Smeg GW6010M6, GW6010M36 INSTALLATION MANUAL

19 561 0121 02 – EN
11 / 01 / 16
Specified cold water limits and added notes for the optional drain pump
19 561 0121 01 – EN
09 / 12 / 15
Update: hydraulic and electric connection from the upper side, Except the models provided with heating tanks
(«boiler»). Improved prescription regarding supply water.
REV. DOC.
DATE
NOTES
INSTALLATION REQUIREMENTS
WD6010 – GW6010
SMEG S.p.A. thank you for choosing this product.
room preparations (as needed) pre-installation of properly operating systems, in compliance with the requirements and
regulations in force
positioning of the machine
Refer to this manual for detailed instructions on the steps mentioned above.
SMEG S.p.A. declines responsibility for damage to persons or property resulting from improperly regulated or defective systems or for any installation of the appliance and/or accessories performed by unauthorized personnel. Any operation performed on the appliance by unauthorized personnel will invalidate the warranty.
1
WD6010-GW6010 INSTALLATION REQUIREMENTS
CAUTION It is essential that the electrical system to which the machine is connected complies with current regulations.
All electrical testing operations and equipment installation should be made by qualified and trained personnel. The designated personnel is responsible for ensuring the safety and efficiency of earth connection.
Components must always be replaced with genuine spare parts.
CIRCUIT-BREAKER
A CIRCUIT-BREAKER must be installed for each appliance.
Circuit-breaker characteristics:
a. Omnipolar: must break all live conductors; b. Easily accessible to the user; c. Easily operated (no additional tools required); d. Located in close proximity to the appliance; e. Clearly marked as the appliance circuit-breaker
The same specifications apply to the main switch on the machine: it must be easily accessible. Do not place objects in a way that limits accessibility.
A PROTECTIVE DEVICE specifically for the appliance (e.g. magneto thermal breaker or fuse on every phase, with appropriate dimensions based on the electrical characteristics indicated) should be installed in the room’s electrical panel.
ELECTRICAL SYSTEM REQUIREMENTS
Refer to the Technical Data sheet to recognize the device’s electrical characteristics and connection requirements.
The device is supplied with a cable with insulated wire terminals; it is not supplied with a plug. The electrical connection of
the device must be carried out with a permanent connection.
2
WD6010-GW6010 INSTALLATION REQUIREMENTS
Technical data
Water connections
Microbial contamination limits - Minimum microbiological
quality required:
“drinking water type” (ref. limits
provided by European Directive 98/83/CE)
"CW" COLD WATER
Connection:
3/4" maschio-male - DN20
Min -Max flow rate:
4 - 12 l/min (0,88-2,64 gal/min)
Min - flow pressure:
100 kPa (1,0 bar)
Max. pressure:
600 kPa (6,0 bar)
Min-Max. temperature:
8°C - 35 °C (46-90°F)
Max. hardness:
10 °f
Ferro Max - Fe2+ / Fe3+ [max]
0,5 ppm
pH:
7÷8
"HW" WARM WATER
Connection:
3/4" maschio-male - DN20
Min/Max flow rate:
4 - 12 l/min (0,88-2,64 gal/min)
Min. flow pressure:
100 kPa (1,0 bar)
Max. pressure:
600 kPa (6,0 bar)
Max. temperature:
60°C (140°F)
Max. hardness:
10 °f
Fe2+ / Fe3+ [max]
0,5 ppm
pH:
7÷8
"DW" DEMI WATER
Connection:
3/4" maschio-male - DN20
Min/Max flow rate:
4 - 12 l/min(0,88-2,64 gal/min)
Min. flow pressure:
100 kPa (1,0 bar)
Max. pressure:
600 kPa (6,0 bar)
Max. temperature:
60°C (140°F)
Max. hardness:
0 °f (0 ppm CaCO3)
Max. conductivity / pH:
30 µS/cm / 5÷8 pH
TDS max
40 mg/l
Note: if local-regional requirements are more stringent than those prescribed above, the local requirements shall be followed. It remains the user's responsibility to provide water supply that comply with the requirements.
3
WD6010-GW6010 INSTALLATION REQUIREMENTS
Electrical connections
"EC" Electrical connections
Type:
Standard
Standard Voltage:
400V 3N~ / PE / 50Hz / 24A
Electrical protection required:
3P+N, 32 A Cable and min. section:
5 x 6 mm2
Configurable Voltage:
230V 3~ / PE / 50Hz / 36A
Electrical protection required:
3P, 40 A Cable and min. section:
4 x 6 mm2
Potenza - Power:
13 kW
Drain and exhaust
"EX" EXHAUST DUCT
Connection:
ø 50 mm ( 2 in)
Peak flow rate:
approx.220-250 m3/h
Max. temperature:
95 °C (203°F)
"FD" DRAIN FLOOR (standard)
Connection:
ø 50 mm ( 2 in)
Peak flow rate:
50 lt/min (6,6 gal/min)
Max. height:
50 mm ( 2 in)
Max. temperature:
95 °C (203°F)
"D" DRAIN WALL (optional)
Connection:
ø 40 mm (1,6 in)
Peak flow rate:
30 lt/min (6,6 gal/min)
Altezza max. - Max. height:
800 mm (32 in)
Temperatura max. - Max. temperature:
95 °C (203°F)
Others
WEIGHTS
Total net max:
280 kg (617 lb)
Total gross max:
310 kg (683 lb)
Max. on working:
380 kg (837 lb)
Floor load:
600 kg/m
2
(61 lb/ft2 )
ENVIRONMENT
Temperature min-max
T = 10 - 40 °C (50-104°F)
Umidity max:
80% for temperatures up to 31°C
(88°F) with a linear drop to 50% humidity at 40°C (104°F)
Noise level emission:
< 66 dB (A)
4
Loading...
+ 8 hidden pages