socomec ENT-RK10, ENT-RK15, ENT-RK20, ENT-TW08, ENT-TW10 Product Manual

...
UPS-ENTERPRISE
800-2000 VA
PRODUCT MANUAL
UPS-ENTERPRISE
800-2000 VA
Tower and rack version
PRODUCT MANUAL
CONTENTS
1 SAFETY STANDARDS.............................................................................................................4
2 GENERAL DESCRIPTION........................................................................................................5
2.1
3 UNPACKING AND INSTALLATION.........................................................................................7
3.1
3.2
4 CONFIGURATION AND START-UP ......................................................................................10
4.1
4.2
OPERATION......................................................................................................................5
2.1.1
2.1.2
3.2.1
3.2.2
3.2.3
Wiring diagram...........................................................................................................5
LED display and control panel...................................................................................6
ENVIRONMENTAL REQUIREMENTS FOR INSTALLATION...........................................7
CONNECTION TO THE MAINS POWER SUPPLY AND CONNECTING THE LOAD......8
Settings for connections.............................................................................................8
Use of the battery expansions (optional) ...................................................................9
Putting an external battery expansion into operation.................................................9
CONFIGURATION OF THE OUTPUT VOLTAGE/BATTERY EXPANSIONS.................10
Power Share Configuration (2000VA version only) .........................................................10
5 DISPLAYS & CONTROL ........................................................................................................11
5.1
5.2
5.3
USE OF SIGNAL RELAY........................................................................................................15
6
7 TECHNICAL DATA.................................................................................................................16
8 MAINTENANCE......................................................................................................................17
8.1
COMMANDS AND SIGNALS ..........................................................................................11
5.1.1
5.1.2
5.1.3
5.1.4
5.2.1
5.3.1
5.3.2
Switching on with mains power present...................................................................11
Battery-powered operation (in cases of black-out) ..................................................12
Operating failures.....................................................................................................13
Switching the UPS off..............................................................................................13
TEST PROCEDURES .....................................................................................................14
Battery test...............................................................................................................14
COMMUNICATION..........................................................................................................14
RS232 interface.......................................................................................................14
USB interface...........................................................................................................14
TROUBLESHOOTING FOR MINOR PROBLEMS..........................................................17
2
SECTION 1
CONDITIONS OF WARRANTY
CERTIFICATE AND
CERTIFICATE AND CONDITIONS OF WARRANTY
This SOCOMEC UPS uninterruptible power system is guaranteed against manufacturing and material defects, for a period of 12 months* from the date of purchase. This certificate of warranty must NOT be sent
back, but must be kept by the customer together with the purchase receipt, to be used if the product should require interventions while under warranty. The period of validity of the warranty is calculated from the date of purchase of the new product, by the final user, from an official reseller (the date shown on the purchase receipt is used as proof). The warranty is of the 'carry-in' type: free supply of parts and labour for repairs, with return of a product to be replaced to SOCOMEC UPS, or authorized centres, at the customer’s cost and risk.
In order to use the warranty service, the user must respect the following rules:
the product must be returned exclusively in its original packaging. Any damage caused during shipping in packaging other than the original is not covered by the warranty;
the product must be accompanied by proof of purchase: a document (bill, invoice, receipt) showing the date of purchase and the information necessary to identify the product (model, serial number). The number of the authorization for return for repairs must also be attached, with a detailed description of the defect found in the product. If any of these elements is missing, the warranty is invalid. The return authorization number is issued by the service centres by telephone on receiving notification of the malfunction;
if it is not possible to provide proof of purchase, the serial number and date of production will be used to calculate expiry of the warranty, which may lead to a reduction in the product’s warranty period.
The product is not covered by warranty for damage caused by negligence (use outside the tolerance ranges: electric power supply, lightning, humidity, temperature, bad ventilation, etc.), tampering or any unauthorized intervention. During the warranty period, SOCOMEC UPS may, at its discretion, decide to repair the product or replace the defective parts with new parts or with used parts that are equivalent to new parts in terms of functions and performance. In the case of the battery, the warranty is valid if periodic recharging has been effected within the terms indicated on the packaging. It is advisable, therefore, after purchase, to check that the date of the next recharging has not passed.
Optionals
Warranty for the optionals is 12 months and is of the carry-in type.
Software products
Warranty for the software is 90 days. The software is guaranteed to function in compliance with the manual and the written material accompanying the product. Hardware accessories or supports (e.g. disks, cables, etc.) attached are guaranteed from material and manufacturing defects under normal use and service, for a period of 12 months from the date of purchase.
Under no circumstances will SOCOMEC UPS be responsible for damages (including, without limitations, damage for loss of earnings, interruption of activity, loss of data or other economic losses) deriving from the use of this product. The present conditions are subject to Italian law. All disputes to be heard by the Court of Vicenza.
* Local warranty condition apply in addition to the general one.
SECTION 1
Q
3
SAFETY STANDARDS
1 SAFETY STANDARDS
This manual must be kept in the vicinity of the UPS, so that the operator may consult it at any time for clarifications on the correct use of the UPS. Read the manual carefully before connecting the unit to the general mains power supply and to the devices to be powered. Before putting the UPS (Uninterruptible Power Supply) into operation, the operator must be fully aware of the functions and positions of all the controls and of the technical and functional characteristics of the system, in order to avoid risks to persons and to the equipment.
Before starting, the unit must be provided with an equipotential conn ection as established by the safety standards in
force. The earth cable of the UPS is to be connected to an efficient earthing point.
If the earth connection is not made, all devices connected to the UPS will be without equipotential connection. In th is
case the manufacturer declines all responsibility for damage or accidents caused by non-observance of the said standard.
In case of mains failure (battery mode), do not disconnect the input cable from mains so to ensure the earth
connection to the loads supplied.
All subsequent mainten ance operations must be carried out solely and exclusively by authorized personnel. Insid e the
system high electric voltages are generated which may endanger maintenance personnel who are not sufficiently prepared and trained for such tasks.
If at any time during use a hazard condition is created, remove the mains power supply (if possible through the
distribution panel upstream of the unit) and switch the UPS off completely following the appropriate procedure.
When assembling and replacing the battery, the UPS should always be switched off and disconnected from the mains
power supply.
The UPS contains an internal power source which is the batteries. The UPS output ma y be powered even when the
UPS is not connected to the mains power supply.
Do not force, break or try to open the batteries. They are sealed and do not require any maintenance. Inside they
contain substances that are toxic to health and that pollute the atmosphere. Do not switch the UPS on if there is any leak of liquid, or if a residual white powder is noted.
Replace the fuses ONLY with other fuses of the same type.
The sockets can be used as output isolating devices (EPO Emergency Power Off). When installing, leave a suitable
space at the back of the UPS near the fuse holder unit for easy access to the fuse holders.
Avoid contact of the UPS unit with water or liquids in general. Do not introduce foreign bodies.
If the unit needs to be scrapped, it is essential to entrust the equipment solely and exclusively to specialist disposal
companies. These are obliged to break up and dispose of the various components in accordance with the legal provisions in force nationally.
The UPS generates a leakage current of about 1.5mA. To guarantee the maximum limit leakage current of 3.5mA,
make sure that the maximum leakage curren t of the load is 2 mA. If the load leakage cur rent exceeds this limit value, have qualified personnel connect the UPS to an industrial t ype, IEC 309 compliant power supply mains, with a current of correct dimensions for the UPS power rating.
UPS-ENTERPRISE is intended for commercial and industrial use; it is not recommended for use in medical
applications which are “essential” to the survival of the patient.
Use the UPS in accordance with specifications shown in the technical data (paragraph 6).
4
Q
SECTION 1
CONDITIONS OF WARRANTY
CERTIFICATE AND
2 GENERAL DESCRIPTION
UPS-ENTERPRISE: sure power supply for servers, graphics stations and network devices.
The main purpose of the UPS is to protect sensitive and critical equipment items from the electrical disturbances that can compromise operation. Black-outs, brown-outs, variations of voltage and frequency, lightning, electrostatic discharges and rapid overvoltages are phenomena found in all office and industrial environments and which cause hardware damage and data losses.
2.1 OPERATION
UPS-ENTERPRISE is based on the on-line, double conversion, VFI (Voltage and Frequency Independent) technology to guarantee the highest level of electrical protection. With this principle of operation, the voltage and the frequency at the input of the UPS are completely regenerated via a first AC/DC conversion followed by a DC/AC conversion in order to provide the consumer a stable waveform that is exempt of noise or distortions, and therefore completely independent of the input mains. In this double conversion process, the UPS also becomes a filter element in relation to the electrical network thus preventing the distorting absorption (typical of IT users) from being reflected on the power supply line. In the event of a black-out, UPS-ENTERPRISE provides for generation of the output voltage without any disturbance, even transient, drawing the power from the internal batteries. During normal operation with the mains line present, UPS-ENTERPRISE recharges the batteries fully automatically and independently.
2.1.1 Wiring diagram
8 9
10
6
7
Key
1 Battery-charger 2 Rectifier (AC/DC)
1 2 3
4
5
3 Batteries for standard back-up 4 Inverter (DC/AC) 5 Automatic internal by-pass 6 Mains input 7 Power output for consumer lines 8 UPS 9 Back-up expansion unit 10 Batteries for back-up extensions (optional)
SECTION 1
Q
5
2.1.2 LED display and control panel
GENERAL DESCRIPTION
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
ON
OFF
<35% 35-55% 55-75% 75-95% 95-100%
<35% 35-55% 55-75% 75-95% 95-105% >105%
Key
ON OFF LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7
On button (mute buzzer, reset alarms) Off button (inverter OFF) Battery capacity % LED bar GREEN Mains up and regular YELLOW Auxiliary mains present and regular (bypass line) RED General alarm (stop or failure) Delivered power % LED bar GREEN no-break output YELLOW by-pass output
6
Q
SECTION 1
CONDITIONS OF WARRANTY
CERTIFICATE AND
3 UNPACKING AND INSTALLATION
3.1 ENVIRONMENTAL REQUIREMENTS FOR INSTALLATION
Install the UPS after first checking the following:
UPS-ENTERPRISE has been designed for use in closed environments.  Place the UPS on a flat and stable surface, in a ventilated environment away from heat sources and
exposure to direct sunlight.
Keep ambient temperature between 0°C and 40°C and humidity less than 90% (non-condensing); the best
temperature to guarantee longest possible battery life is 15-20°C.
Ensure that the environment that the UPS will be installed in is not dusty, and leave a space of at least 20
cm around it to allow for adequate ventilation and access to the rear panel.
Make sure not to set the UPS or any other heavy object on the cables.  Check that the voltage and frequency preset for operation is right for your electrical power supply. The UPS
data can be read on the plate on the rear panel.
For the RS232 serial connection or with a LAN network, use only the manufacturer-supplied cables and
accessories.
In case of RK models for installation in 19” standardized cabinets, the lateral brackets supplied must be mounted. The pictures that follow illustrate the assembly depending on the configuration.
ENT-RK10 ENT-RK15 / RK20
L
WARNING
Extract the UPS or the battery module and remove all the parts from the pack. It is strongly recommended to keep the packaging materials, which have been designed for safe shipping in cases where the unit has to be shipped back for maintenance.
SECTION 1
Q
7
UNPACKING AND
INSTALLATION
3.2 CONNECTION TO THE MAINS POWER SUPPLY AND CONNECTING THE LOAD
3.2.1 Settings for connections
Connection to the mains (1) and the connection of applications (2) should be made by using cables of appropriate cross-section and which conform to the standards in force. A distribution panel must be set up (if there is not one already) which can be used to isolate the mains upstream of the UPS. This panel must have an automatic switch of sufficient capacity for the current absorbed at full load and a differential breaking device. The mains input may be connected through the cable previously powering the server. For the output connections, use the two IEC320 cables supplied.
Tower Version
1
800 / 1000VA
2
2
2
2
Power Share
1500 / 2000VA
8
Q
SECTION 1
3.2.2 Use of the battery expansions (optional)
Where long-life battery operation is required, back-up expansion un its are available. By combining the UPS with a battery expansion unit, back-up times of up to 60 minutes may be obtained.
3.2.3 Putting an external battery expansion into operation
CONDITIONS OF WARRANTY
CERTIFICATE AND
The table above indicates sizing of the back-up expansion depending on the consumers connected: a maximum of two battery expansion units may be connected to a UPS.
Danger
Make sure that the safety switch on the battery expansion is in the “OFF” position during the
!
Set the battery expansion unit beside the UPS on the side that does not have the air vents. Connect the UPS and the battery expansion using the special cable supplied.
Disposition of the connection cables is shown in the example in the figure that follows.
Once connection has been completed, to make the back-up expansion operative, put the safety switch on the battery expansion to the “ON” position and configure it through the special menu as described in chapter 4.
connection steps.
L
WARNING
In the event of operation with an external battery expansion, the charging process takes longer.
ENT-TW08 ENT-TW10
ENT-TW15 / TW20
ENT-RK15 / RK20
SECTION 1
Q
9
CONFIGURATION AND START UP
4 CONFIGURATION AND START-UP
4.1 CONFIGURATION OF THE OUTPUT VOLTAGE/BATTERY EXPANSIONS
WARNING
The factory configuration is for operation with output voltage of 230V, without additional battery
L
To enter configuration mode, put the “UPS in bypass” by pressing the OFF button (if switched off, simply insert the mains power plus):
1. Press both buttons together for 3 seconds until a beep is heard.
2. In configuration mode, the battery LED bar will be flashing.
3. If no action is taken within 10 seconds, the UPS exits from configuration mode.
4. Proceed with configuration by pressing the “OFF” button until the desired configuration is obt ained, displayed
The battery LED bar stops flashing and the LEDs indicate the number of battery expansions included:
Display Selection Total battery capacity Physical appearance
After configuration of the battery expansion, wait for 10 seconds to automatically exit from the setting procedure. If you want to configure the 230V output voltage (default) or 220V or 240V, then press the buttons again
simultaneously for 3 seconds, before exiting from setting mode (within 10 seconds). In output voltage setting mode, as well as the battery LED bar, the no-break output LED also flashes. For configuration of the voltage, use the same arrangements as for the battery expansions with the “OFF” button for selection of the desired value, as shown in the table that follows.
Display Selection
After completing the configuration procedures, it is recommended to switch the UPS off; the new parameters will have effect the next time it is switched on.
expansions.
For normal uses with standard back-up, no configuration work is required.
as in the table that follows:
0 expansions (default) 1 string UPS only 1 expansion 3 strings UPS + 1 battery cabinet 2 expansions 5 strings UPS + 2 battery cabinets
220V 230V (default) 240V
4.2 Power Share Configuration (1500 / 2000VA version only)
Functionality of the Power Share sockets can be configured through the softwar e (Net-Vision/Uni Vision). The purpose of this group of extra sockets is, generally speaking, to feed part of the users (those with low priority) to be able to exclude them in critical situations and leave full availability of power supply to the privileged users connected to the main sockets.
Possible configurations: the Power Share outlet is disconnected in case of:
(Default) Overload on the output with mains line up or load greater than 95% in battery operation.
Residual battery capacity < XX % (user-selectable through the software)
Residual battery back-up time < di XX min (user-selectable through the software)
Emergency Lighting operation (user-selectable through the software)
Emergency Lighting means activating the Power Share sockets only when the mains line is down; this is a contrary logic function, but one which is useful for activating an emergency lights line when the mains line is down without the need for additional circuitry.
10
Q
SECTION 1
5 DISPLAYS & CONTROL
Key
CERTIFICATE AND
CONDITIONS OF WARRANTY
LED lit LED off LED flashing Buzzer
5.1 COMMANDS AND SIGNALS
5.1.1 Switching on with mains power present
See note
After the mains power supply has been connected, the internal battery-charger is activated automatically and the UPS goes into by-pass mode.
Note Under normal conditions (mains present), the associated LED may be flashing, indicating inversion of the phase / neutral polarities: in this case, insert the plug the other way to eliminate the problem.
Press the ON button for about 2 sec. (until you hear a beep) to activate the UPS and power your equipment. After a few seconds for the self-test, the LEDs will be as shown in the figure on the left. The mains power supply is regular and constant and the batteries are in charging or floating. This is normal operation.
Your application is powered by the UPS and continuous power is guaranteed.
If the UPS is switched on with mains absent, follow the same procedure as described above and after the self-test the UPS will go into battery-powered operation. The consumers are powered by the batteries, which will progressively discharge. An intermittent acoustic and visual alarm will indicate that the UPS-ENTERPRISE is operating on battery power.
It is recommended to switch on in this way only if the prot ected equipment has to be switched on under emergency conditions and with the minimum indispensable load.
Your application is powered for the residual time given by the batteries
SECTION 1
Q
11
5.1.2 Battery-powered operation (in cases of black-out)
DISPLAYS & CONTROL
Following a failure of the mains power supply or a condition of mains out of the accepted limits, the UPS goes immediately into battery-powered operation without disturbance of the power supply to the application. An acoustic and a visual signal show the battery operation status.
The acoustic alarm may be muted temporarily by
pressing the “ON” button for 3 sec.
Your application REMAINS powered
In the event of a prolonged mains failure, when battery back-up will soon run out, the imminent shutdown is clearly signalled: “battery low” condition. The battery LED bar is almost out, the buzzer sounds again automatically at a more frequent rate (and can no longer be muted).
It is recommended to close down applications manually if the automatic shutdown procedure has not been activated via the specific software installed on the computer.
WARNING! your application REMAINS powered but residual operation time is nearly out!
When the regular mains power supply returns, normal operation is restored automatically.
Your application IS powered by the UPS with continuous power ensured and the battery is recharged automatically.
If the black-out is not reset, the UPS provides power to the application until the batteries are completely discharged or until shutdown is activated through the software.
The output is thus disconnected while awaiting the return of the mains.
When the mains is restored, the UPS will start again automatically.
12
L
WARNING
A few hours are needed to guarantee recharging of the batteries and return them to fully operative conditions.
Your application is NOT powered.
Q
SECTION 1
5.1.3 Operating failures
If for any reason the red LED comes on permanently, then there is an irregular operating condition. The UPS automatically goes into by-pass mode in order to protect the consumers connected. Turn to the troubleshooting section for the solution to the problem.
CONDITIONS OF WARRANTY
CERTIFICATE AND
L
WARNING
Where the load demands more power than the nominal power of the UPS or if there is a peak of greater than 130%, the UPS enters bypass mode.
The UPS remains in this condition while waiting for the required absorption to return inside the limits.
The load LED bar displays the irregular absorption.
Your application remains powered though with potential risks of interruption of the service or deterioration of performance.
5.1.4 Switching the UPS off
Partial switching off with mains present
Pressing the OFF key for 2 sec. in normal operation with mains present activates the partial switching off of the UPS.
WARNING! This does not lead to switching-off of the applications connected. This is a partial switching-off, as the microprocessor control and battery recharging circuits are still operative with the consumers powered by the mains through the bypass.
Your application remains powered though with potential risks of interruption of the service or deterioration of performance.
Total switching-off
For total switching-off, press the OFF button for 2 sec. (as above) and take out or disconnect the mains power supply.
WARNING! This leads to the switching-off of the applications connected and also of serial communication. This switching-off is only recommended in cases of long periods of inactivity of the UPS.
Your applications are switched off.
SECTION 1
Q
13
DISPLAYS & CONTROL
5.2 TEST PROCEDURES
5.2.1 Battery test
The battery test can be activated manually or via the SW (as long as the conditions are right). The automatic test checks the efficiency of the batteries so that, if necessary, the user can be informed when they need to be replaced in order to guarantee sure service of the UPS. If the test fails, an alarm condition is displayed. For a manual lasts for about 10 seconds with the LED bar flashing to indicate that the test is in progress. It is advisable to perform the test with batteries fully charged (LED bar fully lit up).
test, press the ON button for more than 3 seconds (with the UPS in normal conditions); the test
5.3 COMMUNICATION
All the UPS-ENTERPRISE models are provided with the RS232 serial communication interface and USB. A DB9 serial cable is supplied and is to be used for direct connection to the server. Optional communication and signalling accessories are also available, such as:
Uni Vision local management software with local shutdown functions for Windows systems
Uni Vision pro network management software with local/remote shutdown functions on the leading operating
systems based on JSC (Java Shutdown Client)
Net Vision Web/SNMP manager* for control via LAN with TCP/IP protocol and remote shutdown management
the relay card with 3 zero-potential dry contact signals and an isolated input (ESD)
* Net Vision permits direct connection of the UPS to a LAN (RJ45 ethernet) and remote control of the UPS through TCP/IP using a WEB browser.
5.3.1 RS232 interface
Communication with the server can take place directly via the RS232 interface using the Jbus protocol. In addition to the local or networked shutdown it is possible to perform full monitoring of the electrical parameters of battery status and the automatic ON / OFF programming of the UPS. For a complete description of the software features, refer to the Uni Vision and Uni Vision Pro documentation.
5.3.2 USB interface
In addition to the RS232 serial link, it is also possible to establish communication directly through USB with the HID protocol, where available in the operating system. In this case, it is not necessary to install any SW, a standard USB cable is used and, once connected, recognition takes place in the same way as for any peripheral. The unit’s control parameters may be managed directly through the operating system’s service menu.
Tower Version
Slot for optional communication cards.
Rack Version
14
Q
SECTION 1
CONDITIONS OF WARRANTY
CERTIFICATE AND
6 USE OF SIGNAL RELAY
An optional card is available for insertion in the slot, which is able to handle 3 isolated contact signals with which to remote relay UPS status information.
The relay contacts can be configured NO (standard) or NC via jumpers on the optional interface card
1,2 = NC 2,3 = NO
The maximum voltage that can be applied to the contacts is 60Vdc and the maximum current is 500mA.
Pin DB 9 Signals NC NO J
4 General alarm 1-2 2-3 3 Battery almost out 1-2 2-3 2 Mains down or not in limits: UPS in back-up (20 sec) 1-2 2-3
Where required, it is also possible to switch off the UPS via a remote external contact. The command is received by leaving the contact closed for 3 consecutive seconds. The external contact must be closed between pin 6 and pin 8.
The external contact must be dedicated and at zero potential; if this condition is not respected, permanent damage may be caused to the UPS.
!
PIN LAYOUT
pin 2 Mains missing pin 3 Battery almost out pin 4 General alarm pin 5 Relay common
pin 6 Positive for ESD pin 8 Return for ESD
Logica
Gestione
Relè
Relè
R1 R2 R3
Uscite Relè
9 PIN
Ottici
I1
Ingresso
UMPERS
CN04 CN02 CN03
SECTION 1
Q
15
TECHNICAL DATA
7 TECHNICAL DATA
Technical data ENT-TW08
Power 800VA / 560W 1000VA / 700W 1500VA /1050W 2000VA /1400W Technology VFI (Voltage and Frequency Independent) On line double conversion Input Input voltage 160 ÷ 276Vac (1ph) Frequency 50/60Hz (automatic selection) Power factor >0.97 Input current Sinusoidal absorption Output Output voltage (Vout) Voltage distortion <4% on a linear load Output frequency stability Automatic by-pass Overload (with mains present) AC/AC efficiency 88% Crest factor 3:1 Reference normatives Standard European UPS standard EN50091 and CE marking Safety / EMC standards EN50091-1-1 / EN50091-2 Environmental data Operating temperature 0 +40°C (32-104°F)
for longer life battery from 15°C to 25°C (59°F - 77°F ) Storage temperature (MAX) -5 +50°C (23-122°F) Relative humidity HR 0 ÷ 90% non-condensing Maximum altitude (above sea level) Acoustic noise (ISO 3746) < 45dB @ 1mt Physical data (weight including batteries) Dimensions (WxDxH) TW 145x405x225 mm 87x495x435 TW weight 14 kg 15 kg 22 kg 23kg Dimensions (WxDxH) RK RK weight / 16 kg 22 kg 23kg
1,000mt (3,300ft) with no derating; maximum 3,000mt (10,000ft)
/
ENT-TW10 ENT-RK10
230V (1ph) ± 3% (selectable* 220/240V)
50Hz or 60Hz (± 0.5% in battery mode)
Voltage selected ± 15%
130% for 10 seconds
483x460x87 mm 483x495x87 mm
ENT-TW15 ENT-RK15
ENT-TW20 ENT-RK20
16
Q
SECTION 1
CONDITIONS OF WARRANTY
CERTIFICATE AND
8 MAINTENANCE
DANGEROUS electrical voltages are generated inside the UPS. All maintenance operations to be performed SOLELY AND EXCLUSIVELY by authorized personnel.
!
Optimal operation of the unit is obtained by keeping it constantly powered (24 hours a day). This guarantees correct maintenance of the battery charge.
If there is to be a long period when the equipment is not in use, wait until the batteries are fully charged before switching the UPS off completely ( mains present for eight hours consecutively).
While the unit is not in operation, the batteries should be recharged for 24 hours at least every 4
weeks.
8.1 TROUBLESHOOTING FOR MINOR PROBLEMS
This section describes some of the most likely problems that may compromise proper operation of the UPS, together with an attempt to identify the likely causes and possible solutions
IMPORTANT: if after following the indications in this chapter, the problems persist or are repeated frequently, you should call the technical service centre providing a full description of the problem.
!
Problem Possible cause Solution
The MAINS LED does not come on, the acoustic alarm sounds at intervals
The MAINS LED flashes Phase and neutral inverted at the
The ALARM lamp is lit, the acoustic alarm sounds continuously.
Battery back-up time less than indicated
OVERLOAD indicator lamp lit Overload on the UPS output Reduce the load connected to
No communication between UPS and PC
The main switch is not inserted Insert the main switch Mains voltage is missing Have an electrician check the
mains
Fuse on the input faulty.
input to the UPS UPS broken Contact the customer support Overtemperature Lower the ambient temperature
Battery expansion switch in the “OFF” position The number of external expansion batteries is not set correctly The batteries are not fully charged The batteries are faulty Contact the customer support
The battery-charger is defective Contact the customer support
Serial connection cable error Use the cable provided. The PC interface is busy with another process or defective Interference on the data cable Change position of the cable.
Replace the fuse with another one of the same type. Remove the connection plug from the mains and insert it again inverted
service. Turn the safety switch to “ON” Correct the settings (see chapter
4) Charge the batteries for at least 8
hours consecutively. service. service. within the nominal value. Check that other SW applications
are not interfering.
SECTION 1
Q
17
800 VA / 1000 VA tower
front view rear view
4
2
5
1
7
Battery extension tower 1000 VA rack 19”
Battery extension rack 19”
Rear view Front / Rear view
8
5
5
6
4
VIEW SECTION
Q
6
5
5
7
1 4 2
8
1500-2000 VA tower Battery extension tower
rear view rear view
7
2
5
1
4
6
5
3
5
5
1500-2000 VA rack 19”
6
5
3 4
Rear view
2
1
7
Battery extension rack 19”
Rear view
5
8
5
VIEW SECTION
Q
5
1 Fan 2 Slot for optional communication boards 3 Output socket power share 4 RS232/USB serial port DB9 5 Battery connection for extension 6 Output socket 7 Input socket and fuse 8 Battery switch
GB F
1 Ventilateur 2 Cache pour cartes de communication optionnelles 3 Prise de sortie power share 4 Connecteur série RS232/USB DB9 5 Connecteur batterie pour extension externe 6 Prise de sortie vers l'utilisation 7 Prise arrivée réseau et fusible 8 Commutateur de batterie
1 Ventilatore 2 Slot per schede di comunicazione opzionali 3 Presa di uscita power share 4 Connettore seriale RS232/USB DB9 5 Connettore batteria per espansione esterna 6 Presa di uscita per utenze 7 Presa ingresso rete e fusibile 8 Interruttore batterie
ID
1 Ventilador 2 Slot para tarjetas de comunicación opcionales 3 Toma de salida power share 4 Conector serie RS232/USB DB9 5 Conector de batería para expansión externa 6 Toma de salida hacia utilización 7 Toma de entrada red y fusible 8 Interruptor de batería
E
1 Lüfter 2 Abdeckung für Kommunikationskarten (Option) 3 Ausgang power share 4 Serieller Anschluß RS232/USB DB9 5 Batterieanschluß für eine externe Erweiterung 6 Ausgang zur Last 7 Netzeingang und Sicherung 8 Batterieschalter
6
ООО "Энергетические и Телекоммуникационные Системы" Тел./факс: (495) 981-13-66 http://www.entel.ru, E-Mail: sales@entel.ru
Loading...