socomec COUNTIS ATv2, COUNTIS ATiv2 Operating Instructions Manual

Industrial Switching & Protection Systems
COUNTIS ATv2/ATiv2
GB
Operating instructions
2
SOCOMEC - Ref. : 875 645 D
Contents
PRELIMINARY OPERATIONS ___________________ 4 GENERAL INFORMATION ______________________ 4 PRESENTATION _______________________________ 4 INSTALLATION ________________________________ 5 CONFIGURA TECHNICAL CHARACTERISTICS _______________ 8
TION ______________________________ 7
ENG LI S H
SOCOMEC - Ref. : 875 645 D
3
PRELIMINARY OPERATIONS
1
2
4
3
For personnel and product safety please read the contents of these operating instructions car Check the following points as soon as you receive the package:
• the packing is in good condition,
GENERAL INFORMATIONS
The COUNTIS System comprises energy metering products for balanced or non-balanced 3- or 4-wire network. This system comprises two products:
Tv2
A
ATiv2: a three-phase insulated single
: a non-insulated thr
active energy-meter, which does not allow earthing CT of secondary.
or double rate active energy meter allowing the CT secondary to be earthed.
efully.
ee-phase
• the product has not been damaged during transit, the product reference number con-
• forms to your order,
• the package contains the product as well as the operating instructions.
These products are completely confi­gurable (CT radio, network type and pulse output value) and have a 7-digit display which allows direct display of consumption in kWh. They ar
e equip-
ped with a pulse output as standard.
PRESENTATION
COUNTIS ATv2 / ATiv2 SINGLE RATE
COUNT 105 A
a kWh display
b Total and partial meter display
, or scr
olling parameter settings
c Flashing LED consumption indicator (10 Wh/pulse)
d Validation/scrolling of parameter settings
4
SOCOMEC - Ref. : 875 645 D
PRESENTATION (continued)
1
2
5
4
3
COUNTIS
COUNT 119 B
ATiv2 DOUBLE RATE
a kWh display
b Total and partial meter display, or scrolling parameter settings
c Displays t1 and t2 rate meters
d Flashing LED consumption indicator (10 Wh/pulse)
ENG LI S H
INSTALLATION
Note:
The COUNTIS can be installed on a DIN EN 50022 rail (DIN 43880).
Recommendation:
• Avoid close proximity with systems generating electromagnetic distur bances
• Avoid vibrations including accelera­tions of mor cies lower than 60 Hz.
Note:
The minimum torque for the fixed terminal is 0.8 Nm.
Recommendation:
We recommend that the auxiliary voltage and the voltage inputs should be protected with 0.5 A fuses or BS 88 2A gG.
e than 1 G for frequen-
e Validation/scrolling of parameter settings
CLIMATIC ENVIRONMENT
o guarantee optimum operation, it is
T
ecommended that this device is used
r between - 5 to + 45 °C with a relative humidity of between 20 and 85
-
%.
CONNECTION
The Countis A
Tv2 and A
connection terminals of 1 to 6 mm
Tiv2 consist of
2
for
currents and voltages.
I, F)
SAFETY INSTRUCTIONS (U
,
To avoid damaging the device, take care to observe the following before connecting the device:
• indications on the casing,
• network fr
• maximum permanent voltage at voltage input terminals of 400 V AC
20
±
equency: 50 or 60
%
phase/phase,
Hz,
• maximum permanent current of 7 A (connection fr mer(s)).
om curr
ent transfor
-
SOCOMEC - Ref. : 875 645 D
5
L
1
L
2
L
3
P
1
S
1
P
1
S
1
P
1
S
1
2 4 6 8
1 3 5 7 9
11
ATiv2
1
L
1
L
2
L
3
P
1
S
1
P
1
S
1
2 4 6 8
1 3 5 7 9
11
ATiv2
1
L
1
L
2
L
3
P
1
S
1
A
Tiv2
2 4 6 8
1
1
3 5 7 9
11
L
1
L
2
L
3
P
1
S
1
P
1
S
1
2 4 6 8
1 3 5 7 9
11
ATiv2
1
L
1
L
2
L
3
N
P
1
S
1
P
1
S
1
P
1
S
1
2 4 6 8
1 3 5 7 9
11
ATiv2
1
L
1
L
2
L
3
N
P
1
S
1
2 4 6 8
1 3 5 7 9
11
A
Tiv2
1
L
1
L
2
P
1
S
1
2 4 6 8
1 3 5 7 9
11
ATiv2
1
L
1
N
P
1
S
1
2 4 6 8
1 3 5 7 9
11
ATiv2
1
INSTALLATION (continued)
External counter
1 3 5 7 9
11
External power supply
4 6
2
8 10 12 14
t1 = 0 VAC
4 6
2
8
10
1 3 5 7 9
11
t2 = 230 VAC
NETWORK
Note:
If the current is badly connected or there is poor current/voltage corres­pondence (negative energy) the coun­ter will be stopped and the arrows t flash.
CT earthing, for the ATiv2 only
3 WIRE WITH 1 CT (3 BL) 4 WIRE WITH 1 CT (4 BL)
COUNT 106 C
3 WIRE WITH 2 CT (3 NBL) 3 WIRE WITH 2 CT (3 NBL)
COUNT 108 C
COUNT 107 C
COUNT 109 C
Key to diagrams:
1 Fuses 0.5 gG or BS 88 2A gG
3 WIRE WITH 3 CT (3 NBL) 4 WIRE WITH 3 CT (4 NBL)
COUNT 110 C
COUNT 111 C
TWO-PHASE (2 BL) SINGLE-PHASE (1 BL)
COUNT 112 C
RATE INPUT (t1 / t2)
COUNT 118 C
CONNECTING PULSE OUTPUT
The neutral has to be connected for the dual tarif ATiv2.
6
COUNT 147A
COUNT 35B GB
SOCOMEC - Ref. : 875 645 D
CONFIGURATION
:
Note
The device will automatically leave the configuration menu if no buttons are pressed for a period of 25 seconds.
Note:
Press the t button for a prolonged period to scroll rapidly through the configuration scr short period to scroll through each screen one-by-one.
eens. Press for a
KEY INSTRUCTION
+
For 3 seconds to access access-code entry (CdE).
To enter code 21.
o validate the code and access to
T the network programming (nET).
:
Note
A long press on the button t causes rapid scrolling and a single short press causes scrolling in steps of 5.
Note:
The values available depend on the Ct ratio.
To select the network type, 1bL (single phase), 2bL (two-phase), 3-4 nbL (unbalanced three-phase) and 3-4 bL (balanced three-phase).
To validate the network programming and go on to the current transformer (CT) primary value.
o programme the primary value up
T to 6000 A.
To validate the unit programming and go on to the pulse output (PuLSES).
To go on to the weight of this output (VAL).
To select the weight “0.1” for
kWh, “1” for 1 kWh, “10” for
0.1 kWh, “100” for 100
10
kWh.
ENG LI S H
SOCOMEC - Ref. : 875 645 D
To validate the programming of this weight and go on to the pulse duration (dur).
To select the duration from 60 to 900 ms.
To accept value and pass to partial meter zero reset (rSET).
o select ‘rSEt nO’ (no reset to zero)
T and ‘rSEt YES’ (reset to zero).
To confirm reset to zero and return to network type pr
+
To confirm and quit programming.
ogramming.
7
TECHNICAL CHARACTERISTICS
ENCLOSURE
Connection via 1 to 6 mm2terminal shrouds Weight 300 g Size Protection class (front) IP40
FRONT PANEL
Green LCD/7 digits Digit height 8 x 4 mm
INPUTS
modular: 4 modules of 17.5 mm
Note:
The current inputs are insulated on the ATiv2.
Note:
The Countis ATv2 and ATiv2 are auto­powered from the V1 et V2 voltage inputs.
CURRENT
Via transformer with
• configurable primary 5 to 6000 A
• secondary 5 A Input consumption 10 mA to 7 A (secondary) Consumption ≤ 1 VA
TENSION
Measurement range (Line/Line) 230 V AC - 15% to 400 V AC + 20 % Consumption ≤ 0,5 VA
AUXILIARY POWER SUPPLY
Type auto-powered
DC
/
10
1 VA
mA
Consumption
ACCURACY
Accuracy index IEC 61036 class 1
PULSE OUTPUT
Reed relay (100 V DC - 0.5 A - 12 VA) Pulse duration Maximum tripping number
5 x 10
7
at 10 V
60 to 900 ms
TING CONDITIONS
OPERA
Operating temperature - 5 °C up to 45 °C Storage temperature - 20 °C up to 70 °C
%
Relative humidity
STANDARDS
CE marking
Operating conditions
8
IEC 61000-4
SOCOMEC - Ref. : 875 645 D
/2-3-4-5-6-8-11
EN 50081-1 EN 50082-2
IEC 60068-2-6 IEC 60068-2-11 IEC 60068-2-30
85
ENG LI S H
SOCOMEC - Ref. : 875 645 D
9
SOCOMEC - Ref.: 875 645 D - 10/03
Industrial Switching & Protection Systems
www.socomec.com
COUNT 113 C
HEAD OFFICE
SOCOMEC GROUP Switchgear and UPS
S.A. capital de 11 052 200 R.C. Strasbourg 5484500 149 B
SOCOMEC
1, rue de Westhouse - B.P. 10 F-67235 Benfeld Cedex - FRANCE Tel. +33 (0)3 88 57 41 41 - Fax +33 (0)3 88 57 78 78
SALES MANAGEMENT DIVISION
SOCOMEC
95, rue Pierre Grange F-94132 Fontenay-sous-Bois Cedex-FRANCE Tel. +33 (0)1 45 14 63 40 - Fax +33 (0)1 48 77 31 12 scp.dcm@socomec.com
This document is not contractual. SOCOMEC reserves the right to modify featur
es without prior notice in view of continued impr
ovements.