SMC Sierra Monitor 5000 Sentry Instruction Manual

MODEL 5000
S E N T R Y
GAS MONITORING SYSTEM
Version 6
Effective for all Sentry systems manufactured after September 1, 1995.
APPLICABILITY & EFFECTIVITY
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
FMRC APPROVAL
ONLY THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS ARE FMRC* APPROVED
Sentry Model 5000 Gas Monitoring System
Controllers
Model 5000-02 Two Channel Controller Model 5000-04 Four Channel Controller Model 5000-08 Eight Channel Controller
Controller Options:
Model 5380-00
Rack Mount Configuration
Sensor Module
Model 5100-02 Combustible Gas Sensor Module Model 5100-05 Hydrogen Sulfide Sensor Module - EC Cell Calibration Equipment Model 1200-26 Calibration Gas Delivery System Model 1290-02 Combustible Gas Cylinder Model 5358-00 Calibration Head, Magnetic Model 5358-01 Calibration Head, Standard Model 5360-00 Calibration Gas Delivery Fitting
Notes:
1) FMRC Approval applies only to conventional (one cable run per sensor module) or multiplexed (multiple sensor modules per cable) installations. Apparatus must be installed in accordance with National Electrical Code.
2) FMRC Approval of the RS232C Data Output option applies only if used as a printer port and the apparatus connected to the controller does not use or generate greater than 250 Vrms.
Model 5383-00 Model 5387-00 Model 5392-00
NEMA-4X Configuration Printer Output Software Individual Alarm Relays
3) FMRC Approval for Hydrogen Sulfide Sensor Module applies to Model 5100-05 electrochemical cell only. Model 5100-01 solid state sensor is not approved.
4) FMRC Approval allows the presence of MODBUS firmware in the Sentry controller but does not cover the operation of the MODBUS firmware itself.
*FMRC: Factory Mutual Research Corporation
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
TABLE OF CONTENTS
1. PRODUCT DESCRIPTION.............................................................................................................................................1
1.1 GENERAL.......................................................................................................................................................................1
1.2 CONTROLLER...............................................................................................................................................................1
1.2.1 ENHANCEMENT PACKAGE ...............................................................................................................................1
1.3 SENSOR MODULES......................................................................................................................................................1
1.4 INTERCONNECT WIRING...........................................................................................................................................2
1.5 DATA TRANSMISSION................................................................................................................................................2
1.6 POWER REQUIREMENTS............................................................................................................................................2
2. CAUTIONS & WARNINGS...........................................................................................................................................15
2.1 INTRODUCTION.........................................................................................................................................................15
2.2 CONTROLLER.............................................................................................................................................................15
2.3 WIRING ........................................................................................................................................................................15
2.4 SENSOR MODULES - GENERAL..............................................................................................................................15
2.4.1 COMBUSTIBLE SENSOR MODULES...............................................................................................................15
3. INSTALLATION.............................................................................................................................................................17
3.1 CONTROLLER LOCATION........................................................................................................................................17
3.2 SENSOR MODULE LOCATIONS..............................................................................................................................17
3.3 WIRING ........................................................................................................................................................................17
3.4 SENSOR MODULE INSTALLATION ........................................................................................................................18
3.5 CONTROLLER INSTALLATION ...............................................................................................................................19
3.5.1 CONTROLLER CONFIGURATIONS .................................................................................................................19
3.5.2 CONTROLLER MOUNTING...............................................................................................................................19
3.5.3 ALARM DEVICE INSTALLATION....................................................................................................................20
3.5.4 RELAY OUTPUTS...............................................................................................................................................20
3.5.5 DC POWER LOAD...............................................................................................................................................20
3.5.6 POWER UP ...........................................................................................................................................................21
3.5.7 POWER DOWN....................................................................................................................................................21
4. CONFIGURATION PROCEDURE...............................................................................................................................33
4.1 INTRODUCTION.........................................................................................................................................................33
4.2 START-UP PREPARATION........................................................................................................................................33
4.3 CONFIGURATION INSTRUCTIONS.........................................................................................................................35
4.4 SENTRY TRAINING....................................................................................................................................................35
4.5 SENTRY MENU...........................................................................................................................................................37
4.5.1 TEST KEY.............................................................................................................................................................37
4.5.2 TIME KEY ............................................................................................................................................................37
4.5.3 RESET KEY..........................................................................................................................................................38
4.5.4 MODE KEY - CALIB/CHANGE..........................................................................................................................38
4.5.5 MODE KEY - OTHER..........................................................................................................................................39
5. CALIBRATION...............................................................................................................................................................47
5.1 SENTRY CALIBRATION - AN OVERVIEW.............................................................................................................47
5.1.1 GLOBAL CALIBRATION....................................................................................................................................47
5.1.2 LOCAL CALIBRATION ......................................................................................................................................47
5.2 CALIBRATION INITIALIZATION.............................................................................................................................47
5.2.1 MODULES............................................................................................................................................................47
5.2.2 CALIBRATION PARAMETERS .........................................................................................................................48
5.3 CALIBRATION PROCEDURE....................................................................................................................................48
5.3.1 CONTROLLER SET-UP.......................................................................................................................................48
5.3.2 CALIBRATION GAS DELIVERY METHODS...................................................................................................51
5.3.3 SENSOR EXPOSURE TO GAS ...........................................................................................................................51
TABLE OF CONTENTS
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
6. MAINTENANCE.............................................................................................................................................................53
6.1 MAINTENANCE REQUIREMENTS...........................................................................................................................53
7. SERVICE..........................................................................................................................................................................55
7.1 OVERVIEW ..................................................................................................................................................................55
7.1.1 GENERAL.............................................................................................................................................................55
7.1.2 INSTALLATION INSPECTION...........................................................................................................................55
7.1.3 DATA COLLECTION...........................................................................................................................................55
7.1.4 INSPECTION AND TROUBLESHOOTING GUIDE..........................................................................................55
7.2 CONTROLLER .............................................................................................................................................................58
7.2.1 MECHANICAL/FUNCTIONAL DESCRIPTION................................................................................................58
7.2.2 ELECTRICAL DESCRIPTION.............................................................................................................................58
7.3 COMMUNICATIONS...................................................................................................................................................63
7.3.1 DESCRIPTION OF COMMUNICATIONS..........................................................................................................63
7.3.2 WARNING AND ERROR MESSAGES...............................................................................................................64
7.3.3 WARM-UP TIMERS.............................................................................................................................................64
7.3.4 ACCESS CODES...................................................................................................................................................64
7.3.5 DIAGNOSTIC CODES .........................................................................................................................................64
7.3.6 DIAGNOSTIC REPORT.......................................................................................................................................65
7.4 HYDROGEN SULFIDE MODULE (5100-01).............................................................................................................66
7.4.1 DESCRIPTION......................................................................................................................................................66
7.4.2 TROUBLE ANALYSIS.........................................................................................................................................66
7.4.3 ADJUSTMENT PROCEDURE.............................................................................................................................66
7.4.4 SENSOR REPLACEMENT...................................................................................................................................67
7.5 COMBUSTIBLE GAS SENSOR MODULE (5100-02)................................................................................................69
7.5.1 DESCRIPTION......................................................................................................................................................69
7.5.2 TROUBLE ANALYSIS.........................................................................................................................................69
7.5.3 ADJUSTMENT PROCEDURE.............................................................................................................................69
7.5.4 SENSOR REPLACEMENT...................................................................................................................................70
7.5.5 COMBUSTIBLE GAS SCALING FACTORS......................................................................................................71
7.6 OXYGEN MODULE (5100-03)....................................................................................................................................72
7.6.1 DESCRIPTION......................................................................................................................................................72
7.6.2 TROUBLE ANALYSIS.........................................................................................................................................72
7.6.3 ADJUSTMENT PROCEDURE.............................................................................................................................72
7.6.4 SENSOR REPLACEMENT...................................................................................................................................72
7.7 CARBON MONOXIDE MODULE (5100-04)..............................................................................................................74
7.7.1 DESCRIPTION......................................................................................................................................................74
7.7.2 TROUBLE ANALYSIS.........................................................................................................................................74
7.7.3 ADJUSTMENT PROCEDURE.............................................................................................................................74
7.8 HYDROGEN SULFIDE MODULE (5100-05).............................................................................................................76
7.8.1 DESCRIPTION......................................................................................................................................................76
7.8.2 TROUBLE ANALYSIS.........................................................................................................................................76
7.8.3 ADJUSTMENT PROCEDURE.............................................................................................................................76
7.9 TOXIC GAS SENSOR MODULE ................................................................................................................................78
7.9.1 DESCRIPTION......................................................................................................................................................78
7.9.2 TROUBLE ANALYSIS.........................................................................................................................................78
7.9.3 ADJUSTMENT PROCEDURE.............................................................................................................................78
7.10 AMMONIA SENSOR MODULE (5100-25).................................................................................................................81
7.10.1 DESCRIPTION......................................................................................................................................................81
7.10.2 TROUBLE ANALYSIS.........................................................................................................................................81
7.10.3 ADJUSTMENT PROCEDURE.............................................................................................................................81
TABLE OF CONTENTS
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
8. APPENDICES..................................................................................................................................................................83
8.1 APPENDIX A - SPECIFICATIONS.............................................................................................................................85
8.2 APPENDIX B - LIMITED WARRANTY ....................................................................................................................89
8.3 APPENDIX C - ACCESS CONTROL BY USER CODE.............................................................................................91
8.3.1 INTRODUCTION.................................................................................................................................................91
8.3.2 DEFINITIONS.......................................................................................................................................................91
8.3.3 USER CODE INSTALLATION............................................................................................................................91
8.3.4 USER CODE REMOVAL.....................................................................................................................................91
8.3.5 DIAGNOSTIC CODES:........................................................................................................................................91
8.3.6 LOST ENTRY CODE ...........................................................................................................................................92
8.4 APPENDIX D: - MODEL NUMBERS & PARTS LIST ..............................................................................................93
8.4.1 CONTROLLER ITEMS........................................................................................................................................93
8.4.2 SENSOR MODULE ITEMS.................................................................................................................................94
8.4.3 CALIBRATION EQUIPMENT ............................................................................................................................95
8.5 APPENDIX E - INSTRUCTIONS FOR PRINTER SOFTWARE OPTION...............................................................97
8.5.1 IDENTIFICATION ...............................................................................................................................................97
8.5.2 CAPABILITY........................................................................................................................................................97
8.5.3 REPORTS..............................................................................................................................................................97
8.6 APPENDIX F - MODEL 5392 INDIVIDUAL RELAY ..............................................................................................99
8.6.1 RELAY PANEL DESCRIPTION..........................................................................................................................99
8.6.2 RELAY PANEL ASSEMBLY ..............................................................................................................................99
8.6.3 INSTALLATION ..................................................................................................................................................99
8.6.4 OPERATION.........................................................................................................................................................99
8.6.5 INDIVIDUAL RELAY SPECIFICATIONS.........................................................................................................99
8.7 APPENDIX G - MODEL 4314 OUTPUT EXPANSION PANEL ............................................................................103
8.7.1 EXPANSION PANEL DESCRIPTION ..............................................................................................................103
8.7.2 EXPANSION PANEL ASSEMBLY...................................................................................................................103
8.7.3 INSTALLATION ................................................................................................................................................103
8.7.4 OPERATION.......................................................................................................................................................103
8.7.5 OUTPUT EXPANSION PANEL TESTING.......................................................................................................104
8.7.6 INDIVIDUAL RELAY SPECIFICATIONS.......................................................................................................104
8.8 APPENDIX H - MODEL 5100-99 ANALOG INPUT MODULE.............................................................................106
8.8.1 DESCRIPTION ...................................................................................................................................................106
8.8.2 INSTALLATION ................................................................................................................................................106
8.8.3 ADJUSTMENT PROCEDURE...........................................................................................................................106
8.9 APPENDIX I - MODEL 5100-90 8-CHANNEL ANALOG-DIGITAL CONVERTER............................................107
8.9.1 DESCRIPTION ...................................................................................................................................................107
8.9.2 INSTALLATION ................................................................................................................................................107
8.9.3 SERVICE.............................................................................................................................................................107
8.10 APPENDIX J - REFERENCE DRAWINGS...............................................................................................................109
9. INDEX ............................................................................................................................................................................119
10. LIST OF FIGURES...................................................................................................................................................121
11. LIST OF TABLES.....................................................................................................................................................122
TABLE OF CONTENTS
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
1. PRODUCT DESCRIPTION
1.1 GENERAL
The Sentry 5000 is a fixed installation gas monitoring system designed for continuous operation in open or confined areas. The system is comprised of a controller and up to eight sensor modules. The sensor modules are supplied for detection of combustible gas, oxygen deficiency or various toxic gases and can be mixed within one system as required.
1.2 CONTROLLER
The Sentry controller is a microprocessor computer which performs functions including management of the sensor modules, management of alarm relays and interface with the user via the front panel which includes a concentration display, an alphanumeric display, keypad and status indicators. The microprocessor functions are permanently installed in the controller. They cannot be changed or damaged by the user and will not be altered by loss of power.
Configuration variables, such as alarm levels, can be changed via a simple keypad sequence. Information provided to the controller in this manner is retained even when the power is interrupted. This information can be protected by a "user code" to avoid unauthorized modification.
Sentry continually scans all modules for alarm conditions. No sequence of key presses can prevent the scanning except specific actions during calibration or deliberate disabling of the sensor module.
The Sentry controller is provided in a rack or panel mount version for control rooms, an environmental enclosure for outdoor, stand alone applications, or other packages for specialty applications.
1.2.1 ENHANCEMENT PACKAGE
Various factory installed firmware enhancements are available for the Sentry controller. These are selected at the time of purchase or subsequent upgrade. The enhancements, which are described in detail in the appropriate sections of this manual, include:
Addition of printer output firmware for models
5000-04 or 5000-02. Printer output is standard on model 5000-08.
Replace printer output firmware with MODBUS
data address protocol for host computer or DCS interface. MODBUS is an industry standard communication protocol which allows bi­directional communication via the controller RS­232C serial port.
High Alarm Acknowledge function for alarm
reset.
Low Alarm Acknowledge function for alarm
reset
Emergency Alarm function adds a third alarm
level.
Zone and Voting assignment of individual alarm
relays.
Analog Output software driver for use with
Model 4314-01 output module.
Custom default Gas Tags and Engineering Units
Tags for up to eight input devices.
Custom default Module Tags for up to eight
module addresses.
Configure alarm relays to be normally energized
in the safe condition.
1.3 SENSOR MODULES
Each sensor module ("module") is labeled internally to identify the type of gas it is designed to detect. For each gas group, the sensor and the electronics board in the explosion proof housing is different. During installation, switches in the electronics are set by the user to give the module an address (module number) to make it unique from others in the same system. Sentry then "communicates" with each module to determine its number, the type of gas it detects, the gas concentration and other information.
Inside the module housing is an electronic assembly consisting of two printed circuit board assemblies mounted under a metal top plate. The address switches and adjustment potentiometers are accessible through the plate and electrical test points (test lead jacks) are installed in the plate. Connectors for wiring from the controller and the sensor are located on the bottom of the electronic assembly. The sensor is installed in one hub of the enclosure.
PRODUCT DESCRIPTION
Page: 1
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
1.4 INTERCONNECT WIRING
Not supplied with Sentry, but necessary to the installation and operation is the three conductor wiring which connects the controller to the modules. Before this wiring is installed it is important to read and understand the installation instructions (Chapter 3) because significant economies can be realized by connecting more than one module onto a common wiring run. This standard feature is accomplished by multiplexing the signals from the modules to the controller.
1.5 DATA TRANSMISSION
Transparent to the user is the data transfer which occurs on the installed interconnect wiring. Two of the conductors are used to pass direct current (DC) from the controller to the modules. The third wire transfers a series of very rapid pulses between the controller and the sensor modules. This digital transfer of information is an important feature of the system which significantly reduces RFI and EMI problems.
1.6 POWER REQUIREMENTS
The standard system requires 120 VAC, 60 Hz, at 0.5 Amp electrical supply. A factory option can be ordered for 220 VAC operation. DC voltage (12 to 28 VDC) can be used for standby power. The system will automatically switch to supplied DC operation at any time the AC voltage is interrupted.
The system includes a lithium battery for RAM memory retention during power interruptions. To ensure continuous trouble free operation, however, the primary power source must be one which is continuous and reliable, preferably dedicated to this equipment. Battery back-up or emergency power is recommended to insure continuous operation.
PRODUCT DESCRIPTION
Page: 2
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 1-1
Front Panel Display
PRODUCT DESCRIPTION
Page: 3
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 1-2
Rack Mount Configuration - Outline
PRODUCT DESCRIPTION
Page: 4
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 1-3
NEMA-4 Configuration - Outline
PRODUCT DESCRIPTION
Page: 5
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 1-4
NEMA-7 Configuration - Outline
PRODUCT DESCRIPTION
Page: 6
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 1-5
Panel Mount Configuration Outline
PRODUCT DESCRIPTION
Page: 7
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 1-6
Wall Mount Configuration Outline
PRODUCT DESCRIPTION
Page: 8
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 1-7
Hydrogen Sulfide Module - Outline
PRODUCT DESCRIPTION
Page: 9
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 1-8
Combustible Sensor - Outline
PRODUCT DESCRIPTION
Page: 10
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 1-9
Oxygen and Toxic Sensor Modules - Outline
PRODUCT DESCRIPTION
Page: 11
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Model 5100-05 Hydrogen Sulfide Sensor Module (FMRC Approved) - Outline
Figure 1-10
PRODUCT DESCRIPTION
Page: 12
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 1-11
Model 5100-25 Ammonia Sensor Module - Outline
PRODUCT DESCRIPTION
Page: 13
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
2. CAUTIONS & WARNINGS
2.1 INTRODUCTION
Although the Sentry system is designed and constructed for installation and operation in industrial applications including "hostile" environments, caution should be taken to insure that the installation is made in compliance with this instruction manual and that certain procedures and conditions are avoided. This chapter discusses the necessary cautions. Read the entire chapter prior to
installation of the equipment.
2.2 CONTROLLER
The controller should be installed in a location which is safely accessible during a gas alarm.
Avoid installing the controller where it will be unnecessarily exposed to wind, dust, shock or vibration or direct sun. Observe temperature range limitations.
Adhere to standard electrical installation procedures. The chassis ground on the controller must be connected to earth ground.
2.3 WIRING
While the digital communication method used between the controller and modules will greatly reduce problems associated with electromagnetic and radio frequency interference the manufacturer recommends that extra caution be taken where the installation is near any sources of these interferences:
Avoid running sensor module cable close to high
power cables, radio transmission lines, or cables subject to pulses of high current.
Avoid running cables near large electric motors or
generators.
When the risk of interference is present use shielded
cables. In conduit installations the shield should be connected to the conduit. In cable applications the shield should be connected to the cable connector.
All splices must be via either a lug and terminal
system or soldered. Improperly spliced cable can result in corrosion, resistance changes and system errors.
NOTE
Installation and wiring must be in accordance with the
National Electrical Code
2.4 SENSOR MODULES - GENERAL
Avoid installing sensor modules where they will be unnecessarily exposed to wind, dust, water (esp. direct hose down), shock, or vibration. Observe temperature range limitations.
Sensors may be adversely affected by prolonged exposure to certain materials. Loss of sensitivity, or corrosion, may be gradual if such materials are present in low concentrations. These materials include: Halides (compounds containing chlorine, fluorine, bromine, iodine), silicones, acid vapors, caustic liquids or mists.
Care has been taken by the manufacturer to ship your modules in protective packaging to avoid contamination prior to installation. It is recommended that the sensors remain protected during installation and that the covering be removed immediately prior to system start-up.
During normal use the sensor is protected from dirt and oil contamination by a sintered metal cover. If this cover becomes clogged, the response of the sensor will be reduced. Protect the sensor from contamination by careful placement, or by use of rain and dust shields.
Sensor modules must not be painted. Paint may contain compounds which will contaminate the sensor. Paint will cause clogging of the sintered metal cover and will cause difficulties during attachment of the calibration head or other maintenance activity. It is recommended that the module be tagged "DO NOT PAINT".
When sensors are replaced the thread must be Teflon taped to avoid metal to metal binding which will damage the housing threads.
2.4.1 COMBUSTIBLE SENSOR MODULES
Catalytic type combustible gas sensors may be poisoned by exposure to silicones. Sierra Monitor Corporation supplies resistant sensors, but care should be taken to avoid exposure to silicones. No Silicone caulking (RTV) should be used near the sensors. No other silicone based compounds should be used near the sensors unless they are fully protected during the entire cure cycle. If the sensors will be exposed to silicone during normal operation the manufacturer's sensor warranty is void.
CAUTIONS & WARNINGS
Page: 15
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
3. INSTALLATION
All systems are factory are pre-configured and calibrated.
NOTE
All sensors are tagged to indicate the controller (alpha)
and the sensor module number (1 - 8).
Identify all components of the system during unpacking
and install using the factory configuration.
The system will power up in a calibrated and fully
functional condition.
3.1 CONTROLLER LOCATION
Rack mounted controllers should be installed in a control room environment where they will be relatively free from dust and temperature extremes. For ease of operation select a rack window space at approximately eye level. Four controllers can be installed side by side in a 19" instrument shelf.
Enclosed controllers for outdoor applications should be located in the most protected location available with consideration for easy access for installation and calibration. The enclosures should be mounted on a vertical surface with the key board at approximately eye level. The enclosure should not face directly into the sun.
3.2 SENSOR MODULE LOCATIONS
Select locations for each of the sensor modules based on the following:
Consider the density, relative to dry air, of the gas to
determine height of module above floor or ground level:
Gas Density
(Air = 1.00)
Air 1.00
Ammonia 0.60 Carbon Monoxide 0.97 Chlorine 2.49 Ethylene Oxide 1.52 Hydrogen 0.07 Hydrogen Chloride 1.27 Hydrogen Cyanide 0.94 Hydrogen Sulfide 1.19 Methane 0.55 Nitrogen Dioxide 1.58 Oxygen (Air) 1.10 Sulfur Dioxide 2.26
Modules should be placed close to the potential source
of gas.
Modules should be placed in areas accessible for
calibration.
Sensors should be pointed down and the conduit
should include an inverse trap to reduce moisture (condensation) from accumulating in the electronics enclosure Figure 3-3.
3.3 WIRING
Plan the wiring arrangement to minimize installation expense but with redundancy for critical locations. Wire shall be Belden (or equivalent) 949X (where X = 2, 3, 4, or 5 depending on wire gauge). If high RFI or EMI levels exist wiring should be protected by conduit or shield. Shielded wire shall be Belden (or equivalent) 936X.
In no case should the drain wire of shielded cable be used
as one of the conductors.
NOTE
Any modules which are located in a common
geographical area a long distance from the controller can be connected to the same three conductor wire run installed from the controller to that area. Table 3-2, Figure 3-4.
The remote auxiliary power supply option can be used
for installation of one or more modules a long distance from the controller location. The connection from the controller to the remote power supply is via a two conductor "data link" Figure 3-4.
Number of Maximum length of wire run (feet)
modules 500 1,000 2,000 3,000 5,000
1 2 3 4
20 20 18 16 14 20 18 14 12 xx 18 16 12 xx xx 16 14 12 xx xx
Table 3-2
Minimum Wire Gauges
Table 3-1
Specific Gravity of Selected Gases
INSTALLATION
Page: 17
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Install conduit as required. Provide for splice boxes where multiple modules will be wired to a single run. Pull 3 (typical: white, black, green) conductors of the correct gauge wire from the controller to each splice box and from the respective splice box to each planned module location. See Figure 3-5 for proper wire termination in the splice box. Twisted wire secured with wire nuts is not an acceptable splice.
NOTE
Installation and wiring must be in accordance with the
National Electrical Code
In installations where redundancy of module locations is a requirement do not install multiple modules on one cabling run as any damage to the primary wiring will disable all the modules.
NOTE
Temperature rating of cable wire insulation must be
above 75oC (85oC or greater rating wiring is recommended). If cable runs through higher temperature environments, it should be specified for that environment.
3.4 SENSOR MODULE INSTALLATION
Note: Remove spring from the electromechanical sensor (5100-04 through 5100-23) prior to installation. See technical note provided with sensor module.
1. Remove the electronics from the module housing by:
Unscrew the two captive panel screws in the
top plate.
Lift the electronics out of the housing.
Unplug the sensor harness from the bottom
electronics board.
2. Install the module housing onto the end of the supply conduit and/or bolt into position as required.
Note If housing grounding is required for the installation a grounding lug is located under the two printed circuit
assemblies in the housing. Install the ground wire under
the green lug. Figure 3-5
Controller
Marking
Function Module
Marking
Color
1 +VDC P White 2 Signal S Black 3 DC Return G Green
Table 3-3
Sensor Module Wiring
4. Reconnect the sensor harness to the sensor connector on the bottom of the electronic assembly. Figure 3-7.
5. Twist the assembly 180o to take up the service loop on both the incoming wire and the sensor harness. With the sensor facing down the wording on the cover plate will be correctly oriented.
6. Carefully fit the electronics over the two posts in the housing and tighten the captive panel screws.
Module Switch Positions
# 1 2 3 1 ON ON ON 2 OFF ON ON 3 ON OFF ON 4 OFF OFF ON 5 ON ON OFF 6 OFF ON OFF 7 ON OFF OFF 8 OFF OFF OFF
Table 3-4
Sensor Module Binary Switch Positions
7. Set the dip switch Figure 3-8 on each module to indicate the module number (Table 3-4). Each of the modules connected to one controller must have a different address. (Note: Switch position 4 is not used.)
3. Connect the three wires which run from the controller to the three position terminal strip on the bottom of the electronics assembly. See Table 3-3 for terminal markings and normal wiring color code conventions. Figure 3-7 shows the correct wiring connections and the operation of the connector mechanism.
INSTALLATION
Page: 18
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
3.5 CONTROLLER INSTALLATION
3.5.1 CONTROLLER CONFIGURATIONS
Table 3-5 lists the number of sensor modules which can be operated on each controller model.
Model Controller Capacity
5000-02 2 Sensor Modules 5000-04 4 Sensor Modules 5000-08 8 Sensor Modules
Table 3-5
Sentry Controller Capacity
Table 3-6 lists and describes Sentry controller enclosure options.
Model Description
5380-00 Standard configuration, controller
intended for installation in instrument rack. Wiring to back connector panel.
5381-00 Controller supplied with bezel for panel
or chassis installation. Wiring to back connector panel.
3.5.2.2 CHASSIS MOUNTED CONTROLLER
The chassis mounted controller is provided with a pre­installed bezel and a template for the chassis cut-out. An angle bracket is also provided to support the cantilever of the controller. Select an appropriate location at approximately eye level providing rear access for the module and alarm wiring.
3.5.2.3 WALL MOUNTED CONTROLLER
The wall mounted controller is provided on a sheet metal panel containing brackets which allow for removal of the controller. Select a location, where module and alarm wiring can be run up or down the wall for distribution, and bolt the panel to the wall.
3.5.2.4 NEMA ENCLOSED CONTROLLER
Mount the NEMA enclosed controller on a vertical surface with the display at approximately eye level. Mounting feet are supplied with the enclosure for external mounting bolts. Figure 1-3. Although the enclosure is designed for exposure to weather, normal measures to protect the system from harsh conditions are recommended. It is particularly important to avoid exposure of the display to direct sunlight as this can cause fading of the display during very hot weather.
5382-00 Wall mount configuration includes a
mounting panel and brackets, display is side mounted. Wiring to side facing panel.
5383-00 NEMA-4X Enclosure with latching front
door and window for viewing display. Wiring to front facing terminal strips.
5395-00 NEMA-7 Explosion Proof Enclosure
with screw in window for viewing of display and external switches for operation of keypad. Wiring to side facing panel.
Table 3-6
Sentry Enclosure Options
3.5.2 CONTROLLER MOUNTING
3.5.2.1 RACK MOUNTED CONTROLLER
The instrument rack should be installed in a 19" electronic cabinet at eye level. Care should be taken to avoid heat from other instruments under the controller.
3.5.2.5 WIRING CONNECTIONS
Channel wiring connections at the controller (except NEMA-4X) and at the module are made using a quick connect terminal strip. Figure 3-7. The terminal can be operated using an actuator (supplied in the system accessory bag) or by pressing a small screwdriver into the actuator slot.
It is important to understand that, because of multiplexed communication, there is a difference between "channel" numbers and "module" numbers. Channels are the physical connectors at the controller. Module numbers are the switched addresses on each module. More than one module number may be installed on a channel, up to a maximum of four modules.
NOTE
Installation and wiring must be in accordance with the
National Electrical Code
Make the following connections at the controller.:
Attach the three wires for each channel to separate
channel connectors on the terminal strip marked CH1 through CH8. The sequence should exactly match that at the sensor assembly. (Typical: White 1, Black 2, Green 3.)
INSTALLATION
Page: 19
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Connect the necessary remote audible and visual
alarms or other process control equipment to the
"HIGH", "LOW" and "TROUBLE" dry contact relays on
the connector panel.
The Double Pole/Double Throw (DPDT) relay connections are marked to indicate Normally Open
(N/O) , Normally Closed (N/C) and Common (COM)
terminals for each pole. No voltage is applied to the terminals internally.
Typical wiring configuration is described in Figure 3-11. The trouble relay is fail safe so that it will switch from Normally Closed to Normally Open if all system power is lost.
NOTE It may be preferably to delay wiring the alarms, or delay powering them, until the detection system has been fully
activated, tested and calibrated.
Connect 120 volts AC wiring to the terminals marked Hot (black), Neutral (white), and Ground (Green).
If a 12-28 VDC supply is to be used as either back-up or as the primary operating voltage make the necessary connections to the terminal marked "DC INPUT 12 - 28V" "+" (Red) & "-" (Black).
NOTE
When a battery is to be used for back-up DC supply only,
a Sentry feature provides protection against battery damage by shutting off the battery before complete
discharge. When this feature is used, the Sentry
controller can only be restarted by AC voltage.
To implement the battery protection feature, two red
jumper wires located on the power supply board must be
cut. See Figure 7-3.
If splice boxes are used to combine multiple modules on a channel the splice connections should be made using a terminal block/wire lug assembly or all wires should be soldered and insulated. Figure 3-5.
3.5.3 ALARM DEVICE INSTALLATION
Alarm devices must be installed according to the manufacturer's instructions for the particular device. Sentry dry contact relays provide switching capability as rated in the specifications. (See Appendix A.)
NOTE
Certain warning strobes have a very high peak current
which is dependent upon the phase angle of the AC line at
the precise moment the strobe is switched on. A high
current at the time of switching may cause the relay
contacts to stick together.
The corrective action to avoid contacts sticking together is
to install a 10 Ohm, 5 Watt resistor in series with the
strobe power, preferably close to the relay.
3.5.4 RELAY OUTPUTS
Three relays on the standard Sentry controller are for: high alarm, low alarm and trouble. The trouble relay is normally energized (power applied to coil). The gas alarm relays (high and low) are normally not energized. Individual low and high alarm relays are optional hardware.
NO
RELAY
COM.
110 VAC
NO
RELAY
COM.
+ -
MOV
1N4005
DC
Install MOV
close to switch
Install diode close to load
Figure 3-1
Typical Protection Circuit
The relays are dry contact and may be used to actuate bells, lights, sirens, solenoid valves, or contactors as required. It is recommended that for 120 VAC circuits a metal oxide varistor (MOV) rated for 150 Vrms be place across the load (Figure 3-1). (General Electric V150LA20A or equivalent). For DC circuits a general purpose rectifier diode should be placed across the load (1N4005).
3.5.5 DC POWER LOAD
Table 3-7 is provided to allow correct sizing of battery back-up. To determine total load add the applicable individual loads. (All measurements are at 12 VDC.)
Test Condition Amps Watts
Controller, No Sensors, No Alarms 0.560 6.7 Controller, No Sensors, All Alarms 0.660 8.0 Controller, 8 Combust, All Alarms 4.000 48.0 Individual Relay Board 0.750 9.3 Hydrogen Sulfide (Type 1) Module 0.260 3.1 Combustible (Type 2) Module 0.420 5.0 Electrochemical Sensor (typical) 0.050 0.6
Table 3-7
Sentry Power Load
INSTALLATION
Page: 20
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
3.5.6 POWER UP
Systems shipped complete from the factory are pre­configured and calibrated. When power is turned on the power light will start flashing and the alpha-numeric display will indicate "SYSTEM WARM-UP" "PLEASE WAIT
MM:SS" (where MM:SS is a five minute count-down
clock). When the warm-up ends the two displays will begin functioning in the "continuous scan" mode which is described in the next chapter. The large display will cycle through each module number for any modules which have been installed.
If modules have been added to the system since it was factory configured, those modules will have a blank (“—“) concentration display and the lower display will show the module type and units with "FACTOR MISSING" or
"UNCALIBRATED" messages.
If the display indicates module numbers which match the numbers used in installation, the wiring is correct and module configuration can begin. If any number is omitted the controller is not recognizing that module and the wiring should be checked for errors (the system will display "NO
MODULE" when any attempt is made to obtain information
on that module).
If the controller does not recognize any modules the display will read "NO MODULES INSTALLED".
NOTE
On 2 and 4 Channel systems any module set with a number higher than four will cause the lower display to indicate "MODULE # MUST BE 1 THROUGH 4" and
the upper display to display "#E --" (where # = the
erroneous module number).
3.5.7 POWER DOWN
If it is necessary to remove the power all operator configured data and parameters will be saved by Sentry. (It is important to turn off the main power prior to disconnection of any module wiring because while under power Sentry will interpret certain changes as errors.)
INSTALLATION
Page: 21
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 3-2
Controller Mounting Options
Page: 22
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 3-3
Sensor Module Mounting
Page: 23
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 3-4
Wiring Options
Page: 24
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 3-5
Typical Splice Box Wiring
Page: 25
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 3-6
Sensor Module Cross Section
Page: 26
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 3-7
Sensor Module Connector Detail
Page: 27
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Sensor Module Top Plate Detail - Typical
Figure 3-8
Page: 28
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 3-9
Controller Connector Panel - Rack Configuration
Page: 29
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Controller Connector Panel - NEMA-4X Configuration
Figure 3-10
Page: 30
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 3-11
Typical Alarm Wiring Configuration
Page: 31
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
4. CONFIGURATION PROCEDURE
4.1 INTRODUCTION
Sentry is operated via the seven keys on the front panel. Operation includes initial set-up, periodic calibration, recall of history, and changes to configuration.
Certain procedure and message conventions are used to provide consistency. A knowledge of these conventions will aid in understanding of the set-up and operation steps.
The UP and DOWN arrow keys change information displayed on the alpha-numeric (lower) display. Changes made by using the arrows are not "implemented" until the
ENTER key is pressed.
The ENTER key is used to access the selected activity or to enter selected data or status information into the controller memory.
When any of the four activity keys TEST, RESET, TIME,
MODE are depressed the SENSOR/LEVEL display is
cleared and the activity information is displayed on the alpha-numeric display.
The messages PRESS ENTER TO or ENTER TO indicate that the selected activity can be accessed via the ENTER key.
If the ENTER key is pressed once during normal operation the display locks onto the current module number and can be advanced using the UP and DOWN arrow keys. When the display is locked onto one module number the gas type and units display is shown in round parenthesis “( )”.
If any module is force calibrated, the gas type and units display for that module number is shown in square parenthesis “[ ]”.
The message USE ARROWS/ENTER indicates that the arrows can be used to change the module number or other data on the second line and the ENTER can be used to access the selected activity or module number.
Successive presses of any one of the four activity keys will cycle through each option available and will return the system to the normal operating mode..
When any activity key cycle has been started and not completed the remaining activity keys are disabled except that the RESET key can be used to return the system to normal OPERATE mode.
When the system is in the CHANGE mode the CALIBRATE
OR CHANGE light is ON.
4.2 START-UP PREPARATION
The worksheet, Figure 4-1, will aid in understanding the type of information required to set-up the system, it should be completed prior to system power-up.
The message USE ARROWS/ENTER indicates that module numbers or other variables can be changed with the arrows prior to entering the activity with the ENTER key.
The message PRESENT CONFIG is used in system responses during CHECK activities. Variables displayed as PRESENT CONFIG can be changed via the CHANGE mode.
Positive response messages such as SYSTEM RESET
COMPLETE are displayed for 1.5 seconds to confirm that
the activity has been completed. Activity names are displayed bracketed by "<" and ">"
signs. Normal operation is the condition where the change and
calibrate light is off and the display cycles continuously between all active module numbers.
CONFIGURATION PROCEDURE
Page: 33
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
MODULE ADDRESS
1 2 3 4 5 6 7 8
LOCATION SENTRY
CHANNEL
GAS
TYPE
LOW HIGH LATCH SCALING
FACTORS
SENSOR
SERIAL #
Figure 4-1
System Configuration Worksheet
NOTES
1 Module Address Dip switch setting for each sensor module 2 Location Describe the physical location of the module 3 Sentry Channel Log the channel number to which the module is wired 4 Gas Log the name of the gas which is to be detected 5 Low Alarm Enter the value for the low alarm
Default values are: H2S: 10 PPM, Combustible 20% LEL, Oxygen 19.5%, Toxic 10 PPM
6 High Alarm Enter the value for the high alarm
Default values are: H2S: 20 PPM, Combustible 60% LEL, Oxygen 16.5%, Toxic 20 PPM Note: Combustible Alarms cannot be set greater than 60% LEL.
7. Latch L?/H? Determine if any module will require a latching alarm and write "Y" in the appropriate position (e.g.: N/Y indicates a non-latching low alarm and latching high alarm, Y/Y indicates both relays will be latching). The system "defaults are N/Y. Note: Combustible High Alarms are Latching Only
8 Factors For H2S (5100-01): Record the three (three digit) numbers which are written on the sensor
connector on each sensor. For Combustibles: If the gas to be detected and the gas to be used for calibration are the same write "100". If the calibration gas is methane and a different gas is to be detected select the correct factor from XXXXX.
Note: Combustible Gas Scaling Factors are not FMRC approved.
No factors are required for Oxygen or Toxic sensors.
9 Sensor Serial Number Record the serial number from the label on the connector of each sensor
CONFIGURATION PROCEDURE
Page: 34
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
4.3 CONFIGURATION INSTRUCTIONS
Sentry controllers which are components of complete systems are factory configured and generally do not require changes prior to being placed in service.
Sentry controllers which have not been factory configured can be placed into operation with default values for all configuration parameters by using the diagnostic code “0021” described in Section 8.3 of this manual.
The following are step-by-step configuration instructions which can be used to customize the operation of the controller for specific applications. After initial configuration the controller can be placed in service or used for training as described in the this section.
If an error is made, or suspected, press the RESET key until the display reads <RESET SYSTEM> and then press the ENTER key, the system will reset and the set-up routine can be re­started.
STEP KEY LOWER DISPLAY
1 RESET <RESET ALARMS> 2 RESET <RESET SYSTEM>
3 ENTER SYSTEM RESET COMPLETE
<UNCALIBRATED> Displays continue cycling through each
module number. Power light changes from flashing to solid.
4 MODE <CALIB/CHANGE>
5 ENTER CHANGE MODE SELECTED
Note that if a user entry code has been
initiated it must be input here.
Change/Calibrate light turns on. READ INSTRUCTION MANUAL FIRST PRESS ENTER TO CALIB ALL [GGGG]
Where GGGG is the gas type. 6 MODE <CHANGE CALIB> 7 MODE <CHANGE MODULE>
STEP KEY LOWER DISPLAY
15 ENTER FACTOR = 100
Linearizing factors are required for sensor
modules 5100-01 (H2S) .
Scaling factors can be used for sensor
module 5100-02 (Combustibles)
16 ENTER MODULE # = 2
Repeat steps 9 through 15 for each module.
17 MODE <SET USER CODE> 18 MODE <CHANGE PRINTER>
or
<CHANGE MODBUS>
Displays only if printer or MODBUS
option is installed.
19 MODE CHANGE GAS TAG
20 MODE CHANGE MOD TAG 21 MODE CHANGE ENG UNITS 22 MODE <OPERATE MODE>
23 ENTER OPERATE MODE SELECTED
24 TIME <CHECK HISTORY>
25 TIME <HISTORY REPORT>
For printer option only.
26 TIME <SYSTEM REPORT>
For printer option only.
27 TIME <STATUS REPORT>
For printer option only. 28 TIME <SET DATE & TIME> 29 ENTER D&T MM/DD HH:MM
Set each digit using the arrows, then ENTER to advance to the next digit.
28 RESET H2S PPM
Display will scan through all active gas
sensor modules.
8 ENTER USE ARROWS/ENTER
MODULE # = 1
9 ENTER GAS TYPE : GGGG 10 ENTER # 1 GGGG IS: ON 11 ENTER LO ALM: NONLATCH
12 ENTER HI ALM: LATCH
13 ENTER HIGH ALARM = XX
14 ENTER LOW ALARM = XX
Use arrows to change.
Use arrows to change.
Use arrows to change each digit.
Use arrows to change each digit.
4.4 SENTRY TRAINING
After the controller is configured use this section in conjunction with the Sentry MENU, Table 4-2, and Sentry FLOWCHARTS, Figure 4-3 through Figure 4-7 to develop an understanding of keyboard operation.
To begin, press the RESET key until the lower display reads PRESS ENTER TO RESET SYSTEM then press ENTER. The system is now in "normal operate mode". The Sensor/Level display will cycle through each of the module numbers (CONTINUOUS SCAN). If any module is indicated as MODULE OFF use steps 9 through 15 of Section 4.3 to turn that module ON.
CONFIGURATION PROCEDURE
Page: 35
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
In NORMAL OPERATE mode Sentry scans all modules in sequence and displays their current readings. For any modules which are not correctly initiated and calibrated the status will be indicated. This scanning sequence is by module number by type. (Type 1 = H2S solid state, Type 2 = Combustible, Type 3 = Oxygen and Type 4 = all others)
For H2S, Combustible and Toxic modules the upper (Sensor/Level) display indicates the module number and the concentration. The lower display shows the gas tag and the engineering unit.
For Oxygen the upper display indicates the module number and its deficiency status. The lower display will read the oxygen concentration (e.g.: 20.9%).
Table 4-1 indicates display conditions for each module type.
Type Gas/Status Upper Lower
1 H2S Normal 00 H2S PPM% 2 Combustible Normal 00 COMB* %LEL 3 Oxygen Normal 00 OXY 20.9% 3 Oxygen Below Normal LO OXY <20.7% 3 Oxygen Above Normal HI OXY >21.1% 4 Toxic Normal 00 TOXIC* PPM
* “COMB” and “TOXIC” gas tags can be modified to any six
character tag using CHANGE GAS TAGS.
Table 4-1
Display Conditions
CONTINUOUS SCAN is Sentry's default display mode. To
"lock" the display onto one module wait till that module is displayed and press ENTER. While the "lock" is in effect the arrows can be used to change to other module numbers. The lock is indicated by "( )" around the top line of the lower display. To return to CONTINUOUS SCAN press ENTER.
Other user selectable display modes are described later in this manual.
Press the TEST button, read the display, then press the
TEST button again. Repeat until the system returns to the
continuous scan display. The two test conditions which are displayed are: <TEST SYSTEM> and <TEST ALARMS>. Neither of these tests were implemented because the
ENTER key was not pressed.
Model number, software level, and traceability descriptors.
MODEL 5000 VERS 6.3 8 CH 951234
Low Alarm Test with relays inactive.
RELAYS PASSIVE
TEST LOW ALARMS
High Alarm Test with relays inactive.
RELAYS PASSIVE
TEST HIGH ALARMS
Trouble Alarm Test with relays inactive.
RELAYS PASSIVE
TEST TROUBLE
ALARM
Full Display Test with all display segments and LED’s on.
X X X X X X X X X X X X X X X X X X X X X X
Warm-up Time-out.
SYSTEM WARM-UP
PLEASE WAIT 5:00
Return to normal scan.
COMB %LEL
MODULE TAG
Press the TEST key twice and the display will read TEST
ALARMS. Press the ENTER key and Sentry will execute LOW, HIGH & TROUBLE alarms and then return to the
operate mode. During this test the respective alarm relays will throw. The user code described later in this manual can be used to protect against unauthorized activation of the alarm relays.
Read the Sentry menu, Table 4-2 to find the TEST key. It should now be easy to understand that each step in the menu can be implemented by using the enter key or bypassed by continuing to press the activity key. This process is further described in the flowcharts. Figure 4-3 through Figure 4-7.
To implement the tests, press the TEST key once; display will read <TEST SYSTEM>. Press the ENTER key. Sentry will then step through the following series of displays:
CONFIGURATION PROCEDURE
Page: 36
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
4.5 SENTRY MENU
Table 4-2 describes the primary activities that can be accessed via the Sentry keyboard. Each activity which involves sub­menu selection is identified by an asterisk Menu selections which refer to printer are standard in eight channel systems, optional in two and four channel systems. The MODBUS option replaces Printer software.
Menu selections are further described in the following paragraphs. Press the respective key to select the sub-routines and press the ENTER key to access them. Follow the sequence in the flow charts.
MENU KEYS
TEST RESET TIME MODE
SYSTEM ALARMS HISTORY CALIBRATE/
ALARMS SYSTEM PRINT HISTORY SELECT SCAN HISTORY PRINT SYSTEM
REPORT
PRINT STATUS
REPORT
SET DATE &
TIME
CHANGE
CHECK CALIB
CHECK MODULE
CHECK PRINTER
Lowest concentration LC with date and time
Last Calibration with date and time.
Last logged error with date and time (if applicable).
At the end of the sequence the display will indicate the next module number and will continue to automatically increment as the data is recalled. If the data from a particular module is not required press the UP arrow to manually increment the number. As this recall sequence is a continuous "loop", press the RESET key at any time to return to the OPERATE MODE.
The history information may be collected on a continuous basis without clearing the data because only the last occurrence of each level will be retained. History data can be cleared by using the RESET HISTORY menu selection. Error messages are cleared by using the RESET SYSTEM menu selection.
4.5.2.2 PRINT HISTORY PRESS ENTER TO
PRINT HISTORY
When the printer option is installed in Sentry this menu choice can be used to print all the module history.
4.5.2.3 PRINT SYSTEM
Sentry Primary Menu Selection
Table 4-2
4.5.1 TEST KEY
The TEST KEY activities are described in the training exercise in Section 4.4.
4.5.2 TIME KEY
4.5.2.1 CHECK HISTORY PRESS ENTER TO
CHECK HISTORY
The first display in the CHECK HISTORY menu shows the system clock date and time D/T on the first line. The second line shows the date and time at which the history information was last cleared HR.
The second display indicates the last time the power was interrupted. PD is the Power Down time and PU is the Power Up time. After any interruption of power to the controller the POWER light will flash until the system is reset.
The third display begins the sequence in which the history for any module can be recalled. The display will indicate MODULE NUMBER 1. Successive presses of the ENTER key will result in display of:
PRESS ENTER TO
PRINT SYSTEM
When the printer option is installed in Sentry this menu choice can be used to print a complete system configuration report.
4.5.2.4 PRINT STATUS
PRESS ENTER TO
PRINT STATUS
When the printer option is installed in Sentry this menu choice can be used to print a status report which indicates the present status and concentration for each module.
Date and time of the last low alarm LA and high alarm
HA
Highest concentration HC with date and time
CONFIGURATION PROCEDURE
Page: 37
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
4.5.2.5 SET DATE/TIME
PRESS ENTER TO
SET DATE & TIME
Set the Sentry clock in the same manner as any digital clock is set. The format is MM/DD HH:MM, with the hours set in military time (24 hours). If a user code has been set-up it will be required prior to changing the clock. The cursor is initially under the month MM, set the correct month with the arrow and press ENTER to advance to the day DD. Repeat the process to set day, hour and minute. When the time is correct, press
RESET to exit.
4.5.3 RESET KEY
4.5.3.1 RESET ALARMS PRESS ENTER TO
RESET ALARMS
The RESET ALARMS activity will reset any latched alarm relay when the condition which caused the alarm has been corrected. If RESET ALARMS is selected before the correction has been made, the respective LED and relay will remain in the alarm condition.
4.5.3.2 RESET SYSTEM PRESS ENTER TO
RESET SYSTEM
4.5.3.5 EXTERNAL RESET KEY The external RESET key on NEMA units implements RESET
ALARMS and eliminates the need to open the enclosure for this
purpose.
4.5.4 MODE KEY - CALIB/CHANGE The first menu choice under the MODE key is
CALIB/CHANGE when the ENTER key is pressed the
"Calibrate or Change" light will turn on and the display will indicate ENTER TO CALIB (GAS TYPE) (SPAN VALUE). After initial system set-up the CALIBRATE OR CHANGE activity should be protected via the user access code described in Section 7.3.4. When the user code has been installed only authorized operators may access this activity.
4.5.4.1 CALIBRATE ENTER TO CALIB
COMB 50% LEL
The calibration activity is described in detail in the next chapter.
4.5.4.2 CHANGE CALIB PRESS ENTER TO
CHANGE CALIB
The change calibration activity is described in detail in the next chapter.
The RESET SYSTEM activity wi ll reset all trouble conditions. If the trouble still exists the condition will re-display immediately. RESET SYSTEM can be used at any time to return the system to normal operation and clear all error messages.
4.5.3.3 RESET HISTORY PRESS ENTER TO
RESET HISTORY
The RESET HISTORY activity clears all module history information which is normally accessed via the TIME key. The highest concentration is set to 00 and the lowest concentration is set to HI. The history reset date/time is set to the current system date/time. Sentry will immediately begin collecting new history information. When a user code has been installed the code will be required before the history can be reset.
4.5.3.4 OTHER USE OF RESET KEY
During CHANGE activity if the RESET key is pressed once the display will return to its normal scan operation but the CHANGE/CALIBRATE light will remain on. The MODE key can then be used to return to configuration activities without re-entering a user code. This action is helpful if module scan information is required during a configuration step.
4.5.4.3 CHANGE MODULE PRESS ENTER TO
CHANGE MODULE
Each module in the installation must be initialized via the change module activity. The CHANGE MODULE activity is detailed in step by step form in Section 4.3 steps 6 through 18. The CHANGE MODULE activity should also be used after any sensor or module has been replaced to insure that the correct alarm limits and factors have been established.
CONFIGURATION PROCEDURE
Page: 38
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
4.6 SET USER CODE PRESS ENTER TO
SET USER CODE
To avoid unauthorized access to the configuration activity the USER CODE should be set as soon as the Sentry has been put on line. User codes are described in Section 8.3. Special diagnostic routines, also accessible via the user code, are describe in the same section.
4.6.1.1 CHANGE PRINTER / MODBUS PRESS ENTER TO
CHANGE PRINTER
CHANGE MODBUS
The CHANGE PRINTER or CHANGE MODBUS sub menu will appear if printer or MODBUS software is installed on the Sentry. Printer and MODBUS software is described in Section
8.5.
4.6.1.2 CHANGE GAS TAG PRESS ENTER TO
CHANGE GAS TAG
The system default GAS TAG list contains eight common toxic gas names. (CO, H2S, CL2, SO2, NO2, HCL, H2, NH3). The gas tag names, and their corresponding engineering units can be changed. At the menu prompt press ENTER and the first gas tag will appear. Press ENTER to begin edit, or press ARROW to select a different gas tag.
Edit the tag by pressing the ARROW unit the correct character is selected, then ENTER to advance to the next character. The gas tag allows six characters, the engineering units allow four characters.
4.6.1.3 CHANGE MODULE TAG
PRESS ENTER TO:
CHANGE MOD
TAG
The system default MODULE TAGS are blank for all modules unless changes have been ordered through the enhancement package. Module tags can be changed or edited.. At the menu prompt press ENTER and the first module number will display. Press ENTER to begin edit, or press ARROW to select a different module number.
Edit the tag by pressing the ARROW unit the correct character is selected, then ENTER to advance to the next character. The module tag allows sixteen characters,. It is recommended that shorter tags be centered by leaving leading blank.
When the OPERATE MODE is selected by pressing ENTER the Change/Calibrate light turns off and Sentry returns to the pre-selected scanning mode.
4.6.2 MODE KEY - OTHER
If the first MODE key activity CALIB/CHANGE is not required the following menu selections can be accessed by successive presses of the MODE key:
4.6.2.1 SELECT SCAN PRESS ENTER TO
SELECT SCAN
Select the controller scan mode during normal operation. This selection only affects the display and does not change the alarm or relay activity. The scan mode can be selected by successive presses of the ARROW key. and implemented by implemented by pressing the ENTER key.
1. HIGHEST MODULE: Sentry will find the highest reading
module and will display only that module until another module exceeds the first level. Under certain conditions the display will cycle from one module to another in this mode, those conditions are:
More than one module at the same level.
More than one module type in use (when two types
are in use the highest of each type will display alternately.
All modules in alarm condition will display.
Any module which is uncalibrated, off, or in trouble.
2. CONTINUOUS: The display continuously cycles through
all modules. When two types of module are in use all "Type 1" (H2S) will be displayed, followed by all "Type 2" (CH4) etc..
3. SAFE SCAN: When all modules are below their respective
alarm level Sentry will display a "- -" on the upper display and CONDITION SAFE on the lower display. When any module(s) exceeds it's alarm level that module's information will display. Modules which are uncalibrated, off or in trouble will also display.
4.6.1.4 OPERATE MODE PRESS ENTER TO:
OPERATE MODE
CONFIGURATION PROCEDURE
Page: 39
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
4.6.2.2 CHECK CALIB
PRESS ENTER T O:
CHECK CALIB
The present calibration parameters can be check by successive presses of the ENTER key. These include the gas type, full scale, concentration of calibration gas, the number of days between calibrations and the status of global calibrate.
4.6.2.3 CHECK MODULE
PRESS ENTER TO:
CHECK MODULE
Any module number can be selected and configuration information for that module recalled. Select the module number using ARROWS, then step through the configuration information using the ENTER key.
MEASUREMENT OVERRANGE - When Combustible
concentration exceeds the 99% LEL range of the
instrument, the controller displays "HI".
4.6.2.4 CHECK PRINTER
NOTE
PRESS ENTER T O:
CHECK PRINTER
Press ENTER to review printer configuration.
CONFIGURATION PROCEDURE
Page: 40
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
SENTRY KEY BOARD
Ts = TEST R = RESET M = MODE T = TIME ^ = ARROWS E = ENTER
RESET KEY * GLOBAL CALIBRATION Reset Alarms R E Gas Type (Concentration) ^ E
Reset System R R E Enter to Span E Reset History R R R E Apply Zero Gas E
TIME KEY Enter to Span E Check History T E Apply Span Gas E
Printer History T T E Operate Mode (After timer) E Print System T T T E * LOCAL CALIBRATION
Print Status T T T T E Gas Type (Concentration) ^ E Set Date & Time T T T T T E Apply Zero & Span E
TEST KEY Operate Mode (After timer) E Test System Ts E * CHANGE MODULE Test Alarms Ts Ts E Module # ^ E
MODE KEY - PASSIVE Gas Type ^ E Change/Calib M E Module On/Off ^ E
Select Scan M M E Low Alarm Latch/Non ^ E Check Calib M M M E High Alarm Latch/Non ^ E Check Module M M M M E High Alarm Value ^ E ^ E ^ E
MODE KEY - ACTIVE Low Alarm Value ^ E ^ E ^ E Change/Calib M E Scaling Factors ^ E ^ E ^ E
Calibrate * E * SET USER CODE Change Calibrate * M E User Number ^ E
Change Module * M M E Entry Code ^E ^E ^E ^E Set User Code * M M M E * CHANGE PRINTER
Change Printer * M M M M E Printer On/Off ^ E Change Gas Tag M M M M M E Controller ID ^^ E Change Module Tag M M M M M M E Status Frequency ^^ E
* CHANGE CALIB Print History ^ E Gas Type ^^ E Gas Type ^^ E
Full Scale ^^ E ^^ E ^^ E Min. Conc. ^^ E Calib Concentration ^^ E ^^ E ^^ E Conc. Change ^^ E Calib Frequency ^^ E Gas Type ^ E Global Calib ^ E Exit R
Figure 4-2
Sentry Keyboard - Quick Help
CONFIGURATION PROCEDURE
Page: 41
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
OPERATE MODE
RESET
RESET ALARMS ENTER
RESET
RESET SYSTEM
RESET
RESET HISTORY
ENTER CODE?
ALARMS RESET
SYSTEM RESET OPERATE MODEENTER
Y
N
VALIDRESET
Y
RESET HISTORYACCESS DENIED
OPERATE MODE
N
RESET
COMPLETE
RETURN TO OPERATE MODE
Figure 4-3
Sentry Reset Key Flow Chart
CONFIGURATION PROCEDURE
Page: 42
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
OPERATE MODE
TEST
TEST SYSTEM ENTER
TEST
TEST ALARMS
TEST
ENTER
ACCESS DENIED
SYSTEM TEST
FUNCTIONS
CODE?
Y
N
VALID
Y
ACTIVE
LOW ALARM
ACTIVE
HIGH ALARM
ACTIVE
TROUBLE
SENTRY REV #
IDENTIFIERS
PASSIVE LOW
ALARM
PASSIVE HIGH
ALARM
PASSIVE
TROUBLE
FULL DISPLAY
TEST
RETURN TO OPERATE MODE
Figure 4-4
Sentry Test Key Flow Chart
CONFIGURATION PROCEDURE
Page: 43
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
OPERATE MODE
TIME
CHECK HISTORY ENTER
DATE & TIME
HISTORY RESET
TIME
POWER DOWN
POWER UP
HISTORY
REPORT
ENTER
ENTER
REPORT
TIME
SYSTEM REPORT
TIME
STATUS
REPORT
TIME
SET DATE &
TIME
TIME
REPORT
COMPLETE
ENTER
ENTER
ENTER CODE?
N
ACCESS
DENIED
REPORT
REPORT
COMPLETE
REPORT
REPORT
COMPLETE
VALID?
CHANGE
MM/DD HH/MM
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
Y
Y
N
END?
Y
TIME
CHANGE
MODULE NO.
LOW ALARM D/T
HIGH ALARM D/T
LOWEST CONC.
VALUE D/T
HIGHEST CONC.
VALUE D/T
LAST CALIB.
DATE/TIME
ERROR LOG
IF APPLICABLE
N
ENTER
RETURN TO OPERATE MODE
TIME
Figure 4-5
Sentry Time Key Flow Chart
CONFIGURATION PROCEDURE
Page: 44
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
OPERATE MODE
MODE
CALIB OR
CHANGE
MODE
SELECT SCAN
MODE
CHECK CALIB ENTER
MODE
CHECK MODULE ENTER
ENTER
ENTER
CODE
N
VALID
ENTERS CHANGE
MENU (MODE KEY
ACTIVE))
CONTINUOUS
SAFE SCAN
HIGHEST SENSOR
GAS, CONC, FULL SCALE FREQUENCY
GLOBAL?
MODULE #, ON/OFF
ALARMS LATCH?
ALARM VALUES
FACTORS
Y
N
ACCESS
DENIED
SELECT USING ARROWS
ENTER
ENTER
ENTER
MODE
CHECK PRINTER
MODE
ENTER
PRINTER ON/OFF
CONTROLLER ID
PRINT CONFIG.
RETURN TO OPERATE MODE
Figure 4-6
Sentry Mode Key (Passive) Flow Chart
CONFIGURATION PROCEDURE
Page: 45
ENTER
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
OPERATE MODE
MODE
CALIB OR
CHANGE
ENTER
CODE
VALID
N
READ
INSTRUCTIONS
ACCESS
DENIED
CALIBRATE ** ENTER
MODE
CHANGE
CALIBRATE
MODE
CHANGE
MODULE
Y
N
MODE
SET USER CODE
MODE
CHANGE
PRINT/ MODBUS
MODE
ENTER
ENTER
ENTER
ENTER
CALIBRATION
PROCEDURE
CHANGE CALIB
PROCEDURE
CALIBRATE **
MODULE CONFIG.
PROCEDURE
USER CODES AND
DIAGNOSTICS
EDIT PRINTER OR
MODBUS PROCEDURE
CHANGE
GAS TAG
MODE
CHANGE
MOD TAG
MODE
RETURN TO OPERATE MODE
ENTER
ENTER
Figure 4-7
Sentry Mode Key (Active) Flow Chart
CONFIGURATION PROCEDURE
Page: 46
EDIT GAS TAGS
PROCEDURE
EDIT MOD TAGS
PROCEDURE
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
5. CALIBRATION
5.1 SENTRY CALIBRATION - AN OVERVIEW
Calibration is a simple three step process:
1. Initiate calibration via the controller keyboard.
2. Apply zero gas (if required) and then span gas to the sensors.
3. Close the calibration via the controller keyboard.
Calibration parameters are configured via the CHANGE CALIB activity and are saved by Sentry for future calibrations.
During calibration Sentry "peak holds" the sensor signal output for zero and span gas and then uses those values to construct a curve for continuous reference during normal gas monitoring.
There are two alternative calibration methods, Global Calibration and Local Calibration.
5.1.1 GLOBAL CALIBRATION
When Global Calibration is selected, the Sentry controller collects zero and span value data from all sensor modules eligible for calibration based on a global keyboard command. It is not necessary to calibrate all the sensors, those which do not receive span gas will be rejected automatically.
The operator presses the ENTER key to initiate, and complete, collection of the zero value and then the span value. Calibration gas may be delivered to the sensor module in a variety of methods dependent upon the accessibility of the sensor.
The benefits of Global Calibration are:
Magnetic calibration head not required.
All "zero's" can be set at one time.
Global Calibration is particularly useful when:
The sensor is in a position which is difficult to access, because a calibration gas delivery tube can be installed to a more accessible location.
Individual modules can be calibrated while others
remain on line.
Time savings when sensors must be exposed to zero
air due to the environment.
Local Calibration is particularly useful when:
Plant operating procedures demand that some
modules remain on line while others are being calibrated.
5.2 CALIBRATION INITIALIZATION
5.2.1 MODULES
Before any module can be calibrated it must be initialized via the CHANGE MODULE activity. Initialization includes turning the module on, setting the alarm levels and setting the factor(s). This activity is described in step by step form in Section 4.3 steps 6 through 18. If a module is not initialized, an error prompt INITIALIZE MODULES FIRST will display when calibration is attempted.
NOTE
The following calibration instructions are applicable to
controllers with version 6.xx firmware. For earlier
version firmware (example 4.2) refer to the Instruction Manual furnished with that controller. To determine the firmware version installed in any Sentry controller, press
TEST, ENTER and observe the firmware version number
on the lower LCD screen.
NOTE
If any sensors are not previously calibrated use
Diagnostic Code 0020 or 0021 to force calibration prior
to performing the normal calibration procedure. See
Section 8.3.5.
The magnetic head is not available or the magnetic
switch in one of the sensors is not functioning.
5.1.2 LOCAL CALIBRATION
When Global Calibration is turned off, the Sentry controller collects zero and span value data from each sensor module eligible for calibration based on a local command at the module.
Calibration gas is delivered through a magnetic fitting which causes a switch in the sensor to command the controller to remember the module output. The procedure calls for the magnetic cap to be applied twice (zero first, span second) except that the magnet is applied only once for oxygen modules.
The benefits of Local Calibration are:
CALIBRATION
Page: 47
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
calibrated. Use the arrow keys to change the type.
er is configured for Global Calibration.
red for Local Calibration.
5.2.2 CALIBRATION PARAMETERS
Use the CHANGE CALIB menu to configure calibration parameters as follows: Calibration parameters remain in Sentry memory until changed by the operator, they do not require initiation at every calibration
Step Activity Display
1 Select CHANGE CALIB menu
PRESS ENTER TO
<CHANGE CALIB>
Use MODE key to select CHANGE CALIB
2 Select Gas Type
USE ARROWS/ENTER
GAS TYPE: COMB
Sentry displays the last gas type which was
Press ENTER to continue to the next parameter
3 Edit Full Scale
USE ARROWS/ENTER
FULL SCALE = 100
If the full scale value is set above 999, the display
will default percent full scale (%FS). (Alarm values must be set using PPM, not %FS.) Press
ENTER to continue to the next parameter.
4 Edit Span Gas Concentration
USE ARROWS/ENTER
CALIB CONC = 050
Use arrow keys to set the span gas concentration
to match the concentration of gas to which the sensors will be exposed. Press ENTER to continue to the next parameter
5 Edit Calibration Frequency
USE ARROW/ENTER
CAL FREQ =30 DAYS
Use the arrow keys to set the number of days till
the next calibration. Sentry will use this number to count down to the next calibration and display
"CALIBRATION OVERDUE". Press ENTER to
continue to the next parameter.
5.3 CALIBRATION PROCEDURE
5.3.1 CONTROLLER SET-UP
Use the CALIB menu to initiate the calibration session at the controller.
Step Activity Display
1 Select CALIBRATION activity
PRESS ENTER TO
<CHANGE CALIB>
From normal operate mode, press MODE and
ENTER to access the calibration activity.. (If a
user code has been set in the system it must be input to access the CALIB/CHANGE activity. See Section 8.3.3).
Successive Displays.
Successive Displays
Select Gas Type
CALIB/CHANGE
SELECTED
READ INSTRUCTION
MANUAL FIRST
ENTER TO CALIB
COMB 50% LEL
If the gas type is not correct press the ARROW
until the correct gas type and concentration is displayed. Use CHANGE CALIB menu selection to change span gas concentration. (See Section: 5.2 )
3A Initiate Calibration (Global)
ENTER TO ZERO
1 2 3 4 5 6 7 8
If the display is similar to this example, the
controll Continue to Section 5.3.1.1.
3B Initiate Calibration (Local)
APPLY 0 & 50% LEL
1 2 3 4 5 6 7 8
If the display is similar to this example, the
controller is configu Continue to Section 5.3.1.2.
The calibration overdue message is a notification only and does not cause the module to go out of service. The message can be suppressed by setting the calibration frequency to "00" days at the time of calibration
6 Select Calibration Method
Use the arrow keys to turn Global Calibration ON
for Global Calibration or OFF for Local Calibration.
In all calibration examples, the responses for
NOTE
combustible gas are used as an example. Other gases
will provide appropriate similar displays.)
USE ARROWS/ENTER
GLOBAL CAL ON
CALIBRATION
Page: 48
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
s.
5.3.1.1 GLOBAL CALIBRATION
Proceed with the following steps to perform Global Calibration.
Step Activity Display
1 Begin ZERO value read.
ENTER TO ZERO
1 2 3 4 5 6 7 8
Press ENTER to start the controller recording the
zero signal value for all modules of the selected gas type.
2 Complete ZERO value read.
APPLY ZERO GAS
ENTER WHEN DONE
The upper display will cycle through all the
applicable module numbers with "00" displayed as the level.
Example "1. 00", "2 00" etc.
If any module has not been previously
calibrated the "00" will be replaced by a "--".
If any sensor is not known to be in clean air at
this time, go to each such sensor which is to be calibrated and deliver clean air at 100 cc/min for three minutes using the apparatus in Section 5.3.2.
Wait until the display cycles through all module numbers.
Press ENTER to complete the zero read and the display will advance to the span prompt.
3 Begin SPAN value read
ENTER TO SPAN
1 2 3 4 5 6 7 8
Press ENTER to begin the span process. The top
display begins to cycle through all sensor module numbers which are configured for the selected calibration gas. Each module number will show a "period" immediately after the number and a numerical concentration display as in the following example. [1. 00] [2. 00].
Step Activity Display
application - no errors
PLEASE WAIT 3:00
When all modules have received calibration gas
press ENTER to indicate completion of the span process. If all modules have been successfully calibrated the controller will begin the three minute time delay before placing modules back on line
6 Error Conditions - Low
Sensitivity
LOW SENSITIVITY
1 2 3 4 5 6 7 8
If any modules were missed, or if any sensors
failed to respond correctly to the calibration gas the low sensitivity message will identify those sensor module numbers. If calibration of the module was attempted, note the number and plan corrective action as described in Section 7.
7 Error conditions - Not
Calibrated
NOT CALIBRATED
1 2 3 4 5 6 7 8
Press ENTER again. If all modules have been
successfully calibrated the controller will begin the three minute time delay before placing modules back on line. If any modules were displayed as LOW SENSITIVITY, they will be displayed again as NOT CALIBRATED. Press
ENTER to acknowledge
8 Return to Operate Mode
PRESS ENTER TO
OPERATE MODE
When the time delay is complete the display will
read PRESS ENTER TO OPERATE MODE Press
ENTER and the procedure is complete. Repeat the
process as necessary to recalibrate modules or to calibrate other gases.
Remove all calibration apparatus from sensors.
4 Apply SPAN gas.
Apply calibration gas to each sensor which is to
be calibrated using the apparatus in Section 5.3.2. Use magnetic or non magnetic calibration gas delivery fitting.
During the time calibration gas is being delivered the upper display on the controller will continue to cycle through all applicable module number The module responding to gas will generally show an increasing reading on each pass.
5 Complete SPAN gas
APPLY 50% LEL
ENTER WHEN DONE
CALIB COMPLETE
CALIBRATION
Page: 49
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
head into the sensor assembly.
5.3.1.2 LOCAL CALIBRATION
Proceed with the following steps to perform Local Calibration
Step Activity Display
1 Apply ZERO and SPAN gas to
each sensor.
APPLY 0 & 50% LEL
1 2 3 4 5 6 7 8
Apply zero and span calibration gas to each
sensor for which calibration is required. (Sensors which are not exposed will be reported as "Not Calibrated" and will retain their prior calibration status).
The calibration gas must be applied via the magnetic delivery head supplied with the Sentry system.
1. Remove the rainshield (where applicable).
2. Using the apparatus in Section XXX, thread the calibration At this time the controller top display will lock onto this module number.
If the ambient environment is one which has been
determined to be clean at the time of calibration, leave the magnetic head in place for 30 seconds and then remove. If the ambient environment is potentially contaminated, bleed clean air through the calibration head for two minutes at 100 cc/min and then remove the air and the calibration head.
3. Wait thirty seconds after the magnet is removed. During this period the controller will stop displaying the module number and will show dashes "- -" on the upper display.
Step Activity Display
from the display making it possible, at any time, to read which modules have not been exposed to calibration gas.
2 Gas application complete - no
errors
CALIB COMPLETE
PLEASE WAIT 3:00
When all modules have received calibration gas
press ENTER to indicate completion of the span process. (Required only if module numbers remain on the display)
Press ENTER again. (Required only if error messages appear.) If all modules have been successfully calibrated the controller will begin the three minute time delay before placing sensor modules back on line.
3 Error Conditions
- Low Sensitivity
LOW SENSITIVITY
1 2 3 4 5 6 7 8
If any sensors failed to respond correctly to the
calibration gas the low sensitivity message will identify those sensor module numbers. Note the number and plan corrective action as described in Section 7.
4 Error Conditions
- Not Calibrated
NOT CALIBRATED
1 2 3 4 5 6 7 8
Press ENTER again. Modules which were not
attempted, and any modules which were displayed as "LOW SENSITIVITY", will be displayed as "NOT CALIBRATED". Press ENTER to acknowledge Press ENTER to acknowledge
5 Return to Operate Mode
PRESS ENTER TO
OPERATE MODE
4. Thread the calibration head into the sensor assembly a second time. The controller will again lock onto the number for that module but will add a period immediately following the number.
Bleed calibration span gas through the
magnetic head at 100 cc (or as required for permeation tube calibrator). The controller will display the concentration which would be determined based on the prior calibration of the module
5. Remove the gas and the calibration head,
replace the rainshield and repeat the process for the next module. As each sensor is correctly exposed to calibration gas the
When the time delay is complete the display will
read PRESS ENTER TO OPERATE MODE Press
ENTER and the procedure is complete. Repeat the
process as necessary to recalibrate modules or to calibrate other gases.
Remove all calibration apparatus from sensors.
CALIBRATION
Page: 50
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
5.3.2 CALIBRATION GAS DELIVERY METHODS
Calibration gas is can be delivered to the sensors via the following delivery devices:
Model 5358-00: Calibration Adapter - used with portable calibrators. - See Figure 5-1
Model 5360-00: Calibration Gas Delivery fitting ­permanently installed fitting which allows tubing to be run to a convenient delivery location
5.3.3 SENSOR EXPOSURE TO GAS
Calibration gas must be delivered to the sensor using the flow rate and duration listed in Table 5-1
Model Gas Flow Period
5100-01
H2S
5100-02 Combustible 100 cc/min 3 minutes 5100-03 O2 200 cc/min 3 minutes 5100-04 CO 150 cc/min 3 minutes 5100-05 H2S 300 cc/min 3 minutes 5100-06 CL2 300 cc/min 3 minutes 5100-07 H2 300 cc/min 3 minutes 5100-10 SO2 300 cc/min 3 minutes 5100-12 NO2 300 cc/min 3 minutes 5100-13 CO 300 cc/min 3 minutes 5100-16 CO 300 cc/min 3 minutes 5100-19 NO 300 cc/min 3 minutes 5100-21 HCL 1,000 cc/min 10 minutes 5100-22 HCN 300 cc/min 3 minutes 5100-25 NH3 300 cc/min 3 minutes 5100-26 HF 300 cc/min 3 minutes 5100-27 ETO 1,000 cc/min 3 minutes
300 cc/min 3 minutes
Figure 5-1
Model 5358-00 Calibration Adapter
5.3.3.3 OXYGEN
The calibration procedure is different for Oxygen because zero gas is not required and the sensor will be exposed only to span gas. This is a single point calibration.
Table 5-1
Calibration Gas Flow Rates
5.3.3.1 HYDROGEN SULFIDE
Hydrogen Sulfide gas must be supplied from a permeation tube device or from Sierra Monitor Model 9200 series calibrator.
5.3.3.2 COMBUSTIBLE
For compliance with factory Mutual (FMRC) Approval, the Sierra Monitor Model 1200-26 is the only Approved calibration gas delivery device. Apply 50% LEL methane in air or the calibration concentration of the gas to be monitored at 100 cc/min using Model 5358-00 or 5358-01 Calibration Adapter and Model 5360-00 Gas Delivery Fitting. For calibration with a standard gas and cross reference to a secondary gas, see Appendix D.
NOTE
Cross reference factors are not FMRC approved.
CALIBRATION
Either: Deliver calibration gas (clean air - 20.9%
Oxygen through the magnetic head at 100 cc/min for one minute and then remove the air and the calibration head.
Or: If the local air is known to be clean leave
the magnetic head in place for one minute and then remove.
5.3.3.4 TOXIC GAS
Toxic Gas for may be delivered from Sierra Monitor Model 9200 series calibrator or from appropriate permeation devices.
Page: 51
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
6. MAINTENANCE
6.1 MAINTENANCE REQUIREMENTS
The following are the manufacturer’s recommendations for periodic maintenance of the Sentry system:
1 CALIBRATION: All sensors should be calibrated at a
minimum of every 90 days.
FMRC approved combustible gas sensors are required to
be calibrated every 90 days.
NOTE
2 BATTERY REPLACEMENT: The lithium battery for
memory retention should be replaced every two years. (See Service)
3 DUST AND DIRT CONTROL: When calibration is
performed the controller and the modules should be checked visually to determine if dust or dirt build up needs to be removed. This cleaning should be done with dry instruments such as compressed air, cloth wipes or whisk broom.
4 WIRING OR CABLE CONDITIONS: Any wiring or
cables which are not conduited should be checked once a year for damage to insulation or corrosion of splice or terminal points.
5 LUBRICATION: Lubricate metal to metal parts
(module lid) periodically.
6 INSPECTION: Inspect modules, periodically, for
moisture or water accumulation.
MAINTENANCE
Page: 53
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7. SERVICE
7.1 OVERVIEW
7.1.1 GENERAL
This section provides service information for Sentry systems which have software version 6.0 and above The section is intended for use by a qualified field technician. Sierra Monitor sales and technical staff are available to assist by telephone at (408) 262-6611, during normal west coast working hours.
7.1.2 INSTALLATION INSPECTION
Prior to system start-up or trouble shooting the entire system should be visually inspected. The following are guidelines for that inspection:
7.1.2.1 CONTROLLER INSTALLATION
Controller installed in conformance to
instruction manual recommendations.
AC power is correctly grounded.
Hot AC and relay connections have safety
covers installed.
RS232C cable connection to printer correctly
seated and retaining screws tight.
7.1.2.2 CABLING INSTALLATION
All splices are soldered or via terminal block.
Cabling is away from sources of electrical noise
where possible.
Terminals P, S, G (or 1,2,3) on channel
connector match terminals P, S, G on module. Trace color codes to confirm correct wiring.
electrical conduits and provide moisture traps and drains to avoid water damage
Rainshields installed where applicable.
7.1.2.5 STANDARD VOLTAGES
AC Voltage on AC terminal on connector panel
of controller should be 120 VAC (or 220 VAC option) +10%, -15%, 50-60 Hz.
DC Voltage on DC terminal on connector panel
(if used) should be (12 VDC Nominal), 10 to 29 VDC.
Channel Voltage (power to ground) should be
approximately 20 VDC on open channel and approx. 18 VDC on used channel.
Signal Oscillation on an “in use” channel (signal
to ground) can usually be read with a voltmeter at approx. 0 - 6 VDC.
7.1.3 DATA COLLECTION
Sentry can provide a large amount of data which will be helpful during problem solving. If the system has a printer use the TIME KEY to select HISTORY REPORT and press ENTER. When the report is complete SYSTEM
REPORT will display on the controller, press ENTER to
print. Diagnostic reporting capability is discussed in Section 7.3.5.
If a printer is not in use, key information can be read and manually recorded by selection of the HISTORY (TIME
KEY), CHECK MODULE and CHECK SYSTEM (MODE KEY)
menu choices
7.1.4 INSPECTION AND TROUBLESHOOTING GUIDE
7.1.2.3 SENSOR MODULE INSTALLATION
Module installation in conformance with
instruction manual recommendations.
Modules accessible for calibration.
Terminations to electronics card clean and
correct.
7.1.2.4 MOISTURE TRAPS AND RAINSHIELDS
Conduit seals and drains installed to avoid
moisture build up in electronics enclosure. Water accumulation in sensor module enclosures is a major cause of damage and system failures - take precautions to seal
The inspection and troubleshooting guide can be used to step through the system start-up and to determine the corrective action if a fault occurs.
Instructions:
1. Take the action described in the "Operator Action" column.
2. If the “CORRECT” result occurs, proceed to the next Operator Action.
3. If the “Incorrect” result occurs find the probable cause and corrective action in the “Reason/ Correction” column.
SERVICE
Page: 55
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
INSPECTION GUIDE
OPERATOR ACTION
TURN SYSTEM ON
RESET/RESET/ENTER
MODE/ENTER
RESET
RESULT CORRECT, Incorrect
POWER LIGHT FLASHING Power light solid Power light off
POWER LIGHT SOLID Power light flashing & Top Display = “----" Top display = E1 Top display = E2 Top display blank
BOTTOM DISPLAY = "SYSTEM WARM-UP "PLEASE WAIT MM:SS" Random Blank CLOCK COUNTS DOWN TO ZERO No count down ALARM LED'S BLANK Random LED's ON or flashing CALIB LIGHT OFF Calib light on
CALIB LIGHT ON Calib light off
UPPER DISPLAY CYCLES ALL MODULE NUMBERS Lower display = "No modules installed
Not all installed module #'s displayed
Lower display shows "Module numbers must be 1-2” or “1-4"
TROUBLE LIGHT OFF Trouble light on
Reason/Correction
Turn off & restart Check fuse & line voltage Check power supply 5v fuse
System is re-setting, check for channel cable short
EPROM error (fatal) RAM error (fatal) Check +15 & -12V on power supply Check display ribbon cable, cold start Check line: must be >90 VAC, Check EPROM
Check ribbon cable to display Check -12v on power supply
Check lithium battery for 2.5V, Check U15
Reset alarms, If not fixed cold start.
Reset system
Procedure error: retry
Check module channel wiring Check connector panel seating to controller Check +20V between channel pins 1 and 3 Check +15 & -12V supply Check for oscillation on channel pin 2 Correct above items, replace analog multiplexor Check respective cabling including cross-wiring, opens, shorts, leakage Check cable length & size versus instruction manual Check # of modules on cable run (Max. 4) Check modules for correct digital address Test modules by swapping working for non-working Test modules on short cables at controller to eliminate cable doubts. Modules will only be recognized when controller is in Change/Calib mode
Controller has 2 or 4 channel software, but module numbers have been set >2 or >4
Read lower display for error message and check upper display for module # (See specific error message instructions in this manual)
RESET/RESET/ENTER
TOP DISPLAY CYCLES ALL MODULES WITH "00" CONCENTRATION Some/all modules indicate "no factors" Some/all modules indicate "uncalibrated Lower display reads: "Replace Battery" Lower display reads: "Calib Switch On" Lower display reads: "Diagnostic Scan" Lower display reads: "Fast Error Check" Lower display reads: "Module Off" Lower display reads: "Module Warm-up"
Input factors via Change Module and calibrate Calibrate Check/Replace lithium battery Magnetic switch in sensor head is on Exit Scan with code "0009 Exit Scan with code "0009 Turn module "on" in "Change Module" mode Wait for clock to zero
SERVICE
Page: 56
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
TROUBLE SHOOTING GUIDE
Symptom
CONTROLLER Top Display: wrong characters displaying 8888 or Blank Bottom Display blank
Diagnostic voltages displayed are more than 10% different from manual Keyboard: Wrong action based on key press Alarms intermittent or false
AC fuse blows
Modules not recognized
MODULES Module not recognized
Module recognized as wrong type
Sensor failure
Multiplexing problem
PRINTER Not Printing
Printing garbage
MODBUS Not Communicating
Cause Fix
PROM failure; microprocessor failure; other major component failure; AC brown out
-12 VDC failure on power supply; Component failure Respective module PCB (digital board) bad
Component failure
+15 OR -12 VDC failure or out of adjustment Wiring error or Power Supply or Transformer failure Component failure; wiring defect; power to modules may be low
Component failure; wrong address; reversed wiring
Component failure; controller RAM initialized incorrectly; wire gauge too small
Sensor Module electronics failure Signal voltage misadjusted; environmental deterioration DC ground wire not connected at one module; Wire AWG is wrong; wire connections faulty
AC power glitch
DIP switches set wrong Corrupted printer buffer Failed component in Sentry controller Ribbon cable damaged Paper out light is on
Paper misaligned
Incorrect Configuration
Hardware Problem
Replace components or send to SMC; Power up and down for brown-outs Replace power supply board or factory repair Replace module electronics or factory repair Factory repair
Replace power supply board or factory repair Check wiring; replace power supply and/or transformer; or factory repair Check channel wiring for breaks/opens; move to another channel; multiplexors may be bad on main PCB; replace multiplexors; clear RAM
Set address correctly; check wiring; check all voltages including sensor; turn on “calibrate or change” light by pressing MODE, ENTER, RESET factory repair Check wiring against manual spec; clear RAM for 1 address; clear system RAM factory repair Replace module electronics assembly Adjust per service instructions, replace sensor if necessary Test individual modules on single channel; check all DC ground connections; verify AWG; solder all splices; replace module
Power down and power up complete system at one time Set printer for 1200 baud Clear printer buffer (Diagnostic 0006) Replace printer drivers Check/replace printer cable Replace paper or fix paper to route past paper sensor Fix alignment
Use “Change MODBUS” in Mode menu to turn MODBUS on and set controller address and baud rate to match host. Check for correct interface cable, RS485 configuration and host computer port configuration.
SERVICE
Page: 57
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.2 CONTROLLER
7.2.1 MECHANICAL/FUNCTIONAL DESCRIPTION
The controller consists of four sub assemblies. Figure 7-1.
7.2.1.1 CONNECTOR PANEL
The Back Panel contains all the connectors for providing system power, powering and communicating with the modules, operating alarm devices and communicating with a printer. The panel also contains the AC fuse.
The connector panel contains, internally, an edge card connector which connects the main control card.
To remove the panel from the controller unscrew the four corner screws and gently slide the edge connector apart. This procedure allows the controller to be removed for repair without disconnecting all the wiring from the connector panel.
Except for the AC fuse there are no field repairable components on the connector panel.
7.2.1.2 POWER SUPPLY ASSEMBLY:
The power supply assembly includes the transformer which is installed on the bottom plate of the controller and the power supply board which is "piggy backed" to the main control board. To gain access to the power supply board remove the six screws which hold the perforated side panel on the left side of the controller and slide the panel off toward the connector panel.
The power supply board provides various DC voltages for system operation and is described in Section 7.2.2
To remove the power supply board unplug the large in­line harness connector, remove the four nuts from the corners of the board, and lift the board off the multi-pin connectors which interface the power supply to the main control board.
7.2.1.3 MAIN CONTROL BOARD
The main control board assembly is a printed circuit board which connects to the connector panel and the power supply as described above and to the front panel via a ribbon cable. To access the component side of the board remove the perforated side panel on the right side of the controller.
Field repairs to the main control board involve socketed component replacement only. Board removal is not required for these repairs.
7.2.1.4 FRONT PANEL
he front panel assembly contains the membrane panel, the two displays and the indicator lights (LED's). A ribbon cable connection to the main control card is the only electrical connection to the panel.
Access to the lower display angle adjustment is by removal of the left side panel.
7.2.2 ELECTRICAL DESCRIPTION
7.2.2.1 POWER SUPPLY DESCRIPTION
The controller power supply is configured to accept 120 VAC and/or 12 VDC. See specifications Section 8.1 for specific requirements.
The controller can also accept +10 to +29 VDC. If both AC and DC supplies are connected and the AC drops below 90 VAC the system will operate on DC until that supply drops below 10.5 VDC. At that time the controller will reset.
The power supply provides a regulated +24 to +26 volts for the channel regulators, +5 volts for the main control card and front panel board, and +15 & -12 volts for the main control card. A 1 Amp (120 VAC) or .5 Amp (220 VAC) slo-blow fuse protects the AC input power. Check the fuse on the connector panel if the power light is off. ­Figure 3-9
The power supply is protected by an over-voltage transient protector (MOV), an EMI/RFI line filter and Zener transient protectors.
The following are symptoms of power supply failure. Figure 7-3.
1. No +24 volts: no modules recognized by the system. Action: check the fuse on the connector panel, check that
the 9 pin in-line connector is fully seated. If the +24 volts is still absent, replace the power supply board. (The failed board can be factory repaired.)
2. No +5 volts: no lights or displays on the front panel. Action: check fuse F1 on power supply board.
3. No +15 volts: no modules recognized by the system & no bottom display.
Action: replace power supply board.
4. No -12 volts: no lower display and/or no modules recognized, no printing and no alarm functions.
Action: replace power supply board.
5. No +12 volts with battery back-up: no lights on front panel.
SERVICE
Page: 58
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Action: check fuse F2 on power supply board. If power
supply jumpers have been cut, cold start requires 110 VAC.
7.2.2.2 POWER SUPPLY ADJUSTMENTS
The +24 volts can be measured at TP1 or TP2 (Test Point 1 or 2) with respect to ground (GT1). Figure 7-3. If there is no +24 volts and replace fuse F1
The +5 volts can be measured at TP4 If there is no +5 volts check and replace fuse F3.
The +15 volts can be measured at TP5. The -12 volts can be measured at TP7
7.2.2.3 LITHIUM BATTERY
The lithium battery which is located on the main control board, Figure 7-2, looks like a large coin and is mounted in a round battery holder with a metal retaining clip. Typical battery voltage should be 3.0 volts and can be measured by connecting the negative lead of the meter to Ground Test 1 (GT1) on the main control board, and the positive lead to the shoulder of the battery holder arm. The voltage should be greater than +2.2 volts or the battery should be replaced. To remove the battery (use Panasonic BR2325 or equal) use a nonmetallic probe to carefully lift the metal clip and push the battery to one side.
It is advisable to increase the tension on both the positive and negative contacts before installing the new battery. To do this slide an insulator between the contacts and use a small screwdriver to lift the lower contact up and push the upper contact down. Install the new battery with the positive terminal ("+") facing up. The insulator is important to avoid shorting the two terminals as this will erase the data accumulated in RAM.
Battery replacement is necessary when the REPLACE BATTERY message appears on the lower display during normal operation. The controller memory of factors, calibration and history will be retained for a period of several minutes during battery replacement.
Always remove power to the controller before
removing or installing EPROM’S.
Before installing check each EPROM for bent
pins.
Insure that pin orientation is correct, pin 1 toward
center of controller.
After installation clear RAM using diagnostic
code 0099. (See Section 8.3.5)
If there is a problem with the EPROM, the display
will read an "E-01" error. This is usually a result of an improperly installed EPROM.
7.2.2.5 CHANNEL VOLTAGE
There are eight regulated power supplies on the main control board. The regulators supply power to the module channels. The voltages which can be measured between the power and ground connectors of any channel should be between +20.5 and +19.0 volts with no sensor modules connected to any channel. If the channel voltage is greater than +21 volts that channel should not be used.
7.2.2.6 ALPHANUMERIC DISPLAY ANGLE ADJUSTMENT
The alphanumeric display is the lower display on the front panel. The viewing angle can be altered via the display angle adjustment potentiometer located on the side of the display panel. To access the adjustment slide the left panel back and use a small screwdriver on the only visible potentiometer on the front panel assembly.
7.2.2.7 RELAY REPLACEMENT
The three socketed DPDT 3 Amp dry contact relays are on the main control board Figure 7-2. The relay function can be tested using the TEST ALARMS function of the controller which causes each relay to throw during the time the respective display is indicated on the front panel.
It is important that replacement relays be installed in the same orientation; pin 1 of the relay must line up with pin 1 of the socket.
7.2.2.4 EPROM'S
There is one EPROM located on the main control board. Figure 7-2. The EPROM can be identified by the white label on the window. The EPROM stores all the software for Sentry. The EPROM needs replacement when the user wishes to upgrade to additional options or when a factory upgrade is issued for the system. The following precautions must be exercised when replacing the EPROM:
EPROM’S are sensitive to static discharge and
extreme care must be used in their handling. The technician should be grounded before picking up or installing EPROM’S.
SERVICE
Page: 59
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 7-1
Controller Exploded View
SERVICE
Page: 60
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 7-2
Control Board Component Locator
SERVICE
Page: 61
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Figure 7-3
Power Supply Component Locator
SERVICE
Page: 62
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.3 COMMUNICATIONS
The Sentry controller scans each channel in turn taking less than one second to scan all channels. At each channel:
1. A "reset" signal is sent out to clear all module communications.
2. An address (which is a module number) is sent out and the controller waits for a response. The response is a digital frequency which is proportional to the first of eight parameters which are interrogated by the controller.
3. Because the controller received an answer and knows that the particular module is on that channel it continues to interrogate that module to retrieve the remaining seven parameters before moving to the next module number.
The eight (total) signals are:
Value of Ground.
Value of sensor signal (relates to gas
concentration).
Heater voltage (Type 1 Module) or
Bridge Voltage (Type 2 Module).
Heater current (Type 1 Module) or
Bridge Current (Type 2 Module).
Sensor type (Type 1 through 4
Modules).
Calibration switch condition on/off.
Module voltage (tests line drop from
controller to module).
Reference voltage (used together
with ground to ratiometrically compensate for any temperature drift in module components)
The controller interprets the information received during the polling and takes actions as necessary. (Any deviation from normal is rapidly validated to avoid errors due to electrical noise.) The information, combined with continual system diagnostics allows the controller to accurately determine abnormal conditions. Table 7-1 provides a categorized listing of Sentry messages.
SYSTEM ERRORS MODULE ERRORS WARNING/STATUS MESSAGES
E-01 (ROM Check Failed) DISCONNECTED NO MODULE E-02 (RAM Check Failed) CHECK POWER ADJ MODULE OFF TIMER FAILURE MODULE VOLTAGE LOW WARM-UP WAIT - 00:00 CLOCK FAILURE SENSOR FAILURE FACTOR MISSING DUPLICATE MODULE UNCALIBRATED CHK BRIDGE VOLTAGE REPLACE SENSOR TYPE ERROR CALIBRATION OVERDUE REPLACE BATTERY CALIBRATION SWITCH ON DIAGNOSTIC SCAN FAST ERROR CHECK LOW SENSITIVITY NOT CALIBRATED CALIBRATION ABORTED
Table 7-1
Sentry Error and Diagnostic Messages
SERVICE
Page: 63
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.3.2 WARNING AND ERROR MESSAGES
7.3.2.1 SYSTEM ERRORS
If Sentry cannot operate the basic computer functions one of the System Errors listed in Table 7-1 will display.
These failures indicate internal controller problems which are most likely to require board level repairs by the factory.
7.3.2.2 TROUBLE CONDITIONS
The following "Trouble Conditions" require operator corrective action.
DISCONNECTED: The controller is not able to
communicate with the module
CHECK POWER ADJ
A hydrogen sulfide sensor heater is not functioning. Current drops to zero or voltage increases to maximum.
MODULE VOLT LOW
The module voltage is too low (<11.5V). This indicates there is an excessive drop in the line from the controller to the module.
SENSOR FAILURE
Sensor signal voltage is out of limits.
DUPLICATE MODULE
A response to one address number has been received on two channels.
CHK BRIDGE VOLTAGE
The bridge voltage on a combustible sensor is out of limits.
TYPE ERROR
The module which responded is a different type than previous response.
When any of these conditions are identified the controller:
activates the trouble relay and trouble light
displays an "E --” beside the corresponding
module number (i.e.: "1E --")
describes the error condition on the lower
display, and
logs the error in history memory for later recall
via the keyboard or printer.
Trouble conditions logged into memory are erased by the
Reset System command. All other erasable History is
cleared by the Reset History command.
NOTE
All other modules on the channel and modules on other channels remain in full operation and continue to be scanned by the controller. If the problem is corrected, the trouble light and relay will turn off and the module will be brought back on line after a warm-up period.
7.3.2.3 WARNING AND STATUS
The warning and status messages are displayed when valid and do not log to history.
7.3.3 WARM-UP TIMERS
Three “timers” are used by Sentry to delay bringing the system or parts of the system on-line during a stabilization period. These timers can be cleared via the diagnostic code “0000” described in Appendix C.
SYSTEM WARM-UP: After any loss of power (AC
& DC) Sentry will count down a five minute system warm-up. During this period the modules will be under power but will not be displayed, nor will their output be used to determine a gas concentration.
MODULE WARM-UP: Any module which has
been disconnected, or has just been “recognized” by the controller will be held in a module warm-up delay for a period of five minutes before being displayed as “on line”.
CALIBRATION DELAY: Immediately after
calibration each module is held in a calibration delay which is similar to the module warm-up. Although the controller display indicates
CALIBRATION COMPLETE/PLEASE WAIT if the
system is reset, each applicable module will be indicated as MODULE WARM-UP.
7.3.4 ACCESS CODES
Sentry software allows users to establish user codes which restrict access by unauthorized users to critical parameters or functions. (See Section 8.3).
7.3.5 DIAGNOSTIC CODES
Diagnostic codes allow the technician to use the system software to collect diagnostic data for use in system check-out. Diagnostic code assignment is described in Section 8.3.5.
SERVICE
Page: 64
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.3.6 DIAGNOSTIC REPORT
A Diagnostic report can be printed using diagnostic codes 0008 or 0010. Figure 7-4 is a typical report..
ID:A 11/20 15:16 S1= +0.376 BV= +2.021 BI= 0.323 SP= 0653 ST= +0.284 MV= +19.0 CS= +0.000 S2= +1.20 HV= +0.920 HI= +0.975 SP= 400 ST= +0.009 MV= +19.4 CS= +0.000
Figure 7-4
Typical Diagnostic Report
Table 7-2 is a description of the information contained in a typical diagnostic report
Report Description
ID:A Controller Identification 11/20 15:16 Time report was generated S1 +0.376 Data that follows is for Module 1
Sensor Signal is +0.376 VDC BV +2.021 Bridge Voltage 2.021 VDC BI +0.322 Bridge Current 323 mA SP 0653 Sensor Power 653 mW ST +0.284 Sensor Type
(Where: .2 -.3 VDC: Combustible) MV +19.0 Module Voltage = 19 VDC CS +0.000 Calibration Switch
Off 0.000, On = 2.5 VDC S2 +1.20 Data that follows is for Module
Sensor Signal is + 1.20 VDC HV +0.920 Heater Voltage Signal HI +0.975 Heater Current Signal SP 400 Sensor Power 400 mW ST +0.009 Module Type
(Where: .11-.1 VDC: H2S)
Table 7-2
Diagnostic Report Description
SERVICE
Page: 65
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.4 HYDROGEN SULFIDE MODULE (5100-01)
7.4.1 DESCRIPTION
The Hydrogen Sulfide Sensor Module includes the sensor and electronic assembly installed in an explosion proof housing. The sensor screws into one hub of the enclosure and plugs into the bottom electronics card via a six pin connector. Cabling to the controller connects to a three pin spring loaded terminal strip.
When a sensor is changed it is important that the factors for the new sensor are keyed into the controller and that a 24 hour stabilization period elapses prior to voltage adjustments and calibration. The three factors, each three digits are written on the sensor connector label.
7.4.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
Controller displays the error messages:
CHECK POWER ADJ SENSOR FAILURE LOW SENSITIVITY
Cover Plate - Hydrogen Sulfide Sensor Module
False readings or alarms are received due
to sensor inaccuracy.
Figure 7-5
Warning: During sensor adjustments the concentration
reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the CHANGE MODULE mode.
Note:
Although all the necessary data can be collected with a
voltmeter at the sensor module, some helpful
information can be displayed or printed. See diagnostic
codes 0004 and 0008, Appendix C.
7.4.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-5 to locate test points during the following procedures.
7.4.3.1 POWER ADJUSTMENT
Comparing to the GND (ground) test point measure the
HEATER VOL (heater voltage) and the HEATER CUR
(heater current) values in VDC. Calculate the power by the formula: (HEATER CUR - HEATER VOL) * HEATER
VOL / 5.1. The correct value is 400Mw +/- 5 Mw. (Note
that this calculation is performed by the controller and displayed using diagnostic code 0004.) See Table 7-4 for corresponding voltage and current settings.
Adjust the heater power using HEATER ADJ potentiometer, turn clockwise to decrease, counter-clockwise to increase the power. Make the adjustments 1/4 turn at a time and wait for the values to stabilize before making successive adjustments.
7.4.3.2 MODULE ADJUSTMENT
Compare ground to SIGNAL OUT to read the module voltage. The beginning (no gas) value must be above 1.2 VDC and can be up to 7.5 VDC. If the no gas voltage is lower than 1.2 VDC adjust using RANGE ADJ potentiometer.
SERVICE
Page: 66
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
To adjust the sensitivity apply 20 ppm hydrogen sulfide for five minutes for full stabilization. (Check that the voltage drops by at least .3 volts during this time.) Adjust the signal out value to .6 VDC using the range adjust potentiometer. Remove gas and verify that the voltage climbs to above 1.0 VDC in five minutes.
7.4.4 SENSOR REPLACEMENT
If either of the above adjustments cannot be completed successfully the sensor and/or electronics will require replacement. To check the sensor unplug it from the electronics and remove from the housing so that continuity and resistance tests can be made. Table 7-3 provides the pin out for the sensor assembly.
PIN FUNCTION WIRE COLOR
1 SENSOR FILM GREY 2 HEATER RED 3 HEATER RED 4 SENSOR FILM GREY 5 CALIB. SW. GREEN 6 CALIB. SW. GREEN
Table 7-3
Hydrogen Sulfide Sensor
Wiring Pin-Out
1. Sensor Film resistance (grey wires) should be above 10K ohms.
3. Calibration switch (green wires) should be open in normal operation and should close when the calibration magnet is applied.
If the sensor fails any of these tests it should be replaced. If the sensor passes these tests the electronics are suspect and BOTH the sensor and electronics should be replaced. (The failed components should be returned to the factory for evaluation).
When a new sensor is installed the following actions should be taken:
1. Input new factors into controller. The factors are written onto the sensor connector label. (Three numbers: ###-###-###)
2. Make a preliminary power adjustment to insure heater is below 400 mW.
3. Force calibrate the sensor module.
4. Wait 24 hours for stabilization of the sensor film.
5. Make the power and sensitivity adjustments as described above.
6. Calibrate the sensor.
7.4.4.1 H2S MODULE HEATER VOLTAGES
Table 7-4 may be used during adjustment of Hydrogen Sulfide sensor heater voltages. Make small adjustments to the Heater Adjust potentiometer until the corresponding Heater Voltage and Heater Current readings are obtained. Both values are read as voltages.
2. Heater resistance (red wires) should be between 20 and 35 ohms.
SERVICE
Page: 67
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Heater Heater Heater Heater Heater Heater Heater Heater
Voltage Current Voltage Current Voltage Current Voltage Current
2.50 3.32. 2.90 3.60 3.30 3.92 3.70 4.25
2.51 3.32 2.91 3.61 3.31 3.93 3.71 4.26
2.52 3.33 2.92 3.62 3.32 3.93 3.72 4.27
2.53 3.34 2.93 3.63 3.33 3.94 3.73 4.28
2.54 3.34 2.94 3.63 3.34 3.95 3.74 4.29
2.55 3.35 2.95 3.64 3.35 3.96 3.75 4.29
2.56 3.36 2.96 3.65 3.36 3.97 3.76 4.30
2.57 3.36 2.97 3.66 3.37 3.98 3.77 4.31
2.58 3.37 2.98 3.66 3.38 3.98 3.78 4.32
2.59 3.38 2.99 3.67 3.39 3.99 3.79 4.33
2.60 3.38 3.00 3.68 3.40 4.00 3.80 4.34
2.61 3.39 3.01 3.69 3.41 4.01 3.81 4.35
2.62 3.40 3.02 3.70 3.42 4.02 3.82 4.35
2.63 3.41 3.03 3.70 3.43 4.03 3.83 4.36
2.64 3.41 3.04 3.71 3.44 4.04 3.84 4.37
2.65 3.42 3.05 3.72 3.45 4.05 3.85 4.38
2.66 3.43 3.06 3.73 3.46 4.06 3.86 4.39
2.67 3.43 3.07 3.73 3.47 4.07 3.87 4.40
2.68 3.44 3.08 3.74 3.48 4.07 3.88 4.41
2.69 3.45 3.09 3.75 3.49 4.08 3.89 4.41
2.70 3.46 3.10 3.76 3.50 4.08 3.90 4.42
2.71 3.46 3.11 3.77 3.51 4.09 3.91 4.43
2.72 3.47 3.12 3.77 3.52 4.10 3.92 4.44
2.73 3.48 3.13 3.78 3.53 4.11 3.93 4.45
2.74 3.48 3.14 3.79 3.54 4.12 3.94 4.46
2.75 3.49 3.15 3.80 3.55 4.12 3.95 4.47
2.76 3.50 3.16 3.81 3.56 4.13 3.96 4.48
2.77 3.51 3.17 3.81 3.57 4.14 3.97 4.48
2.78 3.51 3.18 3.82 3.58 4.15 3.98 4.49
2.79 3.52 3.19 3.83 3.59 4.16 3.99 4.50
2.80 3.53 3.20 3.84 3.60 4.17 4.00 4.51
2.81 3.54 3.21 3.85 3.61 4.18 4.01 4.52
2.82 3.54 3.22 3.85 3.62 4.18 4.02 4.53
2.83 3.55 3.23 3.86 3.63 4.19 4.03 4.54
2.84 3.56 3.24 3.87 3.64 4.20 4.04 4.54
2.85 3.57 3.25 3.88 3.65 4.21 4.05 4.55
2.86 3.57 3.26 3.89 3.66 4.22 4.06 4.56
2.87 3.58 3.27 3.89 3.67 4.23 4.07 4.57
2.88 3.59 3.28 3.90 3.68 4.23 4.08 4.58
2.89 3.60 3.29 3.91 3.69 4.24 4.09 4.59
Table 7-4
Heater Voltage and Current Settings
SERVICE
Page: 68
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.5 COMBUSTIBLE GAS SENSOR MODULE (5100-02)
7.5.1 DESCRIPTION
The Combustible Gas Module includes the sensor and electronic assembly installed in an explosion proof housing. The sensor screws into one hub of the enclosure and plugs into the bottom electronics card via a six pin connector. Cabling to the controller connects to a three pin spring loaded terminal strip.
7.5.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error
messages:
CHK BRIDGE VOLT
SENSOR FAILURE
LOW SENSITIVITY
False readings or alarms are received
due to sensor inaccuracy.
Warning: : During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the CHANGE MODULE mode.
NOTE
Although all the necessary data can be collected with a
voltmeter at the sensor module, some helpful
information can be displayed or printed. See diagnostic
codes 0004 and 0008 in Appendix C.
7.5.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-6 to locate test points during the following procedures:
Caution: The area must be free of flammable vapors or gases during any adjustments or maintenance procedures.
7.5.3.1 BRIDGE VOLTAGE ADJUSTMENT
Confirm that no combustible gas is present and remove sensor module cover.
Figure 7-6
Cover Plate - Combustible Gas Module
Comparing to the "GND" (ground) test point measure "BRIDGE VOL" (bridge voltage) and adjust to 2.00 VDC using "BRIDGE ADJ" potentiometer. Turn counter­clockwise to increase.
7.5.3.2 ZERO ADJUSTMENT
Comparing to ground measure SIGNAL OUT and adjust to
0.18 VDC by turning ZERO ADJ potentiometer. Turn counter clock-wise to increase.
7.5.3.3 SPAN ADJUSTMENT
1. Determine the concentration of the calibration gas (CG) in % LEL.
2. Use the following formula to determine the response to the calibration gas at SIGNAL OUT.
Voltage (Signal Out) = (CG+12)/60 For Example: If CG = 50% L.E.L Signal Out = (50+12)/60
= 1.03 volts
SERVICE
Page: 69
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
3. Using a Sierra Monitor Model 1200-26 Gas Calibrator with a Sierra Monitor Model 5358-00 calibration adapter, or Model 5360 Gas Delivery Fitting. Apply the calibration gas at a flow rate of 100 cc/min. until the signal out voltage stops changing (approx. 2 minutes). Then adjust span adj. potentiometer to the calculated value.
4. Remove the calibration gas and wait for the voltage to drop. If the voltage is below 0.30 VDC the procedure is complete. If the voltage is above 0.30 VDC repeat the zero and span adjustments.
5. Calibrate the sensor using the instruction manual procedure.
A LOW SENSITIVITY message during
calibration indicates one of the two conditions for a combustible sensor:
The zero gas voltage must be less than
.3 volts.
The new span change (span voltage less
zero voltage) must exceed 30% of the calculated span change.
For Example:
Zero gas voltage = .20 VDC Span voltage = .43 VDC Span change is .43-.2 = .23 VDC As the calculated span value (from step
5 above) is 1.03, the calculated span change is: 1.03-.2 = .87
By calculation: 30% of .87 = .26 The new span change (.23) is less than
30% of the calculated span change so a
LOW SENSITIVITY message will be
displayed.
The LOW SENSITIVITY calculation is made to insure that the calibration does not adjust the electronics so that the "gain" is large enough to cause false alarms due to minor drift or due to minimal electronic noise.
PIN FUNCTION WIRE COLOR
1 DETECTOR WHITE 2 COMPENSATOR BROWN 3 CALIB. SW. RED 4 DETECTOR BLACK 5 DRAIN BARE 6 CALIB. SW. GREEN
Table 7-5
Combustible Gas Sensor
Wiring Pin Out
1. Detector element resistance should be between 1.5 to 2 ohms.
2. Compensator element resistance should be between
1.5 to 2 ohms.
3. Calibration switch should be open in normal operation and should close when the calibration magnet is applied.
If the sensor fails any of these tests it should be replaced. If the sensor passes these tests the electronics are suspect and BOTH the sensor and electronics should be replaced. (The electronics and sensor which are removed should be returned to the factory for evaluation).
When a new sensor is installed the following actions must be taken:
Make the bridge voltage adjustment
immediately to avoid over-voltage damage to the sensor.
Use diagnostic code 0020 to establish nominal
value calibration.
Allow 24 hours for full stabilization of the
sensor, recheck the zero and span adjustments and calibrate the sensor module.
7.5.4 SENSOR REPLACEMENT
If any of the above adjustments cannot be completed successfully the sensor and/or electronics will require replacement. To check the sensor unplug it from the electronics and remove from the housing so that continuity and resistance tests can be made. Table 7-4 provides the pin out for the sensor assembly.
SERVICE
Page: 70
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.5.5 COMBUSTIBLE GAS SCALING FACTORS
For combustible gas monitoring, a calibration standard of Methane or Propane my be used in conjunction with scaling factors to cause Sentry concentration display and alarm function in %LEL scale of another gas as follows:
GAS METHANE PROPANE
FACTOR FACTOR
Acetaldehyde 60 109 Acetic Acid 54 98 Acetic Anhydride 46 83 Acetone 52 94 Acetylene 57 103 Alkyl Alcohol 51 92 Ammonia 126 229 n-Amyl Alcohol 33 59 Aniline 39 71 Benzene 41 74 Biphenyl 25 45 1,3-Butadiene 56 101 n-Butane 58 106 iso-Butane 52 94 Butene-1 45 82 cis-Butene-2 48 88 trans-Butene-2 51 92 n-Butyl Alcohol 34 62 iso-Butyl Alcohol 53 96 tert-Butyl-Alcohol 74 134 n-Butyl Benzene 31 57 iso-Butyl Benzene 32 58 n-Butyric Acid 38 69 Carbon Disulfide 18 32 Carbon Monoxide 75 137 Carbon Oxysulphide 93 169 Chlorobenzene 34 62 Cyanogen 89 162 Cyclohexane 41 74 Cyclopropane 62 113 n-Decane 33 59 Diethylamine 49 88 Dimethylamine 58 105 2,3-Dimethylpentane 40 72 2,3-Dimethylpropane 40 72 Dimethylsulphide 43 79 1,4-Dioxane 45 81 Epichlorohydrin 45 82 Ethane 68 123 Ethyl Acetate 51 93 Ethyl Alcohol 73 132 Ethylamine 53 95 Ethyl Benzene 36 65 Ethyl Bromide 91 165 Ethyl Chloride 57 103 Ethylcyclopentane 40 72 Ethylene 71 128 Ethylenedichloride 66 120 Ethyleneoxide 52 94
NOTES:
Diethyl Ether 46 84 Dimethoxyethane 42 75 Dimethyl Ether 63 113 Dimethylformamide 46 83 Ethyl Formate 44 80 Ethylmercaptan 56 102 n-Heptane 39 70 n-Hexane 37 67 Hydrazine 45 82 Hydrogencyanide 48 86 Hydrogen 77 139 Hydrogen Sulfide 41 74 Methane 100 181 Methyl Actetate 50 90 Methyl Alcohol 86 156 Methylamine 77 140 Methyl Bromide 90 162 Methyl Chloride 102 186 Methylcyclohexane 44 80 Methylenedichloride 93 168 Methylethylether 44 80 Methylethylketone 41 75 Methyl Formate 67 121 Methylmercaptan 61 110 Methylpropionate 51 93 Methyl n-propylketone 40 73 Napthalene 34 62 Nitromethane 34 62 n-Nonane 31 57 n-Octane 37 68 n-Pentane 46 83 i-Pentane 46 84 Propane 55 100 n-Propyl Alcohol 47 85 n-Propylamine 48 88 n-Propylchloride 50 90 Propylene 52 93 Propyleneoxide 46 83 iso-Propylether 44 79 Propyne 42 75 Toluene 40 73 Triethylamine 40 72 Trimethylamine 48 88 Vinylethylether 42 76 o-Xylene 36 65 m-Xylene 39 71 p-Xylene 39 71 JP-4 (Jet Fuel) 41 73
GAS METHANE PROPANE
FACTOR FACTOR
1. Scaling factors are not FMRC approved.
2. Base data source: EEV sensor specification catalog. (EEV claims some data is the result of specific tests, other data is empirically derived.)
SERVICE
Page: 71
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.6 OXYGEN MODULE (5100-03)
7.6.1 DESCRIPTION
The Oxygen Module includes the electronic assembly installed in an explosion proof housing and the electrochemical sensor connected to one hub of the enclosure. Cabling from the controller connects to a three pin spring loaded terminal strip.
7.6.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error
messages:
CHANGE SENSOR SENSOR FAILURE
REPLACE SENSOR
False readings or alarms are received due to
sensor inaccuracy.
Warning: During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the "Change Module" mode.
Cover Plate - Oxygen Module
Figure 7-7
Although all the necessary data can be collected with a
NOTE
voltmeter at the sensor module, some helpful
information can be displayed on the controller or
printed. See diagnostic codes 0004 and 0008 in
Appendix C.
7.6.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-7 to locate test points during the following procedures.
7.6.3.1 SIGNAL ADJUSTMENT
It is unlikely that any electrical adjustment will be required except when a new sensor is installed.
To make the electrical adjustment connect a voltmeter to
SIGNAL OUT (pos) and GND (ground) and use SENSITIVITY ADJ potentiometer to set the voltage equal to
1/10 of the actual oxygen concentration. In clean air the concentration is 20.9% so the voltage should be set at
2.09 VDC.
7.6.4 SENSOR REPLACEMENT
The oxygen sensor should be replaced when it can no longer be calibrated correctly or when the signal output drops to zero. Generally this is every twelve to eighteen months. The Sentry clock keeps track of the age of the sensor if it is correctly initialized in the "change module" mode.
When a new sensor is installed use the CHANGE MODULE menu selection to answer yes to the "new sensor?" question. After nine months the CHANGE SENSOR message will be displayed to warn that a new sensor should be installed.
The SENSOR FAILURE message for Oxygen sensors does not indicate a specific failure of the sensor but indicates that the sensor is not correctly connected to the electronics. If this message appears check that the sensor harness is correctly installed to the connector on the bottom electronics board.
When sensor replacement is required, open the cover of the sensor module, remove the transmitter and disconnect the sensor wiring harness from the back of the transmitter.
SERVICE
Page: 72
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Unscrew the old sensor from the conduit hub, screw in the new sensor and connect the wiring harness to the transmitter electronics. Replace the transmitter into the enclosure, make signal adjustments as described above, and replace the enclosure cover.
After the sensor is installed:
Update "new sensor" status in the change
module mode.
Allow one hour of stabilization of the new
sensor.
Make the electrical sensitivity adjustment as
described above.
Calibrate the sensor module.
SERVICE
Page: 73
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.7 CARBON MONOXIDE MODULE (5100-04)
7.7.1 DESCRIPTION
The Carbon Monoxide Module includes the sensor and electronic assembly installed in an explosion proof housing.
The sensor screws into one hub of the enclosure and plugs into the bottom electronics card via a six pin connector. Cabling from the controller connects to a three pin spring loaded terminal strip.
7.7.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error
messages
SENSOR FAILURE
LOW SENSITIVITY
False readings or alarms are received
due to sensor inaccuracy.
Warning: During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the "Change Module" mode.
Note
Although all the necessary data can be collected with a
voltmeter at the sensor module, some helpful
information can be displayed on the controller or
printed. See diagnostic codes 0004 and 0008 in
Appendix C.
7.7.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-8 to locate test points during the following procedures.
7.7.3.1 SIGNAL ADJUSTMENT
It is unlikely that any electrical adjustment will be required except when a new sensor is installed.
Figure 7-8
Cover Plate - Carbon Monoxide Module
1 ppm CO = 0.004 VDC.
100 ppm CO = 0.40 VDC.
250 ppm CO = 1.00 VDC.
7.7.3.2 SENSOR REPLACEMENT
The carbon monoxide sensor should be replaced when it can no longer be calibrated correctly. Generally this is every twenty four to thirty months.
The "SENSOR FAILURE" message for Carbon Monoxide sensors does not indicate a specific failure of the sensor but indicates that the sensor is not correctly connected to the electronics. If this message appears check that the sensor harness is correctly installed to the connector on the bottom electronics board.
To make the electrical adjustment connect a voltmeter to
SIGNAL OUT (pos) and GND (ground) and use SENSITIVITY ADJ potentiometer to adjust the voltage
based on the following:
SERVICE
Page: 74
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
If sensor replacement is necessary remove the electronics from the housing and unplug the old sensor from the bottom board, remove it from the enclosure hub and reverse the procedure to install the new sensor.
After the sensor is installed:
Allow one hour of stabilization of the new
sensor.
Make the electrical sensitivity adjustment as
described above.
Calibrate the sensor using the instruction manual
procedure.
SERVICE
Page: 75
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.8 HYDROGEN SULFIDE MODULE (5100-05)
7.8.1 DESCRIPTION
Model 5100-05 Hydrogen Sulfide Sensor Module includes a sensor assembly and electronic assembly installed in an explosion proof housing.
The sensor assembly includes a reuseable housing and disposable electrochemical sensor. The assembly screws into one hub of the sensor module enclosure and plugs into the bottom electronics card via a six pin connector.
Cabling from the controller connects to a three pin spring loaded terminal strip on the electronics assembly.
7.8.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error
messages
SENSOR FAILURE
LOW SENSITIVITY
Figure 7-9
False readings or alarms are received
due to sensor inaccuracy.
Cover Plate - Hydrogen Sulfide Module
Warning: During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the "Change Module" mode.
NOTE
Although all the necessary data can be collected with a
voltmeter at the sensor module, some helpful
information can be displayed on the controller or
printed. See diagnostic codes 0004 and 0008 in
Appendix C.
7.8.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-9 to locate test points during the following procedures.
7.8.3.1 SIGNAL ADJUSTMENT
It is unlikely that any electrical adjustment will be required except when a new sensor is installed.
To make the electrical adjustment connect a voltmeter to
SIGNAL OUT (pos) and GND (ground) and use SPAN ADJ
potentiometer to adjust the voltage based on the following:
1 ppm H2S = 0.02 VDC.
100 ppm H2S = 2.00 VDC.
7.8.3.2 SENSOR REPLACEMENT
The Hydrogen Sulfide sensor should be replaced when it can no longer be calibrated correctly. Generally this is every twenty four to thirty months.
The SENSOR FAILURE message for Hydrogen Sulfide sensors does not indicate a specific failure of the sensor but indicates that the sensor is not correctly connected to the electronics. If this message appears check that the sensor harness is correctly installed to the connector on the bottom electronics board.
The gas sensor which is located inside the sensor assembly housing can be replaced without replacement of the housing. To replace the sensor:
SERVICE
Page: 76
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
1. Confirm that system power has been removed.
2. Remove the transmitter electronics board from the main housing and unplug the sensor harness from the transmitter electronics.
3. Unscrew the sensor housing from the bottom of the enclosure
4. Hold the sensor assembly so that the harness faces down and the sensor faces up. Unscrew and remove the round section of the housing from the hex section. Be careful not to lose the spacer washer which will be sitting on top of the exposed sensor.
5. Carefully pull the old sensor straight up from the socket.
6. Orient the new sensor so that the sensor pin labeled “C” faces the socket labeled
“C” which is on the far side of the board
from the vertical reed switch. The reed switch will slide into a hole on the side of the new sensor. Press the new sensor’s pins into the three sockets.
7. Carefully replace the cover on the sensor assembly including the spacer washer.
8. Install the sensor assembly into the enclosure and tighten firmly.
9. Reconnect the sensor harness to the transmitter, install the transmitter into the housing and restore power.
10. Allow one hour for the sensor to stabilize prior to recalibration.
11. Recalibrate the sensor module.
7.8.3.3 SENSOR OUTPUT ADJUSTMENT
The following procedure is to be used when, during normal calibration of a new sensor, the span voltage cannot be adjusted to a high enough level.
1. Adjust the span potentiometer so that it is approximately mid range. (Twenty turns clockwise and tens turns counter-clockwise).
2. Remove system power and remove both the transmitter and the sensor assembly from the enclosure. Remove the sensor assembly cover so that the sensor is visible.
3. Plug the sensor harness into the transmitter assembly and check that no components are touching the enclosure. Restore power and allow
Hydrogen Sulfide Transmitter Component Locator
a minimum of 30 minutes for stabilization before adjustment.
4. Connect a DVM across TP10 and GT1 on the transmitter assembly. Figure 7-10
5. Locate the gain potentiometer which is on the sensor electronics directly behind one of the holes in the sensor body. The potentiometer is accessible by inserting a jewelers screwdriver through the hole in the sensor.
6. Determine the correct value to be read at TP10 based on the following formula:
V
= 2(C/R) , where C = concentration of span gas,
TP10
and R = range of detection (100 PPM).
7. Apply span gas. Adjust the gain potentiometer until TP10 = correct value as described above. To increase voltage at TP10 turn the gain potentiometer counter clockwise.
8. Remove system power and re-install the sensor and transmitter in the enclosure. Restore power and calibrate.
Figure 7-10
SERVICE
Page: 77
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.9 TOXIC GAS SENSOR MODULE
7.9.1 DESCRIPTION
Toxic Gas Sensor Modules include the following models and default ranges:
5100-06 Chlorine -10 PPM 5100-07 Hydrogen - 2000 PPM 5100-12 Nitrogen Dioxide - 20 PPM 5100-13 Carbon Monoxide, High Range -
1,000 PPM 5100-10 Sulfur Dioxide - 100 PPM 5100-16 Carbon Monoxide, H2 Tolerant -
2,000 PPM 5100-19 Nitric Oxide - 20 PPM 5100-21 Hydrogen Chloride - 20 PPM 5100-22 Hydrogen Cyanide - 20 PPM 5100-27 Ethylene Oxide - 20 PPM
The Toxic Sensor Module includes a sensor assembly and electronic assembly installed in an explosion proof housing.
The sensor assembly includes a reuseable housing and disposable electrochemical sensor. The assembly screws into one hub of the sensor module enclosure and plugs into the bottom electronics card via a six pin connector.
Cabling from the controller connects to a three pin spring loaded terminal strip on the electronics assembly.
7.9.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error messages
SENSOR FAILURE
LOW SENSITIVITY
False readings or alarms are received due to
sensor inaccuracy.
Warning: During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the "Change Module" mode.
Cover Plate - Toxic Gas Module
7.9.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-11 to locate test points during the following procedures.
7.9.3.1 SIGNAL ADJUSTMENT
It is unlikely that any electrical adjustment will be required except when a new sensor is installed.
To make the electrical adjustment connect a voltmeter to
SIGNAL OUT (pos) and GND (ground) and use SPAN ADJ
potentiometer to adjust the voltage based on the following:
1% of full scale = 0.02 VDC.
100% of full scale = 2.00 VDC.
Figure 7-11
Although all the necessary data can be collected with a
NOTE
voltmeter at the sensor module, some helpful
information can be displayed on the controller or
printed. See diagnostic codes 0004 and 0008 in
Appendix C.
7.9.3.2 SENSOR REPLACEMENT
The toxic gas sensor should be replaced when it can no longer be calibrated correctly. Generally this is every twenty four to thirty months.
SERVICE
Page: 78
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
The SENSOR FAILURE message for toxic gas sensors does not indicate a specific failure of the sensor but indicates that the sensor is not correctly connected to the electronics. If this message appears check that the sensor harness is correctly installed to the connector on the bottom electronics board.
The gas sensor which is located inside the sensor assembly housing can be replaced without replacement of the housing. To replace the sensor:
1. Confirm that system power has been removed.
2. Remove the transmitter electronics board from the main housing and unplug the sensor harness from the transmitter electronics.
3. Unscrew the sensor housing from the bottom of the enclosure
4. Hold the sensor assembly so that the harness faces down and the sensor faces up. Unscrew and remove the round section of the housing from the hex section. Be careful not to lose the spacer washer which will be sitting on top of the exposed sensor.
5. Carefully pull the old sensor straight up from the socket.
6. Orient the new sensor so that the sensor pin labeled “C” faces the socket labeled “C” which is on the far side of the board from the vertical reed switch. The reed switch will slide into a hole on the side of the new sensor. Press the new sensor’s pins into the three sockets.
7. Carefully replace the cover on the sensor assembly including the spacer washer.
8. Install the sensor assembly into the enclosure and tighten firmly.
9. Reconnect the sensor harness to the transmitter, install the transmitter into the housing and restore power.
10. Allow one hour for the sensor to stabilize prior to recalibration.
11. Recalibrate the sensor module.
7.9.3.3 SENSOR OUTPUT ADJUSTMENT
The following procedure is to be used when, during normal calibration of a new sensor, the span voltage cannot be adjusted to a high enough level.
Toxic Gas Transmitter Component Locator
1. Adjust the span potentiometer so that it is approximately mid range. (Twenty turns clockwise and tens turns counter-clockwise).
2. Remove system power and remove both the transmitter and the sensor assembly from the enclosure. Remove the sensor assembly cover so that the sensor is visible.
3. Plug the sensor harness into the transmitter assembly and check that no components are touching the enclosure. Restore power and allow a minimum of 30 minutes for stabilization before adjustment.
4. Connect a DVM across TP10 and GT1 on the transmitter assembly. Figure 7-12
5. Locate the gain potentiometer which is on the sensor electronics directly behind one of the holes in the sensor body. The potentiometer is accessible by inserting a jewelers screwdriver through the hole in the sensor.
6. Determine the correct value to be read at TP10 based on the following formula:
V
= 2(C/R) , where C = concentration of span gas,
TP10
and R = range of detection (100 PPM). The value is negative for all models except 5100-06, and 5100-19.
Figure 7-12
SERVICE
Page: 79
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7. Apply span gas. Adjust the gain potentiometer until TP10 = correct value as described above. To increase voltage at TP10 turn the gain potentiometer counter clockwise.
8. Remove system power and re-install the sensor and transmitter in the enclosure. Restore power and calibrate.
SERVICE
Page: 80
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
7.10 AMMONIA SENSOR MODULE (5100-25)
7.10.1 DESCRIPTION
The Ammonia Sensor Module includes a sensor assembly and electronic assembly installed in an explosion proof housing.
The sensor assembly includes a rechargeable electrochemical sensor. The assembly screws into one hub of the sensor module enclosure and plugs into the bottom electronics card via a six pin connector.
Cabling from the controller connects to a three pin spring loaded terminal strip on the electronics assembly.
7.10.2 TROUBLE ANALYSIS
Electrical adjustment, recharge, or replacement of the sensor will be necessary under the following conditions:
Controller displays the following error
messages
SENSOR FAILURE
LOW SENSITIVITY
False readings or alarms are received
due to sensor inaccuracy.
Cover Plate - Ammonia Module
Figure 7-13
Warning: During sensor adjustments the concentration reading on the controller will be inaccurate and alarm level concentrations may be displayed. If false activation of the alarm relays will cause a problem disconnect the relay wiring prior to adjustment or turn the module off using the "Change Module" mode.
NOTE
Although all the necessary data can be collected with a
voltmeter at the sensor module, some helpful
information can be displayed on the controller or
printed. See diagnostic codes 0004 and 0008 in
Appendix C.
7.10.3 ADJUSTMENT PROCEDURE
Prior to reading voltages and making adjustments perform a visual inspection to confirm that there are no physical problems such as water in the electronics enclosure, wiring damage or corrosion.
Use Figure 7-13 to locate test points during the following procedures.
7.10.3.1 SIGNAL ADJUSTMENT
It is unlikely that any electrical adjustment will be required except when a new sensor is installed.
To make the electrical adjustment connect a voltmeter to
SIGNAL OUT (pos) and GND (ground) and use SPAN ADJ
potentiometer to adjust the voltage based on the following:
1% of full scale = 0.02 VDC.
100% of full scale = 2.00 VDC.
7.10.3.2 SENSOR RECHARGE
The Ammonia sensor can be recharged by removing it from service, draining electrolyte, cleaning electrodes and replacing the electrolyte and membrane.
Step by step instructions for sensor recharge are supplied with the recharge kit.
7.10.3.3 SENSOR REPLACEMENT
The Ammonia sensor assembly should be replaced when it can no longer be recharged and calibrated correctly.
SERVICE
Page: 81
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
The SENSOR FAILURE message for ammonia sensors does not indicate a specific failure of the sensor but indicates that the sensor is not correctly connected to the electronics. If this message appears check that the sensor harness is correctly installed to the connector on the bottom electronics board.
To replace the sensor assembly:
1. Confirm that system power has been removed.
2. Remove the transmitter electronics board from the main housing and unplug the sensor harness from the transmitter electronics.
3. Unscrew the sensor housing from the bottom of the enclosure
4. Install the new sensor assembly into the enclosure and tighten firmly.
5. Reconnect the sensor harness to the transmitter, install the transmitter into the housing and restore power.
6. Allow one hour for the sensor to stabilize prior to recalibration.
7. Recalibrate the sensor module.
SERVICE
Page: 82
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
8. APPENDICES
APPENDIX A - SPECIFICATIONS
Page: 83
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
8.1 APPENDIX A - SPECIFICATIONS
A. OPERATING OPERATING TEMPERATURE
Controller 32 to 122oF (0 to 50oC)
STORAGE TEMPERATURE
Controller: -40 to 130oF (-40 to 55oC)
HUMIDITY
Controller: 10% to 95% RH
POWER
Standard 120 VAC +10%/-15%, 60 Hz 12 VDC Nom; 10 to 29 VDC Optional 220 VAC +10%/-15%, 50 Hz 12 VDC Nom; 10 to 29 VDC Consumption 48 Watts max. (eight modules)
RELAYS
Three DPDT 3A, 115 VAC (Low, High, Trouble) Sixteen SPDT 6A, 115 VAC (Model 5392-00) Sixteen SPDT 6A, 115 VAC (Model 4314-01)
ANALOG OUTPUTS
Eight 4-20 mA, channel value (Model 4314-01) Loop Resistance max. 800 Ohms
NUMBER OF CHANNELS
PRINTER INTERFACE
Standard on 5000-08, option on -02 & -04 RS232 Port 1200 Baud 8 bits, no parity 1 start bit, 2 stop bits
MODBUS INTERFACE (Replaces printer interface)
Optional MODBUS communication protocol Honeywell Multivendor Approved for TDC 3000 Gateway
COMPONENTS
Microprocessor Z84 (4 MHz - 8 bit CPU) Memory 64K bytes EPROM 8K bytes Static RAM (battery backed-up) Displays 4 digit 1/2” LCD 32 character (2X16) dot matrix alphanumeric LCD 11 LED indicators Battery Hi energy lithium 3 year retention Keypad 7 key sealed membrane Power Supply Integral High efficiency AC/DC with
line filter
TRANSMISSION
Digital, pulse width modulated - RFI, EMI immune
B. PHYSICAL DIMENSIONS
Controller
Rack Mount 7" X 4.5" X 12" (H W D)
17.5cm X 11.25cm X 30cm
NEMA 4X Enclosure 17.5" X 16.2" X 6.35" (H W D)
44.5cm X 41.1cm X 16cm
NEMA 7 Enclosure 22.0" X 21.5" X 14" (H W D)
55.9cm X 54.6cm X 35.6cm
Module Housing
Environment NEMA 7 (NEMA 4X Optional)
5100-01, 5100-02 7.5" X 4" X 4" (H W D)
19cm X 10cm X 10cm
5100-03 8.5" X 4" X 4" (H W D)
5100-04 : -24, -27 7.5" X 4" X 4" (H W D)
5100-25 10" X 4" X 4" (H W D)
WEIGHT Controller
Rack Mount 7 pounds (3.2 kg) NEMA 4X Enclosure 25 pounds (11.3 kg) NEMA 7 Enclosure 143 pounds (65.0 kg)
Module MOUNTING
Controller Instrument Rack
Module Conduit or flexible cable
MODULE CABLE
Typical: three conductor 18 AWG, See installation instructions for alternative wire sizes
SENSOR TYPES
Hydrogen Sulfide Thin film, solid state (5100-01) Combustible Catalytically bead (5100-02) Oxygen Electrochemical (5100-03). Carbon Monoxide (CO) Electrochemical (5100-04) Hydrogen Sulfide Electrochemical (5100-05) Chlorine Electrochemical (5100-06) Hydrogen Electrochemical (5100-07) Sulfur Dioxide Electrochemical (5100-10) Nitrogen Dioxide Electrochemical (5100-12) CO High Range Electrochemical (5100-13) CO - Hydrogen Tolerant Electrochemical (5100-16) Nitric Oxide electrochemical (5100-19) Hydrogen Chloride Electrochemical (5100-21) Hydrogen Cyanide Electrochemical (5100-22) Ammonia Electrochemical.(5100-25) Ethylene Oxide Electrochemical (5100-27)
19cm X 10cm X 10cm
19cm X 10cm X 10cm
19cm X 10cm X 10cm
2 pounds (0.9 kg)
Chassis Mount Panel Wall Mount Bracket NEMA 4X Enclosure NEMA 7 Enclosure
APPENDIX A - SPECIFICATIONS
Page: 85
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
C. PERFORMANCE
Combustible Gas (5100-02)
Range: 0 - 99% Lower Explosive Limit. Operating Temperature -40oF to 158oF (-40oC to 70oC) Relative Humidity 5 - 99% RH Accuracy: +/- 3% of Full Scale or +/- 10% of Applied Concentration Response: Step to 50% within 10 seconds Recover to 10% within 45 seconds Calibration Frequency Monthly, Recommended Zero Drift: Less than 5% per year. Typical Life: 3 years in normal service. Warranty: 1 year.
Hydrogen Sulfide (5100-05)
Range: 0 - 100 PPM Operating Temperature -40oF to 122oF (-40oC to +50oC) Relative Humidity 10 - 99% RH Accuracy: +/- 2 PPM Response: <30 seconds to 50% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 1% per month Typical Life: 3 years in normal service Warranty: 1 year
Note: Only Combustible Gas (5100-02) and Electrochemical
sensor Hydrogen Sulfide (5100-05) are FMRC Approved
Hydrogen Sulfide (5100-01)
Range: Factory 100 PPM, Max. 100 PPM Operating Temperature -40oF to 158oF (-40oC to 70oC) Relative Humidity 5 - 99% RH Response: <60 seconds to 90% indication Calibration Frequency Monthly, Recommended Zero Drift: Less than 5% per year. Typical Life: 3 years in normal service. Warranty: 1 year.
Oxygen (5100-03)
Range: Factory 25% O2, Max. 25% O2 Operating Temperature -19oF to 122oF (-7oC to 50oC) Relative Humidity 5 - 99% RH Response: 10 seconds to 90% indication. Calibration Frequency 90 Days, Recommended Zero Drift: Less than 5% per year. Typical Life: 1 year in normal service. Warranty: 1 year
Carbon Monoxide (5100-04)
Range: Factory 500 PPM, Max. 2,000 PPM Operating Temperature 4oF to 122oF (-20oC to 50oC) Relative Humidity 15 - 99% RH Response: <25 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 1% per month Typical Life: 2 years in normal service Warranty: 1 year
Chlorine (5100-06)
Range: Factory 10 PPM, Max. 100 PPM Operating Temperature 4oF to 122oF (-20oC to 50oC) Relative Humidity 15 - 99% RH Response: <60 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 1% per month Typical Life: 2 years in normal service Warranty: 1 year
Hydrogen (5100-07)
Range: Factory 1,000 PPM, Max 2,000 PPM Operating Temperature 4oF to 122oF (-20oC to 50oC) Relative Humidity 15 - 99% RH Response: <30 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 1% per month Typical Life: 2 years in normal service Warranty: 1 year
Sulfur Dioxide (5100-10)
Range: Factory 100 PPM, Max 100 PPM Operating Temperature 4oF to 122oF (-20oC to 50oC) Relative Humidity 15 - 99% RH Response: <20 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 1% per month Typical Life: 2 years in normal service Warranty: 1 year
Nitrogen Dioxide (5100-12)
Range: Factory 20 PPM, Max 100 PPM Operating Temperature 4oF to 122oF (-20oC to 50oC) Relative Humidity 15 - 99% RH Response: <35 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 1% per month Typical Life: 2 years in normal service Warranty: 1 year
Carbon Monoxide (5100-13)
Range: Factory 1,000 PPM, Max 2,000 PPM Operating Temperature 4oF to 122oF (-20oC to 50oC) Relative Humidity 15 - 99% RH Response: <25 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 2% per month Typical Life: 3 years in normal service Warranty: 1 year
Carbon Monoxide (5100-16)
Range: Factory 2,00 PPM, Max 4,000 PPM
Tolerates Hydrogen to 2,000 PPM Operating Temperature 4oF to 122oF (-20oC to 50oC) Relative Humidity 15 - 99% RH Response: <35 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 1% per month Typical Life: 2 years in normal service Warranty: 1 year
APPENDIX A - SPECIFICATIONS
Page: 86
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
Nitric Oxide (5100-19)
Range: Factory 20 PPM, Max 100 PPM Operating Temperature 4oF to 122oF (-20oC to 50oC) Relative Humidity 15 - 99% RH Response: <15 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 2% per month Typical Life: 3 years in normal service Warranty: 1 year
Hydrogen Chloride (5100-21)
Range: Factory 20 PPM, Max 100 PPM Operating Temperature 4oF to 122oF (-20oC to 50oC) Relative Humidity 15 - 99% RH Response: <100 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 1% per month Typical Life: 2 years in normal service Warranty: 1 year
Hydrogen Cyanide (5100-22)
Range: Factory 20 PPM, Max 200 PPM Operating Temperature 4oF to 122oF (-20oC to 50oC) Relative Humidity 15 - 99% RH Response: <70 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 1% per month Typical Life: 2 years in normal service Warranty: 1 year
Ammonia (5100-25)
Range: Factory 50 PPM, Max 50 PPM Relative Humidity 20 - 90% RH Operating Temperature 14oF to 113oF (-10oC to 45oC) Response: <30 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 2% per month Typical Life: 2 - 3 years in normal service Warranty: 1 year
Ethylene Oxide (5100-27)
Range: Factory 20 PPM, Max 100 PPM Relative Humidity 5 - 99% RH Operating Temperature 4oF to 122oF (-20oC to 50oC) Response: <90 seconds to 90% indication Calibration Frequency 90 Days, Recommended Zero Drift: Less than 2% per month Typical Life: 2 years in normal service Warranty: 1 year
Model Gas Reading from 100 PPM of interfering gas Number Type CO H2S Cl2 H2 SO2 NO2 NO HCl HCN C2H4 5100-04 5100-05 5100-06 5100-07 5100-10 5100-12 5100-13 5100-16 5100-19 5100-20 5100-22
CO 100 315 -15 <40 50 -55 30 2 40 <50 H2S <0.5 100 -20 <0.1 <15 -15 0 0 0 0 Cl2 0 <-10 100 0 0 105 0 0 0 0 H2 <1 <20 0 100 3 0 35 3 35 85 SO2 <1 0 -40 0 100 -100 0 0 15 0 NO2 0 -20 90 0 0 100 0 0 -3 0 CO 100 350 -40 <60 65 -60 25 5 40 90 CO 100 0 0 0 0 0 0 0 0 35 NO 0 35 0 0 5 25 100 15 0 0 HCl 0 75 -10 0 35 -2 0 100 -8 0 HCN <0.5 -50 0 160 -190 -5 30 100 <1
Ethanol Toluene Methyl-ethyl-ketone Carbon Monoxide
5100-27
C2H4O 55 20 10 40
Table 8-1
Toxic Sensor Cross Sensitivity
APPENDIX A - SPECIFICATIONS
Page: 87
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
8.2 APPENDIX B - LIMITED WARRANTY
SIERRA MONITOR CORPORATION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. SMC will repair or replace without charge any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by SMC personnel.
All warranties hereunder are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without SMC approval or which have been subjected to accident, improper maintenance, installation or application, or on which original identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires, consumables (i.e. calibration gases, batteries , nor to any damage resulting from battery leakage.
In all cases SMC's responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instruction shall be a condition of this warranty.
Except for the express warranty stated above, SMC disclaims all warranties with regard to the products sold hereunder including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of SMC for damages including but not limited to consequential damages arising out of/or in connection with the use or performance of the product.
APPENDIX B - LIMITED WARRANTY
Page: 89
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
8.3 APPENDIX C - ACCESS CONTROL BY USER CODE
8.3.1 INTRODUCTION
Certain critical activities which can be accessed from the keypad are initially unrestricted. Entry codes can be initiated at any time so that these activities are protected from unauthorized access.
8.3.2 DEFINITIONS
USER NUMBER: Single digit number between 1 and 8. This
number is used to establish different authorized users and is printed on reports generated by each user. User number 1 must be established before the other numbers can be used.
ENTRY CODE: Four digit code between 0001 and 9999.
This is the access code which is assigned to each user and is required to access critical menu items which result in changes to the system.
SPECIAL USER NUMBER: The special user number 9 is
reserved for access to the diagnostic mode of operation.
DIAGNOSTIC CODES: When the user number 9 is used to
access diagnostics, four digit entry code numbers are used to select various diagnostic activity.
8.3.3 USER CODE INSTALLATION
1. Select the "SET USER CODE" activity via the
MODE key and press ENTER. Sentry will display "USE ARROWS/ENTER" "USER # 1".
2. To establish an entry code for user number "1" press ENTER and Sentry will display "USE
ARROWS/ENTER" "ENTRY CODE = 0"
3. Use the arrow to change the first digit as required, press ENTER to move to the second digit.
4. Set the second, third and fourth digits in the same manner.
8.3.5 DIAGNOSTIC CODES:
Select the "SET USER CODE" activity, input user number "9" and press ENTER. The display will indicate
"WARNING: DIAGNOSTIC MODE" and will then ask for
the ENTRY CODE. The following are the codes and their Function:
Code Function 0000 Clears all warm-up timers. 0002 Disables error filtering and reduces all warm-
up times. 0003 Not used. 0004 Displays critical module electrical
measurements during normal operation. (H2S:
Sensor signal & Heater Power in mW,
Combustible: Sensor signal & Bridge Power
in mW, O2 & CO: Sensor signal.) 0006 Clears printer buffer. 0007 Clear module X: Asks for the module number
and clears that module's information from the
system memory. 0008 Prints a periodic diagnostic report. The
period is selected in the subsequent menu
selection. (1, 5, 10 , 30 minutes, 1, 8, 12, 24
hours.) 0009 Reset of all diagnostic modes 0010 Prints a single diagnostic report 0012 Forces all Analog Outputs (Model 4314-01)
to 4 mA. 0013 Forces all Analog Outputs (Model 4314-01)
to 20 Ma
5. When an entry code has been established that code must be used to access the controlled sections of the menu.
6. User numbers 1 through 5 have access to all Sentry functions. Users 6 through 8 are restricted to calibration activities only.
8.3.4 USER CODE REMOVAL
1. Change user number 1 entry code to "0000".
0020 Force Calibrates one sensor module. Asks for
the module number after the code is input.
0021 Force Calibrates all uncalibrated sensor
modules. 0022 Disables alarm suppression during calibration. 0023 Restores alarm suppression during calibration 0099 Clears all system RAM including
configuration, calibration and history data.
APPENDIX C - ACCESS CONTROL BY USER CODE
Page: 91
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
8.3.6 LOST ENTRY CODE
If the Entry code is misplaced it will be necessary to
ENTER the "CALIB/CHANGE" activity and delete all codes
as described above. To enter the "CALIB/CHANGE" activity:
1. Turn Sentry off and then on to start the warm­up.
2. Press RESET key three times to "RESET
HISTORY"
3. Press ENTER to display "USE ARROWS/ENTER"
"ENTRY CODE=0"
4. Press TEST key THREE times. No changes will be apparent.
5. Enter the entry code: 9999.
6. The "CALIB/CHANGE" light will turn on and the
"SET USER CODE" activity can be selected so
that the entry code can be changed.
APPENDIX C - ACCESS CONTROL BY USER CODE
Page: 92
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
8.4 APPENDIX D: - MODEL NUMBERS & PARTS LIST
8.4.1 CONTROLLER ITEMS Controllers
5000-02 Sentry 2 Channel Controller 5000-04 Sentry 4 Channel Controller 5000-08 Sentry 8 Channel Controller 5389-50 Sentry Software Enhancement Package
Output Options
4314-01 Output Expansion Module (16 Relays, 8 Analog) 5392-00 Individual Relay Panel (16 Relays)
Mounting Options
4304-03 Cabinet, NEMA 12 Enclosure, 1 shelf 4304-04 Cabinet, NEMA 12 Enclosure, 2 shelf 5331-00 Shelf, 19" Rack Insert 5380-00 Standard (Rack) Configuration (use with 5331-00) 5381-00 Hardware, Panel Mount 5382-00 Hardware, Wall Mount 5383-00 Enclosure, NEMA-4X Weatherproof 5395-00 Enclosure, NEMA-7 Explosion Proof
Controller Accessories
4301-10 Converter RS232-RS485 5332-00 Remote Power Supply - 8 Channel 5346-03 Battery Back-Up System - 3 Hr. (In 5383-00 Encl.) 5346-04 Battery Back-Up System - 5 Hr. (In separate NEMA-12 Encl.) 5346-05 Battery Charger (Mounts in 5331-00) 5346-06 Battery Back-Up System - 24 Hr. (In separate NEMA-4 Encl.)
Printer Options
5301-51 Printer Package, Single Controller, Rack 5301-52 Printer Package, 2-Controller, Rack 5301-53 Printer Package, 3-Controller, Rack 5301-54 Printer Package, 4-Controller, Rack 5301-61 Printer Package, Single Controller, NEMA-4
Controller Upgrades
5357-00 Software, 8 Channel Upgrade from 4 Channel 5357-10 Software, 4-Channel Upgrade from 2-Channel 5357-20 Software, 8-Channel Upgrade from 2-Channel 5389-51 Sentry Software Enhancement Package, Field Upgrade
Sentry Controller Spare/Replacement Parts
5301-00 Printer, 40 Column, Dot Matrix 5301-01 Printer, In 5383-00 5349-00 Connector, On 5383-00 for Printer 5350-00 Printer Cable, RS232C, 15' 5355-00 Printer Network Master Board 5356-00 Printer Network Sub Board 5359-00 Cable, Printer, 6' (use w/5349-00) SPL21701 Sentry Back Panel SPL21703-4 Assy, Master Board SPL21713 Assy, Transformer SPL21714 Cable, Ribbon, Front Panel SPL21714-1 Cable, Ribbon, NEMA Front Panel SPL21760 Assy, Power Supply SPL21768 Assy, Front Panel w/ Label SPL21718 Module, Zone Configuration SPL35079 Panel, Membrane, Keyboard / Label SPL39050 Cover Plate, (Unused Rack Position) SPL49093 Cover, Safety for Alarm Terminal SPL49094 Cover, Safety for AC Terminal Strip SPL49111 Fuse, 1 AMP Slo-Blo (AC) SPL49117 Fuse, 4 AMP Slo-Blo (P/S F1,3)
APPENDIX D: - MODEL NUMBERS & PARTS LIST
Page: 93
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
SPL49121 Varistor (AC) SPL49142 Fuse, 10 AMP (P/S F2) SPL52094 Connector Release Arm (10 Pack) SPL69017 Relay, DPDT SPL69121 Battery, Lithium, Sentry SPL69145 Battery, 12 VDC 20 AH (for 5346-04) SPL69146 Printer Ribbon, Sentry (EA) SPL69148 Printer Paper, Sentry (Roll) SPL69150 Battery, 12 VDC 6.5 AH (for 5346-03)
8.4.2 SENSOR MODULE ITEMS Sensor Modules
5100-01 Sensor Module - Hydrogen Sulfide, H2S, solid state, 0-100 ppm 5100-02 Sensor Module - Combustible Gas, 0-100% L.E.L. 5100-03 Sensor Module - Oxygen, O2, 0-25% 5100-04 Sensor Module - Carbon Monoxide, CO, 0-200 ppm 5100-05 Sensor Module - Hydrogen Sulfide, H2S, electrochemical, 0-100 ppm 5100-06 Sensor Module - Chlorine, Cl2, 0-10 ppm 5100-07 Sensor Module - Hydrogen, H2, 0-1000 ppm 5100-10 Sensor Module - Sulfur Dioxide, SO2, 0-100 ppm 5100-12 Sensor Module - Nitrogen Dioxide, NO2, 0-100 ppm 5100-16 Sensor Module - Carbon Monoxide, CO, H2 Tolerant, 0-2000 ppm 5100-21 Sensor Module - Hydrogen Chloride, HCl, 0-20 ppm 5100-22 Sensor Module - Hydrogen Cyanide, HCN, 0-20 ppm 5100-25 Sensor Module - Ammonia, NH3, 0-50 ppm 5100-90 Input Module - Analog/Digital - 8 channel 5100-99 Input Module - Analog/Digital - 1 channel
Sensor Module Accessories
5311-00 Rainshield 5394-00 Duct Mount Fitting 5398-01 Sample Draw Assembly 5398-02 Sample Draw/Dilution Assembly 5398-24 Sample Draw System - 4 channel 5399-01 Sample Draw Fitting SPL21776 Enclosure, NEMA 4, Group. B, Transmitter Upgrade SPX39128-1 Tag, Stainless Steel
Gas Sensor Modules Spare Parts
5200-01 Sensor, Sentry Hydrogen Sulfide, H2S (Solid State) 5200-02 Sensor, Sentry Combustible (%LEL) 5200-03 Sensor, Sentry Oxygen, O2 (%) 5200-04 Sensor, Sentry, Carbon Monoxide, CO ppm 5200-05 Sensor, Sentry Hydrogen Sulfide, H2S, ppm 5200-06 Sensor, Sentry Chlorine,CL2, ppm 5200-07 Sensor, Sentry Hydrogen, H2, ppm 5200-10 Sensor, Sentry Sulfur Dioxide, SO2, ppm 5200-12 Sensor, Sentry Nitrogen Dioxide, NO2, ppm 5200-16 Sensor, Sentry Carbon Monoxide, CO, H2 Tolerant, ppm 5200-21 Sensor, Sentry Hydrogen Chloride, HCL, ppm 5200-22 Sensor, Sentry Hydrogen Cyanide, HCN, ppm 5200-25 Sensor, Sentry Ammonia, NH3, ppm SPL21756 Assy,. Transmitter, Carbon Monoxide, CO SPL21756-1 Assy, Transmitter, Hydrogen, H2 SPL21757 Assy, Transmitter, Combustibles SPL21758 Assy, Transmitter, Hydrogen Sulfide, H2S SPL21759 Assy, Transmitter, Oxygen, O2 SPL21767 Enclosure, Transmitter SPL21774 Remote Sensor Ext. Kit, H2S SPL21775 Remote Sensor Ext. Kit , Combustible SPL21776-1 Enclosure, Transmitter NEMA-4X SPL21780 Assy, Transmitter - Toxic SPL21781-XX Assy, Sensor - Toxic
APPENDIX D: - MODEL NUMBERS & PARTS LIST
Page: 94
Loading...