socomec ATyS 100A, ATyS 200A, ATyS 260A, ATyS 400A Quick Start Manual

STEP 3B
90°
90°
I II
0
AUT
CONTROL / COMMAND Terminals - Ensure that the product is in Manual Mode.
QUICK START
Installation and Commissioning
STEP 6A
Control by an external
order (AUTO)
STEP 4
STEP 5
STEP 6A
Ensure that the emergency handle is not inserted in the product and turn the mode selector to the AUT position. LED “Power” Green: ON LED Manuel/Default: OFF
___________________________________________________________
order I
order 0
order II
position I
position 0
position II
To enable control, close contact 312 with 317. To force the product to 0 position/OFF bridge
the contact 313 with 317. For contactor logic bridge contact 316 with 317. To operate: close the contact corresponding to
the desired position.
Spares: Motorisation module
Ref. Spare part motorisation
Power Supply Terminal - Remove the Top cover to access and connect the terminal - Replace the cover before putting in service.
1
2
Check
Whilst in manual mode, check the wiring and if ok power up the product.
LED “Power” Green: ON
LED Manuel/Defaut Red (Productnot
Available): ON
NOTE: Nominal Aux. Supply Voltage : 208 – 277Vac
Motorised Operation
Contactor logicImpulse logic
Imp. ≥60ms maintened
97095010 100A 2, 3, 4 P
97095020 200A 2, 3, 4 P 97232020 / 97233020 / 97234020
97095026 260A 2, 3, 4 P
97095040 400A 2, 3, 4 P 97232040 / 97233040 / 97234040
1
1
2
Class CC 4A fuse
ATyS
Transfer Switch UL 1008: Optional Standby Power
100A, 200A, 260A, 400A
Preliminary operations
2
301 3022
312313 314315 316317 63A64A 24 14 04 13
Connect the product with a cable of section of 24 to 16 AWG. Screw M3 - Tightening torque: min.: 5 lb-in - max. 7 lb-in.
3
STEP 6B
Emergency Manual Operation
STEP 6C
Padlocking Mode (in position O)
Check the following upon delivery and after removal of the packaging:
n Packaging and contents are in good condition. n The product reference corresponds to the order. n Contents should include:
Qty 1 x ATyS Qty 1 x Emergency handle and fixing clip Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment. This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further details refer to the product instruction manual available on the SOCOMEC website.
n This product must always be installed and commissioned
by qualified and approved personnel.
n Maintenance and servicing operations should be
performed by trained and authorised personnel.
n Do not handle any control or power cables connected to
the product when voltage may be, or may become present on the product, directly through the mains or indirectly through external circuits.
n Always use an appropriate voltage detection device to
confirm the absence of voltage.
n Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to follow these safety instructions may expose the user and others to serious injury or death.
Risk of damaging the device
n In case the product is dropped or damaged in any way it
is recommended to replace the complete product.
Accessories
n Bridging bars and connection kits. n Terminal screens. n Auxiliary contacts (Additional). n Terminal lugs.
STEP 1
Cabinet / Back Plate
Installation
STEP 2
Connecting the POWER section
storage of
emergency
STEP 3
COMMAND /
CONTROL terminal
connections
Clip for
the
handle
terminal connections
STEP 4
Power SUPPLY
STEP 5
CHECK
STEP 3
STEP 6B
Emergency Manual
Operation
STEP 6C
Padlocking
STEP 4
Spares
n Motorisation module
For further details for spares and accessories, please refer to the instruction manual in chapter ­"Spare parts and accessories"
AUT
USED FOR ATyS REFERENCE
B4
B5
97232010 / 97233010 / 97234010
97232026 / 97233026 / 97234026
AUT
3x
0.15-0.31 in
Ø
Ø 4-8 mm
www.socomec.com
To download, brochures, catalogues and technical manuals:
www.socomec.com/ operating-instructions
Printing informations: 1 color Black. White paper 90g/m2. Printing size: 420x297. Final size 210x297. This page visible first.
UL 1008
542563D
Non contractual document. Subject to change without notice.
STEP 1A
Attention: Ensure that the product is installed on a flat rigid surface.
Recommended
orientation
Ref ATyS UL 97232010 97233010 97234010 97232020 97233020 97234020 97232026 97233026 97234026 97232040 97233040 97234040
Dim. code
Installation
0.29in
7,5mm
Ok
FRAME B4 FRAME B5
100 A 200 A 260 A 400 A
2P 3P 4P 2P 3P 4P 2P 3P 4P 2P 3P 4P
1 1 2 1 1 2 3 3 4 3 3 4
Ø 0.35in Ø 9mm
Ø 0.27in Ø 7mm
STEP 1B
C
Y1
Y
H
J J1
L
K1
N
M
O
STEP 2B
Power Terminal Connections (optional accessories)
To be connected using terminal lugs, rigid or flexable busbars.
FRAME B4 FRAME B5
100 A 200 A 260 A 400 A
2P 3P 4P 2P 3P 4P 2P 3P 4P 2P 3P 4P
Ref ATyS 97232010 97233010 97234010 97232020 97233020 97234020 97232026 97233026 97234026 97232040 97233040 97234040
Ref lugs 39542020 39543020 39544020 39542020 39543020 39544020 39542040 39543040 39544040 39542040 39543040 39544040
B
K
Qty per reference
Ref qty to order x3 x3 x3 x3 x3 x3 x3 x3 x3 x3 x3 x3
2 3 4 2 3 4 2 3 4 2 3 4
Dimensions in/mm
Ref.
code
1
2
3
4
A B C D H H1 H2 J J1 K K1 L M N O T Y Y1
in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm
2/3P
12.91 328
4P
14.88 378 8.26 210
2/3P
14.84 377
4P
17.20 437 10.63 270
Dimensions in/mm
Ref.
code
1
2/3P
2
4P 8.26 210
3
2/3P
4
4P 10.63 270
0.83in 21mm
H1
6.30 160 9.60 244 0.41 10,5 5.08 129 6.8 173 4.21 107
10.23 260 12.62 320,5 0.41 10,5 8 200 9.7 247 6.53 166
C
D
H2
H
6.30 160
8.26 210
T
1.37 35 7.67 195 3.84 97,5 1.18 30 0.53 13,3 0.98 25 0.43 11 2 50 1.51 38,5 5.21 132,5
1.37 35 7.67 195 3.84 97,5 1.96 50 0.49 20 1.38 45 0.51 13 2.6 65 2.04 52 7.48 190
J J1
KB
A B C J J1 K K1 K2
in mm in mm in mm in mm in mm in mm in mm in mm
24 610 24 610 12 305
32 813 32 813 16 406
6.30 160
8.26 210
1.37 35 7.67 195 2.67 68 12 305
1.37 35 7.67 195 3.84 97,5 15 381
Désignation
CMC LA300-R CMC LA630-R
Size (AWG) min. Size (AWG) max. Opening per lug
A
Size of screw
Torque lb.in / mm
# 6
300 Kcmil
1
13 17
160 / 18
# 4 1/0
600 Kcmil - 250 Kcmil
1 2
310 / 35
When ordering ensure to order QTY 3 for each lug reference (Quantity 2 for incoming power cables and quantity 1 for outgoing cables)
A
Door cut-out for front panel.
5.43in
138mm
0.78in 20mm
K1
max < 79in
< 2m
K2
1.98in
3.97in 101mm
50,5mm
STEP 2C
22 lb-in 2,5 Nm Flat 5
Ref. TOP or BOTTOM
Mounting of terminal covers (optional accessory)
USED FOR
41583041
41584041 97234026 / 97234040
97232026 / 97232040 97233026 / 97233040
13.3 lb-in 1,5 Nm pozidriv n°1
Ref.
41583021
USED FOR
97232010 / 97232020 97233010 / 97233020
41584021 97234010 / 97234020
STEP 2A
Bridging bars (optional accessory)
230 lb-in 26 Nm
O
-
OFF
BRIDGING
BAR KIT
USED FOR ATYS REF.
41592021 97232010 / 97232020
41593021 97233010 / 97233020
41594021 97234010 / 97234020
41592041 97232026 / 97232040
41593041 97233026 / 97233040
41594041 97234026 / 97234040
Size 17mm
230 lb-in 26 Nm
STEP 3A
*
Pos II
Mounting of additional auxiliary contacts (optional accessories)
22441
Pos II
2
3
(fast-on)
1
2
Pos I
*
4.4 lb-in 0,5 Nm Pozidriv n°1
Pos I
Pos II
Pos I
1
41590021
125 - 250 V a.c. 60 Hz General Use 10A 1/2 HP I min. 100 mA
41590022
125 V a.c. 60 Hz General Use 1A
*
OR
Loading...