This SOCOMEC continuous power system is guaranteed against any manufacturing or material defects.
The warranty is valid for 12 (twelve) months from the commission date, provided activation is carried out by SOCOMEC personnel or personnel from a support centre authorised by SOCOMEC, and no more than 15 (fifteen) months from being shipped from
SOCOMEC.
The warranty is valid throughout national territory. If the UPS is exported abroad, the warranty will only cover the parts used to repair
defects.
The warranty is valid ex-works and covers labour and parts used to repair the defects.
The warranty shall not apply in the following cases:
• Failure due to unforeseen circumstances or force majeure (lightning, floods, etc.);
• Failure due to negligence or improper use (use outside limits: temperature, humidity, ventilation, electric power supply, applied
load, batteries);
• Insufficient or inappropriate maintenance;
• When maintenance, repairs or modifications have not been carried out by SOCOMEC personnel, or personnel from a support
centre authorised by SOCOMEC.
• If the battery has not been recharged in accordance with the terms indicated on the packaging and in the manual, in the event of
long periods of storage or UPS inactivity.
SOCOMEC may, at its own discretion, opt for the repair of the product or the replacement of faulty or defective parts with new parts,
or with used parts of equivalent quality to new parts with regard to function and performance.
Defective or faulty parts replaced free of charge must to be made available to SOCOMEC, which becomes the sole owner.
Replacement or repair of parts, or any modifications to the product during the warranty period, will not extend the duration of the warranty.
SOCOMEC will not be responsible for damages under any circumstances (including, without limitations, damage for loss of earnings,
interruption of activity, loss of information or other financial losses) arising from the use of the product.
SOCOMEC retains the full and exclusive ownership rights to this document. Only a personal entitlement to use the document for the
application indicated by SOCOMEC is granted to the recipient of this document. The reproduction, modification, distribution of this
document, either partially or wholly and in any manner, is strictly prohibited except upon Socomec’s express prior written consent.
This document is not a specification. SOCOMEC reserves the right to make any changes to the information provided without prior notice.
This user manual specifies installation and maintenance procedures, technical data and safety instructions for SOCOMEC. For
further information visit the Socomec website: www.socomec.com.
NOTE!
Any work carried out on the equipment must be performed by qualified technicians.
NOTE!
Before carrying out any operations on the unit read the installation and operating manual carefully.
Keep this manual safe for future reference.
DANGER!
Failure to observe safety standards could result in fatal accidents or serious injury, and damage equipment or the
environment.
NOTE!
The models are not available for all markets. Contact Socomec for further information.
CAUTION!
If the unit is found to be damaged externally or internally, or any of the accessories are damaged or missing, contact
SOCOMEC. Do not operate the unit if it has suffered a violent mechanical shock of any kind.
NOTE!
Install the unit in accordance with clearances in order to prevent access to handling devices and guarantee sufficient
ventilation (see 'Environmental requirements' chapter).
NOTE!
Only use accessories recommended or sold by the manufacturer.
NOTE!
When the equipment is transferred from a cold to a warm place wait approx. two hours before putting the unit into
operation.
Connect the protective earth (PE) conductor before making any other connections.
The UPS requires three-phase plus neutral input connections (3P+N). The neutral input connection is not required
only in case of input transformer.
The installer is responsible for implementing the backfeed protection with the use of AC input line isolation devices
external to the UPS. Refer to ‘Electrical requirements’ chapter.
DANGER! RISK OF ELECTRIC SHOCK!
Before carrying out any operations on the unit (cleaning and maintenance, connection of appliances, etc.) disconnect all power sources.
DANGER! RISK OF ELECTRIC SHOCK! After disconnecting all power sources wait approx. 5 minutes for the
complete discharge of the unit.
The UPS may be powered from an IT distribution system with a neutral conductor.
WARNING! This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures.
NOTE: any use other than the specified purpose will be considered improper. The manufacturer/supplier shall not
be held responsible for damage resulting from this. Risk and responsibility lies with the system manager.
Note: the product you have chosen is designed for environments that include all commercial, light industry and industrial establishments other than those directly connected to a low-voltage mains that supplies buildings used for residential purposes. In order to
be used for particular “critical applications” such as life support systems, medical applications, commercial transportation, nuclear
facilities or any other application or systems where product failure is likely to cause substantial harms to person or property, the
products may have to be adapted. For such uses we would advise you to contact SOCOMEC beforehand to confirm the ability
of these products to meet the requested level of safety, performance, reliability and compliance with applicable laws, regulations
and specifications.
4
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
1. SAFETY STANDARD
1.1. DESCRIPTION OF THE SYMBOLS
All interior and exterior precautions and warnings on labels and plates on the equipment should be complied with.
ACCUMULATORS ARE HEAVY! USE SUITABLE TRANSPORT AND LIFTING EQUIPMENT TO WORK SAFELY.
DANGER! HIGH VOLTAGE (BLACK/YELLOW)
READ THE USER INSTRUCTIONS CAREFULLY.
READ THE USER MANUAL BEFORE PERFORMING ANY OPERATIONS.
PROTECTIVE EARTH TERMINAL (PE)
BATTERIES AND RELATED PARTS CONTAIN LEAD. LEAD IS DANGEROUS TO HEALTH IF INGESTED. WASH
HANDS AFTER HANDLING!
We advise you to contact SOCOMEC beforehand to confirm the ability of these products to meet the required level of safety, performance, reliability and compliance with applicable laws, regulations and specifications.
ENGLISHENGLISH
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
5
2. ENVIROMENTAL REQUIREMENTS AND HANDLING
NOTE!
Before carrying out any operations on the unit read the Safety standards chapter carefully.
2.1. ENVIRONMENTAL REQUIREMENTS
Install the unit in an equipment room where only skilled technicians have access. The room must be:
• clean and dry;
• of a suitable size;
• free from conductive, inflammable and corrosive items;
• not exposed directly to sunlight.
The floor must support the weight of the unit and guarantee its stability.
The unit is designed for indoor rooms only.
For information regarding ambient temperature, dimensions and weights refer to the Technical specification chapter.
The connections and the UPS breakers need to be accessible from the rear; a space of at least 1.5 meters should be left at the front
of the UPS for maintenance purposes. It is also advisable to ensure that cable connections are sufficiently long and flexible so that
the unit can be extracted during maintenance, if necessary.
A space at least 40 cm must be left at the back for adequate ventilation (see figure 2.1-1 and 2.1-2).
2.1-1
Top view
40 cm
15 cm
UPS
or
BATTERY
CABINET
40 cm
15 cm
UPS
or
BATTERY
CABINET
15 cm
BATTERY
CABINET
1,5 m
40 cm
UPS
or
40 cm
15 cm
UPS
BATTERY
CABINET
free areafree area
15 cm
or
40 cm
15 cm
UPS
1,5 m
15 cm
2.1-2
Front view
≥ 80 cm
UPS
2.2. HANDLING
• The packaging guarantees the stability of the unit during shipping and handling.
• The unit must remain in a vertical position during all shipping and handling operations.
• Ensure that the floor is strong enough to support the weight of the unit.
• Carry the packaged unit as close as possible to the installation site.
The unit MUST be handled by at least two people. The people MUST take position at the sides of the UPS with respect to the
direction of movement.
When moving the unit on even slightly sloping surfaces, use the locking equipment and braking devices to ensure that the unit does
not tip over.
6
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
3. ELECTRICAL INSTALLATION
NOTE!
Before carrying out any operations on the unit read the Safety standards chapter carefully.
3.1. ELECTRICAL REQUIREMENTS
The installation and system must comply with national plant regulations.
The electrical distribution panel must have a sectioning and protection system installed for input and auxiliary mains.
Ensure a type-B RCD (residual current detector) is installed on the mains power switch and that this is inserted upstream of the distribution panel.
Size of input protection devices
Model ratingMagneto-thermal
input
(1)
Magneto-thermal
Aux. Mains
(1)
Differential input
(2)
Battery protection
(kVA)(A)(A)(A)(A)
Single unitSingle unitSelective typeFuse
10 3/125800.550 Gr
15 3/1321000.5100 Gr
20 3/1401250.5100 Gr
10 3/325250.550 Gr
15 3/332320.5100 Gr
20 3/340400.5100 Gr
(3)
ENGLISHENGLISH
Cable core size
Model rating Type of cable
core size
(kVA)mm
Input cable
core size
2
(AWG)mm2 (AWG)mm2 (AWG)
Auxiliary/Output
cable core size
Battery cable
core size
flexible cableflexible cableflexible cable
10 3/1
15 3/1
20 3/1
10 3/3
15 3/3
20 3/3
min6 (AWG10)16 (AWG5)6 (AWG10)
max
(4)
25 (AWG3)25 (AWG3)25 (AWG3)
min6 (AWG10)25 (AWG3)6 (AWG10)
max
(4)
25 (AWG3)25 (AWG3)25 (AWG3)
min10 (AWG7)25 (AWG2)10 (AWG7)
max
(4)
25 (AWG3)25 (AWG3)25 (AWG3)
min6 (AWG10)6 (AWG10)6 (AWG10)
max
(4)
25 (AWG3)25 (AWG3)25 (AWG3)
min6 (AWG10)6 (AWG10)6 (AWG10)
max
(4)
25 (AWG3)25 (AWG3)25 (AWG3)
min10 (AWG7)10 (AWG7)10 (AWG7)
max
(4)
25 (AWG3)25 (AWG3)25 (AWG3)
(1) Recommended magneto-thermal switch: with intervention threshold≥10In (Curve C), it is necessary to use a D curve selective
breaker in case of UPS with transformer. For backfeed protection use a magneto thermal switch with 220 V - 240 V release coil.
(2) Use a single type-B selective (S) breaker installed upstream of the inputs power supply.
(3) Protection on the external battery cabinet. Recommended magneto thermal switch: two poles with intervention threshold = 3 In
suited for DC applications.
(4) Determined by the size of the terminals.
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
7
3. ELECTRICAL INSTALLATION
WARNING!
The UPS is designed for transient overvoltages in category II installations. If the UPS is part of the building’s
electrical circuit, or is likely to be subject to transient overvoltages in category III installations, additional external
protection must be provided, either on the UPS or in the AC power supply network powering the UPS.
WARNING!
As specified in EN62040-3 Attachment 3: Non-linear Load Reference, in the event of three-phase non-linear loads
connected downstream of the UPS, the neutral current on the load can be 1.5 - 2 times higher than the phase
current. This must be considered when estimating the correct size of the output and the auxiliary neutral cables.
WARNING!
Protective earthing conductor (PE) must have sufficient current-carrying capacity. The PE cable core size has to
be chosen according to the PROTECTIVE CURRENT RATING of the earth circuit that depends on the provision
and location of over-current protective devices. We suggest 16 mm2 (AWG4) for ITYS PRO 3/3 version and 25 mm2
(AWG2) for ITYS PRO 3/1 version using the protective devices in the table above.
WARNING!
Do not excede the maximum tightening torque of 2.5 Nm for the terminals.
BACKFEED (BKF) PROTECTION
The UPS protects two power isolation devices against the backfeed of dangerous voltages.
The two power isolation devices are dedicated:
- one for the input line (MAINS SUPPLY);
- one for the auxiliary line (AUX MAINS SUPPLY).
The power isolation devices must be installed externally to the UPS.
3.1-1
Backfeed outputs
XB3XB2
EXTERNAL BACKFEED
NC1
COM1
COM2
NC2
DANGER! RISK OF ELECTRIC SHOCK!
The installer must attach the warning label in order to warn electrical technicians about dangerous backfeed situations (not caused by the UPS).
8
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
The label must be affixed:
• to all primary power isolators installed remotely from the UPS area;
• to all external access points, if present;
• between the isolators and the UPS.
Refer to CEI EN 62040-1 2009-05, paragraph 4.7.3.
3. ELECTRICAL INSTALLATION
3.1-2
Warning label (supplied with the equipment)
Before working on this circuit
- Isolate the Uninterruptible Power System (UPS)
- Then check for Hazardous Voltage between all terminals
including the protective earth
Risk of Voltage Backfeed
3.1-3
Backfeed electrical diagram
L1
L2
L3
N
B
NOTE!
Use a 220-240 V release coil with integrated travel limit contact to pilot the input protection systems. If a trip coil
without an integrated end-of-travel contact is used, add an early auxiliary contact (see figure). Electrical data of
the contacts: 1.6 A 250 Vac.
FunctionConnector nameV OUTInternal fuseDetail
BKF AUXXB2220-240 V rms1.6 A time delay
BKF MAINSXB3220-240 V rms1.6 A time delay
COM 2
COM1
(1). COM1 and COM2 are connected to the neutral.
ENGLISH
(1)
NC2
(1)
NC1
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
9
3. ELECTRICAL INSTALLATION
PROTECTION WITH MAINS AND AUX MAINS CONNECTED SEPARATELY
3.1-4
3/3 models
3.1-5
MAINS
L1
L2
L3
N
AUX MAINS
L11
L21
L31
N1
3/1 models
A
UPS
Key
T1
X10
A Distribution panel
1
L
L2
L3
N
B Trip coil
X10 Mains terminal block
X40 Aux Mains terminal block
T1 Mains BKF power isolation device
T2 Aux Mains BKF power isolation device
B
XB2 Aux Mains BKF connector
XB3 Mains BKF connector
T2
B
X40
BKF
L11
L21
L31
N1
XB3
XB2
Remote switches – rated current
ModelT1 (A)T2 (A)
10 3/32525
15 3/33232
20 3/34040
A
MAINS
T1
L1
L2
L3
N
X10
UPS
1
L
L2
L3
N
Key
A Distribution panel
B Trip coil
X10 Mains terminal block
X40 Aux Mains terminal block
T1 Mains BKF power isolation device
T2 Aux Mains BKF power isolation device
AUX MAINS
L11
N1
B
T2
B
X40
L11
N1
BKF
XB3
XB2
XB2 Aux Mains BKF connector
XB3 Mains BKF connector
Remote switches – rated current
ModelT1 (A)T2 (A)
10 3/12580 (TWO POLES)
15 3/132100 (TWO POLES)
20 3/140125 (TWO POLES)
Activating UPS protection: from mimic panel access the MAIN MENU > SETTINGS > UPS SETTINGS > BACKFEED and set the
BACKFEED TYPE parameter to SEPARATE MAINS.
10
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
3. ELECTRICAL INSTALLATION
PROTECTION WITH MAINS AND AUX MAINS CONNECTED TOGETHER
3.1-6
3/3 models
A
Key
A Distribution panel
B Trip coil
X10 Mains terminal block
T1 Mains BKF power isolation device
XB2 Not connected
XB3 Mains BKF connector
Remote switches – rated current
ModelT1 (A)
10 3/325
L1C
L2C
L3C
NC
T1
B
X10
L1
L2
L3
N
XB3
XB2
15 3/332
20 3/340
Activating UPS protection: from mimic panel access the MAIN MENU > SETTINGS > UPS SETTINGS > BACKFEED and set the
BACKFEED TYPE parameter to COMMON MAINS.
ENGLISH
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
11
4. OVERVIEW
NOTE!
Before carrying out any operations on the unit read the Safety standards chapter carefully.
BLOCK DIAGRAMS
4-1
Mains and Auxiliary mains connected separately
(with external batteries)
4-3
Mains and Auxiliary mains connected separately
(with internal batteries)
4-2
Mains and Auxiliary mains connected in common
(with external batteries)
4-4
Mains and Auxiliary mains connected in common
(with internal batteries)
4-5
Mains and Auxiliary mains connected separately
(with output transformer)
12
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
4-6
Mains and Auxiliary mains connected in common
(with input transformer)
4-7
Transformer-less version without battery inside
4. OVERVIEW
UPS power o (U.P.O.)
Q5 (manual bypass switch)
Q3 (output switch / E.S.D.)
EthernetRS232
Slot 1
Slot 2
Fans
(only 2 fans for 10 kVA version)
Q4 (aux mains switch)
Q1 (mains supply switch)
Terminal connection
(1)
ENGLISH
(1). Only installed on separate mains version.
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
13
4-8
Transformer-less version with battery inside
4. OVERVIEW
EthernetRS232
UPS power o (U.P.O.)
Q5 (manual bypass switch)Q4 (aux mains switch)
Q3 (output switch / E.S.D.)
Slot 1
Slot 2
Fans
(only 2 fans for the 10 kVA version)
Q1 (mains supply switch)
Terminal connection
(1)
Q2 (battery switch)
14
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
4-9
Transformer based version
UPS power o (U.P.O.)
4. OVERVIEW
EthernetRS232
Slot 1
Slot 2
Fans
(only 2 fans for the 10 kVA version)
Q5 (manual bypass switch)Q4 (aux mains switch)
Q3 (output switch / E.S.D.)
Q1 (mains supply switch)
Terminal connection
ENGLISH
(1)
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
15
4-10
Position of the switches
4. OVERVIEW
4-11
Q5 manual bypass switch
124
3
A
Follow the bypass procedure (chapter 8) before removing the bypass switch protection cover (A).
16
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
5. CONNECTIONS
NOTE!
Before carrying out any operations on the unit read the Safety standards chapter carefully.
CABLES WITH ANTI INTRUSION FERRULE
• Remove the protection;
• Remove the pre-cut cable entry slot;
• Loosen the cable gland;
• Cross the cable to the cable gland;
• Carry out all the required connection;
• Once the connection is done, fix the cable gland;
• Insert and fix the cable gland in the protection hole;
• Fix the protection.
5-1
Q5 manual bypass switch
ENGLISH
(1). Only available for separate mains version.
output
AUX input
(1)
mains input
external battery
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
17
5. CONNECTIONS
5.1. MAINS AND AUXILIARY MAINS CONNECTED SEPARATELY (3/3 MODELS)
5.1-1
L12 L22 L32
OUTPUT
Earth Cable terminal characteristic:
tightening torque 3.5-4.5 Nm
N2
X50
M6 screw
L11 L21 L31
AUXILIARY MAINS
X40
N1
L1 L2 L3B
MAINS SUPPLY
X10
N
EXT. BATTERY
B
X20
5.2. MAINS AND AUXILIARY MAINS CONNECTED SEPARATELY (3/1 MODELS)
5.2-1
L12
OUTPUT
N2
X50
L11
AUXILIARY MAINS
X40
N1
L1 L2 L3B
MAINS SUPPLY
X10
N
EXT. BATTERY
B
X20
5.3. MAINS AND AUXILIARY MAINS CONNECTED IN COMMON (3/3 MODELS)
5.3-1
L12 L22 L32
OUTPUT
In case of input trasformer version the mains neutral is not necessary.
18
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
N2
X50
L1 L2 L3B
MAINS SUPPLY
X10
N
EXT. BATTERY
B
X20
5.4. EXTERNAL BATTERY CONNECTION
See chapter 2, 'Environmental requirements'.
For further information refer to the battery cabinet manual.
• Position the battery cabinet next to the UPS.
• Remove the plastic terminal block protection.
• Connect the protective earth (PE) cable.
• Connect the cables between the UPS terminals and the battery cabinet terminals.
WARNING!
Observing strictly:
- the polarity of each individual string (refer to the diagram below);
- the cable cross section (refer to ‘Electrical requirements’ chapter).
WARNING!
Cabling errors with inversion of battery polarity may cause permanent damage to the equipment.
5. CONNECTIONS
ENGLISHENGLISH
• Reassemble the plastic terminal block protection.
5.4-1
UPS
+
NOTE!
When battery cabinets not supplied by Socomec are used the installer is responsible for:
- checking electrical compatibility;
- checking the presence of appropriate protective devices (fuses and switches that ensure the cables are protected
from the UPS to the battery cabinet).
Once the UPS is switched on – before closing the battery switches – check the battery parameters on the mimic
panel menu. For further information, refer to ‘Menu’ chapter.
-
BATTERY CABINET
+B
-B
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
19
6. CONTROL PANEL
6-1
Display
Scrolls up through the available
UP button
menus/values
ESC button
Exits current page, aborts
operations
Luminous status bar
DOWN button
Scrolls down through the
available menus/values
ENTER button
Accesses the currently
displayed menu, accepts/sends
confi gurations and commands
Control panel with LED status bar indicator
ColourDescription
Flashing greenStart-up procedure in progress / Battery test in progress
Flashing green-yellowMaintenance alert / An alarm is present with load supplied by the inverter
YellowOn battery / Forced on bypass (with eco mode off) / Maintenance alert / Redundancy lost
Flashing yellowMaintenance period expired / In maintenance mode / On bypass with an alarm present / Bypass
procedure in progress
Flashing yellow-redA critical alarm occurs / Load supplied / But no longer protected
RedThe load is not supplied due to an alarm
Flashing redStop/shut-down procedure in progress / Output supply switch-off is imminent
Flashing green-yellow-redNo communication with local communication board: no information available
Grey (OFF)Unit off / Unit in standby / Unit off for energy saver / Unit isolated (output breaker open)
KEYPAD LOCK
The keypad can be locked by pressing the buttons in the following sequence:
ESC > UP > DOWN > ENTER
To unlock the keypad the buttons must be pressed in the reverse sequence:
ENTER > DOWN > UP > ESC
These sequences work only on MIMIC PANEL page.
When the keypad is locked the key symbol is shown (see figure below).
20
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
7. MENU
7.1. DISPLAY OVERVIEW
7.1-1
Status bar
Operating mode
ON INVERTER
Unit statusDescription
UPS STARTINGThe start procedure is in progress
UPS STOPPING The stop procedure is in progress
ON MAINT. BYPASSThe manual bypass is active
IMMINENT STOPThe output supplying switch-off is imminent
ON BATTERYThe output load is on battery
BATTERY TESTBattery test in progress
ON INVERTERThe output load is on inverter (normal mode)
ON AUTO BYPASSThe output load is on static bypass
UNIT AVAILABLEEnergy saver is active (inverter is off temporarily)
STANDBYUnit in standby
LOAD OFFThe output load is off
ECO
Unit status
ENGLISH
Functioning modeDescription
SERVThe UPS is on maintenance mode
ISOOutput breaker / output relays open
ECO AUTOEco mode schedule enabled
ECOAn eco mode command has been carried out
STBYA remote stand-by command has been carried out
ENSVThe energy-saver mode has been enabled
<NOTHING DISPLAYED>Normal mode
7.1-2
Mimic panel
N INVERTER
76
5
4321
SEGMENTDESCRIPTION
1INPUT MAINS
2RECTIFIER INPUT
3INVERTER INPUT OR BATTERY OUTPUT
4INVERTER OUTPUT
5UNIT OUTPUT
6OUTPUT FROM STATIC SWITCH
7BYPASS INPUT
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
21
NOTE!
When in converter mode, 6 and 7 are not shown.
Bar styles identify the energy flow:
• solid: enabled
• dotted: disabled
ADDITIONAL ICONS
7.1-3
ON INVERTER
7. MENU
key icon: displayed if the keypad is locked
7.1-4
ON INVERTER
7.1-5
ON INVERTER
General alarm
On maintenance bypass
Bypass mode (or Eco Mode) not possible
22
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
Commissioning Code not inserted or Scheduled
Inspection warning: machine inspection required,
call SOCOMEC support service
7.1-6
O
O
ON INVERTER
7.1-7
Load level
7. MENU
Operating on GenSet
NOTE! Available only with ADC+SL option board.
ENGLISH
N INVERTER
7.1-8
Battery status
N INVERTER
NOTE: Battery symbol is shown only if battery available
Some operations and settings require a password in order to be performed. The default password is SOCO.
7.3-1
Password required
7. MENU
Confi rm password
123
Cancel character
Press UP and DOWN to scroll the letters. Press ENT to confirm the selection or ESC to abort.
ALARMS MENU
This menu displays all pending UPS alarms. Use the ALARMS RESET command in the CONTROLS menu to reset alarms.
STATES MENU
This menu displays all UPS states that are on.
(1)
MEASUREMENTS MENU
This menu displays all UPS measurements relating to the input stage, output stage, batteries and auxiliary mains (bypass).
CONTROLS MENU
This menu contains the commands that can be sent to the UPS. Some of them are password protected. If a command is not available, a COMMAND FAILURE message appears.
• ALARM RESET: this function clears the alarm history
• START/STOP/BYPASS PROCEDURES: see OPERATING PROCEDURES PARAGRAPH
• ECO MODE ON/OFF: this function sets/resets the ECO MODE
• BATTERY TEST: this function checks first if the conditions to do the tests are available, and after it returns the results.
• LED TEST: this function activates the LED blinking for few seconds
(1)
(1)
ENGLISH
SETTINGS MENU
This menu contains all the machine settings. These are the following sub-menus:
• PREFERENCES: user preferences such as language, date and time, buzzer.
To reset the language back to English, press the ESC button for 5 seconds.
• UPS SETTINGS: critical machine settings for output, batteries and backfeed. Some parameters cannot be modified when the
UPS is ON or in converter mode.
Wrong configuration in UPS SETTINGS could damage the load or the batteries.
• CONNECTIVITY: configurations of communication options, Ethernet and serial link.
• SLOT OPTIONS: configurations of available optional boards, which can be mounted on the rear slots.
• U.P.O. CONFIGURATION: refer to the UPS POWER OFF chatper
System critical parameters are password protected and should be modified by specialist personnel only.
(1) Press UP/DOWN to scroll pages.
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
25
7. MENU
BATTERY MENU
This is the menu for battery configuration. The list can be scrolled down to see the full list of battery settings. If batteries are not
available, only the first element of the list is shown. When one of the battery settings is edited, all settings below in the list have to be
checked and confirmed. The battery settings are saved only when the last battery setting is confirmed. To change battery configurations enter the menu: MAIN MENU > SETTINGS > UPS SETTINGS > BATTERIES.
These parameters for battery settings are critical: number of cells, capacity, charge current. Risk of damage to load or batteries.
SERVICE MENU
This menu is reserved for support service personnel and holds UPS identification data and utilities for software upgrades.
COMMISSIONING CODE
To complete equipment activation, a warranty activation code is required. To insert the Commissioning Code go to MAIN MENU >
SERVICE > COMMISSIONING CODE. If the Commissioning Code is not inserted an alert symbol is shown on the mimic panel (
The Commissioning Code is provided directly by the relevant Support Centre upon communication of the serial number. When the
Support Centre is contacted for the Commissioning Code, detailed information can be obtained on the UPS functions available and on
scheduled preventive maintenance programmes.
).
26
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
8. OPERATING PROCEDURES
NOTE!
Before carrying out any operations on the unit read the Safety standards chapter carefully.
NOTE!
While a procedure is being performed, the switches' closing/opening need to be confirmed by pressing the ENTER button.
8-1
Example of procedure step
Request to fulfi ll
ENGLISH
ůŽƐĞĂƩĞƌLJ
NOTE!
For the position of the switches refer to the OVERVIEW chapter.
NOTE!
For the cabling of the UPS refer to the CONNECTION chapter.
Confi rm and go to next step
Abort procedure
8.1. SWITCHING ON
• Supply power to the UPS
• Put switch Q1 into position ON.
• Wait for the display to switch on.
• Enter MAIN MENU > CONTROLS > START PROCEDURE.
• Carry out the operations indicated on the display.
8.2. SWITCHING OFF
This operation interrupts the power supply to the load. The UPS and the battery charger will be shut down.
• Enter MAIN MENU > CONTROLS > STOP PROCEDURE.
• Wait 2 minutes for the UPS shutdown. A countdown shows the remaining seconds.
NOTE!
The controlled shutdown of each server connected to the LAN can be managed by shutdown software.
Refer to the NETVISION chapter.
• Carry out the operations indicated on the display.
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
27
8. OPERATING PROCEDURES
8.3. BYPASS OPERATIONS
NOTE!
For the operation with manual bypass switch (Q5) refer to the OVERVIEW chapter.
SWITCHING ONTO MAINTENANCE BYPASS
This operation creates a direct connection between the UPS input and output, excluding the equipment control part. This operation
is performed to emergency supply the load in the event of:
- standard maintenance
- serious failure has occurred.
WARNING! LOAD POWERED BY BYPASS MAINS!
Your load is exposed to mains disturbances.
• Enter MAIN MENU > CONTROLS > BYPASS PROCEDURE
• Carry out the operations indicated on the display.
NOTE!
When an external manual bypass is present:
- carry out the procedure described above;
- put the external switch to position ON.
SWITCHING ON FROM MAINTENANCE BYPASS
• Put switch Q1 into position ON.
• Wait for the display to switch on.
• Enter MAIN MENU > CONTROLS > START PROCEDURE.
• Carry out the operations indicated on the display.
8.4. OPERATION IN HIGH EFFICIENCY MODE
The UPS makes it possible to select a programmable economy operating mode that can increase overall efficiency up to 98% for
energy saving purposes. If the power supply fails, the UPS will automatically switch onto the inverter and continue to supply power
to the load by drawing energy from the battery. This mode does not provide perfect stability in frequency and voltage like the ON
LINE mode. Thus the use of this mode should be carefully evaluated according to the level of protection required by the application.
Eco Mode operation provides very high efficiency, since the application is powered directly from the auxiliary mains via the automatic
bypass in normal operating conditions.
8.5. OPERATION IN CONVERTER MODE
ITYS PRO can operate as a frequency converter. For such use please contact SOCOMEC.
WARNING!
SOCOMEC recommends using the converter mode only for UPS with separate auxiliary mains and auxiliary mains
disconnected from the power source.
28
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
8. OPERATING PROCEDURES
8.6. EXTENDED 'OUT OF SERVICE'
When the UPS is off for some time, the batteries must be periodically recharged regularly.
They have to be recharged every three months or as requested by the battery supplier.
• Connect the mains and auxiliary mains to the UPS.
• Put switch Q1 into position ON.
• Wait for the display to switch on.
• Enter MAIN MENU > CONTROLS > START PROCEDURE.
• Carry out the operations indicated on the display.
• Be sure that the external battery breaker/fuse are closed.
• Put switch Q3 into position OFF
• The battery must be charged for at least ten hours.
• Once ten hours have elapsed, carry out the Stop procedure to deactivate the UPS.
8.7. EMERGENCY SHUTDOWN (E.S.D.)
Put switch Q3 into position OFF when it’s necessary to interrupt the power supply quickly.
ENGLISH
NOTE!
This operation interrupts the supply to the output load from both inverters and automatic bypass.
If the UPS is operating from the maintenance bypass with the mains present, the emergency shutdown does not
interrupt the power supply to the load.
When an emergency condition occurs, all power supplies upstream of the UPS (also batteries) must be disconnected.
8.8. UPS POWER OFF (U.P.O.)
A Power Off button can be installed outside the unit when it's necessay to interrupt the UPS quickly (see diagrams 4.5 and 4.6 ).
The electrical characteristic of the signal are:
UPS POWER OFF
max cable sectionvoltage (SELV)current
AWG 1615V 5mA
To configure enter MAIN MENU > SETTINGS > UPO CONFIGURATION.
There are three different configuration modes:
• DISABLED (the ‘UPS Power Off’ doesn’t work. Default mode).
• NORMALY CLOSED (the UPS is powered off when the button/switch connected to the UPO is open)
• NORMALY OPEN (the UPS is powered off when the button switch connected to the UPO is closed)
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
29
9. STANDARD FEATURES AND OPTIONS
NOTE!
The features are not available for all markets. Contact Socomec for further information.
FeaturesTypeAvailability
Modbus RTU (RS232)CommunicationAvailable as standard
Modbus TCP (Ethernet)CommunicationAvailable as standard
Standard web pagesCommunicationAvailable as standard
Web firmware updateCommunicationAvailable as standard
ADC + SL cardCommunicationAvailable as option
Net VisionCommunicationAvailable as option
Software optionCommunicationAvailable as option
IP31 option kitMechanicalAvailable as stardand
NOTE!
For slots positions see figures 4-5 and 4-6.
MODBUS
MODBUS is a Master/Slaves protocol, in which the UPS is one of the slaves. The Master sends a request to a slave, the slave sends
the data or an ACK to the Master.
For further information about protocol and UPS mapping visit these websites:
www.socomec.com.
www.modbus.org
MODBUS RTU (RS232)
9-1
RS232 pinout
34521
8976
1 Not connected
2 RX for RS232
3 TX for RS232
4 Not connected
5 GND
6 Not connected
7 Not connected
MODBUS TCP (ETHERNET)
To configure the MODBUS TCP, enter MAIN MENU > SETTINGS > CONNECTIVITY > NETWORK SERVICES.
MODBUS TCP can be configured in three different transmission modes:
• Disabled
• Standard TCP (available at port 502)
• Tunneling (available at port 1025)
30
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
9. STANDARD FEATURES AND OPTIONS
STANDARD WEB PAGES
The UPS can be remotely monitored using an Internet browser
To remotely monitor the UPS, connect the browser to the UPS IP on port 80.
The IP can be found into MAIN MENU > SETTINGS > CONNECTIVITY > NETWORK PARAMETERS > IP ADDRESS.
NOTE!
The web server is a read-only interface, no commands/settings can be sent to the UPS remotely.
To set the network configuration enter SETTINGS > CONNECTIVITY > NETWORK PARAMETERS.
In this menu it’s possible to manage the DHCP and set the static IP address, subnet mask and gateway.
9-2
ITYS PRO
HOME
Alert (0)
States
Measures
Graphs
Information
Log
(1)
.
Language: en | it | fr | de | es | pt | ru | 中文
ON INVERTERNormal
Select your language
Graphical
overview of UPS
working status
ENGLISH
9-3
HOME
Alert (0)
States
Measures
Graphs
Information
Log
UPS general information
Graphs of all values measured (plotted with 5 seconds of refresh period)
UPS information
Download the after-sales UPS history log (hst file)
(1) Tested on Windows 7 with IE 9, Chrome 36, Firefox 24, Safari 5.0 with javascript enabled through a standard Ethernet connection.
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
31
9. STANDARD FEATURES AND OPTIONS
ADC+SL CARD
The ADC+SL (Advanced Dry Contact + Serial Link) is a optional slot board that provides 4 relays for external device activation, 3
free inputs to report external contacts to UPS and one connector for external temperature sensor. There is also an RS485 insulated
serial link that provides MODBUS RTU protocol. A maximum of two cards can be installed on each unit.
This card can be configured to control four outputs and three digital inputs. The first output can be configured as normally open
(NO) or normally closed (NC). The other three outputs are configured as normally open (NO).
Available configurations:
OPTIONS SUPERVISOR
DIP1:ON - DIP2:OFF
IN/OUT DescriptionFilter (s)
In1UPS Power O 1
In2Fan Failure10
In3Battery disconnected10
Out1General Alarm10
Out2Battery Discharging30
Out3Redundancy lost10
Out4Battery disconnected1
ENVIROMENTAL
DIP1:ON - DIP2:ON
IN/OUT DescriptionFilter (s)
In1UPS Power O 1
In2Programmable Alarm10
In3Battery Temperature Alarm10
Out1General Alarm10
Out2Battery Temperature Alarm10
Out3Overload or Redundancy lost10
Out4Programmable Alarm10
SAFETY
DIP1:OFF - DIP2:ON
IN/OUT DescriptionFilter (s)
In1UPS Power O 1
In2Insulation Fault1
In3Charger Disable/Enable1
Out1General Alarm10
Out2UPS Power O activated1
Out3
Out4Insulation Fault (A026)1
Battery Low or Imminent UPS stop alarm
10
NOTE!
For further information refer to the ADC+SL manual.
NET VISION CARD
NET VISION is a communication and management interface designed for business networks. The UPS behaves exactly like a
networked peripheral, it can be managed remotely, and allows the shutdown of network workstations.
NET VISION allows a direct interface between the UPS and LAN network avoiding dependence on the server and support SMTP,
SNMP, DMCP and many other protocols. It interacts via the web browser.
SOFTWARE OPTION
Visit www.socomec.com and enter DOWNLOAD > SOFTWARE > UPS SOFTWARE to find the communication software suitable
for your requirements.
NOTE!
Before making any operation, check that the software is compatible with your UPS model.
32
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
IP31 ROOF
9-4
9. STANDARD FEATURES AND OPTIONS
ENGLISH
NOTE!
For further information, refer to the IP31 assembling instruction.
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
33
10. WEB FIRMWARE UPDATE
• Switch off the UPS or switch the UPS onto maintenance bypass;
• Connect to the Upgrading Web Page through a standard Internet browser (i.e Internet Explorer, Chrome, etc.): using the UPS IP
address at port 55000:
http://UPS_IP_ADDRESS:55000
To get UPS IP address enter MAIN MENU > SETTINGS > CONNECTIVITY > NETWORK PARAMETERS > IP ADDRESS.
• Wait until the Upgrading Web Page shows you the UPS firmware versions
10-1
• Press ‘HERE’ button to start the upgrade procedure
10-2
• Wait until the flash memory has been reset.
10-3
34
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
10. WEB FIRMWARE UPDATE
• Select the firmware package (filename.pkg) and press ‘SEND’ button to start programming.
10-4
• Wait until the firmware package has been uploaded.
10-5
ENGLISH
• Wait until all the firmware items in the table have been upgraded (Finished OK)
Once the upgrading procedure has been completed the Communication board will be reset, so you will lose the ethernet communication.
•
In case of DHCP enabled, IP address may change; check the UPS IP address again.
NOTE!
Visit us at www.socomec.com for more info.
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
35
11. MAINTENANCE
NOTE!
Before carrying out any operations on the unit read the Safety standards chapter carefully.
NOTE!
Any work carried out on the equipment must be performed by qualified technicians authorised by SOCOMEC.
Routine maintenance carried out annually is recommended in order to provide optimum operating efficiency and avoid equipment
downtime.
Maintenance consists of thorough functionality checks on:
- electronic and mechanical parts;
- dust removal;
- battery inspection;
- software updating;
- environmental checks.
BATTERIES
The condition of the battery is fundamental to UPS operation.
During the operating lifetime of the battery, the UPS stores statistics on the conditions of use of the battery for analysis.
The expected life time of the batteries is very much dependent on operating conditions:
- number of charging and discharging cycles;
- load rate;
- temperature.
NOTE!
Batteries must only be replaced with batteries recommended or sold by the manufacturer. Batteries must only be
replaced by qualified technicians.
BEWARE!
Used batteries contain harmful substances. Do not open the plastic cover!
NOTE!
Used batteries must be placed in the appropriate containers to avoid leakage acid.
They should only be entrusted to a specialist waste disposal company.
FANS & CAPACITORS
The lifespan of consumable parts such as fans and capacitors (AC and DC) depends on whether or not the use and environmental
conditions (premises, usage or load type) are abnormal or harsh for the equipment.
It is advisable to replace consumables as follows
Consumable partYears
Fan5
DC capacitor10
AC capacitor10
(1). Based on operation of the unit according to the manufacturer’s specification.
(1)
:
36
ITYS PRO 10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
12. TROUBLESHOOTING
For other alarms that may appear please contact Service.
AlarmNameDescription
A000Imminent StopAn imminent stop is about to happen. In two minutes the UPS will be shut down.
This can be provoked by a critical alarm or a user request.
A001UPS overloadThe load is exceeding the UPS power specification. The machine will turn off.
Reduce the load immediately.
A003Transfer locked The UPS is unable to transfer the load between bypass and inverter.
A004Transfer impossibleBypass is not available.
A008Eco mode disabled by UPSEco mode is disabled due to bypass failure.