Control and power supply interface
EN
1. DOCUMENTATION |
---|
2. HAZARDS AND WARNINGS |
2.1. Risk of electrocution, burns or explosion |
2.2. Risk of damaging the device |
2.3. Liability |
3. PRELIMINABY OPERATIONS |
4. INTRODUCTION |
4.1. hange |
4.3. Introduction to DIRIS Digiware D |
4.3.1 Introduction to DIRIS Digiware D-40 |
4.3.2. Introduction to DIRIS Digiware D-50 |
4.3.3. Introduction to DIRIS Digiware D-70 |
4.4. Touchscreens |
4.5. LED display |
4.6. Navigation |
4.7. Menu structure |
4.8. Dimensions |
5. MOUNTING |
5.1. Recommendations and safety14 |
5.2. Back-plate mounting14 |
6. CONNECTION |
6.1. DIRIS D-30 - wiring |
6.2. DIRIS Digiware D-40 - wiring |
6.3. DIRIS Digiware D-50 / D-70 - wiring |
7. CONFIGURATION |
7.1. Specific display settings |
7.1.1. DIRIS Digiware D-40 |
7.1.2. DIRIS Digiware D-50 / D-70 |
7.1.3. Language |
7.1.4. Date format |
7.1.6. Ethernet communication 10 |
7.1.7. Setting the date/time on the remote product. |
7.1.8. Configuring SNMP - BACNET - FTP - SMTP (DIRIS Digiware D-70) . 20 |
7.2. Detecting and addressing |
7.2.1. DIRIS Digiware D-50 / D-70 |
7.2.2. DIRIS Digiware D-40 |
7.3. Configuring each meter and measuring device |
7.3.1. Network configuration |
8. USE |
9. SNMP COMMUNICATION WITH THE DIRIS DIGIWARE D-70 |
9.1. SNMP generalities |
9.2. SNMP functions supported |
9.3. SNMP versions supported |
9.4. SNMP ports |
9.5. Retrieving data using the D-70 MIB file |
10. BACNET COMMUNICATION WITH THE DIRIS DIGIWARE D-70 |
10.1. BACnet Generalities |
10.2. BACnet Objects |
10.3. BACnet Services |
11. CHARACTERISTICS |
11.1. DIRIS D-30 and DIRIS Digiware D-40/D-50/D-70 - characteristics 55 |
11.1.1. Mechanical features |
11.1.2. DIRIS D-30 communication characteristics | 55 |
---|---|
11.1.3. DIRIS Digiware D-40 communication characteristics | 55 |
11.1.4. DIRIS Digiware D-50 communication characteristics | 55 |
11.1.5. DIRIS Digiware D-70 communication characteristics | 55 |
11.1.6. Electrical characteristics | 56 |
11.1.7. Environmental specifications | 56 |
All documentation on DIRIS D-30 and DIRIS Digiware D-40/ D-50/D-70 is available on the SOCOMEC website: www.socomec.com/en/diris-d
The term "device" used in this document covers both DIRIS D-30 and DIRIS Digiware D-40. D-50 and D-70.
The assembly, use, servicing and maintenance of this equipment must only be carried out by trained, qualified professionals.
SOCOMEC shall not be held responsible for failure to comply with the instructions in this manual.
Failure to take these precautions could cause death or serious injuries.
To ensure that the device operates correctly, make sure that:
To ensure the safety of personnel and the product, please carefully read the contents of these instructions before installation.
Check the following points as soon as you receive the package containing the device:
PSocomec
PLANE Directory PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLANE CONTRACTOR PLA |
|
Socomec Dets Composition Socomec Soco | Proceeding of the second of th |
---|---|---|---|
DIRIS D-30
Single-point display |
DIRIS Digiware D-40
Multipoint display |
DIRIS Digiware D-50
Multipoint display |
DIRIS Digiware D-70
Multipoint display |
Ref. 4829 0200 | Ref. 4829 0199 | Ref. 4829 0201 | Ref. 4829 0202 |
- |
RS485 output
Modbus RTU |
Ethernet output
Modbus TCP |
Ethernet output
Modbus TCP BACnet IP SNMP v1, v2 & v3 |
- | - | - |
Webview embedded web
server Power & Energy Monitoring |
DIRIS D-30 is a local single-point display connected to the measuring device DIRIS B or DIRIS Digiware I-4x via an RJ9 cable (1.50m cable reference: 4829 0280 - 3m cable: 4829 0281). The screen is powered through the RJ9 cable.
The DIRIS Digiware D-40, D-50 and D-70 displays are shared between DIRIS Digiware meters and measuring devices.
They can also display measurements from other SOCOMEC meters and measuring devices: COUNTIS, DIRIS A, DIRIS B (with the exception of DIRIS Digiware D-40).
They centralise data from up to 32 devices (a maximum of 186 outputs).
These products may be connected by a Digiware bus and/or an RS485 bus.
Centralised products can be shown as well as configured by DIRIS Digiware D displays.
A DIRIS Digiware D-40 display is a slave device on the RS485 bus and master on the DIRIS Digiware bus.
A DIRIS Digiware D-50 display is a master device on the RS485 bus and master on the DIRIS Digiware bus. It is used like an Ethernet gateway.
The Ethernet port is for:
A DIRIS Digiware D-70 display is a master device on the RS485 bus and master on the DIRIS Digiware bus. It is used like an Ethernet gateway.
The Ethernet port is for:
Consumption curves | Load curves | Measuring logs | |
---|---|---|---|
Logged data | Energy: kWh, kvarh, kVAh | Power: kW, kvar, kVA |
Average measurements:
U, V, I, P, Q, S, PF, Temperature |
Compatible products |
COUNTIS Exx (all)
DIRIS Axx (all) DIRIS Bxx (all) DIRIS Digiware XXX (all) |
Countis Eci , Countis E3x
DIRIS A40 + MEM / A60/A80 DIRIS B-30 DIRIS Digiware I-31 / I-61 /I-35 / I-45 |
DIRIS B30
DIRIS Digiware I-35 / I-45 / U-30 |
Integration period | 10 min to 60 min | 1 min to | o 60 min |
Archiving period in D-70 |
1 yea
P For example: This applies no matter how level of detail of the loc |
ar with a 60-min integration period.
Proportional for different values: 3 months with a 15-min integration period. w many devices (1 to 32) are connected to the D-70. The |
|
Operation |
Readings taken every
10 min / 60 min in the meter/PMD. |
The data is recorded in a cache memory on the me
and then downloaded by the D-70. If communicati is interrupted, the missing data is recovered by th D-70 once the connection is restored so that record continues. |
|
Data backup | NO | YES (in the meter | 's cache memory) |
Export to the FTP server | YES | YES | YES |
Webview link |
Monitor
Measure Arms and Events Analyse Consumptions Terms |
Monitor
Measures Measures Austra and Events Austra and Events Consumptions Vieweds |
|
Specific configuration Nothing to configure (data is recorded automatically). |
Load curves must be
activated on the meters (via Easy Config). Load curves are then automatically downloaded from the meter's cache memory to the D-70. |
Measuring logs must be
activated on the meters (via Easy Config). The logs are then automatically downloaded from the meter's cache memory to the D-70. |
The display consists of a screen and 10 shortcut keys:
IP | Shortcut keys for load measurements: current, active power, reactive power, apparent power, power factor, cosinus phi | |
---|---|---|
V F | Shortcut keys for electrical network measurements: single voltage, composite voltage, frequency | |
E | Shortcut keys for active, reactive, apparent energy meters (total and partial readings) | |
Arrow keys for navigation | ||
Use this to go up a level in the display navigation menus | ||
» | Use this to go to the previous/next product (to scroll through all your meters and centralised measuring devices) | |
ОК | Use this to confirm your navigation or entry selection |
|
---|
|
Menu structure | D-30 | D-40 |
D-50
D-70 |
||
---|---|---|---|---|---|
Load | • | • | • | ||
Load phase-neutral | • | • | • | ||
Phase-phase load | • | • | • | ||
Net. frequency | • | • | ٠ | ||
Net. phase-neutral | • | • | • | ||
Net. phase-neutral unbalanced | • | • | • | ||
Net. phase-neutral THD | • | • | • | ||
Voltages | Net. phase-neutral harmonic | • | • | • | |
Net. phase-neutral crest factor | • | • | • | ||
Net. phase-phase | • | • | • | ||
Net. phase-phase unbalanced | • | • | • | ||
Net. phase-phase IHD | • | • | |||
Net. phase-phase harmonic | • | • | |||
Net. phase-phase crest factor | • | • | • | ||
Currents | • | • | • | ||
Currents system | • | • | • | ||
Unbalanced currents | • | • | • | ||
Magguramonto | Currents | Currents THD | • | • | • |
weasurements | Currents K factor | • | • | • | |
Currents harmonics | • | • | • | ||
Current crest factor | • | • | • | ||
Active powers | • | • | • | ||
Reactive powers | • | • | • | ||
Apparent powers | • | • | • | ||
Powers | Predictive power | • | • | • | |
Power factors | • | • | • | ||
• | • | • | |||
Ian Phi | • | • | • | ||
Positive active energies | • | • | • | ||
Negative active energies | • | • | • | ||
Energies | Positive reactive energies | • | • | • | |
Ū | Negative reactive energies | • | - | • | |
Positive/negative inductive/capacitive reactive energies | • | • | |||
Apparent energies | • | • | • | ||
RESET all Min/Max values | • | • | • | ||
Enable | In progress | • | • | • | |
Events | History | Alarms, quality | • | • | • |
language | • | • | • | ||
Date format | • | • | • | ||
Digiware Addressing Range | • | ||||
Slave RS485: Baudrate, stop, parity, address | • | ||||
Display | Master RS485: Baudrate, stop, parity, address | • | |||
Ethernet communication: DHCP, IP address, mask, gateway | • | ||||
Setting the date/time on the remote product Date/Time: Activation - manual setting | • | • | • | ||
SNTP (server IP address, server port, time zone, Send settings) | • | ||||
Change password | • | • | • | ||
Parameters | Configure a device | Network, loads | • | • | • |
Autodetect serial devices | Status, found devices, address conflicts, start | • | • | ||
List products | • | • | |||
Add new device | Type of device, address | • | • | ||
Bemove device | • | • | |||
╞══┦ | — | ||||
Restore device's factory settings | • | • | • | ||
Device software version | • | • | • | ||
IP address | • | ||||
MAC address | • | ||||
About | Serial number | • | • | • | |
Software version | • | • | • | ||
Reboot | • | • | • |
Note: the menus available depend on the product features.
Refer to the safety instructions (section "2. Hazards and warnings", page 5)
DIRIS D-30 and DIRIS Digiware D are board-mounted (slot: 92x92mm). The display is secured with clips.
Note: DIRIS Digiware D-40 and D-50, class B in radiated power is obtained using ferrites (ref. 4829 0048) on the power cable (two rounds): The ferrites are not supplied with the DIRIS Digiware D-70 which is Class A in radiated power.
(*) 24 VDC 1A fuse if using a non-SOCOMEC supply
To return to the navigation menu, press "OK" to call up the various menus:
Select the "PARAMETERS" menu by using the navigation key "DOWN ARROW" 3x and confirm with "OK":
HOME | 1 |
---|---|
I FVFNTS | |
Enter the password "100" using the arrow pad (4 arrow keys) and confirm with "OK":
🕆 HOME | |||
---|---|---|---|
& LOADS
☑ MEASURES ☑ INPUTS/OUTPUTS 圓! EVENTS |
CODE: | 100 | |
PARAMETERS | |||
You can access 3 main settings:
When going back to the "DISPLAY" menu, press "OK" to confirm
To access the various specific display settings:
DISP PARAMETERS | |
---|---|
LANGUAGE | • |
DATE FORMAT | |
DIGIWARE ADDRESSING RANGE | |
RS485 SLAVE COMMUNICATION | |
SET REMOTE DEVICE DATE/TIME | |
• LANGUAGE: to set the display's navigation language
To access the various specific display settings:
LANGUAGE | $ |
---|---|
DATE FORMAT | |
RS485 COMMUNICATION | |
ETHERNET COMMUNICATION | |
SET REMOTE DEVICE DATE/TIME | |
You can change the display's navigation language here.
Choose from: English, French, German, Italian, Spanish, Flemish, Polish, Turkish and Chinese.
Select your language with the arrow pad and confirm with "OK".
1 | |
---|---|
You can select the display's date format, including the separator between the day, month and year:
DATE FORMAT | ||
---|---|---|
DATE FORMAT: | MM/DD/YYYY | |
DATE SEPARATOR: | $ | |
Configure the display's Modbus address.
Configure the baudrate, stop bits, parity of the RS485 and Digiware bus.
Caution: these settings must be identical on the RS485 and Digiware buses, which are centralised on DIRIS Digiware D-50 / D-70 displays.
DIRIS Digiware D-40 is a slave device on the RS485 bus and master on the Digiware bus (2 different buses in terms of baudrate, parity, stop bits).
DIRIS D-50 / D-70 are master devices on the RS485 bus (baudrate, parity, stop bits).
BAUDRATE: | ∢ 38400 ► ♦ |
---|---|
STOP: | 1BIT |
PARITY: | NONE |
ADDRESS: | 001 |
You can configure the Ethernet settings of DIRIS Digiware D-50 / D-70 displays:
DHCP: | |
---|---|
IP ADDRESS: | 192.168.000.003 |
MASK: | 255.255.255.000 |
GATEWAY: | 000.000.000 |
You can configure the time on the DIRIS Digiware D display:
If the D-50/D-70 clock is set by the SNTP, the display sends the date and time to all the meters and measuring devices on the network, to synchronise all your devices.
CONF. DATE/TIME | |||
---|---|---|---|
AUTO. REMOTE DATE/TIME SET | ■ MANUAL ► | ¢ | |
YEAR | 00 | ||
MONTH | 01 | ||
DAY | 01 | ||
TIME | 00 | ||
To configure the SNTP you need advanced IT knowledge (see your IT Department) to enter the following fields:
SNTP server IP address
SNTP server port
AUTO. REMOTE DATE/TIME SET | SNTP ► | $ |
SERVER IP ADDRESS: | 000.000.000 | |
SERVER PORT: | 00123 | |
TIME ZONE: | GMT +9:00 | |
ОК |
Configuring meters and centralised measuring devices
You can automatically detect and assign the addresses of the meters and measuring devices connected to the DIRIS Digiware D display.
You can also automatically set the key parameters of the DIRIS Digiware and DIRIS B meters and measuring devices with the DIRIS Digiware D display.
DIRIS Digiware D-70 devices act as a gateway:
Access the data via this Ethernet port in a variety of formats:
Bacnet IP, SNMP, SMTP and FTP settings are not accessible via the onscreen interface of the device and are only available on a PC:
20 EN
After logging into Easy Config on the DIRIS Digiware D-70, you can find the SNMP settings in the following menu:
- | |||
---|---|---|---|
DIRIS Digiware | CONFIG TOOL V2 . | 6 J | |
D-70 | |||
Advantian | |||
Band Community Life | Ľ | ||
Read Official Community VI | |||
Tran community M1 | 0 | ||
Trap community V1 | |||
Read Write Community V2 | 0 | ||
Authentication protocol | UNY CONTRACTOR OF | ||
Rounce aconoral |
na
na |
||
Privacy protocol | |||
Read security username | |||
Read OV-site cerusity uncomme | |||
Read/Minite sectority docting in | |||
Tran configuration | Liver Subst | ||
Tran 1 narvar IP address | |||
Tran 1 server port | The later of the l | 0 | |
Tran 2 server IP address | |||
Trap 2 server port | 102 | 0 | |
Trap report frequency | man Second | 0 | |
· · | 1 | ||
New File : DIRIS Digiware D-70 | Polie Level : User | socomec |
• Community configuration SNMP v1 & v2:
Read Community V1: Read-only community string for SNMP v1. Default community string is "public". It allows a manager to retrieve read-only data from a device connected to the D-70.
Read-Write Community V1: Read-Write community string for SNMP v1. Default Read/Write community string is "private".
It allows a manager to change a setting (ex: position of a Digital output) in a device connected to the D-70.
Trap Community V1: The Trap community string allows the manager to receive notifications in case of an event or alarm
Read Community V2: Read-only community string for SNMP v2. Default community string is "publicv2". It allows a manager to retrieve read-only data from a device connected to the D-70.
Read-Write Community V2: Read-Write community string for SNMP v2. Default Read/Write community string is "privatev2". It allows a manager to change a setting (ex: position of a Digital output) in a device connected to the D-70.
SNMP v3 configuration:
Authentication protocol: If SNPM v3 is activated, you can choose an authentication protocol (MD5 or SHA) to hash your password. For no authentication, select "None".
Privacy Protocol: Choose between DES or AES privacy protocols for the encryption of data messages. For no encryption, select "None".
Read security username: Username enabling authentication for read-only functions.
Read authentication & privacy password: Password (also passphrase) accompanying the authentication and privacy protocols, and allowing read-only functions.
The length of the Read-only authentication & privacy password must be between 8 and 16 characters.
Read-Write security username: Username enabling authentication for read and write functions
Read-Write authentication & privacy password: Password (also called passphrase) accompanying the authentication and privacy protocols and allowing read and write functions. The length of the Read-Write authentication & privacy password must be between 8 and 16 characters.
• Trap configuration:
Choose to deactivate or activate the traps. For activation, you can choose to broadcast trap notifications to all supervisers on the network or to notify only specific host stations (up to 2).
Trap 1 server IP address: enter the IP address of the 1st host station which will receive trap notifications.
Trap 1 server port: enter the port used to send traps for the 1st host station.
Trap 2 server IP address: enter the IP address of the 2nd host station which will receive trap notifications.
Trap 2 server port: enter the port used to send traps for the 2nd host station.
Trap report frequency: enter the time after which a trap reminder will be sent for on-going alarms. By default, it is set to 60min.
7.1.8.2. Bacnet IP
The PICS file (Protocol Implementation Conformance Statement) is available at www.socomec.com
After logging into Easy Config on the D-70, you can find the BACNET IP settings on the following page:
EASY CONFIG TOOL V2.6 | ||
---|---|---|
DIRIS Digiware
D-70 |
||
O Product Identification | ||
O 1P Configuration | ||
O Naster RS-485 Modb | us configuration | |
SNMP slave configura | ation | - |
Bacnet slave configur | ration | |
Activation | No | • 0 |
Virtual network ID | 100 | 0 |
1 | ||
i |
Activation: enable or disable the Bacnet IP function
Virtual network ID: set the virtual network ID
The port used by the DIRIS Digiware D-70 for BACnet IP communication is set to 47808 (BAC0 in hexadecimal) and cannot be changed.
7.1.8.3. SMTP(s):
automatic alarm notification emails. Available as standard and secure SMTP.
After logging into Easy Config on the DIRIS Digiware D-70, you can find the SNMP settings on the following page:
smec Easy Config | ||
---|---|---|
EASY CONFIG TOOL V2.6 | ||
D-70 | ||
SMTP server settings | (m) | |
Activation | .0 | |
SMTP server IP address or name | 0 | |
Security | Re | • 0 |
SMTP Port | 25 💼 | 0 |
Authentification | ho | • 0 |
User Name | user | 0 |
Password | 0 | |
C Email Setting | ||
Source Email Address | D70@sicomes.com | 0 |
Destination Email Address 1 | 0 | |
Destination Email Address 2 | 0 | |
Destination Email Address 3 | 0 | |
Language | PR. | . 0 |
Criticality | Consid | . 0 |
Ninimum Send Frequency Time | Constant of the second s | 0 |
Send Test Mail | - | |
New File : DIRIS Digiwere D-70 | Profit I. | -socomec |
Activation: enable/disable the SMTP email export function
SMTP server IP address or name: IP address of the SMTP server or name (backup for configured DNS server)
Security: enable or disable security (SMTPs)
SMTP Port: enter the standard unencrypted SMTP port
Secured port: enter the port number for a secured connection. Default port number is 465
Authentication: enable or disable SMTP authentication
User name: enter the user name for the authentication
Password: enter the password for the authentication
Source Email Address:: email address shown when sending emails.
Destination Email Address 1: email address #1 to send email notifications to.
Destination Email Address 2: email address #2 to send email notifications to.
Destination Email Address 3: email address #3 to send email notifications to.
Language: language in which emails are sent.
Criticality: set the degree of criticality to email alerts with just a minimum level of criticality.
Minimum send frequency time: Time after which the email notification is sent by the D-70. This limits the number of emails sent by the D-70, especially when the same alarm changes state repeatedly.
Historical measurement data (see "4.3.3. Introduction to DIRIS Digiware D-70", page 9) can be automatically exported via FTP.
Go to the FTP configuration using the embedded web server Webview of the DIRIS Digiware D-70.
FTP system: configure FTP server settings
Planning: set how often data needs to be exported
Activation | Files | ||
---|---|---|---|
Activate FTP | • Yes | No | Destination folder |
Activate Logs | Ves | No | data |
Activate FTPS | 0 | File format | |
Tes | NO | CSV | |
Identification | FTP server network settings | ||
Site ID | Host | ||
SITE | 0.0.0.0 |
CSV | |
---|---|
FTP server network set | tings |
Host | |
0.0.0.0 | |
Port | |
21 | |
Secured Port | |
990 | |
Login | |
Password | |
Conne | ction test |
Activate FTP: required to activate automatic data export
Activate LOGS: can be useful for troubleshooting in case of a problem
Activate FTPS: activate secure FTP data export
Site ID and gateway ID: used to identify from which DIRIS Digiware D-70 the files are being exported.
If the file format is configured to "EMS", the site ID must be changed.
Destination folder: tree view of the FTP server folder in which you want to place the files
File format: there are two different types of data file;
In EMS mode, the exported files are named according to the following: Site ID Gateway Id Device name Data type date time
Example: if an export file is named socomec_8AD4A2_I35_LoadCurve_2017-08-15_20-00-00.csv, it means it contains Load curves (Demand Power) from a device named I35 from a gateway whose ID is 8AD4A2 and site ID is socomec.
This shows the login details for the FTP server (standard or secure).
Host: enter the IP address of your FTP server
Port: enter the non-secure port to use for FTP export
Secured port: enter the secured port to use for FTP(s) export
Login: enter your login
Password: enter your password
Deactivated Every Every |
1
Days |
Hours 🔽 | Hours | 0 | Minutes |
---|---|---|---|---|---|
Every | Days | at 0 | Hours | 0 | Minutes |
25 | 55 | 5 |
DIRIS Digiware D-70 devices can log 3 types of data:
Data can also be exported separately, manually specifying their time intervals.
With auto-addressing mode you can have the system automatically assign addresses to devices connected to the DIRIS Digiware D. This mode is only compatible with DIRIS B and Digiware PMDs. The addresses will be allocated manually on the other PMD (DIRIS A) and meters (COUNTIS).
Four products are connected to the D-50 / D-70. Two are addressed correctly, the other two have an identical address
D-50 / D-70
@2 |
Reconnet ONN Dial Dial 0 100000000 1 10000000 100000000 100000000 1 10000000 500000000 1000000000 1 100000000 5000000000 1000000000000000000000000000000000000 |
---|---|
To resolve address conflicts, go to PARAMETERS / AUTODETECT SERIAL DEVICES:
With this function you can detect all the products connected with the Digiware bus and/or the RS485 bus to the DIRIS Digiware D display. This function does not apply to DIRIS D-30.
PARAMETERS | |
---|---|
DISPLAY | |
CONFIGURE A DEVICE | |
AUTODETECT SERIAL DEVICES | $ |
LIST PRODUCTS | |
ADD NEW DEVICE | |
Select "START" then "OK" to start the scan/detection process (this can take up to 3 minutes).
AUTODETECT. | |
---|---|
STATUS: | STOPPED |
FOUND DEVICES | 000 |
ADDR CONFLICTS | 000 |
START $ | |
Please be aware that this removes all previously found devices (if they are still there they will be found again).
* | AUTODETECT. |
---|---|
DEVICES ALREADY PRESENT!
PRESS OK TO CONTINUE. |
|
PRESS BACK TO CANCEL. | |
The different stages follow automatically:
• DETECTING ADDRESS
AUTODETECT. | ۲ |
---|---|
STATUS:
FOUND DEVICES ADDR CONFLICTS |
DETEC. ADDRESS
000 000 |
STOP 🔷 | |
AUTODETECT. | × | |
---|---|---|
STATUS: | ADDR SCANNI | NG |
FOUND DEVICES | 002 | |
ADDR CONFLICTS | 001 | |
STOP | $ | |
When the STATUS "STOPPED" appears, the system has ended its search.
The number of found devices is the number of devices that have been correctly located (two in this example). If there is an address conflict (if 10 products have the same address, this is taken as a single conflict, not 10 conflicts), this means multiple products have the same address (two in this example). In this case, assign them individual and unique addresses.
AUTODETECT. | |
---|---|
ADDRESS CONFLICTS DETECTED!
PRESS THE AUTOADDRESS BUTTON ON ALL NON-BLINKING DEVICES TO SOLVE THE CON- FLICTS. |
Press "OK".
AUTODETECT. | 1 |
---|---|
STATUS: | SET ADDRESSES |
FOUND DEVICES | 002 |
ADDR CONFLICTS | 001 |
STOP 🗢 | |
To go to this address, locate the lit "COM" LED on the front of each product. Press and hold down this button for a few seconds until the LED flashes:
The display now shows the number of detected products increase and the number of conflicts decrease to reach zero once all products have a unique address.
28 EN
You can then check the list of found products along with their addresses.
LOAD1 | |
---|---|
DISPLAY | |
CONFIGURE A DEVICE | |
AUTODETECT SERIAL DEVICES | |
LIST PRODUCTS | $ |
ADD NEW DEVICE | |
Example:
LIST PROD. | LOAD1 | |
---|---|---|
Diris U30 ID:545434 | @003 | ¢ |
Diris I30 ID:F0C1D2 | @004 | |
Diris I30 ID:F0C1D3 | @005 | |
Diris I30 ID:F0C1D4 | @006 | |
You can find the codes on the marking on the products (546434 on U-30 and F0C1D2 on one of the I-30s) in the photo:
We can now configure the products individually.
To avoid a conflict of addresses, first define a range of addresses that can be assigned to auto-detected when products.
Below are some examples of communication architecture.
With this communication architecture, each DIRIS Digiware D-40 allocates addresses to the products on its branch, but it ignores addresses of devices from a different branch where there is a potential risk of conflicting addresses! The RS485 communication parameters upstream of the D-40 devices are separate from the Digiware parameters downstream of the D-40 devices. This means that the communication baudrate is also separate, and may vary between the upstream RS485 bus and the downstream Digiware bus.
To avoid these conflicts:
Example address selection:
The user must also take into account the addresses of other products connected to the RS485 network.
7.2.2.2. Setting the addressing range
A HOME | | |
---|---|
a LUADS | |
퍧 INPUTS/OUTPUTS | |
』 EVENTS | |
PARAMETERS | $ |
CONFIGURE A DEVICE
AUTODETECT SERIAL DEVICES
LIST PRODUCTS
ADD NEW DEVICE
PARAM AFF | |
---|---|
LANGUAGE
DATE FORMAT |
|
DIGIWARE ADDRESSING RANGE | $ |
RS485 SLAVE COMMUNICATION
CONF. DATE ON REMOTE PRODUCT |
START ADDRESS | 002 | $ |
END ADDRESS | 035 | |
D40 ADDRESS | 002 | |
NB ADDR. POSSIBLE | 032 | |
APPLY SETTINGS |
DIGIWARE ADDR | ||
---|---|---|
START ADDRESS | 002 | |
END ADDRESS | 009 | $ |
D40 ADDRESS | 002 | |
NB ADDR. POSSIBLE | 007 | |
APPLY SETTINGS | ||
START ADDRESS | 002 |
---|---|
END ADDRESS | 009 |
D40 ADDRESS | 002 |
NB ADDR. POSSIBLE | 007 |
APPLY SETTINGS | |
7.2.2.3. Auto-addressing
Once the address ranges are configured on the D-40, you can launch the auto-addressing process for connected products.
Two products are connected to the D-40. They have an identical address.
To resolve address conflicts, go to PARAMETERS / AUTODETECT SERIAL DEVICES:
With this function you can detect all the products connected with the DIGIWARE bus and/or the RS485 bus to the DIRIS Digiware D display.
PARAMETERS | |
---|---|
DISPLAY | |
CONFIGURE A DEVICE | |
AUTODETECT SERIAL DEVICES | $ |
LIST PRODUCTS | |
ADD NEW DEVICE | |
Select "START" then "OK" to start the scan/detection process (this can take up to 3 minutes).
AUTODETECT. | ||
---|---|---|
STATUS | STOPPED | |
FOUND DEVICES | 000 | |
ADDR CONFLICTS | 000 | |
DIGIWARE ADDRESSING RANGE | 002-009 | |
START 🔶 | ||
Caution: this removes all previously found products (if they are still there they will be found again).
* | AUTODETECT. |
---|---|
WARNING: AUTODETECT WILL REMOVE ALL DE- | |
VICES ALREADY PRESENT!
PRESS OK TO CONTINUE. |
|
PRESS BACK TO CANCEL. | |
Press "OK".
The different stages follow automatically:
• DETECTING ADDRESS
AUTODETECT. | 1 | ⊠ |
---|---|---|
STATUS: | DETEC. ADDRESS | |
FOUND DEVICES | 000 | |
ADDR CONFLICTS | 000 | |
DIGIWARE ADDRESSING RANGE | 002-009 | |
STOP | ¢ | |
ADDR SCANNING
AUTODETECT. | ⊠ | |
---|---|---|
STATUS: | ADDR SCANNING | |
FOUND DEVICES | 000 | |
ADDR CONFLICTS | 001 | |
DIGIWARE ADDRESSING RANGE | 002-009 | |
STOP | $ | |
When the STATUS "STOPPED" appears, the system has ended its search.
The number of found devices is the number of devices that have been correctly located. If there is an address conflict (if 10 products have the same address, this is taken as a single conflict, not 10 conflicts), this means multiple products have the same address (two in this example). In this case, assign them
Press "OK". The following screen appears:
AUTODETECT. | |
---|---|
STATUS: | SET ADDRESSES |
FOUND DEVICES | 001 |
ADDR CONFLICTS | 001 |
DIGIWARE ADDRESSING RANGE | 002-009 |
STO | P 🔶 |
To go to this address, locate the lit "COM" LED on the front of each product. Press and hold down this button for a few seconds until the LED flashes:
The display now shows the number of detected products increase and the number of conflicts decrease to reach zero once all products have a unique address.
D-40
Range [2-9] @2 |
Processes Course and |
---|---|
Digiware bus | |
U-30 I-30
@3 @4 |
You can then check the list of found products along with their addresses.
LOAD1 | |
---|---|
DISPLAY | |
CONFIGURE A DEVICE | |
AUTODETECT SERIAL DEVICES | |
LIST PRODUCTS | $ |
ADD NEW DEVICE | |
Example:
LIST PROD. | LOAD1 |
---|---|
Diris U30 ID:545434 | @003 🗢 |
Diris I30 ID:F0C1D2 | @004 |
You can also set the DIRIS Digiware range and the DIRIS B range with the display.
"Parameters" > "Configure a device".
LOAD1 | |
---|---|
DISPLAY | |
CONFIGURE A DEVICE | $ |
AUTODETECT SERIAL DEVICES | |
ADD NEW DEVICE |
There are two stages to electrically configuring the various devices:
With DIRIS Digiware U-xx you can configure the network
PROD. | |||
---|---|---|---|
Diris I3 | 30 ID:FOC1D2 | @004 | |
Diris U | I30 ID:546434 | @006 | > |
SELECT PROD. | Diris U30 ID:5464 | 434 | |
SELECT PROD. | Diris U30 ID:5464 | 134 | |
SELECT PROD. | Diris U30 ID:5464 | 434 | |
SELECT PROD. | Diris U30 ID:5464 | 134 | |
SELECT PROD. | Diris U30 ID:5464 | 134 |
With DIRIS Digiware I-XX you can configure the loads
With DIRIS B you can configure the network and loads at the same time.
You can configure the various network voltage parameters:
Diris U30 ID:546434 | |
---|---|
NOMINAL VOLTAGE
NETWORK TYPE NOMINAL EREQUENCY |
00400
3P + N 50HZ |
PRESS O | K TO CONFIRM 🔶 |
You can simultaneously measure multiple single-phase, two-phase and three-phase loads on a DIRIS B or DIRIS Digiware display.
This example shows a DIRIS Digiware I-30 measuring a three-phase + neutral load using 3 current transducers.
Diris I30 ID:FOC1D2 | ||||||
---|---|---|---|---|---|---|
LINES | | |1 | 12 | 13 | |||
тс | 250 A | 250 A | 250 A | 103 | ||
DIRECTION | +/DIRECT | +/DIRECT | +/DIRECT | |||
LINE V | V3 | V2 | V1 | |||
OUTPUT | L1 | L1 | L1 | 12 | ||
TYPE | 3P+N_3CT | 3P+N_3CT | 3P+N_3CT | |||
PRESS C | K TO ENTER | SETTINGS |
The transducer connected to the current 1 input measures the current of phase 3 (V3)
The transducer connected to the current 2 input measures the current of phase 2 (V2)
The transducer connected to the current 3 input measures the current of phase 1 (V1)
Diris | 130 ID:FO | C1D2 | |||
---|---|---|---|---|---|
LINES | |1 | 12 | 13 | ||
TC | 250 A | 250 A | 250 A | ||
DIRECTION | +/DIRECT | +/DIRECT | +/DIRECT | ||
LINE V | V3 | V2 | V1 | ||
OUTPUT | L1 | L1 | L1 | ||
TYPE | 3P+N_3CT | 3P+N_3CT | 3P+N_3CT | ||
PRESS OK TO ENTER SETTINGS |
The 3 current inputs I1, I2, I3 are assigned to the same output / three-phase load no. 1 (L1).
Diris I30 ID:FOC1D2 | ||||||
---|---|---|---|---|---|---|
LINES | |1 | 12 | 13 | |||
TC | 250 A | 250 A | 250 A | |||
DIRECTION | +/DIRECT | +/DIRECT | +/DIRECT | |||
LINE V | V3 | V2 | V1 | |||
OUTPUT | L1 | L1 | L1 | |||
TYPE | 3P+N_3CT | 3P+N_3CT | 3P+N_3CT | |||
PRESS OK TO ENTER SETTINGS |
The TC field indicates the type of earth fault connected and the direction shows if it was mounted upright or inverted (upright gives a good overview of the positive powers rather than the negative powers shown when inverted: see +100 kW instead of -100 kW, for example):
Diris I30 ID:FOC1D2 | |||||
---|---|---|---|---|---|
1 | |||||
LINES | | |1 | 12 | 13 | ||
тс | 250 A | 250 A | 250 A | ||
DIRECTION | +/DIRECT | +/DIRECT | +/DIRECT | ||
LINE V | V3 | V2 | V1 | ||
OUTPUT | L1 | L1 | L1 | ||
TYPE | 3P+N_3CT | 3P+N_3CT | 3P+N_3CT | ||
PRESS OK TO ENTER SETTINGS |
7.3.2.2. Changing the load settings
Following the example above, to change the settings, press "OK".
Diris I30 ID:FOC1D2 | |||||
---|---|---|---|---|---|
LINES | 11 | 12 | 13 | ||
TC | 250 A | 250 A | 250 A | ||
DIRECTION | +/DIRECT | +/DIRECT | +/DIRECT | ||
LINE V | V3 | V2 | V1 | ||
OUTPUT | L1 | L1 | L1 | ||
TYPE | 3P+N_3CT | 3P+N_3CT | 3P+N_3CT | ||
PRESS OK TO ENTER SETTINGS |
You can change each parameter to configure each of the loads (the values shown onscreen are shown in bold - see the example below).
Diris I30 ID:FOC1D2 | ||
---|---|---|
OUTPUT |
$
|
|
NAME | LOAD 1 | |
TYPE | 3P+N_3CT | |
I NOMINAL | 00020 | |
CT1 | 11 | |
Go back to "CONFIG CT" to make detailed settings for the current transducer:
Diris I30 ID:FOC1D2 | ||
---|---|---|
NAME | LOAD 1 | |
TYPE | 3P+N_3CT | |
I NOMINAL | 00020 | |
CT1 | 11 | |
CONFIG. CT | ¢ | |
Configure:
Complete the process by selecting "OK" then "OK" again
CONFIG LINES | Diris I30 ID:FOC1D2 |
---|---|
DIRECTION | +/DIRECT |
LINE V | V3 |
тс | 0600 |
DETECT | $ |
ОК | |
If a load is configured as three-phase or three-phase+neutral, for example, you would have to configure multiple current transducers (e.g. 3 transducers for one three-phase load):
CONFIG LINES | Diris I30 ID:FOC1D2 |
---|---|
CONFIG. CT | |
CT2 | 12 |
CONFIG. CT | |
CT3 | I3 |
CONFIG. CT | |
When you have finished configuring the entire load (L1) (type of load, name, rated current, all configured transducers), set the following loads (L2, L3) from the "OUTPUT" line:
4 | PARAMETERS | Diris I30 ID:FOC1D2 | |
---|---|---|---|
OUTPUT | ∢ L1 ► | ¢ | |
NAME | LOAD 1 | ||
TYPE | 3P+N_3CT | ||
I NOMINAL | 00020 | ||
CT1 | 11 | ||
For example, a DIRIS Digiware I-30 with 3 current inputs is best for measuring:
There are a number of other possible load combinations.
When all the outputs/loads are configured (maximum 3 on one DIRIS Digiware I-30), apply your settings by selecting "SEND SETTINGS" and click "OK".
CONFIG LINES | Diris I30 ID:FOC1D2 |
---|---|
CT3 | 13 |
CONFIG. CT | |
CT4 | 11 |
CONFIG. CT | |
SEND SETTINGS | |
Once the loads are configured, you can view the measures of each load on the "MEASURES" menu. You can view active and past alerts on the "EVENTS" menu. If an alert is active, the "ALARM" LED is on.
SNMP stands for Simple Network Management Protocol and is widely used by administrators for an easy network monitoring of devices on IP networks. It works in a client-server communication mode on an Ethernet physical laver.
Once enabled from the Easy Config configuration software, the DIRIS Digiware D-70 display supports SNMP v1, v2 and v3. The D-70 is an agent SNMP v1, v2, v3 which responds to queries from managers (also called management stations or supervisors).
The D-70 allows access through SNMP of measurement data from SOCOMEC slaves connected via the RS485 bus or the Digiware bus.
Data from the slaves can be reached through a file called "MIB" ("Management Information Base") under a hierarchical and pre-defined structure. The MIB file of the D-70 is named "socomec-diris-products-mib" and is available from www.socomec.com
The file must be uploaded in the Management station managing your metering system.
The Tree structure of the MIB contains multiple OIDs (Object Identifiers). An OID uniquely identifies and labels a managed object (=parameter from metering devices) in the MIB.
For example, the electrical parameter "Current Inst I1" is identified by one OID. "Current Inst I2" is identified by another one.
Common SNMP terms | Consumption curves |
---|---|
Agent | Corresponds to the D-70: Interface between the PMDs and the manager |
Managed device | The PMDs connected downstream the D-70 (ex: I-35, DIRIS B, DIRIS A) |
MIB | Management information base where the OIDs are organized in a hierarchical tree |
OID | An object identifier that uniquely identifies and labels a managed object in the MIB hierarchy |
Community strings | A text that enables the authentication between an agent and the manager |
Traps | Notifications sent by the agent and received by the manager |
There are 4 types of SNMP requests supported by the D-70:
Traps are sent by the agent in case one of the following alarms occurs:
Traps are sent automatically when the alarm occurs. They will be sent again once the "Trap report frequency" time (entered in Easy Config) is elapsed.
The alarm must be activated in the product (using the configuration software Easy Config) in order for the Traps to be sent.
Traps can either be configured for specific hosts or "broadcast" to the whole network. Up to two server IP addresses can be entered in Easy Config for SNMP trap notification of specific hosts.
The DIRIS Digiware D-70 can use all three versions of SNMP: SNMPv1, v2 and v3.
The identification is based on Read-only and Read-Write Community passwords. They are non-encrypted and are passed over the network in plaintext.
Both passwords have to be entered in the Agent (D-70) and the Manager and must be identical.
A matching Read Community allows the Get functions to be executed on the agent.
A matching Read-Write Community also allows the Set function to be executed on the agent.
- The default Read Community V1 password is "public" and the default Read-Write Community V1 password is "Private".
- The default Read Community V2 password is "publicv2" and the Read-Write Community V2 is "privatev2".
SNMPv3 uses the USM (User-based Security Module) for controlling access to information available via SNMP. This version offers more security using three important features to prevent the interception and deciphering of data:
The D-70 is configured with standard SNMP ports to receive requests and send notifications:
Port | Description | |
---|---|---|
161 | Used to send and receive requests from the manager. | |
162 | Used by the manager to receive notifications from the agent |
The D-70 is compliant with MIB-II defined by the MIB standard RFC 1213 which defines the following structure:
The standard branches are under the same parent branch structure: 1.3.6.1.4.1
The "Private (4)" group enables vendors to define private branches including the MIB OIDs of their own products. Data related to SOCOMEC metering devices is located under the SOCOMEC enterprise category identified by OID 1.3.6.1.4.1.4555. This implies that all queries from a manager to SOCOMEC agents will start by the base path 1.3.6.1.4.1.4555.
Because the Digiware system is a multi-circuit system, the D-70 creates a dynamic table which depends on the products connected downstream compatible with the D-70 and the loads configured on each product. After adding/deleting a downstream device or a load, make sure to update the topology of the D-70 display. This can be done either directly from the display or from Webview:
Example: The OID for "Current Inst I1" will return a value for all I-xx, B-xx, DIRIS A etc.. On the contrary, the OID for "THD Inst I1" will return "0" for an I-30 or an I-31 module.
This implies that each OID can be associated with several products and several loads.
OID sequence | Description |
---|---|
4555 | "SOCOMEC" enterprise branch |
10 | "SocomecProducts" table |
20 | "ProductMetrology" table |
20 | "InstantaneousTable" |
1 | Entry (always = 1) |
10000 | Service ID |
This OID is associated with the multiple devices connected downstream the D-70.
To identify those multiple devices, the Modbus address and the load number are added to the end of the OID.
Example: Let us consider the following architecture:
Product | I-30 | I-30 |
---|---|---|
Modbus address | 4 | 5 |
Load type | Load 1: 3P + N - 3CT |
Load 1: 1P + N - 1CT
Load 2: 1P + N - 1CT Load 3: 1P + N - 1CT |
The final OID to get the instantaneous current I1 for the I-30 module @ Modbus address 4 for load 1 is: 1.3.6.1.4.1.4555.10.20.1.10000.4.1
For the I-30 module @ address 5, there are multiple loads configured. This implies that the Modbus address must be followed by the Load number in the OID.
Therefore, the final OID used to request 11 Inst for load 1 of the I-30 @ address 5 is:
The final OID to request 11 Inst for load 2 of the I-30 @ address 5 is 1.3.6.1.4.1.4555.10.20.1.10000.5.2 The final OID to request 11 Inst for load 3 of the I-30 @ address 5 is 1.3.6.1.4.1.4555.10.20.1.10000.5.3
OID sequence | Description |
---|---|
4555 | "SOCOMEC" enterprise branch |
10 | "SocomecProducts" table |
20 | "ProductMetrology" table |
20 | "InstantaneousTable" |
1 | Entry (always = 1) |
10000 | Service ID |
5 | Modbus Address |
3 | Load number |
Note: A request to OID 1.3.6.1.4.1.4555.10.20.1.10001.5 will return "0" because only single-phase loads are configured in the I-30 module @ address 5, which means currents I2 and I3 parameters aren't used.
The DIRIS Digiware D-70 supports the BACnet IP protocol, once enabled from the Easy Config software (see 7.1.8.2).
It acts as a BACnet IP gateway to all devices compatible and connected downstream via RS485 or the Digiware Bus.
The PICS (Protocol Implementation Conformance Statement) of the D-70 is available on the Socomec website at www.socomec.com.
BACnet provides a method for computer-based control equipment from different manufacturers to be interoperable. BACnet is designed to handle many types of building controls, including HVAC, lighting, security, fire, access control, maintenance, waste management and so forth.
Common terms used in BACnet communication:
Object: Represents a device and its data. Multiple objects type can be available for each device *analog input, binary input...). Each object has a number of properties which fully describe the BACnet object to the network.
Object identifier: Uniquely identifies an object within a BACnet device.
Property: A property describes a BACnet object to the network.
Present value: It is one of the properties of the Analog_Input Object. It represents the current value of an analog input object.
Service: Message type between one BACnet device to another.
BACnet uses a client/server communication mode between devices. Devices communicate between each other using services describing the type of exchange.
A BACnet client is a device that requests a service, and a BACnet server is a device that executes a service. Data inside a BACnet device is organized as a series of objects, each composed of multiple properties.
Ex: the analog_input object defines a property for present_value, a property for average_value etc...
A BACnet client initiates a request to a BACnet server using a service (ex: read_property) to a specific property (ex: present value) contained in a BACnet object (ex: analog input).
BACnet defines a standard set of "Objects", each of which has a standard set of "Properties" describing the object and its current status to other devices on the BACnet internetwork. The properties allow for the object to be controlled by other BACnet devices.
BACnet defines 54 objects. Each element of the building control system is represented by one or more objects. The DIRIS Digiware D-70 supports the below Objects:
Object type | Exemple of use |
---|---|
Device | To describe the device to the BACnet network. |
Analog input | Instantaneous current for phase 1 (I1) measured by a DIRIS Digiware I-xx current module with associated current sensor |
Binary input | Status (ON/OFF) of an auxiliary contact |
Binary output | Change of status of the output of a DIRIS Digiware IO-20 |
A list of properties defines each BACnet Object. Properties can be:
Every BACnet device compatible with the DIRIS Digiware D-70 must have the Device Object and its associated required properties that fully describe the BACnet device to the network
Example for the Device Object of the DIRIS Digiware D-70:
Property | BACnet |
---|---|
Object_Identifier (OID) | Required |
Object_Name | Required |
Object_Type | Required |
System_Status | Required |
Vendor_Name | Required |
Vendor_Identifier | Required |
Model_Name | Required |
Firmware_Revision | Required |
Application_Software_
Version |
Required |
Protocol_Version | Required |
Protocol_Conformance_
Class |
Required |
Protocol_Services_
Supported |
Required |
Protocol_Object_Types_
Supported |
Required |
Object_List | Required |
Max_APDU_Length_
Supported |
Required |
Segmentation_Supported | Required |
APDU_Timeout | Required |
Location | Optional |
Description | Optional |
Local_Time | Optional |
Utc_Offset | Optional |
Local_Date | Optional |
Daylight_Saving_Status | Optional |
Active_COV_Subscriptions | Optional |
Serial_Number | Optional |
Property_List | Optional |
Version_Build_Date | Proprietary |
Operating_Hour_Counter | Proprietary |
The way the OID is assigned to a device (instance number) is the following:
OID = Main OID (= default 100) + ModbusAddress
The DIRIS Digiware D-70 acts as a BACnet gateway. It provides a number of Analog Input objects which may be available from the devices compatible and connected to the D-70. Whether a device supports an AI object depends on its measurement functionalities.
Ex: The OID for THD_I1 will return 0 for a DIRIS Digiware I-30 module because this parameter is not handled.
The AI object defines 25 properties. The devices compatible and connected downstream the D-70 support the following properties:
Property | BACnet |
---|---|
Object_Identifier | Required |
Object_Name | Required |
Object_Type | Required |
Present_Value | Required |
Status_Flags | Required |
Event_State | Required |
Out_Of_Service | Required |
Units | Required |
Description | Optional |
Reliability | Optional |
Min_Pres_Value | Optional |
Minimum_Value_
Timestamp |
Optional |
Max_Pres_Value | Optional |
Maximum_Value_
Timestamp |
Optional |
Average_Value | Optional |
Instantaneous_Timestamp | Proprietary |
Average_Timestamp | Proprietary |
Max_Average_Value | Proprietary |
Max_Average_Timestamp | Proprietary |
Min_Average_Value | Proprietary |
Min_Average_Timestamp | Proprietary |
Harmonics_Row_02 | Proprietary |
Harmonics_Row_03 | Proprietary |
Harmonics_Row_04 | Proprietary |
Harmonics_Row_05 | Proprietary |
Harmonics_Row_06 | Proprietary |
Harmonics_Row_07 | Proprietary |
Harmonics_Row_08 | Proprietary |
Harmonics_Row_09 | Proprietary |
Harmonics_Row_10 | Proprietary |
Energy_Total_Residual | Proprietary |
---|---|
Energy_Total_Hourmeter | Proprietary |
Energy_Partial | Proprietary |
Energy_Partial_Residual | Proprietary |
Energy_Partial_Hourmeter | Proprietary |
Energy_Total_Lagging | Proprietary |
Energy_Total_Lagging_Res | Proprietary |
Energy_Total_Leading | Proprietary |
Energy_Total_Leading_Res | Proprietary |
Energy_Last_Partial | Proprietary |
Energy_Last_Partial_Res | Proprietary |
Energy_Last_Partial_
Timestamp |
Proprietary |
Multifluid_Partial | Proprietary |
Multifluid_Weight | Proprietary |
Instant_Min_Max_Reset | Proprietary |
Average_Min_Max_Reset | Proprietary |
The way the OID is assigned to an Analog Input Object (instance number) is the following: OID = LLMM
• with LL = Load # of the device (starting at 1)
• with MM = Index of the measurement type (see Analog Input Measurement List).
For example, Analog Input with OID 204 reflects Phasis/Neutral Voltage V1 of Load 2 of corresponding device.
The table with indexes of the analog input measurement list is given below:
Index | Object Namew | Object Description | Unit | Type |
Present
+ Timestamp |
Present Min/Max
+ Timestamp |
Average
+ Timestamp |
Average Min/Max
+ Timestamp |
Harmonics
2 -> 10 |
Energies Total +
Partial + LastPartial |
Energies Total
Lagging/Leading |
Multifluid | Reset Min/Max |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
0 | VystPhN |
System Ph-N
Voltage |
V | Unsigned | • | • | |||||||
1 | VystPhPh |
System Ph-Ph
Voltage |
V | Unsigned | • | • | |||||||
2 | CurrentSyst | System Current | А | Unsigned | • | ٠ | |||||||
3 | Frequency |
System
Frequency |
Hz | Unsigned | • | • | • | • | • | ||||
4 | VoltPhNV1 | Ph-N Voltage V1 | V | Unsigned | • | • | • | • | ٠ | ||||
5 | VoltPhNV2 | Ph-N Voltage V2 | V | Unsigned | • | • | • | • | ٠ | ||||
6 | VoltPhNV3 | Ph-N Voltage V3 | V | Unsigned | • | • | • | • | ٠ | ||||
7 | VoltPhNVn | Ph-N Voltage Vn | V | Unsigned | • | • | • | • | ٠ | ||||
8 | VoltPhPhU12 |
Ph-Ph Voltage
U12 |
V | Unsigned | • | • | • | • | • | ||||
9 | VoltPhPhU23 |
Ph-Ph Voltage
U23 |
V | Unsigned | • | • | • | • | • |
10 | VoltPhPhU31 |
Ph-Ph Voltage
U31 |
V | Unsigned | • | ٠ | • | ٠ | ٠ | ||
---|---|---|---|---|---|---|---|---|---|---|---|
11 | Currentl1 | Current I1 | А | Unsigned | • | ٠ | • | ٠ | ٠ | ||
12 | Currentl2 | Current I2 | А | Unsigned | • | ٠ | • | ٠ | ٠ | ||
13 | Currentl3 | Current I3 | А | Unsigned | • | ٠ | • | ٠ | ٠ | ||
14 | CurrentIn | Current In | А | Unsigned | • | ٠ | • | ٠ | ٠ | ||
15 | CurrentInba | Current Inba | % | Unsigned | • | ٠ | |||||
16 | CurrentIdir | Current Idir | А | Unsigned | • | ٠ | |||||
17 | Currentlinv | Current linv | А | Unsigned | • | ٠ | |||||
18 | Currentlhom | Current Ihom | А | Unsigned | • | ٠ | |||||
19 | CurrentInb | Current Inb | % | Unsigned | • | ٠ | |||||
20 | PowerApparentNom |
Nominal
Apparent Power |
VA | Unsigned | • | ٠ | |||||
21 | TotalPowerActive |
Total Active
Power |
W | Signed | • | • | • | • | ٠ | ||
22 | TotalPowerRActive |
Total Reactive
Power |
VAr | Signed | • | • | • | • | • | ||
23 | TotalPowerApparent |
Total Apparent
Power |
VA | Unsigned | • | • | • | • | • | ||
24 | TotalPowerFactor |
Total Power
Factor |
- | Signed | • | • | • | • | ٠ | ||
25 | TotalPowerFactorType |
Total Power
Factor Type |
- | Unsigned | • | • | • | • | ٠ | ||
26 | PowerActiveP1 | P1 Active Power | W | Signed | • | • | • | • | • | ||
27 | PowerActiveP2 | P2 Active Power | W | Signed | • | • | • | • | ٠ | ||
28 | PowerActiveP3 | P3 Active Power | W | Signed | • | • | • | • | • | ||
29 | PowerRActiveQ1 |
Q1 Reactive
Power |
VAr | Signed | • | • | • | • | • | ||
30 | PowerRActiveQ2 |
Q2 Reactive
Power |
VAr | Signed | • | • | • | • | ٠ | ||
31 | PowerRActiveQ3 |
Q3 Reactive
Power |
VAr | Signed | • | • | • | • | ٠ | ||
32 | PowerApparentS1 |
S1 Apparent
Power |
VA | Unsigned | • | • | • | • | ٠ | ||
33 | PowerApparentS2 |
S2 Apparent
Power |
VA | Unsigned | • | • | • | • | ٠ | ||
34 | PowerApparentS3 |
S3 Apparent
Power |
VA | Unsigned | • | • | • | • | ٠ | ||
35 | PowerFactorPF1 |
PF1 Power
Factor |
- | Signed | • | • | • | • | ٠ | ||
36 | PowerFactorTypeSPF1 |
sPF1 Power
Factor Type |
- | Unsigned | • | • | • | • | ٠ | ||
37 | PowerFactorPF2 |
PF2 Power
Factor |
- | Signed | • | • | • | • | • | ||
38 | PowerFactorTypeSPF2 |
sPF1 Power
Factor Type |
- | Unsigned | • | • | • | • | ٠ | ||
39 | PowerFactorPF3 |
PF3 Power
Factor |
- | Signed | • | • | • | • | ٠ | ||
40 | PowerFactorTypeSPF3 |
sPF1 Power
Factor Type |
- | Unsigned | • | ٠ | • | ٠ | • | ||
41 |
LoadCurve_
P+ |
Load Curve
Positive Active Power |
W | Unsigned | • | ٠ | |||||
42 | LoadCurve_P- |
Load Curve
Negative Active Power |
W | Unsigned | • | ٠ |
43 |
LoadCurve_
Q+ |
Load Curve
Positive Reactive Power |
VAr | Unsigned | • | ٠ | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
44 | LoadCurve_Q- |
Load Curve
Negative Reactive Power |
VAr | Unsigned | ٠ | ٠ | ||||||
45 | LoadCurve_S |
Load Curve
Apparent Power |
VA | Unsigned | ٠ | ٠ | ||||||
46 | THD_I1 | THD I1 | % | Unsigned | ٠ | • | ٠ | ٠ | ||||
47 | THD_I2 | THD I2 | % | Unsigned | ٠ | • | ٠ | ٠ | ||||
48 | THD_I3 | THD I3 | % | Unsigned | ٠ | • | ٠ | ٠ | ||||
49 | THD_In | THD In | % | Unsigned | ٠ | • | ٠ | ٠ | ||||
50 | THD_V1 | THD V1 | % | Unsigned | ٠ | • | ٠ | ٠ | ||||
51 | THD_V2 | THD V2 | % | Unsigned | ٠ | • | ٠ | ٠ | ||||
52 | THD_V3 | THD V3 | % | Unsigned | • | • | ٠ | ٠ | ||||
53 | THD_U12 | THD U12 | % | Unsigned | ٠ | • | ٠ | ٠ | ||||
54 | THD_U23 | THD U23 | % | Unsigned | ٠ | • | ٠ | ٠ | ||||
55 | THD_U31 | THD U31 | % | Unsigned | ٠ | • | ٠ | ٠ | ||||
56 | A+ |
Positive Active
Energy |
Wh | Unsigned | • | • | ٠ | |||||
57 | A- |
Negative Active
Energy |
Wh | Unsigned | ٠ | • | ٠ | |||||
58 | ER+ |
Positive Reactive
Energy |
VArh | Unsigned | ٠ | • | ٠ | ٠ | ||||
59 | ER- |
Negative
Reactive Energy |
VArh | Unsigned | ٠ | • | ٠ | ٠ | ||||
60 | ES | Apparent Energy | VAh | Unsigned | ٠ | • | ٠ | |||||
61 | Mff | Multifluid feeder | - | Signed | ٠ | • | ٠ |
The services define methods for BACnet devices to communicate and exchange data with one another. The D-70 supports the following services:
Service list | Description |
---|---|
readProperty | Used by a BACnet device (the client) to ask another BACnet device (the server) to provide the value of one of its object properties |
readPropertyMultiple | Used by a BACnet device (the client) to ask another BACnet device (the server) to provide the values of multiple object properties |
writeProperty | Used by a BACnet device (the client) to ask another BACnet device (the server) to change the value of one of its object properties |
timeSynchronization | Used to broadcast the current time to one or more BACnet servers |
who_Has | Asks which BACnet devices contain a particular Object |
who_ls | Used by a BACnet client to ask the presence of BACnet servers |
Type of screen | Capacitive touch-screen technology, 10 keys |
---|---|
Screen resolution | 350 x 160 pixels |
Front panel protection index | IP65 |
Weight of the DIRIS D-30 / DIRIS Digiware D-40/D-
50/D-70 |
160g / 180g |
Type of screen | Local single-point screen for DIRIS Digiware I-4x and DIRIS B |
---|---|
RJ9 | Self-powered and data |
USB | Upgrade and configuration via type B micro USB connector |
Type of screen | Multipoint remote screen |
---|---|
RJ45 Digiware | Control and power supply interface function |
RS485 2-3 wires | Modbus RTU slave communication function |
USB | Upgrade and configuration via type B micro USB connector |
Type of screen | Multipoint remote screen |
---|---|
Ethernet RJ45 10/100 Mbs | Modbus TCP gateway function (max.4 simultaneous connections) |
RJ45 Digiware | Control and power supply interface function |
RS485 2-3 wires | Modbus RTU master communication function |
USB | Upgrade and configuration via type B micro USB connector |
Type of screen | Multipoint remote screen |
---|---|
Ethernet RJ45 10/100 Mbs
(use a shielded Ethernet cable) |
Gateway function:
- Modbus TCP (max. 32 simultaneous connections) - Webview embedded web server (Power & Energy Monitoring version) - BACnet IP - SNMP v1, v2 & v3 |
SNTP protocol |
Updates the screen from an NTP server.
The display updates the connected devices. |
SMTP protocol(s) | Sends email notifications from the display. |
FTP protocol(s) | Automatically exports data via FTP standard or secure server (consumption curves, load curves, measurement logs) |
RJ45 Digiware | Control and power supply interface function |
RS485 2-3 wires | Modbus RTU master communication function |
USB | Upgrade and configuration via type B micro USB connector |
Power supply | 24 VDC +10% / -20% |
---|---|
Power consumption | 2 VA |
Battery life (D-70 only) | 3 days |
Storage temperature | -20 to +70°C |
---|---|
Operating temperature | -10 to +55°C |
Humidity | 95% at 40°C |
Installation category - degree of pollution | CAT III, 2 |
______________________________________