SMC Networks ZSE30A series,ISE30A Series,ZSE30AF series Operation Manual

Pressure Setting
Set ON and OFF point of the Pressure switch.
Operation
When the pressure exceeds the set value, the Pressure switch will turn ON. When the pressure falls below the set value by the amount of hysteresis or more, the Pressure switch will turn OFF. The default setting of the output set value is the central value between the atmospheric pressure and the upper limit of the rated pressure range. If this condition, shown to the right, is acceptable, then keep these settings.
<How to operate>
[Hysteresis mode]
1. Press the button once in measurement mode.
2. [P_1] or [n_1] and the set value are displayed in turn.
Connector C
onnecting / Disconnecting
When mounting the connector, insert it straight into the socket, holding the lever and connector body, and push the connector until the lever hooks into t
he housing, and locks. When removing the connector, press down the lever to release the hook from the housing and pull the connector straight out.
Digital Pressure Switch
Operation Manual
ZSE30A(F)/ISE30A
Thank you for purchasing an SMC ZSE30A(F)/ISE30A Series Digital Pressure Switch. Please read this manual carefully before operating the product and make sure you understand its capabilities and limitations. Please keep this manual handy for future reference.
To obtain more detailed information about operating this product, please refer to the SMC website (URL http:// www.smcwor ld.com
) or co ntact SMC
directl y.
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or equipment damage. These instructions indicate the level of potential hazard with the labels of "Caution", "Warning" or "Danger". They are all important notes for safety and must be followed in addition to International standards (ISO/IEC) and other safety regulations.
Function Setting
Default setting
At the time of shipment, the following settings are provided. If the setting is acceptable, keep it for use.
Refer to the SMC website (URL http://www.smcworld.com
) for more detailed
information about setting changes, or contact SMC.
[F 0] Unit conversion function
[F 1] Setting of OUT1
[F 2] Setting of OUT2 S
ame setting as [F 1] OUT1. The display colour is linked to the setting of OUT1, and can not be set for OUT2.
Other parameter setting
Item Default setting [F 3] Setting of response time 2.5 ms [F 4] Setting of display resolution 1000-split [F 5] Setting of auto-preset Manual
0%[F 6] Setting of fine adjustment of display value OFF[F 7] Setting of power saving mode OFF[F 8] Setting of security code O
FF
[
F90] Setting of all functions
OFF[F97] Selection of copy function
Normal[F98] Check of output
OFF[F99] Reset to the default setting
Item Description
Output mode Selects hysteresis mode or window comparator mode.
R
eversed outputSelects reversed output.
Pressure setting Sets ON or OFF point of the switch output.
Default setting
Hysteresis Chattering can be prevented by setting hysteresis.
Hysteresis mode
ISE30A: 0.500 MPa ZSE30A: -50.5 kPa ZSE30AF: 50.0 kPa
N
ormal output
ISE30A: 0.050 MPa
ZSE30A: 5.0 kPa
ZSE30AF: 5.0 kPa
Unit specification Model
Nil or M
ISE30A
ZSE30A(F)
Default setting
P
ISE30AMPa
kPa ZSE30A(F)
M
easurement mode
The measurement mode is the condition where the pressure is detected and indicated, and the switch function is operating. This is the basic mode, and the other modes should be selected for setting changes and other function settings.
Measurement mode
1 s
1
s
1 s
Display to show the unit specification
D
isplay to show the product
The power is supplied
1 s
D
isplay to show the standard product
D
isplay to show the pressure range
Indication LED (Green OUT1 and Red OUT2): Displays the switch condition. LCD display:
Displays the current status of pressure, setting mode, selected indication unit and error code. Four display modes can be selected: display always in red or green, or display changing from green to red, or red to green, according to the output status.
button (UP): Selects the mode or increases the ON/OFF set value.
Press this button to change to the peak display mode.
button (DOWN): Selects the mode or decreases the ON/OFF set value.
Press this button to change to the bottom display mode.
b
utton (SET):
P
ress this button to change to another mode and to set a value.
Unit indication: Displays the unit currently selected (only for kPa or MPa unit
indication).
Summary of Product parts
Installation
Mounting with bracket
: The tightening torque of the piping port must be 7 to 9 Nm.
The tightening torque of the mounting screw for the bracket must be 0.5 to 0.7 Nm.
Fix the bracket to the pressure switch with the set screws M3x5L (2 pcs.) supplied, before installation.
•Bracket A (Model: ZS-38-A1) Bracket B (Model: ZS-38-A2) Bracket C (Model: ZS-38-A3)
Mounting and Installation
Names of individual parts
C
onnector pin numbers
psi
LCD display Indication LED
button (UP)
button (SET)
b
utton (DOWN)
Unit indication
M3x5 L
Bracket B
M3x5 L
Bracket A
M3x5 L
M3x5 L
M3x5 L
Bracket C
M
3x5 L
DC(+) Brown 5
P
in No.
OUT1
Black 4
OUT2
White 3
(
FUNC)
2
DC(-)
Blue 1
Housing
Pins
Lever
Lead wire (Brown)
Connector
Lead wire (Blue)
Displays in turnNor mal output
Reversed output
Display colour
Selects the display colour.
ON: Green O
FF: Red
CAUTION indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury.
Operator
This operation manual is intended for those who have knowledge of machinery using pneumatic equipment, and have sufficient knowledge of assembly, operation and maintenance of such equipment. Only those persons are a
llowed to perform assembly, operation and maintenance. Read and understand this operation manual carefully before assembling, operating or providing maintenance to the product.
Caution:
Warning:
Danger:
WARNING indicates a hazard with a medium level of risk which, if not avoided, could result in death or serious injury.
DANGER indicates a hazard with a high level of risk which, if not avoided, will result in death or serious injury.
Safety Instructions
Do not disassemble, modify (including changing the printed circuit board) or repair.
An injury or failure can result.
Do not operate in an atmosphere containing flammable or explosive gases.
Fire or an explosion can result. This product is not designed to be explosion proof.
Do not use the product in a place where static electricity is a problem.
Otherwise it can cause failure or malfunction of the system.
NOTE
•The direct current power supply to be used should be UL approved as follows: Circuit (of Class2) which is of maximum 30 Vrms (42.4 V peak), with UL1310 Class2 power supply unit or UL1585 Class2 transformer.
•The product is a approved product only if it has a mark on the body.
If using the product in an interlocking circuit:
•Provide a double interlocking system, for example a mechanical system
•Check the product regularly for proper operation
Otherwise malfunction can result, causing an accident.
The following instructions must be followed during maintenance:
•Turn off the power supply
•Stop the air supply, exhaust the residual pressure and verify that the air is released before performing maintenance work
Otherwise an injury can result.
After maintenance is complete, perform appropriate functional inspections and leak tests.
Stop operation if the equipment does not function properly or there is a leakage of fluid. When leakage occurs from parts other than the piping, the product might be faulty. Disconnect the power supply and stop the fluid supply. Do not apply fluid under leaking conditions. Safety cannot be assured in the case of unexpected malfunction.
Do not touch the terminals and connectors while the power is on.
Otherwise electric shock, malfunction or damage to the product can result.
D
o not operate the product outside of the specifications.
Do not use for flammable or harmful fluids. Fire, malfunction, or damage to the product can result. Verify the specifications before use.
The Pressure switch operates within a set pressure range (from P1L to P1H) during window comparator mode. Set P1L (switch lower limit) and P1H (switch upper limit) with the setting procedure above. (When reversed output is selected, [n1L] and [n1H] are displayed.)
Zero clear of display
The display is reset to zero when the and buttons are pressed simultaneously for 1 second. For the initial operation, always perform zero clear with no pressure applied.
Other Settings
Peak / Bottom hold display Zero clear Key lock
To set each of these functions, refer to the SMC website (
URL http://www.smcworld.com)
for more detailed information, or contact SMC.
Maintenance
How to reset the product after a power cut or forcible de-energizing
The setting of the product will be retained as it was before a power cut or de-energizing. The output condition is also basically recovered to that before a power cut or de-energizing, but may change depending on the operating environment. Therefore, check the safety of the whole installation before operating the product. If the installation is using accurate control, wait until the product has warmed up (approximately 10 to 15 minutes).
Troubleshooting
The switch output load current is more than 80 mA.
T
urn the power off and remove the cause of the over current. Then turn the power on.
Error Indication
This function is to display error location and content when a problem or an error occurs.
Residual Pressure Error
Pressurizing Error
System Error
During the zero clear operation, pressure above ±7%F.S. (±3.5%F.S. for compound pressure) has been applied. After 1 second, the mode will return to measurement mode. The zero clear range can vary ±1%F.S. with individual product differences.
Perform zero clear operation again after restoring the applied pressure to an atmospheric pressure condition.
Pressure has exceeded the upper limit of the set pressure range.
Displayed in the case of an internal data error.
Reset applied pressure to a level within the set pressure range.
Turn the power off and turn it on again. If resetting fails, an investigation by SMC Corporation will be required.
If the error can not be reset after the above measures are taken, then please contact SMC.
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer. © 2011 SMC Corporation All Rights Reserved
Pressure has exceeded the lower limit of the set pressure range.
Akihabara UDX 15F, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, JAPAN Phone: +81 3-5207-8249 Fax: +81 3-5298-5362
URL http://www.smcworld.com
E
rror Name
Error Display Error Type Troubleshooting Method
Over current Error
3. Press the or button to change the set value. The button is to increase and the button is to decrease.
Press the button once to increase by one digit, and press it continuously to keep increasing the set value. Press the button once to decrease by one digit, and press it continuously to keep decreasing the set value.
4. Press the button to complete the setting. For models with 2 outputs, [P_2] or [n_2] will be displayed. Set as above.
Function selection mode
In measurement mode, press the
button for 2 seconds or longer to display [F 0]. Select to display the function to be changed, [F ]. Press the button for 2 seconds or longer in function selection mode to return to measurement mode.
Measurement mode
Function selection mode
Function setting
Press the button for 2 s or longer
: Some functions are not available depending on part number. All functions are displayed with
[F ] followed by the function description. If a function is not available, the function is displayed as [---].
Unit specification Model Default setting
Warning
Caution
Switch ON
At normal output
Switch OFF
Set value
P_1
Hysteresis
H
_1
Time [s]
Pressure [Pa]
: The bracket A/B/C can be mounted in 4 ways.
Piping
Connection using One-touch fitting
1. Cut the tube end perpendicular.
2. Hold the tube and insert it into the One-touch fitting slowly until it bottoms out.
Allow sufficient tube length to prevent twist and tensile or moment loads from being applied to the fitting or tube. When using a tube manufactured by a company other than SMC, check that its outside diameter tolerance satisfies the following values:
1) Nylon tube: ±0.1 mm maximum
2) Soft nylon tube: ±0.1 mm maximum
3) Polyurethane tube: +0.15 mm/-0.2 mm maximum
Wiring
Connection
Connections should only be made with the power supply turned off. Use separate routes for the Pressure switch wiring and any power or high voltage wiring. Otherwise, malfunction may result due to noise. Ensure that the FG terminal is connected to ground when using a commercially available switch-mode power supply. When a switch-mode power supply is connected to the product, switching noise will be superimposed and the product specification can no longer be met. This can be prevented by inserting a noise filter, such as a line noise filter and ferrite core, between the switch-mode power supply and the product, or by using a series power supply instead of the switch-mode power supply.
Mounting with panel mount adapter
Fix the panel mount adapter to the product with the mounting screws (nominal seiz: 3 x 8 L, 2 pcs.) supplied.
•Panel mount adapter (Model: ZS-27-C) Panel mount adapter + Front protective cover (Model: ZS-27-D)
Panel
Front protective cover
(Option)
Panel mount adapter
(Model: ZS-27-C/D)
Mounting screws
Tube
One-touch fitting
: The panel mount adapter can be rotated by 90 degrees for mounting.
Specifications Outline with Dimensions (in mm)
Refer to the product catalogue or SMC website (URL http://www.smcworld.com) for more information about the product specifications and outline dimensions.
Refer to the product catalogue or SMC website (URL http://www.smcworld.com) for more information about panel cut-out and mounting hole dimensions.
Refer to the SMC website (URL http://www.smcworld.com
) for more information
about troubleshooting.