Specified cold water limits and added notes for the optional drain pump
Update: hydraulic and electric connection from the upper side, Except the models provided with heating tanks
(«boiler»). Improved prescription regarding supply water.
INSTALLATION REQUIREMENTS
WD6010 – GW6010
SMEG S.p.A. thank you for choosing this product.
Pre-installation operations (to be performed by the client):
room preparations (as needed)
pre-installation of properly operating systems, in compliance with the requirements and
regulations in force
positioning of the machine
Refer to this manual for detailed instructions on the steps mentioned above.
SMEG S.p.A. declines responsibility for damage to persons or property resulting from improperly
regulated or defective systems or for any installation of the appliance and/or accessories performed by
unauthorized personnel.
Any operation performed on the appliance by unauthorized personnel will invalidate the warranty.
1
WD6010-GW6010 INSTALLATION REQUIREMENTS
CAUTION
It is essential that the electrical system to which the machine is connected complies with current regulations.
All electrical testing operations and equipment installation should be made by qualified and trained personnel.
The designated personnel is responsible for ensuring the safety and efficiency of earth connection.
Components must always be replaced with genuine spare parts.
CIRCUIT-BREAKER
A CIRCUIT-BREAKER must be installed for each appliance.
Circuit-breaker characteristics:
a. Omnipolar: must break all live conductors;
b. Easily accessible to the user;
c. Easily operated (no additional tools required);
d. Located in close proximity to the appliance;
e. Clearly marked as the appliance circuit-breaker
The same specifications apply to the main switch on the machine: it must be easily accessible. Do not place
objects in a way that limits accessibility.
A PROTECTIVE DEVICE specifically for the appliance (e.g. magneto thermal breaker or fuse on every phase, with
appropriate dimensions based on the electrical characteristics indicated) should be installed in the room’s
electrical panel.
ELECTRICAL SYSTEM REQUIREMENTS
Refer to the Technical Data sheet to recognize the device’s electrical characteristics and connection requirements.
The device is supplied with a cable with insulated wire terminals; it is not supplied with a plug. The electrical connection of
the device must be carried out with a permanent connection.
2
WD6010-GW6010 INSTALLATION REQUIREMENTS
Microbial contamination limits - Minimum microbiological
quality required:
“drinking water type” (ref. limits
provided by European Directive
98/83/CE)
4 - 12 l/min (0,88-2,64 gal/min)
Ferro Max - Fe2+ / Fe3+ [max]
4 - 12 l/min (0,88-2,64 gal/min)
4 - 12 l/min(0,88-2,64 gal/min)
Note: if local-regional requirements are more stringent than those prescribed above, the local
requirements shall be followed. It remains the user's responsibility to provide water supply that
comply with the requirements.
3
WD6010-GW6010 INSTALLATION REQUIREMENTS
"EC" Electrical connections
400V 3N~ / PE / 50Hz / 24A
Electrical protection required:
3P+N, 32 A
Cable and min. section:
230V 3~ / PE / 50Hz / 36A
Electrical protection required:
3P, 40 A
Cable and min. section:
"FD" DRAIN FLOOR (standard)
"D" DRAIN WALL (optional)
Altezza max. - Max. height:
Temperatura max. - Max. temperature:
T = 10 - 40 °C (50-104°F)
80% for temperatures up to 31°C
(88°F) with a linear drop to 50%
humidity at 40°C (104°F)
4