Smith GS110W User Manual

GS110IOM-2
GS110W NATURAL OR PROPANE GAS BOILERS INSTALLATION & OPERATION MANUAL
MEA#117-96-E
DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE OF 50 PSI WATER.
TO INSTALLER NOTE: READ THESE INSTRUCTIONS CAREFULLY. THEY WILL SAVE YOU TIME IN ASSEMBLING BOILER PROPERLY.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch. Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE HEATER.
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.
NOTE: Installation and service must be performed by a qualified installer, service agency or the gas supplier.
260 NORTH ELM STREET WESTFIELD, MA 01085 TEL. (413) 562-9631 FAX: (413) 562-3799
GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONSPage 2
AVERTISSMENT. Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommoge matériel, toute blessure ou la mort
Ne pas entreposer ni utiliser d’essence ou ni d’autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gas depuis un voisin. Suivez les intructions du fournisseur.
• Si vous ne purvez rejoindre le fournisseur, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
CONTENTS
Before You Start .................................................page 2
Boiler Ratings & Capacities................................ page 3
Boiler Location ................................................... page 3
Clearances to Combustible Construction ...........page 3
Combustion Air & Ventilation ..............................page 4
Chimney & Vent Pipe Connections .................. page 10
Heating System Piping .....................................page 15
Gas Supply Piping............................................ page 18
Electrical Wiring ............................................... page 18
Lighting Instructions .........................................page 22
Boiler Set Up ....................................................page 24
Boiler Operation ...............................................page 24
Checking & Adjusting .......................................page 25
Boiler Maintenance .......................................... page 26
Replacement Parts........................................... page 28
Instructions to the Installer ...............................page 31
Health Warnings ...............................................page 31
BEFORE YOU START
WARNING: This manual must be read and fully understood before installing, operation or servicing this boiler! Failure to follow these instructions could result in a fire or explosion causing extensive property damage, personal injury or death!
Each unit has been constructed and hydrostatically tested for a maximum working pressure of 30 psi in accordance with the ASME Boiler and Pressure Vessel Code, Section IV for cast iron boilers. Each boiler has been equipped with a 30 psi pressure relief valve.
This manual covers the application, installation, operation and maintenance of a GS110 low pressure hot water boiler.
To obtain the safe, dependable, efficient operation and long life for which this boiler was designed, these instructions must be read, understood and followed.
Direct all questions to your Smith Cast Iron Boiler distributor or to the Customer Service Department, 260 North Elm Street, Westfield, MA 01085. Always include the model and serial numbers from the rating plate of the boiler in question.
The owner should maintain a record of all service work performed with the date and a description of the work done. Include the name of the service organization for future reference.
Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
These instructions cover the GS110 gas fired, direct vent, low pressure, sectional, cast iron hot water boiler. GS110 boilers have been design certified by CSA for use with natural and propane gas under the latest edition of ANSI-Z21.13/CSA 4.9, Gas-Fired Low Pressure Steam and Hot Water Boilers.
If installed in the Commonwealth of Massachusetts, you MUST FOLLOW the additional instructions contained in Hydrotherm’s instruction sheet MA IOM. If you don’t have a copy, call your Hydrotherm distributor or Hydrotherm.
GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS Page 3
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest revision. In Canada, the installation must be in accordance with the requirements of CSA B149.1 or B149.2 Installation Code for Gas Burning Appliances and Equipment.
BOILER RATINGS & CAPACITIES
Before undertaking the installation of the GS110 check the boiler rating plate to ensure that the boiler is the proper size for the job. The "Net I=B=R Ratings" specify the equivalent amount of direct cast iron radiation that the boiler can handle under normal conditions.
Also ensure that the boiler has been set up for the type of gas available at the installation site. Other important considerations are the availability of an adequate electrical supply, fresh air for combustion and proximity a suitable outside wall.
BOILER LOCATION
WARNING: The clearances to combustible construction show in Figure 1 must be main­tained. Failure to comply with this warning can result in extensive property damage, severe personal injury or death!
2. An optimum site will be level, central to the hot water piping system, close to an outside wall and have adequate fresh air for combustion.
3. Ensure that the floor is structurally sound and will support the weight of the boiler.
NOTE: This boiler is designed for direct placement on a combustible floor. Never install this boiler on carpeting!
4. DO NOT install this boiler in a location that would subject any of the gas ignition components to direct contact with water or excessive moisture during operation or servicing.
5. NEVER store objects on or around the boiler.
WARNING: Never store combustible materials, gasoline or any product containing flammable vapors or liquids in the vicinity of the boiler. Failure to comply with this warning can result in extensive property damage, severe personal injury or death!
Figure 2 - Moving Boiler
CAUTION: Do not lift the boiler by the jacket. Use a hand truck under the base frame as shown in Figure 2.
1. Locate the boiler in an area that provides good access to the unit. Keep in mind that servicing may require the removal of jacket panels. Accessibility clearances must take precedence over fire protection clearances.
Figure 1 - Clearances to Combustible Construction
GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONSPage 4
COMBUSTION AIR & VENTILATION
WARNING: This boiler must be supplied with combustion air in accordance with Section 5.3, Air for Combustion & Ventilation, of the latest revision of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and all applicable local building codes. Canadian installations must comply with CSA B149.1 or .2 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes. Failure to provide adequate combustion air for this boiler/water heater can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
To operate properly and safely this boiler requires a continuous supply of air for combustion. NEVER store objects on or around the boiler!
CAUTION: Combustion air contaminated with fluorocarbons or other halogenated compounds such as cleaning solvents and refrigerants will result in the formation of acids in the combustion chamber. These acids will cause premature failure of the boiler voiding the warranty!
CAUTION: If the boiler is operated while the building is under construction it MUST be protected from wood, concrete, sheet rock and other types of dust. Failure to properly protect the unit from construction dust will damage the unit voiding the warranty!
Buildings may require the installation of a fresh air duct or other means of providing make-up air if the intake air option isn't used. Any building utilizing other gas burning appliances, a fireplace, wood stove or any type of exhaust fan must be checked for adequate combustion air when all of these devices are in operation at one time. Sizing of an outside air duct must be done to meet the requirements of all such devices.
WARNING: Never operate this boiler in an environment subjected to a negative pressure unless the air intake is connected to the outdoors. Failure to comply with this warning can result in excessive levels of carbon monoxide causing severe personal injury or death!
All Combustion Air From Inside The Building
Older houses often have enough “leakage” to provide an adequate amount of combustion air provided that the demand for combustion air is not too great, Figure 3. Homes that are relatively new or “tight” will most likely require that the combustion be ducted to the boiler from outside the building. Any home utilizing other gas burning appliances, a fireplace, wood stove or any type of exhaust fan must be checked for adequate combustion air when all of these devices are in operation at one time.
If the boiler is to be located in an alcove, closet or other confined space the distances from the boiler and it's vent system to all-combustible construction must be equal to or greater than the minimum clearances in Figure 1. When installed in a closet or confined space two permanent openings of equal area adjoining another room or rooms having sufficient volume to meet the requirements of an unconfined space must be provided, Figures 4 & 5. Each opening must have a minimum free area of one square inch per 1000 Btu/hr (2200 mm kW) based on the total input rating of all gas utilization equipment in the confined area. Each opening must be no less than 100 square inches (64516 mm2) in size. The upper opening must be within 12 inches (305 mm) of, but not less than 3 inches (76 mm) from, the top of the enclosure. The bottom opening must be within 12 inches (305 mm) of, but not less than 3 inches (76 mm) from, the bottom of the enclosure.
All Combustion Air From Outside The Building
When installed in a confined space without the intake air option two permanent openings communicating directly with, or by ducts to, the outdoors or spaces that freely communicate with the outdoors must be present. The upper opening must be within 12 inches (305 mm) of, but not less than 3 inches (76 mm) from, the top of the enclosure. The bottom opening must be within 12 inches (305 mm) of, but not less than 3 inches (76 mm) from, the bottom of the enclosure.
Where directly communicating with the outdoors or communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in2/ 4000 Btu/hr (550 mm2/kW) of the total input rating of all of the equipment in the enclosure.
Where communicating with the outdoors through hori­zontal ducts, each opening shall have a minimum free area of 1 in2/2000 Btu/hr (1100 mm2/kW) of the total input rating of all of the equipment in the enclosure.
2
/
When ducts are used, they must have the same cross­sectional area as the free area of the opening to which they connect. Sizing of an outside air duct must be based on the total input rating of all gas utilization equipment in the confined space.
GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS Page 5
When calculating the free area necessary to meet the make-up air requirements of the enclosure, consideration must be given to the blockage effects of louvers, grills and screens.
Screens must have a minimum mesh size of 1/4" (6.4mm). If the free area through a louver or grill is not known ducts should be sized per Table 1.
Table 1 - Combustion Air Duct Sizing
FreshAir
Duct Size
3” x 12” 8” x 8” 8” x 12” 8-1/2” x 16”
Input Btuh
1/4” Wire
Screen Mesh
144,000 256,000 384,000 512,000
Input Btuh
Figure 3 - Horizontal Positive Pressure Venting Using Inside Combustion Air (Cat. III)
Metal
Louvers
108,000 192,000 288,000 384,000
Input Btuh
Wooden Louvers
36,000 64,000 96,000 128,000
Figure 4 - Vertical Negative Pressure Masonry Chimney System Using Inside Combustion Air (Cat. I)
GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONSPage 6
Figure 5 - Vertical Negative Pressure Metal Chimney System and Inside Combustion Air (Cat. I)
Intake Air Option - General Guidelines
This configuration provides combustion air directly to the boiler using a dedicated pipe. Combustion air can be drawn in horizontally through an outside wall or vertically through the roof, see Figures 6, 7, 8, 9 & 10.
WARNING: Each boiler must have it's own intake air system. Common intake air systems are not to be used! Improper installation can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
Single wall galvanized smoke pipe, single wall aluminum pipe, flexible aluminum pipe, PVC or CPVC pipe can be used for the intake air pipe. Maximum intake lengths must not be exceeded per Table 2, larger diameters may be used on 3,4,and 5 section boilers.
Table 2 - Combustion Air System Sizing
Boiler Model
Number
GS110-3 GS110-4 GS110-5 GS110-6 GS110-7
Equivalent Intake Length (see note)
3” Diameter
45 feet (13.7 m) 45 feet (13.7 m) 45 feet (13.7 m)
n/a n/a
Equivalent Intake Length (see note)
4” Diameter
65 feet (19.8 m) 65 feet (19.8 m)
65 feet (19.8 m) * 40 feet (12.2 m) * 40 feet (12.2 m)
* 4" to 3" reducer required. Note: Subtract 5 feet (1.5 m) for each 90° elbow.
GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS Page 7
All joints in metal intake air systems must be secured using corrosion resistant fasteners and sealed using a suitable Silicone caulk. If PVC or CPVC is used, the joints must be cleaned with a suitable solvent and connected using a solvent based PVC cement. The intake air system MUST be supported by the building structure not the boiler/water heater.
Intake Air Option - Vertical Guidelines
A listed, nonrestrictive intake air cap must be used. The intake air cap must terminate as shown in Figure 6. The penetration point in the roof must be properly flashed and sealed.
Figure 6 - Vertical Positive Pressure Venting with Outdoor Combustion Air (Cat. III)
Intake Air Optional - Horizontal Guidelines
The maximum equivalent length for the horizontal intake air pipe is listed in Table 2. The intake air system must be pitched down, toward the terminal, 1/4" per foot (21 mm per meter).
If horizontal runs exceed 5 feet (1.5 m) they must be supported at 3 foot (0.98 m) intervals with overhead hangers. Figures 7 through 10 show the four horizontal air intake options. The intake terminations certified for use the GS110 are listed in Table 5.
GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONSPage 8
Figure 7 - Horizontal Positive Pressure Venting with Outdoor Combustion Air
Figure 8 - Horizontal Positive Pressure Venting with Outdoor Combustion Air
Smith
GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS Page 9
Figure 9 - Vertical Negative Pressure Masonry Chimney System using Outside Combustion Air (Cat. I)
Figure 10 - Vertical Positive Pressure Venting using Outside Combustion Air (Cat. III)
GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONSPage 10
GENERAL VENTING GUIDELINES
WARNING: The vent installation must be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1/ NFPA 54-latest revision or applicable provisions of the local building codes. Canadian installations must comply with CSA B149.1 or .2 Installation Code. Improper venting can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
WARNING: Thimbles and fire-stops must be used where required. A minimum clearance of 6" must be maintained between single wall metal vents and combustible construction or a fire resulting in severe personal injury or death may occur!
WARNING : Each boiler/water heater must have it's own vent system. Common positive pressure vent systems are not to be used! Improper installation can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
All vent systems must be fully supported by the building structure and not by the boiler/water heater.
VENT SYSTEM OPTIONS
The GS110 may be vented the following ways:
Certified vent systems are manufactured by the following companies:
Heat-fab, Inc. 130 Industrial Blvd., Turners Falls, MA 01376 (800) 772-0739.
Z-Flex U.S., Inc. 20 Commerce Park North, Bedford, NH 03110-6911 (800) 654-5600.
Protech Systems Inc. 26 Gansevoort Street, Albany, NY 12202 (518) 463-7284
GENERAL DIRECT VENT INFO
In this configuration the boiler blower is used to push the flue products to the outdoors while drawing combustion air from the outdoors. The instructions under the COMBUSTION AIR & VENTILATION SECTION must be followed! The vent system must be sized per Table 3.
Table 3 - Positive Pressure Vent System Sizing
Boiler Model
Number
GS110-3 GS110-4 GS110-5 GS110-6 GS110-7
Equivalent Vent
Length (see note)
3” Diameter
45 feet (13.7 m) 45 feet (13.7 m) 45 feet (13.7 m)
n/a n/a
* 4" to 3" reducer required Note: Subtract 5 feet (1.5 m) for each 90° elbow.
Equivalent Vent
Length (see note)
4” Diameter
*65 feet (19.8 m) *65 feet (19.8 m) *65 feet (19.8 m)
40 feet (12.2 m)
40 feet (12.2 m)
1) Direct Vent (Positive Pressure), uses a vent system certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. Combustion air is piped from the outdoors to the blower inlet.
2) Horizontal Vent (Positive Pressure), uses a vent system certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. Combustion air is obtained from the space in which the unit is installed.
3) Vertical Vent (Positive Pressure), uses a vent system certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. Combustion air is piped from the outdoors to the blower inlet or is obtained from the space in which the unit is installed.
4) Vertical/Chimney Vent (Negative Pressure), uses an approved metal chimney system or masonry chimney. Combustion air is obtained from the space in which the unit is installed or is piped from the outdoors to the blower inlet.
HORIZONTAL DIRECT VENT SYSTEMS
See figures 7 & 8. The vent materials used in horizontal positive pressure vent systems must be certified to UL 1738 for installations in the United States, ULS636 for installations in Canada.
Each 90° elbow is equal to 5 linear feet (1.5 m) of pipe. To maximize the performance of single wall sheet metal vent systems locate 90° elbows as far from the boiler as possible and from one another. For best results, horizontal vent systems should be as short and straight as possible. The vent system must be both gas tight and watertight. All seams and joints in metal pipes must be joined and sealed in accordance with the vent system manufacturer’s instructions.
When horizontal vent runs exceed 5 feet (1.5m) they must be supported at 3 foot (0.98 m) intervals with overhead hangers. The vent system must be pitched down, toward the vent terminal, 1/4" per foot (21mm per meter). If any part of a single wall metal vent system passes through an unheated space it must be insulated with insulation rated for 400°F. Structural penetrations must be made using approved thimbles.
Loading...
+ 22 hidden pages