SMC Networks ZSE40A(F),ISE40A Operation Manual

Item Default setting [F 3] Setting of response time 2.5 ms [F 4] Setting of auto-preset Manual
[F 6] Setting of fine adjustment of display value 0%
1000-split[F11] Setting of display resolution
OFF[F80] Setting of power saving mode OFF[F81] Setting of security code OFF[F90] Setting of all functions OFF[F97] Selection of copy function
Normal[F98] Check of output
OFF[F99] Reset to the default setting
Digital Pressure Switch
Operation Manual
ZSE40A(F)/ISE40A
Thank you for purchasing the SMC ZSE40A(F)/ISE40A Series Digital Pressure Switch. Please read this manual carefully before operating the digital pressure switch and make sure you understand the digital pressure switch, its capabilities and limitations. Please keep this manual handy for future reference.
To get information in detail for operating this product, refer to SMC website (URL http:/ /www.smcwo rld.com
) or c ontact us.
Safety Instructions
D
o not operate the product outside of the specifications.
Do not use for flammable or harmful fluids. Fire, malfunction, or damage to the product can result. Verify the specifications before use.
Do not disassemble, modify (including changing the printed circuit board) or repair.
An injury or failure can result.
Do not operate in an atmosphere containing flammable or explosive gases.
Fire or an explosion can result. This product is not designed to be explosion proof.
Do not use the product in a place where static electricity is a problem.
Otherwise it can cause failure or malfunction of the system.
NOTE
The direct current power supply to be used should be UL approved as follows : Circuit (of class 2) which is of maximum 30Vrms (42.4V peak) or less, with UL 1310 class 2 power supply unit or UL 1585 class 2 transformer. The Pressure switch is a approved product only if it has a mark on the body.
Indication light (Orange LED): Displays the switch operation condition. L
CD display: Displays the current status of pressure, setting mode and error code.
Four display modes can be selected to display always in red or green only, or changing from green to red, red to green according to the output status.
button (UP): Selects the mode or increases the ON/OFF set value.
P
ress this button to change to the peak display mode.
button (DOWN): Selects the mode or decreases the ON/OFF set value.
Press this button to change to the bottom display mode.
button (SET): Press this button to change to either mode and to set a value.
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or equipment damage. These instructions indicate the level of potential hazard with the labels of "Caution", " Warning" or "Danger". They are all important notes for safety and must be followed in addition to International standards (ISO/IEC), Japan Industrial Standards (JIS) and other safety regulations.
Operato r erro r coul d resu lt in injury or equipmen t damage.
Operator
This operation manual is intended for those who have knowledge of machinery using pneumatic equipment, and have sufficient knowledge of assembly, operation and maintenace of such equipment. Only those persons are allowed to perform assembly, operation and maintenance. Read and understand this operation manual carefully before assembling, operating or providing maintenance to the product.
Warning
If using the product in an interlocking circuit:
• Provide a double interlocking system, for example a mechanical system
• Check the product regularly for proper operation Otherwise malfunction can result, causing an accident.
The following instructions must be followed during maintenance:
• Turn off the power supply
• Stop the air supply, exhaust the residual pressure and verify that the air is released before performing maintenance.
Otherwise an injury can result.
After maintenance is complete, perform appropriate functional inspections and leak tests.
Stop operation if the equipment does not function properly or there is a leakage of fluid. When leakage occurs from parts other than the piping, the product might be faulty. Disconnect the power supply and stop the fluid supply. Do not apply fluid under leaking conditions. Safety cannot be assured in the case of unexpected malfunction.
Do not touch the terminals and connectors while the power is on.
Otherwise electric shock, malfunction or damage to the product can result.
Caution
Names and Functions of Product
button(DOWN)
LCD display
button(UP)
button(SET)
Indication light
Installation
M
ounting
Mount the optional bracket and panel mount adapter to the pressure switch. When the pressure switch is to be mounted in a place where water and dust splashes occur, insert a tube into the air-relieving port of the pressure switch. (Refer to "Tube attachment")
Mounting with bracket
Fix the bracket to the pressure switch with the set screws M3x5L (2 pcs.) or M4x5L (2 pcs.) supplied. Apply a tightening torque of 0.5 to 0.7 Nm for the M3 set screws or 1.4 to
1.6 Nm for the M4 set screws .
Mounting and Installation
Bracket A or D
M3
Bracket A or D
M4
5
Mounting with panel mount adapter
Panel mount adapter (Model: ZS-35-C/ZS-35-D) Panel mount adapter + Front protective cover (Model: ZS-35-F/ZS-35-G)
Piping
Connection using screw type piping
Connect suitable piping to the mating port. Hold the hexagon part of the pressure port and fix. Apply a tightening torque of 7 to 9 Nm. When using an M5 female fitting confirm the fitting specification.
Connection using One-touch fitting
1. Cut the tube perpendicularly.
2. Hold the tube and insert it into the One-touch ftting slowly until it bottoms out.
Allow sufficient tube length to prevent twist, tensile and moment load from being applied to the fitting and tube. When using a tube manufactured by a company other than SMC, check its outside diameter accuracy satisfies the following values.
1) Nylon tube: ±0.1 mm at maximum
2) Soft nylon tube:
±0.1 mm at maximum
3) Polyurethane tube: +0.15 mm/-0.2 mm at maximum
Tube attachment
When this pressure switch is used in a place where water and dust splashes may occur, insert a tube in the air-relieving port, and bring piping of the opposite side up to the safe position to keep it from water and dust. (See the right figure.)
: The tube should be inserted to the end of the air-relieving port.: SMC TU0425 (polyurethane, O.D ø4, I.D ø2.5) is a suitable tubing.
Wiring
Connection
Make connection after turning the power off. Use a separate route when connecting the wire of the Pressure switch. Malfunction stemming from noise may occur if the wire is installed in the same route as that of power or high-voltage cable. Be sure to ground terminal FG when using a
commerically available switch-mode power supply. When the switch-mode power supply is connected to the Pressure switch, switching noise wil be superimposed and product specification can no longer be met. This can be prevented by inserting a noise filter, such as a line noise filter and ferrite core, between the switch-mode power supply and the Pressure switch, or by using a series power supply instead of the switch-mode power supply.
B
rown
Gray
Black
White
B
lue
Caution: Warning:
Danger:
Operator error could result in serious injury or loss of life.
In extreme conditions, there is a possibility of serious injury or loss of life.
Names of individual parts
Pressure Setting
Set ON point and OFF point of the Pressure switch.
O
peration
When the pressure exceeds a set value, the Pressure switch will be turned on. When the pressure falls below the set value by the amount of hysteresis or more, the Pressure switch will be turned off. T
he default setting of the output set value is the central value between the atmospheric pressure and the upper limit of the rated pressure range. If the operation shown the right does not cause any problem, keep this operation setting.
Switch ON
Switch OFF
set value
P_1
hysteresis
H_1
Time [s]
P
r
e
s
s
u
r
e
[
P
a
]
<
How to operate>
[Hysteresis mode] (1)Press the button once in measurement mode.
(2)[P_1] or [n_1] and set value are
displayed in turn.
D
isplays in turn
N
ormal output
Reversed output
(3)Press the or button to change the set value.
The button is for increase and the button is for decrease.
Press the button once to increase by one figure, and press it continuously to keep increasing the set figure. Press the button once to decrease by one figure, and press it continuously to keep decreasing the set figure.
(4)Press the button to finish the setting of OUT1.
[P_2] is displayed. Set OUT2 same way as OUT1.
[ Window comparator mode ] The Pressure switch turns on within a set pressure range (from P1L to P1H) during window comparator mode. Set P1L (switch lower limit) and P1H (switch upper limit) using the setting procedure above.
Zero clear of indication
Indication is reset to zero when and buttons are pressed simultaneously for 1 second. For the first operation, perform zero clear without pressure supply.
Setting of Function
Default setting
At the time of shipment, the following settings are provided. If the setting is acceptable, keep it for use. To change setting, refer to SMC website (URL http://www.smcworld.com
) to get
information in detail or contact us.
[F 0] Unit conversion function
[F 1] Setting of OUT1
[F 2] Setting of OUT2
Same setting as [F 1] OUT1. At the output mode, Error detection mode can be selected. Display color is linked to the setting of OUT1, and can not be selected.
Other parameter setting
Item Explanation
Output mode
Selects hysteresis mode, window comparator mode or OFF mode.
Reversed output Selects reversed output.
Pressure setting Sets ON point or OFF point of the switch output
Default setting
Hysteresis Chattering can be prevented by setting hysteresis.
Hysteresis mode
ISE40A: 0.500 MPa ZSE40A: -50.7 kPa ZSE40AF: 50.0 kPa
Normal output
5%
Unit specification Pressure range
Nil or M
ISE40A
ZSE40A(F)
Default setting
P
ISE40A
MPa kPa
PSI
ZSE40A(F)
Measurement mode
The measurement mode is the condition where the pressure is detected and indicated, and the switch function is operating. This is the basic mode, and other modes should be selected for setting change and other function setting changes.
Measurement mode
1 s
1 s
1 s
Display to show the unit specification
Display to show the product
T
he power is supplied
1 s
D
isplay to show the standard product
D
isplay to show the pressure range
F
unction selection mode
Measurement mode
F
unction selection mode
Setting functions
Press the button f
or 2 s or longer
Other Settings
Peak/Bottom hold value indication Zero clear Key lock
To set each function the above in detail, refer to SMC website (URL http://www.smcworld.com) to get information in detail or contact us.
Maintenance
How to reset the product after power cut or forcible de-energizing
The setting of the product will be retained as it was before a power cut or de-energizing. The output condition is also basically recovered to that before a power cut or de-energizing, but may change depending on the operating environment. Therefore, check the safety of the whole facility before operating the product. If the facility is using accurate control, wait until the pressure switch has warmed up. (About 10 to 15 minutes)
∗: Some functions are not available depending on part number. All functions are displayed with
[F ] and followed with function description. If a function is not available for specified type, the function is displayed as [---].
Troubleshooting
O
ver current
Error
A load current of switch output is 80 mA or more.
Turn the power off and remove the output factor for the over current. Then turn the power on.
Error indication function
This function is to display error location and content when a problem or an error occurs.
R
esidual
Pressure Error
P
ressurizing
Error
System Error
During zero clear operation, pressure over ±7%F.S. (±3.5%F.S.for compound pressure) is applied. After 1 second, the mode will reset to the measurement mode. ±1%F.S. of the zero clear range varies with individual product differences.
P
erform zero clear operation again after restoring the applied pressure to an atmospheric pressure condition.
Pressure has exceeded the upper limit of the set pressure range.
Displayed in the case of an internal data error.
Reset applied pressure to a level within the set pressure range.
Turn the power off and turn it on again. If resetting fails, an investigation by SMC CORPORATION will be required.
Specification
Refer to the product catalogue or SMC website (URL http://www.smcworld.com) to get information about product specifications in detail.
Outline with Dimensions (in mm)
Refer to the product catalogue or SMC website (URL http://www.smcworld.com) to get information about outline dimensions in detail.
If the error can not be reset after the above measures are taken, then please contact SMC.
Akihabara UDX 15F, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, JAPAN Phone: +81 3-5207-8249 Fax: +81 3-5298-5362
URL http://www.smcworld.com
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer. © 2009 SMC Corporation All Rights Reserved
Pressure has exceeded the lower limit of the set pressure range.
•Bracket A or D(Model: ZS-24-A/ZS-24-D) •Bracket B (Model: ZS-24-B)
[01/N01 type] [W1/WF1 type]
Bracket B
M4 5L
Front protective cover (Option)
Panel mount adapter (Model ZS-35-C/D)
P
anel
Spanner (12 mm)
Tube
One-touch fitting
To the safe position to keep from water and dust
Tube
Air-relieving port
Brown
Gray
Black
DC(+)
A
nalog output/Auto-shift input
c
opy terminal
OUT1
OUT2
White
B
lue
DC(-)
[F 5] Setting of analog output/auto-shift input Analog output
Display color Selects the display color.
ON: Green OFF: Red
Error Name Error Display Error Type Troubleshooting Method
Auto-shift Error
The measured pressure auto-shift input has exceeded the set pressure range.
: After 1 second, the mode will reset to
measurement mode.
Auto-shift input signal is invalid. Check the connected equipment and correct the signal.
In measurement mode, press the button for 2 seconds or longer to display [F 0]. Select to display the function setting to be changed, [F ].
Press the button for 2 seconds or longer in function selection mode to return to measurement mode.