UPS/NTA GB/DMX-DMP JBUS.D Page 19 / 22
5. ALARMS: Address 0x40, 4 words
CODE DESCRIPTION BIT ADRESSE
basse
AC Module Unite
A00 General Alarm 0 0x40
X X X
A01 Battery failure 1 0x40
X X
A02 UPS overload 2 0x40
X X X
A03
A04 Control failure - critical alarm 4 0x40
A05 Rectifier input supply out of tolerance 5 0x40
X X X
A06 Bypass input supply out of tolerance 6 0x40
X X
A07 Over temperature alarm 7 0x40
X X X
A08 Maintenance bypass closed 8 0x40
X X
A09
A10 Battery charger fault
X X
A11
A12
A13
A14
A15
A16
A17 Improper condition of use (Q3 and Q5 closed) 1 0x41
X X
A18 Inverter stopped for overload
(or bypass transfer)
2 0x41
X X
A19 Microprocessor control system - preventive al. 3 0x41 X X X
A20
A21 PLL fault 5 0x41
X X
A22 Rectifier input supply fault 6 0x41
X X
A23 Rectifier preventive alarm 7 0x41 X X
A24
A25 Inverter preventive alarm 9 0x41 X X
A26 Charger general alarm 10 0x41
X X
A27
A28
A29 Bypass preventive alarm 13 0x41 X X X
A30
A31 Imminent STOP 15 0x41
X X X
A32 Unit 1 general alarm 0 0x42
X X
A33 Unit 2 general alarm 1 0x42
X X
A34 Unit 3 general alarm 2 0x42
X X
A35 Unit 4 general alarm 3 0x42
X X
A36 Unit 5 general alarm 4 0x42
X X
A37 Unit 6 general alarm 5 0x42
X X
A38 External alarm 6 0x42
X X X
A39
A40
A41
A42 e-Service 10 0x42
A43 redundancy loss 11 0x42
X X
A44 Servicing alarm 12 0x42
X
A45 Automatic and manual transfer disable 13 0x42
X X
A45 Automatic transfer disable 14 0x42
X X
A47 Battery room alarm 15 0x42
X X
A48 Maintenance bypass alarm 0 0x43
X X
A49 Battery discharged 1 0x43
X X
A50 2 0x43
X X
A51 Synoptic alarm 3 0x43
A52 Rectifier fault - critical alarm 4 0x43 X X
A53
A54 Inverter fault - critical alarm 6 0x43 X X
A55
A56
A57
A58 ESD activated 10 0x43
X X X
A59 Battery circuit open 11 0x43
X X
A62 Bypass critical alarm 14 0x43 X X X
For more detail, please refer to the single unit UPS table §1.5