SMC Networks ZSE30AF-#-#-X576, ZSE10, ZSE10F, ISE10 Operation Manual

Page 1
No.PS※※-OMV1001
PRODUCT NAME
Digital Pressure Switch
MODEL / Series / Product Number
ZSE30AF-#-#-X576~X580
Page 2
-1-
No.PS※※-OMV1001
Table of Contents
Safety Instructions 2 Model Indication and How to Order 8 Summary of Product parts 10
Definition and terminology 11
Mounting and Installation 14
Installation 14 Wiring 16
Pressure Setting 19
Measurement mode 19
Function Setting 22
Function selection mode 22 Default setting 22 F0 Units selection function 24 F1 Setting of OUT1 25 F2 Setting of OUT2 28 F3 Response time 29 F4 Display resolution 32 F5 Auto-preset function 33 F6 Fine adjustment of display value 35 F7 Power saving mode 36 F8 Security code 37 F9 Setting of low-cut function 38 Special function setting 39 F90 Setting of all functions 39 F97 Copy function 41 F98 Check of output 43
F99 Reset to default settings 45 Other Settings 46 Maintenance 49 If the security code is forgotten 50 Troubleshooting 51 Specification 59
Dimensions 62
Page 3
-2-
No.PS※※-OMV1001
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or equipment damage. These instructions indicate the level of potential hazard with the labels of "Caution", "Warning" or "Danger". They are all important notes for safety and must be followed in addition to International Standards (ISO/IEC)*1), and other safety regulations.
*1) ISO 4414: Pneumatic fluid power -- General rules relating to systems.
ISO 4413: Hydraulic fluid power -- General rules relating to systems. IEC 60204-1: Safety of machinery -- Electrical equipment of machines .(Part 1: General requirements) ISO 10218: Manipulating industrial robots -Safety. etc.
Caution
Caution indicates a hazard with a low level of risk which, if not avoided, could
result in minor or moderate injury.
Warning
Warning indicates a hazard with a medium level of risk which, if not avoided,
could result in death or serious injury.
Danger
Danger indicates a hazard with a high level of risk which, if not avoided, will
result in death or serious injury.
Warning
1. The compatibility of the product is the responsibility of the person who designs the equipment or decides its specifications.
Since the product specified here is used under various operating conditions, its compatibility with specific equipment must be decided by the person who designs the equipment or decides its specifications based on necessary analysis and test results. The expected performance and safety assurance of the equipment will be the responsibility of the person who has determined its compatibility with the product. This person should also continuously review all specifications of the product referring to its latest catalog information, with a view to giving due consideration to any possibility of equipment failure when configuring the equipment.
2. Only personnel with appropriate training should operate machinery and equipment.
The product specified here may become unsafe if handled incorrectly. The assembly, operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced.
3. Do not service or attempt to remove product and machinery/equipment until safety is confirmed.
1. The inspection and maintenance of machinery/equipment should only be performed after measures to
prevent falling or runaway of the driven objects have been confirmed.
2. When the product is to be removed, confirm that the safety measures as mentioned above are
implemented and the power from any appropriate source is cut, and read and understand the specific product precautions of all relevant products carefully.
3. Before machinery/equipment is restarted, take measures to prevent unexpected operation and malfunction.
4. Contact SMC beforehand and take special consideration of safety measures if the product is to be used in any of the following conditions.
1. Conditions and environments outside of the given specifications, or use outdoors or in a place
exposed to direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space, shipping,
vehicles, military, medical treatment, combustion and recreation, or equipment in contact with food and beverages, emergency stop circuits, clutch and brake circuits in press applications, safety equipment or other applications unsuitable for the standard specifications described in the product catalog.
3. An application which could have negative effects on people, property, or animals requiring special
safety analysis.
4. Use in an interlock circuit, which requires the provision of double interlock for possible failure by using
a mechanical protective function, and periodical checks to confirm proper operation.
Page 4
-3-
No.PS※※-OMV1001
Safety Instructions
Caution
1.The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in manufacturing industries. If considering using the product in other industries, consult SMC beforehand and exchange specifications or a contract if necessary. If anything is unclear, contact your nearest sales branch.
Limited warranty and Disclaimer/Compliance Requirements
The product used is subject to the following "Limited warranty and Disclaimer" and "Compliance Requirements". Read and accept them before using the product.
Limited warranty and Disclaimer
1. The warranty period of the product is 1 year in service or 1.5 years after the product is delivered, whichever is first.2) Also, the product may have specified durability, running distance or replacement parts. Please consult your nearest sales branch.
2. For any failure or damage reported within the warranty period which is clearly our responsibility, a replacement product or necessary parts will be provided. This limited warranty applies only to our product independently, and not to any other damage incurred due to the failure of the product.
3. Prior to using SMC products, please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products.
2) Vacuum pads are excluded from this 1 year warranty.
A vacuum pad is a consumable part, so it is warranted for a year after it is delivered. Also, even within the warranty period, the wear of a product due to the use of the vacuum pad or failure due to the deterioration of rubber material are not covered by the limited warranty.
Compliance Requirements
1. The use of SMC products with production equipment for the manufacture of weapons of
mass destruction (WMD) or any other weapon is strictly prohibited.
2. The exports of SMC products or technology from one country to another are governed by
the relevant security laws and regulation of the countries involved in the transaction. Prior to the shipment of a SMC product to another country, assure that all local rules governing that export are known and followed.
Caution
SMC products are not intended for use as instruments for legal metrology.
Products that SMC manufactures or sells are not measurement instruments that are qualified by pattern approval tests relating to the measurement laws of each country. Therefore, SMC products cannot be used for business or certification ordained by the measurement laws of each country.
Page 5
-4-
No.PS※※-OMV1001
Operator
This operation manual is intended for those who have knowledge of machinery using pneumatic
equipment, and have sufficient knowledge of assembly, operation and maintenance of such equipment. Only those persons are allowed to perform assembly, operation and maintenance.
Read and understand this operation manual carefully before assembling, operating or providing
maintenance to the product.
Safety Instructions
Warning
Do not disassemble, modify (including changing the printed circuit board) or repair.
An injury or failure can result.
Do not operate the product outside of the specifications.
Do not use for flammable or harmful fluids. Fire, malfunction, or damage to the product can result. Verify the specifications before use.
Do not operate in an atmosphere containing flammable or explosive gases.
Fire or an explosion can result. This product is not designed to be explosion proof.
Do not use the product in a place where static electricity is a problem.
Otherwise it can cause failure or malfunction of the system.
If using the product in an interlocking circuit:
Provide a double interlocking system, for example a mechanical system Check the product regularly for proper operation
Otherwise malfunction can result, causing an accident.
The following instructions must be followed during maintenance:
Turn off the power supply Stop the air supply, exhaust the residual pressure and verify that the air is released before performing
maintenance
Otherwise an injury can result.
Page 6
-5-
No.PS※※-OMV1001
Caution
Do not touch the terminals and connectors while the power is on.
Otherwise electric shock, malfunction or damage to the product can result.
After maintenance is complete, perform appropriate functional inspections and leak tests.
Stop operation if the equipment does not function properly or there is a leakage of fluid. When leakage occurs from parts other than the piping, the product might be faulty. Disconnect the power supply and stop the fluid supply. Do not apply fluid under leaking conditions. Safety cannot be assured in the case of unexpected malfunction.
NOTE
Follow the instructions given below when designing, selecting and handling the product.
The instructions on design and selection (installation, wiring, environment, adjustment, operation,
maintenance, etc.) described below must also be followed.
Product specifications
The direct current power supply to combine should be UL approved as follows.
Circuit (of Class2) which is of maximum 30 Vrms (42.4 V peak) or less, with UL1310 Class2 power supply unit or UL1585 Class2 transformer.
The Pressure switch is a UL approved product only if it has a mark on the body. Use the specified voltage.
Otherwise failure or malfunction can result.
Do not exceed the specified maximum allowable load.
Otherwise it can cause damage or shorten the lifetime of the Pressure switch.
Design the product to prevent reverse current when the circuit is opened or the product is forced to operate for
operational check. Reverse current can cause malfunction or damage to the product.
Input data to the Pressure switch is not deleted, even if the power supply is cut off.
(Writing time: 1,000,000 times, Data duration: 10 years after power off)
Use the clean air
This can cause operating failure. If compressed air containing condensate is used, install an air dryer or drain catch before the filter and perform drainage regularly. If drainage is not performed regularly and condensate enters the secondary side, it can cause operating failure of pneumatic equipment. If regular drainage is difficult, the use of a filter with an auto drain is recommended.
Applicable fluid is air, inert gases and incombustible gases.
Do not use a fluid containing chemicals, synthetic oils including organic solvent, salt and corrosive gases. Otherwise, damage to the product and malfunction can result.
Check the details of the specifications before using.
Use the specified measurement flow rate and operating pressure.
Otherwise it can cause damage to the pressure switch or inability to measure correctly.
Reserve a space for maintenance.
Allow sufficient space for maintenance when designing the system.
Page 7
-6-
No.PS※※-OMV1001
Product handling
Installation
Tighten to the specified tightening torque.
If the tightening torque is exceeded the mounting screws and brackets may be broken. If the tightening torque is insufficient, the product can be displaced and loosen the mounting screws. (Refer to "Mounting and Installation" on page 14.)
Do not apply excessive stress to the product when it is mounted with a panel mount.
Otherwise damage to the product and disconnection from the panel mount can result.
Be sure to ground terminal FG when using a commercially available switch-mode power supply. Do not drop, hit or apply shock to the Pressure switch.
Otherwise damage to the internal parts can result, causing malfunction.
Do not pull the lead wire forcefully, not lift the product by pulling the lead wire. (Tensile force 35 N or less)
Hold the body when handling to avoid the damage of the Pressure switch which lead to cause the failure and malfunction.
For piping of the Pressure switch, hold the piping with a spanner on the metal part of the piping (Piping
attachment).
Holding other part with spanner leads to damage the Pressure switch.
Eliminate any dust left in the piping by air blow before connecting the piping to the product.
Otherwise it can cause damage or malfunction.
Do not apply excessive pressure to the piping port.
The product detects very small pressure. Do not apply pressure in excess of the proof pressure.
Do not insert metal wires or other foreign matter into the pressure measurement port.
It can damage the pressure sensor causing failure or malfunction.
Never mount a Pressure switch in a location that will be used as a foothold.
The product may be damaged if excessive force is applied by stepping or climbing onto it.
If the entering of foreign material to the fluid is possible, install and pipe the filter or the mist separator to
the inlet to avoid failure and malfunction.
Wiring
Do not pull the lead wires.
In particular, never lift a Pressure switch equipped with fitting and piping by holding the lead wires. Otherwise damage to the internal parts can result, causing malfunction or to be off the connector.
Avoid repeatedly bending or stretching the lead wire, or placing heavy load on them.
Repetitive bending stress or tensile stress can cause the sheath of the wire to peel off, or breakage of the wire. If the lead wire can move, fix it near the body of the product. The recommended bend radius of the lead wire is 6 times the outside diameter of the sheath, or 33 times the outside diameter of the insulation material, whichever is larger. Replace the damaged lead wire with a new one.
Wire correctly.
Incorrect wiring can break the Pressure switch.
Do not perform wiring while the power is on.
Otherwise damage to the internal parts can result, causing malfunction.
Do not route wires and cables together with power or high voltage cables.
Otherwise the product can malfunction due to interference of noise and surge voltage from power and high voltage cables to the signal line. Route the wires (piping) of the product separately from power or high voltage cables.
Confirm proper insulation of wiring.
Poor insulation (interference from another circuit, poor insulation between terminals, etc.) can lead to excess voltage or current being applied to the product, causing damage.
Design the system to prevent reverse current when the product is forced to operate for operational check.
Depending on the circuit used, insulation may not be maintained when operation is forced, allowing reverse current to flow, which can cause malfunction and damage the product.
Keep wiring as short as possible to prevent interference from electromagnetic noise and surge voltage.
Wiring has to be less than 10 m. Wire the DC(-) line(blue) as close as possible to the power supply.
When analogue output is used, install a noise filter (line noise filter, ferrite element, etc.) between the
switch-mode power supply and this product.
Environment
Do not use the product in area that is exposed to corrosive gases, chemicals, sea water, water or steam.
Otherwise failure or malfunction can result.
Page 8
-7-
No.PS※※-OMV1001
Do not use in a place where the product could be splashed by oil or chemicals.
If the product is to be used in an environment containing oils or chemicals such as coolant or cleaning solvent, even for a short time, it may be adversely affected (damage, malfunction, or hardening of the lead wires).
Do not use in an area where surges are generated.
If there is equipment which generates a large amount of surge (solenoid type lifter, high frequency induction furnace, motor, etc.) close to the Pressure switch, this may cause deterioration or breakage of the internal circuit of the Pressure switch. Avoid sources of surge generation and crossed lines.
Do not use a load which generates surge voltage.
When a surge-generating load such as a relay or solenoid is driven directly, use a Pressure switch with a built-in surge absorbing element.
The product is CE marked, but not immune to lightning strikes. Take measures against lightning strikes
in the system.
Mount the product in a place that is not exposed to vibration or impact.
Otherwise failure or malfunction can result.
Prevent foreign matter such as remnant of wires from entering the Pressure switch.
Take proper measures for the remnant not to enter the Pressure switch in order to prevent failure or malfunction.
Do not use the product in an environment that is exposed to temperature cycle.
Heat cycles other than ordinary changes in temperature can adversely affect the inside of the product.
Do not expose the product to direct sunlight.
If using in a location directly exposed to sunlight, shade the product from the sunlight. Otherwise failure or malfunction can result.
Keep within the specified fluid and ambient temperatures range.
The fluid and ambient temperatures should be 0 to 50 °C. Operation under low temperature (5 °C or less) leads to cause damage or operation failure due to frozen moist in the fluid or air. Protection against freezing is necessary. Air dryer is recommended for elimination of drain and water. Avoid sudden temperature change even within specified temperature.
Do not operate close to a heat source, or in a location exposed to radiant heat.
Otherwise malfunction can result.
Adjustment and Operation
Turn the power on after connecting a load.
Otherwise it can cause excess current causing instantaneous breakage of the Pressure switch.
Do not short-circuit the load.
Although error is displayed when the Pressure switch load is short circuit, generated excess current lead to cause the damage of the Pressure switch.
Do not press the setting buttons with a sharp pointed object.
It may damage the setting buttons.
If using the product to detect very small pressure rates, warm up the product for 10 to 15 minutes first.
There will be a drift on the display and the analogue output of approximate 1% immediately after the power supply is turned on, within 10 minutes.
Perform settings suitable for the operating conditions.
Incorrect setting can cause operation failure. For details of each setting, refer to page 19 to 48 of this manual.
Do not touch the LCD during operation.
The display can vary due to static electricity.
Maintenance
Turn off the power supply, stop the supplied air, exhaust the residual pressure and verify the release of
air before performing maintenance.
There is a risk of unexpected malfunction.
Perform regular maintenance and inspections.
There is a risk of unexpected malfunction.
Perform drainage regularly.
If condensate enters the secondary side, it can cause operating failure of pneumatic equipment.
Do not use solvents such as benzene, thinner etc. to clean the Pressure switch.
They could damage the surface of the body and erase the markings on the body. Use a soft cloth to remove stains. For heavy stains, use a cloth soaked with diluted neutral detergent and fully squeezed, then wipe up the stains again with a dry cloth.
Page 9
-8-
No.PS※※-OMV1001
Model Indication and How to order
Table1. Made to order
Symbol
Specification (Rated pressure range)
X576
±500 Pa
X577
±1 kPa
X578
±2 kPa
X579
±5 kPa
X580
±10 kPa
Page 10
-9-
No.PS※※-OMV1001
Accessories / Part numbers
If an accessory is required independently, order with the following part number.
Description
Part number
Remarks
Bracket A
ZS-38-A1
Mounting screw (M3 x 5L, 2 pcs.)
Bracket B
ZS-38-A2
Mounting screw (M3 x 5L, 2 pcs.)
Bracket C
ZS-38-A3
Mounting screw (M3 x 5L, 2 pcs.)
Panel mount adapter
ZS-27-C
Mounting screw (M3 x 8L, 2 pcs.)
Panel mount adapter + Front protective cover
ZS-27-D
Mounting screw (M3 x 8L, 2 pcs.)
Lead wire with connector
ZS-38-3L
3 cores for 1 output, 2 m
Lead wire with connector
ZS-38-4L
4 cores for 2 outputs, 2 m
Lead wire with connector + connector cover
ZS-38-3G
3 cores for 1 output, 2 m
Lead wire with connector + connector cover
ZS-38-4G
4 cores for 2 outputs, 2 m
Lead wire with connector for copy function
ZS-38-5L
3 cores (for copy function), 1 m
Lead wire with connector unit for copy function
ZS-38-U
for copy function (10 slaves max.)
Front protective cover
ZS-27-01
-
Page 11
-10-
No.PS※※-OMV1001
Summary of Product parts
Names of individual parts
Indicator LED (Green OUT1 and Red OUT2): Displays the switch output condition. LCD display: Displays the current status of pressure, setting mode, selected indication unit and error code.
Four display modes can be selected: display always in red or green, or display changing from green to red, or red to green, according to the output status.
button: Selects the mode or increases the ON/OFF set value.
Press this button to change to the peak display mode.
button: Selects the mode or decreases the ON/OFF set value.
Press this button to change to the bottom display mode.
button: Press this button to change to another mode and to set a value.
Unit indication: Displays the unit currently selected. (only for kPa unit indication).
Page 12
-11-
No.PS※※-OMV1001
Definition and terminology
Terms
Meaning
2
2-colour display
2 colours are used to indicate a value, which change according to the output status.
7
7-segment display
When "8" is shown on the display. It is called 7-segment because 8 consists of 7 pieces of "- (segments)".
A
Analogue current output
Refer to "Analogue output (function)".
Analogue output function
A function to output the voltage or current in proportion to the pressure.
Analogue voltage output
Refer to "Analogue output (function)".
Auto preset
A function to automatically set up the pressure by having equipment hold and release a workpiece via vacuum adsorption. This function is used in an application where vacuum adsorption of a workpiece is confirmed by a Pressure switch.
B
Bottom value display
Displays the minimum pressure reached up to that moment.
C
Chattering
The problem of the switch output turning ON and OFF repeatedly around the set value at high frequency due to the effect of pulsation.
Chattering prevention function
A function to delay the response time of switch output in order to prevent chattering.
Copy function
A function to copy a pressure setting value and function setting (excluding fine adjustment of display value).
D
Delay time
The setting time from when the pressure applied to the pressure switch reaches the set value, to when the ON-OFF output actually begins working. Delay time setting can prevent the output from chattering.
Digit (Minimum setting unit)
Shows how precisely the pressure can be displayed or set by the digital Pressure switch. When 1 digit = 1 kPa, the pressure is given with an increment of 1kPa, e.g., 1, 2, 3, …, 99, 100.
Digital filter
Function to add digital filtering to the fluctuation of pressure value. Smooth the fluctuation of displayed value and analogue output for sharp start up or fall of the pressure. When the function is valid, digital filtering is reflected to the ON/OFF of the switch output. Output chattering or flicker in the measurement mode display can be reduced by setting the digital filter. The response time indicates when the set value is 90% in relation to the step input.
Display accuracy
The deviation between displayed pressure value and the true pressure.
Display colour
The colour of the digital display. There are four choices: normally green, normally red, green (off) to red (on), and red (off) to green (on).
Display resolution
How fine the rated pressure range can be displayed.
Display unit
The unit of pressure used on the display.
E
Error indication
With the self-diagnostic function of the Pressure switch, this indicates that there is an error which could cause a switch failure.
F
Fine adjustment mode
Refer to "Fine adjustment of display value".
Fine adjustment of display value
A displayed pressure value can be adjusted within the range of ±5%R.D. (±5% of the displayed value). It is used if a true pressure value is known or to correct the difference of a displayed value of the measurement equipment nearby which measures the same pressure.
F.S. (full span/full scale)
Abbreviation for full span or full scale; this means the maximum fluctuation range of the Pressure switch rated value. For example, when the output voltage is 1 to 5[V], the F.S. will be 5-1 = 4[V]. (Ref: 1%F.S. = 4 × 0.01 = 0.04[V])
Function selection mode
This is a mode in which each function is set up, and is a separate menu from the pressure setup. If the setting needs to be changed, "F*", each item can be set up. The items to be set up are: display colour, operation mode, output type, response time, display resolution, fine adjustment of display value, auto preset, power-saving mode, security code number and low-cut function.
Page 13
-12-
No.PS※※-OMV1001
Terms
Meaning
H
Hysteresis
The difference between the pressure switch ON and OFF points, used to prevent chattering.
Hysteresis mode
Refer to "List of output modes" on page 27.
I
Indicator LED
The LED that turns on when the switch output is on.
Insulation resistance
Insulation resistance of the product itself. The resistance between an electricical circuit and the pressure switch body.
K
Key lock (function)
A function that locks the setting buttons so that no accidental setting changes can be made.
L
Load impedance
Refer to "Max. load impedance".
Low-cut function
Function to prevent display flicker at atmospheric pressure. 0 is displayed for pressure when the pressure is near atmospheric pressure.
M
Manual set up
Manual pressure set up without using auto preset. This term is used to distinguish from the pressure set up using auto preset.
Master Pressure switch
A Pressure switch whose settings are copied when using the copy function.
Max. applied voltage
The maximum value of applied voltage available to the output wire of the NPN output.
Max. load current
The maximum current available to the output wire of the switch output.
Max. (Min.) load impedance
The maximum (minimum) load (resistance value and impedance) which can be connected to the output (output wire) of the analogue current output.
Measurement mode
The condition in which the pressure is detected and displayed and the switch output is operating.
Min. setting unit
Refer to "digit".
N
Normal output
The switch output operation in which the switch is turned on when pressure equal to or greater than the set value is detected. In the (hysteresis mode) window comparator mode, it is the operation in which the switch is turned on when pressure is within the switch output range (P1L to P1H or P2L to P2H). (Refer to "List of output modes" on page 27.)
NPN (open collector) output
The switch output which uses the NPN transistor for output.
O
Operating mode
There are two choices, hysteresis mode and window comparator mode.
Output impedance
The resistance value of a component between the voltage output element and the analogue voltage output. It is indicated as a resistance value which is converted in accordance with the condition in which resistance is directly connected to the voltage output element. There may be an error in the output voltage depending on this output impedance and the input impedance of customers' equipment. (example: If the Pressure switch with output impedance of 1 kΩ is connected to the A/D converter to detect the analogue output of 5 V, the detected voltage by the A/D converter becomes 5(V) × 1(MΩ)/(1(kΩ) + 1(MΩ)) ≒ 4.995(V), and there is an error of approximate 0.005 V).
Output type
The operation type of the switch output. Either normal output or reversed output can be selected. (Refer to "List of output modes" on page 27.)
Page 14
-13-
No.PS※※-OMV1001
Terms
Meaning
P
Peak value display
Displays the maximum pressure reached up to that moment.
Piping-port size
The size of the port on the switch body with which a device can be connected.
PNP (open collector) output
The switch output that uses the PNP transistor for output.
Power saving mode
The condition in which the display is turned off to reduce current consumption.
Pressure-sensing part
The pressure-detecting part of a pressure-detecting element.
Pressure setting
The setting of pressure to determine the point at which the Pressure switch turns on and off.
Proof pressure
The pressure beyond which the Pressure switch will be damaged.
R
Rated pressure range
The pressure range in which the Pressure switch meets the specifications. Values outside of this range can be set if they are within the set pressure range, but cannot be guaranteed to meet the product specifications.
R.D.
The value currently displayed. For example, when the displayed value is 1.000, 5%R.D. will be 0.05, which is 5% of 1.000, while for a displayed value of 0.800 it will be 0.04.
Repeatability
Reproducibility of the displayed value for pressure and ON-OFF output operating point when the pressure changes.
Residual voltage
The difference between the ideal ON voltage and the actual voltage when the switch output is on. It depends on the load current and ideally should be "0".
Resolution
Refer to "Indication resolution".
Reversed output
The switch output operation in which the switch is turned on when pressure equal to or less than the set value is detected. In the (hysteresis mode) window comparator mode, it indicates the operation in which a switch is turned on when pressure is outside the switch output range (n1L to n1H or n2L to n2H). (Refer to "List of output modes" on page 27.)
Ripple
A type of chattering.
S
Setting of function
Refer to "Function selection mode".
Setting pressure range
The pressure range within which the switch output can be set.
Slave Pressure switch
A Pressure switch whose settings are copied to when using the copy function.
Switch output
Alternatively called "ON-OFF output".
U
Units selection function
Function to change the unit in which the value of pressure is displayed. Only a product with this function can change the unit. A product with Units selection function cannot be purchased if it is used within Japan. Pressure is indicated only by SI units in Japan.
W
Wetted part (or part exposed to fluid)
The part of the Pressure switch which is in contact with the detected fluid, such as a pressure sensor, seal, or fitting.
Window comparator mode
An output type which holds the output when the pressure is within a certain range. (Refer to "List of output modes" on page 27.)
Withstand voltage
The ability to withstand a voltage applied between an electrical circuit and the body. If more voltage is applied to the product, the product may be damaged. (voltage mentioned here is not power voltage to activate the product).
Z
Zero clear function
The function which can adjust the displayed pressure value to "0".
Page 15
-14-
No.PS※※-OMV1001
Mounting and Installation
Installation
Mounting with bracket
: The required tightening torque of the piping port is 7 to 9 Nm.
The required tightening torque of the mounting bracket screws is 0.5 to 0.7 Nm.
Fix the bracket to the Pressure switch with the set screws M3×5L (2 pcs) supplied.
Bracket A (Model: ZS-38-A1)
Bracket B (Model: ZS-38-A2)
Bracket C (Model: ZS-38-A3)
: The bracket A/B/C can be mounted in 4 ways.
Page 16
-15-
No.PS※※-OMV1001
Mounting with panel mount adapter
Fix the panel mount adapter to the Pressure switch with the set screws M3×8L (2 pcs.) supplied.
Panel mount adapter (Model: ZS-27-C)
Panel mount adapter + Front protective cover (Model: ZS-27-D)
: The panel mount adapter can be rotated by 90 degrees for mounting.
Note when removing the switch
The Pressure switch with panel mount adapter can be removed from the installation
by removing 2 screws and releasing the hooks at the sides, as illustrated. Take care not to damage the Pressure switch and panel mount adapter.
Page 17
-16-
No.PS※※-OMV1001
Wiring
Connection
Connections should only be made with the power supply turned off. Use a separate route for the Pressure switch wiring and any power or high voltage wiring. Otherwise,
malfunction may result due to noise.
Ensure that the FG terminal is connected to ground when using a commercially available switch-mode
power supply. When a switch-mode power supply is connected to the product, switching noise will be superimposed and the product specification can no longer be met. This can be prevented by inserting a noise filter, such as a line noise filter and ferrite core, between the switch-mode power supply and the product, or by using a series power supply instead of a switch-mode power supply.
Connector
Connecting/Disconnecting
When mounting the connector, insert it straight into the socket, holding the lever and connector body, and
push the connector until the lever hooks into the housing, and locks.
When removing the connector, press down the lever to release the hook from the housing and pull the
connector straight out.
Connector pin numbers
Page 18
-17-
No.PS※※-OMV1001
Internal circuit and wiring example
Z/ISE30A(F)-
- - -
X576 ~ X580
Output specification
-N
NPN open collector 1 output
Max. 28 V, 80 mA Residual voltage 1 V or less
-P
PNP open collector 1 output
Max. 80 mA Residual voltage 1 V or less
-A
NPN open collector 2 outputs
Max. 28 V, 80 mA Residual voltage 1 V or less
-B
PNP open collector 2 outputs
Max. 80 mA Residual voltage 1 V or less
Page 19
-18-
No.PS※※-OMV1001
-C
NPN open collector 1 output Max. 28 V, 80 mA
Residual voltage 1 V or less
Analogue voltage output
Output impedance approx. 1 k
-D
NPN open collector 1 output Max. 28 V, 80 mA
Residual voltage 1 V or less
Analogue current output
Max. load impedance
300  at 12 V power supply voltage 600  at 24 V power supply voltage
Min. load impedance 50
-E
PNP open collector 1 output
Max. 80 mA Residual voltage 1 V or less
Analogue voltage output
Output impedance approx. 1 k
-F
PNP open collector 1 output
Max. 80 mA Residual voltage 1 V or less
Analogue current output
Max. load impedance
300  at 12 V power supply voltage 600  at 24 V power supply voltage
Min. load impedance 50
Page 20
-19-
No.PS※※-OMV1001
Pressure Setting
Measurement mode
The measurement mode is the condition where the pressure is detected and displayed, and the switch function is operating. This is the basic mode, and other modes should be selected for setting changes and other function settings.
Setting the ON and OFF points of the Pressure switch. Operation When the pressure exceeds a set point, the Pressure switch will be turned ON. When the pressure falls below the set point by the amount of hysteresis or more, the Pressure switch will be turned OFF. The default setting of the output set value is the central value between the atmospheric pressure and the upper limit of the rated pressure range. If this condition, shown below, is acceptable, then keep these settings.
Page 21
-20-
No.PS※※-OMV1001
<Operation>
[Hysteresis mode]
1, Press the button once in measurement mode.
2, [P_1] or [n_1] and the set value are displayed in turn.
3, Press the or button to change the set value.
The button is to increase and the button is to decrease.
Press the
button once to increase by one digit, and press it continuously to keep increasing the
set value.
Press the button once to decrease by one digit, and press it continuously to keep decreasing the
set value.
Page 22
-21-
No.PS※※-OMV1001
4, Press the button to finish the setting.
For models with 2 outputs, [P_2] or [n_2] will be displayed. Set as above.
The Pressure switch operates within a set pressure range (from P1L to P1H) during window comparator mode. Set P1L (switch lower limit) and P1H (switch upper limit) with the setting procedure above. (When reversed output is selected, [n1L] and [n1H] are displayed.)
Zero clear of Display
The display is reset to zero when the and buttons are pressed simultaneously for 1 second. For the first operation, always perform zero clear with no pressure applied.
Page 23
-22-
No.PS※※-OMV1001
Function Setting
Function selection mode
In measurement mode, press the button for 2 seconds or longer to display [F 0]. Select to display the function to be changed, [F ]. Press the button for 2 seconds or longer in function selection mode to return to measurement mode.
: Some functions are not available depending on part number. All functions are displayed with [F ] followed by the function
description. If a function is not available, the function is displayed as [---].
Default setting
At the time of shipment, the following settings are provided. If this condition is acceptable, then keep these settings. To change the settings, enter function selection mode.
[F 0] Units selection function Page 24
Part number
Default setting
X576
Pa
X577 X578 X579 X580
kPa
Page 24
-23-
No.PS※※-OMV1001
[F 1] Setting of OUT1 Page 25
Item
Description
Default setting
Output mode
Select hysteresis mode or window comparator mode.
Hysteresis mode
Reversed output
Select reversed output.
Normal output
Pressure setting
Set the ON or OFF point of the switch output
X576: 250 Pa X577: 0.500 kPa X578: 1.00 kPa X579: 2.50 kPa X580: 5.00 kPa
Hysteresis
Set the hysteresis to prevent chattering.
X576: 25 Pa X577: 0.050 kPa X578: 0.10 kPa X579: 0.25 kPa X580: 0.50 kPa
Display colour
Select the display colour.
ON: Green
OFF: Red
[F 2] Setting of OUT2 Page 28
Same setting as for [F 1] OUT1. The display colour is linked to the setting of OUT1, and can not be set for OUT2.
Other parameter settings
Item
Page
Default setting
[F 3] Response time
page 29
Digital filter:1 s
Delay time: 4 ms
[F 4] Display resolution
page 32
Depends on the specification of the
special product
[F 5] Auto-preset function
page 33
Manual
[F 6] Fine adjustment of display value
page 35
0%
[F 7] Power saving mode
page 36
OFF
[F 8] Security code
page 37
OFF
[F 9] Setting of low-cut function
Page 38
OFF
[F90] Setting of all functions
page 39
OFF
[F97] Copy function
page 41
OFF
[F98] Check of output
page 43
Normal
[F99] Reset to the default setting
page 45
OFF
Page 25
-24-
No.PS※※-OMV1001
[F 0] Units selection function
Only the product with Units selection function can be set. The displayed unit can be changed, and depends on the pressure range. (Pa/kPa units are available when the product does not have the units selection function).
<Operation>
Press the or button in function selection mode to display [F 0].
Press the button. Move on to select the display unit.
Press the button to set. Return to function selection mode.
Setting of [F 0] Units selection function completed
Display unit and minimum setting unit
Part Number
Rated value
kPa
Pa
mbar
psi
inHg
mmHg
inH2O
mmH2O
X576
±500 Pa
0.001
1
(Initial
operation)
0.01
0.001
0.001
0.01
0.01
0.1
X577
±1 kPa
0.001
(Initial
operation)
1
0.01
0.001
0.001
0.01
0.01
0.1
X578
±2 kPa
0.01
(Initial
operation)
2
0.1
0.001
0.001
0.1
0.01
1
X579
±5 kPa
0.01
(Initial
operation)
-
0.1
0.001
0.01
0.1
0.1 1 X580
±10 kPa
0.01
(Initial
operation)
-
0.1
0.01
0.01
0.1
0.1
1
-: No unit for display
Select the Display Unit
Press the or
button to select the display unit.
Page 26
-25-
No.PS※※-OMV1001
[F 1] Setting of OUT1
Set output method of OUT1. The output turns on when the pressure exceeds the set value. The default setting of the output set value is the central value between the atmospheric pressure and the upper limit of the rated pressure range. The display colour depends on the condition of OUT1. The default setting of the display colour is as follows: green display when the output is ON and red display when the output is OFF. For the operation of each setting, refer to "List of output modes" on page 27.
<Operation>
Press the or button in function selection mode to display [F 1].
Press the button. Move on to setting of output mode.
Press the button to set. Move on to setting of reversed output.
Press the button to set. Move on to setting of pressure.
Pressure Setting
Set the pressure based on the setting procedure on page 20. "P" becomes "n" when reversed output is selected. ([P_1] [n_1]) Hysteresis mode: [P_1] Window comparator mode: [P1L] [P1H]
Press the button to set. Move on to setting of hysteresis.
Select output mode
Press the
or
button to select output mode.
Select reversed output
Press the
or
button to select reversed
output.
Page 27
-26-
No.PS※※-OMV1001
Press the button to set. Move on to setting of display colour.
Press the button to set. Return to function selection mode.
Setting of [F 1] operation of OUT1 completed
1: The selected parameter becomes effective after pressing the button. 2: After setting, it is possible to move to measurement mode by pressing the button for 2 seconds or longer.
Setting of Hysteresis
Press the
or
button to select hysteresis.
Selection of display colour
Press the
or
button to select display colour.
Page 28
-27-
No.PS※※-OMV1001
List of output modes
If the set point when the switch output is changed is outside the set pressure range due to switching between normal and reversed output, the hysteresis will automatically be compensated.
: The above figure shows the operation of OUT1.
For the operation of OUT2, "1" shown in the figure above becomes "2". (Ex) P_1 P_2
Page 29
-28-
No.PS※※-OMV1001
[F 2] Setting of OUT2
Set output method of OUT2. The display colour is linked to the setting of OUT1, and can not be set for OUT2
<Operation>
Press the or button in function selection mode to display [F 2].
Press the button Moves on to setting of output mode
Set [F 2] based on [F 1] setting of OUT1 (page 25 to 27)
: If there is only 1 output or the analogue output is used, the display indicates [---], and this function cannot be set.
Page 30
-29-
No.PS※※-OMV1001
[F 3] Response time
There are 2 types of setting for the response time. (1) Digital filter and (2) Delay time.
(1) Digital filter setting ("FiL")
Filter time constant can be set (90% response).
The Digital filter can be set in 2 modes. Rough adjustment mode (0, 0.2, 0.5, 1, 2, 5, 10, and 20s) and
fine adjustment mode (200 to 1000 ms, incremented by 5 ms).
Fluctuation of pressure display and analogue output can be reduced by increasing the set value of the digital filter. The chattering of the switch output can also be reduced. (Effective when the pressure fluctuation is large).
: The digital filter set value affects the response of the pressure display, analogue output and switch output. (refer to the figure below.)
(2) Delay time setting ("dt")
•Delay time of the switch output can be set.
The chattering of the switch output can also be reduced by increasing the delay time.
Fig.: Relation between the filter and response time
Page 31
-30-
No.PS※※-OMV1001
<Operation>
Press the or button in function selection mode to display [F 3].
Press the button. Move on to the setting of the filter time constant.
Rough adjustment mode
Press the button to set.
Fine adjustment mode
Press the button to set.
Press the button to set.
Press the button to set.
(1) Digital filter setting ("FiL")
Press the or button to select the desired output mode.
Rough adjustment mode setting
Press the or button to set the filter time constant (90% response).
Fine adjustment mode setting
Press the or button to set the filter time constant (90% response) with increments of 5 ms.
Page 32
-31-
No.PS※※-OMV1001
Press the button to set. Return to function selection mode.
Setting of [F 3] Response time completed
: Measurement mode can be returned from any setting item by pressing the button for 2 seconds or longer.
(2) Delay time setting ("dt")
Press the or button to select the response time of the switch output.
Page 33
-32-
No.PS※※-OMV1001
[F 4] Display resolution
This function is used to change the pressure display resolution. This can be used to prevent the digits from flickering on the display.
<Operation>
Press the or button in function selection mode to display [F 4].
Press the button. Move on to setting of display resolution.
Press the button to set. Return to function selection mode.
Setting of [F 4] Display resolution completed
: Not selectable depending on the selected display units.
Setting of display resolution may not be available depending on the units for display.
Part Number
Rated value
kPa
Pa
mbar
psi
inHg
mmHg
inH2O
mmH2O
X576
±500 Pa
×
○ ○ ○ ○ ○
X577
±1 kPa
○ × ○ ○ ○ ○ ○
X578
±2 kPa
○ × ○ ○ ○ ○ ○
×
X579
±5 kPa
○ - ○ ○ ○ ○ ○
×
X580
±10 kPa
○ - ○ ○ ○ ○ ○
× ○: Setting available
×: Setting not available
-: No units for display
Setting of display resolution
Press the
or
button to select display
resolution.
Page 34
-33-
No.PS※※-OMV1001
[F 5] Auto-preset function
When hysteresis mode is selected, the auto-preset function can calculate an optimum pressure value automatically based on the on-going operation.
<Operation>
Press the or button in function selection mode to display [F 5].
Press the button. Move on to setting of auto-preset.
Press the button to set. Return to function selection mode.
Setting of [F 5] Auto-preset function completed
Press the
button during measurement mode to set the pressure.
Then press the
button again to change the pressure setting, while the display is flashing.
Setting of Auto-preset
Press the
or
button to select auto-preset.
Page 35
-34-
No.PS※※-OMV1001
Auto-preset
When auto-preset is selected in function selection mode, the set pressure can be calculated and stored from a measured pressure value. The set value is automatically optimized by repeating the suction and release of the workpiece during setting.
1, Selection of auto-preset OUT1
Press the button in measurement mode to display "AP1". (If OUT1 does not need to be set, press the and buttons simultaneously for 1 second or longer to move to "AP2").
2, Preparation of OUT1 device
Prepare the device for which the pressure of OUT1 is to be set.
3, Setting of auto-preset value for OUT1
Press the button to display "A1L". After measurement starts, operate the device and change the pressure. When the pressure change is detected, "A1H" will appear automatically, and so continue to operate the device. (If the and buttons are pressed simultaneously for 1 second or longer while "A1L" is displayed, measurement is stopped and "AP2" will appear).
4, Selection of auto-preset OUT2
Press the button to set "P_1" and "H_1" ("n_1" and "H_1" for reversed mode) and display "AP2". (If OUT2 does not need to be set, press the and buttons simultaneously for 1 second or longer to return to measurement mode).
5, Preparation and setting of OUT2 device
Prepare the device for which the pressure of OUT2 is to be set, and perform the setting of OUT2 in the same way as for OUT1. After "A2L" is displayed and measurement starts, the pressure change will be detected, and "A2H" will appear automatically. (If the and buttons are pressed simultaneously for 1 second or longer when "A2L" is displayed, measurement is stopped and the display will return to measurement mode).
6, Completion of setting
Press the button to set "P_2" and "H_2" ("n_2" and "H_2" for reversed output) and complete auto-preset mode. After that, the display will return to measurement mode.
The set values for OUT1 are displayed in auto-preset mode as follows:
Normal output Reversed output
P_1 = A-(A-B)/4 n_1 = B+(A-B)/4 A = Max. pressure H_1 = (A-B)/2 H_1 = (A-B)/2 B = Min. pressure
The set values of OUT2 become as follows "_", i.e. "P_2", "n_2", "H_2".
If this setting is not necessary, press the and buttons simultaneously for 1 second or longer.
Page 36
-35-
No.PS※※-OMV1001
[F 6] Fine adjustment of display value
This function is used to manually perform fine adjustment of the displayed pressure. It is adjustable within the range ±5%R.D.
<Operation>
Press the or button in function selection mode to display [F 6].
Press the button. Move on to setting of fine adjustment of display value.
Press the button to set
Press the button to set. Return to function selection mode.
Setting of [F 6] Fine adjustment of display value completed
Setting of fine adjustment of display value
Press the
or
button to change the set
pressure value.
If the and buttons are pressed simultaneously for 1 second or longer while [FSC] is displayed, the adjusted value is set.
Page 37
-36-
No.PS※※-OMV1001
[F 7] Power saving mode
Power saving mode is selectable. When the Pressure switch is left for 30 seconds with no key operation, it will enter power saving mode.
<Operation>
Press the or button in function selection mode to display [F 7].
Press the button. Move on to setting of power saving mode.
Press the button to set. Return to function selection mode.
Setting of [F 7] Power saving mode completed
In power saving mode, any key operation will return the normal display. If there is no key operation for 30 seconds, the display will return to power saving mode (only in measurement mode).
In power saving mode, only the decimal points and indicator LEDs will flash (the LEDs flash only when the switch is ON).
: The indicator LEDs will flash when the switch is ON, but it is not synchronized with the output.
Setting of power saving mode
Press the
or
button to select power saving
mode.
Page 38
-37-
No.PS※※-OMV1001
[F 8] Security code
A security code can be selected, which must be entered to unlock the keys when the keys are locked.
<Operation>
Press the or button in function selection mode to display [F 8].
Press the button. Move on to setting of security code.
Press the button to set. Return to function selection mode.
Setting of [F 8] Security code completed
If the security code is used, it becomes necessary to enter the security code to release the key lock. The security code can be decided optionally by the operator. The default setting is "0000".
Refer to page 47 for the security code input.
Setting of security code
Press the
or
button to select security code.
Page 39
-38-
No.PS※※-OMV1001
[F 9] Setting of low-cut function
This function is used to prevent display flicker at atmospheric pressure. The displayed value of the pressure range in the table below will be "0" when the low-cut function is on.
Low-cut function
Part number
Rated value
kPa
Pa
mbar
psi
inHg
mmHg
inH2O
mmH2O
X576
±500 Pa
±0.003
±3
±0.03
×
±0.001
±0.02
±0.01
±0.3
X577
±1 kPa
±0.005
±5
±0.05
±0.001
±0.001
±0.04
±0.02
±0.5
X578
±2 kPa
±0.01
±10
±0.1
±0.001
±0.003
±0.1
±0.04
±1
X579
±5 kPa
±0.03
-
±0.3
±0.004
±0.01
±0.2
±0.1
±3
X580
±10 kPa
±0.05
-
±0.5
±0.01
±0.01
±0.4
±0.2
±5
×: Low-cut function not available
-: No units for display
<Operation>
Press the or button in function selection mode to display [F 9].
Press the button. Move on to the setting of the low-cut function.
Press the button to set. Return to function selection mode.
[F 9] Low-cut setting completes
: Measurement mode can be returned from any setting items by pressing and holding the S button for 2 seconds or longer.
Setting of low-cut function
Press the or button to select low-cut function.
Page 40
-39-
No.PS※※-OMV1001
Special function setting
[F90] Setting of all functions
All functions can be set, one after the other.
<Operation>
Press the or button in function selection mode to display [F90].
Press the button. Move on to setting of all functions.
[oFF] (unused) selected.
Press the button to set.
Return to function selection mode.
[on] (used) selected
Setting of each function
1
After the change to [oFF] (unused),
press the button to set.
Return to function selection mode.
Press the
button for 2 seconds or longer.
[F90] Setting of all functions completed Measurement mode
1: Setting of functions
Every time the button is pressed, the function steps in the order of Function setting on page 40. Set using the or buttons. Refer to each section for further details of the setting.
Setting of all functions
Press the
or
button to select all functions.
Page 41
-40-
No.PS※※-OMV1001
Order of Function setting
Order
Function
Applicable model
1
Selection of display unit
All models
2
Select output mode (OUT1)
All models
3
Select reversed output (OUT1)
All models
4
Setting of pressure (OUT1)
All models
5
Setting of hysteresis (OUT1)
All models
6
Setting of display colour
All models
7
Select output mode (OUT2)
Only for the product
with output specification
of NPN2 and PNP2
8
Select reversed output (OUT2)
9
Setting of pressure (OUT2)
10
Setting of hysteresis (OUT2)
11
Response time
All models
12
Display resolution
All models
13
Auto-preset function
All models
14
Fine adjustment of display value
All models
15
Power saving mode
All models
16
Security code
All models
17
Setting of low-cut function
All models
: Measurement mode will return from any setting by pressing the button for 2 seconds or longer. : Function that will be set by the return to the measurement mode.
Page 42
-41-
No.PS※※-OMV1001
[F97] Copy function
The set values of pressure and functions (except for corrected value of fine adjustment of display value) can be copied. When the pressure range, output and unit specifications are the same, this function becomes available. The set value can be copied to up to 10 pressure switches simultaneously.
<Connection>
Connect the Pressure switches with the power supply turned off. Connect the FUNC terminals of the master Pressure switch and the slave Pressure switches, and then turn on the power supply. The master Pressure switch is the switch from which the setting is to be copied. The slave Pressure switch is the switch to which the setting is to be copied.
<Operation>
Press the or button of the master Pressure switch in function selection mode to display [F97].
Press the button. Move on to the selection of copy function.
Press the button to set.
Selection of copy function
Press the
or
button to select copy function.
Page 43
-42-
No.PS※※-OMV1001
Press the
button to start copying.
The master Pressure switch
The slave Pressure switch
Sending/
Receiving
Copy
completed
(Red)
(Green)
Press the button.
To complete the copy function, press the and buttons simultaneously for 1 second or longer. Setting of [F97] Copy function completed
: If the copy to the slave pressure switch is not completed, it is detected as a copy function sending/receiving error.
Press the and buttons simultaneously for 1 second or longer to return to measurement mode. Then, check the wiring and specifications of the switch and retry the copy function.
The copy can be made continuously and the copy ready status can be held even if the power supply is turned off.
Press the
and buttons simultaneously for 1 second or longer.
Press the button.
Flashing
(Red)
Flashing
(Green)
The copy ready status is held even if the power supply is turned off.
Page 44
-43-
No.PS※※-OMV1001
[F98] Check of output
<Operation>
Press the or button in function selection mode to display [F98].
Press the button. Move on to check of output.
If [A] (normal output) is selected,
Press the button to set.
Return to function selection mode.
If [F] (forcibly output) is selected.
Press the button to set.
If OUT2 output is not provided,
press the button to set after returning to [A] (normal output).
Return to function selection mode.
If OUT2 output is provided,
press the button to set.
Check of output
Press the or button to select check of output.
OUT1 check of output
Press the or button to select OUT1 check of output.
Page 45
-44-
No.PS※※-OMV1001
: For the analogue output type: oFF will be at 1 V or 4 mA , and on
will be at 5 V or 20 mA.
Press the button to set after returning to [A] (normal output).
Return to function selection mode.
Press the
button for 2 seconds or longer.
Setting of [F98] Check of output completed Measurement mode
: If the button is pressed for 2 seconds or longer, the mode is returned to measurement mode regardless of the current mode.
OUT2 check of output
Press the or
button to
select OUT2 check of output.
Page 46
-45-
No.PS※※-OMV1001
[F99] Reset to the default setting
If the setting of the pressure switch becomes unknown, the default setting can be restored.
<Operation>
Press the or button in function selection mode to display [F99].
Press the button. Move on to reset to the default setting.
[oFF] (unused) selected Press the button to set Return to function selection
mode.
The setting is reset to the default setting, and the mode returns to the function selection mode.
Setting of [F99] Reset to the default setting completed
Reset to the default setting
Set the display [ON] by pressing the or button, then press the and buttons
simultaneously for 5 seconds or longer.
Page 47
-46-
No.PS※※-OMV1001
Other Settings
Peak/Bottom value display
The maximum (minimum) pressure from when the power was supplied to this moment is detected and updated. In peak/bottom display mode, this pressure is displayed. For peak display, when the button is pressed for 1 second or longer, the maximum pressure and "Hi" starts flashing, and is held. To release holding the display of the maximum pressure, press the button for 1 second or longer again to return to measurement mode. For bottom display, when the button is pressed for 1 second or longer, the minimum pressure and "Lo" starts flashing, and is held. To release holding the display of the minimum pressure, press the button for 1 second or longer again to return to measurement mode. If the and buttons are pressed simultaneously for 1 second or longer while the pressure is being held, the maximum (minimum) values are reset.
Zero clear
The displayed value can be adjusted to zero when the measured pressure is within 3.5%F.S. of the pressure, at the time of shipment from the factory. (A tolerance range of 1%F.S. may apply due to individual product differences). Press the and buttons simultaneously for 1 second or longer, to clear the display to "0". The display will return to measurement mode automatically. For analogue output, the analogue output will be changed along with the display.
Key lock
The key lock function is used to prevent errors occurring due to unintentional changes of the set values. If a button operation is performed while the key lock setting is ON, "LoC" is displayed for approximately 1 second. (When the button is pressed, the set pressure will be displayed following "LoC").
<Operation - Without security code input- >
1, Press the button for 5 seconds or longer in measurement mode.
The current setting "LoC" or "UnL" will be displayed. (Selecting or releasing the key lock is carried out in a similar way).
2, Press the or button to select key lock (or key unlock).
3, Press the button to store the setting.
Page 48
-47-
No.PS※※-OMV1001
<Operation - With security code input- >
Locking
1, Press the button for 5 seconds or longer in measurement mode.
The current setting “UnL is displayed.
2, Press the or button to select keys lock LoC.
3, Press the button to store the setting.
Unlocking
1, Press the button for 5 seconds or longer in measurement mode.
The current setting “LoC is displayed.
2, Press the or button to select keys unlock UnL.
3, When the button is pressed, input of the security code will be requested.
For how to enter the security code, refer to "How to enter the security code" on page 48.
4, If the security code entered is correct, the display will change to UnL. Press any of the , or
buttons to release the key lock and return to measurement mode. If the security code entered is incorrect, FAL will be displayed and the security code must be entered again. If an incorrect security code is entered three times, LoC is be displayed and the display will return to measurement mode.
Page 49
-48-
No.PS※※-OMV1001
How to change the security code
At the time of shipment, the security code is set to 0000, but this can be changed to any number.
<Operation>
1, After the key lock setting has been completed, perform the first three steps in the unlocking
procedure (page 47).
2, After the security code has been entered and the display changes to UnL, press the and
buttons simultaneously for 5 seconds or longer. 0000 is displayed and a new security code can now be entered. For how to enter the security code, refer to "How to enter the security code". The new security code will be displayed.
3, After checking the security code is as required, press the button for 1 second or longer.
The display will return to measurement mode. At this time, if the or button is pressed, any security code changes are lost, and the change of security code procedure must be repeated.
How to enter the security code
The first digit will start flashing. Press the or button to select a value. Press the button to set and the next digit will start flashing. (If the button is pressed at the last digit, the first digit will start flashing again).
After the setting is completed, press the button for 1 second or longer. (If a key operation is not performed for 30 seconds while entering the security code, the measurement mode will return).
Page 50
-49-
No.PS※※-OMV1001
Maintenance
How to reset the product after a power cut or forcible de-energizing
The setting of the product will be retained as it was before a power cut or de-energizing. The output condition is also basically recovered to that before a power cut or de-energizing, but may change depending on the operating environment. Therefore, check the safety of the whole installation before operating the product. If the installation is using accurate control, wait until the product has warmed up (approximately 10 to 15 minutes).
Page 51
-50-
No.PS※※-OMV1001
If the security code is forgotten
The following procedure can be used when the security code has been forgotten.
<Operation>
Press the button for 5 seconds or longer in measurement mode. The current setting "UnL" or "LoC" is displayed.
Press the and buttons simultaneously for 5 seconds or longer. Then, press the and buttons simultaneously for 5 seconds or longer.
: There will be no change to the display.
(at this time, if another operation is performed or no key operation is performed for 30 seconds, the display will return to measurement mode).
Press the and buttons simultaneously for 5 seconds or longer. The display will change to "0000" and the security code change mode will return. (at this time, if another operation is performed or no key operation is performed for 30 seconds, the display will return to measurement mode).
Refer to "How to change the security code" (page 48) and select a new security code. The new security code will be displayed.
Check the security code is as required, and press the button for 1 second or longer.
The display will return to measurement mode. At this time, if the or button is pressed, any security code changes will be lost, and the change of
security code procedure must be repeated.
Page 52
-51-
No.PS※※-OMV1001
Troubleshooting
If the cause of the failure cannot be identified and normal operation can be recovered by replacement with a new Pressure switch, this indicates that the Pressure switch itself is faulty. Pressure switch damage can be caused by the operating environment (network construction, etc.), therefore contact SMC.
Yes
No
The pressure
switch does not
operate correctly
Refer to Fault
No.1
The switch output
is ON
The Indicator LED
is ON
The indicator LED
operates incorrectly
The switch output
is OFF
The switch output
is chattering
The Indicator LED
is OFF
The Indicator
LED is OFF
The Indicator LED
is ON
The product is
faulty
Refer to Fault
No.2
Refer to Fault
No.1
Refer to Fault
No.4
Refer to Fault
No.3
The product is
faulty
The product is
faulty
Analogue output
is not provided
(specified accuracy
is not satisfied)
Refer to Fault
No.6
Slow switch
output response
Refer to Fault
No.5
An Error is
displayed
Refer to Fault
No.7
Page 53
-52-
No.PS※※-OMV1001
The units cannot
be changed
The buttons cannot
be operated
The display
fluctuates
The product is
noisy
The product
Is loose
The display
disappears
The display
flashes
Pressure display
difference when using
2 or more pressure
switches
Refer to Fault
No.8
The display is
not normal
Refer to Fault
No.9
Refer to Fault
No.9
Refer to Fault
No.11
Refer to Fault
No.14
Refer to Fault
No.13
Refer to Fault
No.15
Refer to Fault
No.16
The display
breaks off
Refer to Fault
No.19
Refer to Fault
No.10
The display accuracy
does not satisfy the
specifications
Refer to Fault
No.12
Copy function error
Not able to copy
Slave pressure
switch does not
complete copying
Refer to Fault
No.17
Refer to Fault
No.18
Yes
No
Page 54
-53-
No.PS※※-OMV1001
Faults and countermeasures
Fault No. Fault
Possible cause
Investigation method
Countermeasure
1
Output remains
ON.
Indicator LED remains ON.
Output remains
OFF.
Indicator LED remains OFF.
Incorrect pressure setting
(1) Check the set pressure. (2) Check the operation mode,
hysteresis and output type. (hysteresis mode / window comparator mode, normal / reversed output)
(1) Reset the pressure
setting.
(2) Reset the function
settings.
Product failure
Replace the product.
2
Output remains ON. Indicator LED works correctly.
Incorrect wiring
Check the wiring of the output. Check if the load is connected directly to DC(+) or DC(-).
Correct the wiring. Product failure
Replace the product.
3
Output remains OFF. Indicator LED works correctly.
Incorrect wiring
Check the wiring of the output. Check if the load is connected directly to DC(+) or DC(-).
Correct the wiring.
Unsuitable model selection
Check if PNP is used when NPN should have been selected, or the other way around.
Review the selected model (output type).
Broken lead wire
Check if there is bending stress applied to any parts of the lead wire. (bending radius and tensile force applied).
Correct the wiring conditions. (adjust the tensile force and increase the bending radius).
Product failure
Replace the product.
4
Switch output generates chattering.
Incorrect wiring
Check the wiring. Check that the brown and blue wires are connected to DC(+) and DC(-) respectively, and if the output wiring is loose (contact failure).
Correct the wiring.
Incorrect settings
(1) Check the set pressure. (2) Check that the hysteresis range
is not too narrow.
(3) Check the digital filter and delay
time setting. Check if the digital filter and delay time are too short.
(1) Reset the pressure
setting.
(2) Increase the hysteresis. (3) Reset the function
settings.
Product failure
Replace the product.
5
Slow switch output response
Incorrect pressure setting
Check the pressure setting. Check that the detected pressure and the set pressure value are not the same or not too close.
Reset the pressure setting. Set the pressure setting value so it is not too close to the detected pressure.
Page 55
-54-
No.PS※※-OMV1001
Fault No. Fault
Possible cause
Investigation method
Countermeasure
6
Analogue output (OUT2) is not provided. (specified accuracy is not satisfied).
Incorrect wiring
Check that the analogue output (OUT2) is connected to a load.
Correct the wiring.
Non-compliance with the load specification.
(1) Check that the correct load is
connected.
(2) Check that the impedance of the
input equipment (A/D transformer) is suitable.
Connect a suitable load.
Insufficient warm-up time
Check if the product satisfies the specified accuracy after 10 minutes warm up time.
After energizing, the display and output can drift. For detecting fine pressures, warm up the product for 10 to 15 minutes.
Product failure
Replace the product.
7
An over current
error (Er1, Er2) is displayed.
System error
(Er0, Er4, Er6, Er7, Er8 or Er9) is displayed.
The display
shows "HHH".
The display
shows "LLL".
Residual
pressure error (Er3) is displayed.
Over current to the output (Er1, Er2)
(1) Check that the switch output load
current is not more than 80 mA.
(2) Check that the connected load
satisfies the specifications, and check the load for short circuits.
(3) Check that any relay is connected
with a surge voltage suppressor.
(4) Check if the wiring is not in the
same route as (or bundled together with) a high voltage cable or power cable.
(1)(2) Connect the load as
specified.
(3) Use a relay with a surge
voltage suppressor or take measures to prevent noise.
(4) Separate the wiring route
from any high voltage cable or power cable.
Incorrect operation of the internal data of the Pressure switch (Er0, Er4, Er6, Er7, Er8, Er9)
(1) Check that there is no noise
interference such as static electricity, and check for noise sources.
(2) Check that the power supply
voltage is within the range 12 to 24 VDC ±10%.
(1) Remove the noise and the
noise source (or take measures to prevent noise interference), and reset the product, or turn off the power supply and turn it on again.
(2) Supply a correct voltage
of 12 to 24 VDC ±10%.
Applied pressure is above the upper limit (HHH).
(1) Check that the pressure is not
above the upper limit of the set pressure range.
(2) Check that foreign matter has not
entered the piping.
(1) Adjust the pressure to
within the set pressure range.
(2) Take measures to prevent
foreign matter from entering the piping.
Applied pressure is below the lower limit (LLL).
(1) Check that the pressure is not
below the lower limit of the set pressure range.
(2) Check that foreign matter has not
entered the piping.
(1) Adjust the pressure to
within the set pressure range.
(2) Take measures to prevent
foreign matter from entering the piping.
Pressure is not atmospheric pressure at zero-clear operation (Er3)
Check that during the zero clear operation, pressure above ±3.5%F.S. was not applied.
Return the applied pressure to atmospheric pressure, and retry the zero clear operation.
Product failure
Replace the product.
Page 56
-55-
No.PS※※-OMV1001
Fault No. Fault
Possible cause
Investigation method
Countermeasure
8
Displayed value fluctuates.
Incorrect power supply
Check that the power supply voltage is within the range 12 to 24 VDC ±10%.
Supply the correct voltage of 12 to 24 VDC ±10%.
Incorrect wiring
Check the wiring to the power supply. Check that the brown and blue wires are connected to DC(+) and DC(-) respectively and that the output wiring is not loose (contact failure).
Correct the wiring.
Factory pressure change
Check if the factory pressure has changed.
If the fluctuation is not acceptable, the pressure switch display resolution can be changed.
Product is exposed to the wind
Check if the product is exposed to the wind.
(3) Do not expose the product to
the wind.
(2) Change the number of digits
by setting the display resolution.
9
Display turns
OFF.
Part of the
display is missing.
Incorrect power supply
Check that the power supply voltage is within the range of 12 to 24 VDC ±10%.
Supply the correct voltage of 12 to 24 VDC ±10%.
Power saving mode
Check if the power saving mode is selected.
Reset the function settings.
Incorrect wiring
Check the power supply wiring. Check that the brown and blue wires are connected to DC(+) and DC(-) respectively and that the output wiring is not loose (contact failure).
Correct the wiring.
Product failure
Replace the product.
10
Display is flashing.
The peak / bottom value display mode is selected.
Check if the peak value or bottom value display mode has been selected.
Turn off the peak / bottom value display mode if not required.
Wiring failure
(1) Check the power supply wiring. (2) Check if there is bending stress
applied to any parts of the lead wire.
(1) Correct the wiring (2) Correct the wiring
conditions (reduce the tensile force and increase the bending radius).
11
Pressure display difference when using 2 or more Pressure switches.
Dispersion within the display accuracy range
Check if the dispersion is within the display accuracy range.
Use the fine adjustment mode to adjust the display if the dispersion is within the display accuracy range.
Product failure
Replace the product.
Page 57
-56-
No.PS※※-OMV1001
Fault No. Fault
Possible cause
Investigation method
Countermeasure
12
The pressure display accuracy does not satisfy the specifications.
Foreign matter
Check if any foreign matter has entered the pressure port.
Install a 5 m filter to prevent foreign matter from entering the pressure port. Also, clean the filter regularly to prevent drainage deposits.
Air or fluid leakage
Check if air or fluid are leaking from the piping.
Rework the piping. If an excessive tightening torque is applied, the mounting bracket, screws or the product may be damaged.
Insufficient warm-up time
Check if the product satisfies the specified accuracy after 10 minutes warm up time.
After energizing, the display and output can drift. For detecting fine pressures, warm up the product for 10 to 15 minutes.
Product failure
Replace the product.
13
The display units cannot be changed.
Improper model selection (selection of model without “units selection function")
Check if there is an "-M" at the end of the part number printed on the product.
"M" in the part number means that the units cannot be changed.
: The unit change function is
not available in Japan due to a new measurement law.
Product failure
Replace the product.
14
The buttons cannot be operated.
Key lock mode
Check if the key lock mode is turned on.
Turn off the key lock mode. Product failure
Replace the product.
15
The product is loose.
Incorrect installation
Check that the panel mount adapter and the product are correctly assembled.
Mount the product on the panel correctly.
Product failure
Replace the product.
16
The product is noisy.
Air or fluid leakage
Check if air or fluid are leaking from the piping.
Rework the piping. If an excessive tightening torque is applied, the mounting bracket, screws or the product may be damaged.
Product failure
Replace the product.
17
Copy function
error
Unable to copy
Incorrect wiring
(1) Check the wiring connection at
the FUNC terminal.
(2) Check the power supply wiring.
Correct the wiring. Product failure
Replace the product.
Page 58
-57-
No.PS※※-OMV1001
Fault No. Fault
Possible cause
Investigation method
Countermeasure
18
Slave Pressure switch does not complete the copy function.
Incorrect wiring
(1) Check the wiring connection at
the FUNC terminal.
Check the power supply wiring.
(2) Check the lead wire lengths.
(1) Correct the wiring. (2) The maximum
transmitting distance of the copy function is 4 m. Shorten the lead wire to 4 m or less.
Improper model selected
The model number of the master Pressure switch and the slave Pressure switch are different from each other.
Check the model numbers. Copying is available when the pressure range, output specification and units specification are identical.
Too many pressure switches connected
Check the number of connected slave Pressure switches.
The number of connected products for which copying is possible is up to 10 pcs. Reduce the number to 10 pcs or less.
Product failure
Replace the product.
19
The operation is unstable.
(chattering) Pressure source fluctuation, small hysteresis or the response time is too short.
(1) Check the set pressure
(hysteresis)
(2) Check the digital filter and delay
time.
(1) Check the pressure
setting.
(2) Reset the function
settings.
Incorrect wiring
or broken lead
wire
(1) Check the power supply wiring.
(2) Check if there is bending stress applied to any parts of the lead wire.
(1) Correct the wiring
(2) Correct the wiring
conditions (reduce the tensile force and increase the bending radius).
Product failure
Replace the product.
Page 59
-58-
No.PS※※-OMV1001
Error indication
This function is to display error location and content when a problem or an error occurs.
Error Name
Error Display
Error Type
Troubleshooting Method
Over current
Error
The switch output load current is
more than 80 mA.
Turn the power off and remove the cause
of the over current.
Then turn the power on.
Residual
Pressure Error
During zero clear operation, pressure
above ±3.5%F.S. has been applied.
After 1 second, the mode will return
to measurement mode. The zero
clear range can vary ±1%F.S. with
individual product differences.
Perform zero clear operation again after
restoring the applied pressure to an
atmospheric pressure condition.
Pressurizing Error
Pressure has exceeded the upper
limit of the set pressure range.
Adjust the applied pressure to a level
within the set pressure range.
Pressure has exceeded the lower
limit of the set pressure range.
System Error
Displayed in the case of an internal
data error.
Turn the power off and turn it on again.
If resetting fails, an investigation by SMC
Corporation will be required.
If the error can not be reset after the above measures are taken, then please contact SMC.
Page 60
-59-
No.PS※※-OMV1001
Specification
Model No.
X576
X577
X578
X579
X580
Rated pressure range
±500 Pa
±1.000 kPa
±2.00 kPa
±5.00 kPa
±10.00 kPa
Set pressure range (Refer to page 61)
±525 Pa
±1.050 kPa
±2.10 kPa
±5.25 kPa
±10.50 MPa
Withstand pressure
2.5 kPa
5 kPa
10 kPa
25 kPa
50 kPa
Applicable fluid
1 Pa
0.001 kPa
0.01 kPa
0.01 kPa
0.01 kPa
Power supply voltage
Air, inert gases and incombustible gases
Current consumption
12 to 24 VDC ±10%, ripple (p-p) 10% or less
Switch output
40 mA or less
Digital filter
Rough adjustment mode: 0, 0.2, 0.5, 1, 2, 5, 10, 20 s Fine adjustment mode: 200 to 1000 ms (increments of 5 ms) : The digital filter set value affects the response of the pressure display,
analogue output and switch output. (See Figure on page 60)
Switch output
NPN or PNP open collector output: 1 output NPN or PNP open collector output: 2 outputs
Max. load current
80 mA
Max. applied voltage
28 V (NPN output)
Residual voltage
1 V or less (at 80 mA load current)
Delay time
4 ms or less
(with anti-chatter function: 20 ms, 100 ms, 500 ms, 1000 ms, 2000 ms,
10 s, 30 s or 60 s selected)
Short circuit protection
Provided
Repeatability
±1%F.S. ±1 digit
Hys teresis
Hysteresis mode
0 to variable
1
Window comparator mode
OUT2
Voltage output
2
Output Voltage (rated pressure range)
1 to 5 V ±2.5F.S.
Linearity
±1.5F.S.
±1F.S.
Output impedance
approx. 1 k
Current output 3
Output current (rated pressure range)
4 to 20 mA ±2.5F.S.
Linearity
±1.5F.S.
±1%F.S.
Load impedance
Max. load impedance: 300 (at power supply voltage of 12 VDC)
600 (at power supply voltage of 24 VDC)
Min. load impedance: 50
Display
4 digits, 7-segment, dual-colour display (red/green)
Display accuracy
±2%F.S. ±1digit (at ambient temperature 25±3 C)
Indicator LED
LED is ON when output is ON OUT1: Green OUT2: Red
1: If the applied voltage fluctuates around the set value, the hysteresis must be set to more than the fluctuation width. Otherwise,
chattering will occur.
2: If analogue voltage output is selected, the analogue current output cannot be selected. 3: If analogue current output is selected, the analogue voltage output cannot be selected.
Page 61
-60-
No.PS※※-OMV1001
Model No.
X576
X577
X578
X579
X580
Environ ment
Enclosure
IP40
Ambient temperature range
Operation: 0 to 50 C, Storage: -10 to 60 C (no condensation or freezing)
Ambient humidity range
Operation, Storage: 35 to 85%RH (no condensation)
Withstand voltage
1000 VAC, 1 minute between terminals and housing
Insulation resistance
50 M or more at 500 VDC between terminals and housing
Temperature characteristics
±3%F.S. (25 C reference)
Lead wire
Oil resistant vinyl cabtyre cable
3 cores 3.5, 2 m 4 cores Sectional area of conductor: 0.15 mm2 (AWG26)
Outside diameter of insulator: 1.0 mm
Fig.: Relation between the filter and response time
Piping specifications
Model No.
01
N01
Port size
R1/8
M5 x 0.8
NPT1/8
M5 x 0.8
Material of wetted parts
Pressure sensing part
Silicone
Piping port
C3602
(electroless nickel plating)
O-ring: HNBR
Weight With lead wire and connector attached
(3-core, 2 m)
81 g
With lead wire and connector attached (4-core, 2 m)
85 g
Without lead wire and connector
43 g
Page 62
-61-
No.PS※※-OMV1001
Settable pressure range per unit
Part number
Rated value
kPa
Pa
mbar
psi
inHg
mmHg
inH2O
mmH2O
X576
±500 Pa
±0.525
±525
±5.25
±0.076
±0.155
±3.94
±2.11
±53.5
X577
±1 kPa
±1.050
±1050
±10.50
±0.152
±0.310
±7.88
±4.22
±107.1
X578
±2 kPa
±2.10
-1998 to 2100
±21.0
±0.305
±0.620
±15.8
±8.43
±214
X579
±5 kPa
±5.25
-
±52.5
±0.761
±1.55
±39.4
±21.1
±535
X580
±10 kPa
±10.50
-
±105.0
±1.52
±31.0
±78.8
±42.2
±1071
-: No units for display
Analogue output
Voltage output
Current output
Range
Rated pressure range
A B C
X576
±500 Pa
-500 Pa
0 Pa
500 Pa
X577
±1 kPa
-1 kPa
0 kPa
1 kPa
X578
±2 kPa
-2 kPa
0 kPa
2 kPa
X579
±5 kPa
-5 kPa
0 kPa
5 kPa
X580
±10 kPa
-10 kPa
0 kPa
10 kPa
Page 63
-62-
No.PS※※-OMV1001
Dimensions
Body dimensions
Page 64
-63-
No.PS※※-OMV1001
○Mounting brackets
Bracket A
Bracket B
Page 65
-64-
No.PS※※-OMV1001
Bracket C
Page 66
-65-
No.PS※※-OMV1001
Panel mount adapter
Panel mount adapter + Front protective cover
Page 67
-66-
No.PS※※-OMV1001
Panel cut-out dimensions
Single Pressure switch
Two or more in a row n: The number of the Pressure switch
<Horizontal>
<Vertical>
Page 68
No.PS※※-OMV1001
Revision history
4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021 JAPAN Tel: + 81 3 5207 8249 Fax: +81 3 5298 5362 URL http://www.smcworld.com
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2017 SMC Corporation All Rights Reserved.
Loading...