socomec DIRIS Am Operating Instructions Manual

Page 1
DIRIS Am
Notice d’utilisation Operating instructions
Bedienungsanleitung Istruzioni per l’uso
Gebruiksaanwijzing Instrucciones de servicio
Manual de instruções
GB
ID
E
NL
P
Systèmes de Coupure et de Protection
Switching and Protection Systems
Page 2
F
Sommaire
OPERATIONS PREALABLES_____________________4 INFORMATIONS GENERALES ___________________4 PRESENTATION ________________________________5 INSTALLATION _________________________________6 PROGRAMMATION____________________________10 UTILISATION__________________________________21 COMMUNICATION (option)_____________________23 CARACTERISTIQUES TECHNIQUES ____________29
GB
Contents
PRELIMINARY OPERATIONS___________________32 GENERAL INFORMATION______________________32 PRESENTATION _______________________________33 INSTALLATION ________________________________34 CONFIGURATION _____________________________38 OPERATION___________________________________49 COMMUNICATION (optional) ___________________51 TECHNICAL CHARACTERISTICS _______________57
D
Inhaltsverzeichnis
VORAUSGEHENDE KONTROLLEN______________60 ALLGEMEINE HINWEISE _______________________60 PRODUKTDARSTELLUNG _____________________61 INSTALLATION ________________________________62 KONFIGURATION _____________________________66 BETRIEB______________________________________77 KOMMUNIKATION (Option) ____________________79 TECHNISCHE DATEN__________________________85
I
Sommario
OPERAZIONI PRELIMINARI ____________________88 INFORMAZIONI GENERALI ____________________88 PRESENTAZIONE _____________________________89 INSTALLAZIONE ______________________________89 PROGRAMMAZIONE __________________________94 UTILIZZO ____________________________________105 COMMUNICAZIONE (Opzione) ________________107 CARATTERISTICHE TECNICHE________________113
Page 3
4 SOCOMEC - Réf. : 875 508 A
Au moment de la réception du colis contenant le DIRIS Am, il est nécessai- re de vérier les points suivants:
l’état de lemballage,
le produit n’a pas eu de dommage
pendant le transport,
Nota:
Pour la sécurité du personnel et du matériel, il est impératif de bien s’im­prégner du contenu de cette notice avant la mise en service.
la référ ence de lappareil est confor­me à votre commande,
le produit est équipé de 2 caches bornes,
une notice dutilisation.
OPÉRATIONS PRÉALABLES
INFORMATIONS GÉNÉRALES
avant (clavier de 6 touches et affi­cheurs rétroéclairé en option) de configurer et de visualiser tous les paramètres et dexploiter les fonc­tions de:
FONCTIONS
Le Diris Am est un appareil de multi­mesures des grandeurs électriques pour réseaux monophasés, biphasés et triphasés basse tension et haute tension. Il permet à partir de sa face
maximums sur une période pro­grammable (5 à 60 min.),
de la puissance apparente par pha­se et totale en valeurs instantanées, moyennes et maximums sur une période programmable (5 à 60 min.),
du Facteur de Puissance (PF) par phase et total avec l'indication L pour inductif et C pour capacitif.
des courants par phase et du neutre instantanés, moyens et maximums sur une période pro­grammable (5 à 60 min.),
des tensions simples et composées;
de la fréquence (Hz),
de la puissance active sur 4 qua-
drants (+/-) par phase et totale en valeurs instantanées, moyennes et maximums sur une période pro­grammable (5 à 60 min.),
de la puissance réactive sur 4 qua­drants (+/-) par phase et totale en valeurs instantanées, moyennes et
COMPTAGE HORAIRE
Compteur en 1/100 d'heure pour la durée de fonctionnement avec remi­se à zéro.
OPTIONS
Les options sont intégrées dusine et sont décomposées de la manière sui­vante:
Comptage des énergies: Le comptage d'énergie active (0 à 99 999 999 kWh) et réactive (0 à 99 999 999 kvarh) sur 4 quadrants et de l'énergie apparente (0 à 99 999 999 kVAh). On peut égale- ment utiliser deux sorties impul-
Nota:
Les compteurs peuvent être remis à zéro à partir de la conguration (accès limité par code secret).
sions congurables sur le type d'é- nergie, le poids (0,1, 1, 10, 100 kWh, kvarh ou kVAh et 1 ou 10 MWh, Mvarh et MVAh) et la durée (100 ms
à 900 ms).
Communication
Une liaison série RS485 (2 ou 3 ls) protocole JBUS/MODBUS permet une exploitation à partir dun PC ou dun API.
MESURE EN VALEURS EFFICACES VRAIES (TRMS)
Page 4
SOCOMEC - Réf. : 875 508 A 5
FRANÇAIS
SOCOMEC - Réf. : 875 508 A 5
Le DIRIS Am est intégré dans un boî- tier modulaire 7 modules. Pour facili­ter son utilisation, il est équipé dun afcheur et dun clavier.
1 Afficheur LCD (rétroéclairage en
option)
2 Clavier composé de 6 boutons
poussoirs à double fonctionnalités (visualisation ou conguration)
PRÉSENTATION
2
1
DIRIS 245 B
Page 5
6 SOCOMEC - Réf. : 875 508A
BORNIERS
Le DIRIS Am est composé de bornes de raccordement de 1 à 6 mm
2
(câbles souples) et de 1,5 à 10 mm
2
CONSIGNES DE SÉCURITÉ (U, I ET F)
Pour éviter toutes détériorations de lappareil, il est nécessaire avant de le raccorder de veiller à respecter :
les indications sur la face arrière du boîtier
la tension dalimentation : 110 à 440 V AC ou 120 à 350 V DC avec une tolérance de +/- 10 %
Nota:
Nous conseillons de protéger l’ali- mentation et les entrées tension à partir de fusibles gG de 0,5 A.
Nota:
Le couple de serrage maximum de chaque vis est de 0,4 Nm.
la fréquence du réseau 50 ou 60 Hz
une tension maximum aux bornes
des entrées tension de 700 V AC phase/phase ou de 404 V AC entre phases/neutre.
un courant maximum de 6 A (rac­cordement à partir de transforma­teur(s) de courant).
RACCORDEMENT
RÉSEAU TRIPHASÉ DÉSÉQUILIBRÉ (4 FNE)
DIRIS 272 A
DIRIS 273 A
Le DIRIS Am s’installe sur rail DIN, sur une platine ou en façade darmoire à partir dun kit de fixation spécifique (nous consulter).
Recommandations:
L’installer à une distance dau moins 30 cm dun appareil de coupure (interrupteurs, contacteurs,...),
Éviter la proximité avec des sys­tèmes générateurs de perturbations
électromagnétiques,
• Éviter les vibrations comportant des
accélérations supérieures à 1 G pour des fréquences inférieures à 60 Hz.
INSTALLATION
ENVIRONNEMENT CLIMATIQUE
Pour garantir un fonctionnement opti­mal, il est recommandé d’utiliser cet appareil de -10 °C à 55 °C avec une humidité relative comprise entre 20 et
95%. Lappareil en fonctionnement supporte une température ambiante de
- 15 °C.
(câbles rigides) pour les courants, les tensions, l'alimentation auxiliaire et les options.
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
V1 V2 V3 VN AUX
110 à 440 V AC 120 à 350 V DC
FUSIBLES 0,5 A
L1 (R
L2 (S
L3 (T
N
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
V1 V2 V3 VN AUX
aaa
AAA
110 à 440 V AC 120 à 350 V DC
L1 (R
L2 (S
L3 (T
N
)
)
)
Page 6
SOCOMEC - Réf. : 875 508 A 7
FRANÇAIS
Nota:
La solution avec 2 TC diminue de 0,5 % la précision de la phase dont le courant est déduit par calcul vectoriel.
DIRIS 274 A
DIRIS 275 A
DIRIS 276 A
DIRIS 277 A
RÉSEAU TRIPHASÉ ÉQUILIBRÉ (4 FE)
RÉSEAU TRIPHASÉ DÉSÉQUILIBRÉ (3 FNE)
Nota:
La solution avec 1 TC diminue de 0,5 % la précision des phases dont le courant est déduit par calcul vectoriel.
DIRIS 280 A
DIRIS 281 A
I2 I3I1
S2 S1 S2 S1 S2S1
V1 V2 V3 VN AUX
I2 I3I1
S2 S1 S2 S1 S2S1
V1 V2 V3 VN AUX
110 à 440 V AC 120 à 350 V DC
FUSIBLES 0,5 A
S1
P1
L1 (R
L2 (S
L3 (T
N
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
V1 V2 V3 VN AUX
110 à 440 V AC 120 à 350 V DC
FUSIBLES 0,5 A
L1 (R
L2 (S
L3 (T
)
)
)
aaa
aaa
AAA
S1
P1
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
AAA
V1 V2 V3 VN AUX
aaa
AAA
110 à 440 V AC 120 à 350 V DC
L1 (R
L2 (S
L3 (T
N
110 à 440 V AC 120 à 350 V DC
L1 (R
L2 (S
L3 (T
)
)
)
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
V1 V2 V3 VN AUX
110 à 440 V AC 120 à 350 V DC
FUSIBLES 0,5 A
L1 (R
L2 (S
L3 (T
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
V1 V2 V3 VN AUX
aaa
AAA
110 à 440 V AC 120 à 350 V DC
L1 (R
L2 (S
L3 (T
)
)
)
Page 7
8 SOCOMEC - Réf. : 875 508 A
RÉSEAU TRIPHASÉ ÉQUILIBRÉ (3 FE)
RESEAU BIPHASÉ (2 FE) RESEAU MONOPHASÉ (1 FE)
Recommandations:
Lors dune déconnexion du DIRIS, il est indispensable de court-circuiter les secondaires de chaque transfor­mateur de courant. Cette manipula­tion peut se faire automatiquement à partir dun produit du catalogue SOCOMEC: le PTI. Pour plus dinfor­mations sur ce produit, merci de nous consulter.
DIRIS 283 A
DIRIS 282 ADIRIS 285 A
DIRIS 284 A
DIRIS 278 A
DIRIS 279 A
RESEAU TRIPHASÉ DÉSÉQUILIBRÉ (3 FNE) SUITE
Nota:
La solution avec 1 TC diminue de 0,5 % la précision des phases dont le courant est déduit par calcul vectoriel.
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
V1 V2 V3 VN AUX
110 à 440 V AC 120 à 350 V DC
FUSIBLES 0,5 A
L1 (R
L2 (S
L3 (T
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
V1 V2 V3 VN AUX
110 à 440 V AC 120 à 350 V DC
FUSIBLES 0,5 A
L1 (R
L2 (S
L3 (T
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
)
)
)
)
)
)
V1 V2 V3 VN AUX
aaa
AAA
V1 V2 V3 VN AUX
aaa
AAA
110 à 440 V AC 120 à 350 V DC
110 à 440 V AC 120 à 350 V DC
L1 (R
L2 (S
L3 (T
L1 (R
L2 (S
L3 (T
)
)
)
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
V1 V2 V3 VN AUX
110 à 440 V AC 120 à 350 V DC
FUSIBLES 0,5 A
L1 (R
L2 (S
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
V1 V2 V3 VN AUX
FUSIBLES 0,5 A
110 à 440 V AC 120 à 350 V DC
)
L1 (R
N
Page 8
SOCOMEC - Réf. : 875 508 A 9
FRANÇAIS
SORTIES À ÉMETTEUR DIMPULSIONS (OPTION DUSINE)
Nota:
La durée de vie de ce relais est de 10
8
manœuvres.
Le DIRIS Am met à disposition à par­tir de 2 relais (100 V - 0,5 A - 10 VA) une impulsion pour l'énergie active, réactive et apparente. Le poids et la durée sont congurables (voir § pro­grammation).
COMMUNICATION (OPTION D’USINE)
Recommandations:
Il est nécessaire dutiliser une paire torsadée blindée type LIYCY. Dans un environnement perturbé ou sur un réseau important en longueur et en nombre de DIRIS, nous conseillons dutiliser 2 paires blindées avec un blindage général type LIYCY-CY. Dans ce cas, une paire est utilisée pour le + et le – et une autre pair e, dont les 2 fils sont court-circuités, pour le 0 V. Si la distance de 1500 m ou/et le nombre de 31 DIRIS sont dépassés, il est nécessaire de raccorder un répé- teur (1 voie) ou un éclateur (4 voies) pour permettre un raccordement sup­plémentaire de DIRIS Am sur plus de 1500 m. Pour plus dinformations sur la méthodologie de raccordement merci de nous consulter.
Nota:
Aux 2 extrémités de la liaison, il est indispensable de xer une résistance de 120 ohms qui se trouve sur le DIRIS Am.
Dautres solutions existent (modem, bre optique,). Merci de nous consulter.
Dans une conguration standard, une liaison RS485 permet de mettre en relation 31 DIRIS Am avec un PC ou un automate sur 1500 mètres à partir du protocole JBUS/MODBUS®.
DIRIS 109 BDIRIS 110 B
1500 M
Automates
programmables
Autres systèmes
R = 120
N° 1 N° 2 N° n
R = 120
Automates
programmables
Autres systèmes
R = 120
1500 M 1500 M
N° 1
0+- -+0
répéteur
RS485
N° n
R = 120
Page 9
10 SOCOMEC - Réf. : 875 508 A
ENTRER EN MODE PROGRAMMATION
PROGRAMMATION
1
PROGRAMMATION DU TYPE DE RESEAU (NETWORK)2
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Appuyez pendant au moins 3 secondes, puis relâchez
Appuyez une fois
Appuyez une fois Pour faire clignoter 4NBL
Appuyez une fois
Validez sur et pas­sez à la programmation du réseau (NETWORK)
Nota: Il est nécessaire de saisir le code secret 100 pour pouvoir programmer cet appareil en procédant de la façon suivante:
Nota: Par défaut, le réseau est conguré en 4NBL (4 ls non équilibrés avec 3 TC). Si vous souhaitez le conserver, appuyez sur . Vous accéderez à la ligne de programmation (CT). Sinon, procédez comme suit:
Appuyez une fois
Une nouvelle fois pour: 2BL 3BL 3NBL 4BL
Appuyez une fois
Une nouvelle fois pour: 3NBL 3BL 2BL 1BL
ou
PROG
Page 10
SOCOMEC - Réf. : 875 508 A 11
FRANÇAIS
PROGRAMMATION DU TRANSFORMATEUR DE COURANT (CT)
3
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, le transformateur de courant est conguré en 500/5. Si vous souhaitez le conser ver, appuyez sur ▼. Vous accéderez à la ligne de programmation du transformateur de tension (VT). Sinon, procédez comme suit:
Appuyez une fois
Validation du type. Appuyez sur ▼ pour programmation du CT
Appuyez une fois
Appuyez autant de fois que nécessaire pour se déplacer vers la droite ou sur pour se déplacer vers la gauche
Appuyez deux fois Pour faire clignoter le 2
e
digit
Appuyez une fois Pour incrémenter le 2
e
digit
Appuyez une fois Pour valider le rapport.
Appuyez sur
pour pro-
grammer le VT
Sur pour décrémenter ou sur pour incrémenter la valeur du digit sélectionné. Une fois pour valider la valeur. Une fois pour passer à la programmation du VT.
Nota: les 5 premiers digits correspondent à la valeur du primaire du transformateur (1 à 10000) et le dernier à la valeur du secondaire du transformateur (1 ou 5 A).
Exemple: programmation de 1500/5 une fois entré dans le menu CT.
Page 11
12 SOCOMEC - Réf. : 875 508 A
PROGRAMMATION DU TRANSFORMATEUR DE TENSION (VT)4
PROGRAMMATION DU TRANSFORMATEUR DE TENSION (VT)
5
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, le réseau est conguré sans transformateur de tension (NO). Si vous n'en souhaitez pas, appuyez sur ▼. Vous accéderez à la programmation du temps d'intégration (TIME 3I). Sinon, procédez comme suit:
Appuyez une fois Pour faire clignoter NO
Appuyez une fois Pour programmer lutilisa-
tion dun VT.
Appuyez une fois
Appuyez autant de fois que nécessaire pour se déplacer vers la droite ou sur pour se déplacer vers la gauche
Appuyez une fois
Validation d’un VT. Appuyer sur ▼ pour programmer le rapport du VT
Sur pour décrémenter ou sur pour incrémenter la valeur du digit sélectionné. 1 fois sur pour valider la valeur 1 fois sur pour passer à la programmation (TIME 3I).
Nota: les 6 digits correspondent à la valeur du primaire (maximum 400 000 V) et les 3 derniers à la valeur du secondaire (60, 100, 110, 173 et 190 V).
Nota: Par défaut, le rapport est conguré à 100/100. Pour le modier, procédez comme suit:
PROGRAMMATION DU TEMPS D'INTEGRATION DES COURANTS (TIME 3I)6
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota:Par défaut, le temps est programmé à 15 minutes (3I 15). Si vous souhaitez le conserver , appuyez sur ▼. V ous accé- derez à la ligne de programmation du temps d'intégration des puissances (TIME P/Q/S). Sinon, procédez comme suit:
Appuyez une fois
Pour faire clignoter 15 minutes
Page 12
SOCOMEC - Réf. : 875 508 A 13
FRANÇAIS
Appuyez une fois
Une nouvelle fois pour: 30, 60, 5, 8, 10 et 15 minutes
Appuyez une fois
Une nouvelle fois pour: 8, 5, 60, 30, 20 et 15 minutes
Appuyez une fois
Validation du temps. Appuyez sur pour pro­grammer le temps din­tégration des puissances (TIME P/Q/S)
PROGRAMMATION DU TEMPS D'INTEGRATION DES PUISSANCES (TIME P/Q/S)7
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, le temps est programmé à 15 minutes (P/Q/S 15). Si vous souhaitez le conserver, appuyez sur . Vous accéderez à la ligne de programmation des remises à zéro (RSET). Sinon, procédez comme suit:
Appuyez une fois
Pour faire clignoter 15 minutes
ou
Appuyez une fois
Une nouvelle fois pour: 30, 60, 5, 8, 10 et 15 minutes
Appuyez une fois
Une nouvelle fois pour: 8, 5, 60, 30, 20 et 15 minutes
Appuyez une fois
Validation du temps. Appuyez sur pour pro­grammer la remise à zéro (RSET)
ou
Page 13
14 SOCOMEC - Réf. : 875 508 A
PROGRAMMATION DES REMISES A ZERO (RSET)8
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, le paramètre est le courant (MAX 3I). Si vous ne souhaitez pas faire de remises à zéro, appuyez sur ▼. Vous accéderez à la programmation du type de réseau (NETWORK) ou à la programmation de la sortie impulsion numé- ro 1 (Option). Sinon, procédez comme suit:
Appuyez une fois Pour faire clignoter MAX 3I
Appuyez une fois
Une nouvelle fois pour: MAX P-, MAX Q, MAX Q-, MAX S, TIME, EA, ER, ES, EA-, ER
-
Appuyez une fois
Une nouvelle fois pour: EA-, ES, ER, EA, TIME, MAX S, MAX Q-, MAX Q, MAX P-, MAX P
Appuyez une fois Pour faire clignoter NO
ou
Appuyez une fois YES pour remise à zéro
Appuyez une fois
Validation du paramètre. Appuyez sur pour pas­ser à la programmation du type OUT 1.
Nota: EA, ER et ES apparaissent si le module énergies est connecté.
Page 14
SOCOMEC - Réf. : 875 508 A 15
FRANÇAIS
PROGRAMMATION DU TYPE DE LA SORTIE N°1 (OUT 1 EA) (OPTION)9
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, le type est l'énergie active (EA) et le poids est de 10 kWh (10). Si vous souhaitez conserver ces para- mètres, appuyez sur . Vous accéderez à la programmation de la durée impulsion (DUR). Sinon, procédez comme suit:
Nota: Si vous souhaitez valider le type et conser ver un poids de 10 kWh (10), appuyez sur , sinon procédez comme suit:
Appuyez une fois Pour faire clignoter EA
Appuyez une fois
Une nouvelle fois pour: ES, EA-, ER-et EA
Appuyez une fois
Une nouvelle fois pour: EA-, ES, ER et EA
Appuyez une fois
Pour faire clignoter 10
Appuyez une fois
Une nouvelle fois pour 1000; 10000; 0,1; 1 et 10
Appuyez une fois
Une nouvelle fois pour 0,1; 10000; 1000; 100 et 10
Appuyez une fois
Validation du paramètre. Appuyer sur pour pas­ser à la programmation de la durée (OUT 1 DUR)
ou
ou
Page 15
16 SOCOMEC - Réf. : 875 508 A
PROGRAMMATION DE LA DURÉE DE LA SORTIE IMPULSIONS N°1 (OUT 1 DUR) (OPTION)10
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, la durée est à 100 ms (DUR 100). Si vous souhaitez la conserver, appuyez sur . Vous accéderez à la ligne de programmation de la sortie impulsion numéro 2 (OUT 2). Sinon, procédez comme suit :
Appuyez une fois Pour faire clignoter le 1
er
digit
Appuyez une fois
Une nouvelle fois pour: 300, 400, 500, 600, 700, 800 et 900 ms
Appuyez une fois
Une nouvelle fois pour: 800, 700, 600, 500, 400, 300 et 200 ms
Appuyez une fois
Validation du temps. Appuyez sur pour pro­grammer le type de la 2
e
sortie (OUT 2)
PROGRAMMATION DU TYPE ET DU POIDS DE LA SORTIE N°2 (OUT2 EA) (OPTION)11
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, le type est l'énergie active (EA) et le poids est de 10 kWh (10). Si vous souhaitez conserver ces para- mètres, appuyez sur . Vous accéderez à la durée dimpulsion (DUR). Sinon, procédez comme suit:
ou
Appuyez une fois Pour faire clignoter EA
Appuyez une fois
Une nouvelle fois pour: ES, EA-, ER-et EA
Appuyez une fois
Une nouvelle fois pour: EA-, ES, ER et EA
ou
Page 16
SOCOMEC - Réf. : 875 508 A 17
FRANÇAIS
Appuyez une fois
Pour faire clignoter 10
Appuyez une fois
Une nouvelle fois pour 1000; 10000; 0,1; 1 et 10
Appuyez une fois
Une nouvelle fois pour 0,1; 10000; 1000; 100 et 10
Appuyez une fois
Validation du paramètre. Appuyer sur pour pas­ser à la programmation de la durée (OUT 2 DUR)
ou
PROGRAMMATION DE LA DURÉE DE LA SORTIE IMPULSIONS N°2 (OUT 2 DUR) (OPTION)12
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, la durée est à 100 ms (DUR 100). Si vous souhaitez la conserver, appuyez sur ▼. Vous accéderez à la ligne de programmation du réseau (NETWORK) ou de la communication (option). Sinon, procédez comme suit :
Appuyez une fois Pour faire clignoter le 1
er
digit.
Appuyez une fois
Une nouvelle fois pour: 300, 400, 500, 600, 700, 800 et 900 ms
Appuyez une fois
Une nouvelle fois pour: 800, 700, 600, 500, 400, 300 et 200 ms
Appuyez une fois
Validation du temps. Ap­puyez sur
pour program­mer la communication (modu­le communication connecté) ou retour à la programmation du réseau (NETWORK).
ou
Nota:Si vous souhaitez valider le type et conserver un poids de 10 kWh (10), appuyez sur , sinon procédez comme suit:
Page 17
18 SOCOMEC - Réf. : 875 508 A
PROGRAMMATION DE L’ADRESSE DE COMMUNICATION (COM ADR) (OPTION)13
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, l'adresse est 5 (ADR 5). Si vous souhaitez la conserver, appuyez sur . Vous accéderez à la pro- grammation de la vitesse de communication (COM BDS). Sinon, procédez comme suit:
Appuyez une fois
Pour faire clignoter le 1
er
digit (2 et 3 fois pour le 2
e
et le 3e) ou sur pour revenir vers la gauche
Sur pour décrémenter ou sur pour incrémenter la valeur du digit sélectionné; 1 fois sur pour valider; 1 fois sur pour passer à la programmation de la vitesse (COM BDS).
Nota: ladresse peut varier de 1 à 255.
PROGRAMMATION DE LA VITESSE DE COMMUNICATION (COM BDS) (OPTION)
14
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, la vitesse est à 9600 BDS (BDS 9600). Si vous souhaitez la conser ver, appuyez sur ▼. Vous accé- derez à la programmation de la parité (COM PAR). Sinon, procédez comme suit :
Appuyez une fois
Une nouvelle fois pour: 38400, 2400, 4800 et 9600 bauds
Appuyez une fois
Pour faire clignoter 9600 bauds
Appuyez une fois
Une nouvelle fois pour: 2400, 38400, 19200 et 9600 bauds
Appuyez une fois
Validation de la vitesse. Appuyez sur pour pro­grammer la parité (PAR)
ou
Page 18
SOCOMEC - Réf. : 875 508 A 19
FRANÇAIS
Appuyez une fois Pour aucune parité
Appuyez une fois
Une nouvelle fois pour: EVEN (parité paire) et NO (sans parité)
Appuyez une fois
Une nouvelle fois pour: ODD (parité impaire) et NO (sans parité)
PROGRAMMATION DE LA PARITÉ DE COMMUNICATION (COM PAR) (OPTION)15
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, la communication est sans parité (PAR NO). Si vous souhaitez la conserver, appuyez sur . Vous accéderez à la programmation du bit de stop de communication (COM STOP). Sinon, procédez comme suit:
ou
Appuyez une fois
Validation de la parité. Appuyez sur pour pro­grammer le bit de stop (STOP)
PROGRAMMATION DU BIT DE STOP DE COMMUNICATION (COM STOP) (OPTION)16
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Nota: Par défaut, le bit de stop est à 1 (STOP 1). Si vous souhaitez le conserver, appuyez sur ▼. Vous reviendrez à la programmation du type de réseau (NETWORK). Sinon, procédez comme suit:
Appuyez une fois Pour faire clignoter un bit
de stop
Appuyez une fois 1 pour 1 bit et 2 pour 2
bits
Appuyez une fois
Validation du bit de stop. Appuyez sur ▼ pour revenir au type de réseau.
ou
Page 19
20 SOCOMEC - Réf. : 875 508 A
POUR QUITTER LA PROGRAMMATION17
TOUCHE INSTRUCTIONS MESSAGE REMARQUE
Appuyez au moins pendant 3 secondes, puis relâchez
L’affichage reviendra auto- matiquement sur les cou­rants.
PROG
Page 20
SOCOMEC - Réf. : 875 508 A 21
FRANÇAIS
AFFICHEUR
UTILISATION
CLAVIER
I: Visualisation des courants instantanés et moyens par pressions successives ou défilement vers la gauche en conguration ( )
U/F: Visualisation des tensions simples et composées et de la fréquence par pres-
sions successives
ou défilement vers la droite en conguration ( )
Il est composé de 6 boutons poussoirs à double fonctionnalités (visualisation ou conguration).
Type
Valeur
Phase
Unité
Type
Valeur
Phase
Unité
Page 21
22 SOCOMEC - Réf. : 875 508 A
P/Q/S: Visualisation de la puissance active, réactive et apparente sur 4 quadrants par phase et totale ainsi que des valeurs moyennes totales par pressions successives
ou
défilement vers le bas en conguration
()
PF: Visualisation du facteur de puissance inductif ou capacitif par phase et total par pressions successives
ou défilement vers le haut en conguration ()
MAX: Visualisation des valeurs maximums pour les 3 courants et les 3 puissances totales sur 4 quadrants
ou validation des paramètres en conguration ()
h/E: Visualisation du compteur horaire et des énergies (option) par pressions succes- sives
ou entrée/ sortie de la programmation (PROG)
Page 22
SOCOMEC - Réf. : 875 508 A 23
FRANÇAIS
COMMUNICATION (OPTION)
DIRIS Am communique à partir d'un protocole JBUS/MODBUS®qui im­plique un dialogue selon une structure maître/esclave. Deux dialogues sont possibles:
le maître dialogue avec un esclave (DIRIS Am) et attend sa réponse
le maître dialogue avec tous les esclaves (DIRIS Am) sans attendre leur réponse.
La trame de communication standard est composée de:
Le mode de communication est le mode RTU (Remote Terminal Unit) avec des caractères hexadécimaux composés au minimum de 8 bits.
Adresse de l’esclave Code de la fonction Adresse Données CRC 16
Conformément au protocole JBUS/MODBUS®, le temps interca­ractère doit être inférieur à 3 silences, cest-à-dire au temps d'émission de 3 caractères pour que le message soit traité par le DIRIS®.
Nota:
En sélectionnant ladresse de lesclave 0, on transmet un message à tous les appareils présents sur le réseau (uni­quement pour les fonctions 6 et 16).
Pour exploiter correctement les infor­mations, il est indispensable dutiliser les fonctions:
3: pour la lecture de n mots (maxi-
mum 128).
6: pour l’écriture dun mot. 8:pour le diagnostic des échanges
entre le maître et l'esclave à par­tir des compteurs 1, 3, 4, 5 et 6.
16: pour l’écriture de n mots (maxi-
mum 128).
LISTE DES PARAMÈTRES À VISUALISER (FONCTION 3)
TABLEAU DES VALEURS AFFECTÉES DES RAPPORTS DE TRANSFORMATION COURANT ET TENSION
Adresse Adresse Nombre Libellé Unité
Déc. Hex. de mots
768 300 2 courant phase 1 mA 770 302 2 courant phase 2 mA 772 304 2 courant phase 3 mA 774 306 2 courant du neutre mA 776 308 2 tension composée U12 V/100 778 30A 2 tension composée U23 V/100 780 30C 2 tension composée U31 V/100 782 30E 2 tension simple phase 1 V/100 784 310 2 tension simple phase 2 V/100 786 312 2 tension simple phase 3 V/100 788 314 2 Fréquence Hz/100 790 316 2
Puissance active +/- kW/100
792 318 2
Puissance réactive +/- kvar/100
794 31A 2
Puissance apparente +/- kVA/100
796 31C 2
Facteur de puissance
0,001
-: capacitif et + : inductif 798 31E 2 Puissance active phase 1 +/- kW/100 800 320 2 Puissance active phase 2 +/- kW/100 802 322 2 Puissance active phase 3 +/- kW/100 804 324 2 Puissance réactive phase 1 +/- kvar/100
806 326 2 Puissance réactive phase 2 +/- kvar/100 808 328 2 Puissance réactive phase 3 +/- kvar/100 810 32A 2 Puissance apparente phase 1 kVA/100 812 32C 2 Puissance apparente phase 2 kVA/100 814 32E 2 Puissance apparente phase 3 kVA/100 816 330 2 Facteur de puissance phase 1
-: capacitif et + : inductif
0,001
818 332 2 Facteur de puissance phase 2
-: capacitif et + : inductif
0,001
Page 23
24 SOCOMEC - Réf. : 875 508 A
Exemple: Pour visualiser toutes les valeurs du DIRIS numéro 5 en une seule interro­gation, il est nécessaire denvoyer la trame suivante:
Esclave
05
Fonction
03
Adresse
poids fort
03
Adresse
poids faible
00
Nombre de mots
poids fort
00
Nombre de mots
poids faible
62
CRC 16
C5E3
Taille de cette zone: 98 mots en décimale ou 62 en hexadécimale.
Adresse Adresse Nombre Libellé Unité
Déc. Hex. de mots
820 334 2 Facteur de puissance phase 3
-: capacitif et + : inductif
0,001
822 336 2 Valeur moyenne I1 mA 824 338 2 Valeur moyenne I2 mA 826 33A 2 Valeur moyenne I3 mA 828 33C 2
Puissance active + moyenne kW/100 830 33E 2 Puissance active - moyenne kW/100 832 340 2 Puissance réactive + moyenne kvar/100 834 342 2 Puissance réactive - moyenne kvar/100 836 344 2 Puissance apparente moyenne kVA/100 838 346 2 Valeur maximale I1 mA 840 348 2 Valeur maximale I2 mA 842 34A 2 Valeur maximale I3 mA 844 34C 2
Puissance active + maximale kW/100 846 34E 2 Puissance active - maximale kW/100 848 350 2 Puissance réactive + maximale kvar/100 850 352 2 Puissance réactive - maximale kvar/100 852 354 2 Puissance apparente maximale kVA/100 854 356 2 Compteur horaire 1/100 h 856 358 2 Energie active + kWh 858 35A 2 Energie réactive + kvarh 860 35C 2 Energie apparente kVAh 862 35E 2 Energie active - kWh 864 360 2 Energie réactive - kvarh
Page 24
FRANÇAIS
SOCOMEC - Réf. : 875 508 A 25
Adresse Adresse Nombre Libellé Unité
Déc. Hex. de mots 1792 700 1 courant phase 1 mA 1793 701 1 courant phase 2 mA 1794 702 1 courant phase 3 mA 1795 703 1 courant du neutre mA 1796 704 1 tension composée U12 V/100 1797 705 1 tension composée U23 V/100 1798 706 1 tension composée U31 V/100 1799 707 1 tension simple phase 1 V/100 1800 708 1 tension simple phase 2 V/100 1801 709 1 tension simple phase 3 V/100 1802 70A 1 Fréquence Hz/100 1803 70B 1
Puissance active +/- kW/100
1804 70C 1
Puissance réactive +/- kvar/100
1805 70D 1
Puissance apparente +/- kVA/100
1806 70E 1
Facteur de puissance L/C
-: capacitif et + : inductif
0,001
1807 70F 1 Puissance active phase 1 +/- kW/100 1808 710 1 Puissance active phase 2 +/- kW/100 1809 711 1 Puissance active phase 3 +/- kW/100 1810 712 1 Puissance réactive phase 1 +/- kvar/100 1811 713 1 Puissance réactive phase 2 +/- kvar/100 1812 714 1 Puissance réactive phase 3 +/- kvar/100 1813 715 1 Puissance apparente phase 1 kVA/100 1814 716 1 Puissance apparente phase 2 kVA/100 1815 717 1 Puissance apparente phase 3 kVA/100 1816 718 1 Facteur de puissance phase 1
-: capacitif et + : inductif
0,001
1817 719 1 Facteur de puissance phase 2
-: capacitif et + : inductif
0,001
1818 71A 1 Facteur de puissance phase 3
-: capacitif et + : inductif
0,001
1819 71B 1 Valeurs moyennes I1 mA 1820 71C 1 Valeurs moyennes I2 mA 1821 71D 1 Valeurs moyennes I3 mA 1822 71E 1
Puissance active + moyenne kW/100 1823 71F 1 Puissance active - moyenne kW/100 1824 720 1 Puissance réactive + moyenne kvar/100 1825 721 1 Puissance réactive - moyenne kvar/100 1826 722 1 Puissance apparente moyenne KVA/100 1827 723 1 Valeur maximale I1 mA 1828 724 1 Valeur maximale I2 mA 1829 725 1 Valeur maximale I3 mA 1830 726 1
Puissance active + maximale kW/100 1831 727 1 Puissance active - maximale kW/100 1832 728 1 Puissance réactive + maximale kvar/100 1833 729 1 Puissance réactive - maximale kvar/100 1834 72A 1 Puissance apparente maximale kVA/100 1835 72B 1 Energie active + < 10000 kWh 1836 72C 1 Energie active + > 10000 kWh 1837 72D 1 Energie réactive + < 10000 kvarh 1838 72E 1 Energie réactive + > 10000 kvarh 1839 72F 1 Energie apparente < 10000 kVAh 1840 730 1 Energie apparente > 10000 kVAh 1841 731 1 Energie active - < 10000 kWh 1842 732 1 Energie active - >10000 kWh 1843 733 1 Energie réactive - < 10000 kvarh 1844 734 1 Energie réactive - > 10000 Kvarh
TABLEAU DES VALEURS NON AFFECTÉES DES RAPPORTS DE TRANSFORMATION COURANT ET TENSION
Nota:
Les valeurs doivent être multipliées par un coefficient:
TC = 100 = 20 TP = 20000 = 200
5 100
TC x TP = 20 x 200
= 4000
Les puissances seront multipliées par 4000 (si pas de TP, alors TP = 1), les courants par 20 et les tensions par
200.
Taille de cette zone: 53 mots en décimale ou 35 en hexadécimale.
Page 25
26 SOCOMEC - Réf. : 875 508 A
Exemple: Pour visualiser toutes les valeurs du DIRIS numéro 5 en une seule interro­gation, il est nécessaire denvoyer la trame suivante:
Esclave
05
Fonction
03
Adresse
poids fort
07
Adresse
poids faible
00
Nombre de mots
poids fort
00
Nombre de mots
poids faible
35
CRC 16
852D
LISTE DES PARAMÈTRES À VISUALISER OU À CONFIGURER (FONCTION 3, 6 OU 16)
Adresse Adresse Nombre Libellé Unité
Déc. Hex. de mots
512 200 1 Type de réseau: /
0: 1BL 1: 2BL 2: 3BL
3:3NBL
4:4BL
5: 4NBL
513 201 1 Secondaire du TC: A
1: 1 A
5: 5 A 514 202 1 Primaire du TC A 515 203 1 Entrée tension sur TP: /
0 : No
1: Yes 516 204 2 Primaire du TP V 518 206 1 Secondaire du TP: V
60: 60 V 100: 100 V 110: 110 V 173: 173 V 190: 190 V
519 207 1 Synchronisation de I AVG/MAX: /
5 :5 minutes
8: 8 minutes 10: 10 minutes 15: 15 minutes 20: 20 minutes 30: 30 minutes 60: 60 minutes
520 208 1 Synchronisation de /
P/Q/S AVG/MAX :
5 : 5 minutes
8 : 8 minutes 10 : 10 minutes 15 : 15 minutes 20 : 20 minutes
30: 30 minutes 60: 60 minutes
521 209 1 Affectation de OUT 1 /
0 : kWh +
1 : kvarh +
2 : kVAh
3: kWh –
4 : kvarh -
522 20A 1 Poids d'impulsions OUT1: /
0 : 0,1 kWh/kvarh/kVAh
1 : 1 kWh/kvarh/kVAh
2 : 10 kWh/kvarh/kVAh
3: 100 kWh/kvarh/kVAh
4: 1000 kWh/kvarh/kVAh
5: 10000 kWh/kvarh/kVAh
Page 26
SOCOMEC - Réf. : 875 508 A 27
FRANÇAIS
523 20B 1 Durée d'impulsions OUT1: /
1 : 100 ms 2 : 200 ms 3 : 300 ms 4 : 400 ms 5 : 500 ms 6 : 600 ms 7 : 700 ms 8 : 800 ms 9 : 900 ms
524 20C 1 Affectation de OUT 2: /
0 : kWh +
1 : kvarh +
2 : kVAh
3: kWh –
4 : kvarh -
525 20D 1 Poids d'impulsions OUT 2: /
0 : 0,1 kWh/kvarh/kVAh
1 : 1 kWh/kvarh/kVAh
2 : 10 kWh/kvarh/kVAh
3: 100 kWh/kvarh/kVAh
4: 1000 kWh/kvarh/kVAh
5: 10000 kWh/kvarh/kVAh
526 20E 1 Durée d'impulsions OUT 2 : /
1 : 100 ms 2 : 200 ms 3 : 300 ms 4 : 400 ms 5 : 500 ms 6 : 600 ms 7 : 700 ms 8 : 800 ms 9 : 900 ms
Esclave
05
Fonction
06
Adresse
poids fort
02
Adresse
poids faible
00
Nombre de mots
poids fort
00
Nombre de mots
poids faible
05
CRC 16
49F5
Exemple: Conguration dun réseau 4 ls non équilibré (4 LNB) pour le DIRIS numéro 5.
Taille de cette zone: 15 mots ou F hexadécimale
Réponse du DIRIS Am: identique au message envoyé
Page 27
28 SOCOMEC - Réf. : 875 508 A
Exemple: Pour remettre à zéro toutes les va- leurs du DIRIS numéro 5, il est néces­saire denvoyer la trame suivante:
Réponse du DIRIS Am: identique au message envoyé
COMMANDE SAUVEGARDE (RESET)
Après avoir modifié les paramètres de programmation et pour les enregis­trer dans le DIRIS numéro 5, il est nécessaire de programmer cette commande.
Nota:
Le DIRIS Am ne répond pas à cet­te commande.
Nota:
Pour remettre à zéro plusieurs para­mètres, il est nécessaire daddition­ner le chiffre correspondant indiqué dans la colonne «Libellé». Exemple : Remise à zéro de Max P+ et kvarh + : 2 + 100 = 102 (Hex)
Esclave
05
Fonction
06
Adresse
poids fort
04
Adresse
poids faible
00
Nombre de mots
poids fort
10
Nombre de mots
poids faible
00
CRC 16
84BE
Esclave
05
Fonction
06
Adresse
poids fort
06
Adresse
poids faible
00
Valeur
0000
CRC 16
88C6
Adresse Adresse Nombre Libellé Unité
Déc. Hex. de mots Hex.
1024 400 1 R.A.Z. de: /
Max3I : 1
MaxP+ : 2
MaxP- : 4
MaxQ+ : 8
MaxQ- : 10
MaxS : 20
Compteur horaire : 40
kWh+ : 80
kvarh+ : 100
kVA : 200
kWh- : 400
kvarh- : 800
tous les paramètres : 1000
REMISE À ZÉRO DES COMPTEURS D’ÉNERGIES ET DES VALEURS MAX. (FONCTION 6)
Taille de cette zone: 1 mot ou 1 hexadécimale
Page 28
FRANÇAIS
SOCOMEC - Réf. : 875 508 A 29
CARACTÉRISTIQUES TECHNIQUES
BOITIER
AFFICHEUR
MESURES
Dimensions: 7 modules (7 x 18 mm) Raccordement: 1 à 6 mm2(câbles souples) et
1,5 à 10 mm2(câbles rigides)
Indice de protection: Face avant IP40 et
boîtier IP20
Poids: 640 g
Type: LCD haute luminosité (en option rétroéclairage)
Réseau triphasé (3 ou 4 ls), biphasé (2 ls) et monophasé
TENSION (TRMS)
Mesure directe :
Phases/phases: de 0 à 700 V AC Phase/neutre: de 0 à 404 V AC
Mesure à partir de TP:
Primaire: jusqu'à 400 kV
Secondaire: 60, 100, 110, 173 et 190 V AC
Afchage de 0 à 400,0 kV Surcharge permanente entre phases: 760 V AC Période d'actualisation: 1 s
COURANT (TRMS)
A partir du TC avec un:
Primaire: jusqu’à 10000 A
Secondaire: 1 ou 5 A
Consommation des entrées: 0,1 VA Afchage: de 0 à 11 kA (1,1 fois la valeur du primaire) Surcharge permanente : 6 A Surcharge intermittente : 10 In pendant 1 s Période d'actualisation: 1 s Rapport maximum TC x TP: 2 000 000
PUISSANCES
Par phase: 0 à 1660 MW/Mvar/MVA Totales: 0 à 8000 MW/Mvar/MVA Période d'actualisation: 1 s FRÉQUENCE: de 45,0 à 65,0 Hz Période d'actualisation: 1 s
PRÉCISION DES MESURES
Courants: 0,5 % de 10 à 110 % de In Tensions: 0,5 % de 140 à 700 V AC Puissances: 1 % de la pleine échelle (-90°à +90°) Facteur de Puissance: 1 % pour 0,5 < FP < 1 Fréquence: 0,1 Hz de 45 à 65 Hz Comptage de l'énergie active :
+/- 1% de 0,02 à 1,2 In avec PF = 0,5 L ou 0,8 C (classe 1 CEI 61036)
Comptage de l’énergie réactive:
+/- 2% de 0,1 à 1,2 In avec sinϕ = 0,5 L ou C (classe 2 CEI 61268)
Page 29
30 SOCOMEC - Réf. : 875 508 A
ALIMENTATION AUXILIAIRE
110 à 440 V AC en 50/60 Hz +/- 10 % 120 à 350 V DC: +/- 20 % Consommation: 10 VA Autre version: 18 à 100 V DC (+/-10%)
SORTIES IMPULSIONS
Relais reed: (100 V DC - 0,5 A - 10 VA) Nombre de manœuvres: 10
8
COMMUNICATION
RS 485: 2 ou 3 ls half duplex Protocole: JBUS/MODBUS®mode RTU Vitesse: de 2400 à 38400 Bauds
ISOLATION GALVANIQUE (tension disolement AC)
Alimentation auxiliaire: 4 kV Entrées tension: 1,5 kV Entrées courant: 1,5 kV Liaison série: 1,5 kV Sortie impulsions: 1,5 kV
CONDITIONS DUTILISATION
Température de fonctionnement: -10°C à +55°C (14°F à 131°F) Température de stockage: -20°C à +85°C (-4°F à 158 °F) Humidité relative: 95 %
NORMES
Comptage: IEC 61036 classe 1
IEC 61268 classe 2
Marquage CE: IEC 61000-4/2-3-4-5-6-8-11
EN 50081-1 EN 50082-2
Environnement: IEC 60068-2/6-11
Page 30
SOCOMEC - Réf. : 875 508 A 31
FRANÇAIS
Page 31
32 SOCOMEC - Ref. : 875 508A
Check the following points as soon as you receive the Diris Am package:
the packing is in good condition,
the product has not been damaged
during transit,
the product reference number conforms to your order,
NB:
For personnel and product safety please read the contents of these operating instructions carefully before connecting.
the package contains the product fitted with a fixed current terminal as well as a pull-out terminal block for the auxiliary supply and voltage inputs,
operating instructions.
PRELIMINARY OPERATIONS
GENERAL INFORMATION
play all the parameters and use the functions provided to carry out the following:
FUNCTIONS
The Diris Am is an instrument for measuring and metering electrical values for single, two and three-pha­se LV/HV electrical networks. From the front panel (6 keys and LED dis­plays) you can programme and dis-
instantaneous, average and maxi­mum apparent power S over a pro­grammable integration time (5 to 60 min.),
instantaneous and maximum power factor PF with L (inductive) and C (capacitive) indications.
instantaneous, average and maxi­mum current over a programmable integration time (5 to 60 min.),
phase to neutral and phase to pha­se voltage,
frequency,
instantaneous, average and maxi-
mum active power P on 4 display quadrants (L/C/+/-) over a program­mable integration time (5 to 60 min.),
instantaneous, average and maxi­mum reactive power Q on 4 display quadrants (L/C/+/-) over a program­mable integration time (5 to 60 min.),
HOUR RUN METER
Metering in 1/100th of an hour for operating time, with reset to zero.
OPTIONS
Options are factory set and are avai­lable as follows:
Energy metering
Active (0 to 99 999 999 kWh) and reactive energy metering on 4 qua­drants. Two programmable pulse outputs can be used for active, reactive or apparent energy mete­ring, with a programmable value (0.1, 1, 10, 100 kWh, kvarh or kVAh
NB:
Meters can be programmed to reset to zero (programme access via access code).
and 1 or 10 MWh, Mvarh and MVAh) and duration (100 ms to 900 ms).
Communication
An RS485 serial link (2 or 3 wires) with JBUS/MODBUS protocol for use with a PC or PLC.
TRMS (TRUE ROOT MEAN SQUARED) MEASUREMENT
Page 32
SOCOMEC - Ref. : 875 508A 33
ENGLISH
SOCOMEC - Ref. : 875 508A 33
The Diris Am is housed in a modular case. The self-adjusting display and 6 key-pad make it a truly user-friend­ly instrument.
1 LED display (with back-lit option)
2 Key-pad with 6 dual-function keys
(display or programming)
PRESENTATION
2
1
DIRIS 245 B
Page 33
34 SOCOMEC - Ref. : 875 508A34 SOCOMEC - Réf. : 875 508A
TERMINALS
The Diris Am consists of 1 - 6 mm
2
(exible wires) and 1.5 - 10 mm2(rigid) connection terminals for current, volta-
SAFETY INSTRUCTIONS (U, I AND F)
To avoid damage to the device plea­se ensure the following points are respected before connecting:
the connections follow the diagram shown on the rear of the device,
the indications on the rear face of the case,
power supply: 110 to 440 V AC or
NB:
The use of BS 88 2A gG fuses is recommended for power supply and voltage input protection.
NB:
The maximum coupling torque for each screw is 0.4 Nm.
120 to 350 V DC (+/- 10 %),
50 or 60 Hz network,
maximum 700 V AC phase/phase
for input terminals or 404 V AC bet­ween phases/neutral,
6A maximum current (via current transformer[s]).
CONNECTION
UNBALANCED THREE-PHASE NETWORK (4 LNB)
DIRIS 272 A GB
DIRIS 273 A GB
The Diris Am is fitted on a DIN rail onto a panel or on the front of a control panel with a special mounting kit. (Please contact us for more infor­mation)
Recommendations:
Install the Diris Am at least 30 cm from a switching device (switch, contactor, etc.)
Avoid proximity to systems which generate electromagnetic interfe­rence
Avoid vibrations with accelerations in excess of 1 G for frequencies below 60 Hz.
INSTALLATION
CLIMATIC ENVIRONMENT
To guarantee optimal operation, it is recommended to use this equip­ment at -10° to 55 °C with relative humidity between 20 and 95 %. During operation, the instrument
can tolerate an ambient temperatu­re of - 15 °C.
ge, auxiliary supply and other options.
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
V1 V2 V3 VN AUX
110 to 440 V AC
120 to 350 V DC
FUSES 2 A
L1 (R
L2 (S
L3 (T
N
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
V1 V2 V3 VN AUX
aaa
AAA
110 to 440 V AC 120 to 350 V DC
L1 (R
L2 (S
L3 (T
N
)
)
)
Page 34
SOCOMEC - Ref. : 875 508A 35
ENGLISH
SOCOMEC - Ref. : 875 508A 35
NB:
The solution with 2 CT with the cur­rent calculated via vectoral summa­tion results in an 0.5% reduction in phase accuracy, of which current is deducted vectorially.
DIRIS 274 A GB
DIRIS 275 A GB
DIRIS 276 A GB
DIRIS 277 A GB
BALANCED THREE-PHASE NETWORK (4 LB)
UNBALANCED THREE-PHASE NETWORK (3 LNB)
NB:
The solution using one CT with the current calculated via vectoral sum­mation, results in an 0.5% reduction in phase accuracy, of which current is deducted vectorially.
DIRIS 280 A GB
DIRIS 281 A GB
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
V1 V2 V3 VN AUX
110 to 440 V AC 120 to 350 V DC
FUSES 2 A
L1 (R
L2 (S
L3 (T
N
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
V1 V2 V3 VN AUX
aaa
aaa
AAA
AAA
110 to 440 V AC 120 to 350 V DC
L1 (R
L2 (S
L3 (T
N
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
I2 I3I1
S2 S1 S2 S1 S2S1
V1 V2 V3 VN AUX
110 to 440 V AC 120 to 350 V DC
FUSES 2 A
V1 V2 V3 VN AUX
L1 (R
L2 (S
L3 (T
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
I2 I3I1
S2 S1 S2 S1 S2S1
V1 V2 V3 VN AUX
aaa
AAA
110 to 440 V AC 120 to 350 V DC
V1 V2 V3 VN AUX
L1 (R
L2 (S
L3 (T
)
)
)
110 to 440 V AC 120 to 350 V DC
FUSES 2 A
S1
P1
S1
P1
L1 (R
L2 (S
L3 (T
)
)
)
S1
P1
S1
P1
aaa
AAA
110 to 440 V AC 120 to 350 V DC
)
L1 (R
)
L2 (S
)
L3 (T
Page 35
36 SOCOMEC - Ref. : 875 508A
BALANCED THREE-PHASE NETWORK (3 LB)
TWO-PHASE NETWORK (2 LB) SINGLE-PHASE NETWORK (1 LB)
Recommendations:
Each CTs secondary winding must be short-circuited when disconnec­ting the Diris Am. This can be done automatically using one of Socomec’s catalogue products: the PTI. Please contact us for further information.
DIRIS 283 A GB
DIRIS 282 A GBDIRIS 285 A GB
DIRIS 284 A GB
DIRIS 278 A GB
DIRIS 279 A GB
UNBALANCED THREE-PHASE NETWORK (3 LNB)
NB:
The solution using one CT, with the 3rd phase current calculated via vec­toral summation, results in an 0.5% reduction in phase accuracy.
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
V1 V2 V3 VN AUX
110 to 440 V AC 120 to 350 V DC
FUSES 2 A
L1 (R
L2 (S
L3 (T
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
V1 V2 V3 VN AUX
110 to 440 V AC 120 to 350 V DC
FUSES 2 A
S1
P1
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
I2 I3I1
S2 S1 S2 S1 S2S1
V1 V2 V3 VN AUX
aaa
AAA
110 to 440 V AC 120 to 350 V DC
V1 V2 V3 VN AUX
110 to 440 V AC 120 to 350 V DC
L1 (R
L2 (S
L3 (T
FUSES 0,5 A
)
)
)
S1
P1
L1 (R
L2 (S
L3 (T
)
)
)
S1
P1
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
V1 V2 V3 VN AUX
110 to 440 V AC 120 to 350 V DC
FUSES 2 A
L1 (R
L2 (S
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
V1 V2 V3 VN AUX
FUSES 2 A
L1 (R
)
L2 (S
)
L3 (T
N
110 to 440 V AC 120 to 350 V DC
)
L1 (R
N
)
Page 36
SOCOMEC - Ref. : 875 508A 37
ENGLISH
PULSE EMITTER OUTPUTS (FACTORY OPTION)
NB:
The lifetime of this relay is 108opera­tions.
2 reed relays (100 V - 0,5 A - 10 VA) available on the Diris Am provide a pulse for active, reactive and apparent energy. Values and duration can be programmed (see § programming).
COMMUNICATION (FACTORY OPTION)
Recommendations:
You should use a shielded twisted pair (LIYCY type). In a disturbed envi­ronment or large network (in terms of length) we recommend the use of 2 shielded pairs (type LIYCY -CY). In this case, one pair is used for the + and the –, and another pair, where the 2 wires are short-circuited, for the 0 V. A repeater (1 channel) or an arrestor (4 channels) should be used if you intend to exceed the distance (1500 m) and/or maximum number (31) of Diris. Please contact us for more information.
NB:
A 120 ohms resistance (found on Diris Am) must be xed at both ends of the link.
Other solutions are available (modem, optical bre, etc.). Please contact us.
For standard congurations, an RS 485 link is used to connect up to 31 Diris Am with a PC or a PLC over a distance of 1500 meters, using JBUS/MODBUS
©
protocol.
DIRIS 109 BDIRIS 110 B
1500 M
Programmable
controllers
Other systems
R = 120
N° 1 N° 2 N° n
R = 120
Programmable
controllers
Other systems
R = 120
1500 M 1500 M
N° 1
0+- -+0
repetor
RS485
N° n
R = 120
Page 37
38 SOCOMEC - Ref. : 875 508A
HOW TO ACCESS PROGRAMMING MODE
PROGRAMMING
1
PROGRAMMING THE NETWORK2
KEYS INSTRUCTION DISPLAY COMMENT
KEYS INSTRUCTION DISPLAY COMMENT
Press for 3 seconds, then release.
Press once
Press once To display ashing 4NBL
Press once
Conrm with the code and pass to network programming (NETWORK)
NB: Enter the access code 100 to access programming, and proceed as follows:
NB: As a default setting, the network is congured as 4NBL (4 unbalanced wires with 3 CTs). If you want this setting,
press on . You will pass to the CT programming line. If not, proceed as follows:
Press once
Press again for: 2BL 3BL 3NBL 4BL
Press once
Press again for: 3NBL 3BL 2BL 1BL
or
PROG
Page 38
SOCOMEC - Ref. : 875 508A 39
ENGLISH
SOCOMEC - Ref. : 875 508A 39
PROGRAMMING THE CURRENT TRANSFORMER RATIO (CT)
3
KEYS INSTRUCTION DISPLAY COMMENT
KEYS INSTRUCTION DISPLAY COMMENT
NB: The default CT setting is 500/5. If you want this setting, press ▼. You will pass to the voltage transformer line (VT). If not, proceed as follows:
Press once
Conrm type. Press on to pass to CT programming.
Press once
Press as many times as necessary to move to the right, or press to move to the left.
Press twice
To display ashing the 2nd digit
Press once
To increment the 2nd digit
Press once
To conrm the ratio Press on to pass to VT programming.
Press to decrement or to increment selected digit value Press once to conrm value Press once to pass to VT programming
NB: the rst 5 digits correspond to the transformer primar y value (1 to 10000), and the last digit to the transformer secondary value (1 or 5 A).
Example: Programming 1500/5 once in the CT menu.
Page 39
40 SOCOMEC - Ref. : 875 508A
PROGRAMMING THE VOLTAGE TRANSFORMER (VT)4
PROGRAMMING THE VOLTAGE TRANSFORMER (VT)
5
KEYS INSTRUCTION DISPLAY COMMENT
KEYS INSTRUCTION DISPLAY COMMENT
NB: As a default setting, the network is configured for low voltage operation without a voltage transformer (NO). If you do not want this, press . You will pass to the time integration programming (TIME 3I) .If not, proceed as follows:
Press once to display ashing NO
Press once
to programm the use of a VT
Press once
Press as many times as necessary to move to the right, or press to move to the left.
Press once
Conrm a VT. Press on to pass to VT programming
Press to decrement or to increment the selected digit value. Press once to conrm value Press once to pass to programming (TIME 3I).
NB: The 6 digits correspond to the primary value (400 000V maximum) and the last 3 digits to the secondary value (60, 100, 110, 173 and 190V)
NB: The default ratio setting is 100/100. To change it, proceed as follows:
PROGRAMMING INTEGRATION TIME (TIME 3I)6
KEYS INSTRUCTION DISPLAY COMMENT
NB: The time default setting is 15 minutes (3I 15). If you want this value, pr ess ▼. You will pass to the power integra- tion time programming line (TIME P/Q/S) . If not, proceed as follows:
Press once
to display ashing 15 minutes
Page 40
SOCOMEC - Ref. : 875 508A 41
ENGLISH
Press once
Press again for: 30, 60, 5, 8, 10 and 15 minutes
Press once
Press again for: 8, 5, 60, 30, 20 and 15 minutes
Press once
Conrm time. Press on to pass to power integration time programming (TIME P/Q/S)
PROGRAMMING POWER INTEGRATION TIME (TIME P/Q/S)7
KEYS INSTRUCTION DISPLAY COMMENT
NB: The time default setting is 15 minutes (P/Q/S 15). If you want this value, press ▼. You will pass to the reset to zero programming line (RSET). If not, proceed as follows:
Press once
to display ashing 15 minutes
or
Press once
Press again for: 30, 60, 5, 8, 10 and 15 minutes
Press once
Press again for: 8, 5, 60, 30, 20 and 15 minutes
Press once
Conrm time. Press on to pass to reset to zero programming (RSET)
or
Page 41
42 SOCOMEC - Ref. : 875 508A
PROGRAMMING RESET TO ZERO (RSET)8
KEYS INSTRUCTION DISPLAY COMMENT
NB: The parameter default setting is the current (MAX 3I). If you do not wish to reset values to zero, press ▼. You will pass to network type programming (NETWORK) or to the N° 1 pulse output programming line (option). If not, proceed as follows:
Press once
to display ashing MAX 31
Press once
Press again for: MAX P-, MAX Q, MAX Q-, MAX S, TIME, EA, ER, ES, EA-, ER
-
Press once
Press again for: EA-, ES, ER, EA, TIME, MAX S, MAX Q-, MAX Q, MAX P-, MAX P
Press once to display ashing NO
or
Press once YES to set to zero
Press once
Conrm parameter. Press on to pass to type OUT1 programming.
Nota: EA, ER and ES appear if the energy module is connected.
Page 42
SOCOMEC - Ref. : 875 508A 43
ENGLISH
PROGRAMMING N° 1 PULSE OUTPUT TYPE (OUT 1 EA) (OPTION)9
KEYS INSTRUCTION DISPLAY COMMENT
NB: The energy type default setting is active energy (EA) and the value is 10 kWh (10). If you want this value, press ▼. You will pass to pulse duration programming (DUR). If not, proceed as follows:
NB: Press if you want to confirm type and maintain a value of 10 kWh (10). If not, proceed as follows:
Press once to display ashing EA
Press once
Press again for: ES,EA-,ER- and EA
Press once
Press again for: EA-, ES, ER and EA
Press once to display ashing 10
Press once
Press again for: 1000; 10000; 0.1; 1 and 10
Press once
Press again for:
0.1; 10000; 1000; 100 and 10
Press once
Conrm parameter. Press on to pass to duration programming (OUT 1 DUR)
or
or
Page 43
44 SOCOMEC - Ref. : 875 508A
PROGRAMMING N° 1 PULSE OUTPUT DURATION (OUT 1 DUR) (OPTION)10
KEYS INSTRUCTION DISPLAY COMMENT
NB: The value default setting is 100 ms (DUR 100). If you want this value, press ▼. You will pass to N° 2 pulse output duration programming (OUT 2). If not, proceed as follows:
Press once
to display ashing the rst digit
Press once
Press again for: 300,400,500,600,700, 800 and 900 ms
Press once
Press again for: 800,700,600,500,400, 300 and 200 ms
Press once
Conrm time. Press on to pass to N°2 pulse output type programming (OUT2)
PROGRAMMING N° 2 PULSE OUTPUT TYPE AND VALUE (OUT 2 EA) (OPTION)11
KEYS INSTRUCTION DISPLAY COMMENT
NB: The energy type default setting is active energy (EA) and the value is 10 kWh (10). If you want this value, press ▼. You will pass pulse duration value programming (DUR). If not, proceed as follows:
or
Press once to display ashing EA
Press once
Press again for: ES,EA-,ER- and EA
Press once
Press again for: EA-,ES,ER and EA
or
Page 44
SOCOMEC - Ref. : 875 508A 45
ENGLISH
Press once
to display ashing 10
Press once
Press again for: 1000;10000;0,1;1 and 10
Press once
Press again for: 0,1;10000;1000;100 and 10
Press once
Conrm parameter. Press on to pass to duration programming (OUT 2 DUR)
or
PROGRAMMING N° 2 PULSE OUTPUT DURATION (OUT2 DUR) (OPTION)12
KEYS INSTRUCTION DISPLAY COMMENT
NB: The default setting is 100 ms (DUR 100). If you want this value, press ▼. You will pass to network (NETWORK) or communication programming (option). If not, proceed as follows:
Press once
to display ashing the rst digit
Press once
Press again for: 300,400,500,600,700, 800 and 900 ms
Press once
Press again for: 800,700,600,500,400, 300, and 200 ms
Press once
Conrm time. Press on to pass to commu­nication programming (communication module connected) or return to network programming.
or
NB: Pr ess if you want to conrm type and maintain a value of 10 kWh (10). If not, proceed as follows:
Page 45
46 SOCOMEC - Ref. : 875 508A
PROGRAMMING THE COMMUNICATION ADDRESS (COM ADR) (OPTION)13
KEYS INSTRUCTION DISPLAY COMMENT
NB: The address default setting is 5 (ARD 5). If you want this value, press ▼. You will pass to communication speed programming (COM BdS) . If not, proceed as follows:
Press once
to display ashing 1st digit (press twice and three times for the 2nd and 3rd digit), or press
to return to the left.
Press to decrement or to increment the selected digit value Press once to confirm Press once to pass to speed programming (COM BdS)
NB: the address can vary between 1 to 255.
PROGRAMMING COMMUNICATION SPEED (COM BDS) (OPTION)
14
KEYS INSTRUCTION DISPLAY COMMENT
NB: The speed default setting is 9600 BdS (BDS 9600). If you want this value, pr ess ▼. You will pass to communica- tion parity programming (COM PAR). If not, proceed as follows:
Press once
Press again for: 38400,2400,4800 and 9600 bauds
Press once
to display flashing 9600 bauds
Press once
Press again for: 2400,38400,19200 and 9600 bauds
Press once
Conrm speed. Press on to pass to parity programming (PAR).
or
Page 46
SOCOMEC - Ref. : 875 508A 47
ENGLISH
Press once No parity
Press once
Press again for: EVEN (even parity) and NO (without parity)
Press once
Press again for: ODD (odd parity) and NO (without parity)
PROGRAMMING COMMUNICATION PARITY (COM PAR) (OPTION)15
KEYS INSTRUCTION DISPLAY COMMENT
NB: As a default setting, the communication is without parity (PAR NO). If you want this setting, press ▼. You will pass to communication stop bit programming (COM STOP). If not, proceed as follows:
or
Press once
Conrm parity. Press on to pass to stop bit programming (STOP)
PROGRAMMING COMMUNICATION STOP BIT (COM STOP) (OPTION)16
KEYS INSTRUCTION DISPLAY COMMENT
NB: The stop bit default setting is 1 (STOP 1). If you want this value, press ▼. You will return to network type pro- gramming (NETWORK) . If not, proceed as follows:
Press once
to display ashing stop bit value
Press once 1 for 1 bit and 2 for 2 bits
Press once
Conrm stop bit. Press on
to return to network type programming.
or
Page 47
48 SOCOMEC - Ref. : 875 508A
TO QUIT PROGRAMMING17
KEYS INSTRUCTION DISPLAY COMMENT
Press for 3 seconds then release
The display will automati­cally return to current.
PROG
Page 48
SOCOMEC - Ref. : 875 508A 49
ENGLISH
DISPLAY
OPERATION
KEYPAD
I: Instantaneous and average current display via successive key depressions, or
scrolling to the left in programming ( ),
U/F: Phase to neutral, phase to phase and frequency display via successive key depressions or scrolling to the right in programming mode ( )
with six dual-function keys (display or conguration)
Type
Values
Phase
Unit
Type
Valeur
Unité
Phase
Page 49
50 SOCOMEC - Ref. : 875 508A
P/Q/S: instantaneous and maximum active, reactive and apparent power dis­play on 4 quadrants, as well as successive total average values,
or down-
ward scrolling in programming mode ()
PF: instantaneous or maximum inductive or capacitive power factor display via successive key depressions, or upward scrolling in programming mode (▲)
MAX: Maximum values display for the 3 currents and total powers on 4 qua­drants, or parameter conrmation in programming mode ( )
h/E: Hour meter and energy display (option) via successive key depressions,
or enter / quit programming menu (PROG).
Page 50
SOCOMEC - Ref. : 875 508A 51
ENGLISH
COMMUNICATION (OPTIONAL)
The JBUS/MODBUS used by the Diris Am involves a dialogue using a master-slave hierarchical structure. There are two possible dialogues:
the master communicates with a slave (Diris Am) and waits for its reply
the master communicates with all the slaves (Diris Am) without waiting for their reply.
The standard communications frame consists of:
The mode of communication is the RTU (Remote Terminal Unit) using hexadecimal characters of at least 8 bits.
Slave address Function code Address Data CRC 16
According to the JBUS/MODBUS
©
protocol, transmission time must be less than 3 silences, i.e. the emission time of 3 characters so that the mes­sage is processed by the Diris©.
NB:
When selecting slave address 0, a message is sent to all the instruments present on the network (only for func­tions 6 and 16).
To correctly use information, the fol­lowing functions are important:
3: to read n words (maximum 128). 6: to write one word. 8: to diagnose exchanges bet-
ween the master and the slave via meters 1, 3, 4, 5 and 6.
16 : to write n words (maximum 128).
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
TABLE OF VALUES WITH ALLOCATED CURRENT AND VOLTAGE WINDING RATIOS
Decimal Hexa. Number Text Unit address address of words
768 300 2 phase 1 current mA 770 302 2 phase 2 current mA 772 304 2 phase 3 current mA 774 306 2 Neutral current mA 776 308 2 phase to phase voltage U12 V/100 778 30A 2 phase to phase voltage U23 V/100 780 30C 2 phase to phase voltage U31 V/100 782 30E 2 phase to neutral voltage phase 1 V/100 784 310 2 phase to neutral voltage phase 2 V/100 786 312 2 phase to neutral voltage phase 3 V/100 788 314 2 Frequency Hz/100 790 316 2 Active power +/- kW/100 792 318 2 Reactive power +/- kvar/100 794 31A 2 Apparent power +/- kVA/100 796 31C 2 Power factor L/C
-: capacitive and +: inductive
0,001
798 31E 2 Active power phase 1 +/- kW/100 800 320 2 Active power phase 2 +/- kW/100 802 322 2 Active power phase 3 +/- kW/100 804 324 2 Reactive power phase 1 +/- kvar/100 806 326 2 Reactive power phase 2 +/- kvar/100 808 328 2 Reactive power phase 3 +/- kvar/100 810 32A 2 Apparent power phase 1 kVA/100 812 32C 2 Apparent power phase 2 kVA/100 814 32E 2 Apparent power phase 3 kVA/100 816 330 2 Power factor phase 1
-: capacitive and +: inductive
0,001
818 332 2 Power factor phase 2
-: capacitive and +: inductive
0,001
Page 51
52 SOCOMEC - Ref. : 875 508A
Example: To display all the values for Diris num­ber 5 in one inquiry, the following fra­me should be sent
Slave
05
Function
03
High-order
address
03
Low-order
address
00
High-order
word n°
00
Low-order
word n°
62
CRC 16
C5E3
Zone size: 98 words (decimal) or 62 (hexadecimal).
Decimal Hexa. Number Text Unit
address address of words
820 334 2 Power factor phase 3
-: capacitive and +: inductive
0,001
822 336 2 Average values I1 mA 824 338 2 Average values I2 mA 826 33A 2 Average values I3 mA 828 33C 2 Average value Active power + kW/100 830 33E 2 Average value Active power - kW/100 832 340 2 Average value Reactive power + kvar/100 834 342 2 Average value Reactive power - kvar/100 836 344 2 Average value Apparent power kVA/100 838 346 2 Maximum value I1 mA 840 348 2 Maximum value I2 mA 842 34A 2 Maximum value I3 mA 844 34C 2 Maximum value Active power + kW/100 846 34E 2 Maximum value Active power - kW/100 848 350 2 Maximum value
Reactive power + kvar/100
850 352 2 Maximum value
Reactive power - kvar/100
852 354 2 Maximum value
Apparent power kVA/100 854 356 2 Hour meter 1/100 h 856 358 2 Active energy + kWh 858 35A 2 Reactive energy + kWh 860 35C 2 Apparent energy kVAr 862 35E 2 Active energy - kWh 864 360 2 Reactive energy - kvarh
Page 52
SOCOMEC - Ref. : 875 508A 53
ENGLISH
Decimal Hexa. N° of Text Unit address address words
1792 700 1 current phase 1 mA 1793 701 1 current phase 2 mA 1794 702 1 current phase 3 mA 1795 703 1 Neutral current mA 1796 704 1 phase to phase voltage U12 V/100 1797 705 1 phase to phase voltage U23 V/100 1798 706 1 phase to phase voltage U31 V/100 1799 707 1 phase to neutral phase 1 V/100 1800 708 1 phase to neutral phase 2 V/100 1801 709 1 phase to neutral phase 3 V/100 1802 70A 1 Fr equency Hz/100 1803 70B 1 Active power +/- kW/100 1804 70C 1 Reactive power +/- kvar/100 1805 70D 1 Apparent power +/- kVA/100 1806 70E 1 Power factor L/C
-: capacitive and +: inductive
0,001
1807 70F 1 Active power phase 1 +/- kW/100 1808 710 1 Active power phase 2 +/- kW/100 1809 711 1 Active power phase 3 +/- kW/100 1810 712 1 Reactive power phase 1 +/- kvar/100 1811 713 1 Reactive power phase 2 +/- kvar/100 1812 714 1 Reactive power phase 3 +/- kvar/100 1813 715 1 Apparent power phase 1 kVA/100 1814 716 1 Apparent power phase 2 kVA/100 1815 717 1 Apparent power phase 3 kVA/100 1816 718 1 Power factor phase 1
-: capacitive and +: inductive
0,001
1817 719 1 Power factor phase 2
-: capacitive and +: inductive
0,001
1818 71A 1 Power factor phase 3
-: capacitive and +: inductive
0,001
1819 71B 1 Average values I1 mA 1820 71C 1 Average values I2 mA 1821 71D 1 Average values I3 mA 1822 71E 1 Average value Active power + kW 1823 71F 1 Average value Active power - kW/100 1824 720 1 Average value Reactive power + kvar/100 1825 721 1 Average value Reactive power - kvar/100 1826 722 1 Average value Apparent power KVA/100 1827 723 1 Maximum value I1 mA 1828 724 1 Maximum value I2 mA 1829 725 1 Maximum value I3 mA 1830 726 1 Maximum value Active power + kW/100 1831 727 1 Maximum value Active power - kW/100 1832 728 1 Maximum value
Reactive power + kvar/100
1833 729 1 Maximum value
Reactive power - kvar/100
1834 72A 1 Maximum value
Apparent power kVA/100 1835 72B 1 Active energy + < 10000 kWh 1836 72C 1 Active energy + > 10000 kWh 1837 72D 1 Reactive energy + < 10000 kvarh
1838 72E 1 Reactive energy - > 10000 kvarh 1839 72F 1 Apparent energy < 10000 kvarh 1840 730 1 Apparent energy > 10000 kVAh 1841 731 1 Active energy - <10000 kVAh 1842 732 1 Active energy - > 10000 kWh 1843 733 1 Reactive energy - < 10000 kWh 1844 734 1 Reactive energy - > 10000 kvarh
TABLE OF VALUES WITHOUT ALLOCATED CURRENT AND VOLTAGE WINDING RATIOS
NB:
Values should be multiplied by the fol­lowing coefcient:
CT = 100 = 20 VT = 20000 = 200
5 100
CT x VT = 20 x 200
= 4000
Powers will be multiplied by 4000 (if there is no VT, then VT = 1), currents by 20 and voltages by 200.
Zone size: 53 words (decimal) or 35 (hexadecimal).
Page 53
54 SOCOMEC - Ref. : 875 508A
Example: To display all the values for Diris num­ber 5 in one inquiry, the following fra­me should be sent:
Slave
05
Function
03
Address
High-order
07
Address
Low-order
00
Word n°
High-order
00
Word n°
Low-order
35
CRC 16
852D
LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16):
Decimal Hexa. N° of Label Unit
address address words
512 200 1 Network type:
0: 1BL 1: 2BL
2: 3BL 3: 3 NBL 4: 4 NBL /
513 201 1 CT secondary:
1: 1 A
5: 5 A A 514 202 1 CT primary A 515 203 1 Voltage input on PT:
0: No
1: Yes / 516 204 2 PT primary V 518 206 1 PT secondary:
60: 60 V 100: 100 V 110: 110 V 173: 173 V 190: 190 V V
519 207 1 Synchronisation of
I AVG/MAX: 5: 5 minutes 8: 8 minutes
10: 10 minutes 15: 15 minutes 20: 20 minutes 30: 30 minutes 60: 60 minutes /
520 208 1 Synchronisation of
P/Q/S AVG/MAX:
5: 5 minutes 8: 8 minutes
10: 10 minutes 15: 15 minutes 20: 20 minutes 30: 30 minutes 60: 60 minutes /
521 209 1 OUT 1 allocation
0: kWh +
1: kvarh +
2: kVA
3: kWh –
4: kvarh - /
522 20A 1 OUT1 pulse value:
0: 0.1 kWh/kvarh/kVA
1: 1 kWh/kvarh/kVA
2: 10 kWh/kvarh/kVA
3: 100 kWh/kvarh/kVA
4: 1000 kWh/kvarh/kVA
5: 10000 kWh/kvarh/kVA /
Page 54
SOCOMEC - Ref. : 875 508A 55
ENGLISH
523 20B 1 OUT1 pulse duration:
1: 100 ms 2: 200 ms 3: 300 ms 4: 400 ms 5: 500 ms 6: 600 ms 7: 700 ms 8: 800 ms 9: 900 ms /
524 20C 1 OUT 2 allocation:
0: kWh +
1: kvarh +
2: kVA
3: kWh –
4: kvarh - /
525 20D 1 OUT 2 pulse value:
0: 0.1 kWh/kvarh/kVA
1: 1 kWh/kvarh/kVA
2: 10 kWh/kvarh/kVA
3: 100 kWh/kvarh/kVA
4: 1000 kWh/kvarh/kVA
5: 10000 kWh/kvarh/kVA /
526 20E 1 OUT 2 pulse duration:
1: 100 ms 2: 200 ms 3: 300 ms 4: 400 ms 5: 500 ms 6: 600 ms 7: 700 ms 8: 800 ms 9: 900 ms /
Slave
05
Function
06
Address
High-order
02
Address
Low-order
00
Word n°
High-order
00
Word n°
Low-order
05
CRC 16
49F5
Example: Configuration of a 4-wired unbalan­ced network (4 LNB) for DIRIS num­ber 5.
Zone size: 15 words or F hexadecimal
Diris Am reply: identical to message sent
Page 55
56 SOCOMEC - Ref. : 875 508A
Example: To reset all values for Diris number 5 to zero, the following frame should be sent:
Diris Am reply: identical to message sent
SAVED COMMAND (RESET)
The following command should be done to save programming parame­ters changes for Diris number 5.
Nota:
Diris Am will not reply to this com­mand.
NB:
To reset several parameters to zero, add the corresponding gure indica­ted in the text column.
Example: reset Max P+ and kvarh + to zero: 2 = 100 = 102 (Hex)
Slave
05
Function
06
Address
High-order
04
Address
Low-order
00
Word n°
High-order
10
Word n°
Low-order
00
CRC 16
84BE
Slave
05
Function
06
Address
High-order
06
Address
Low-order
00
Values
0000
CRC 16
88C6
Decimal Hexa. N° of Text Unit
address address words (Hex.)
1024 400 1 reset to zero for:
0: Max3I
1: MaxP+
2: MaxP-
3: MaxQ+
4: MaxQ-
5: MaxS
6: Hour meter
7: kWh+
8: kvarh+
9: kVA
10: kWh-
11: kvarh-
12: all parameters /
RESET TO ZERO: ENERGY METERS AND MAX. VALUES (FUNCTION 6):
Zone size: 1 word or 1 hexadecimal
Page 56
SOCOMEC - Ref. : 875 508A 57
ENGLISH
TECHNICAL CHARACTERISTICS
CASE
DISPLAY
MEASUREMENTS
Dimensions: 7 modules (7x18mm) Connection via 1 to 6 mm2(exible wires)
and 1.5 to 10 mm2(rigid) IP index: IP54 (front panel) and IP20 (case) Weight: 640 gr.
Type: High luminosity self adjusting LCD display (with back-light option)
Three-phase (3 or 4 wires), two-phase (1 wire) and single-phase networks
VOLTAGE (TRMS)
Direct measurement: from 0 to 700 V AC (phase/phase)
from 0 to 404 V AC (phase/neutral)
Measurement via PT:
Primary: up to 400 kV
Secondary: 60, 100, 110, 173 and 190 V AC
Display and resolution: from 0 to 400.0 kV Permanent overload: 760 V AC Update period: 1 second
CURRENT (TRMS)
Via CT with:
Primary: up to 10000 A
Secondary: from 1 or 5 A
Input consumption: 0.1 VA Display: from 0 to 11 kA (1.1 times the primary value) permanent overload: 6 A intermittent overload: 10 In / 1 second Update period: 1 second Maximum ratio TC x TP: 2 000 000
POWER
Per phase: 0 to 1660 MW/Mvar/MVA Total: 0 to 8000 MW/Mvar/MVA Update period: 1 second
FREQUENCY
from 45,0 to 65,0 Hz Update period: 1 second
MEASUREMENT ACCURACY
Current: 0.5 % from 10 to 110 % / In Voltage: 0.5 % from 140 to 700 V AC Power: 1 % of full scale (-90° to + 90°) Power factor: 1 % for 0.5 < FP < 1 Frequency: 0.1 Hz from 45 to 65 Hz Active energy metering: +/- 1% from 0.02 to 1,2 In with PF = 0.5 L
or 0.8 C (class 1 IEC 61036)
Reactive energy metering: +/- 2% from 0.1 to 1,2 In with sinϕ = 0.5 L
or C (class 1 IEC 61268)
Page 57
58 SOCOMEC - Ref. : 875 508A
AUXILIARY SUPPLY
110 to 440 V AC 50/60 Hz +/- 10 % 120 to 350 V DC +/- 20 % Consumption 10 VA Other version: 18 to 100 V DC (+/-10%)
PULSE OUTPUTS
Reed relays (100 V DC - 0.5 A - 10 VA) N° of operations < 10
8
COMMUNICATION
RS 485: 2 or 3 wires half duplex JBUS/MODBUS©protocol RTU mode Parity 2400 to 38400 Bauds
GALVANIC INSULATION (AC INSULATION VOLTAGE)
Aux. supply: 4 kV Voltage inputs: 1.5 kV Current inputs: 1.5 kV Serial link: 1.5 kV Pulse outputs: 1.5 kV
OPERATING CONDITIONS
Operating temperature: -10° to + 55°C (14°à 131°F) Storage temperature: -20° to + 85°C (-4°à 158°F) Relative humidity: 95 %
STANDARDS
Metering IEC 61036 class 1
IEC 61268 class 2
CE marking IEC 61000-4/2-3-4-5-6-8-11
EN 50081-1 EN 50082-2
Environment: IEC 60068-2/6-11
Page 58
88 SOCOMEC - Réf. : 875 508A
Al momento del ricevimento della scatola contenente il Diris Am, è ne­cessario vericare i seguenti punti:
lo stato dellimballo;
la presenza di danneggiamenti o
rotture dovuti al trasporto;
se il numero di riferimento dell’ap- parecchio è conforme a quello della richiesta;
Nota:
Per la sicurezza del personale e del materiale, è indispensabile leggere attentamente il contenuto del presente libretto prima della messa in servizio.
se limballo comprende il prodotto dotato di due coprimorsetti;
la presenza del libretto di istruzione originale.
OPERAZIONI PRELIMINARI
INFORMAZIONI GENERALI
frontalino (tastiera di 6 tasti e display LCD retroilluminato in opzione) di congurare e di visualizzare tutti i para­metri e di gestire le seguenti funzioni:
FUNZIONI
Il Diris Am è un apparecchio multimi­sura di grandezze elettriche per reti monofasi, bifasi e trifasi a bassa, media ed alta tensione. Permette, dal suo
potenza apparente su 4 quadranti (+/-) per fase e totale in valori istan­tanei, medi e massimi su un perio­do programmabile (da 5 a 60 min.);
Fattore di Potenza (PF) per fase e totale con lindicazione L per indut­tivo e C per capacitivo.
correnti di fase e neutro istantanee, medie e massime su un periodo programmabile (da 5 a 60 min.);
tensioni di fase e concatenate;
frequenza (Hz);
potenza attiva su 4 quadranti (+/-)
per fase e totale in valori istantanei, medi e massimi su un periodo pro­grammabile (da 5 a 60 min.);
potenza reattiva su 4 quadranti (+/-) per fase e totale in valori istantanei, medi e massimi su un periodo pro­grammabile (da 5 a 60 min.);
CONTEGGIO ORARIO
Contatore in 1/100 di ora per la durata di funzionamento con possibilità di azzeramento.
OPZIONI
Le opzioni sono integrate in fabbrica e sono scomposte nella seguente maniera:
Conteggio delle energie
conteggio di energie attive (da 0 a 99 999 999 kW/ora [kWh]) e reattive (da 0 a 99 999 999 kvar/ora [kvarh]) su 4 quadranti e dellenergia appa­rente (da 0 a 99 999 999 kVA/ora [kVAh]). E ugualmente possibile uti­lizzare due uscite a impulsi di energia
Nota:
I contatori possono essere azzerati entrando nel modo configurazione (accesso limitato da codice segreto).
configurabili per peso e durata dell impulso (0,1-1-10-100 kWh, kvarh o kVAh e 1 o 10 MW/ora, Mvar/ora e MVA/ora e da 100 a 900 ms).
Comunicazione
La scheda di comunicazione seriale RS485 (a 2 o 3 fili) con protocollo JBUS/MODBUS®permette il collega­mento con un PC o un PLC ad una velocità massima di 38400 baud.
MISURA IN VERI VALORI EFFICACI (TRMS) DI
Page 59
SOCOMEC - Réf. : 875 508A 89
ITALIANO
Il Diris Am è realizzato in un conteni­tore modulare da 7 moduli ed è dotato di un display e di una tastiera.
1 Display LCD (retroilluminato
in opzione)
2 Tastiera composta da 6 pulsanti
a doppia funzionalità (visualiz­zazione o congurazione)
PRESENTAZIONE
2
1
DIRIS 245 B
Page 60
90 SOCOMEC - Réf. : 875 508A
MORSETTIERA
Il Diris Am è dotato di morsetti di col­legamento da 1 a 6 mm2per cavi fles- sibili e da 1,5 a 10 mm2per cavi rigidi
DISPOSIZIONI DI SICUREZZA (U, I E F)
Per evitare qualsiasi deterioramento dellapparecchio, è necessario, prima di collegarlo, vericare che:
siano rispettate le indicazioni ripor­tate sulla sua targhetta,
la tensione di alimentazione sia compresa tra 110 e 440 V AC o tra 120 e 350 V DC con una tolleranza di +/- 10 %
Nota:
Si consiglia comunque di proteggere lalimentazione e le entrate di tensione con dei fusibili gG da 0,5 A.
Nota:
La coppia di serraggio massima dei morsetti è di 0,4 Nm.
la frequenza di rete sia 50 o 60 Hz,
la tensione massima ai morsetti
delle entrate di tensione sia inferio­re o uguale a 700 V AC fase/fase o 404 V AC fase/neutro,
la corrente massima sia 6 A (collega­mento a partire da trasformatore(i) di corrente).
COLLEGAMENTO
RETE TRIFASE NON EQUILIBRATA (4 FNE)
DIRIS 272 A I
DIRIS 273 A I
Il Diris Am si installa su guida DIN, fondoquadro o, a richiesta, fronte­quadro per mezzo di un kit di fissag- gio specifico non incluso di serie (contattarci).
Prescrizioni:
Installarlo ad una distanza di almeno 30 cm da un apparecchio di interru­zione (Interruttori, contattori,...).
Evitare la vicinanza con sistemi generatori di perturbazioni elettro­magnetiche.
Evitare le vibrazioni che comportino delle accelerazioni superiori a 1 G per delle frequenze inferiori a 60 Hz.
INSTALLAZIONE
CARATTERISTICHE AMBIENTALI
Per garantire un funzionamento otti­male, è necessario utilizzare questo apparecchio da -10 ° a +55 °C con una umidità relativa compresa tra il
20 e il 95 %, tuttavia lapparecchio può comunque funzionare con una temperatura compresa tra -15 °C.
per le correnti, le tensioni, lalimenta­zione ausiliaria e le opzioni.
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
V1 V2 V3 VN AUX
da 110 a 440 V AC da 120 a 350 V DC
FUSIBILI 0,5 A
L1 (R
L2 (S
L3 (T
N
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
V1 V2 V3 VN AUX
aaa
AAA
da 110 a 440 V AC
da 120 a 350 V DC
L1 (R
L2 (S
L3 (T
N
)
)
)
Page 61
SOCOMEC - Réf. : 875 508A 91
ITALIANO
Nota:
La soluzione con 2 TA diminuisce di 0,5 % la precisione di misura della fase da cui la corrente viene dedotta in maniera vettoriale.
DIRIS 274 A I
DIRIS 275 A I
DIRIS 276 A I
DIRIS 277 A I
RETE TRIFASE EQUILIBRATA (4 FE)
RETE TRIFASE NON EQUILIBRATA (3 FNE)
Nota:
La soluzione con 1 TA diminuisce di 0,5 % la precisione di misura delle fasi da cui la corrente viene dedotta in maniera vettoriale.
DIRIS 280 A I
DIRIS 281 AI
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
V1 V2 V3 VN AUX
da 110 a 440 V AC da 120 a 350 V DC
FUSIBILI 0,5 A
L1 (R
L2 (S
L3 (T
N
I2 I3I1
S2 S1 S2 S1 S2S1
)
)
)
S1
P1
V1 V2 V3 VN AUX
aaa
aaa
AAA
AAA
da 110 a 440 V AC da 120 a 350 V DC
L1 (R
L2 (S
L3 (T
N
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
I2 I3I1
S2 S1 S2 S1 S2S1
V1 V2 V3 VN AUX
da 110 a 440 V AC da 120 a 350 V DC
FUSIBILI 0,5 A
V1 V2 V3 VN AUX
L1 (R
L2 (S
L3 (T
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
S1
P1
V1 V2 V3 VN AUX
aaa
da 110 a 440 V AC da 120 a 350 V DC
AAA
L1 (R
L2 (S
L3 (T
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
V1 V2 V3 VN AUX
da 110 a 440 V AC da 120 a 350 V DC
FUSIBILI 0,5 A
S1
P1
S1
P1
L1 (R
L2 (S
L3 (T
)
)
)
S1
P1
S1
P1
aaa
AAA
da 110 a 440 V AC da 120 a 350 V DC
)
L1 (R
)
L2 (S
)
L3 (T
Page 62
92 SOCOMEC - Réf. : 875 508A
RETE TRIFASE EQUILIBRATA (3 FE)
RETE BIFASE (2 FE) RETE MONOFASE (1 FE)
Prescrizioni:
Al momento del collegamento del Diris, è indispensabile cortocircuitare le uscite secondarie di ogni trasfor­matore di corrente. Questa operazione può essere fatta automaticamente con un prodotto Socomec: il PTI. Per maggiori informazioni, contattarci.
DIRIS 283 A I
DIRIS 282 A IDIRIS 285 A I
DIRIS 284 A I
DIRIS 278 A I
DIRIS 279 A I
RETE TRIFASE NON EQUILIBRATA (3 FNE)
Nota:
La soluzione con 1 TA diminuisce di 0,5 % la precisione di misura delle fasi da cui la corrente viene dedotta in maniera vettoriale.
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
V1 V2 V3 VN AUX
da 110 a 440 V AC da 120 a 350 V DC
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
V1 V2 V3 VN AUX
da 110 a 440 V AC da 120 a 350 V DC
FUSIBILI 0,5 A
L1 (R
L2 (S
L3 (T
FUSIBILI 0,5 A
L1 (R
L2 (S
L3 (T
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
S1
P1
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
)
)
)
)
)
)
V1 V2 V3 VN AUX
aaa
AAA
V1 V2 V3 VN AUX
aaa
AAA
da 110 a 440 V AC da 120 a 350 V DC
da 110 a 440 V AC da 120 a 350 V DC
L1 (R
L2 (S
L3 (T
L1 (R
L2 (S
L3 (T
)
)
)
)
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
V1 V2 V3 VN AUX
da 110 a 440 V AC da 120 a 350 V DC
FUSIBILI 0,5 A
L1 (R
L2 (S
)
)
I2 I3I1
S2 S1 S2 S1 S2S1
S1
P1
V1 V2 V3 VN AUX
da 110 a 440 V AC da 120 a 350 V DC
FUSIBILI 0,5 A
L1 (R
N
)
Page 63
SOCOMEC - Réf. : 875 508A 93
ITALIANO
USCITE AD EMISSIONE DI IMPULSI (OPZIONE DI FABBRICA)
Nota:
La durata di vita minima di questo relais è di 108operazioni.
Il Diris Am utilizzando 2 relais (100 V ­0,5 A - 10 VA) possiede unuscita ad impulsi per lenergia attiva, reattiva e apparente. Il peso, la durata e le grandezze da associare alle uscite sono congurabili (vedere § program­mazione).
COMUNICAZIONI (OPZIONE DI FABBRICA)
Importante:
E necessario utilizzare un paio di cavi intrecciati schermati di tipo LIYCY. In un ambiente perturbato o su una rete grande per lunghezza e per numero di Diris, si consiglia di utilizzare 2 paia di cavi schermati di tipo LIYCY-CY. In questo caso, un paio viene utilizzato per il positivo e il negativo e un altro paio, di cui i 2 li sono cortocircuitati, per lo 0 V. Se la distanza di 1500 m o/e il numero di 31 Diris viene superato, è necessa­rio collegare un ripetitore (1 via) o uno scaricatore (4 vie) per permettere un collegamento supplementare di Diris Am su altri 1500 m. Per maggiori infor­mazioni sulla metodologia di collega­mento, contattarci.
Nota:
Alle 2 estremità della linea di comuni­cazione, è indispensabile collegare una resistenza di 120 Ohm che si trova sul Diris Am.
Per altre soluzioni o configurazioni particolari (modem, fibra ottica,...) contattarci.
In una configurazione standard, un collegamento RS 485 consente di met­tere in comunicazione 31 Diris Am con un PC o un PLC su 1500 metri utiliz­zando il protocollo JBUS/MODBUS®.
DIRIS 109 B IDIRIS 110 B I
1500 M
R = 120
PLC
Altri sistemi
N° 1 N° 2 N° n
R = 120
PLC
Altri sistemi
R = 120
1500 M 1500 M
N° 1
0+- -+0
ripetitore
RS485
N° n
R = 120
Page 64
94 SOCOMEC - Réf. : 875 508A
ACCESSO ALLA MODALITÀ DI PROGRAMMAZIONE
PROGRAMMAZIONE
1
PROGRAMMAZIONE DEL TIPO DI RETE (NETWORK)2
TASTO ISTRUZIONE MESSAGGIO NOTA
TASTO ISTRUZIONE MESSAGGIO NOTA
Tenere premuto per almeno 3 secondi, poi rilasciare
Premere 1 volta
Premere 1 volta
Per far lampeggiare 4NBL
Premere 1 volta
Convalidare col tasto per passare alla programmazione del tipo di rete (NETWORK)
Nota: È necessario inserire il codice segreto 100 per accedere alla modalità di programmazione
Nota: Per default la rete è congurata in 4 NBL (4 li non equilibrati con 3 TA). Se si desidera conservarla, premere ▼.
Così facendo si accede alla programmazione dei TA. Altrimenti, proceder e come segue:
Premere 1 volta
Premere ancora per selezionare una delle seguenti possibilità: 2BL 3BL 3NBL 4BL
Premere 1 volta
Premere ancora per scorrere la lista nel senso opposto 3NBL 3BL 2BL 1BL
o
PROG
Page 65
SOCOMEC - Réf. : 875 508A 95
ITALIANO
PROGRAMMAZIONE DEL/DEI TRASFORMATORE/I DI CORRENTE (CT)
3
TASTO ISTRUZIONE MESSAGGIO NOTA
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default il trasformatore/i di corrente è congurato in 500/5. Se si desidera mantenere questo valore, premere sul tasto . Si accede così alla programmazione del trasformatore di tensione (VT). Altrimenti, procedere come segue:
Premere 1 volta
Per convalidare. Premere sul tasto ▼ per programmare il/i TA
Premere 1 volta
Premere ancore per spostarsi verso destra sul digit da modicare o premere per tornare verso sinistra
Premere 2 volte
Per far lampeggiare il secondo digit
Premere 1 volta
Per incrementare di una unità il valore del secondo digit
Premere 1 volta
Per convalidare. Premere sul tasto ▼ per programmare il TV
Premere sul tasto per decrementare il valore o sul tasto per incrementarlo Premere una volta sul tasto per convalidare il valore Premere quindi sul tasto per passare alla programmazione del trasformatore di tensione (VT)
Nota: I primi 5 digit corrispondono al valore del primario del trasformatore (da 1 a 10000) e lultimo al valore del secondario (1 o 5 A).
Esempio: Programmazione di un trasformatore con rapporto 1500/1
Page 66
96 SOCOMEC - Réf. : 875 508A
PROGRAMMAZIONE DELL’USO DI UN TRASFORMATORE DI TENSIONE (VT)4
PROGRAMMAZIONE DEI PARAMETRI DEL TRASFORMATORE DI TENSIONE (VT)
5
TASTO ISTRUZIONE MESSAGGIO NOTA
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default la rete è congurata senza trasformatore di tensione (NO). Se non si desidera modicarlo, premere su .Si accede alla programmazione del tempo di integrazione (TIME 3I). Altrimenti, procedere come segue:
Premere 1 volta Per far lampeggiare NO
Premere 1 volta
Per programmare lutilizzo di un TA
Premere 1 volta
Premere ancore per spostarsi verso destra sul digit da modicare o premere per tornare verso sinistra
Premere 1 volta
Per convalidare. Premere sul tasto ▼ per programmare il/i TA
Premere sul tasto per decrementare il valore o sul tasto per incrementarlo Premere una volta sul tasto per convalidare il valore Premere quindi sul tasto per passare alla programmazione del tempo di integrazione delle correnti (TIME 3I)
Nota: I primi 6 digit corrispondono al valor e del primario del trasformatore (massimo 400000V) e gli altri 3 digit al valore del secondario (da scegliere fra i seguenti possibili: 60, 100, 110, 173 o 190V).
Nota: Per default il rapporto del trasfor matore di tensione è configurato in 100/100. Per modificarlo procedere come segue:
PROGRAMMAZIONE DEL TEMPO DI INTEGRAZIONE DELLE CORRENTI (TIME 3I)6
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default il tempo di integrazione delle correnti è programmato a 15 minuti (3I 15). Se si desidera mantenerlo, premere sul tasto . Si accede così alla programmazione del tempo di integrazione delle potenze (TIME P/Q/S). Altrimenti, procedere come segue:
Premere 1 volta
Per far lampeggiare 15 minuti
Page 67
SOCOMEC - Réf. : 875 508A 97
ITALIANO
Premere 1 volta
Premere ancora per scorrere la lista dei valori predefiniti: 30, 60, 5, 8, 10 e 15
Premere 1 volta
Premere ancora per scorrere la lista in senso opposto: 8, 5, 60, 30, 20 e 15
Premere 1 volta
Per convalidare. Premere sul tasto per program­mare il tempo di integra­zione delle potenze (TIME P/Q/S)
PROGRAMMAZIONE DEL TEMPO DI INTEGRAZIONE DELLE POTENZE (TIME P/Q/S)7
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default il tempo di integrazione delle potenze è programmato a 15 minuti (P/Q/S 15). Se si desidera man- tenerlo, premere sul tasto . Si accede così allazzeramento dei contatori (RSET). Altrimenti, procedere come segue:
Premere 1 volta
Per far lampeggiare 15 minuti
o
Premere 1 volta
Premere ancora per scorrere la lista dei valori predefiniti: 30, 60, 5, 8, 10 e 15
Premere 1 volta
Premere ancora per scorrere la lista in senso opposto 8, 5, 60, 30, 20 e 15
Premere 1 volta
Per convalidare. Premere sul tasto ▼ per passare allazzeramento dei contatori (RSET)
o
Page 68
98 SOCOMEC - Réf. : 875 508A
AZZERAMENTO DEI VALORI MASSIMI E DEI CONTATORI (RSET)8
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default il parametro visualizzato è la corrente massima (MAX3I). Se non si desidera azzerare questo valore o i successivi, premere su . Si accede alla programmazione del tipo di rete (NETWORK o ) alla programmazione delluscita ad impulsi numero 1 (Opzione). Altrimenti, procedere come segue:
Premere 1 volta
Per far lampeggiare MAX 3I
Premere 1 volta
Premere ancora per scorrere la lista dei valori predeniti: MAX P-, MAX Q, MAX Q-, MAX S, TIME, EA, ER, ES, EA-, ER
-
Premere 1 volta
Premere ancora per scorrere la lista in senso opposto EA-, ES, ER, EA, TIME, MAX S, MAX Q-, MAX Q, MAX P-, MAX P
Premere 1 volta Per far lampeggiare NO
o
Premere 1 volta YES per azzerare
Premere 1 volta
Per convalidare. Premere sul tasto per passare alla programmazione delluscita ad impulsi N° 1
Nota: EA, ER, ES (energia attiva, reattiva ed apparente) compaiono solo se è connesso il modulo energie.
Page 69
SOCOMEC - Réf. : 875 508A 99
ITALIANO
PROGRAMMAZIONE DELL’USCITA AD IMPULSI N° 1 (OUT 1 EA) (OPZIONE)9
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default luscita è assegnata al contatore di energia attiva (EA) e il peso è 10kWh. Se si desidera conservare questa impostazione, premere sul tasto . Si accede alla programmazione della durata delluscita ad impulsi numero 1 (DUR). Altrimenti, procedere come segue.
Nota: Se si vuole convalidare il parametro assegnato e mantenere un peso di 10kWh (10), pr emere su altrimenti procedere come segue:
Premere 1 volta Per far lampeggiare EA
Premere 1 volta
Premere ancora per scorrere la lista delle uscite: ES,EA-,ER- e EA
Premere 1 volta
Premere ancora per scorrere la lista in senso opposto EA-, ES, ER e EA
Premere 1 volta Per far lampeggiare 10
Premere 1 volta
Premere ancora per scorrere la lista dei peso dellimpulso: 1000; 10000; 0.1; 1 e 10
Premere 1 volta
Premere ancora per scorrere la lista in senso opposto
0.1; 10000; 1000; 100 e 10
Premere 1 volta
Per convalidare. Premere sul tasto ▼ per programmare la durata dellimpulso (OUT 1 DUR)
o
o
Page 70
100 SOCOMEC - Réf. : 875 508A
PROGRAMMAZIONE DELLA DURATA DELLUSCITA AD IMPULSI N ° 1 (OUT 1 DUR) (OPZIONE)10
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default la durata dellimpulso è 100ms (DUR 100). Se si desidera conservare questa impostazione, pr emere sul tasto . Si accede alla programmazione delluscita ad impulsi numero 2 (OUT 2). Altrimenti, procedere come segue.
Premere 1 volta
Per far lampeggiare il primo digit
Premere 1 volta
Premere ancora per scorrere la lista dei valori predeniti: 300, 400, 500, 600, 700, 800 e 900 ms
Premere 1 volta
Premere ancora per scorrere la lista in senso opposto 800, 700, 600, 500, 400, 300 e 200 ms
Premere 1 volta
Per convalidare. Premere sul tasto ▼ per programmare luscita ad impulso N° 2 (OUT 2)
PROGRAMMAZIONE DELL’USCITA AD IMPULSI N° 2 (OUT 2 EA) (OPZIONE)11
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default luscita è assegnata al contatore di energia attiva (EA) e il peso è 10kvarh. Se si desidera conserva- re questa impostazione, premere sul tasto . Si accede alla programmazione della durata delluscita ad impulsi numero 2 (DUR). Altrimenti, procedere come segue.
o
Premere 1 volta Per far lampeggiare EA
Premere 1 volta
Premere ancora per scorrere la lista delle uscite: ES,EA-,ER- e EA
Premere 1 volta
Premere ancora per scorrere la lista in senso opposto EA-,ES,ER e EA
o
Page 71
SOCOMEC - Réf. : 875 508A 101
ITALIANO
Nota: Se si vuole convalidare il parametro assegnato e mantenere un peso di 10kvarh (10), premere su altrimenti procedere come segue:
Premere 1 volta
Per far lampeggiare 10
Premere 1 volta
Premere ancora per scorrere la lista delle peso dellimpulso: 1000; 10000; 0,1; 1 e 10
Premere 1 volta
Premere ancora per scorrere la lista in senso opposto 0,1; 10000; 1000; 100 e 10
Premere 1 volta
Per convalidare. Premere sul tasto ▼ per programmare la durata dellimpulso (OUT 2 DUR)
o
PROGRAMMAZIONE DELLA DURATA DELLUSCITA AD IMPULSI N ° 2 (OUT 2 DUR) (OPZIONE)12
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default la durata dellimpulso è 100ms (DUR 100). Se si desidera conservare questa impostazione, pr emere sul tasto . Si accede alla programmazione dei parametri di comunicazione (COM ADR) se è presente lopzione comu­nicazione, altrimenti si ritorna alla programmazione del tipo di rete (NETWORK). Altrimenti, procedere come segue.
Premere 1 volta
Per far lampeggiare il primo digit
Premere 1 volta
Premere ancora per scorrere la lista dei valori predeniti: 300, 400, 500, 600, 700, 800 e 900 ms
Premere 1 volta
Premere ancora per scorrere la lista in senso opposto 800, 700, 600, 500, 400, 300 e 200 ms
Premere 1 volta
Per convalidare. Premere sul tasto per accedere alla programmazione dei para­metri di comunicazione (COM ADR) se è presente l’opzione comunicazione, altrimenti si ritorna alla programmazione del tipo di rete (NETWORK).
o
Page 72
102 SOCOMEC - Réf. : 875 508A
PROGRMMAZIONE DELL’INDIRIZZO DI COMUNICAZIONE (COM ADR) (OPZIONE)13
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default lindirizzo assegnato allo strumento è 5 (ADR 5). Se si desidera mantenerlo, premere sul tasto ▼. Si accede in questo modo alla programmazione della velocità di comunicazione (COM BDS). Altrimenti, procedere come segue.
Premere 1 volta
Per far lampeggiare il primo digit (due o tre volte per il 2° o il 3° digit) e premere sul tasto per spostarsi verso sinistra
Premere su per decrementare il valore o su per incrementarlo Premere 1 volta sul tasto per convalidare il valore impostato Premere 1 volta sul tasto per passare alla programmazione della velocità di comunicazione
Nota: lindirizzo dello strumento deve essere un numero compreso tra 1 e 255.
PROGRAMMAZIONE DELLA VELOCITÀ DI COMUNICAZIONE (COM BDS) (OPZIONE)
14
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default la velocità di comunicazione è 9600 bauds (BDS 9600). Se si desidera mantenerla, premere sul tasto . Si accede alla programmazione del bit di parità (COM PAR). Altrimenti, procedere come segue
Premere 1 volta
Premere ancora per scorrere la lista dei valori predeniti: 38400, 2400, 4800 e 9600 bauds
Premere 1 volta Per far lampeggiare 9600
Premere 1 volta
Premere ancora per scorrere la lista in senso opposto 2400, 38400, 19200 e 9600 bauds
Premere 1 volta
Per convalidare. Premere sul tasto ▼ per impostare il bit di parità (PAR)
o
Page 73
SOCOMEC - Réf. : 875 508A 103
ITALIANO
Premere 1 volta Per far lampeggiare NO
Premere 1 volta
Premere ancora per impostare EVEN (pari) e NO (senza parità)
Premere 1 volta
Premere ancora per impostare ODD (dispari) e NO (senza parità)
PROGRAMMAZIONE DEL BIT DI PARITÀ (COM PAR) (OPZIONE)15
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default la comunicazione è senza bit di parità (PAR NO). Se si desidera mantenerla, premere sul tasto ▼. Si accede alla programmazione del bit di stop (COM STOP). Altrimenti, procedere come segue
o
Premere 1 volta
Per convalidare. Premere sul tasto ▼ per impostare il bit di stop (STOP)
PROGRAMMAZIONE DEL BIT DI STOP DI COMUNICAZIONE (COM STOP) (OPZIONE)16
TASTO ISTRUZIONE MESSAGGIO NOTA
Nota: Per default il bit di stop di comunicazione è impostato a 1 (STOP 1). Se si desidera mantenerla, premere sul tasto . Si ritorna alla programmazione del tipo di rete (NETWORK). Altrimenti, procedere come segue
Premere 1 volta Per far lampeggiare 1
Premere 1 volta
Premere 1 volta per 1 bit e 2 volte per 2 bit
Premere 1 volta
Per convalidare. Premere sul tasto
per ritornare allimpostazione del tipo di rete
o
Page 74
104 SOCOMEC - Réf. : 875 508A
PER ABBANDONARE LA PROGRAMMAZIONE17
TASTO ISTRUZIONE MESSAGGIO NOTA
Tenere premuto per almeno 3 secondi, poi rilasciare
Lo strumento ritorna automaticamente a mostrare le correnti assorbite.
PROG
Page 75
SOCOMEC - Réf. : 875 508A 105
ITALIANO
DISPLAY
UTILIZZO
TASTIERA
I: Visualizzazione delle correnti istantanee e medie attraverso pressioni successive
o scorrimento verso la sinistra in modalità configurazione ()
U/F: Visualizzazione delle tensioni di fase e concatenate e della frequenza attraverso pressioni successive
o scorrimento verso la destra in modalità congurazione ()
Tastiera composta da 6 pulsanti a doppia funzione (lettura o congurazione)
Parametro
Valore
Fase
Unità di misura
Type
Valeur
Unité
Phase
Page 76
106 SOCOMEC - Réf. : 875 508A
P/Q/S: Visualizzazione della potenza attiva, reattiva e apparente su 4 quadranti per fase e totale nonché dei valori medi totali successivi
o scorrimento verso il basso nella
modalità congurazione
()
PF: Visualizzazione del fattore di potenza induttiva o capacitiva per fase e totale attra­verso pressioni successive
o scorrimento verso lalto in modalità congurazione (▲)
MAX: Visualizzazione dei valori massimi per le 3 correnti e le 3 potenze massime su 4 quadranti
o convalida dei parametri nella modalità congurazione (),
h/E: Visualizzazione del contatore orario e delle energie attraverso pressioni successive o entrata e uscita dalla modalità di programmazione (PROG).
Page 77
SOCOMEC - Réf. : 875 508A 107
ITALIANO
COMUNICAZIONE (OPZIONE)
Il Diris Am comunica utilizzando il protocollo JBUS/MODBUS®che im­plica un dialogo secondo una struttura master/slave. Due sono i dialoghi possibili:
il master dialoga con uno slave (Diris Am) e aspetta la sua risposta
Il master dialoga con tutti gli slave (Diris Am) senza aspettare la loro risposta.
La sintassi di comunicazioni standard è la seguente:
La comunicazione avviene con mo­dalità RTU (Remote Terminal Unit) con stringhe di valori esadecimali di minimo 8 bit.
Indirizzo dello slave Codice della funzione Indirizzo Dati CRC 16
Secondo il protocollo JBUS/MOD­BUS®, il tempo di integrazione deve essere inferiore a 3 silenzi e cioè al tempo di emissione di tre caratteri perché il messaggio sia trattato dal Diris®.
Nota:
Selezionando lindirizzo dello slave 0, si trasmette un messaggio a tutti gli apparecchi presenti sulla rete (unica­mente per le funzioni 6 e 16).
I codici delle funzioni utilizzate sono i seguenti:
3: per la lettura di un numero n di
parole (massimo 128).
6: per la scrittura di una parola. 8: per la diagnosi degli scambi tra
il master e lo slave a partire dai contatori 1, 3, 4, 5 e 6.
16: per la scrittura di un numero n di
parole (massimo 128).
LISTA DEI PARAMETRI IN LETTURA (FUNZIONE 3)
TABELLA DEGLI INDIRIZZI (DECIMALE ED ESADECIMALE) DEI VALORI REALI DELLE GRANDEZZE DELLO STRUMENTO (VALORI REALI - 2 PAROLE)
Indirizzo Indirizzo Numero Descrizione Unità
decimale esadec. di parole di misura
768 300 2 corrente fase 1 mA 770 302 2 corrente fase 2 mA 772 304 2 corrente fase 3 mA 774 306 2 Corrente del neutro mA 776 308 2 tensione concatenata U12 V/100 778 30A 2 tensione concatenata U23 V/100 780 30C 2 tensione concatenata U31 V/100 782 30E 2 tensione di fase fase 1 V/100 784 310 2 tensione di fase fase 2 V/100 786 312 2 tensione di fase fase 3 V/100 788 314 2 Frequenza Hz/100 790 316 2 Potenza attiva +/- kW/100 792 318 2 Potenza reattiva +/- kvar/100 794 31A 2 Potenza apparente +/- kVA/100 796 31C 2 Fattore di potenza L/C
-: capacitivo e +: induttivo
0,001
798 31E 2 Potenza attiva fase 1 +/- kW/100 800 320 2 Potenza attiva fase 2 +/- kW/100 802 322 2 Potenza attiva fase 3 +/- kW/100 804 324 2 Potenza reattiva fase 1 +/- kvar/100 806 326 2 Potenza reattiva fase 2 +/- kvar/100 808 328 2 Potenza reattiva fase 3 +/- kvar/100 810 32A 2 Potenza apparente fase 1 kVA/100 812 32C 2 Potenza apparente fase 2 kVA/100 814 32E 2 Potenza apparente fase 3 kVA/100 816 330 2 Fattore di potenza fase 1
-: capacitivo e +: induttivo
0,001
818 332 2 Fattore di potenza fase 2
-: capacitivo e +: induttivo
0,001
Page 78
108 SOCOMEC - Réf. : 875 508A
Esempio: Per visualizzare tutti i valori di un Diris Am con indirizzo 5 in una sola interro­gazione, è necessario inviare il codice seguente:
Slave
05
Funzione
03
Indirizzo
Peso forte
03
Indirizzo
Peso debole
00
Numero parole
Peso forte
00
Numero parole
Peso debole
62
CRC 16
C5E3
Dimensioni di questa zona: 98 parole in decimale o 62 in esadecimale.
Indirizzo Indirizzo Numero Descrizione Unità
decimale esadec. di parole di misura
820 334 2 Fattore di potenza fase 3
-: capacitivo e +: induttivo
0,001
822 336 2 Valore medo I1 mA 824 338 2 Valore medo I2 mA 826 33A 2 Valore medo I3 mA 828 33C 2 Valore medio Potenza attiva + kW/100 830 33E 2 Valore medio Potenza attiva - kW/100 832 340 2 Valore medio Potenza reattiva + kvar/100 834 342 2 Valore medio Potenza reattiva - kvar/100 836 344 2 Valore medio Potenza apparente kVA/100 838 346 2 Valore massimo I1 mA 840 348 2 Valore massimo I2 mA 842 34A 2 Valore massimo I3 mA 844 34C 2 Valore massimo Potenza attiva + kW/100 846 34E 2 Valore massimo Potenza attiva - kW/100 848 350 2 Valore massimo
Potenza reattiva + kvar/100
850 352 2 Valore massimo
Potenza reattiva - kvar/100
852 354 2 Valore massimo
Potenza apparente kVA/100 854 356 2 Contatore orario 1/100 h 856 358 2 Energia attiva + kWh 858 35A 2 Energia reattiva + kWh 860 35C 2 Energia apparente kVAr 862 35E 2 Energia attiva - kWh 864 360 2 Energia reattiva - kvarh
Page 79
SOCOMEC - Réf. : 875 508A 109
ITALIANO
Indirizzo Indirizzo Numero Descrizione Unità
decimale esadec. di parole di misura
1792 700 1 corrente fase 1 mA 1793 701 1 corrente fase 2 mA 1794 702 1 corrente fase 3 mA 1795 703 1 Corrente del neutro mA 1796 704 1 tensione concatenata U12 V/100 1797 705 1 tensione concatenata U23 V/100 1798 706 1 tensione concatenata U31 V/100 1799 707 1 tensione di fase fase 1 V/100 1800 708 1 tensione di fase fase 2 V/100 1801 709 1 tensione di fase fase 3 V/100 1802 70A 1 Fr equenza Hz/100 1803 70B 1 Potenza attiva +/- kW/100 1804 70C 1 Potenza attiva +/- kvar/100 1805 70D 1 Potenza apparente +/- kVA/100 1806 70E 1 Fattore di potenza L/C
-: capacitivo e +: induttivo
0,001
1807 70F 1 Potenza attiva fase 1 +/- kW/100 1808 710 1 Potenza attiva fase 2 +/- kW/100 1809 711 1 Potenza attiva fase 3 +/- kW/100 1810 712 1 Potenza reattiva fase 1 +/- kvar/100 1811 713 1 Potenza reattiva fase 2 +/- kvar/100 1812 714 1 Potenza reattiva fase 3 +/- kvar/100 1813 715 1 Potenza apparente fase 1 kVA/100 1814 716 1 Potenza apparente fase 2 kVA/100 1815 717 1 Potenza apparente fase 3 kVA/100 1816 718 1 Fattore di potenza fase 1
-: capacitivo e +: induttivo
0,001
1817 719 1 Fattore di potenza fase 2
-: capacitive e +: inductive
0,001
1818 71A 1 Fattore di potenza fase 3
-: capacitivo e +: induttivo
0,001
1819 71B 1 Valori medi I1 mA 1820 71C 1 Valori medi I2 mA 1821 71D 1 Valori medi I3 mA 1822 71E 1 Valore medio Potenza attiva + kW 1823 71F 1 Valore medio Potenza attiva - kW/100 1824 720 1 Valore medio Potenza reattiva + kvar/100 1825 721 1 Valore medio Potenza reattiva - kvar/100 1826 722 1 Valore medio Potenza apparente KVA/100 1827 723 1 Valore massimo I1 mA 1828 724 1 Valore massimo I2 mA 1829 725 1 Valore massimo I3 mA 1830 726 1 Valore massimo Potenza attiva + kW/100 1831 727 1 Valore massimo Potenza attiva - kW/100 1832 728 1 Valore massimo
Potenza reattiva + kvar/100
1833 729 1 Valore massimo
Potenza reattiva - kvar/100
1834 72A 1 Valore massimo
Potenza apparente kVA/100 1835 72B 1 Energia attiva + < 10000 kWh 1836 72C 1 Energia attiva + > 10000 kWh 1837 72D 1 Energia reattiva + < 10000 kvarh
1838 72E 1 Energia reattiva + > 10000 kvarh 1839 72F 1 Energia apparente < 10000 kvarh 1840 730 1 Energia apparente > 10000 kVAh 1841 731 1 Energia attiva - <10000 kVAh 1842 732 1 Energia attiva - > 10000 kWh 1843 733 1 Energia reattiva - < 10000 kWh 1844 734 1 Energia reattiva - > 10000 kvarh
TABELLA DEGLI INDIRIZZI (DECIMALE ED ESADECIMALE) DEI VALORI PROPORZIONALI DELLE GRANDEZZE DELLO STRUMENTO (VALORI PROPORZIONALI - 1 PAROLA)
Nota:
Questi valori dovranno essere moltipli­cati per i rapporti di trasformazione dei trasformatori per avere i valori reali, es:
TA = 100 = 20 TV = 20000 = 200
5 100
TA x TV = 20 x 200
= 4000
Quindi tutti le potenze andranno mol­tiplicati per k = 4000 (se non c’è un TV, allora KTV = 1), le correnti per 20 e le tensioni per 200.
Dimensioni di questa zona: 53 parole in decimale o 35 in esadecimale.
Page 80
110 SOCOMEC - Réf. : 875 508A
Esempio: Per visualizzare tutti i valori di un Diris Am con indirizzo 5 in una sola interro­gazione, è necessario inviare il codice seguente:
Slave
05
Funzione
03
Indirizzo
Peso forte
07
Indirizzo
Peso debole
00
Numero parole
Peso forte
00
Numero parole
Peso debole
35
CRC 16
852D
LISTA DEI P ARAMETRI IN LETTURA O IN CONFIGURAZIONE REMOTA (FUNZIONE 3, 6 O 16)
Indirizzo Indirizzo Numero Descrizione Unità
decimale esadec. di parole di misura
512 200 1 Tipo di rete:
0: 1BL 1: 2BL
2: 3BL 3: 3 NBL 4: 4 NBL /
513 201 1 Secondario del/i TA:
1: 1 A
5: 5 A A 514 202 1 Primario del/i TA A 515 203 1 Entrata in tensione su TV:
0: No (nessun TV)
1: Yes (attraverso TV) / 516 204 2 Primario del TV V 518 206 1 Secondario del TV:
60: 60 V 100: 100 V 110: 110 V 173: 173 V 190: 190 V V
519 207 1 Sincronizzazione di I AVG/MAX
(corrente media/massima):
5: 5 minuti
8: 8 minuti 10: 10 minuti 15: 15 minuti 20: 20 minuti 30: 30 minuti 60: 60 minuti /
520 208 1 Sincronizzazione di P/Q/S AVG/MAX
(valore medio/massimo):
5: 5 minuti
8: 8 minuti 10: 10 minuti 15: 15 minuti 20: 20 minuti 30: 30 minuti 60: 60 minuti /
521 209 1 Assegnazione di OUT 1
0: kWh +
1: kvarh +
2: kVA
3: kWh –
4: kvarh - /
522 20A 1 Peso degli impulsi OUT1:
0: 0.1 kWh/kvarh/kVA
1: 1 kWh/kvarh/kVA
2: 10 kWh/kvarh/kVA
3: 100 kWh/kvarh/kVA
4: 1000 kWh/kvarh/kVA
5: 10000 kWh/kvarh/kVA /
Page 81
SOCOMEC - Réf. : 875 508A 111
ITALIANO
523 20B 1 Durata degli impulsi OUT1:
1: 100 ms 2: 200 ms 3: 300 ms 4: 400 ms 5: 500 ms 6: 600 ms 7: 700 ms 8: 800 ms 9: 900 ms /
524 20C 1 Assegnazione di OUT 2:
0: kWh +
1: kvarh +
2: kVA
3: kWh –
4: kvarh - /
525 20D 1 Peso degli impulsi OUT2:
0: 0.1 kWh/kvarh/kVA
1: 1 kWh/kvarh/kVA
2: 10 kWh/kvarh/kVA
3: 100 kWh/kvarh/kVA
4: 1000 kWh/kvarh/kVA
5: 10000 kWh/kvarh/kVA /
526 20E 1 Durata degli impulsi OUT2:
1: 100 ms 2: 200 ms 3: 300 ms 4: 400 ms 5: 500 ms 6: 600 ms 7: 700 ms 8: 800 ms 9: 900 ms /
Slave
05
Funzione
06
Indirizzo
Peso forte
02
Indirizzo
Peso debole
00
Numero parole
Peso forte
00
Numero parole
Peso debole
05
CRC 16
49F5
Esempio: Congurazione di una rete a 4 li non equilibrata (4 LNB) per il Diris Am con indirizzo 5.
Dimensioni di questa zona: 15 parole in decimale o F in esadecimale
Risposta del Diris Am: Identico al messaggio inviato
Page 82
112 SOCOMEC - Réf. : 875 508A
Esempio: Per azzerare tutti i valori del Diris Am con indirizzo 5, è necessario inviare il codice seguente:
Risposta del Diris Am: Identico al messaggio inviato
COMANDO SALVATAGGIO (RESET)
Dopo avere modicato i parametri di programmazione del Diris Am con indirizzo 5 per registrarli, è necessario inviare questo comando.
Nota:
Il Diris Am non risponde a questo comando.
Nota:
Per azzerare più parametri, è neces­sario sommare i valori corrispondenti elencati nella colonna descrizione. Esempio: azzeramento di Max P+ e kvarh: 2 + 100 = 102 (esadecimale)
Slave
05
Funzione
06
Indirizzo
Peso forte
04
Indirizzo
Peso debole
00
Numero parole
Peso forte
10
Numero parole
Peso debole
00
CRC 16
84BE
Slave
05
Funzione
06
Indirizzo
Peso forte
06
Indirizzo
Peso debole
00
Valore
0000
CRC 16
88C6
Indirizzo Indirizzo Numero Descrizione Unità
decimale esadec. di parole (esadecimale) di misura
1024 400 1 R.A.Z. di:
Max3I: 1
MaxP+: 2
MaxP-: 4
MaxQ+: 8
MaxQ-: 10
MaxS: 20
Contatore orario: 40
kWh+: 80
kvarh+: 100
kVA: 200
kWh-: 400
kvarh-: 800
tutti i parametri: 1000 /
AZZERAMENTO DEI CONTATORI DI ENERGIA E DEI VALORI MASSIMI. (FUNZIONE 6)
Dimensioni di questa zona: 1 parola in decimale o 1 in esadecimale
Page 83
SOCOMEC - Réf. : 875 508A 113
ITALIANO
CARATTERISTICHE TECNICHE
SCATOLA
DISPLAY
MISURE
Dimensioni: 7 moduli (7 x 18 mm) Collegamenti: da 1 a 6 mm2per cavi flessibili
e da 1,5 a 10 mm2per cavi rigidi
Grado di protezione: Frontale IP40 e
Scatola IP20
Peso: 640 g
Tipo: LCD alta luminosità (retroilluminato in opzione)
Rete trifase (3 o 4 li), bifase (2 li) e monofase
TENSIONE (TRMS)
Misura diretta:
Fase/fase: da 0 a 700 V AC Fase/neutro: da 0 a 404 V AC
Misura attraverso un TV:
Primario: no a 400 kV
Secondario: 60, 100, 110, 173 o 190 V AC
Visualizzazione e risoluzione da 0 a 400,0 kV Sovraccarico permanente (fase/fase): 760 V AC Periodo di attualizzazione: 1 s
CORRENTE (TRMS)
Intresso da TA con:
Primario: no a 10000 A
Secondario: da 1 o 5 A
Consumo delle entrate: 0,1 VA Visualizzazione: da 0 a 11 kA (1,1 volte il valore del primario) Sovraccarico permanente: 6 A Sovraccarico intermittente: 10 In per 1 s Periodo di attualizzazione: 1 s Rapporto massimo KTAx KTV: 2 000 000
POTENZE
Per fase: da 0 a 1660 MW/Mvar/MVA Totale: da 0 a 8000 MW/Mvar/MVA Periodo di attualizzazione: 1 s
FREQUENZA
da 45,0 a 65,0 Hz Periodo di attualizzazione: 1 s
PRECISIONE DELLE MISURE
Corrente: 0,5 % da 10 a 110 % di In Tensione: 0,5 % da 140 a 700 V AC Potenza: 1 % del fondo scala (da -90° a + 90°) Fattore di Potenza: 1 % per 0,5 < FP < 1 Frequenza: 0,1 Hz da 45 a 65 Hz Conteggio dellenergia attiva:
+/- 1% da 0,02 a 1,2 In con PF = 0,5 L o 0,8 C (classe 1 CEI 61036)
Conteggio dellenergia reattiva:
+/- 2% da 0,1 a 1,2 In con sinϕ = 0,5 L o C (classe 2 CEI 61268)
Page 84
114 SOCOMEC - Réf. : 875 508A
ALIMENTAZIONE AUSILIARIA
da 110 a 440 V AC 50/60 Hz +/- 10 % da 120 a 350 V DC: +/- 20 % Consumo: 10 VA Altre versioni (a richiesta): da 18 a 100 V DC (+/-10%)
USCITE A IMPULSI
Relais reed: (100 V DC - 0,5 A - 10 VA) Numero di operazioni: 10
8
COMUNICAZIONE
RS 485: 2 o 3 li half duplex Protocollo: JBUS/MODBUS®modalità RTU Velocità: da 2400 a 38400 Bauds
ISOLAMENTO GALVANICO (tensione di isolamento AC)
Alimentazione ausiliaria: 4 kV Entrate di tensione: 1,5 kV Entrate di corrente: 1,5 kV Collegamento seriale: 1,5 kV Uscite a impulsi: 1,5 kV
CONDIZIONI DI UTILIZZO
Temperatura di funzionamento: da -10°C a + 55°C (da 14°F a 131°F) Temperatura di conservazione: da -20°C a + 85°C (da -4°F a 158 °F) Umidità relativa massima: 95 %
NORME
Misura: IEC 61036 classe 1
IEC 61268 classe 2
Marcatura CE: IEC 61000-4/2-3-4-5-6-8-11
EN 50081-1 EN 50082-2
Ambiente: IEC 60068-2/6-11
Page 85
SIEGE SOCIAL
HEAD OFFICE
GROUPE SOCOMEC Interrupteurs industriels et Onduleurs
SOCOMEC S.A.
au capital de 74 650 530 F - 11 380 400 R.C. Strasbourg 5484500 149 B
BP 10 - Rue de Westhouse - F-67230 Benfeld Tél. (33) 3 88 57 41 41 - Fax (33) 3 88 57 42 60
SOCOMEC
118, av. du Mal de Lattre de Tassigny F-94132 Fontenay-sous-Bois Cedex Tél. (33) 1 45 14 63 40 - Fax (33) 1 48 77 31 12
DIRECTION COMMERCIALE
SALES MANAGEMENT DIVISION
Ce document nest pas contractuel. La société SOCOMEC se réserve le droit de modier sans préavis les caractéris- tiques dans un souci permanent damélioration.
This document is not contractual. SOCOMEC reserves the right to modify features without prior notice in view of continued improvements.
Réf. : 875 508A - 10/00
DIRIS 245 A
Systèmes de Coupure et de Protection
Switching and Protection Systems