socomec DELPHYS MX 250, DELPHYS MX 400, DELPHYS MX 300, DELPHYS MX 500, DELPHYS MX 800 Operating Manual

...
Page 1
DELPHYS MX
250 to 900 kVA
Operating manual
GB
Page 2
Page 3
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
1. WARRANTY CERTIFICATE 4
2. FOREWORD 5
3. GENERAL 6
3. 1. Scope
6
3. 2. purpoSe And upS compoSition
6
3. 3. SAfety
7
3. 4. power Supply inputS
7
4. SINGLE UNITS WITH BYPASS 8
4. 1. StAndArd BASic SchemeS
8
4. 2. lAyout of SwitcheS
8
4. 3. mimic control pAnel
9
4. 4. meAning of the pictogrAmS
10
4. 5. menu Structure
11
4. 6. operAting A Single upS
12
5. MODULAR SYSTEMS 14
5. 1. BASic SchemeS
14
5. 2. lAyout of SwitcheS
15
5. 3. control pAnel
16
5. 4. meAning of the pictogrAmS
17
5. 5. Structure of the SyStem relAted menu
18
5. 6. Structure of the unit relAted menuS (unit)
19
5. 7. operAting the modulAr SyStem
20
6. CENTRAL BYPASS SYSTEMS 23
6. 1. StAndArd BASic Scheme
23
6. 2. lAyout of SwitcheS
23
6. 3. control pAnelS
24
6. 4. mimic pAnel of the centrAl BypASS cABinet
25
6. 5. mimic pAnel of A module
27
6. 6. operAting the centrAl BypASS SyStem
29
7. DESCRIPTION OF THE MENUS 32
7. 1. lcd diSplAy
32
7. 2. commentS concerning the menuS
33
7. 3. overloAd monitoring
40
7. 4. remAining BAck up time
40
TABLE OF CONTENTS
Page 4
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
The warranty terms and conditions are stipulated in the offer, by default the following clauses apply.
The SOCOMEC UPS warranty is strictly limited to the product(s) and does not extend to equipment which may
be integrated with this/these product(s), nor the performance of such equipment.
The manufacturer guarantees its products to be free from manufacturing faults and defects in design, material
or workmanship, subject to the limits set forth below.
The manufacturer reserves the right to modify the delivery with a view to fullling these guarantees or to replace
defective parts. The manufacturer's warranty does not apply in the following cases:
fault or defect in the design of parts added or supplied by the customer
fault due to unforeseen circumstances or force majeure
replacement or repair resulting from normal wear and tear of the modules or machinery
damage caused by negligence, lack of proper maintenance or misuse of the products
• repair, modication, adjustment or replacement of parts undertaken by unqualied third parties or person-
nel without the express consent of SOCOMEC UPS.
The warranty period is twelve months commencing from the date of delivery of the product.
The repair, replacement or modication of the parts during the warranty period does not imply or justify any
extension of the warranty beyond the original period.
In order to establish a valid warranty claim, the purchaser must notify the manufacturer in writing immediately
after the discovery of any apparent material defects and provide any and all supporting evidence of the defects
at the latest within eight days before the date of expiry of the warranty.
Defective parts which have been returned and replaced free of charge shall become the property of SOCOMEC UPS.
The warranty is void if the purchaser has undertaken modications or repairs on the devices on his or her own
initiative and without the express consent of the manufacturer.
The manufacturer's responsibility is strictly limited to the obligations dened in this warranty (repair and replace-
ment) excluding any other right to claim compensation or indemnity.
Any import tax, duty, fee or charge of any nature whatsoever imposed by European regulations or those of an
importing country or of a transit country shall be paid by the purchaser.
1. WARRANTY CERTIFICATE
Page 5
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
We thank you for the trust you have in our Uninterruptible Power Systems.
This equipment is tted with up to date technology. Rectier and inverter subsets are provided with power semicon­ductors (IGBT) including a digital micro-controller.
Our equipment complies with standard IEC EN 62040-2 and 62040-1.
“This is a product for restricted sales distribution to informed partners. Installation restrictions or addi­tional measures may be needed to prevent disturbances”.
SAFETY REQUIREMENTS
Using conditions:
Do read carefully these operation instructions before using the UPS and comply with the safety notes mentioned.
Whatever the repairs, they must be made only by authorised staff, who have been suitably trained. It is recommend­ed that the ambient temperature and humidity of the UPS environment are maintained below the values specied by the manufacturer.
This equipment meets the requirements of the European directives applied to this product. As a consequence it is labelled as follows:
REGULATIONS CONCERNED WITH ENVIRONMENTAL ISSUES
Recycling of electrical products and equipment
Provision is made in European countries to break up and recycle materials making up the system. The various com­ponents must be disposed of in accordance with the legal provisions in force in the country where the system is installed.
Battery wastes
Used batteries are considered as toxic wastes. It is therefore essential to entrust them solely and exclusively to rms specialised in their recycling. They can not be treated with other industrial or household wastes, as set out in local regulations in force.
2. FOREWORD
Page 6
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
3. GENERAL
3. 1.
Scope
This document provides required information for operating DELPHYS MX systems. It describes the facilities of-
fered on the control panels:
Scrolling through the menus displayed
Load transfer onto the automatic and/or maintenance bypass
System start up or shutdown
The operating instructions refer to the most frequently used congurations, i.e.:
Single UPS’s with bypass
Modular systems
Central bypass systems
3. 2.
purpoSe And upS compoSition
DELPHYS MX provide:
very low distortion and high power factor to the upstream power supply,
voltage and frequency stability as well as continuity of supply to downstream loads –whatever the outages
or disturbances on the upstream power supply-.
The system is tted with double conversion VFI-SS-111 technology.
When the input power supply is present, the UPS acts as a stabilizer. In the event of a utility outage, it acts as
a source of electrical power. In such case, the required power is supplied by the battery, which is kept charged
when the mains is present.
DELPHYS MX provide three-phase sinusoidal output. The UPS is composed of:
1 fully controlled three-phase rectier of DBC type (Double Bridge Converter),
1 three-phase inverter of S.V.M. type (Space Vector Modulation),
1 static bypass to transfer the load automatically and without interruption to the bypass supply.
1 maintenance bypass, which allows a seamless load transfer to the mains during maintenance operations,
1 battery,
1 DC/DC converter for recharging the batteries,
1 control panel made up of a mimic panel, an 8-line display and an intuitive user interface.
Page 7
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
3. GENERAL
3. 3.
SAfety
CAUTION
The equipment can only be switched on or used if the following conditions are fullled:
• electrical connections comply with the regulation in force (earth bonding, appropriate protections and cross- section of cables)
• all means to comply with the protection index of the system are in place, such as side panels, doors,
glands, shields or whatever....
ADVICE
• Carefully follow the instructions described in this manual.
• All operations must only be carried out by personnel who are suitably trained and with authorized ac- cess to restricted areas.
CAUTION
Do not forget that even when the load is stopped the unit is live:
because of the mains voltage, the rectier and the bypass.
because of the voltage generated by the battery and by the rectier.
because of the load voltage when the maintenance bypass Q5 is closed and the bypass mains is present.
DANGER
Any operation inside the cabinets is to be completed:
• once the UPS is stopped and no longer live
after 5 minutes, the time for the capacitors upstream of the rectier and inverter to discharge.
the residual voltage of the capacitors may still cause heavy electrical arcs after 5 minutes.
HAzARD INDICATION
While the UPS is operating, this label indicates that the parts are live and therefore the risk of electrical hazard.
All operations behind protection panels must only be carried out by personnel who are suitably trained.
3. 4.
power Supply inputS
Three power supply inputs are needed to operate the system:
voltage on input 1 for the supply to the rectier,
voltage on input 2 for the supply to the automatic bypass (depending on the system, inputs 1 and 2 can be common),
the DC voltage for the battery (about 500Vdc).
Page 8
Q1
Q4
Q3
Q5
Q20
X40
X10
X50
X20
MBP
ABP
BPREC
INV
DCC
BAT
*
Q1
Q4
Q3
Q5
Q20
X20
MBP
ABP
BPREC
INV
DCC
BAT
X40
X50
*
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
4. SINGLE UNITS WITH BYPASS
4. 1.
StAndArd BASic SchemeS
SEPARATED RECTIFIER AND BYPASS INPUTS COMMON RECTIFIER AND BYPASS INPUT
X40 = rectier input X10 = bypass input X50 = to the load ABP = automatic bypass MBP = maintenance bypass
BP = bypass facility REC = rectier INV = inverter DCC = battery charger converter * other protection upon request.
NOTE: in any case, see the technical details of the drawing on the inner side of the UPS door.
4. 2.
lAyout of SwitcheS
Q1: rectier input switch
Q4: automatic bypass switch
Q3: output switch
Q5: maintenance bypass switch
Note: Q20: battery protection is located in the battery cabinet or battery enclosure.
Q1 Q4 Q5 Q3
Q1
Q4
Q5
Q3
DELpHYS MX 250-500 kVA
DELpHYS MX 800-900 kVA
Page 9
ENGLISH
ESC
ENTER
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
4. SINGLE UNITS WITH BYPASS
4. 3.
mimic control pAnel
The control panel is composed of:
1 mimic panel 1 eight-line LCD display (with up to 40 characters) 1 four-key intuitive user interface:
1 validation key (ENTER)1 ESC key2 scrolling keys (UP/DOWN)
1 luminous status bar
4. 3.1. Contrast setting
The display contrast is set by the factory. It is automatically adjusted according to the temperature of the technical plant. No setting is required.
4. 3.2. Luminous status bar
The status bar provides immediate indication about the operating conditions of the system. The following information can be displayed.
Green bar:
the load is supplied via the inverter
the load is supplied via the bypass path if in Eco-mode
Yellow bar: the load is supplied via the automatic / maintenance bypass
Yellow blinking bar: maintenance alarm or request for servicing.
Red bar: the load is not supplied.
Red blinking bar: the imminent shutdown alarm is given.
Page 10
10
1
2
3
4
5
6
7
8
9
10
11
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
4. 4.
meAning of the pictogrAmS
Rectier and battery charger
Battery
Inverter
Output to the loads
Transfer impossible
Maintenance bypass
General alarm
4. 4.1. Mimic panel description
SYMBOLS GREEN YELLOW RED BLINKING
1 RECTIFIER INPUT Within tolerances Without tolerances
2 BYPASS INPUT Within tolerances Without tolerances
3 RECTIFIER ON Operating and alarm ON
4 BATTERY Charged discharging
Green: charging
Yellow: battery alarm
5 INVERTER ON Operating and alarm ON
6 LOAD ON INVERTER OK CS conducts
7 LOAD ON MAINS If Eco Mode ON
8 LOAD OUTPUT supplied Not supplied Red: imminent stop
9 TRANSFER Impossible
10 MAINTENANCE BYPASS Operating Yellow: maintenace Bypass alarm
11 GENERAL ALARM Alarm ON Yellow: communication problem
4. SINGLE UNITS WITH BYPASS
Page 11
11
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
4. 5.
menu Structure
From the permanently displayed screen:
Load protected by inverter
Load rate:
0
50 100
120
Press "ENTER" to reach the various menus, Select the menu with the UP or DOWN key, Press "ENTER" to reach the various sub-menus, Select the sub-menu with the UP or DOWN key, Validate with the "ENTER" key.
LIST OF MENUS LIST OF SUB-MENUS
MEASUREMENTS
"ENTER"
UPS SYSTEM OUTPUT
UPS SYSTEM OUTPUT POWER
BYPASS. – INVERTER MAINS
RECTIFIER - BATTERY
UPS COMMANDS
"ENTER"
AUTOMATIC START UP
LOAD TO MAINS / LOAD TO INVERTER
TRANSFER TO MAINTENANCE BYPASS
OPERATING MODE
"ENTER"
ECO MODE PROGRAMMING
TRANSFER TO NORMAL MODE
EVENT LOG
"ENTER"
SYSTEM
BATTERY
"ENTER"
BATTERY TEST INFORMATION
BATTERY TEST PROGRAMMING
BATTERY MEASUREMENTS
BATTERY MANUAL TEST
UPS GENERAL DATA
"ENTER"
DIAGNOSTIC CODES
REFERENCES
STATUS
"ENTER"
UPS SYSTEM STATUS
AUXILIARY INPUTS
SUBSET COMMAND
"ENTER"
RECTIFIER ON / OFF
INVERTER ON / OFF
LOAD ON MAINS / LOAD ON INVERTER
SHUTDOWN UPS OUTPUT
CLOCK
"ENTER"
PROGRAMMING
CONFIGURATION
"ENTER"
LANGUAGE
BUZZER
ACCESS CODE
LOCAL / REMOTE
JBUS LINK
"ENTER"
PROGRAMMING
Note: Controls are only displayed when available.
4. SINGLE UNITS WITH BYPASS
Page 12
12
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
4. 6.
operAting A Single upS
The « UPS COMMANDS » menu is designed for the operation of the UPS.
Note: controls are only displayed when available.
4. 6.1. Starting up the UPS
Prior to any operation, please refer to the basic scheme of the system.
CONDITIONS TO bE COMpLETED:
• - The system is live,
- wait for the control panels to light up.
COMpLY WITH THE FOLLOWING CHRONOLOGY pROCEDURE:
The UPS is started from the "UPS COMMANDS" menu and the "AUTOMATIC START UP" sub-menu through an interactive procedure. Just follow the instructions displayed and validate with the "ENTER" key.
Display for the automatic start up control:
UPS COMMANDS: AUTOMATIC START UP
CONFIRM THE START UP WITH UPS
SYSTEM OUTPUT SWITCHING ON
Cancel Validate
ESC ENTER
4. 6.2. Load transfer from inverter to mains
The load transfer is achieved from the "UPS COMMANDS" menu and the "LOAD TO MAINS" submenu, which enables the seamless switching from the inverter source to the non protected bypass source. Validate with the "ENTER" key.
Display for the LOAD TO MAINS control:
SUBSET COMMAND: LOAD TO MAINS
CONFIRM TRANSFER
TO AUTOMATIC BYPASS
Cancel Validate
ESC ENTER
4. SINGLE UNITS WITH BYPASS
Page 13
13
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
4. 6.3. Load transfer from mains to inverter
The load transfer is achieved from the "UPS COMMANDS" menu and the "LOAD TO INVERTER" sub-menu, which enables the seamless switching of the load from the bypass source to the protected inverter source. Validate with the "ENTER" key
Display for the LOAD TO INVERTER control:
SUBSET COMMAND: LOAD TO INVERTER
CONFIRM TRANSFER TO INVERTER
Cancel Validate
ESC ENTER
4. 6.4. UPS shutdown with transfer to the maintenance bypass
The Maintenance bypass is for ensuring supply to the load, while the system is stopped for servicing reasons, for instance.
The transfer is achieved from the "UPS COMMANDS" menu and the "TRANSFER TO MAINTENANCE BYP" sub­menu. This is achieved through an interactive procedure. Just follow the instructions displayed and validate when "ENTER" is displayed.
Display for the "TRANSFER TO MAINTENANCE BYP" control:
UPS COMMANDS: TRANSFER TO M. BYPASS
CONFIRM TRANSFER
TO MAINTENANCE BYPASS
Cancel Validate
ESC ENTER
4. 6.5. Operating Mode
Note: the operating mode is displayed only if the conguration is available. Seek advice to the CIM department.
The UPS can either operate in normal or Eco mode. The mode can be selected manually or programmed to be made automatically.
Mode normal: the load is supplied by the inverter. Should a problem occur on the rectier-inverter path, the load is
automatically transferred to mains.
Eco mode: the load is supplied by the bypass input. Should a problem occur on the bypass path, the load is
automatically transferred to inverter.
4. SINGLE UNITS WITH BYPASS
Page 14
Q1
Q4
Q3
Q5
Q20
X20
MBP
ABP
BPREC
INV
DCC
BAT
X50
Q1
Q4
Q3
Q5
Q20
X20
MBP
ABP
BPREC
INV
DCC
BAT
X40
X10
X10
*
*
X50
Q1
Q4
Q3
Q20
X20
ABP
BPREC
INV
DCC
BAT
X40
X10
Q1
Q4
Q3
Q20
X20
ABP
BPREC
INV
DCC
BAT
X10
MBP Q5
*
*
14
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
5. MODULAR SYSTEMS
5. 1.
BASic SchemeS
Modular systems can include up to six UPS units.
5. 1.1. Modular systems with two redundant UPS units
X10: rectier input X40: bypass input X50: to the load X20: battery connection REC: rectier INV: inverter BAT: battery DCC: battery charger converter BP: bypass facility ABP: automatic bypass MBP: maintenance bypass
* other protection upon request.
NOTE: in such a conguration each UPS unit has its own maintenance bypass.
X10: rectier input X40: bypass input X50: to the load X20: battery connection REC: rectier INV: inverter BAT: battery DCC: battery charger converter BP: bypass facility ABP: automatic bypass MBP: maintenance bypass
* other protection upon request.
NOTE: in such a conguration, the system is tted with an EXTERNAL maintenance bypass.
NOTE: in any case, see the technical details of the drawing.
5. 1.2. Modular systems with two non redundant UPS units
NOTE: in any case, see the technical details of the drawing on the inner side of the UPS door.
Page 15
Q1
Q4
Q3
Q20
X20
ABP
BPREC
INV
DCC
BAT
X50
Q1
Q4
Q3
Q20
X20
ABP
BPREC
INV
DCC
BAT
X40
X10
X10
Q1
Q4
Q3
Q20
X20
ABP
BPREC
INV
DCC
BAT
X10
MBP Q5
*
*
*
15
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
5. MODULAR SYSTEMS
NOTE: in any case, see the technical details of the diagram on the inner side of the UPS door.
5. 1.3. Modular systems with three UPS units or more
X10: rectier input X40: bypass input X50: to the load X20: battery connection REC: rectier INV: inverter BAT: battery DCC: battery charger converter BP: bypass facility ABP: automatic bypass MBP: maintenance bypass
* other protection upon request.
NOTE: in such a conguration, the system is tted with an EXTERNAL maintenance bypass.
5. 2.
lAyout of SwitcheS
Description of switches:
Q1: rectier input switch Q4: automatic bypass switch Q3: output switch Q5: maintenance bypass switch
Note: Q20: battery protection is located in the battery cabinet or battery enclosure.
Q1 Q4 Q5 Q3
Q1
Q4
Q5
Q3
DELpHYS MX 250-500 kVA
DELpHYS MX 800-900 kVA
Page 16
16
ESC
ENTER
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
5. 3.
control pAnel
The control panel is composed of:
1 mimic panel
1 eight-line LCD display (with up to 40 char-
acters)
1 four-key intuitive user interface:1 validation key (ENTER)1 ESC key2 scrolling keys (UP/DOWN)
1 luminous status bar
5. 3.1. Contrast setting
The display contrast is set by the factory. It is automatically adjusted according to the temperature of the technical plant. No setting is required.
5. 3.2. Description of the luminous status bar
Green bar:
• the load is supplied via the inverter
• the load is supplied via the bypass path if in Eco-mode
Yellow bar: the load is supplied via the automatic / maintenance bypass
Yellow blinking bar: maintenance alarm or request for servicing.
Red bar: the load is not supplied.
Red blinking bar: the imminent shutdown alarm is given.
OFF: UPS unit isolated or not available.
5. MODULAR SYSTEMS
Page 17
17
ENGLISH
1
2
3
4
5
6
7
8
9
10
11
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
5. 4.
meAning of the pictogrAmS
Rectier and battery charger
Battery
Inverter
Output to the loads
Transfer impossible
Maintenance bypass
General alarm
5. 4.1. Mimic panel description
SYMBOLS GREEN YELLOW RED BLINKING
1 RECTIFIER INPUT Within tolerances Without tolerances
2 BYPASS INPUT Within tolerances Without tolerances
3 RECTIFIER ON Operating and alarm ON
4 BATTERY Charged Discharged
Green: charging
Yellow: battery alarm
5 INVERTER ON Operating and alarm ON
6 LOAD ON INVERTER OK Eco-Mode ON
7 LOAD ON MAINS If Eco Mode ON CS conducts
8 LOAD OUTPUT supplied Not supplied Red: imminent stop
9 TRANSFER Impossible
10 MAINTENANCE BYPASS Operating Yellow: maintenace Bypass alarm
11 GENERAL ALARM Alarm ON Yellow: communication problem
5. MODULAR SYSTEMS
Page 18
18
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
5. 5.
Structure of the SyStem relAted menu
It is intended for operating the whole system, i.e. all the UPS units.
Display information about
UPS SYSTEM
UNIT
Cancel Validate
ESC ENTER
Press "ENTER" to reach the various menus, Select the menu with the UP or DOWN key, Press "ENTER" to reach the various sub-menus, Select the sub-menu with the UP or DOWN key, Validate with the "ENTER" key.
LIST OF MENUS LIST OF SUB-MENUS
MEASUREMENTS
"ENTER"
UPS SYSTEM OUTPUT
UPS SYSTEM OUTPUT POWER
SYSTEM BYPASS SUPPLY
UPS COMMANDS
"ENTER"
UPS AUTOMATIC STARTUP
LOAD TO MAINS / LOAD TO INVERTER
TRANSFER TO MAINTENANCE BYPASS
OPERATING MODE
"ENTER"
ECO MODE PROGRAMMING
TRANSFER TO NORMAL MODE
EVENT LOG
"ENTER"
UPS
STATUS
"ENTER"
UPS SYSTEM STATUS
CLOCK
"ENTER"
PROGRAMMING
CONFIGURATION
"ENTER"
LANGUAGE
BUZZER
ACCESS CODE
LOCAL / REMOTE
JBUS LINK (if available)
"ENTER"
PROGRAMMING
Note: Controls are only displayed when available.
5. MODULAR SYSTEMS
Page 19
19
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
5. 6.
Structure of the unit relAted menuS (unit)
It is only for operating the related unit.
Display information about
UPS SYSTEM
UNIT
Cancel Validate
ESC ENTER
Press "ENTER" to reach the various menus, Select the menu with the UP
or DOWN key,
Press "ENTER" to reach the various sub-menus, Select the sub-menu with the UP
or DOWN key,
Validate with the "ENTER" key.
LIST OF MENUS LIST OF SUB-MENUS
MEASUREMENTS
"ENTER"
UPS UNIT OUTPUT
UPS UNIT OUTPUT POWER
INVERTER - BYPASS MAINS
RECTIFIER - BATTERY
UNIT COMMANDS
"ENTER"
UPS AUTOMATIC STARTUP
UNIT COUPLING / UNCOUPLING
EVENT LOG
"ENTER"
UNIT
BATTERY
"ENTER"
BATTERY TEST INFORMATION
BATTERY TEST PROGRAMMING
BATTERY MEASUREMENTS
BATTERY MANUAL TEST
UNIT DATA
"ENTER"
DIAGNOSTIC CODES
REFERENCES
STATUS
"ENTER"
UPS UNIT STATUS
AUXILIARY INPUTS
SUBSET COMMANDS
"ENTER"
RECTIFIER ON / OFF
INVERTER ON / OFF
LOAD TO MAINS / LOAD TO INVERTER
UNIT COUPLING / UNCOUPLING
Note: Controls are only displayed when available.
5. MODULAR SYSTEMS
Page 20
20
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
5. 7.
operAting the modulAr SyStem
Each unit has it’s own control panel. The menu structure is divided into two distinctive parts (Please, refer to sections
5.5 and 5.6)
the second one is for operating the system (System).
one is intended for operating the unit (Unit)
Note: controls are only displayed when available.
5. 7.1. Starting up the modular system
Prior to any operation, please refer to the basic scheme of the system.
CONDITIONS TO bE COMpLETED:
the system is live on the input of each UPS unit,
the battery circuit of each UPS unit is open.
wait for all the control panels to light up,
ON THE CONTROL pANEL OF ONE OF THE UNIT, SELECT:
menu "UPS SYSTEM",
menu " UPS COMMANDS"
and submenu "AUTOMATIC STARTUP".
The startup of all the units is run through an interactive procedure. Just follow the instructions displayed and validate with the "ENTER" key. Pressing the ESC key cancels the action.
At the end of this stage, the load is protected by the UPS units.
The display indicates the end of the automatic start up procedure:
Load protected by inverter
1 2 3 4 5 6
Load rate:
•
0
50 100
120
UNIT 2
5. 7.2. Load transfer from inverter to mains
In the control panel of one of the unit, select:
menu "UPS SYSTEM",
menu "UPS COMMANDS"
and submenu "LOAD TO MAINS".
Display for the "LOAD TO MAINS" control
UPS COMMANDS: LOAD TO MAINS
CONFIRM TRANSFER TO
AUTOMATIC BYPASS
Cancel Validate
ESC ENTER
Validate pressing the ENTER key.
Number of operating units
5. MODULAR SYSTEMS
Page 21
21
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
5. 7.3. Load transfer from mains to inverter
IN THE CONTROL pANEL OF ONE OF THE UNIT, SELECT:
- menu "UPS SYSTEM",
- menu "UPS COMMANDS"
- and submenu "LOAD TO INVERTER".
Display for the "LOAD TO INVERTER" control
UPS COMMANDS: LOAD TO INVERTER
CONFIRM TRANSFER TO INVERTER
Cancel Validate
ESC ENTER
Validate pressing the ENTER key.
5. 7.4. Switching to maintenance bypass - shutdown of the system
pURpOSE:
The Maintenance bypass is for ensuring supply to the load, while the system is stopped for servicing, for instance.
COMpLY WITH THE FOLLOWING pROCEDURE:
In the control panel of one of the unit, select:
- menu "UPS SYSTEM",
- menu "UPS COMMANDS"
- menu "TRANSFER TO MAINTENANCE BYPASS". The startup is run through an interactive procedure. Just follow the instructions displayed and validate with the "ENTER" key.
Display for "TRANSFER TO MAINTENANCE BYP"
UPS commands: to MAINTENANCE BYPASS
CONFIRM LOAD TRANSFER
TO MAINTENANCE BYPASS
Cancel Validate
ESC ENTER
NOTE: when the process is completed, all the UPS units are stopped.
Do not forget that even when the loads are stopped the units are live:
- because of the mains voltage to the rectier and the bypass.
- because of the residual voltage of the capacitors.
- because of the load voltage when the maintenance bypass Q5 is closed and the bypass mains is present.
5. MODULAR SYSTEMS
Page 22
22
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
5. 7.5. System with two redundant units
In a system with two redundant units, only one maintenance bypass can be closed.
5. 7.6. System with two non redundant units or more than two parallel units
In such a system, the maintenance bypass is common to the whole system.
5. 7.7. Uncoupling of a unit
Unit uncoupling can only be achieved if the system is redundant, meaning that it can supply all the energy required to the load with one unit disconnected.
The uncoupling of a unit is to be made from its control panel by selecting:
- the menu "UPS UNIT",
- the menu "UNIT COMMANDS"
- the submenu "UNIT UNCOUPLING",
At this point the UPS unit is uncoupled but still operating:
• Open switch Q3 in the appropriate unit to isolate it from the system.
Note: At this point the UPS unit can be autonomously operated.
5. 7.8. Shutdown of a unit
(The unit has been previously uncoupled - See section 5.7.7)
Shutdown the unit in the following chronology order:
select the menu "SUBSET COMMAND"
select the submenu "INVERTER SHUTDOWN",
select the submenu "RECTIFIER SHUTDOWN"
At this point:
- open battery protection Q20,
- open switch Q4
- open switch Q1.
Do not forget that even when the load is stopped the unit is live:
- because of the mains voltage to the rectier and the bypass.
- because of the residual voltage of the capacitors.
- because of the load voltage coming from the common busbar (downstream of Q3).
5. 7.9. Unit switching on or coupling to the common busbar
CONDITIONS TO bE COMpLETED:
• The system is live upstream of the UPS unit
wait for the control panel to light up,
IN THE CONTROL pANEL OF THE ADEQUATE UNIT, SUCCESSIVELY SELECT:
the menu "UPS UNIT"
the menu "UNIT COMMANDS"
the submenu "AUTOMATIC STARTUP".
The automatic startup is run through an interactive procedure. Just follow the instructions displayed and validate with the "ENTER" key.
Note: at the end of the start up sequence the unit is coupled to the common busbar and Q3 is closed.
5. MODULAR SYSTEMS
Page 23
Q1
Q4
Q3
Q5
Q1
Q1
Q20
MBP
ABP
BP
X50
X40
X10
REC INV
DCC
X20
Q20
X20
Q20
X20
DCC
DCC
X10
REC INV
X10
REC
INV
*
*
*
Q4
Q5
Q3
Q1
Q2
23
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
6. CENTRAL BYPASS SYSTEMS
6. 1.
StAndArd BASic Scheme
Central bypass systems can include up to six modules in parallel.
NOTE: in any case, see the technical details of the drawing.
X10: rectier input X40: bypass input X50: to the load X20: battery connection REC: rectier INV: inverter BAT: battery DCC: battery charger converter BP: bypass facility ABP: automatic bypass MBP: maintenance bypass
* other protection upon request.
6. 2.
lAyout of SwitcheS
UPS UNIT BYPASS CABINET
Q1: Input rectier switch Q2: Unit output switch Q20: Battery protection in the battery enclosure or cabinet
Q4: Input automatic bypass switch Q3: Output switch to the load Q5: Maintenance bypass switch
Page 24
24
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
6. 3.
control pAnelS
CONTROL PANEL OF THE MODULE
Each control panel is composed of:
1 mimic panel
1 eight-line LCD display (with up to 40 charac-
ters)
1 four-key intuitive user interface:1 validation key (ENTER)1 ESC key2 scrolling keys (UP/DOWN)
1 luminous status bar.
The display contrast is set by the factory. It is auto­matically adjusted according to the temperature of the technical plant. No setting is required.
CONTROL PANEL OF THE BYPASS CABINET
6. CENTRAL BYPASS SYSTEMS
Page 25
1
25
ENGLISH
2
1
4
5
3
6
3
4
5
7
6
1
2
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
6. 4.
mimic pAnel of the centrAl BypASS cABinet
Modules 1 to 6
General output to the loads
Transfer impossible
Maintenance bypass
General alarm
6. 4.1. Mimic Panel Description
SYMBOLS GREEN YELLOW RED BLINKING
MODULES 1 to 6 connected Connected and alarm ON
1.BYPASS INPUT Within tolerances Without tolerances
2.LOAD ON INVERTER OK Eco-mode ON
3.LOAD ON MAINS Eco-mode ON OK
4.GENERAL OUTPUT TO THE LOAD
supplied
Load not
supplied
Red: imminent shutdown of
the system
5.LOAD TRANSFER impossible
6.MAINTENANCE BYP ON Yellow: Maint. byp alarm
7.GENERAL ALARM At least one alarm ON Yellow: communication error
6. 4.2. Description of the luminous status bar on the central bypass cabinet
Green bar:
- the loads are protected by the inverters
- the loads are supplied via the bypass path if in Eco-mode
- the system operates on the "Energy Saver" mode
(i.e. the number modules ON depends on the energy required)
Yellow bar:
- the loads are supplied via the bypass mains
- the loads are supplied via the maintenance bypass
Yellow blinking bar: - the general alarm is given or request for servicing
Red bar: - the loads are not supplied
Red blinking bar: - the imminent shutdown alarm is given and the loads will shortly be disconnected.
6. CENTRAL BYPASS SYSTEMS
Page 26
26
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
6. 4.3. Structure of the central bypass cabinet menu
Load protected by inverter
1 2 3 4 5 6
Load rate:
Press "ENTER" to reach the various menus, Select the menu with the UP
or DOWN key,
Press "ENTER" to reach the various sub-menus, Select the sub-menu with the UP or DOWN key, Validate with the "ENTER" key.
LIST OF MENUS LIST OF SUB-MENUS
MEASUREMENTS
"ENTER"
UPS SYSTEM GENERAL OUTPUT
UPS SYSTEM OUTPUT POWER
INVERTER / BYPASS MAINS
UPS COMMANDS
"ENTER"
UPS AUTOMATIC START UP
LOAD TO MAINS / LOAD TO INVERTER
TRANSFER TO MAINTENANCE BYPASS
EVENT LOG
"ENTER"
UPS
UNIT
BYPASS DATA
"ENTER"
DIAGNOSTIC CODES
REFERENCES
STATUS
"ENTER"
UPS GENERAL STATUS
SUBSET COMMAND
"ENTER"
LOAD TO MAINS / LOAD TO INVERTER
SHUTDOWN UPS OUTPUT
CLOCK
"ENTER"
PROGRAMMING
CONFIGURATION
"ENTER"
LANGUAGE
BUZZER
ACCESS CODE
LOCAL / REMOTE
JBUS LINK
"ENTER"
PROGRAMMING
Note: Controls are only displayed when available.
0
50 100
120
6. CENTRAL BYPASS SYSTEMS
Page 27
27
ENGLISH
1
2 3
4
5
6
7
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
6. 5.
mimic pAnel of A module
Rectier and battery charger
Battery
Inverter Modules 1 to 6
Output to the loads
General alarm
6. 5.1. Mimic Panel Description
SYMBOLS GREEN YELLOW RED BLINKING
1.RECTIFIER INPUT Within tolerances Without tolerances
2.RECTIFIER ON ON and Alarm ON
3.BATTERY Charged discharging
Green: charging
Yellow: battery alarm
4.INVERTER ON ON and Alarm ON
5.OUTPUT SWITCH closed Closed and Eco-Mode ON
6.OUTPUT TO THE COMMON BUSBAR
Module
connected
Module not
connected
Red: imminent stop
7.GENERAL ALARM General Alarm ON Communication error
6. 5.2. Description of the luminous status bar on a module
Green bar: the module is connected to the common busbar
Yellow bar: the load is supplied via the automatic or the maintenance bypass
Yellow blinking bar: maintenance alarm or request for servicing
Red bar: the load is not supplied
Red blinking bar: the imminent shutdown alarm is given for the module
OFF Module isolated
6. CENTRAL BYPASS SYSTEMS
Page 28
28
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
6. 5.3. Structure of the Unit menus
Load protected by inverter
1 2 3 4 5 6
Load rate:
Module 1
Press "ENTER" to reach the various menus, Select the menu with the UP
or DOWN key,
Press "ENTER" to reach the various sub-menus, Select the sub-menu with the UP or DOWN key, Validate with the "ENTER" key.
LIST OF MENUS LIST OF SUB-MENUS
MEASUREMENTS
"ENTER"
UPS UNIT OUTPUT
UPS UNIT OUTPUT POWER
INVERTER - BYPASS MAINS
RECTIFIER - BATTERY
UNIT COMMANDS
"ENTER"
UNIT AUTOMATIC STARTUP
UNIT COUPLING / UNCOUPLING
EVENT LOG
"ENTER"
UNIT
BATTERY
"ENTER"
BATTERY TEST INFORMATION
BATTERY TEST PROGRAMMING
BATTERY MEASUREMENTS
BATTERY MANUAL TEST
UNIT DATA
"ENTER"
DIAGNOSTIC CODES
UPS REFERENCES
STATUS
"ENTER"
UPS UNIT STATUS
AUXILIARY INPUTS
SUBSET COMMANDS
"ENTER"
RECTIFIER ON / OFF
INVERTER ON / OFF
LOAD TO MAINS / LOAD TO INVERTER
UNIT COUPLING / UNCOUPLING
Note: Controls are only displayed when available.
0
50 100
120
6. CENTRAL BYPASS SYSTEMS
Page 29
29
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
6. 6.
operAting the centrAl BypASS SyStem
6. 6.1. Using
The central bypass cabinet has a control panel intended for the operation of the system. The control panel of the modules is only dedicated to the module operation.
6. 6.2. Preliminary conditions
Q4, Q5 and Q3 in the central bypass cabinet are open,
Q1, Q2 and Q20 of each module are open.
6. 6.3. Starting up the system
Prior to any operation, please refer to the basic scheme of the system.
CONDITIONS TO bE COMpLETED:
• the input of the system is live
wait for the control panels to light up.
IN THE CENTRAL bYpASS CAbINET:
The UPS is started from the menu "UPS commands /automatic start up" through an interactive procedure. Just follow the instructions displayed and validate with the "ENTER" key. The action can be interrupted by pressing the key "ESC".
The display indicates the end of the automatic start up procedure:
Load protected by inverter
1 2 3 4 5 6
Load rate:
0
50 100
120
Number of operating units
6. CENTRAL BYPASS SYSTEMS
Page 30
30
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
6. 6.4. Load transfer from inverter to mains
IN THE CENTRAL bYpASS CAbINET:
The seamless transfer command from inverter to mains can be achieved from the menu "UPS COMMANDS" and the submenu "LOAD TO MAINS". Validate with the "ENTER" key.
Display for the "LOAD TO MAINS" control
UPS COMMANDS: LOAD TO MAINS
CONFIRM TRANSFER TO AUTOMATIC BYP
Cancel Validate
ESC ENTER
6. 6.5. Load transfer from mains to inverter
IN THE CENTRAL bYpASS CAbINET:
The seamless load transfer from mains to inverter can be achieved in the menu "UPS COMMANDS" and the sub­menu "LOAD TO INVERTER". Validate with the "ENTER" key.
Display for the "LOAD TO MAINS" control
UPS COMMANDS: LOAD TO INVERTER
CONFIRM TRANSFER TO INVERTER
Cancel Validate
ESC ENTER
6. 6.6. UPS shutdown with switching to the maintenance bypass
IN THE CENTRAL bYpASS CAbINET:
The transfer of the system to maintenance bypass should be carried out by selecting the menu "UPS COMMANDS" and the submenu "TRANSFER TO MAINTENANCE BYPASS". This control is run through an interactive procedure. Just follow the instructions displayed and validate with the "ENTER" key.
IN EACH MODULE:
- follow the instructions given on the control panel.
- successively shutdown the rectiers (open Q1).
Note: at this stage the load is supplied by the maintenance bypass (no protection) and the modules are stopped.
6. CENTRAL BYPASS SYSTEMS
Page 31
31
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
6. 6.7. Operating a module of the system
Module uncoupling can only be achieved if the system is redundant, meaning that it can supply all the energy required to the load with one module disconnected.
UNCOUpLING OF A MODULE
The uncoupling of a module is to be made from its control panel by selecting:
the menu "UNIT COMMANDS"
the submenu "UNIT UNCOUPLING" ("cancel" is being displayed)
• press key to reach the module uncoupling option
press key ENTER to conrm the request
open switch Q2
SHUTDOWN OF A MODULE
In the control panel of the relevant module:
select the menu "SUBSET COMMAND"
select the submenu "INVERTER OFF" and conrm with the ENTER key
select the submenu "RECTIFIER OFF" and conrm with the ENTER key
open Q1 and Q20 (battery protection),
Note 1: operations are identical for all modules. Note 2: in case of a redundant system, the command is inhibited if the module uncoupling causes the loss of redun­dancy, and the corresponding alarm is displayed on the central bypass cabinet.
Do not forget that even when the load is stopped the module is live:
because of the input voltage upstream of Q1,
because of the load voltage coming from the common busbar downstream of Q2,
because of the continuous voltage generated by the capacitors. The safety level is only reached after
5 minutes.
STARTING AND COUpLING A MODULE
The startup of the modules is run through an interactive procedure.
In the control panel of the adequate module:
select the menu "UNIT COMMANDS"
select the submenu " UNIT AUTOMATIC STARTUP"
conrm with the ENTER key
comply with the instructions displayed i.e.:close Q1 to supply the rectiervalidate startup with the battery before closing Q20
close Q2.
Note 1: operations are identical for all modules. At this point, the module is connected to the common busbar.
6. CENTRAL BYPASS SYSTEMS
Page 32
32
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
7. DESCRIPTION OF THE MENUS
7. 1.
lcd diSplAy
Various screens can be displayed:
THE pERMANENT DISpLAY bY DEFAULT
Load protected by inverter
Load rate:
0
50 100
120
A)THE LOAD SUppLY SOURCE IS DISpLAYED, I.E.:
LOAD PROTECTED BY INVERTER,
LOAD SUPPLIED BY AUTOMATIC BYPASS,
LOAD SUPPLIED BY MAINTENANCE BYPASS,
OPERATING ON BATTERY,
LOAD OFF,
b)THE ACTUAL ALARMS ARE DISpLAYED AS LONG AS THEY HAVE NOT bEEN RESET bY THE OpERATOR (OR AUTO-RESET).
C) T
HE LOAD RATE IS DISpLAYED AS LONG AS LESS THAN 4 ALARMS ARE NOT ACTIVATED.
Note: if the "
" icon is displayed, some maintenance has to be planned.
THE MENU SCREEN
MEASUREMENTS AUTOMATIC START UP
UPS COMMANDS LOAD TO MAINS / INVERTER
OPERATING MODE TRANSFER TO MAINTENANCE BYP
EVENT LOG
D) THE MENUS AVAILAbLE ARE DISpLAYED.
E) T
HE SUbMENU RELATED TO THE SELECTED MENU IS HIGHLIGHTED ON THE DISpLAY.
Note: the remaining displays are described in the corresponding paragraphs.
A
Area D Area E
B
C
}
} }
Page 33
33
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
7. DESCRIPTION OF THE MENUS
7. 2.
commentS concerning the menuS
7. 2.1. Menu measurements
This menu displays the following system measurements:
general measurements of the UPS
• output power of the UPS,
inverter and bypass measurements,
rectier measurements.
7. 2.2. Menu UPS commands
The UPS commands menu enables (Please refer to the sections related to the menu structure):
the automatic start up (interactive procedure)
the transfer from the inverter to the mains (and vice-versa),
the transfer to the maintenance bypass (interactive procedure),
Note: in the event of a modular system, the UPS COMMANDS menu is common to all the modules connected. The control can be performed on whatever module.
7. 2.3. Menu Event log
Principle: The UPS has a memory enabling the record and date all alarms, status or commands that could arise during opera­tion. This memory is saved utilising a separate supply. The log can record up to 500 items according to the FIFO principle (First In - First out). When the log is lled up, the latest information recorded overwrites the earliest one.
Use: To improve the user-friendliness, the latest records of the relevant date are displayed over six lines. Press key or to respectively scroll up to previous line or scroll down to next line. The "ENTER" key provides access to the previous days.
7. 2.4. Battery
The battery test is for controlling the battery capacity to supply energy. The battery test can either be made manually or automatically.
bATTERY TEST INFORMATION
This menu provides information to show:
the result of the latest battery test (OK, failed or aborted),
date and time of the latest battery test,
date and time of the next battery test. If the test is not scheduled, "----" is displayed instead of the date.
TEST pROGRAMMING
The battery test can be made automatic from the control panel by setting the frequency, the day of the week and the time.
BATTERY: BATTERY TEST PROGRAMMING
BATTERY TEST: inactive
PROGRAMMED ON: Friday at 20:00
EVERY: 8 weeks
Page 34
34
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
bATTERY MEASUREMENTS
The following measurements can be displayed:
Battery voltage,
Battery current (minus sign in front of the value means the battery is discharging)
Battery temperature,
Load rate.
BATTERY MEASUREMENTS
Vdc = 450 V I batt = - 56 A
Load rate :
7. 2.5. UPS system data
DIAGNOSTIC CODES
UPS SYSTEM DATA: DIAGNOSTIC CODES
User Status Alarms
Adv Rect 120000456087 000000000
Adv Byp 000657003300 000007650
Adv Inv 000765876000 006549800
Adv Hmi 076431789700 054687900
Adv Com 000006757400 000007650
In case of UPS failure, the customer can transmit these codes to the CIM DEPARTMENT for complete diagnostic.
UpS REFERENCES
This menu displays the following module information:
- module number,
- serial number,
- power in kVA.
7. 2.6. Status menu
UpS SYSTEM STATUS
The activation or de-activation of each state is conrmed by YES or NO. By means of the up and down keys, you can scroll the list. Symbol is not displayed at the beginning of the list and is not displayed at the end.
7. DESCRIPTION OF THE MENUS
Page 35
35
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
List of STATUS
Wording
Rectier ON
Rectier input supply out of tolerances
Charger ON
Boost charge
Commissioning charge
Synchronisation reference on bypass input
Synchronisation reference on ACS
Battery charging
Battery charged
Battery test aborted
Battery test running
Inverter ON
ACS functioning forced
Output on inverter
Output on automatic bypass
Output not supplied
Output on maintenance bypass
In eco mode
Transfer to eco mode
Bypass input supply out of tolerances
Bypass input absent
Inverter switch ON
Bypass switch ON
Unit available
Unit isolated
Q2 closed
Q3 closed
Maintenance bypass Q5 closed
General maintenance bypass closed
Q21 …..Q22 closed
ESD activated
Input supplied by EmSet (emergency set)
Maintenance mode active
Load protected by inverter
Load on automatic bypass
Load OFF
Load on maintenance bypass
Automatic start in progress
Transfer to maintenance bypass
Energy saver activated (parallel system with central bypass)
Unit in standby mode
Automatic start forced
Energy saver deactivated (parallel system with central bypass)
Local/remote control
Auxiliary inputs 1 to 12
7. DESCRIPTION OF THE MENUS
Page 36
36
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
7. 2.7. Clock
The UPS is tted with a clock that enables the time and date of every event to be known. The clock can only be set from the control panel.
PROGRAMMING
FRIDAY 09:09:21
30/05/2005
CLOCK
The "ENTER" key enables to select the eld to be modied. The "ESC" key enables to return to the previous eld. The scrolling keys
or enable to change the parameters of the selected eld.
7. 2.8. Configuration
LANGUAGE
Two languages are available. on the control panel.
CONFIGURATION:LANGUAGE
Language: FRENCH
Cancel Validate
ESC ENTER
The scrolling keys
or enable to select the appropriate language.
Note: other languages can be downloaded by the Servicing Department.
bUzzER
The buzzer can be activated or de-activated when the alarm appears by means of the scrolling keys or . The buzzer is activated by default.
CONFIGURATION:BUZZER
Buzzer: YES
Cancel Validate
ESC ENTER
7. DESCRIPTION OF THE MENUS
Page 37
37
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
ACCESS CODE
The access code enables to lock the access to the following menus:
UPS COMMANDS,
OPERATING MODE,
BATTERY / BATT TEST PROGRAMMING,
SUBSET COMMAND,
CLOCK,
CONFIGURATION,
JBUS LINK.
CONFIGURATION: ACCESS CODE
Type new access code:??????
This code can only be set from the control panel. It can contain up to 6 characters from "A" to "Z" and "0" to "9".
Keys
or enable to select the character.
The "ENTER" key is for entering the character selected.
The "ESC" key enables to return to the previous eld.
For coding with less than 6 characters, the ENTER key needs to be pressed up to the sixth character, and once
more for validation.
CONFIGURATION: ACCESS CODE
CONFIRM NEW
ACCESS CODE: ??????
Cancel Validate
ESC ENTER
Note: the access code is only activated when the display is in standby, i.e. after 4 minutes without action on any key.
7. DESCRIPTION OF THE MENUS
Page 38
38
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
LOCAL / REMOTE
The UPS can be connected to a remote equipment. By default the control panel has the master function while the remote control has the slave function (all controls are inhibited). Through this menu, controls can be sent from the
remote equipment.
CONFIGURATION:LOCAL-REMOTE
Switch to: LOCAL MONITORING
Cancel Validate
ESC ENTER
7. 2.9. JBUS link
Note: the JBUS link menu is only displayed if the setting is available on the UPS.
Conguration parameters are:
the baudrate (1200 to 19200),
the parity (none, even, odd),
the slave number (001 to 255).
PROGRAMMING 1
baudrate: 19200
Parity: NONE
Slave: 001
JBUS LINK
If a second JBUS link is available, the corresponding screen is automatically displayed after completing the setting of the rst JBUS link.
7. DESCRIPTION OF THE MENUS
Page 39
39
ENGLISH
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
7. 2.10. List of alarms
DISpLAY OF ACTIVATED ALARMS
When an alarm is activated, the description is displayed and an audible signal is given.
RESETTING AN ALARM
The alarms can be reset by means of the "ENTER" key. Thus, the audible alarm is silenced, but its description re­mains displayed as long as the alarm is activated. If several alarms are displayed, each of them needs to be silenced individually.
LIST OF ALARMS FOR SINGLE UNITS AND MODULAR SYSTEMS
Wording
Rectier critical alarm
Rectier preventive alarm
Charger general alarm
Battery alarm
Battery room alarm
Battery test failed
Battery circuit open
Operating on battery
Battery autonomy end
Battery discharged
Inverter critical alarm
Inverter preventive alarm
Bypass critical alarm
Bypass preventive alarm
Manual/automatic transfer disabled
Automatic transfer disabled
Maintenance bypass alarm
Backfeed protection open
Unit imminent stop
Unit overload
Insufcient resources
Synchronisation reference ACS absent
Control preventive alarm
Control alarm
Internal temperature alarm
Loss of redundancy
Unit general alarm
Load imminent stop
Servicing preventive alert
UPS overload alarm
Control panel alarm
7. DESCRIPTION OF THE MENUS
Page 40
40
DELPHYS MX 250-900 - Ref.:
OPMDELMX1010-GB_01
7. 3.
overloAd monitoring
pRINCIpLE:
The UPS overload monitoring is based on reference levels (the higher the load rate, shorter the overload capacity). There are two distinct reference levels:
the rst one corresponds to the overload capacity of the bypass input,
the second one corresponds to the overload capacity of the inverter.
While operating from the inverter, the load is automatically transferred to the automatic bypass when the reference level reaches 50% and the bypass input is present.
SIGNALLING AND AUTOMATIC ACTIONS:
The UPS OVERLOAD alarm is activated if:
the load rate exceeds 103% ("LOAD ON INVERTER"),
the load rate exceeds 105% ("LOAD ON MAINS").
The alarm disappears if the load rate drops below 100%
TYpICAL UNIT OVERLOAD < 30°C
Overload rate Inverter and byp locked Automatic bypass
Total overload time inverter
+ automatic bypass
110% 60 minutes 60 minutes 30 min + 60 min
125% 10 minutes 10 minutes 5 min + 10 min
150% 30 seconds 1 minute 30 sec + 1 min
NOTE: Should an extended overload occur, the static switch warms up, which results in the disconnection of the load after some time. If the load is supplied by the bypass mains following an automatic transfer, no return to the inverter is possible as long as the UPS is overloaded and the UPS OVERLOAD alarm has not been reset.
7. 4.
remAining BAck up time
The remaining back up time is displayed on the control panel when the UPS operates from the battery. The calcula­tion is obtained from the battery capacity and the Ampères per hour (Ah) consumed by the load. Text displayed can be set by Consulting, Inspection and Maintenance Department.
7. DESCRIPTION OF THE MENUS
Page 41
Page 42
Non contractual document. © 2010, Socomec SA. All rights reserved.
HEAD OFFICE
SOCOMEC GROUP
S.A. SOCOMEC capital 11 102 300 € - R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse - F-67235 Benfeld Cedex
SOCOMEC UPS Strasbourg
11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex- FRANCE Tel. +33 (0)3 88 57 45 45 - Fax +33 (0)3 88 74 07 90 ups.benfeld.admin@socomec.com
SOCOMEC UPS Isola Vicentina
Via Sila, 1/3 - I - 36033 Isola Vicentina (VI) - ITALY Tel. +39 0444 598611 - Fax +39 0444 598622 info.it.ups@socomec.com
SALES, MARKETING AND SERVICE MANAGEMENT
SOCOMEC UPS Paris
95, rue Pierre Grange F-94132 Fontenay-sous-Bois Cedex - FRANCE Tel. +33 (0)1 45 14 63 90 - Fax +33 (0)1 48 77 31 12 ups.paris.dcm@socomec.com
Socomec UPS
worldwide
IN EUROPE
BELGIUM
Tel. +32 (0)2 340 02 34 Fax +32 (0)2 346 16 69 be.ups.sales@socomec.com
FRANCE
Tel. +33 (0)1 45 14 63 90 Fax +33 (0)1 48 77 31 12 ups.paris.dcm@socomec.com
GERMANY
Tel. +49 (0) 621 71 68 40 Fax +49 (0) 621 71 68 44 4 de.ups.all@socomec.com
ITALY
Tel. +39 02 98 242 942 Fax +39 02 98 240 723 siconmi@socomec.com
NETHERLANDS
Tel. +31 (0)30 63 71 504 Fax +31 (0)30 63 72 166 nl.ups.sales@socomec.com
POLAND
Tel. +48 (0)22 2345 223 Fax +48 (0)22 2345 223 ups.poland@socomec.com
PORTUGAL
Tel. +351 261 812 599 Fax +351 261 812 570 portugal@socomec.com
RUSSIA
Tel. +7 495 775 19 85 Fax +7 495 775 19 85 ups.russia@socomec.com
SLOVENIA
Tel. +386 1 5807 860 Fax +386 1 5611 173 si.ups.info@socomec.com
SPAIN
Tel. +34 935 407 575 Fax +34 935 407 576 info@socomec-aron.com
UNITED KINGDOM
Tel. +44 (0)1285 863300 Fax +44 (0)1285 862304 uk.ups.sales@socomec.com
IN ASIA
CHINA
Tel. +86 10 8889 2202 Fax +86 10 8889 2150 socomec@socomec.com.cn
INDIA
Tel. +91 44 3921 5400 Fax +91 44 3921 5450 — 51 sales@socomec-ups.co.in
MALAYSIA
Tel. +603 7804 1153 Fax +603 7803 8901 sales@cspm.com.my
SINGAPORE
Tel. +65 6745 7555 Fax +65 6458 7377 sg.ups.sales@socomec.com
THAILAND
Tel. +66 2 941-1644-7 Fax. +66 2 941-1650 info@socomec-th.com
VIETNAM
Tel. +84-839734.990 Fax +84-839735.088 info@socomec-vn.com
IN OCEANIA
AUSTRALIA
Tel. +61 2 8985 7365 Fax +61 2 8985 7345 james.fraser@socomec.com
www.socomec.com
YLAT I ROF D I LAVECNARF ROF D I L AV
ISO 9001:2008
FM 28237
ISO14001:2004
EMS 553476
Loading...