socomec ITYS 10 kVA, ITYS 20 kVA, ITYS 10LB kVA, ITYS 20LB kVA Installation And Operating Manual

Page 1
ITYS
10-20 kVA
安装及操作手册
CN
Installations- und bedienungsanleitung
DE
Installation and operating manual
Manual de instalación y uso
ES
Manuel d’installation et d’utilisation
FR
Manuale di installazione e uso
IT
Page 2
2
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
This SOCOMEC appliance is guaranteed against manufacturing and material defects for a period of 12 months from the date of purchase (local warranty conditions are applicable in addition to the general conditions). This warranty certificate should NOT be e-mailed, but kept by the customer along with proof of purchase, for use in the event of a claim being made for repairs or repla­cement under warranty.
The warranty period commences on the date the new product was purchased by the end user at an authorised showroom (refe­rence details are shown on the receipt).
Return-to-base warranty is provided: components and labour for repairs supplied free of charge, any products to be replaced must be returned to SOCOMEC or authorised service centres, at the customer’s own risk and expense.
The warranty valid throughout national territory. If the UPS is exported abroad, the warranty shall be limited to the cover of the parts used to repair the fault.
To claim service under the warranty please observe the following:
• The product must be returned in the original packing. Any damage caused during shipping in packaging other than the original will not be covered by the warranty;
• The product must be accompanied by proof of purchase such as an invoice or receipt indicating the date of purchase and product ID information (model, serial number). The sender must also attach the reference number issued to authorise the return of the product, together with a detailed description of the defect. If any of this information is missing the warranty will be invalid. The authorisation number is issued by service centres over the telephone on receiving information on the malfunction in question;
• If it is not possible to provide proof of purchase the serial number and date of manufacture will be used to calculate the probable expiry date of the warranty; this could result in a reduction of the original warranty period.
The warranty on the product does not cover damage caused by carelessness (improper use: wrong input power, explosions, excessive humidity, temperature, poor ventilation, etc.), tampering or any unauthorised repair work.
During the warranty period, SOCOMEC reserves the right to decide whether the product should be repaired, or whether to replace defective parts with new parts, or used parts that are equivalent to new parts in terms of functionality and performance.
In the case of batteries, warranty is valid only if the battery has been recharged regularly in accordance with the manufacturer’s instructions. On purchasing the product it is advisable to check that the next recharge date indicated on the packaging has not expired.
Battery
• Batteries are treated as consumable parts and warranty only covers manufacturing defects.
• Batteries must be stored in compliance with Supplier recommendations.
• Warranty is valid only if the battery has been recharged regularly in accordance with the manufacturer’s instructions. On purchasing the product it is advisable to check that the next recharge date indicated on the packaging has not expired.
Optionals
A 12-month return-to-base warranty is provided on optionals.
Software products
Software products are guaranteed for 90 days. The software is guaranteed to work as indicated in the manual accompanying the product. Hardware media or accessories (e.g. diskettes, cables, etc.) used with appliances are guaranteed free of material or manufacturing defects under normal conditions of use for a period of 12 months from the date of purchase.
SOCOMEC will not be responsible for damages (including loss of income, interruption of business activity, loss of information or other financial losses of any nature) arising from the use of the product.
These conditions are subject to Italian law. Disputes shall come under the jurisdiction of the Court of Vicenza.
WARRANTY CERTIFICATE AND CONDITIONS
SOCOMEC retains the full and exclusive ownership rights over this document. Only a personal entitlement to use the document for the application indicated by SOCOMEC is granted to the recipient of the document. The reproduction, modification, distribution of this document either partially or completely and in any way are expressly prohibited except upon Socomec’s express prior written consent.
This document is not a specification. SOCOMEC reserves the right to make any changes to information without prior notice.
Page 3
3
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
TABLE OF CONTENTS
ENGLISH
1. SAFETY STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1. DESCRIPTION OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2. BACKFEED PROTECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1. SHIPPING AND MOVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2. ENVIRONMENTAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3. NOTES FOR INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3. ELECTRICAL REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4. REAR VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5. CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1. OPERATION IN HIGH EFFICIENCY MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2. OPERATION IN CONVERTER MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6. MIMIC PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7. OPERATING MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.1. SWITCHING THE ITYS ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.2. SWITCHING THE ITYS OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.3. OPERATING MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.4. MENU TREE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8. COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.1. RS232 INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.2. USB INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.3. INTELLIGENT SLOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.4. AUX SLOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9. TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
10. TECHNICAL SPECIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Page 4
4
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
1. SAFETY STANDARDS
• This document describes the procedures for the installation, maintenance, technical specifications and safe use of this SOCOMEC unit. For further information visit the SOCOMEC website www.socomec.com.
Any work carried out on the equipment must be performed by qualified technicians authorised by SOCOMEC.
Failure to observe safety standards could result in fatal accidents or serious injury, and damage equipment or the environment.
Read the user manual before performing any operations. Keep this manual safe for future reference.
Connect the PE ground conductor first before making any other connections.
WARNING!
RISK OF ELECTRIC SHOCK!
After the unit is disconnected from the mains power supply components inside the UPS are still connected to the battery, which are potentially dangerous.
• Do not expose the unit to rain or liquids in general. Do not insert foreign bodies.
• Do not block ventilation.
• Do not connect any kind of equipment to the UPS output which may overload it.
• Place cables in such a way that no one can step on or trip over them.
• The UPS must be connected to earth and the battery cabinet must be connected to the same earth as the UPS.
• An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation.
• An appropriate disconnection device such as short-circuit backup protection should be provided in the building wiring installation.
• For three-phase equipment connection to an IT power system, a four-pole device which disconnects all phase conductors and the neutral conductor should be provided in the building wiring installation.
• High electrical voltages are generated inside the power system, which is dangerous for maintenance personnel not suitably qualified or trained for such work.
• Do not interfere with the disconnection switches on the unit while the UPS is operating.
• Before carring out any operations ensure the UPS has been shut down completely and disconnected.
There is no insulation between the batteries and the mains supply therefore it is extremely dangerous to touch any part of the accumulator battery.
Do not interfere with the disconnecting switches on the unit while the UPS is operating on battery power.
• Batteries must only be replaced with batteries recommended or sold by the manufacturer. Batteries must only be replaced by qualified technicians.
• The batteries are toxic waste. If they are replaced send used batteries to local specialist disposal companies only.
• If the unit needs to be disposed of it should only be entrusted to a specialist waste disposal company.
The product you have chosen is designed for commercial and industrial use only.
Products may have to be adapted for particular critical applications such as life support systems, medical applications, commercial transportation, nuclear facilities or any other application or systems where product failure is likely to cause substantial harm to people or property.
For such use it is advisable to contact SOCOMEC beforehand to confirm the ability of these products to meet the required level of safety, performance, reliability and compliance with applicable laws, regulations and specifications.
Page 5
5
ENGLISH
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
1. SAFETY STANDARDS
1.1. DESCRIPTION OF SYMBOLS
Accumulators are heavy! Use suitable transport and lifting equipment to work safely.
Connecting accumulators in series creates hazar­dous voltages.
The electrolyte corrodes metals and burns the skin and all parts of the human body.
WARNING! Risk of explosion! Avoid short circuits! Never place tools or metal objects on the accumula­tors.
Batteries and related parts contain lead. Lead is dangerous to health if ingested. Wash hands after handling!
Wear safety goggles and suitable clothing.
Read the user instructions carefully. Read the user manual before performing any opera­tions.
Wear protective gloves and clothing.
Ground terminal.
In the event of contact with the eyes, wash imme­diately with plenty water and call a doctor. Call a doctor immediately in the event of accidents or illness.
The unit MUST be handled by at least two people.
1.2. BACKFEED PROTECTION
If the UPS does not have an automatic protection device against current backfeed, the operator/installer must:
- attach
warning labels to all the mains power disconnection switches installed at a distance from the UPS area; this serves to remind
technicians of the fact that the circuit is connected to a UPS.
ISOLATE THE UPS BEFORE
OPERATING ON THIS CIRCUIT
B
L
Q1
T1
L1
Output/L
Output/N
Backfeed terminal
AUX Mains T.B
Mains T.B
L2
L3
N
F
N
B
Q
T
F
Legend B Coil F 2A slow blow fuse Q Magneto-thermal input main switch Q1 Magneto-thermal input aux main switch T 30 A AC1 remote contactor 4-pole; 230 V coil T 1 90 A AC1 remote contactor 2-pole; 230 V coil
External distribution panel
UPS
B
L
Q1
T1
L1
Output/L
Output/N
Backfeed terminal
AUX Mains T.B
Mains T.B
N
F
N
B
Q
T
F
Legend B Coil F 2A slow blow fuse Q Magneto-thermal input main switch Q1 Magneto-thermal input aux main switch T 30 A AC1 remote contactor 4-pole; 230 V coil T 1 90 A AC1 remote contactor 2-pole; 230 V coil
External distribution panel
UPS
- install an external isolating device as shown in the figure.
Page 6
6
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
2. INSTALLATION
2.1. SHIPPING AND MOVING
• The packaging guarantees the stability of the unit during shipping and physical transfer.
• The unit must remain in a vertical position during all shipping and moving operations.
• Ensure that the fl oor is strong enough to support the weight of the unit.
• Carry the packaged unit as close as possible to the installation site.
WARNING! HEAVY WEIGHT! Move the unit using a forklift truck taking the utmost care at all times.
The unit MUST be handled by at least two people.
Do not move the unit by putting pressure on the front door.
When moving the unit on even slightly sloping surfaces, use the locking equipment and braking devices to ensure that the unit does not fall over.
WARN
ING!
RISK OF ELECT
RIC SHOCK!
When the equipment is transferred from a cold to a warm place wait approx. two hours after unpacking before Installing the unit and putting it into operation.
CAUTION IF DAMAGED. If the unit is found to be damaged externally or internally, or any of the accessories are damaged or missing, contact SOCOMEC.
All packaging material must be recycled in compliance with the laws in force in the country where the system is installed.
2.2. ENVIRONMENTAL REQUIREMENTS
Install the unit in a technical room to which only skilled technicians have access. The room must be:
• of a suitable size;
• clean and dry;
• free from infl ammable items;
• maintained at a temperature between 0 and 40 °C.
The unit is not designed for outdoor use. Do not expose the unit to direct sunlight.
See TECHNICAL SPECIFICATIONS.
Page 7
7
ENGLISH
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
2.3-1
2.3. NOTES FOR INSTALLATION
Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least 0.5 m of space on each side.
Once the installation is completed, the side mounting brackets (used in shipping) shall be fixed back to ensure the stability of the UPS enclosure. If this is not possible, additional stability can be added by anchoring the assembly brackets to the floor with M8 bolts.
386 mm
8 mm diamete
r
(4 places)
320 mm
2. INSTALLATION
Page 8
8
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
3. ELECTRICAL REQUIREMENTS
The installation and system must comply with national plant regulations. The electrical distribution panel must have a protection and sectioning system installed for the input mains and auxiliary mains. If a differential switch is installed on the mains power switch (optional) it must be inserted upstream from the distribution panel.
The table below shows the size of the input protection devices recommended for correct installation.
Size of input protection devices
Model rating
Magneto-thermal
Input
Magneto-thermal
Aux. Mains
Differential input
Input mains cable
core size
Input mains fuse
Aux mains
cable core size
Output
cable core size
Battery cable
core size
Protective Earthing
conductor
Battery protection
Torque for fixing
above terminals
(kVA) (A) (A) (A) (mm2) (mm2) (mm2) (mm2) (mm2) (A) Lb in
single single selective type min max min max min max min max max
10
1/1
63 A
250 VAC
63 A
250 VAC
0.5 A 10 13
30 A
250 VAC
10 13 10 13 10 13 13 50 10
10
3/1
40 A
250 VAC
63 A
250 VAC
0.5 A 2.5 4
30 A
250 VAC
10 13 10 13 10 13 13 50 10
20
1/1
100 A
250 VAC
100 A
250 VAC
0.5 A 21 25
50 A
690 VAC
21 25 21 25 21 25 25 100 18
20
3/1
60 A
250 VAC
100 A
250 VAC
0.5 A 6 10
50 A
690 VAC
21 25 21 25 21 25 25 100 18
Page 9
9
ENGLISH
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
4. REAR VIEW
AUX slot
Neutral switch cover
Manual bypass
Input and output terminal board
ITYS 10 kVA
RS232 serial connector USB serial port
Slot for optional communication boards
Fans
Input breakers
Backfeed cover
EPO (Emergency Power Off)
Page 10
10
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
4. REAR VIEW
Fans Fans
ITYS 20 kVA
Slot for optional communication boards
Neutral switch cover
Manual bypass
Input and output terminal board
RS232 serial connector USB serial port
AUX slot
Input breakers
Backfeed cover
EPO (Emergency Power Off)
Page 11
11
ENGLISH
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
5. CONNECTIONS
The installation and the system must comply with national plant regulations. If a di erential switch is installed on the mains power switch (optional) it must be inserted upstream from the distribution panel.
CAUTION! Use selective differentials. Any current dispersed by the loads will be summed to that of the UPS. The differential protection must be regulated in cases of loads with high current dispersion.
NA N L + - NL
L3 NL1 L2 LN LN JP1 JP2
MAINS
MAINS
AUX MAINS
AUX MAINS
OUTPUT
OUTPUT
UPS
Mains Output
ø UPS ø
(mm²) (mm²)
≥ 10 10 kVA ≥ 10 ≥ 21 20 kVA ≥ 21
5-2
5-1
5-4
ITYS B model
5-3
L3NL1 L2 L N L N JP1 JP2 + -
MAINS
MAINS
AUX MAINS
AUX MAINS
OUTPUT
OUTPUT
BATTERY
BATTERY
5-4
ITYS LB model
Page 12
12
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
5. CONNECTIONS
5.1. OPERATION IN HIGH EFFICIENCY MODE
The UPS has a selectable, programmable economy operating mode that can increase overall efficiency by up to 98% for energy saving purposes. With this mode of operation, specific daily or weekly time intervals can be selected and programmed to power the applications directly from the auxiliary mains. If there is a power cut the UPS will automatically switch onto the inverter and continue to supply power to the load by drawing energy from the battery.
This mode does not provide perfect stability in frequency and voltage like the ON LINE mode. Thus the use of this mode should be carefully evaluated according to the level of protection required by the application.
5.2. OPERATION IN CONVERTER MODE
In converter mode the UPS can supply a fully stabilised sinusoidal output voltage with a different frequency from the input power line (50Hz or 60Hz is available as output frequency value).
IMPORTANT! Only set this mode on UPS units with the mains power (MAINS) and auxiliary mains (AUX MAINS) separate, and with the auxiliary mains (AUX MAINS) disconnected! Do not set this mode on UPS units with common mains lines as it could damage the load!
All cables must be securely connected.
L3 NL1 L2 LN LN JP1 JP2 + -
5-7
5-8
UPS input UPS input
External distribution panel
L1
N
Q
L1
L2
L3
N
Q1
5-5
Sigle phase connection
5-6
Three phase connection
External distribution panel
Page 13
13
ENGLISH
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
6. MIMIC PANEL
Normal mode
(green)
Fault (red)
Battery (yellow)
Bypass mode
(yellow)
ON/OFF
Up/Exit
1
Enter
Down
Bypass
Inverter
Input
Battery status
Output Load
Output load
Alert icon
1. Press for 1 second
Page 14
14
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
7. OPERATING MODES
7.1. SWITCHING THE ITYS ON
7.2. SWITCHING THE ITYS OFF
7.1-3
5 sec
7.1-4 7.1-5
7.2-2
7.2-1
5 sec
7.2-6
7.2-5
Wait for complete shutdown.
7.1-1
7.1-2
7.2-4
7.2-3
Page 15
15
ENGLISH
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
7.3. OPERATING MODES
7.3-1
Line mode
7.3-3
UPS OFF
7.3-6
Manual Bypass
7.3-2
Battery mode
7.3-4
HE mode
7.3-5
Converter Mode
7. OPERATING MODES
7.4. MENU TREE
FIRST LEVEL SECOND LEVEL THIRD LEVEL
UPS STATUS
EVENT LOG OUTPUT OVERLOAD
UTILITY ABNORMAL
OVER CHARGER
MEASUREMENTS OUTPUT
TEMPERATURE
DC BUS
BATTERY
BYPASS INPUT
LINE INPUT
CONTROL BUZZER MUTE Buzzer Mute: no
SINGLE UPS BATTERY TEST Status: battery test OK
Schedule battery test: no
CLEAR EPO STATUS Status EPO active
Clear: no
RESET FAULT STATUS Status: Fault active
Reset fault: no
CLEAR EVENT LOG Total events: 30
Clear event log: no
RESTORE FACTORY SETTINGS Reset: no
Page 16
16
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
7. OPERATING MODES
FIRST LEVEL SECOND LEVEL THIRD LEVEL
IDENTIFICATION TYPE/MODEL
SERIAL NUMBER
UPS FIRMWARE
SETTINGS USER PASSWORD enabled/disabled
AUDIO ALARM enabled/disabled
OUTPUT VOLTAGE 208/220/230/240 V
OUTPUT FREQUENCY autosensing 50/60 Hz
POWER STRATEGY normal/high e ciency/ converter
DC START enabled/disabled
AUTOMATIC BATTERY TEST PERIOD 0 to 31days
AUTO RESTART enabled/disabled
AUTOMATIC OVERLOAD RESTART enabled/disabled
AUTO BYPASS enabled/disabled
SHORT CIRCUIT CLEARANCE enabled/disabled
BYPASS VOLTAGE LOW LIMIT 110 to 215 V
BYPASS VOLTAGE HIGH LIMIT 245 to 276 V
BYPASS FREQUENCY LOW LIMIT 1 to 10 %
BYPASS FREQUENCY HIGH LIMIT 1 to 10 %
HE VOLTAGE LOW LIMIT 1 to 10 %
HE VOLTAGE HIGH LIMIT 1 to 10 %
HE FREQUENCY LOW LIMIT 1 to 10 %
HE FREQUENCY HIGH LIMIT 1 to 10 %
EXTERNAL BATTERY MODULE 0-4
SET RUNNING TIME Day:hour:minute:second
0000:0000:00~9999:23:59:59
LCD CONTRAST -5 to +5
Page 17
17
ENGLISH
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
8. COMMUNICATION
Communication software and accessories are available for monitoring UPS status, with the aim of optimising normal operation and ensuring that shutdown at the end of backup time is managed correctly. Applications allow recording of all power outages and any depletion of battery power so as to enable the activation of an automatic procedure for closing programs in an ordered sequence and shutting down the system.
ITYS no-break systems are equipped with an RS232 serial communication interface and slots for NetVision cards.
8.1. RS232 INTERFACE
Communication with the server can take place directly via the RS232 interface.
In addition to local or networked shutdown it is possible to perform full monitoring of the electrical parameters regarding battery status and the automatic programming of UPS start-up and shutdown procedures.
For a complete description of software features refer to the UniVision and UniVision Pro documentation.
8.2. USB INTERFACE
The UPS can communicate with the server direct by way of the USB interface, if available on the computer operating system, without the need to install any additional software. Once connected, recognition of the UPS occurs in the same way as for any other peripheral, and the operating parameters can be managed by way of the OS service menu. Use the connecting cable provided.
8.3. INTELLIGENT SLOT
This UPS series is equipped with intelligent slot for Net Vision (optional accessory) or other optional card to remotely manage the UPS through internet / intranet. Please contact your local distributor for further information.
8.4. AUX SLOT
This UPS series is equipped with auxiliary slot for dry contact interface. Optional card (available for insertion in the slot) which is able to handle isolated contact signals to remote relay UPS status information.
Please contact your local distributor for details.
Page 18
18
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
If the UPS system does not operate correctly use the table below to try and solve the problem.
Please have the following information at hand before calling the After-Sales Service Department:
• Model number, serial number
• Date on which the problem occurred
• LCD display status, alarm buzzer status
• Utility power condition, load type and capacity, ambient temperature, ventilation conditions
• The information (battery capacity, quantity) of external battery pack if the UPS is an S model
• Other information for a complete description of the problem
IMPORTANT! If problems persist or recur frequently after following the instructions in this chapter call the technical service centre providing a full description of the problem.
Alert code Problem Possible cause Solution
Warning 11 Battery Disconnected Battery pack is not connected
correctly
Do the battery test to confirm.
Check the battery bank is connected to the UPS.
Check the battery breaker is turned on.
Warning 12 Battery low Battery voltage is low When alarm sounds every second battery is
almost empty.
Warning 14 Over Charge Battery is over charged The UPS will turn off the charger until the battery
voltage is normal
Warning 15 Charger Failure Charging fails Consult dealer
Fault 21 Bus Over Voltage UPS internal fault Consult dealer.
Fault 22 Bus Under Voltage UPS internal fault Consult dealer.
Fault 23 Bus Unbalance UPS internal fault Consult dealer.
Fault 24 Bus short UPS internal fault Consult dealer.
Fault 25 Bus Softstart Fail UPS internal fault Consult dealer.
Fault 31 Output Short Circuit Output short circuit Remove all the loads. Turn off the UPS.
Check if UPS output and loads have short­circuited. Ensure short circuit is removed before turning on again.
Fault 32 Inv Over Voltage UPS internal fault Consult dealer.
Fault 33 Inv Under Voltage UPS internal fault Consult dealer.
Fault 34 Inv Softstart Fail UPS internal fault Consult dealer.
Warning 41 Output Overload Overload Check the loads and remove some non-critical
loads.
Check if some loads have failed.
Fault 42 Inv Overload Fault Overload Check the loads and remove some non-critical
loads. Check if some loads have failed.
Fault 43 Byp Overload Fault Overload Check the loads and remove some non-critical
loads. Check if some loads have failed.
Warning 71 Epo Active EPO connector is open Check the EPO connector status
Warning 72 On Maintain Bypass Maintain bypass switch is
open
Check the maintain bypass switch status
Fault 81 Heatsink Over Temperature
Fault
Internal UPS temperature too high
Make sure the UPS is not overloaded; the air vents are not blocked and the ambient temperature is not too high. Wait for 10 minutes for the UPS to cool down before turning on again. If fails, please contact the distributor or service centre.
Warning 84 Fan Failure Fan abnormal Check the fan is running normally.
9. TROUBLESHOOTING
Page 19
19
ENGLISH
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
10. TROUBLESHOOTING
Alert code Problem Possible cause Solution
Warning 86 Heatsink Over Temperature Internal UPS temperature of
UPS too high
Check the ventilation of the UPS and ambient temperature.
Warning 92 Model Pin Error UPS internal fault Consult dealer.
Fault 93 Backfeeder UPS internal fault Don’t touch any terminal of equipment which
connects utility power with the UPS even if you cut off the utility power. Please consult dealer.
Fault E1 Negative Power Fault
The load is pure inductive and capacitive
Remove some non-critical loads. Bypass supplies the load fi rst, ensure there is no overload, then turn on UPS.
Other - No indication, no warning
tone even though system is connected to mains power supply
No input voltage Check the building wiring and input cable.
Check if the input breaker is closed.
Other -
BYPASS LED lights up even though the power supply is available
Inverter not switched on Press On-Switch 'I' to turn on UPS.
Other - BATTERY LED lights up,
and alarm sounds every 4 seconds
Input voltage and/or frequency are out of tolerance
Check input power source. Check the building wiring and input cable. Check if the input breaker is closed.
Other - Emergency supply period
shorter than nominal value
Batteries not fully charged / battery defect
Charge the batteries for at least 12 hours and then check capacity.
Page 20
20
ITYS 10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
10. TECHNICAL SPECIFICATION
Models
KVA 10 10 (LB) 20 20 (LB)
Nominal Power
VA/W
10000/9000 20000/18000
Input/Output phases 3/1 or 1/1
Electrical Specifications - Input
Mains voltage (Vin) Vin (110-276) VAC (Depends on Load Level) 3Ph+1N+PE,
Bypass input Voltage(Vin) Vbp 220 V 1Ph+N
Input frequency Hz 50-60 Hz ±10%
Input power factor > 0.99 (@Full load)
THDI < 5% with full load
Electrical Specifications - Output
Output Voltage V 208/220/230/240 V
(If output voltage is set at 200 V output power will derate to 90% of power rating)
Output Current A 45/48.1/45.5/43.5/41.7 90/96.2/90.9/87.0/83.3
Frequrency Hz 50-60 ±10% in normal mode
50-60 ±0.1% in battery mode
Overload – Normal Mode (@ 25°C)
10 m 1 m 10 s 100 ms
kW
105% to 110% 110% to 130% 130% to 150%
> 150%
Voltage distortion <5% Non Linear Load; <2% Linear Load
Electrical Specifications - Battery
Type
Sealed lead acid maintenance free-expected lifetime 3-5 years
Voltage
V 280
BUT
2
min 12 - 12 -
Charger
A-4-4
Environment
Operating temperature °C 0 to 45
1
Relative humidity % 0 to 95 No Condensing
Max. altitude m < 1000 without derating
Acoustic noise dBA 55 at front 1 m
Standards
Safety EN 62040-1
EMC EN 62040-2 C3
Product Certification CE
Protection Level IP20
Mechanical Characteristics
Dimensions (W x D x H) mm 350 x 650 x 890
Weight kg 48 128 58 188
1. 15-25 °C for longer battery lifetime.
2. Back-up time @75 % of rated load (models with internal batteries) PF 0.7
Page 21
Page 22
www.socomec.com
HEAD OFFICE
SOCOMEC GROUP
S.A. SOCOMEC capital 10 816 800€ R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE Tel. +33 3 88 57 41 41 Fax +33 3 88 74 08 00 info.scp.isd@socomec.com
Socomec worldwide
BELGIUM
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +32 2 340 02 30 Fax +32 2 346 28 99 info.be@socomec.com
FRANCE
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +33 1 45 14 63 00 Fax +33 1 48 67 31 12 dcm.ups.fr@socomec.com
GERMANY
Power Control & Energy Efficiency
Tel. +49 7243 65292 0 Fax +49 7243 65292 13 info.scp.de@socomec.com
UPS
Tel. +49 621 71 68 40 Fax +49 621 71 68 444 info.ups.de@socomec.com
ITALY
Power Control & Energy Efficiency
Tel.+39 02 98 49 821 Fax +39 02 98 24 33 10 info.scp.it@socomec.com
Solar
Tel. +39 0444 598611 Fax +39 0444 598627 info.solar.it@socomec.com
UPS
Tel.+39 02 98 242 942 Fax +39 02 98 240 723 info.ups.it@socomec.com
NETHERLANDS
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +31 30 760 0900 Fax +31 30 637 2166 info.nl@socomec.com
POLAND
Power Control & Energy Efficiency
Tel. +48 91 442 64 11 Fax +48 91 442 64 19 info.scp.pl@socomec.com
UPS
Tel. +48 22 825 73 60 Fax. +48 22 825 73 60 info.ups.pl@socomec.com
PORTUGAL
UPS / Solar
Tel.+351 261 812 599 Fax +351 261 812 570 info.ups.pt@socomec.com
ROMANIA
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +40 21 319 36 88 Fax +40 21 319 36 89 info.ro@socomec.com
RUSSIA
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +7 495 775 19 85 Fax +7 495 775 19 85 info.ru@socomec.com
SLOVENIA
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +386 1 5807 860 Fax +386 1 561 11 73 info.si@socomec.com
SPAIN
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +34 93 540 75 75 Fax +34 93 540 75 76 info.es@socomec.com
UNITED KINGDOM
Power Control & Energy Efficiency
Tel. +44 1462 440 033 Fax +44 1462 431 143 info.scp.uk@socomec.com
UPS
Tel.+44 1285 863 300 Fax+44 1285 862 304 info.ups.uk@socomec.com
TURKEY
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel. +90 216 540 71 20-21-22 Fax +90 216 540 71 27 info.tr@socomec.com
Non contractual document. © 2013, Socomec SA. All rights reserved. - To help protect the environment, this document has been printed on PEFC paper (Programme for the Endorsement of Forest Certification).
YOUR DISTRIBUTOR
IN ASIA PACIFIC
AUSTRALIA
UPS
Tel. +61 2 9325 3900 Fax +61 2 9888 9544 info.ups.au@socomec.com
CHINA
UPS / Power Control & Energy Efficiency
Tel. +86 21 52 98 95 55 Fax +86 21 62 28 34 68 info.cn@socomec.com
INDIA
Power Control & Energy Efficiency
Tel. +91 124 4027210 Fax +91 124 4562738 info.scp.in@socomec.com
836}6RODU
Tel. +91 44 39215400 Fax +91 44 39215450 & 51 info.ups.in@socomec.com info.solar.in@socomec.com
SINGAPORE
UPS / Power Control & Energy Efficiency
Tel.+65 6506 7600 Fax +65 64 58 7377 info.sg@socomec.com
THAILAND
UPS
Tel. +66 2 941 1644 7 Fax +66 2 941 1650 info.ups.th@socomec.com
VIETNAM
UPS
Tel. +84 8 3559 1220 Fax +84 8 3559 1221 info.ups.vn@socomec.com
IN MIDDLE EAST
UNITED ARAB EMIRATES
8363RZHU&RQWURO(QHUJ\(IILFLHQF\}
Solar
Tel.+971 4 29 98 441 Fax +971 4 29 98 449 info.ae@socomec.com
IN AMERICA
USA, CANADA & MEXICO
Power Control & Energy Efficiency
Tel. +1 617 245 0447 Fax +1 617 245 0437 info.us@socomec.com
OTHER COUNTRIES
NORTH AFRICA
Algeria / Morocco / Tunisia
info.naf@socomec.com
AFRICA
Other countries
info.africa@socomec.com
SOUTH EUROPE
Cyprus / Greece / Israel / Malta
info.se@socomec.com
SOUTH AMERICA
Tel. +34 93 540 75 75 info.es@socomec.com
MORE DETAILS
www.socomec.com/worldwide
IN EUROPE
*IOMITYTWXX0C-GB 00*
IOMITYTWXX0C-GB 00 02.2014