Smeg F23-S, F49-S, F72-S, R23-S, R49-S Installation And Operation Instructions Manual

...
BOTTOM MOUNT
REFRIGERATORS AND FREEZERS
INSTALLATION AND
OPERATION INSTRUCTIONS
INSPECTION
INSTALLATION
The unit has been secured to the shipping base with four bolts. Remove these bolts and separate the unit from the shipping base. Locate the casters or legs found inside the unit. Attach the casters or legs to the unit base by screwing them into the threaded fittings that were used to secure the shipping base. Use the wrench provided to tighten the casters to the unit. The casters with the brakes should be installed on the front of the unit. For proper drainage of condensate, the unit should be level when placed in its permanent location. Leveling shims are included in the accessories package in the cabinet. Loosen the casters and insert shims between caster and bottom of the unit. Retighten the caster.
The exterior of the cabinet and doors have been protected by a plastic covering. Peel this protective covering before installation. After removing the covering, clean the interior and exterior surfaces of the unit with soap and water and a rinse with clean water. Do not use chlorinated cleaners on the surfaces as they can cause corrosion.
If the door(s) have come out of alignment during shipping they will need to be adjusted. This can be accomplished by opening the door(s) and loosening the screws that hold both the top and bottom hinges to the cabinet. After adjusting the door so it is aligned correct, tighten the screws to securely hold the hinges and door(s) in place. The door on a single door unit can be reversed in the field by installing Hinge Kit part number 146524 available from your parts dealer.
The shelves and self clips are packaged inside the unit. Install the shelf clips on the pilasters inside the unit and set the shelves on the clips. The shelves are adjustable in ½” increments.
1
7/10 Rev. A 146527
The refrigeration system located at the bottom of the unit requires free air access for proper operation. Allow a minimum of seven inches between the back of the cabinet and the wall. Do not locate the unit next to heat generating equipment or in direct sunlight.
Confirm that the proposed electrical outlet has the correct voltage, frequency and current carrying capacity for the requirements of the unit. This information is noted on the data plate on the inside left wall of the unit. The unit should be isolated on a circuit. Do not use an extension cord to get power to the unit. Improper electrical installations will void the compressor warranty.
OPERATION
Once the unit is connected to the proper power supply, the display panel will be lit for two (2) seconds followed by a beep, and then the cabinet temperature will be displayed and the compressor will start to run. The compressor is running whenever ‘comp’ is lit on the display. If the cabinet temperature is higher than 68˚F (refrigerator) or 14˚F (freezers) the display will read <Hi> and lower than14˚F (refrigerator) or -50˚F (freezer) the display will read <Lo>. If the unit does not start immediately, check the power switch located on the bottom of the top grill. If the cabinet temperature is below 14˚F (freezer) or 50˚F (refrigerator) when the unit is plugged in there will be a three minute delay before the compressor will start.
The interior light will come on when a door is opened. Whenever a door is opened the door open light on the display will be lit and the
evaporator fans will stop. The fans will start three seconds after the door is closed. If a door is open for more than 30 seconds, the door open alarm will beep two times. If a door is open more than 60 seconds, the alarm beeps five times and if open more than five minutes the alarm will beep continuously.
The electronic control has an alarm function to remind the operator to periodically clean the condenser coil. The condenser coil will collect dust and debris during normal operation. If left unclean, this will lead to poor performance, high energy consumption and possible compressor failure. Warranties do not cover failures related to condenser cleaning. At 6 month intervals the display will blink “CL” and the buzzer will sound to remind the operator to clean the condenser coil. After one hour the buzzer will stop but the display will continue to blink “CL”. Refer to the ‘MAINTENANCE’ section of this manual to learn how to clean the condenser coil. The electronic control can be reset to normal operation by pressing the ‘Mode’ and ‘Verify’ buttons at the same time for five seconds. Depending on conditions, the condenser coil may require more frequent cleaning.
2
7/10 Rev. A 146527
MAINTENANCE
Cleaning
Beginning with the initial installation, the interior surfaces of the cabinet should be periodically cleaned with a solution of warm water and baking soda. This solution will remove any odors from spillage that has occurred. The exterior of the cabinet should also be cleaned frequently with a commercial stainless steel cleaner, glass cleaner or mild soap solution. Do not use chlorinated cleaners on the stainless steel surfaces.
The door gaskets should be cleaned in place with a mild soap solution to extend their life.
The shelving can be and cleaned in a sink with a mild soap solution and a soft bristled brush.
Condenser Coil
Prior to cleaning the condenser coil disconnect the unit from power. Periodic cleaning of the condenser coil will aid the heat transfer of the refrigeration system and increase its efficiency. Cleaning is recommended a minimum of every 6 months. To accomplish this, remove the lower front grill from the cabinet. The condenser coil is located behind the grill. Use a soft bristled brush to remove any dirt particles that are on the fins of the condenser coil. Use a vacuum cleaner or compressed air to remove the loosened particles. Replace the front grill and reconnect the unit to power. Failure to clean the condenser coil can lead to performance loss and compressor failure.
1. ELECTRONIC CONTROLLER DISPLAY PANEL LAYOUT Compressor ON
ELECTRONIC CONTROL
Displays Cabinet Temperature or Current Mode
Up Button
Manual DF/ Verify Button
Door Open
Power On
Mode/Set Button
Down Button
3
7/10 Rev. A 146527
2. ELECTRONIC CONTROLLER DISPLAY LEGEND
Display Description
St Temperature Setting Mode di Temperature Differential Setting Mode th Cabinet Temperature Verification Mode dt Defrost Frequency Setting Mode tb Rapid Freeze Mode dF Forced Defrost Mode
Electronic Control Settings
Setting Temperature-
The temperature set point is adjustable from -22˚F to 8˚F for the freezers and 25˚F to 50˚F for refrigerators. The default set point is -5˚F for freezers and 36˚F for refrigerators.
To set or adjust the cabinet temperature;
Press the ‘Mode/Set’ button.
Press the ‘Up’ or ‘Down’ button until<St> is displayed.
Press the ‘Mode/Set’ button to display current temperature set point.
Press ‘Up’ or ‘Down’ buttons until desired set point is displayed.
Press ‘Mode/Set’ button to set the new value.
Press “Up’ or “Down’ button until <th> is displayed.
Press ‘Verify’ button to return to display cabinet temperature.
Setting Temperature Differential-
The temperature differential is the amount of swing that the cabinet temperature does either side of the temperature set point. If the temperature set point is 36˚F and the temperature differential is 8˚F, the compressor will start when the control shows 40˚F and stop when the control shows 32˚F. The default temperature differential set point is 8˚F and the range is 4˚F to 16˚F.
To set the temperature differential;
Press ‘Mode/Set’ button.
Press ‘Up’ or ‘Down’ button until <di> is displayed.
Press ‘Mode/Set’ button to see current temperature differential setting.
Press ‘Up’ or ‘Down’ button until the desired value is displayed.
Press ‘Mode/Set’ button to set the value.
Press ‘Up’ or ‘Down’ button until <th> is displayed.
Press ‘Verify’ button to return to display cabinet temperature.
Rapid Freeze Mode (freezers only)-
When in rapid freeze mode the compressor will run continuously for 120 minutes and then return to normal operation and set points.
4
7/10 Rev. A 146527
To start rapid freeze mode;
Press ‘Mode/Set’ button.
Press ‘Up’ or ‘Down’ button until <tb> is displayed.
Press ‘Mode/Set’ button for two seconds to start rapid freeze.
To stop rapid freeze;
During rapid freeze, press ‘Mode/Set’ button for two seconds. <tb> will flash five times and then return to normal operation.
Setting Defrost Frequency-
The unit is preset to defrost every 6 hours. The defrost frequency can be set from 4 to 12 hours with a 2 hour interval. During defrost <dF> is displayed instead of cabinet temperature. To set defrost frequency;
Press ‘Mode/Set’ button.
Press ‘Up’ or ‘Down’ button until <dt> is displayed.
Press ‘Mode/Set’ button to see current defrost frequency setting.
Press ‘Up’ or ‘Down’ button until desired value is displayed.
Press ‘Mode/Set’ button to set the value.
Press ‘Up’ or ‘Down’ button until <th> is displayed.
Press ‘Verify” button to return to display cabinet temperature.
Setting Forced Defrost-
To start a forced defrost;
Press ‘Mode/Set’ button.
Press ‘Up’ or ‘Down’ button until <dF> is displayed.
Press ‘Manual DF’ for 2 seconds to start a forced defrost.
To stop a forced defrost; During a forced defrost, press ‘Manual DF’ button for 2 seconds to stop a forced defrost. <dF> will flash five times and then return to normal operation.
Problem Possible Cause Remedy
Compressor will not start
Power connection failure Check power cord and plug it in Power switch is in ‘off’ position Move it to ‘on’ position Temperature set point is too high Correct temperature set point The door is opened too frequently Loading of too much warm or
The unit does not
moist product
refrigerate well
Not enough ventilation
Condenser is clogged Clean it
Condensation on cabinet exterior
High humidity air can result in condensation
TROUBLESHOOTING
Move the unit in a well ventilated place with at least 7 inches of clearance on all sides
Wipe with cloth
5
7/10 Rev. A 146527
SPECIFICATIONS
Product Solid Door Freezer Solid Door Refrigerator
MODEL F23-S F49-S F72-S R23-S R49-S R72-S
Capacity (CuFt) 23 49 72 23 49 72
(W) 27.4 55.2 78.0 27.4 55.2 78.0
Exterior Dimension (in) (including casters)
Swing Doors 1 2 3 1 2 3
Shelves 4 8 12 4 8 12
(D) 31.3 31.3
(H) 83.7 83.7
Compressor 1/2HP 3/4HP 1.1HP 3/8HP 3/8HP 1/2HP
Power Voltage 115V 115V
Plug In-Installation NEMA 5-15P
Amps 8.5A 9.5A 9.0A 7.5A 7.5A 10.0A
Range of Temperature Below 0 °F 32~40 °F
Refrigerant R404a R134a
Net Weight (lb) 295 499 622 288 475 609
115/208­230V
NEMA 14-20P
115V
NEMA 5-15P
Above specifications are subjected to change without prior notice for quality
improvement.
The nameplate (includes Serial Number) is located on the upper left of the cabinet
interior.
6
7/10 Rev. A 146527
Loading...