COUNTIS E40/E41
GB
E
B
A
D
U1
U2
U3
T1/T2 *
*
COUNTIS E41
+
-
N
L2
L1
L3
N
L2
L1
L3
N
11
1 3 5 7 9
4 6 8 10 12 14 16 2
S1 S2 S1 S2 S1 S2
Web: www.socomec.com
Three phase kWh meter, measure via CT 50 to 6000 A
User instructions
Product presentation
A
LCD display.
B
Key to scroll readings.
C
"Prog" key to set up the CT ratio and the type of network.
D
Reset to reset the partial counter.
E
Metrological LED (1 Wh = 10 impulses).
Meter setup
The following settings have to be made before the meter can be put to use :
- CT ratio.
- Type of network (single or three-phase).
- Type of three-phase installation (balanced or unbalanced).
1. Press the Prog key during 3 sec. to enter the set-
up mode.
2. The CT ratio setting is displayed (100A). Press
the key "Read" repeatedly to scroll the possible CT values (50, 100, 150, 200, 250, 300, 400, 600, 800… 6000A).
3. Press "Prog" to conrm and switch to the next
setting.
4. The type of network (1L+N, 2L, 3L, 3L+N) is
displayed. Press the key "Read" repeatedly to scroll the possible values and select the type of network.
5. Press "Prog" to conrm and switch to the next setting.
6. On three-phase installations, the type of installa­tion is displayed as "Balanced/Unbalanced" (Bl, Unbl). Press the key "Read" to scroll the values and select the type of
installation.
7. Press "Prog" to conrm.
8. Press the Prog key during 3 sec. to exit the programming mode.
Display of readings
The various datas can be scrolled by pressing the Key "Read". The Default display will indicate power consumption according to the current tari.
COUNTIS E40 :
1 1
st
pressure: backlight switches ON.
Total active energy consumption (kWh).
2 2
nd
pressure: partial active energy
consumption (kWh).
3
3rdpressure: total reactive energy consumption (kVAR).
4
4thpressure: partial reactive energy consumption (kVAR).
5 5
th
pressure: instant power consumption
(kW).
COUNTIS E41 :
The COUNTIS E41 provides detailed display of the total/partial active energy consumptions accor­ding to tari (T1 or T2) and in total (T).
To reset the partial meter
- Press the scrolling key several times in order to display partial energy.
- Press the reset button during 3 sec.
The partial meters (active and reactive energy) will be set to zero.
ERROR message :
In case of bad wiring, an "ERROR" message will be displayed.
- Check for each phase that current (I1, I2, I3) and voltage (L1, L2, L3) are
measured on the
right phase.
- Check the correct wiring of the product (L/N).
Note :
The information on the display indicates that the corresponding phase (1, 2,3) is under voltage.
Technical specifications
Metrological characteristics
- Accuracy class B (1%) according to EN50470-3
- Metrological LED : 1 pulse = 0.1Wh current transformer ratio e.g. in a installation with a 100/5A C.T., 1 pulse = 0.1Wh /20 pulses = 2Wh
- Starting current : 10 mA
- Basic current : 5 A
- Max current : 6 A
Technical characteristics
Note: in a unbalanced network, please connect 1 C.T. for each phase. if the installation settings is related to a "balanced network", 1 C.T. on the phase 1 has to be connected
- Consumption: < 0,6 W et 2,8 VA max per phase
- Supply : 230/400 V
+/- 15%
- Frequency : 50/60 Hz +/- 2 Hz
- Savings of measures are made regularly and in
case of power failure in EEPROM
- Characteristic of tari input COUNTIS E41 : tari 1 = 0 V, tari 2 = 230 V
+/- 15%
- Impulse output characteristics :
1 pulse : 100 Wh
Pulse duration : 100 ms
External supply :20 ... 30 V
Mechanical characteristics
- Modular casing 4 M (72 mm)
- Protection degree (casing) : IP20
- Protection degree noze : IP50/IK03
- Insulation class : II
Environment
- Storage temperature : -25 °C to +70 °C
- Working temperature: -10 °C to +55 °C
- Connection capacity :
exible : 1 à 6 mm
2
rigid : 1,5 à 10 mm
2
Operating principle
This kilowatt hour meter measures the active and reactive electrical energy used in an electrical installation. This device has a digital LCD to display energy used and power. This device has a total counter and a partial resettable counter. In case of two tari levels, the COUNTIS E41 will count separetely the energy used in tari 1 and in tari 2.