SMC Sierra Monitor FieldServer ProtoNode,FieldServer ProtoCessor,FieldServer ProtoCarrier Recovery Manual

Document Revision: 1.A
Date: 7/18
T18060
FieldServer ENOTE
Recovery Instructions
FS ENOTE
Page 2 of 4
WHEN TO PERFORM A RECOVERY
Perform the following recovery if unable to connect to a FieldServer. The following recovery instructions only apply to FieldServer ProtoNodes, ProtoCarriers or ProtoCessors
of model type 2.
If the FieldServer was received before June 2018, the FieldServer is model type 1. However, model type 1 FieldServers are still being shipped so a visual check of the ProtoCessor board is needed to confirm the model type of a FieldServer. Check the images below for confirmation of the FieldServer model type.
Model Type 1 Standard (Left) and LonWorks (Right) ProtoCessors
Model Type 2 Standard (Left) and LonWorks (Right) ProtoCessors
FS ENOTE
Page 3 of 4
RECOVERY INSTRUCTIONS
Put a jumper on the first and second pins shown on the left side of the Ethernet port as shown below:
Wait for 1 to 2 minutes for the Run LED to start flashing.
NOTE: See Run LED location below:
When the Run LED starts flashing, remove the jumper.
The unit IP Address will be set to 192.168.2.100.
Open a browser window on a PC connected to the local network and download the
config/firmware/img files for the application.
LED Locations for Standard (Left) and LonWorks (Right) ProtoCessors
ProtoNode with Jumper Set for Recovery
FS ENOTE
Page 4 of 4
Technical Support
Thank you for purchasing the FieldServer from Sierra Monitor Corporation. Please call us for any technical support needs related to the FieldServer product.
Sierra Monitor Corporation 1991 Tarob Court Milpitas, CA 95035
Website: www.sierramonitor.com
U.S. Support Information:
+1 408 964-4443 +1 800 727-4377
Email: support@sierramonitor.com
EMEA Support Information:
+44 2033 1813 41 Email: support.emea@sierramonitor.com
Loading...