
(XB3)
V OUT Internal fuse
250 V RMS 2 A time delay
The backfeed protection for the input mains supply (MAINS SUPPLY) is incorporated inside the UPS modules as standard.
As an option the unit can be delivered with the integrated internal backfeed switches.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
11EN
Page 12
3.2 CABLE POSITIONING
WARNING! The cables must be installed on trays according to the following diagrams. The trays must be positioned near the UPS.
WARNING! All metal and suspended ducts or those in raised flooring MUST be connected to earth and to the various cabinets
WARNING! Power cables and control cables MUST NEVER be installed in the same duct.
WARNING! Risk of electromagnetic interference between battery cables and output cables.
Correct installation Acceptable installation
Battery
Common
Mains Load
N N
Control
cables
(1)
Battery
Common
Mains Load
N N
0.3 ft 0.3 ft
0.3 ft
Control cables
(1)
1. Control cables: connections between the cabinets and each unit, alarm signals, remote mimic panel, connection to the BMS (Building Management System), emergency stop, connection to generator.
12 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 13
4. OVERVIEW
MODULYS GP front view
Slots not available
Control panel
UPS door
Slots for power modules only
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
13EN
Page 14
SYSTEM WITH MANUAL BYPASS AND INPUT, AUX MAINS, OUTPUT SWITCHES
USB connector (only for service)
Ethernet network (only for service)
Option slot 1
Option slot 2
Over voltage protection
Hot-swap bypass
WIRING DIAGRAM
Q1 (Input mains switch)
Fuse
Service connection
Service Fuse
Q3 (output switch)
UPS connections
14 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 15
5. CONNECTIONS
NOTE! Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
WARNING! Battery power terminals can be supplied by:
- external battery cabinet;
- internal battery modules;
- UPS power modules.
Before working on this circuit ensure that:
- all the external battery cabinet switches are in OFF position;
- all the internal battery modules are disconnected;
- the UPS is in maintenance bypass mode (refer to 'Operating modes' chapter);
- all UPS power modules are disconnected;
Check the presence of voltage before operating.
WARNING! The unit is supplied with the bars already installed. In the case of separate mains connection remove the bars.
FLOOR MOUNTING ANTI-INTRUSION INSTALLATION KIT
NOTE! The cables coming from the rear of the unit must pass through the appropriate gap. This operation must be carried out:
- before wiring operations;
- before securing the kit to the unit and the floor.
1
A B C
2 3 4
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
15EN
Page 16
EXTERNAL
BATTERY MAINS SUPPLY
PROTECTIVE EARTH
TERMINAL
OUTPUT
16 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 17
5.1 EXTERNAL BATTERY CONNECTION
NOTE! For further information refer to the battery cabinet manual.
• Remove the plastic terminal block protection.
• Connect the protective earth (PE) cable.
• Connect the cables between the UPS terminals and the battery cabinet terminals.
WARNING! Strictly observe:
- the polarity of each individual string (refer to the figure below);
- the cable cross section (refer to 'Electrical requirements' chapter).
WARNING! Cabling errors with inversion of battery polarity may cause permanent damage to the equipment.
Reassemble the plastic terminal block protection.
UPSBATTERY CABINET
-- ++ NN
Note! Not all battery/capacity combinations are available.
Note for Li-ion batteries (LIB): The UPS interface to the Li-ion batteries (LIB), which could be based on a communication protocol or on dry contacts, monitors battery operation for the sole purpose of ensuring overall system service. This UPS battery interface cannot in any way replace safety systems to protect the battery against abuse or improper use, which requires an independent system in compliance with the relevant standards.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
17EN
Page 18
5.2 POWER AND BYPASS MODULE INSERTION
Note! Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
WARNING! RISK OF TIPPING OVER! Before carrying out any operations, ensure the UPS is secured at the feet.
WARNING! RISK OF TIPPING OVER! The six feet must be secured evenly to ensure the unit is stable.
WARNING! RISK OF TIPPING OVER! The modules must be inserted from the bottom upwards and removed from the top downwards to ensure the unit remains stable.
WARNING! Before removing any module, ensure that the remaining power modules can support the load.
Power module electrical diagram Bypass module electrical diagram
INPUT BATTERY INPUT MAINS
X1 X1
F1/F2
80 A
400 Vac 3ph+N 50 Hz+/-400 Vdc 3 W
F3/F4/F5
80 A
F6/F7/F8
80 A
X2
400 Vac 3ph+N 50 Hz
UPS OUTPUT
AUXILIARY MAINS
400 Vac 3ph 50 Hz
X3X4
400 Vac 3ph 50 Hz
UPS OUTPUT
18 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 19
POWER MODULE INSERTION
1 2 3
4 5
WARNING!
6 7
Ensure the module is installed in the correct position.
8 9 10
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
19EN
Page 20
POWER MODULE REMOVAL
1 2 3
4 5
6 7
A
B
C
20 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 21
BYPASS MODULE REPLACEMENT
WARNING! It is only possible to remove the bypass module when the unit is in normal mode or in mainte­nance bypass mode (refer to 'Operating modes' chapter). Before removing the bypass ensure that the unit is not in bypass mode.
1 2
A
B
C
3 4
A
B
C
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
21EN
Page 22
5 6 7
8 9
WARNING! The screws provide protective bonding and avoid unauthorised bypass removal. Tighten the screws to ensure the bonding protection.
DANGER! Failure to observe this safety instruction could result in fatal accident or serious injury, and damage equip­ment or the environment.
22 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 23
6. CONTROL PANEL
Luminous
status bar
Power module LED indicators
Bypass module LED indicator
LED indicator
Colour Power module Bypass module
Green Module on inverter Bypass ready to start Flashing green - Load on bypass Yellow Module ready to start Maintenance bypass
Flashing yellow Module initialising
Load on inverter or bypass and transfer impossible/
locked Red Module stopped due to alert Bypass alert present Flashing red Initialising failure Bypass blocked with alert Flashing green yellow and red
No communication No communication
Control panel luminous status bar indicator
Colour Status
No communication. The data is no longer updated or not
Flashing red-yellow-green-red
present.
Load status cannot be given. Flashing red Load supplied, but the output will stop in few minutes. Red Load not supplied: Output switched OFF due to an alarm. Flashing yellow-red Load supplied, but no longer protected. A critical alarm occurs. Flashing yellow Maintenance request / in progress. Yellow Load supplied with warning. Flashing green-yellow-green Load supplied and preventive alarm present.
Flashing green Load going to be supplied and testing.
Green Load protected in inverter. Grey (OFF) Load not supplied output on standby / isolated / OFF.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
23EN
Page 24
CONTROL PANEL EXTRACTION
A
D
B
E
C
F
Display
HOME button
Luminous status bar
24 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 25
Only two elements are necessary to interact with the unit:
• HOME button: is a mono-stable button used to interact manually with the display especially in emergency situa­tions. Logic behind the interaction is:
- Single pressing (below 3 sec): HOME page return of graphic display
- 3 sec < time < 6 sec: change the language to the default (English)
- 6 sec < time < 8/9 sec: go to the calibration screen automatically
- Above 8/9 sec: implement the hw reset of the micro controller and restart of the graphic
• Display: is the main active matrix of the display sensitive to touch pressure. The display is designed for rugged industrial applications. The display is single-touch only (no double touch effects). Depending on pressure, the navi­gation tree and various functions will be executed.
Two special functions are present on the control panel:
• Standby screen: for safety reasons, after a programmable amount of time, the display goes on standby. Display goes to the main screen and touch screen sensitivity is disabled. A label on the bottom of the main screen displays this status. To exit this status press the screen for the HOME button.
• OFF status: for power consumption and life enhancement, after a programmable amount of time display goes in “off”. Display goes black and no interaction is possible. Touching the HOME button or screen resumes normal operations.
Handle the control panel with care. It is made of metal, glass and plastic and contains delicate electronic components. The control panel may be damaged if dropped, pierced or broken or comes into contact with liquids. Do not use the control panel with a cracked screen, as it may cause injury.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
25EN
Page 26
7. DISPLAY OPERATION
7.1 DISPLAY DESCRIPTION
Stand alone UPS or unit view
4
6
2 31
8
9
Modules view:
2 31
8
10
UPS parallel system: System view
5
7
4
6
Menu access
5
1
Device reference
2
Functioning mode (see 'Functioning mode' chap-
3
ter) Status displaying / Status page access
4
Alarm present – access to alarm page
5
“Alarms” icon appears in case of preventive/criti­cal alarm. A dedicated pop-up appears and can be cleared. Clock
4
6
6
Maintenance alert
7
2 31
8
9
UPS parallel system: Units overview
4
2 31
8
10
5
7
Synoptic area
8
Help message area
9
“Press Key to wake up” appears when the display goes on standby. Touch the display to wake it up. Measures report
10
6
5
26 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 27
7.2 MENU ARCHITECTURE
MENU ITEMS
Modular Unit
[UPS]
MONITORING
▶ ALARMS
▶ STATUS
▶ SYNOPTIC
▶ UNIT
▶ SYSTEM
▶ MODULES OVERVIEW
▶ MODULE
EVENTS LOG MEASUREMENTS
▶ OUTPUT MEASUREMENTS
Modular Unit
[1] to [3]
Modular System
[SYS]
▶ BATTERY MEASUREMENTS ^ ^ ^
▶ INPUT MEASUREMENTS
▶ INVERTER MEASUREMENTS
▶ BYPASS MEASUREMENTS ^ ^ ^
CONTROLS
▶ UPS PROCEDURE
▶ START ▶ STOP ▶ ON MAINTENANCE BYPASS
▶ MODE
▶ ECO MODE CONTROLS
▶ Eco Mode ON ^ ^ ▶ Eco Mode OFF ^ ^
▶ ECO MODE SCHEDULE ^ ^
▶ ENERGY SAVER CONTROLS
▶ Energy Saver ON ^ ▶ Energy Saver OFF ^
1
1
1
1
1
1
▶ BATTERY
▶ BATTERY CONTROLS
▶ BATTERY TEST ^ ^ ^
▶ BATTERY SCHEDULE ^ ^ ^
▶ MAINTENANCE
▶ Alarms reset ▶ LED test
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
27EN
Page 28
MENU ITEMS
Modular Unit
[UPS]
Modular Unit
[1] to [3]
Modular System
[SYS]
CONFIGURATIONS
▶ CLOCK
▶ COM-SLOTS
▶ COM-Slot 1 ^
▶ COM-Slot 2 ^
▶ TEMPERATURE PROBE ^ ^ ^
▶ REFERENCE
▶ SOCOMEC REFERENCE
▶ SERIAL NUMBER
▶ User Reference
▶ Location
▶ REMOTE
▶ Remote ON
▶ Remote OFF
USER PARAMETERS
▶ LANGUAGE
▶ PASSWORD
▶ BUZZER
▶ DISPLAY
▶ PREFERENCES
▶ TOUCHSCREEN
28 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 29
MENU ITEMS
Modular Unit
[UPS]
Modular Unit
[1] to [3]
Modular System
[SYS]
SERVICE
▶ SERVICE REPORT
▶ FW VERSION
▶ UPS SETTINGS
▶ OUTPUT MENU
▶ Output voltage ▶ Output frequency ▶ Converter mode ▶ Automatic restart
▶ BATTERY MENU
▶ BATTERY INSTALLATION
▶ Battery available ^ ^ ^ ▶ Battery type ^ ^ ^ ▶ Battery connection ^ ^ ^ ▶ Recharge type ^ ^ ^
▶ BATTERY DATA
▶ Capacity ^ ^ ^ ▶ N° of cells ^ ^ ^ ▶ N° of blocks ^ ^ ^ ▶ Premin. Voltage ^ ^ ^ ▶ Min. Voltage ^ ^ ^ ▶ Floating ^ ^ ^ ▶ Boost Voltage ^ ^ ^
▶ BATTERY THRESHOLDS
▶ Rech. Curr. Limit ^ ^ ^ ▶ Float-Boost Threshold ^ ^ ^ ▶ Boost-Float Threshold ^ ^ ^
▶ TEMP.COMPENSATION
Temper.Compensation ^ ^ ^
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
29EN
Page 30
MENU ITEMS
Modular Unit
[UPS]
▶ TRANSFORMER MENU
▶ Input transformer ▶ Output transformer ▶ Aux transformer ▶ Input trasfo Voltage ▶ Output trasfo Voltage ▶ Aux trasfo Voltage
▶ MAINS CONFIGURATION
▶ Mains confi guration
▶ REDUNDANCY
▶ Nominal Number of Modules ▶ Redundancy level
▶ NETWORK PARAMETERS
(Only for service)
▶ DHCP
▶ IP
Modular Unit
[1] to [3]
Modular System
[SYS]
▶ MASK
▶ GATEWAY
▶ MAC (ready only)
▶ COMMISSIONING
(^). Depending on setting
1. Displayed depending on state.
30 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 31
7.3 FUNCTIONING MODE
Service
Isolated
Eco mode scheduling active
Eco Mode active
Standby active
Energy saver active
Autotest
7.4 STATUS
7.4.1 STATUS PAGE
Filtering
List all active status
List all status
List all status not active
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
31EN
Page 32
7.5 ALARMS MANAGEMENT
7.5.1 ALARM REPORT
The alarm icon is present if at least one alarm is present.
Tap on the icon to open the alarm list.
7.5.2 ALARM POPUP
In case of critical alarm a popup message appears and the buzzer is running according its settings.
The highest priority alarm is displayed.
Tap on valid button to stop the buzzer and to close the popup message. The alarm page is automatically display after this action.
7.5.3 ALARM PAGE
Filtering
List all active alarms
List all active preventive alarms
List all active critical alarms
POPUP ALARM FOR PREVENTIVE ALARM
In USER PARAMETERS menu, PREFERENCES item gives the possibility to enable popup alarm also with preventive alarms.
32 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 33
7.6 SYNOPTIC ANIMATION
Stand alone UPS or unit view
6
1
16 16
11
UPS parallel system: System view
7
2 4
14
13
3
3
15
12
8
9
5
10
6
1
5
9
10
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
33EN
Page 34
Item Description
1
Rectifier input supply Not present Present
Grey Green Yellow Red
Normal
2
Rectifier status
status
Rules of animation
Out of toler-
ance
-
Preventive
alarm
Touch actions
--
Critical alarm
Access to input
measurements page
3
DC voltage bus
DC voltage
absent
Normal
4
Inverter status
5
Inverter output Inverter OFF Inverter ON
6
Maintenance bypass * MBP present -
7
Bypass input * Not present Present
status
Normal
8
Bypass status *
status
No load
9
Load rate symbol
DC voltage
presence
-
-
Fill-up to
95%
-- -
Preventive
alarm
Critical alarm
Access to inverter
measurements page
Inverter on
battery
--
Load on
maintenance
--
bypass
Out of toler-
ance
Preventive
alarm
--
Critical alarm
Access to bypass
page
Fill-up to
110%
Fill-up over
110%
Access to output
measurements pages
10
Load rate value Instantaneous value. displayed if value > 0 -
11
DC battery input **
12
DC battery output **
DC voltage
absent
DC voltage
absent
-
13
Battery indicator **
-
Battery charging /
14
discharging **
Battery level or remain-
15
ing backup time during
The backup time is no more displayed if it is below two
battery discharge **
16
Shared battery symbol not present if each unit has its own battery. ** -
* Element disappears if converter mode is active ** Not present if batteries are not present
DC voltage
presence
DC voltage
presence
Fill-up to
100%
Battery
charging
BCR function
running
Inverter on
battery
Fill-up to
45%
Battery
discharging
Fill-up to
Instantaneous value. displayed if value > 0
minutes.
--
-
15%
Access to bat. meas-
urements page
-
-
-
34 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 35
UPS parallel system: Units overview
Unit selected Load report Battery report
Module number
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
35EN
Page 36
Battery animation
Battery status DESCRIPTION
If battery is absent, the battery icon is not displayed
If battery is present but not connected, the icon is
displayed
If the battery is present and charging, the arrow icon is
displayed
If the battery is present and discharging, the arrow
icon is displayed
If a battery alarm has occurred, the red icon is
displayed
36 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 37
7.6.1 ADDITIONAL ICONS
Bypass impossible
Bypass locked
“Genset Mode” when the gen set contact is active. Need ADC+SL correctly configured.
Maintenance alarm.
Preventive maintenance is requested.
7.7 EVENT LOG PAGE
Show STATUS events
Show ALARMS events
Show CONTROLS
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
37EN
Page 38
7.8 MENU FUNCTION DESCRIPTIONS
7.8.1 ENTERING PASSWORDS
Some operations and settings require a password in order to be performed.
Press “123” to cycle to number view page.
Press ENTER to confirm.
Wildcard covering of the password is active by default.
The default password is SOCO.
NOTE! The password must only contain capi­tal letters and not include the following characters ():*<>._
Press ENTER to confirm the selection or HOME BUTTON to abort.
7.8.2 MONITORING MENU
Submenu Alarm opens the alarm pages.
Submenu Status opens the status pages.
7.8.3 EVENTS LOG MENU
This menu accesses the event log (Status and Alarms).
7.8.4 MEASUREMENTS MENU
This menu displays all UPS measurements relating to the rectifier input stage, output stage, batteries, bypass input stage and inverter.
The pins on the bottom of the screen indicate whether or not there are more pages. Sliding to the right or left changes measurements page.
7.8.5 CONTROLS MENU
This menu contains the commands that can be sent to the UPS. Some of them are password protected. If a command is not available, a COMMAND FAILURE message appears.
UPS PROCEDURE: START/ON MAINTENANCE BYPASS/STOP see 'Operating procedures' chapter.
BATTERY: BATTERY CONTROL > BATTERY TEST: this function checks whether or not test conditions are
available and returns the results.
ECO MODE CONTROLS: this function sets/resets the ECO MODE.
MAINTENANCE: Alarms reset: this function clears the alarm history, LED test: this function activates LED flash-
ing for a few seconds.
38 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 39
7.8.6 UPS CONFIGURATION MENU
CLOCK: this function sets the date and time.
COM-SLOTS: this function configures the RS485 modbus serial link.
REFERENCE: this function gives the possibility to customised the unit reference and the location.
REMOTE: this function enables controls from remote devices through MODBUS protocol (NET VISION for exam- ple).
7.8.7 USER PARAMETERS MENU
This menu contains the different functions for users such as language, password, buzzer, display, preferences, touchscreen calibration.
7.8.8 SERVICE MENU
This menu is reserved for support service personnel and holds UPS identification data and utilities for software upgrades.
UPS SETTINGS: critical machine settings for output. Some parameters cannot be modified when the UPS supplies the load by INVERTER or BYPASS.
Wrong configuration in UPS SETTINGS could damage the load or the batteries.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
39EN
Page 40
7.9 ADDITIONAL USER FUNCTIONS
7.9.1 PHASE COLOR MODIFICATION
• Enter MAIN MENU > USER PARAMETERS > PREFERENCES
For each phase is possible to select a specific colour in a set of colour range. Those colours are applying in the measurements pages.
Colour Default colour
Yellow Phase 3
Orange
Red
Green
Light blue Phase 2
Dark blue
Purple Phase 1
Brown
Light grey
Dark grey
Black
The popup alarm appears in case of critical alarms. This function can be extended to preventive alarms by switching “Preventive Popup Alarm” to ON.
40 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 41
8. OPERATING PROCEDURES
NOTE: before carrying out any operations on the unit read the 'Safety standards' chapter care­fully.
NOTE: with the stop procedure the load will be disconnected.
8.1 SWITCHING ON
• Connect the mains to the UPS.
• Put switch Q1 (or the external input mains switching device) into position 1.
• Wait for the display to switch on.
• Enter MAIN MENU > COMMANDS > UPS PROCEDURES.
• Select Automatic Start Procedure and press ENTER.
• Carry out the operations indicated on the display.
8.2 SWITCHING OFF
This operation interrupts the power supply to the load. The UPS and the battery charger will be shutdown.
• Enter menu MAIN MENU > CONTROLS > UPS PROCEDURE.
• Select Automatic Stop Procedure and press ENTER.
• Wait approx. 2 minutes for the UPS shutdown.
NOTE: the controlled shutdown of each server connected to the LAN can be managed by shut­down software (only with Net Vision option card).
• Carry out the operations indicated on the display. This operation cannot be aborted.
8.3 BYPASS OPERATIONS
Available only with external manual bypass.
SWITCHING ONTO MAINTENANCE BYPASS
This operation creates a direct connection between the UPS input and output, excluding the equipment control part. This operation is performed in the event of:
- standard maintenance.
- serious failure has occurred.
WARNING! This operation interrupts temporarily the power supply to the load.
WARNING! LOAD POWERED BY INPUT MAINS! Your load is exposed to mains disturbances.
• Enter menu MAIN MENU > CONTROLS > UPS PROCEDURE.
• Select Automatic Stop Procedure and press ENTER.
• Carry out the operations indicated on the display.
NOTE! When an external manual bypass is present:
- carry out the procedure described above;
- put the switch to position 1.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
41EN
Page 42
SWITCHING ON FROM MAINTENANCE BYPASS
• Put the external manual bypass switch to position 0.
WARNING! This operation interrupts the power supply to the load.
• Put switch Q1 (or the external input mains switching device) into position 1.
• Wait for the display to switch on.
• Enter menu MAIN MENU > CONTROLS > UPS PROCEDURE.
• Select Automatic Start Procedure and press ENTER.
• Carry out the operations indicated on the display.
8.4 EXTENDED OUT OF SERVICE
When the UPS is deactivated for some time, the batteries must be recharged regularly.
They have to be recharged every three months.
• Connect the mains to the UPS.
• Put switch Q1 into position 1.
• Wait for the display to switch on.
• Close the external battery breaker/fuses.
• Put or keep switch Q3 in position 0.
• The battery must be charged for at least ten hours.
• Once ten hours have elapsed, open the external battery breaker/fuses.
• Put switch Q1 into position 0.
8.5 EMERGENCY SHUTDOWN
NOTE! This operations interrupts the supply to the output load from both inverters and automatic bypass.
UPS POWER OFF
System with input and output switches: put Q3 to position 0 when it’s necessary to interrupt the power supply quickly. Refer to figure
1
.
1
REMOTE UPS POWER OFF
It is possible to interrupt the power supply to the output load using the ADC+SL board. Refer to 'Standard features and options' chapter.
42 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 43
9. OPERATING MODES
9.1 ON LINE MODE
A special feature of the UPS is the ONLINE double conversion in conjunction with low distortion mains power absorp­tion. In ON LINE mode, the UPS can supply a voltage that is fully stabilised in frequency and amplitude, regardless of any interference in the mains power supply, within the most stringent classification of UPS regulations.
ONLINE operation provides three operating modes according to mains and load conditions:
Inverter mode
This is the most frequent operating condition: energy is drawn from the primary mains power supply and converted and used by the inverter to generate the output voltage to power the connected loads.
The inverter is constantly synchronised in frequency with the auxiliary mains to enable load transfer (due to an over­load or inverter shutdown) without any break in the power supply to the load.
The battery charger supplies the energy required to maintain or recharge the battery.
Bypass mode
In the event of inverter failure, the load is automatically transferred onto the auxiliary mains without any interruption in the power supply.
This procedure may occur in the following situations:
- in the event of a temporary overload, the inverter continues to power the load. If the condition persists, the UPS output is switched
- on to the auxiliary mains via automatic bypass. Normal operation, which is from the inverter, returns automatically a few seconds after the overload disappears.
- when the voltage generated by the inverter goes outside the limits due to a major overload or a fault on the inverter.
- when the internal temperature exceeds the maximum value allowed.
Battery mode
In the event of a mains failure (micro interruptions or extended power cuts), the UPS continues to power the load using the energy stored in the battery.
9.2 HIGH EFFICIENCY MODE
The UPS has a selectable, programmable economy operating mode (ECO MODE) that can increase overall efficiency by up to 99% for energy saving purposes. If the power supply fails, the UPS will automatically switch onto the inverter and continue to supply power to the load by drawing energy from the battery.
This mode does not provide perfect stability in frequency and voltage like the NORMAL MODE. Therefore the use of this mode should be carefully evaluated according to the level of protection required by the application. With the optional board Net Vision specific daily or weekly time intervals can be selected and programmed to power applica­tions directly from the auxiliary mains.
ECO MODE operation provides very high efficiency, since the application is powered directly from the auxiliary mains via the automatic bypass under normal operating conditions.
To activate follow the correct procedure in the control panel.
9.3 OPERATION WITH MOTOR GENERATOR (GENSET)
The UPS can be operated in conjunction with a generator (GENSET) over the ADC+SL card (refer to 'Standard features and options' chapter). With a generator, the frequency and voltage ranges of the auxiliary mains can be increased to accept the instability of the GENSET and at the same time to avoid operation from the battery or risks of out-of-synchronisation switching on to the bypass.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
43EN
Page 44
10. STANDARD FEATURES AND OPTIONS
Availability
Factory-installed option
Available as option
Not available
Features MODULYS GP Compatibility
Communication Option
ADC+SL card
Temperature sensor
Net Vision card
EMD
Li-ion battery interactivity kit
IOT kit
Mechanical Option
Top air exhausted
Top entry cables
Seismic adaptation kit
Required option
Incompatible option
ADC+SL card
Net Vision card
ADC+SL card
Top entry cables
Top air exhausted
44 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 45
10.1 ADC+SL CARD
The ADC+SL (Advanced Dry Contact + Serial Link) is a slot optional board that provides:
• 4 relays for external device activation (can be set as normally closed or normally open).
• 3 free inputs to report external contacts to UPS.
• 1 connector for external battery temperature sensor (optional).
• RS485 insulated serial link providing MODBUS RTU protocol.
• 2 LEDs indicating board status.
The board is plug&play: the UPS is able to recognise its presence and configuration (up to 4 standard operating modes can be selected by the display) and manages the ADC+SL outputs and the inputs accordingly. It is possible to create a custom operation mode through after sales service.
D
­+
C
IN1-
IN1+
IN2-
IN2+
C1
IN1-
IN1+
IN3-
A
IN3+
NO1
NC1
C3
NO3
B
C2
NO2
C4
NO4
IN1 IN2
IN1- IN1+ IN2- IN2+
IN1- IN1+ IN3- IN3+
IN1 IN3
OUT1 OUT3
C1 NO1 NC1 C3 NO3
C2 NO2 C4 NO4
OUT2 OUT4
KEY
A 3 free inputs to link external contacts to UPS.
B 4 relays for external device activation.
C 1 connector for external temperature sensor.
D RS485 insulated serial link.
NOTE! If the board is removed while operating, an alarm is flagged on the control panel. Perform an “Alarm reset” control to cancel it.
INPUT
• Free voltage loop.
• INx+ has to be connected to INx- to close the loop on XB4 connector.
• Inputs must be isolated with basic insulation from a primary circuit up to 277 V.
• IN1 is duplicated, giving the possibility to link the UPS POWER OFF signal to other equipment, for example.
RELAY OUTPUTS
• Contact voltage guaranteed at 277 V (AC) / 25 V (DC) – 4 A (for higher voltage, please contact the manufacturer).
• Relay 1 gives the possibility of choosing between normally closed (NC1) or normally open (NO1) position. Relays 2, 3 and 4 only have normally open position (NOx).
• On connector XB3, Cx means common, NOx means normally open position.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
45EN
Page 46
STANDARD configuration (default)
IN/OUT DESCRIPTION
IN1 UPS POWER OFF 1 Command sent to UPS
IN2 GEN SET ON 1 Activate S023 status Open to activate Normally close
IN3 INSULATION FAULT 10 Activate A026 Open to activate Normally close
RELAY 1 GENERAL ALARM 10
RELAY 2 OPERATING ON BATTERY 30 Relating to A019 Normally open
RELAY 3
RELAY 4
END OF BACK-UP TIME 10 Relating to A017 Normally open
IMMINENT STOP 10 Relating to A000 Normally open
LOAD SUPPLIED BY AUTO-
MATIC BYPASS
ACTIVATION
DELAY (s)
10 Relating to S002 Normally open
REMARK
(NC1 or NO1 position can be chosen)
Relating to A015
(1)
(2)
INPUT TYPE STATE
Close to activate Normally open
Normally open/close
OPTIONS SUPERVISOR configuration
IN/OUT DESCRIPTION
IN1 UPS POWER OFF 1 Command sent to UPS
IN2 FAN FAILURE 10 Activate A054 Close to activate Normally open
IN3 BATTERY DISCONNECT 10 Activate A016 Open to activate Normally closed
RELAY 1 GENERAL ALARM 10
RELAY 2 OPERATING ON BATTERY 30 Relating to A019 Normally open
RELAY 3 REDUNDANCY LOST 10 Relating to A006 Normally open
RELAY 4 BATTERY DISCONNECTED 1 Relating to A016 Normally open
ACTIVATION
DELAY (s)
REMARK
(NC1 or NO1 position can be chosen)
Relating to A015
(1)
(2)
INPUT TYPE STATE
Close to activate Normally open
Normally open/close
SAFETY configuration
IN/OUT DESCRIPTION
IN1 UPS POWER OFF 1 Command sent to UPS
IN2 INSULATION FAULT 1 Activate A026 Open to activate Normally close
IN3 CHARGER DISABLE/ENABLE 10 Command sent to UPS
RELAY 1 GENERAL ALARM 10
RELAY 2 UPS POWER OFF 1 Relating to A059 Normally open
RELAY 3
RELAY 4 INSULATION FAULT 1 Relating to A026 Normally open
END OF BACK-UP TIME 10 Relating to A017 Normally open
IMMINENT STOP 10 Relating to A000 Normally open
ACTIVATION
DELAY (s)
REMARK
(NC1 or NO1 position can be chosen)
Relating to A015
(1)
(2)
(2)
INPUT TYPE STATE
Close to activate Normally open
Open to activate Normally close
Normally open/close
ENVIRONMENTAL configuration
IN/OUT DESCRIPTION
IN1 UPS POWER OFF 1 Command sent to UPS
IN2 PROGRAMMABLE ALARM 10 Activate A064 Open to activate Normally close
IN3
RELAY 1 GENERAL ALARM 10
RELAY 2
RELAY 3 REDUNDANCY LOST 10 Relating to A006 Normally open
RELAY 4 PROGRAMMABLE ALARM 10 Relating to A064 Normally open
BATTERY TEMPERATURE
ALARM
BATTERY TEMPERATURE
ALARM
ACTIVATION
DELAY (s)
10 Activate A020 Open to activate Normally close
10 Relating to A020 Normally open
REMARK
(NC1 or NO1 position can be chosen)
Relating to A015
1. The acronyms mentioned are linked to MODBUS table (Snnn=Status/Annn=Alarm).
2. A self-locking emergency push button must be used for the UPS Power Off input.
Note: custom configuration is also available. For more information contact Socomec.
(1)
(2)
INPUT TYPE STATE
Close to activate Normally open
Normally open/close
46 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 47
CUSTOM ADC+SL CONFIGURATION FOR REMOTE SIGNAL BOX MANAGEMENT
In addition to the four standard configurations a customized configuration is available to manage the remote SIGNALLING BOX OPTION.
SIGNALLING BOX OPTION configuration
IN/OUT DESCRIPTION
IN1 UPS POWER OFF 1 Command sent to UPS
IN2 NOT USED - -
IN3 NOT USED - -
RELAY 1
RELAY 2 BATTERY DISCHARGING 10 Relating to A019 Normally open
RELAY 3
RELAY 4 NORMAL OPERATION 1 Relating to S000 Normally open
REQUEST TECHNICAL AS-
SISTANCE
END OF BACK-UP TIME
IMMINENT STOP Relating to A000
ACTIVATION
DELAY (s)
1 Relating to a list of technical alarms Normally closed
1
REMARK
Relating to A017
1. The acronyms mentioned are linked to MODBUS table (Snnn=Status/Annn=Alarm).
2. A self-locking emergency push button must be used for the UPS Power Off input.
(1)
(2)
INPUT TYPE STATE
Close to activate Normally open
Normally open
RS485 SERIAL LINK
• Insulated RS485, protected against over voltage. Only for local bus purposes; maximum ~500 m.
• Pull up and pull down line resistor XJ1 (failsafe biasing): jumper open by default.
• Possibility of fixing the RS485 cable to the board.
2
• Cable type required: twister pair cable + shield to connect to ground. (AWG 24, 0.2 mm
for example).
The INPUT and RELAYS are managed with information coming from the UPS.
NOTE! Inputs and relays can be re-programmed depending on requirements. Contact your SOCOMEC after-sales service to change Input/Output programming.
Information coming from inputs can be reported in the UPS database for display on the mimic panel and is accessible on the MODBUS table.
The UPS can manage up to two ADC+SL option cards. The cards can be re-programmed for other uses.
In this specific case, the 2 serial links (SLOT 1 and SLOT 2) are independent.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
47EN
Page 48
MODBUS SERIAL LINK
The RS485 provides MODBUS RTU protocol.
The description of MODBUS addresses and UPS database are described in the MODBUS user manual. All manuals are available on SOCOMEC’s web site (www.socomec.com).
SERIAL LINK SETTINGS
COM1 relates to serial port on board in SLOT 1.
COM2 relates to serial port on board in SLOT 2.
Settings are available via the mimic panel to configure:
• Baud rate: 2400, 9600, 19200.
• Parity: None, Even, Odd.
• MODBUS slave number: 1 to 32.
BOARD STATUS
Board presence is reported through status S064 for slot 1 and S065 for slot 2.
In the case of board failure, ‘Option board alarm’ (A062) occurs to prevent malfunctioning.
10.1.1 TEMPERATURE SENSOR
The temperature sensor can be used to monitor the battery temperature.
The ADC+SL card can be ordered with or without the temperature sensor in kit.
If the sensor is present, temperature values are available on MODBUS protocol at following addresses:
Temperature board
Slot 1 0xn0AF
Slot 2 0xn0AE
1. n = unit number
(1)
(1)
Format ##
Format ##
Temperature range: 0 °C to 40 °C.
48 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 49
10.2 NET VISION CARD
NET VISION is a communication and management inter­face designed for business networks. The UPS behaves exactly like a networked peripheral, it can be managed remotely, and allows the shutdown of network worksta­tions.
NET VISION allows a direct interface between the UPS and LAN network avoiding dependence on the server and support SMTP, SNMP, DHCP and many other protocols. it interacts via the web browser.
10.2.1 EMD
EMD (Environmental Monitoring Device) is a device to be used in conjunction with the NET VISION interface and provides the following features:
- temperature and humidity measurements + dry contact inputs,
010101
- alarm thresholds configurable via Web browser,
- notification of environmental alarm via email and SNMP traps.
1
2
10.3 LI-ION BATTERY INTERACTIVITY KIT
This kit is designed to implement interactive UPS-Li-Ion battery control.
The interactive control system checks and manages all Li-Ion cell parameters (i.e. temperature, voltage, current, charging status, etc.) and dynamically adapt how the UPS operates depending on the status of the Li-Ion battery.
UPS interaction guarantees the most reliable performance and improves system availability by:
• Ensuring proper Li-Ion battery control,
• Preventing any irreversible overcharge failure,
• Performing automatic corrective actions in the event of critical conditions that may affect battery performance.
NOTE! If Li-Ion batteries are connected in parallel, with a multiple BMS setup, the Li-Ion battery option will require a single connection to a concentrator to operate, which acts as the master BMS.
The UPS interface to the Li-ion batteries (LIB), which could be based on a communication protocol or on dry contacts, monitors battery operation for the sole purpose of ensuring overall system service. This UPS battery interface cannot in any way replace safety systems to protect the battery against abuse or improper use, which requires an independent system in compliance with the relevant standards.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
49EN
Page 50
10.4 TOP AIR EXHAUSTED
10.5 TOP ENTRY CABLES
50 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 51
11. PREVENTIVE MAINTENANCE
NOTE! Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
NOTE! Any work carried out on the equipment must be performed by qualified technicians authorised by SOCOMEC.
Routine maintenance carried out annually is recommended in order to provide optimum operating efficiency and avoid equipment downtime.
Maintenance consists of thorough functionality checks on:
- electronic and mechanical parts;
- dust removal;
- battery inspection;
- software updating;
- environmental checks.
11.1 BATTERIES
The condition of the battery is fundamental to UPS operation.
During the operating lifetime of the battery, the UPS stores statistics on the conditions of use of the battery for analy­sis.
Expected battery lifetime is very much dependent on operating conditions:
- number of charging and discharging cycles;
- load rate;
- temperature.
NOTE! Batteries must only be replaced with batteries recommended or sold by the manufacturer. Batteries must only be replaced by qualified technicians.
BEWARE! Used batteries contain harmful substances. Do not open the plastic cover!
NOTE! Used batteries have to be placed in the appropriate containers to avoid leakage acid. They should only be entrusted to a specialist waste disposal company.
11.2 FANS & CAPACITORS
The lifespan of consumable parts such as fans and capacitors (AC and DC) depends on whether or not the use and environmental conditions (premises, usage or load type) are abnormal or harsh for the equipment.
(1)
It is advisable to replace consumables as follows
Consumable part Years
Fan 5 AC and DC capacitor 7
1. Based on operation of the unit according to the manufacturer’s specification.
:
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
51EN
Page 52
12. SAFEGUARDING THE ENVIRONMENT
Do not dispose of electrical appliances with normal waste, use separate collection facilities.
Follow local council waste regulations for proper disposal arrangements to reduce the environmental impact of waste electrical and electronic equipment or contact your local government for information regarding the collection arrange­ments available.
If electrical appliances are disposed of in landfills or dumps, hazardous substances can leak into the groundwater and get into the food chain, damaging health and wellbeing. Depleted batteries are considered as toxic waste. When battery replacement becomes necessary, only give rundown batteries to certified and licensed waste disposal companies. In accordance with local legislation, it is prohibited to dispose of batteries together with other industrial waste or household refuse.
The crossed-out trash bin symbol is placed on this product to encourage users to recycle components and units whenever possible. Please be environmentally responsible and recycle this product through your recy­cling facility at the end of its lifetime.
For any questions regarding the disposal of the product, contact local distributors or retailers.
52 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Page 53
13. TECHNICAL SPECIFICATIONS
Number of modules 1 2 3 4 5
Power kW 25 50 75 100 100
Power kVA 25 50 75 100 100
Input
Input mains voltage 3ph 480 V (+15/-15%) up to -40% @ 50% of nominal load
Input mains frequency Hz 60 +/-10%
Input power factor 0.99
Total harmonic input current distor­tion (THDi)
3% (@: Pn, Resistive load, Mains THDv 1%)
Output
Output voltage (three phase) V 480
Frequency Hz 60
Total output voltage distortion (THDv)
Overload
Overload
(2)
(2)
10 min kW 125
1 min kW 150
% 1% (@ Pn, Resistive load)
% 125% for 10 minutes, 150% for 1 minute
Crest Factor 2.7 3.3
Bypass
Bypass input voltage V Nominal output voltage ±15%
Bypass input frequency Hz 60 +/-2% selectable (±8% if GENSET is used)
Stored energy mode of operation
Number of battery blocks (VRLA) From 18+18 to 24+24
Environmental
Operating temperature °F / °C 32 to 104 °F / 0 to +40 °C
Storage temperature °F / °C 23 to 122 °F / -5 to +50 °C
Relative humidity % 95% condensation-free
Altitude (max) ft 3280 ( 9840 with derating)
Acoustic noise at 1m dBA ≤ 58
Required air capacity CFM 1178
Dissipated power (max) W 5200 @ Pn (3000 @ 56 kW)
Dissipated power (max) BTU/h 17750 @ Pn (10250 @ 56 kW)
Dimensions and Weight
Dimensions (W x D x H) ft / mm 1.97 x 2.92 x 6.48 ft. / 600 x 890 x 1975 mm
Empty cabinet lbs / kg 1043 lbs / 473 kg
UPS module lbs / kg 75 lbs / 34 kg
Bypass module lbs / kg 55 lbs / 25 kg
Battery module lbs / kg -
Standard
Safety UL1778 CSA C22.2 N. 107.3-05
EMC FCC part15 Class A
Performance IEC 62040-3 (VFI-SS-111)
Degree of protection standard NEMA 1 (IP20)
SEISMIC OSHPD Pre-approval (optional)
(1)
(3)(4)
5
1. Pout 50% Sn.
2. Initial Condition Pout 80% Pn.
3. For best battery lifetime the suggested temperature range is 59 °F ÷ 77 °F.
4. According to IEC62040-3.
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
5. Modular battery cabinet.
53EN
Page 54
Page 55
Page 56
Socomec: our innovations supporting your energy performance
10
1
independent manufacturer
3,200
worldwide
Your power management expert
employees
% of sales revenue
dedicated to R&D
400
dedicated to service provision
experts
POWER
SWITCHING
POWER
MONITORING
The specialist for critical applications
q Control, command of LV
facilities
qSafety of persons and assets
q Measurement of electrical
parameters
qEnergy management
A worldwide presence
8
production sites
qFrance (x3) qItaly qTunisia qIndia qChina (x2)
27
q TRSQ@KH@q!DKFHTLq"GHM@q%Q@MBD q&DQL@MXq(MCH@q(S@KXq-DSGDQK@MCR q/NK@MCq1NL@MH@q2HMF@ONQD q2KNUDMH@q2O@HMq2VHSYDQK@MCq3G@HK@MC q3TMHRH@q3TQJDXq4*q42
subsidiaries
POWER
CONVERSION
qEnergy quality qEnergy availability qEnergy storage
EXPERT
SERVICES
q Prevention and repairs qMeasurement and analysis qOptimisation q Consultancy, commissioning
and training
80
countries
where our brand is distributed
HEAD OFFICE
SOCOMEC GROUP
SAS SOCOMEC capital 10 633 100 € R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex Tel. +33 3 88 57 41 41 - Fax -33 3 88 57 78 78 info.scp.isd@socomec.com
www.socomec.com
YOUR DISTRIBUTOR / PARTNER
*IOMMODGPXX09-EN 03*
IOMMODGPXX09-EN 03 02.2019
-NMBNMSQ@BST@KCNBTLDMS¡2NBNLDB2 2 KKQHFGSRQDRDQUDC#NBTLDMSOQHMSDCNMO@ODQEQNLRTRS@HM@AKXL@M@FDCENQDRSR
Loading...