socomec DIRIS D-30, DIRIS DigiwareD-40, DIRIS Digiware D-50, DIRIS Digiware D-70 Instruction Manual

Page 1

DIRIS D-30 DIRIS Digiware D-40 / D-50 / D-70

Control and power supply interface

EN

Page 2

EN CONTENTS

1. DOCUMENTATION
2. HAZARDS AND WARNINGS
2.1. Risk of electrocution, burns or explosion
2.2. Risk of damaging the device
2.3. Liability
3. PRELIMINABY OPERATIONS
4. INTRODUCTION
4.1. hange
4.3. Introduction to DIRIS Digiware D
4.3.1 Introduction to DIRIS Digiware D-40
4.3.2. Introduction to DIRIS Digiware D-50
4.3.3. Introduction to DIRIS Digiware D-70
4.4. Touchscreens
4.5. LED display
4.6. Navigation
4.7. Menu structure
4.8. Dimensions
5. MOUNTING
5.1. Recommendations and safety14
5.2. Back-plate mounting14
6. CONNECTION
6.1. DIRIS D-30 - wiring
6.2. DIRIS Digiware D-40 - wiring
6.3. DIRIS Digiware D-50 / D-70 - wiring
7. CONFIGURATION
7.1. Specific display settings
7.1.1. DIRIS Digiware D-40
7.1.2. DIRIS Digiware D-50 / D-70
7.1.3. Language
7.1.4. Date format
7.1.6. Ethernet communication 10
7.1.7. Setting the date/time on the remote product.
7.1.8. Configuring SNMP - BACNET - FTP - SMTP (DIRIS Digiware D-70) . 20
7.2. Detecting and addressing
7.2.1. DIRIS Digiware D-50 / D-70
7.2.2. DIRIS Digiware D-40
7.3. Configuring each meter and measuring device
7.3.1. Network configuration
8. USE
9. SNMP COMMUNICATION WITH THE DIRIS DIGIWARE D-70
9.1. SNMP generalities
9.2. SNMP functions supported
9.3. SNMP versions supported
9.4. SNMP ports
9.5. Retrieving data using the D-70 MIB file
10. BACNET COMMUNICATION WITH THE DIRIS DIGIWARE D-70
10.1. BACnet Generalities
10.2. BACnet Objects
10.3. BACnet Services
11. CHARACTERISTICS
11.1. DIRIS D-30 and DIRIS Digiware D-40/D-50/D-70 - characteristics 55
11.1.1. Mechanical features
Page 3
11.1.2. DIRIS D-30 communication characteristics 55
11.1.3. DIRIS Digiware D-40 communication characteristics 55
11.1.4. DIRIS Digiware D-50 communication characteristics 55
11.1.5. DIRIS Digiware D-70 communication characteristics 55
11.1.6. Electrical characteristics 56
11.1.7. Environmental specifications 56
Page 4

1. DOCUMENTATION

All documentation on DIRIS D-30 and DIRIS Digiware D-40/ D-50/D-70 is available on the SOCOMEC website: www.socomec.com/en/diris-d

Page 5

2. HAZARDS AND WARNINGS

The term "device" used in this document covers both DIRIS D-30 and DIRIS Digiware D-40. D-50 and D-70.

The assembly, use, servicing and maintenance of this equipment must only be carried out by trained, qualified professionals.

SOCOMEC shall not be held responsible for failure to comply with the instructions in this manual.

2.1. Risk of electrocution, burns or explosion

  • This device must only be installed and serviced by qualified personnel who have in-depth knowledge of installing, commissioning and operating the device and who have had appropriate training. He or she should have read and understood the various safety measures and warnings stated in the instructions.
  • Before carrying out any work on the device, switch off the power supply to the device.
  • Always use an appropriate voltage detection device to confirm the absence of voltage.
  • Replace all devices, doors and covers before turning on power to this equipment.
  • Always power the device with the correct rated voltage.
  • Install the device following the recommended installation instructions and in a suitable electrical cabinet.

Failure to take these precautions could cause death or serious injuries.

2.2. Risk of damaging the device

To ensure that the device operates correctly, make sure that:

  • The device is correctly installed.
  • The auxiliary power supply voltage indicated on the product is observed: 24 VDC ± 10% (for D-40, D-50 and D-70 only).
  • Use 230 VAC / 24 VDC SOCOMEC or use a 1 A 24 VDC safety fuse.
Failure to respect these precautions could cause damage to the device.

2.3. Liability

  • Assembly, connection and use must be carried out in accordance with the installation standards currently in force.
  • The device must be installed in accordance with the rules given in this manual.
  • Failure to observe the rules for installing this device may compromise the device's intrinsic protection.
  • The device must be positioned within an installation which complies with the standards currently in force.
  • Any cable which needs to be replaced may only be replaced with a cable having the correct rating.
Page 6

3. PRELIMINARY OPERATIONS

To ensure the safety of personnel and the product, please carefully read the contents of these instructions before installation.

Check the following points as soon as you receive the package containing the device:

  • The packaging is in good condition
  • The device has not been damaged during transportation
  • The device reference number conforms to your order
  • The packaging includes the device fitted with removable terminal blocks and a Quick start guide.
Page 7

4. INTRODUCTION

4.1. Range

PSocomec
PLANE Directory
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLANE CONTRACTOR
PLA
  • ★ SOCOMEC
  • DIES DECEMBENT ALL
  • C EFFECULIENCY CHE DE COLOR
  • C EFFECULIENCY CHE DE COLOR
  • C EFFECULIENCY CHE DE COLOR
  • C EFFECULIENCY CHE DE COLOR
  • C E
Socomec Dets Composition Socomec Soco Proceeding of the second of th
DIRIS D-30
Single-point display
DIRIS Digiware D-40
Multipoint display
DIRIS Digiware D-50
Multipoint display
DIRIS Digiware D-70
Multipoint display
Ref. 4829 0200 Ref. 4829 0199 Ref. 4829 0201 Ref. 4829 0202
- RS485 output
Modbus RTU
Ethernet output
Modbus TCP
Ethernet output
Modbus TCP
BACnet IP
SNMP v1, v2 & v3
- - - Webview embedded web
server Power & Energy
Monitoring

4.2. DIRIS D-30 - introduction

DIRIS D-30 is a local single-point display connected to the measuring device DIRIS B or DIRIS Digiware I-4x via an RJ9 cable (1.50m cable reference: 4829 0280 - 3m cable: 4829 0281). The screen is powered through the RJ9 cable.

Page 8

4.3. Introduction to DIRIS Digiware D

The DIRIS Digiware D-40, D-50 and D-70 displays are shared between DIRIS Digiware meters and measuring devices.

They can also display measurements from other SOCOMEC meters and measuring devices: COUNTIS, DIRIS A, DIRIS B (with the exception of DIRIS Digiware D-40).

They centralise data from up to 32 devices (a maximum of 186 outputs).

These products may be connected by a Digiware bus and/or an RS485 bus.

Centralised products can be shown as well as configured by DIRIS Digiware D displays.

4.3.1. Introduction to DIRIS Digiware D-40

A DIRIS Digiware D-40 display is a slave device on the RS485 bus and master on the DIRIS Digiware bus.

4.3.2. Introduction to DIRIS Digiware D-50

A DIRIS Digiware D-50 display is a master device on the RS485 bus and master on the DIRIS Digiware bus. It is used like an Ethernet gateway.

The Ethernet port is for:

  • Using the Ethernet network in ModbusTCP (max. 4 simultaneous connections) to share all the data taken from the meters and measuring devices connected to its Digiware and RS485 ports.
  • Displaying on DIRIS Digiware D-50 the data taken from remote products connected to the local Ethernet network.

Page 9
4.3.3. Introduction to DIRIS Digiware D-70

A DIRIS Digiware D-70 display is a master device on the RS485 bus and master on the DIRIS Digiware bus. It is used like an Ethernet gateway.

The Ethernet port is for:

  • Sharing on the Ethernet network in ModbusTCP (max. 32 simultaneous connections) all the data taken from the meters and measuring devices connected to its Digiware and RS485 ports.
  • Displaying on the DIRIS Digiware D-70 the data taken from remote products connected to the local Ethernet network
  • Providing the data measured and archived on the embedded web server, Webview
  • Providing the data in protocols SNMP and BACNET IP
  • Automatically exporting data via FTP(s)
  • Automatically sending notification emails via SMTP(s)
  • For archiving data, see the table below
Consumption curves Load curves Measuring logs
Logged data Energy: kWh, kvarh, kVAh Power: kW, kvar, kVA Average measurements:
U, V, I, P, Q, S, PF,
Temperature
Compatible products COUNTIS Exx (all)
DIRIS Axx (all)
DIRIS Bxx (all)
DIRIS Digiware XXX (all)
Countis Eci , Countis E3x
DIRIS A40 + MEM /
A60/A80
DIRIS B-30
DIRIS Digiware I-31 /
I-61 /I-35 / I-45
DIRIS B30
DIRIS Digiware I-35 /
I-45 / U-30
Integration period 10 min to 60 min 1 min to o 60 min
Archiving period in D-70 1 yea
P
For example:
This applies no matter how
level of detail of the loc
ar with a 60-min integration period.
Proportional for different values:
3 months with a 15-min integration period.
w many devices (1 to 32) are connected to the D-70. The
Operation Readings taken every
10 min / 60 min in the
meter/PMD.
The data is recorded in a cache memory on the me
and then downloaded by the D-70. If communicati
is interrupted, the missing data is recovered by th
D-70 once the connection is restored so that record
continues.
Data backup NO YES (in the meter 's cache memory)
Export to the FTP server YES YES YES
Webview link Monitor
Measure
Arms and Events
Analyse
Consumptions
Terms
Monitor
Measures
Measures
Austra and Events
Austra and Events
Consumptions
Vieweds
Specific configuration Nothing to configure (data is recorded automatically). Load curves must be
activated on the meters
(via Easy Config).
Load curves are then
automatically downloaded
from the meter's cache
memory to the D-70.
Measuring logs must be
activated on the meters
(via Easy Config).
The logs are then
automatically downloaded
from the meter's cache
memory to the D-70.
Page 10

Page 11

4.4. Touchscreens

The display consists of a screen and 10 shortcut keys:

IP Shortcut keys for load measurements: current, active power, reactive power, apparent power, power factor, cosinus phi
V F Shortcut keys for electrical network measurements: single voltage, composite voltage, frequency
E Shortcut keys for active, reactive, apparent energy meters (total and partial readings)
Arrow keys for navigation
Use this to go up a level in the display navigation menus
» Use this to go to the previous/next product (to scroll through all your meters and centralised measuring devices)
ОК Use this to confirm your navigation or entry selection

4.5. LED display

  • ALARM
    • Off: no alerts in progress.
    • Solid: alarm (logical/analogue) is active or finished and not reset on one device connected to the display
    • Flashing: system alarm is active on one device connected to the display
  • COM
    • Off: no communication.
    • Flashing: communication in progress on the RS485 and/DIGIWARE bus.
  • ON
  • Off: device is off.
  • On: device working OK.

4.6. Navigation

Page 12

4.7. Menu structure

Menu structure D-30 D-40 D-50
D-70
Load
Load phase-neutral
Phase-phase load
Net. frequency ٠
Net. phase-neutral
Net. phase-neutral unbalanced
Net. phase-neutral THD
Voltages Net. phase-neutral harmonic
Net. phase-neutral crest factor
Net. phase-phase
Net. phase-phase unbalanced
Net. phase-phase IHD
Net. phase-phase harmonic
Net. phase-phase crest factor
Currents
Currents system
Unbalanced currents
Magguramonto Currents Currents THD
weasurements Currents K factor
Currents harmonics
Current crest factor
Active powers
Reactive powers
Apparent powers
Powers Predictive power
Power factors
Ian Phi
Positive active energies
Negative active energies
Energies Positive reactive energies
Ū Negative reactive energies -
Positive/negative inductive/capacitive reactive energies
Apparent energies
RESET all Min/Max values
Enable In progress
Events History Alarms, quality
language
Date format
Digiware Addressing Range
Slave RS485: Baudrate, stop, parity, address
Display Master RS485: Baudrate, stop, parity, address
Ethernet communication: DHCP, IP address, mask, gateway
Setting the date/time on the remote product Date/Time: Activation - manual setting
SNTP (server IP address, server port, time zone, Send settings)
Change password
Parameters Configure a device Network, loads
Autodetect serial devices Status, found devices, address conflicts, start
List products
Add new device Type of device, address
Bemove device
╞══┦
Restore device's factory settings
Device software version
IP address
MAC address
About Serial number
Software version
Reboot

Note: the menus available depend on the product features.

Page 13

4.8. Dimensions

Page 14

5. MOUNTING

5.1. Recommendations and safety

Refer to the safety instructions (section "2. Hazards and warnings", page 5)

5.2. Back-plate mounting

DIRIS D-30 and DIRIS Digiware D are board-mounted (slot: 92x92mm). The display is secured with clips.

Page 15

6. CONNECTION

6.1. DIRIS D-30 - wiring

6.2. DIRIS Digiware D-40 - wiring

6.3. DIRIS Digiware D-50 / D-70 - wiring

Note: DIRIS Digiware D-40 and D-50, class B in radiated power is obtained using ferrites (ref. 4829 0048) on the power cable (two rounds): The ferrites are not supplied with the DIRIS Digiware D-70 which is Class A in radiated power.

(*) 24 VDC 1A fuse if using a non-SOCOMEC supply

Page 16

7. CONFIGURATION

To return to the navigation menu, press "OK" to call up the various menus:

Select the "PARAMETERS" menu by using the navigation key "DOWN ARROW" 3x and confirm with "OK":

HOME 1
I FVFNTS

Enter the password "100" using the arrow pad (4 arrow keys) and confirm with "OK":

🕆 HOME
& LOADS
☑ MEASURES
☑ INPUTS/OUTPUTS
圓! EVENTS
CODE: 100
PARAMETERS
Page 17

You can access 3 main settings:

  • Display-specific settings
  • List of meters and measuring devices to centralise on the DIRIS Digiware D display
  • Settings of the meters and centralised measuring devices

7.1. Specific display settings

When going back to the "DISPLAY" menu, press "OK" to confirm

7.1.1. DIRIS Digiware D-40

To access the various specific display settings:

DISP PARAMETERS
LANGUAGE
DATE FORMAT
DIGIWARE ADDRESSING RANGE
RS485 SLAVE COMMUNICATION
SET REMOTE DEVICE DATE/TIME

• LANGUAGE: to set the display's navigation language

  • DATE FORMAT: to set the date/time format
  • DIGIWARE ADDRESSING RANGE: this setting is described in section "7.2.2. DIRIS Digiware D-40", page 30
  • RS485 SLAVE COMMUNICATION: to set the RS485 bus communication as the slave
  • SET REMOTE DEVICE DATE/TIME: to set the date and time
  • CHANGE PASSWORD: to change the password to access the settings menu (default: "100")
Page 18
7.1.2. DIRIS Digiware D-50 / D-70

To access the various specific display settings:

LANGUAGE $
DATE FORMAT
RS485 COMMUNICATION
ETHERNET COMMUNICATION
SET REMOTE DEVICE DATE/TIME

  • LANGUAGE: to set the display's navigation language
  • DATE FORMAT: to set the date/time format
  • RS485 COMMUNICATION: to set the RS485 bus communication and Digiware as master
  • ETHERNET COMMUNICATION: to set the display's IP address
  • SET REMOTE DEVICE DATE/TIME: to set the date and time
  • CHANGE PASSWORD: to change the password to access the settings menu (default: "100")

7.1.3. Language

You can change the display's navigation language here.

Choose from: English, French, German, Italian, Spanish, Flemish, Polish, Turkish and Chinese.

Select your language with the arrow pad and confirm with "OK".

1

7.1.4. Date format

You can select the display's date format, including the separator between the day, month and year:

DATE FORMAT
DATE FORMAT: MM/DD/YYYY
DATE SEPARATOR: $

7.1.5. RS485 communication

Configure the display's Modbus address.

Configure the baudrate, stop bits, parity of the RS485 and Digiware bus.

Page 19

Caution: these settings must be identical on the RS485 and Digiware buses, which are centralised on DIRIS Digiware D-50 / D-70 displays.

DIRIS Digiware D-40 is a slave device on the RS485 bus and master on the Digiware bus (2 different buses in terms of baudrate, parity, stop bits).

DIRIS D-50 / D-70 are master devices on the RS485 bus (baudrate, parity, stop bits).

BAUDRATE: 38400 ►
STOP: 1BIT
PARITY: NONE
ADDRESS: 001
7.1.6. Ethernet communication

You can configure the Ethernet settings of DIRIS Digiware D-50 / D-70 displays:

  • DHCP (automatic address location via the Ethernet network) ON/OFF
  • IP address
  • Subnet mask
  • LAN gateway
DHCP:
IP ADDRESS: 192.168.000.003
MASK: 255.255.255.000
GATEWAY: 000.000.000
7.1.7. Setting the date/time on the remote product

You can configure the time on the DIRIS Digiware D display:

  • Manually by entering the hour, minute, second, month, day, year
  • Automatically (like a computer) by NTP server (DIRIS Digiware D-50 / D-70 only)

If the D-50/D-70 clock is set by the SNTP, the display sends the date and time to all the meters and measuring devices on the network, to synchronise all your devices.

CONF. DATE/TIME
AUTO. REMOTE DATE/TIME SET ■ MANUAL ► ¢
YEAR 00
MONTH 01
DAY 01
TIME 00
Page 20

To configure the SNTP you need advanced IT knowledge (see your IT Department) to enter the following fields:

SNTP server IP address

SNTP server port

AUTO. REMOTE DATE/TIME SET SNTP ► $
SERVER IP ADDRESS: 000.000.000
SERVER PORT: 00123
TIME ZONE: GMT +9:00
ОК

Configuring meters and centralised measuring devices

You can automatically detect and assign the addresses of the meters and measuring devices connected to the DIRIS Digiware D display.

You can also automatically set the key parameters of the DIRIS Digiware and DIRIS B meters and measuring devices with the DIRIS Digiware D display.

7.1.8. Configuring SNMP - BACNET - FTP - SMTP (DIRIS Digiware D-70)

DIRIS Digiware D-70 devices act as a gateway:

  • Digiware => Ethernet
  • RS485 => Ethernet

Access the data via this Ethernet port in a variety of formats:

  • Modbus TCP
  • SNMP
  • Bacnet IP
  • SMTP(s): Secure or non-secure SMTP: automatic notification emails
  • FTP(s): Secure or non-secure FTP: logged data automatic exported

Bacnet IP, SNMP, SMTP and FTP settings are not accessible via the onscreen interface of the device and are only available on a PC:

  • SNMP => via the configuration software Easy Config which connects via USB or Ethernet to the DIRIS Digiware D-70 (for more, see the notes on Easy Config)
  • Bacnet IP => via the configuration software Easy Config which connects via USB or Ethernet to the DIRIS Digiware D-70 (for more, see the notes on Easy Config)
  • SMTP(s) => via the configuration software Easy Config which connects via USB or Ethernet to the DIRIS Digiware
  • D-70 (for more, see the notes on Easy Config)
  • FTP => via the embedded web interface Webview on the DIRIS Digiware D-70

20 EN

Page 21
7.1.8.1. SNMP

After logging into Easy Config on the DIRIS Digiware D-70, you can find the SNMP settings in the following menu:

-
DIRIS Digiware CONFIG TOOL V2 . 6 J
D-70
Advantian
Band Community Life Ľ
Read Official Community VI
Tran community M1 0
Trap community V1
Read Write Community V2 0
Authentication protocol UNY CONTRACTOR OF
Rounce aconoral na
na
Privacy protocol
Read security username
Read OV-site cerusity uncomme
Read/Minite sectority docting in
Tran configuration Liver Subst
Tran 1 narvar IP address
Tran 1 server port The later of the l 0
Tran 2 server IP address
Trap 2 server port 102 0
Trap report frequency man Second 0
· · 1
New File : DIRIS Digiware D-70 Polie Level : User socomec

• Community configuration SNMP v1 & v2:

Read Community V1: Read-only community string for SNMP v1. Default community string is "public". It allows a manager to retrieve read-only data from a device connected to the D-70.

Read-Write Community V1: Read-Write community string for SNMP v1. Default Read/Write community string is "private".

It allows a manager to change a setting (ex: position of a Digital output) in a device connected to the D-70.

Trap Community V1: The Trap community string allows the manager to receive notifications in case of an event or alarm

Read Community V2: Read-only community string for SNMP v2. Default community string is "publicv2". It allows a manager to retrieve read-only data from a device connected to the D-70.

Read-Write Community V2: Read-Write community string for SNMP v2. Default Read/Write community string is "privatev2". It allows a manager to change a setting (ex: position of a Digital output) in a device connected to the D-70.

SNMP v3 configuration:

Authentication protocol: If SNPM v3 is activated, you can choose an authentication protocol (MD5 or SHA) to hash your password. For no authentication, select "None".

Privacy Protocol: Choose between DES or AES privacy protocols for the encryption of data messages. For no encryption, select "None".

Read security username: Username enabling authentication for read-only functions.

Read authentication & privacy password: Password (also passphrase) accompanying the authentication and privacy protocols, and allowing read-only functions.

The length of the Read-only authentication & privacy password must be between 8 and 16 characters.

Read-Write security username: Username enabling authentication for read and write functions

Read-Write authentication & privacy password: Password (also called passphrase) accompanying the authentication and privacy protocols and allowing read and write functions. The length of the Read-Write authentication & privacy password must be between 8 and 16 characters.

Page 22

• Trap configuration:

Choose to deactivate or activate the traps. For activation, you can choose to broadcast trap notifications to all supervisers on the network or to notify only specific host stations (up to 2).

Trap 1 server IP address: enter the IP address of the 1st host station which will receive trap notifications.

Trap 1 server port: enter the port used to send traps for the 1st host station.

Trap 2 server IP address: enter the IP address of the 2nd host station which will receive trap notifications.

Trap 2 server port: enter the port used to send traps for the 2nd host station.

Trap report frequency: enter the time after which a trap reminder will be sent for on-going alarms. By default, it is set to 60min.

7.1.8.2. Bacnet IP

The PICS file (Protocol Implementation Conformance Statement) is available at www.socomec.com

After logging into Easy Config on the D-70, you can find the BACNET IP settings on the following page:

EASY CONFIG TOOL V2.6
DIRIS Digiware
D-70
O Product Identification
O 1P Configuration
O Naster RS-485 Modb us configuration
SNMP slave configura ation -
Bacnet slave configur ration
Activation No • 0
Virtual network ID 100 0
1
i

Activation: enable or disable the Bacnet IP function

Virtual network ID: set the virtual network ID

The port used by the DIRIS Digiware D-70 for BACnet IP communication is set to 47808 (BAC0 in hexadecimal) and cannot be changed.

7.1.8.3. SMTP(s):

automatic alarm notification emails. Available as standard and secure SMTP.

After logging into Easy Config on the DIRIS Digiware D-70, you can find the SNMP settings on the following page:

smec Easy Config
EASY CONFIG TOOL V2.6
D-70
SMTP server settings (m)
Activation .0
SMTP server IP address or name 0
Security Re • 0
SMTP Port 25 💼 0
Authentification ho • 0
User Name user 0
Password 0
C Email Setting
Source Email Address D70@sicomes.com 0
Destination Email Address 1 0
Destination Email Address 2 0
Destination Email Address 3 0
Language PR. . 0
Criticality Consid . 0
Ninimum Send Frequency Time Constant of the second s 0
Send Test Mail -
New File : DIRIS Digiwere D-70 Profit I. -socomec
Page 23
Setting up the SMTP server

Activation: enable/disable the SMTP email export function

SMTP server IP address or name: IP address of the SMTP server or name (backup for configured DNS server)

Security: enable or disable security (SMTPs)

SMTP Port: enter the standard unencrypted SMTP port

Secured port: enter the port number for a secured connection. Default port number is 465

Authentication: enable or disable SMTP authentication

User name: enter the user name for the authentication

Password: enter the password for the authentication

Email settings:

Source Email Address:: email address shown when sending emails.

Destination Email Address 1: email address #1 to send email notifications to.

Destination Email Address 2: email address #2 to send email notifications to.

Destination Email Address 3: email address #3 to send email notifications to.

Language: language in which emails are sent.

Criticality: set the degree of criticality to email alerts with just a minimum level of criticality.

Minimum send frequency time: Time after which the email notification is sent by the D-70. This limits the number of emails sent by the D-70, especially when the same alarm changes state repeatedly.

7.1.8.4. FTP(s)

Historical measurement data (see "4.3.3. Introduction to DIRIS Digiware D-70", page 9) can be automatically exported via FTP.

Go to the FTP configuration using the embedded web server Webview of the DIRIS Digiware D-70.

FTP system: configure FTP server settings

Planning: set how often data needs to be exported

Page 24
FTP system
Activation Files
Activate FTP • Yes No Destination folder
Activate Logs Ves No data
Activate FTPS 0 File format
Tes NO CSV
Identification FTP server network settings
Site ID Host
SITE 0.0.0.0
CSV
FTP server network set tings
Host
0.0.0.0
Port
21
Secured Port
990
Login
Password
Conne ction test
Activation

Activate FTP: required to activate automatic data export

Activate LOGS: can be useful for troubleshooting in case of a problem

Activate FTPS: activate secure FTP data export

Identification

Site ID and gateway ID: used to identify from which DIRIS Digiware D-70 the files are being exported.

If the file format is configured to "EMS", the site ID must be changed.

Files

Destination folder: tree view of the FTP server folder in which you want to place the files

File format: there are two different types of data file;

  • CSV: file in a .csv format in which data is in a user-friendly layout
  • EMS: file in .csv format whose layout is more practical to integrate into monitoring or energy management software

In EMS mode, the exported files are named according to the following: Site ID Gateway Id Device name Data type date time

Example: if an export file is named socomec_8AD4A2_I35_LoadCurve_2017-08-15_20-00-00.csv, it means it contains Load curves (Demand Power) from a device named I35 from a gateway whose ID is 8AD4A2 and site ID is socomec.

FTP server network settings

This shows the login details for the FTP server (standard or secure).

Host: enter the IP address of your FTP server

Port: enter the non-secure port to use for FTP export

Secured port: enter the secured port to use for FTP(s) export

Login: enter your login

Password: enter your password

Page 25
Planning
Deactivated Every Every 1
Days
Hours 🔽 Hours 0 Minutes
Every Days at 0 Hours 0 Minutes
25 55 5

DIRIS Digiware D-70 devices can log 3 types of data:

  • The energy counters => INDEX
  • The load curves (Demand power) => LOAD CURVES
  • Historical measurements (archived data: I, U, P, FP, T °C...) => TRENDS

Data can also be exported separately, manually specifying their time intervals.

Page 26

7.2. Detecting and addressing

With auto-addressing mode you can have the system automatically assign addresses to devices connected to the DIRIS Digiware D. This mode is only compatible with DIRIS B and Digiware PMDs. The addresses will be allocated manually on the other PMD (DIRIS A) and meters (COUNTIS).

7.2.1. DIRIS Digiware D-50 / D-70

Example of auto-addressing on the D-50 / D-70.

Four products are connected to the D-50 / D-70. Two are addressed correctly, the other two have an identical address

D-50 / D-70
@2
Reconnet ONN Dial Dial 0 100000000 1 10000000 100000000 100000000 1 10000000 500000000 1000000000 1 100000000 5000000000 1000000000000000000000000000000000000

To resolve address conflicts, go to PARAMETERS / AUTODETECT SERIAL DEVICES:

With this function you can detect all the products connected with the Digiware bus and/or the RS485 bus to the DIRIS Digiware D display. This function does not apply to DIRIS D-30.

PARAMETERS
DISPLAY
CONFIGURE A DEVICE
AUTODETECT SERIAL DEVICES $
LIST PRODUCTS
ADD NEW DEVICE

Select "START" then "OK" to start the scan/detection process (this can take up to 3 minutes).

AUTODETECT.
STATUS: STOPPED
FOUND DEVICES 000
ADDR CONFLICTS 000
START $
Page 27

Please be aware that this removes all previously found devices (if they are still there they will be found again).

* AUTODETECT.
DEVICES ALREADY PRESENT!
PRESS OK TO CONTINUE.
PRESS BACK TO CANCEL.

The different stages follow automatically:

• DETECTING ADDRESS

AUTODETECT. ۲
STATUS:
FOUND DEVICES
ADDR CONFLICTS
DETEC. ADDRESS
000
000
STOP 🔷
ADDR SCANNING
AUTODETECT. ×
STATUS: ADDR SCANNI NG
FOUND DEVICES 002
ADDR CONFLICTS 001
STOP $

When the STATUS "STOPPED" appears, the system has ended its search.

The number of found devices is the number of devices that have been correctly located (two in this example). If there is an address conflict (if 10 products have the same address, this is taken as a single conflict, not 10 conflicts), this means multiple products have the same address (two in this example). In this case, assign them individual and unique addresses.

AUTODETECT.
ADDRESS CONFLICTS DETECTED!
PRESS THE AUTOADDRESS BUTTON ON ALL
NON-BLINKING DEVICES TO SOLVE THE CON-
FLICTS.
Page 28

Press "OK".

AUTODETECT. 1
STATUS: SET ADDRESSES
FOUND DEVICES 002
ADDR CONFLICTS 001
STOP 🗢

To go to this address, locate the lit "COM" LED on the front of each product. Press and hold down this button for a few seconds until the LED flashes:

The display now shows the number of detected products increase and the number of conflicts decrease to reach zero once all products have a unique address.

28 EN

Page 29

You can then check the list of found products along with their addresses.

LOAD1
DISPLAY
CONFIGURE A DEVICE
AUTODETECT SERIAL DEVICES
LIST PRODUCTS $
ADD NEW DEVICE

Example:

LIST PROD. LOAD1
Diris U30 ID:545434 @003 ¢
Diris I30 ID:F0C1D2 @004
Diris I30 ID:F0C1D3 @005
Diris I30 ID:F0C1D4 @006
Page 30

You can find the codes on the marking on the products (546434 on U-30 and F0C1D2 on one of the I-30s) in the photo:

We can now configure the products individually.

7.2.2. DIRIS Digiware D-40

7.2.2.1. Addressing range

To avoid a conflict of addresses, first define a range of addresses that can be assigned to auto-detected when products.

Below are some examples of communication architecture.

Page 31

With this communication architecture, each DIRIS Digiware D-40 allocates addresses to the products on its branch, but it ignores addresses of devices from a different branch where there is a potential risk of conflicting addresses! The RS485 communication parameters upstream of the D-40 devices are separate from the Digiware parameters downstream of the D-40 devices. This means that the communication baudrate is also separate, and may vary between the upstream RS485 bus and the downstream Digiware bus.

To avoid these conflicts:

  • The user must first define a different range of addresses for each Digiware D-40 DIRIS branch.
  • The smallest address is assigned to the D-40.
  • The following addresses are assigned to products connected to the D-40.
Page 32

Example address selection:

The user must also take into account the addresses of other products connected to the RS485 network.

Page 33

7.2.2.2. Setting the addressing range

A HOME |
a LUADS
퍧 INPUTS/OUTPUTS
EVENTS
PARAMETERS $

DISPLAY

CONFIGURE A DEVICE

AUTODETECT SERIAL DEVICES

LIST PRODUCTS

ADD NEW DEVICE

PARAM AFF
LANGUAGE
DATE FORMAT
DIGIWARE ADDRESSING RANGE $
RS485 SLAVE COMMUNICATION
CONF. DATE ON REMOTE PRODUCT

DIGIWARE ADDR

START ADDRESS 002 $
END ADDRESS 035
D40 ADDRESS 002
NB ADDR. POSSIBLE 032
APPLY SETTINGS
DIGIWARE ADDR
START ADDRESS 002
END ADDRESS 009 $
D40 ADDRESS 002
NB ADDR. POSSIBLE 007
APPLY SETTINGS
Page 34
START ADDRESS 002
END ADDRESS 009
D40 ADDRESS 002
NB ADDR. POSSIBLE 007
APPLY SETTINGS

7.2.2.3. Auto-addressing

Once the address ranges are configured on the D-40, you can launch the auto-addressing process for connected products.

Example of auto-addressing on the D-40.

Two products are connected to the D-40. They have an identical address.

To resolve address conflicts, go to PARAMETERS / AUTODETECT SERIAL DEVICES:

With this function you can detect all the products connected with the DIGIWARE bus and/or the RS485 bus to the DIRIS Digiware D display.

PARAMETERS
DISPLAY
CONFIGURE A DEVICE
AUTODETECT SERIAL DEVICES $
LIST PRODUCTS
ADD NEW DEVICE
Page 35

Select "START" then "OK" to start the scan/detection process (this can take up to 3 minutes).

AUTODETECT.
STATUS STOPPED
FOUND DEVICES 000
ADDR CONFLICTS 000
DIGIWARE ADDRESSING RANGE 002-009
START 🔶

Caution: this removes all previously found products (if they are still there they will be found again).

* AUTODETECT.
WARNING: AUTODETECT WILL REMOVE ALL DE-
VICES ALREADY PRESENT!
PRESS OK TO CONTINUE.
PRESS BACK TO CANCEL.

Press "OK".

The different stages follow automatically:

• DETECTING ADDRESS

AUTODETECT. 1
STATUS: DETEC. ADDRESS
FOUND DEVICES 000
ADDR CONFLICTS 000
DIGIWARE ADDRESSING RANGE 002-009
STOP ¢

ADDR SCANNING

AUTODETECT.
STATUS: ADDR SCANNING
FOUND DEVICES 000
ADDR CONFLICTS 001
DIGIWARE ADDRESSING RANGE 002-009
STOP $

When the STATUS "STOPPED" appears, the system has ended its search.

The number of found devices is the number of devices that have been correctly located. If there is an address conflict (if 10 products have the same address, this is taken as a single conflict, not 10 conflicts), this means multiple products have the same address (two in this example). In this case, assign them

Page 36

Press "OK". The following screen appears:

AUTODETECT.
STATUS: SET ADDRESSES
FOUND DEVICES 001
ADDR CONFLICTS 001
DIGIWARE ADDRESSING RANGE 002-009
STO P 🔶

To go to this address, locate the lit "COM" LED on the front of each product. Press and hold down this button for a few seconds until the LED flashes:

Page 37

The display now shows the number of detected products increase and the number of conflicts decrease to reach zero once all products have a unique address.

D-40
Range [2-9]
@2
Processes Course and
Digiware bus
U-30 I-30
@3 @4

You can then check the list of found products along with their addresses.

LOAD1
DISPLAY
CONFIGURE A DEVICE
AUTODETECT SERIAL DEVICES
LIST PRODUCTS $
ADD NEW DEVICE

Example:

LIST PROD. LOAD1
Diris U30 ID:545434 @003 🗢
Diris I30 ID:F0C1D2 @004
Page 38

7.3. Configuring each meter and measuring device

You can also set the DIRIS Digiware range and the DIRIS B range with the display.

"Parameters" > "Configure a device".

LOAD1
DISPLAY
CONFIGURE A DEVICE $
AUTODETECT SERIAL DEVICES
ADD NEW DEVICE

There are two stages to electrically configuring the various devices:

  • Network: setting the type of voltage network: single-phase (1P+N), two-phase (2P), three-phase without neutral (3P), three-phase with neutral (3P+N).
  • Load: configuring all the loads/outputs used. You can, for example, have a three-phase network voltage, on which three-phase and single-phase loads are measured.

With DIRIS Digiware U-xx you can configure the network

PROD.
Diris I3 30 ID:FOC1D2 @004
Diris U I30 ID:546434 @006 >
SELECT PROD. Diris U30 ID:5464 434
SELECT PROD. Diris U30 ID:5464 134
SELECT PROD. Diris U30 ID:5464 434
SELECT PROD. Diris U30 ID:5464 134
SELECT PROD. Diris U30 ID:5464 134
Page 39

With DIRIS Digiware I-XX you can configure the loads

With DIRIS B you can configure the network and loads at the same time.

7.3.1. Network configuration

You can configure the various network voltage parameters:

  • Nominal voltage: This is the phase-phase voltage (usually 400 V) for three-phase networks This is the phase-neutral voltage (usually 230 V) for single-phase networks
  • Network type: single-phase (1P+N), two-phase (2P), three-phase without neutral (3P), three-phase+neutral (3P+N)
  • Nominal frequency: 50 or 60 Hz depending on the country
Diris U30 ID:546434
NOMINAL VOLTAGE
NETWORK TYPE
NOMINAL EREQUENCY
00400
3P + N
50HZ
PRESS O K TO CONFIRM 🔶
Page 40

7.3.2. Configuring loads

You can simultaneously measure multiple single-phase, two-phase and three-phase loads on a DIRIS B or DIRIS Digiware display.

7.3.2.1. Example of a load configuration

This example shows a DIRIS Digiware I-30 measuring a three-phase + neutral load using 3 current transducers.

Diris I30 ID:FOC1D2
LINES | |1 12 13
тс 250 A 250 A 250 A 103
DIRECTION +/DIRECT +/DIRECT +/DIRECT
LINE V V3 V2 V1
OUTPUT L1 L1 L1 12
TYPE 3P+N_3CT 3P+N_3CT 3P+N_3CT
PRESS C K TO ENTER SETTINGS

The transducer connected to the current 1 input measures the current of phase 3 (V3)

The transducer connected to the current 2 input measures the current of phase 2 (V2)

The transducer connected to the current 3 input measures the current of phase 1 (V1)

Diris 130 ID:FO C1D2
LINES |1 12 13
TC 250 A 250 A 250 A
DIRECTION +/DIRECT +/DIRECT +/DIRECT
LINE V V3 V2 V1
OUTPUT L1 L1 L1
TYPE 3P+N_3CT 3P+N_3CT 3P+N_3CT
PRESS OK TO ENTER SETTINGS
Page 41

The 3 current inputs I1, I2, I3 are assigned to the same output / three-phase load no. 1 (L1).

Diris I30 ID:FOC1D2
LINES |1 12 13
TC 250 A 250 A 250 A
DIRECTION +/DIRECT +/DIRECT +/DIRECT
LINE V V3 V2 V1
OUTPUT L1 L1 L1
TYPE 3P+N_3CT 3P+N_3CT 3P+N_3CT
PRESS OK TO ENTER SETTINGS

The TC field indicates the type of earth fault connected and the direction shows if it was mounted upright or inverted (upright gives a good overview of the positive powers rather than the negative powers shown when inverted: see +100 kW instead of -100 kW, for example):

Diris I30 ID:FOC1D2
1
LINES | |1 12 13
тс 250 A 250 A 250 A
DIRECTION +/DIRECT +/DIRECT +/DIRECT
LINE V V3 V2 V1
OUTPUT L1 L1 L1
TYPE 3P+N_3CT 3P+N_3CT 3P+N_3CT
PRESS OK TO ENTER SETTINGS

7.3.2.2. Changing the load settings

Following the example above, to change the settings, press "OK".

Diris I30 ID:FOC1D2
LINES 11 12 13
TC 250 A 250 A 250 A
DIRECTION +/DIRECT +/DIRECT +/DIRECT
LINE V V3 V2 V1
OUTPUT L1 L1 L1
TYPE 3P+N_3CT 3P+N_3CT 3P+N_3CT
PRESS OK TO ENTER SETTINGS
Page 42

You can change each parameter to configure each of the loads (the values shown onscreen are shown in bold - see the example below).

  • OUTPUT -> configure load 1: L1 load 2: L2 load 3: L3
  • NAME -> name of the load: LOAD 1 (edit with max. 16 characters)
  • TYPE -> type of load: single-phase (1P+N), two-phase (2P), three-phase (3P), three-phase+neutral (3P+N)
  • I RATED -> set the rated current of the load: 20A (caution: the rated current of the load may differ from the transducer (CT1) used: you can have a 63A transducer monitoring a 20A circuit breaker output.
  • CT1 -> current measured by the transducer: 11 , I2, I3,
Diris I30 ID:FOC1D2
OUTPUT $
NAME LOAD 1
TYPE 3P+N_3CT
I NOMINAL 00020
CT1 11

Go back to "CONFIG CT" to make detailed settings for the current transducer:

Diris I30 ID:FOC1D2
NAME LOAD 1
TYPE 3P+N_3CT
I NOMINAL 00020
CT1 11
CONFIG. CT ¢

Configure:

  • DIRECTION -> Direction of the transducer (+/DIRECT, -/REVERSE)
  • LINE V -> V1, V2, V3 (is the transducer positioned on phase 1, phase 2, phase 3?).
  • TC -> change report. If a transducer is connected to the product, press "DETECT" to configure it automatically

Complete the process by selecting "OK" then "OK" again

CONFIG LINES Diris I30 ID:FOC1D2
DIRECTION +/DIRECT
LINE V V3
тс 0600
DETECT $
ОК
Page 43

If a load is configured as three-phase or three-phase+neutral, for example, you would have to configure multiple current transducers (e.g. 3 transducers for one three-phase load):

CONFIG LINES Diris I30 ID:FOC1D2
CONFIG. CT
CT2 12
CONFIG. CT
CT3 I3
CONFIG. CT

When you have finished configuring the entire load (L1) (type of load, name, rated current, all configured transducers), set the following loads (L2, L3) from the "OUTPUT" line:

4 PARAMETERS Diris I30 ID:FOC1D2
OUTPUT L1 ► ¢
NAME LOAD 1
TYPE 3P+N_3CT
I NOMINAL 00020
CT1 11

For example, a DIRIS Digiware I-30 with 3 current inputs is best for measuring:

  • 1 three-phase load (1 three-phase load L1 using the current inputs I1, I2, I3)
  • 3 single-phase loads (1 L1 single-phase load with a transducer connected to the I1 current input, 1 L2 single-phase load with a transducer connected to the I2 current input, 1 L3 single-phase load with a transducer connected to the I3 current input).

There are a number of other possible load combinations.

When all the outputs/loads are configured (maximum 3 on one DIRIS Digiware I-30), apply your settings by selecting "SEND SETTINGS" and click "OK".

CONFIG LINES Diris I30 ID:FOC1D2
CT3 13
CONFIG. CT
CT4 11
CONFIG. CT
SEND SETTINGS
Page 44

8. USE

Once the loads are configured, you can view the measures of each load on the "MEASURES" menu. You can view active and past alerts on the "EVENTS" menu. If an alert is active, the "ALARM" LED is on.

Page 45

9. SNMP COMMUNICATION WITH THE DIRIS DIGIWARE D-70

9.1. SNMP generalities

SNMP stands for Simple Network Management Protocol and is widely used by administrators for an easy network monitoring of devices on IP networks. It works in a client-server communication mode on an Ethernet physical laver.

Once enabled from the Easy Config configuration software, the DIRIS Digiware D-70 display supports SNMP v1, v2 and v3. The D-70 is an agent SNMP v1, v2, v3 which responds to queries from managers (also called management stations or supervisors).

The D-70 allows access through SNMP of measurement data from SOCOMEC slaves connected via the RS485 bus or the Digiware bus.

Data from the slaves can be reached through a file called "MIB" ("Management Information Base") under a hierarchical and pre-defined structure. The MIB file of the D-70 is named "socomec-diris-products-mib" and is available from www.socomec.com

The file must be uploaded in the Management station managing your metering system.

The Tree structure of the MIB contains multiple OIDs (Object Identifiers). An OID uniquely identifies and labels a managed object (=parameter from metering devices) in the MIB.

For example, the electrical parameter "Current Inst I1" is identified by one OID. "Current Inst I2" is identified by another one.

Common SNMP terms Consumption curves
Agent Corresponds to the D-70: Interface between the PMDs and the manager
Managed device The PMDs connected downstream the D-70 (ex: I-35, DIRIS B, DIRIS A)
MIB Management information base where the OIDs are organized in a hierarchical tree
OID An object identifier that uniquely identifies and labels a managed object in the MIB hierarchy
Community strings A text that enables the authentication between an agent and the manager
Traps Notifications sent by the agent and received by the manager

9.2. SNMP functions supported

There are 4 types of SNMP requests supported by the D-70:

  • GetRequest: to retrieve the variable of an OID (I1 Inst for example)
  • GetNextRequest: to retrieve the variable of the next OID (I2 Inst in this case)
  • GetBulk: to retrieve multiple variables gathered together
  • SetRequest: to change the value of one variable. In the D-70, only used to change the state of a Digital output (for an IO-10 for example).
  • Traps: Unlike the above commands which are initiated by the SNMP manager, Traps are initiated by the Agents with no solicitation from the Manager. Traps are notifications to the Manager by the Agent of the occurrence of an event.

Traps are sent by the agent in case one of the following alarms occurs:

  • Alarm on a measurement
  • Logical alarm (change of status of a Digital input)
  • Combination alarms
  • PQ events (inrush, voltage swells, voltage sags/dips, voltage interruptions)
  • System alarms (Phase Rotation, CT disconnect, VI association)
Page 46

Traps are sent automatically when the alarm occurs. They will be sent again once the "Trap report frequency" time (entered in Easy Config) is elapsed.

The alarm must be activated in the product (using the configuration software Easy Config) in order for the Traps to be sent.

Traps can either be configured for specific hosts or "broadcast" to the whole network. Up to two server IP addresses can be entered in Easy Config for SNMP trap notification of specific hosts.

9.3. SNMP versions supported

The DIRIS Digiware D-70 can use all three versions of SNMP: SNMPv1, v2 and v3.

• SNMPv1 and v2:

The identification is based on Read-only and Read-Write Community passwords. They are non-encrypted and are passed over the network in plaintext.

Both passwords have to be entered in the Agent (D-70) and the Manager and must be identical.

A matching Read Community allows the Get functions to be executed on the agent.

A matching Read-Write Community also allows the Set function to be executed on the agent.

- The default Read Community V1 password is "public" and the default Read-Write Community V1 password is "Private".

- The default Read Community V2 password is "publicv2" and the Read-Write Community V2 is "privatev2".

• SNMPv3:

SNMPv3 uses the USM (User-based Security Module) for controlling access to information available via SNMP. This version offers more security using three important features to prevent the interception and deciphering of data:

  • A username (called security username)
  • MD5 and SHA1 authentication protocols to hash the passwords
  • DES and AES Privacy protocols to encrypt the data
Page 47

9.4. SNMP ports

The D-70 is configured with standard SNMP ports to receive requests and send notifications:

Port Description
161 Used to send and receive requests from the manager.
162 Used by the manager to receive notifications from the agent

9.5. Retrieving data using the D-70 MIB file

The D-70 is compliant with MIB-II defined by the MIB standard RFC 1213 which defines the following structure:

The standard branches are under the same parent branch structure: 1.3.6.1.4.1

The "Private (4)" group enables vendors to define private branches including the MIB OIDs of their own products. Data related to SOCOMEC metering devices is located under the SOCOMEC enterprise category identified by OID 1.3.6.1.4.1.4555. This implies that all queries from a manager to SOCOMEC agents will start by the base path 1.3.6.1.4.1.4555.

Because the Digiware system is a multi-circuit system, the D-70 creates a dynamic table which depends on the products connected downstream compatible with the D-70 and the loads configured on each product. After adding/deleting a downstream device or a load, make sure to update the topology of the D-70 display. This can be done either directly from the display or from Webview:

  • Add or delete a device
  • Refresh the loads

Example: The OID for "Current Inst I1" will return a value for all I-xx, B-xx, DIRIS A etc.. On the contrary, the OID for "THD Inst I1" will return "0" for an I-30 or an I-31 module.

This implies that each OID can be associated with several products and several loads.

Page 48
OID sequence Description
4555 "SOCOMEC" enterprise branch
10 "SocomecProducts" table
20 "ProductMetrology" table
20 "InstantaneousTable"
1 Entry (always = 1)
10000 Service ID

This OID is associated with the multiple devices connected downstream the D-70.

To identify those multiple devices, the Modbus address and the load number are added to the end of the OID.

Example: Let us consider the following architecture:

Product I-30 I-30
Modbus address 4 5
Load type Load 1: 3P + N - 3CT Load 1: 1P + N - 1CT
Load 2: 1P + N - 1CT
Load 3: 1P + N - 1CT

The final OID to get the instantaneous current I1 for the I-30 module @ Modbus address 4 for load 1 is: 1.3.6.1.4.1.4555.10.20.1.10000.4.1

For the I-30 module @ address 5, there are multiple loads configured. This implies that the Modbus address must be followed by the Load number in the OID.

Therefore, the final OID used to request 11 Inst for load 1 of the I-30 @ address 5 is:

1.3.6.1.4.1.4555.10.20.1.10000.5.1

The final OID to request 11 Inst for load 2 of the I-30 @ address 5 is 1.3.6.1.4.1.4555.10.20.1.10000.5.2 The final OID to request 11 Inst for load 3 of the I-30 @ address 5 is 1.3.6.1.4.1.4555.10.20.1.10000.5.3

OID sequence Description
4555 "SOCOMEC" enterprise branch
10 "SocomecProducts" table
20 "ProductMetrology" table
20 "InstantaneousTable"
1 Entry (always = 1)
10000 Service ID
5 Modbus Address
3 Load number

Note: A request to OID 1.3.6.1.4.1.4555.10.20.1.10001.5 will return "0" because only single-phase loads are configured in the I-30 module @ address 5, which means currents I2 and I3 parameters aren't used.

Page 49

10. BACNET COMMUNICATION WITH THE DIRIS DIGIWARE D-70

The DIRIS Digiware D-70 supports the BACnet IP protocol, once enabled from the Easy Config software (see 7.1.8.2).

It acts as a BACnet IP gateway to all devices compatible and connected downstream via RS485 or the Digiware Bus.

The PICS (Protocol Implementation Conformance Statement) of the D-70 is available on the Socomec website at www.socomec.com.

10.1. BACnet Generalities

BACnet provides a method for computer-based control equipment from different manufacturers to be interoperable. BACnet is designed to handle many types of building controls, including HVAC, lighting, security, fire, access control, maintenance, waste management and so forth.

Common terms used in BACnet communication:

Object: Represents a device and its data. Multiple objects type can be available for each device *analog input, binary input...). Each object has a number of properties which fully describe the BACnet object to the network.

Object identifier: Uniquely identifies an object within a BACnet device.

Property: A property describes a BACnet object to the network.

Present value: It is one of the properties of the Analog_Input Object. It represents the current value of an analog input object.

Service: Message type between one BACnet device to another.

BACnet uses a client/server communication mode between devices. Devices communicate between each other using services describing the type of exchange.

A BACnet client is a device that requests a service, and a BACnet server is a device that executes a service. Data inside a BACnet device is organized as a series of objects, each composed of multiple properties.

Ex: the analog_input object defines a property for present_value, a property for average_value etc...

A BACnet client initiates a request to a BACnet server using a service (ex: read_property) to a specific property (ex: present value) contained in a BACnet object (ex: analog input).

10.2. BACnet Objects

BACnet defines a standard set of "Objects", each of which has a standard set of "Properties" describing the object and its current status to other devices on the BACnet internetwork. The properties allow for the object to be controlled by other BACnet devices.

BACnet defines 54 objects. Each element of the building control system is represented by one or more objects. The DIRIS Digiware D-70 supports the below Objects:

Object type Exemple of use
Device To describe the device to the BACnet network.
Analog input Instantaneous current for phase 1 (I1) measured by a DIRIS Digiware I-xx current module with associated current sensor
Binary input Status (ON/OFF) of an auxiliary contact
Binary output Change of status of the output of a DIRIS Digiware IO-20
Page 50

A list of properties defines each BACnet Object. Properties can be:

  • Required by the BACnet specification.
  • Optional. In this case, vendors can choose whether to implement them for their devices.
  • Proprietary. Vendors can add their own created properties.
Device Object:

Every BACnet device compatible with the DIRIS Digiware D-70 must have the Device Object and its associated required properties that fully describe the BACnet device to the network

Example for the Device Object of the DIRIS Digiware D-70:

Property BACnet
Object_Identifier (OID) Required
Object_Name Required
Object_Type Required
System_Status Required
Vendor_Name Required
Vendor_Identifier Required
Model_Name Required
Firmware_Revision Required
Application_Software_
Version
Required
Protocol_Version Required
Protocol_Conformance_
Class
Required
Protocol_Services_
Supported
Required
Protocol_Object_Types_
Supported
Required
Object_List Required
Max_APDU_Length_
Supported
Required
Segmentation_Supported Required
APDU_Timeout Required
Location Optional
Description Optional
Local_Time Optional
Utc_Offset Optional
Local_Date Optional
Daylight_Saving_Status Optional
Active_COV_Subscriptions Optional
Serial_Number Optional
Property_List Optional
Version_Build_Date Proprietary
Operating_Hour_Counter Proprietary
Page 51

The way the OID is assigned to a device (instance number) is the following:

OID = Main OID (= default 100) + ModbusAddress

  • Device with Main OID (100) is the D-70 display itself
  • The device with OID (1xx) is the device with the Modbus address xx.
Analog Input Object:

The DIRIS Digiware D-70 acts as a BACnet gateway. It provides a number of Analog Input objects which may be available from the devices compatible and connected to the D-70. Whether a device supports an AI object depends on its measurement functionalities.

Ex: The OID for THD_I1 will return 0 for a DIRIS Digiware I-30 module because this parameter is not handled.

The AI object defines 25 properties. The devices compatible and connected downstream the D-70 support the following properties:

Property BACnet
Object_Identifier Required
Object_Name Required
Object_Type Required
Present_Value Required
Status_Flags Required
Event_State Required
Out_Of_Service Required
Units Required
Description Optional
Reliability Optional
Min_Pres_Value Optional
Minimum_Value_
Timestamp
Optional
Max_Pres_Value Optional
Maximum_Value_
Timestamp
Optional
Average_Value Optional
Instantaneous_Timestamp Proprietary
Average_Timestamp Proprietary
Max_Average_Value Proprietary
Max_Average_Timestamp Proprietary
Min_Average_Value Proprietary
Min_Average_Timestamp Proprietary
Harmonics_Row_02 Proprietary
Harmonics_Row_03 Proprietary
Harmonics_Row_04 Proprietary
Harmonics_Row_05 Proprietary
Harmonics_Row_06 Proprietary
Harmonics_Row_07 Proprietary
Harmonics_Row_08 Proprietary
Harmonics_Row_09 Proprietary
Harmonics_Row_10 Proprietary
Page 52
Energy_Total_Residual Proprietary
Energy_Total_Hourmeter Proprietary
Energy_Partial Proprietary
Energy_Partial_Residual Proprietary
Energy_Partial_Hourmeter Proprietary
Energy_Total_Lagging Proprietary
Energy_Total_Lagging_Res Proprietary
Energy_Total_Leading Proprietary
Energy_Total_Leading_Res Proprietary
Energy_Last_Partial Proprietary
Energy_Last_Partial_Res Proprietary
Energy_Last_Partial_
Timestamp
Proprietary
Multifluid_Partial Proprietary
Multifluid_Weight Proprietary
Instant_Min_Max_Reset Proprietary
Average_Min_Max_Reset Proprietary

The way the OID is assigned to an Analog Input Object (instance number) is the following: OID = LLMM

• with LL = Load # of the device (starting at 1)

• with MM = Index of the measurement type (see Analog Input Measurement List).

For example, Analog Input with OID 204 reflects Phasis/Neutral Voltage V1 of Load 2 of corresponding device.

The table with indexes of the analog input measurement list is given below:

Index Object Namew Object Description Unit Type Present
+ Timestamp
Present Min/Max
+ Timestamp
Average
+ Timestamp
Average Min/Max
+ Timestamp
Harmonics
2 -> 10
Energies Total +
Partial + LastPartial
Energies Total
Lagging/Leading
Multifluid Reset Min/Max
0 VystPhN System Ph-N
Voltage
V Unsigned
1 VystPhPh System Ph-Ph
Voltage
V Unsigned
2 CurrentSyst System Current А Unsigned ٠
3 Frequency System
Frequency
Hz Unsigned
4 VoltPhNV1 Ph-N Voltage V1 V Unsigned ٠
5 VoltPhNV2 Ph-N Voltage V2 V Unsigned ٠
6 VoltPhNV3 Ph-N Voltage V3 V Unsigned ٠
7 VoltPhNVn Ph-N Voltage Vn V Unsigned ٠
8 VoltPhPhU12 Ph-Ph Voltage
U12
V Unsigned
9 VoltPhPhU23 Ph-Ph Voltage
U23
V Unsigned
Page 53
10 VoltPhPhU31 Ph-Ph Voltage
U31
V Unsigned ٠ ٠ ٠
11 Currentl1 Current I1 А Unsigned ٠ ٠ ٠
12 Currentl2 Current I2 А Unsigned ٠ ٠ ٠
13 Currentl3 Current I3 А Unsigned ٠ ٠ ٠
14 CurrentIn Current In А Unsigned ٠ ٠ ٠
15 CurrentInba Current Inba % Unsigned ٠
16 CurrentIdir Current Idir А Unsigned ٠
17 Currentlinv Current linv А Unsigned ٠
18 Currentlhom Current Ihom А Unsigned ٠
19 CurrentInb Current Inb % Unsigned ٠
20 PowerApparentNom Nominal
Apparent Power
VA Unsigned ٠
21 TotalPowerActive Total Active
Power
W Signed ٠
22 TotalPowerRActive Total Reactive
Power
VAr Signed
23 TotalPowerApparent Total Apparent
Power
VA Unsigned
24 TotalPowerFactor Total Power
Factor
- Signed ٠
25 TotalPowerFactorType Total Power
Factor Type
- Unsigned ٠
26 PowerActiveP1 P1 Active Power W Signed
27 PowerActiveP2 P2 Active Power W Signed ٠
28 PowerActiveP3 P3 Active Power W Signed
29 PowerRActiveQ1 Q1 Reactive
Power
VAr Signed
30 PowerRActiveQ2 Q2 Reactive
Power
VAr Signed ٠
31 PowerRActiveQ3 Q3 Reactive
Power
VAr Signed ٠
32 PowerApparentS1 S1 Apparent
Power
VA Unsigned ٠
33 PowerApparentS2 S2 Apparent
Power
VA Unsigned ٠
34 PowerApparentS3 S3 Apparent
Power
VA Unsigned ٠
35 PowerFactorPF1 PF1 Power
Factor
- Signed ٠
36 PowerFactorTypeSPF1 sPF1 Power
Factor Type
- Unsigned ٠
37 PowerFactorPF2 PF2 Power
Factor
- Signed
38 PowerFactorTypeSPF2 sPF1 Power
Factor Type
- Unsigned ٠
39 PowerFactorPF3 PF3 Power
Factor
- Signed ٠
40 PowerFactorTypeSPF3 sPF1 Power
Factor Type
- Unsigned ٠ ٠
41 LoadCurve_
P+
Load Curve
Positive Active
Power
W Unsigned ٠
42 LoadCurve_P- Load Curve
Negative Active
Power
W Unsigned ٠
Page 54
43 LoadCurve_
Q+
Load Curve
Positive Reactive
Power
VAr Unsigned ٠
44 LoadCurve_Q- Load Curve
Negative
Reactive Power
VAr Unsigned ٠ ٠
45 LoadCurve_S Load Curve
Apparent Power
VA Unsigned ٠ ٠
46 THD_I1 THD I1 % Unsigned ٠ ٠ ٠
47 THD_I2 THD I2 % Unsigned ٠ ٠ ٠
48 THD_I3 THD I3 % Unsigned ٠ ٠ ٠
49 THD_In THD In % Unsigned ٠ ٠ ٠
50 THD_V1 THD V1 % Unsigned ٠ ٠ ٠
51 THD_V2 THD V2 % Unsigned ٠ ٠ ٠
52 THD_V3 THD V3 % Unsigned ٠ ٠
53 THD_U12 THD U12 % Unsigned ٠ ٠ ٠
54 THD_U23 THD U23 % Unsigned ٠ ٠ ٠
55 THD_U31 THD U31 % Unsigned ٠ ٠ ٠
56 A+ Positive Active
Energy
Wh Unsigned ٠
57 A- Negative Active
Energy
Wh Unsigned ٠ ٠
58 ER+ Positive Reactive
Energy
VArh Unsigned ٠ ٠ ٠
59 ER- Negative
Reactive Energy
VArh Unsigned ٠ ٠ ٠
60 ES Apparent Energy VAh Unsigned ٠ ٠
61 Mff Multifluid feeder - Signed ٠ ٠

10.3. BACnet Services

The services define methods for BACnet devices to communicate and exchange data with one another. The D-70 supports the following services:

Service list Description
readProperty Used by a BACnet device (the client) to ask another BACnet device (the server) to provide the value of one of its object properties
readPropertyMultiple Used by a BACnet device (the client) to ask another BACnet device (the server) to provide the values of multiple object properties
writeProperty Used by a BACnet device (the client) to ask another BACnet device (the server) to change the value of one of its object properties
timeSynchronization Used to broadcast the current time to one or more BACnet servers
who_Has Asks which BACnet devices contain a particular Object
who_ls Used by a BACnet client to ask the presence of BACnet servers
Page 55

11. CHARACTERISTICS

11.1. DIRIS D-30 and DIRIS Digiware D-40/D-50/D-70 - characteristics

11.1.1. Mechanical features

Type of screen Capacitive touch-screen technology, 10 keys
Screen resolution 350 x 160 pixels
Front panel protection index IP65
Weight of the DIRIS D-30 / DIRIS Digiware D-40/D-
50/D-70
160g / 180g

11.1.2. DIRIS D-30 communication characteristics

Type of screen Local single-point screen for DIRIS Digiware I-4x and DIRIS B
RJ9 Self-powered and data
USB Upgrade and configuration via type B micro USB connector

11.1.3. DIRIS Digiware D-40 communication characteristics

Type of screen Multipoint remote screen
RJ45 Digiware Control and power supply interface function
RS485 2-3 wires Modbus RTU slave communication function
USB Upgrade and configuration via type B micro USB connector

11.1.4. DIRIS Digiware D-50 communication characteristics

Type of screen Multipoint remote screen
Ethernet RJ45 10/100 Mbs Modbus TCP gateway function (max.4 simultaneous connections)
RJ45 Digiware Control and power supply interface function
RS485 2-3 wires Modbus RTU master communication function
USB Upgrade and configuration via type B micro USB connector

11.1.5. DIRIS Digiware D-70 communication characteristics

Type of screen Multipoint remote screen
Ethernet RJ45 10/100 Mbs
(use a shielded Ethernet cable)
Gateway function:
- Modbus TCP (max. 32 simultaneous connections)
- Webview embedded web server (Power & Energy Monitoring version)
- BACnet IP
- SNMP v1, v2 & v3
SNTP protocol Updates the screen from an NTP server.
The display updates the connected devices.
SMTP protocol(s) Sends email notifications from the display.
FTP protocol(s) Automatically exports data via FTP standard or secure server (consumption curves, load curves, measurement logs)
RJ45 Digiware Control and power supply interface function
RS485 2-3 wires Modbus RTU master communication function
USB Upgrade and configuration via type B micro USB connector
Page 56

11.1.6. Electrical characteristics

Power supply 24 VDC +10% / -20%
Power consumption 2 VA
Battery life (D-70 only) 3 days

11.1.7. Environmental specifications

Storage temperature -20 to +70°C
Operating temperature -10 to +55°C
Humidity 95% at 40°C
Installation category - degree of pollution CAT III, 2
Page 57
Page 58

______________________________________

Loading...