socomec COUNTIS M43 User Manual

Page 1
THREE PHASE DIN RAIL ENERGY METER
COUNTIS M43
MANUAL V1.0
SOCOMEC CHINA CO., Ltd
SOCOMEC CHINA CO., Ltd
SOCOMEC CHINA CO., LtdSOCOMEC CHINA CO., Ltd 溯高美索克曼电气
溯高美索克曼电气((((上海
溯高美索克曼电气溯高美索克曼电气 http://www.socomec.com
上海))))有限公司
上海上海
有限公司
有限公司有限公司
Page 2
Statement
All rights reserved. Without the written permission of Socomec, the contents of any passages and chapters
in this manual shall not be copied or reproduced or disseminated in any form. Otherwise, all
consequences shall be borne by the violator.
Socomec reserves all legal rights.
Socomec reserve the right to modify the product specifications described in this manual without prior
notice. Before ordering, please contact our company or local agent for the latest specifications of this
product.
SOCOMEC CHINA CO., Ltd
SOCOMEC CHINA CO., Ltd
SOCOMEC CHINA CO., LtdSOCOMEC CHINA CO., Ltd 溯高美索克曼电气
溯高美索克曼电气((((上海
溯高美索克曼电气溯高美索克曼电气 http://www.socomec.com
上海))))有限公司
上海上海
有限公司
有限公司有限公司
Page 3
Contents
Part 1. Product overview
1.1 Brief Introduction --------------------------------------------------------------------------------------------------------------1
1.2 Product characteristics -------------------------------------------------------------------------------------------------------1
1.3 Application ----------------------------------------------------------------------------------------------------------------------2
Part 2. General Specifications
2.1 Specifications-----------------------------------------------------------------------------------------------------------------3
2.2 Accuracy -------------------------------------------------------------------------------------------------------------------------3
2.3 RS485 Communication-------------------------------------------------------------------------------------------------------4
2.4 Environment--------------------------------------------------------------------------------------------------------------------4
2.5 Dimendions---------------------------------------------------------------------------------------------------------------------5
2.6 Wiring Diagram----------------------------------------------------------------------------------------------------------------5
Part 3. Operation Instructions
3.1
Display and Operation
3.1.1
Button Definition
3.2
Measurement
---------------------------------------------------------------------------------------------------------------6
---------------------------------------------------------------------------------------------------6
-------------------------------------------------------------------------------------------------------6
3.2.1 Voltage & Current----------------------------------------------------------------------------------------------------------6
3.2.2 Frequency, Power Factor & Demand---------------------------------------------------------------------------------8
3.2.3 Power ------------------------------------------------------------------------------------------------------------------------9
3.2.4 Energy------------------------------------------------------------------------------------------------------------------------10
3.3 Setting by button--------------------------------------------------------------------------------------------11
3.3.1
Button Operation
-------------------------------------------------------------------------------------------------------13
3.3.2
Number Entry Procedure
-------------------------------------------------------------------------------------------13
3.3.3 Set Password----------------------------------------------------------------------------------------------------------------14
SOCOMEC CHINA CO., Ltd
SOCOMEC CHINA CO., Ltd
SOCOMEC CHINA CO., LtdSOCOMEC CHINA CO., Ltd
((((上海
上海))))有限公司
溯高美索克曼电气
溯高美索克曼电气
溯高美索克曼电气溯高美索克曼电气 http://www.socomec.com
上海上海
有限公司
有限公司有限公司
Page 4
3.3.4 Modbus Address-----------------------------------------------------------------------------------------------------------14
3.3.5 Baud Rate--------------------------------------------------------------------------------------------------------------------15
3.3.6 Parity--------------------------------------------------------------------------------------------------------------------------15
3.3.7 Stop Bit-----------------------------------------------------------------------------------------------------------------------16
3.3.8 CT Setting---------------------------------------------------------------------------------------------------------------------17
3.3.9 PT Setting---------------------------------------------------------------------------------------------------------------------18
3.3.10 Pule Output----------------------------------------------------------------------------------------------------------------19
3.3.11 Pulse Constant-------------------------------------------------------------------------------------------------------------19
3.3.12 Pulse Duration-------------------------------------------------------------------------------------------------------------20
3.3.13 Set DIT ----------------------------------------------------------------------------------------------------------------------21
3.3.14 Set backlit lasting time--------------------------------------------------------------------------------------------------22
3.3.15 Set System------------------------------------------------------------------------------------------------------------------23
3.3.16 Clear-------------------------------------------------------------------------------------------------------------------------24
Part 4...Modbus register Map------------------------------------------------------------------------------------------------25
SOCOMEC CHINA CO., Ltd
SOCOMEC CHINA CO., Ltd
SOCOMEC CHINA CO., LtdSOCOMEC CHINA CO., Ltd
((((上海
溯高美索克曼电气
溯高美索克曼电气
溯高美索克曼电气溯高美索克曼电气 http://www.socomec.com
上海))))有限公司
上海上海
有限公司
有限公司有限公司
Page 5
-
Part 1 Product overview
1.1 Brief Introduction
COUNTIS M43 measures and displays the characteristics of single phase two wires (1p2w), three phase
three wires(3p3w,) and three phase four wires(3p4w) supplies, including voltage, frequency, current,
power ,active and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh.
Maximum demand current can be measured over preset periods of up to 60minutes. In order to measure
energy, the unit requires voltage and current inputs in addition to the supply required to power the
product. The requisite current input(s) are obtained via current transformers(CT).
This meter can be configured to work with a wide range of CTs, giving the unit a wide range of operation.
Built-in interfaces provides pulse and RS485 Modbus RTU outputs. Configuration is password protected.
This unit can be powered from a separate auxiliary (AC or DC) supply. Alternatively it can be powered from
the monitored supply, where appropriate.
1.2 Product characteristics
Measures kWh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, THD, etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail mounting 35mm
1/5A CT connection
Class 0.5S
The Unit can measure and display:
Line voltage and THD% (total harmonic distortion) of all phases
Line Frequency
Currents, Current demands and current THD% of all phases
Power, maximum power demand and power factor
Active energy imported and exported
Reactive energy imported and exported
- 1
Page 6
-
The unit has password-protected set-up screens for:
Changing password
Supply system selection 1p2w, 3p3w,3p4w
Demand Interval time
Reset for demand measurements
Pulse output duration
Two pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring
from another display or a computer.
1.3 Application
COUNTIS M43 is a multi-functional three phase energy meter, designed for power system, public facilities,
industrial applications and residential power monitoring needs. It can also be used in AC charging piles,
solar photovoltaic and other occasions. Its complete communication function makes it very suitable for
real-time power monitoring systems.
- 2
Page 7
-
Part 2 General Specifications
2.1 Specifications
Voltage::Rated Voltage ( Un) L-N 100 to 276V a.c. (not for 3p3w supplies)
173 to 480V AC. (3p supplies only)
Primary Voltage: 20V-500kV
Second Voltage:100-500V
Auxiliary Supply85~275V AC / 120~380V DC
Current Primary Current :1-9999A
Second Current1A or 5A
Over current withstand: 20 Imax for 0.01s
Operational frequency:Rated50/60Hz
Range45-65 Hz
Insulation capabilities AC voltage withstand 4KV/1min
Impulse voltage withstand 6kV – 1.2µS waveform
Internal Power Consumption≤ 2W.
Pulse Output 1Configurable
Pulse Output 2Fixed 3200imp/kWh
DisplayLCD with backlit
Max Reading9999999.9 kWh / kVArh
2.2 Accuracy
Voltage0.2%
Current0.2%
Frequency0.2%
Power Factor0.5%
- 3
Page 8
-
Active Power0.5%
Reactive Power±0.5%
Apparent power±0.5%
Active energyClass 0.5S
Reactive energyClass2
2.3 RS485 Communication
Bus TypeRS485
Communication ProtocolModbus RTU
Baud rate 2400/4800/9600/19200/38400bps
Modbus Address1-247
Bus load64pcs
Communication distance1000m
ParityEVEN /ODD/NONE
Data bit8
Stop bit1
2.4 Environment
Operating humidity ≤90%
Storage humidity ≤95%
Operating temperature -25~+55
Storage temperature -40~+70
Standard GB-T 17215/ IEC62053-21/ EN50470-1/3
Accuracy Class 1.0
Installation category CAT III
- 4
Page 9
-
Protection against penetration of dust and water: IP51indoor
Insulating encased meter of protective class: II
Altitude ≤2000m
2.5 Dimensions
3
5
m
m
2.6 Wiring Diagram
3P4W 3P3W 1P2W
Width72 mm
Length: 94.5 mm
Height:65 mm
- 5
Page 10
-
Part 3. Operation Instructions
3.1 Display and Operation
When the meter is powered on, the meter will initialize and do self-checking
Display as following:
1
2
3
Full screen
Software version
Self-checking finish
3.1.1 Button Definition
Selects V and A display screen.
In Set-up Mode, it is the “Left” or “Back” button
Selects Hz and PF display screen.
In Set-up Mode, it is the “Up” button
Selects power display screen.
In Set-up Mode, it is the “Down” button
Selects energy display screen.
In Set-up Mode, it is the “Enter” or "Right" button.
3.2 Measurement
3.2.1
Voltage & Current
Press button :
- 6
Page 11
-
1
1-1
2
Phase to neutral voltages(3p4w)
Phase to neutral voltages(3p3w)
Current on each phase
3
Neutral current
4 Phase to neutral voltage THD%(3p4w)
- 7
Page 12
-
5 Current THD% for each phase
3.2.2
Frequency, Power Factor & Demand
Press button
1
Frequency and Power Factor (total)
2
Power Factor of each phase
3
Maximum Current Demand
- 8
Page 13
-
4 Maximum Power Demand
3.2.3 Power
Press
1
Instantaneous Active Power in kW
2
Instantaneous Reactive Power in kVAr
3 Instantaneous Volt-amps in KVA
- 9
Page 14
-
4
Total kW, kVAr, kVA
3.2.4 Energy
Press button
1 Total active energy in kWh
2 Total reactive energy in kVArh
3 Imported active energy in kWh
- 10
Page 15
-
4 Exported active energy in kWh
5
Imported reactive energy in kVArh
6 Exported reactive energy in kVArh
3.3 Setting by button
To enter set-up mode, pressing the button for 3 seconds, until the password screen
appears.
Setting up is password-protected so you must enter the correct password (default ‘1000’) before
processing. If an incorrect password is entered, the display will show: Err
- 11
Page 16
-
To exit setting-up mode, press repeatedly until the measurement screen is restored.
3.3.1 Button Operation
1. After Entering the Setting manu, use the and buttons to select the
required item from the menu. Selection does not roll over between bottom and top of list
2.
Press
3. If an item flashes, then it can be adjusted by the and buttons. If not,
there may be a further layer.
4.
Having selected an option from the current layer, press to confirm your selection. The
SET indicator will appear.
5.
Having completed a parameter setting, press to return to a higher menu level. The SET
indicator will be removed and you will be able to use the and buttons for
to confirm your selection.
further menu selection.
- 12
Page 17
-
6.
On completion of all set-up, press repeatedly until the measurement screen is restored.
3.3.2Number Entry Procedure
When setting up the unit, some screens require the entering of a number. In particular, on entry to the
setting up section, a password must be entered. Digits are set individually, from left to right. The
procedure is as follows:
1.
The current digit to be set flashes and is set using the and
2. Press to confirm each digit setting. The SET indicator appears after the last digit has
been set.
3. After setting the last digit, press to exit the number setting routine. The SET indicator
will be removed.
3.3.3
Set Password
1
2-1
Use the and
to choose the change password option
Press the to enter the
change password routine. The new
password screen will appear with the
first digit flashing
- 13
Page 18
-
2-2
Use and to set
the first digit and press to
confirm your selection. The next digit will
flash.
Press to exit the number setting routine and return to the Set-up menu. SET will
be removed
3.3.4 Modbus Address
1
2-1
(The range is from 001 to 247)
From the Set-up menu, use
and buttons to select the
Address ID
Press button to enter the
selection routine. The current setting will
be flashing.
- 14
Page 19
-
2-2
3.3.5 Baud Rate
Options: 2.4k, 4.8k, 9.6k, 19.2k, 38.4k.
1
Use and
buttons to choose Modbus Address(001
to 247)
From the Set-up menu, use
and buttons to select the
Baud Rate option.
2-1
2-2
Press to enter the selection
routine. The current setting will flash.
Use and
buttons to choose Baud rate 2.4k. 4.8k,
9.6k, 19.2k, 38.4k
3.3.6
Parity
Options: EVEN / ODD / NONE.
- 15
Page 20
-
1
2-1
2-2
From the Set-up menu, use
and buttons to select the
Parity option.
Press to enter the selection
routine. The current setting will flash.
Use and
buttons to choose Parity (EVEN / ODD /
NONE)
3.3.7 Stop bit
Option1 or 2.
1
From the Set-up menu, use
and buttons to select the
Stop Bit option.
- 16
Page 21
-
2
Press to enter the selection
routine. The current setting will flash.
Use and
buttons to choose Stop Bit (2 or 1)
Note: Default is 1, and only when the parity is NONE that the stop bit can be changed to 2.
3.3.8 CT Setting
The CT option sets the secondary current (CT2 1A or 5A) of the current transformer (CT) that wires to the
meter.
1
From the Set-up menu, use
and buttons to select the CT
option.
2
Secondary CT setting
Press to enter the CT
secondary current selection
routine.:5A/1A
3
Set CT Ratio value Press to
enter the CT Ratio setting screen. Use
and buttons to
choose the CT ratio. The range is from
0001 to 9999.
- 17
Page 22
-
Example: If set the ratio to be 100,it means the primary current equals secondary currentx100
3.3.9 PT Setting
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer(PT) that wires to
the meter.
1
From the Set-up menu, use
and buttons to select the
PT option. The screen will show the
voltage PT secondary voltage value. The
default value is 400V
2
Secondary PT setting
Press to enter the PT
secondary voltage selection routine. The
range is from 100 to 500V
3
Set PT ratios value
Press to enter the PT ratio
screen.
The range is from 0001 to 9999
For example, if set the ratio to be 100,it means the primary voltage equals secondary
voltagex100
- 18
Page 23
-
3.3.10 Pulse Output
On completion of the entry procedure, press
This option allows you to configure the pulse output. The output can be set to provide a pulse for a
defined amount of energy active or reactive.
Use this section to set up the pulse output 1—Units: Total kWh, Total kVArh
1
From the Set-up menu, use and
buttons to select the Pulse output
option.
2
Press to enter the selection
routine. The unit symbol will flash.
Use and buttons to
choose kWh or kVArh.
to confirm the setting and press
to return to the main set up menu.
3.3.11Pulse Constant
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per
0.01kWh/0.1kWh/1kWh/10kWh/100/1000kWh.
- 19
Page 24
-
and
(It shows 1 impulse = 10kWh/kVArh)
1
From the Set-up menu, use
buttons to select the Pulse Rate
option.
2
Press to enter the selection routine.
The current setting will flash. Use
and buttons to choose the
Constant.
Press to confirm the
Pulse
setting and press to return to the
main set up menu.
3.3.12
The energy monitored can be active or reactive and the pulse width can be selected as 200, 100(default)
or 60ms.
Pulse Duration
- 20
Page 25
-
(It shows pulse width of 200ms)
1
From the Set-up menu, use and
buttons to select the Pulse width
option.
2
Press to enter the selection routine.
The current setting will flash.
Use and buttons to
choose pulse width. On Completion of the entry
procedure, press to confirm the
setting and press to return to the
main set up menu.
3.3.13 Demand Integration Time
This sets the period in minutes over which the current and power readings are integrated for maximum
demand measurement. The options are: 0, 5, 8, 10, 15, 20, 30, 60 minutes
- 21
Page 26
-
and
1
From the set-up menu, use
buttons to select the DIT option. The
screen will show the currently selected integration
time.
2
Press to enter the selection routine.
The current time interval will flash
Use and buttons to
select the time required.
ress to confirm the selection. SET
indicator will appear.
Press to exit the DIT selection routine and return to the menu.
3.3.14
Set backlit lasting time
1 The backlit lasting time is settable
Default lasting time is 60minutes
For example, if it’s set as 5, the backlit will be off
in 5minutes from the last time operation on the
meter.
- 22
Page 27
-
2
Press to enter the selection routine.
The current time interval will flash
The options can be:
0(always on),5,10,30,60,120minutes
Use and buttons to
select the time required. Press to
confirm the set-up,
3.3.15
Set System
Use this section to set the type of power supply being monitored.
1
From the Set-up menu, use and
The screen will show the currently selected power
supply.
2
Press to enter the selection routine.
The current selection will flash. Use
and buttons to select the required
system option: 1P2(W), 3P3(W) ,3P4(W). Press
buttons to select the System option.
to confirm the selection. SET
indicator will appear. Press to exit
the system selection routine and return to the
menu. SET will disappear and you will be returned
to the main Set-up Menu.
- 23
Page 28
-
3.3.16
Clear
The meter provides a function to reset the maximum demand value of current and power.
1
From the Set-up menu, use
and buttons to select the
reset option.
2
Press to enter the selection
routine. The MD will flash.
Press to confirm the setting
and press to return to the
main set up menu.
- 24
Page 29
-
Part 4...Modbus register Map
Function code
04 to read input parameters
Address
(Register
)
30001
30003
30005
30007
30009
Parameter
Phase 1 line to neutral volts.
Phase 2 line to neutral volts.
Phase 3 line to neutral volts.
Phase 1 current.
Phase 2 current.
Input Register Parameter
Length of the byte
4 Float V 00 00 X
4 Float V 00 02 X X
4 Float V 00 04 X X
4 Float A 00 06
4 Float A 00 08 X
Data
Format
unit
寄存器首地址
寄存器首地址
寄存器首地址寄存器首地址
High
Low
Byte
Byte
3 Ø 3 Ø 1
Ø
4 W 3 W 2
W
30011
30013
30015
30017
30019
30021
Phase 3 current.
Phase 1 power.
Phase 2 power.
Phase 3 power.
Phase 1 volt amps.
Phase 2 volt amps.
4 Float A 00 0A X
4 Float W 00 0C X
4 Float W 00 0E X X
4 Float W 00 10 X X
4 Float VA 00 12 X
4 Float VA 00 14 X X
- 25
Page 30
-
30023
30025
30027
30029
30031
30033
30035
30037
30039
Phase 3 volt amps.
Phase 1 Reactive Power
Phase 2 Reactive Power
Phase 3 Reactive Power
Phase 1 power factor (1).
Phase 2 power factor (1).
Phase 3 power factor (1).
Phase 1 phase angle.
Phase 2 phase angle.
4 Float VA 00 16 X X
4 Float VAr 00 18 X
4 Float VAr 00 1A X X
4 Float VAr 00 1C X X
4 Float None 00 1E X
4 Float None 00 20 X X
4 Float None 00 22 X X
4 Float Degrees 00 24 X
4 Float Degrees 00 26 X X
30041
30043
30047
30049
30053
30057
30061
30063
30067
Phase 3 phase angle.
Average line to neutral volts.
Average line current.
Sum of line currents.
Total system power.
Total system volt amps.
Total system VAr.
Total system power factor (1).
Total system phase angle.
4 Float Degrees 00 28 X X
4 Float V 00 2A X X
4 Float A 00 2E
4 Float A 00 30
4 Float W 00 34
4 Float VA 00 38
4 Float VAr 00 3C
4 Float None 00 3E
4 Float Degrees 00 42
- 26
Page 31
-
30071
30073
30075
30077
30079
30081
30083
30085
Frequency of supply voltages.
Total Import kWh
Total Export kWh.
Total Import kVArh .
Total Export kVArh .
Total VAh
Ah
Total system power demand (2).
Maximum total system power demand
4 Float Hz 00 46
4 Float kWh 00 48
4 Float kWH 00 4A
4 Float kVArh 00 4C
4 Float kVArh 00 4E
4 Float kVAh 00 50
4 Float Ah 00 52
4 Float W 00 54
30087
30101
30103
30105
30107
30109
30111
30201
30203
(2).
Total system VA demand.
Maximum total system VA demand.
Neutral current demand.
Maximum neutral current demand.
Total system reactive power demand. (2)
Maximum total system reactive power
demand(2)
Line 1 to Line 2 volts.
Line 2 to Line 3 volts.
4 Float W 00 56
4 Float VA 00 64
4 Float VA 00 66
4 Float Amps 00 68 X X
4 Float Amps 00 6A X X
4 Float VAr 00 6C X
4 Float VAr 00 6E X
4 Float V 00 C8 X
4 Float V 00 CA X
30205
Line 3 to Line 1 volts.
4 Float V 00 CC X
- 27
Page 32
-
30207
30225
30235
30237
30239
30241
30243
30245
30249
Average line to line volts.
Neutral current.
Phase 1 L/N volts THD
Phase 2 L/N volts THD
Phase 3 L/N volts THD
Phase 1 Current THD
Phase 2 Current THD
Phase 3 Current THD
Average line to neutral volts THD.
4 Float V 00 CE X
4 Float A 00 E0 X X
4 Float % 00 EA X
4 Float % 00 EC X X
4 Float % 00 EE X X
4 Float % 00 F0
4 Float % 00 F2 X
4 Float % 00 F4 X
4 Float % 00 F8 X
30251
30259
30261
30263
30265
30267
30269
30335
30337
Average line current THD.
Phase 1 current demand.
Phase 2 current demand.
Phase 3 current demand.
Maximum phase 1 current demand.
Maximum phase 2 current demand.
Maximum phase 3 current demand.
Line 1 to line 2 volts THD.
Line 2 to line 3 volts THD.
4 Float % 00 FA
4 Float A 01 02
4 Float A 01 04 X
4 Float A 01 06 X
4 Float A 01 08
4 Float A 01 0A X
4 Float A 01 0C X
4 Float
4 Float
01 4E X
01 50 X
30339
Line 3 to line 1 volts THD.
4 Float
- 28
01 52 X
Page 33
-
30341
30343
30345
30347
30349
30351
30353
30355
30357
Average line to line volts THD.
Total kwh(3)
Total kvarh(3)
L1 import kwh
L2 import kwh
L3 import kWh
L1 export kWh
L2 export kwh
L3 export kWh
4 Float
01 54 X
4 Float kWh 01 56
4 Float kVArh 01 58
4 Float kWh 01 5A
4 Float kWh 01 5C X
4 Float kWh 01 5E X
4 Float kWh 01 60
4 Float kWh 01 62 X
4 Float kWh 01 64 X
30359
30361
30363
30365
30367
30369
30371
30373
30375
L1 total kwh(3)
L2 total kWh(3)
L3 total kwh(3)
L1 import kvarh
L2 import kvarh
L3 import kvarh
L1 export kvarh
L2 export kvarh
L3 export kvarh
4 Float kWh 01 66
4 Float kWh 01 68 X
4 Float kWh 01 6A X
4 Float kVArh 01 6C
4 Float kVArh 01 6E X
4 Float kVArh 01 70 X
4 Float kVArh 01 72
4 Float kVArh 01 74 X
4 Float kVArh 01 76 X
- 29
Page 34
-
Modbus
30377
30379
30381
30385
30387
30389
30391
30393
30395
L1 total kvarh (3)
L2 total kvarh (3)
L3 total kvarh (3)
resettable total active energy
resettable total reactive energy
resettable import active energy
resettable export active energy
resettable import reactive energy
resettable export reactive energy
4 Float kVArh 01 78
4 Float kVArh 01 7A X
4 Float kVArh 01 7C X
4 Float kWh 01 80
4 Float kVArh 01 82
4 Float kWh 01 84
4 Float kWh 01 86
4 Float kVArh 01 88
4 Float kVArh 01 8A
Function code
10 to set holding parameter
03 to read holding parameter
Address
Register
40003 2
Parameter
Number
Parameter
Demand
Period
Protocol
Start Address
Hex
High
Byte
Low
Byte
00 02
Valid range
Write demand period: 0, 5,8, 10,
15, 20, 30 or 60 minutes, default 60.
Setting the period to 0 will cause the
Mode
r/w
- 30
Page 35
-
demand to show the
Network Parity
Current parameter value and demand
max to show the maximum parameter
value since last demand reset.
Length : 4 byte
Data Format : Float
Write system type: 3p4w = 3, 3p3w = 2 &
1p2w= 1
40011 6 System Type 00 0A
40013 7 Pulse1 Width 00 OC
40015 8 Password Lock 00 OE
Requires password, see parameter 13
Length : 4 byte
Data Format : Float
Write pulse1 on period in milliseconds:
60, 100 or 200, default 100.
Length : 4 byte
Data Format : Float
Write any value to password lock
protected registers.
Read password lock status:
0 = locked. 1 = unlocked.
Reading will also reset the password
timeout back to one minute.
r/w
r/w
r
40019 10
Stop
00 12
Length : 4 byte
Data Format : Float
Write the network port parity/stop bits
for MODBUS Protocol, where: 0 = One
stop bit and no parity, default. 1 = One
stop bit and even parity. 2 = One stop bit
- 31
r/w
Page 36
-
40021 11 Network Node 00 14
and odd parity.3 = Two stop bits and no
parity. Requires a restart to become
effective.
Length : 4 byte
Data Format : Float
Write the network port node address:
1 to 247 for MODBUS Protocol, default 1.
Requires a restart to become effective.
Length : 4 byte
Data Format : Float
Write pulse divisor index: n
= 1 to 6
r/w
40023
40025
1--0.01kwh/imp
2--0.1kwh/imp
3--1kwh/imp
12
Pulse 1 Divisor 00
13
Password
16
4-10kwh/imp
5-100kwh/imp
6-1000kwh/imp
Length : 4 byte
Data Format : Float
Write password for access to protected
registers. Default password is 1000.
00
18
Length : 4 byte
Data Format : Float
r/w
r/w
- 32
Page 37
-
Write the baud rate for MODBUS Protocol,
where:
0 = 2400 baud. 1 = 4800 baud.
40029
40063
15
32
Baud Rate
CT ratio
00
00
2 = 9600 baud, default.
1C
3 = 19200 baud. 4 = 38400 baud.
Length : 4 byte
Data Format : Float
CT Ratio range:1~2000
CT Ratio= primary current /secondary current
Length : 4 byte
3E
Data Format : Float
Requires password, see parameter 13
(Non MID)
PT Ratio range:1~2000
r/w
r/w
40065
40087
PT ratio= primary voltage /secondary voltage
Length : 4 byte
33
44
PT ratio
Pulse 1
Energy Type
00
40
Data Format : Float
Requires password, see parameter 13
(Non MID)
Write MODBUS Protocol
00
input parameter for pulse
56
out 1: 37 = total kwh or 39 = total kVarh,
default 39.
- 33
r/w
r/w
Page 38
-
Length : 4 byte
461457
464513
30729 Reset
32257 Serial number
Data Format : Float
00 00 reset the Maximum demand
00 03reset the resettable energy
F0
10
Length : 2 byte
Data Format: Hex
Serial number
FC
Length: 4 byte
00
Data Format: unsigned int32
Note: Only read
wo
ro
- 34
Loading...