SMC Networks VFS2100, VFS2200, VFS2300 Installation And Maintenance Manual

Wiring (Fig 4)
CAUTION
Isolate both power and air supplies before removing/replacing connector.
In the case of DIN connector and terminal block (with lamp and surge voltage suppressor), the internal wiring is shown in Fig 4.
1. Loosen the top screw and remove the connector housing from the terminal spades on the solenoid.
3. Loosen the terminal screws on the block and insert the stripped leads. Secure each lead by re-tightening the appropriate terminal screw.
4. Tighten the housing grommet nut to secure the cable.
CAUTION
Pull connector out vertically,never at an angle.
Wiring plug-in type (Fig 5)
Remove cover 1 (Fig. 6) on subplate to expose terminal block 2 (Fig. 6).
The terminal block is marked as follows:-
Designation Solenoid Solenoid
A-side B-side
Terminal block board A B Marking
• Note: Non polar
Lead wire wiring/manifold/plug-in type
Type 01 insert plug with lead wire
Series VFS2000 (only VFS2000)
How to remove junction cover (type 01 Fig 7)
Turn the knob 2 of junction cover 1 on the manifold block side by hand or slotted screwdriver to the C R O direction (counter clockwise) 90°.While holding the knob and upper part of junction cover, pull out­ward to remove junction cover.When reassembling, do the opposite.
Wiring (Fig 8)
The insert plug 1 is attached to the manifold block and lead wire is plugged in with valve side as shown in the following list: Single solenoid Double solenoid Please connect with corresponding power side.
AC power/lead wire colour identification
Solenoid A side B side
Lead wire colour Red,black -
DC power/lead wire colour identification
Solenoid A side B side
Lead wire colour Red Black Brown White
• Lead wire length is 1m.
• No polarity.
Installation and Maintenance Manual Series VFS2000 5 Port Metal Seal Type Solenoid Valves
This manual should be read in conjunction with the current catalogue
For future reference, please keep this manual in a safe place
Safety Instructions
These safety instructions are intended to prevent a hazardous situa­tion and/or equipment damage.These instructions indicate the level of potential hazard by label of “Caution”,“Warning” or “Danger”. To ensure safety,be sure to observe ISO4414
(Note1)
, JIS B 8370
(Note2)
and other safety practices. Note 1: ISO 4414:Pneumatic fluid power – Recommendations for the application of equipment to transmission and control systems. Note 2: JIS B 8370: Pneumatic system axiom.
CAUTION : Operator error could result in injury or
equipment damage.
WARNING: Operator error could result in serious
injury or loss of life.
DANGER : In extreme conditions, there is a
possible result of serious injury or loss of life.
WARNING
1. The compatibility of pneumatic equipment is the respon­sibility of the person who designs the pneumatic system or decides its specifications.
Since the products specified here are used in various operating conditions, their compatibility for the specific pneumatic system must be based on specifications or after analysis and/or tests to meet your specific requirements.
Compressed air can be dangerous if an operator is unfamiliar with it. Assembly, handling or repair of pneumatic systems should be performed by trained and experienced operators.
3. Do not service machinery/equipment or attempt to remove component until safety is confirmed.
1) Inspection and maintenance of machinery/equipment should
only be performed after confirmation of safe locked-out control positions.
2) When equipment is to be removed, confirm the safety process
as mentioned above.Switch off air and electrical supplies and exhaust all residual compressed air in the system.
3) Before machinery/equipment is re-started, ensure all safety
measures to prevent sudden movement of cylinders etc. (Bleed air into the system gradually to create back-pressure, i.e. incorporate a soft-start valve).
4. Contact SMC if the product is to be used in any of the following conditions:
1) Conditions and environments beyond the given specifica-
tions, or if product is used outdoors.
2) Installations in conjunction with atomic energy, railway, air
navigation, vehicles,medical equipment, food and beverage, recreation equipment, emergency stop circuits, press applications, or safety equipment.
3) An application which has the possibility of having negative
effects on people, property, or animals, requiring special safety analysis.
CAUTION
Ensure that the air supply system is filtered to 5 micron.
Standard specifications
Fluid Air and inert gas Max. operating pressure 9.9 kgf/cm2(990kPa) Min. operating 2 position 1.0 kgf/cm2(100kPa) pressure 3 position 1.5 kgf/cm2(150kPa)
Valve Ambient and fluid temperature Note 1:-10~+60°C
Lubrication Note 2: Not required Pilot operator manual override Non-locking push type (flush type) Protection structure Dust proof Rated voltage AC 100, 200V (50/60Hz)
DC 24V Allowance voltage range -15~+10% rated voltage Coil insulation Class B or equivalent
Electricity Apparent power
Inrush 5.0VA/60Hz, 5.6VA/50Hz (Power AC
consumption)
Holding 2.3VA (1.5W)/60Hz, 3.4VA (2.1W)/50Hz Power consumption DC 1.8W
Electrical entry Grommet,Grommet terminal
Conduit terminal, DIN connector
Note 1: Use dry-air at low temperature. Note 2: Use turbine oil No.1 (ISO VG 32), if lubricated.
032a/eng
Installation
WARNING
Ensure all air and power supplies are ISOLATED before commencing installation. Do not install these valves in explosive atmospheres. If these valves are exposed to water or oil droplets, ensure that they are protected. If it is intended to energise a valve for an extended period please con­sult SMC. If air leakage causes associated equipment to malfunction cease using valve and inspect for cause. Check fixings while pressure and power are applied. Initial function and leakage tests should be performed after installation. Only install once safety instructions have been read and understood.
Symbol
2 position
Single
Double
Exhaust centre
Pressure centre
Closed centre
3 position
Construction and parts (Fig 1)
2 position single
2 position double
3 position closed centre/exhaust centre/pressure centre
6
6
6 21 5 4
2
1
7
4
4
2
1
5
3
Closed centre
Pressure centre
Exhaust centre
Fig 1
Fig 2
Fig 5
Main parts
No. Description Material Note
1 Body Aluminum die-cast Platinum silver 2 Spool/sleeve Stainless steel - 3 End plate Resin - 4 Piston Resin -
Body Ported type
2 position single
2 position double
3 position closed centre/exhaust centre/pressure centre
M
6
8
8
3
3
9 5 1
2
M
M
K
K
8
3 4
4 9
6
6
2
2K1
J
1
L
7
7
7
J
Closed centre
Pressure centre
Base mounted type
Exhaust centre
Main parts
No. Description Material Note
1 Body Aluminum die-cast Platinum silver 2 Sub plate Aluminum die-cast Platinum silver 3 Spool/sleeve Stainless steel - 4 Adapter plate Aluminum die-cast Platinum silver 5 Endplate Resin Black 6 Piston Resin - 7 Junction cover Resin - 8 Light cover Resin -
Fig 3
Fig 6
Fig 7
Fig 4
Electrical connection body ported type
Lamp and surge voltage suppressor (Fig 3)
AC and 100VDC
24VDC or less
Single
Double
Double
Terminal No.1(+)
Terminal No.1+(-)
Terminal No.2-(+) Note: No polarity.
Terminal No.2-(+) Note: No polarity.
With light Terminal No. 2-(+)
B side terminal No. 1+(-) With light
Terminal No.1+(-) A side
Terminal No.2 (-)
Terminal No.2 (-)
Terminal No.2 (-)
B side terminal No. 1(+)
With light
Terminal No. 1(+)
With light A side
With light
Single
Applicable terminals :
1.25-3, 1.25-3S,1.25Y-3N or 1.25Y3S. Not required for DIN connector board.
With terminal block board
With DIN
connector board
Note: No polarity
With indicator light and surge voltage suppressor
Plug-in type
Fig 8
2
1
1
as to occlude exhaust galleries. Perfect spacer
When fixed between a valve with built in double check valves and sub­plate the perfect spacer can hold an actuator in a desired position any­where along it's stroke for a considerable period of time.
Environment
When valve is mounted in a control panel or is energised for long periods of time, make sure the ambient temperature is within the specified range.
When used in temperatures higher than 60° please contact SMC.
How to use insert plug (Fig 9, 10)
When removing insert plug 1 from manifold base,push the lever area 2 of insert plug downward with thumb and pull it together with the
lead wire 3 out.
When plugging the insert plug 1 into the manifold base, push the lever area of insert plug with thumb and plug it in its place in the receptacle housing 4 horizontally. After plugging, pull lead wire out a little bit to ensure that insert plug is secure.
Type 01T with terminal block board (Fig 11)
Series VFS2000
Remove junction cover of manifold, exposing terminal block board attached to the manifold block. Lead wires from solenoid valve are connected with the terminals on upper side of terminal block board. (On the terminal block board, lead wire is connected with both A and B sides of solenoid valve in accordance with the corresponding mark­ings A and B on the block board.) Connect each lead wire of power side corresponding to each respec­tive solenoid valve on the lower terminal block board. Terminal block wiring specification is in accordance with +COM.
Block board
marking
Model
A COM B
VFS2100 A side COM B side VFS2200 A side COM B side VFS2300 A side COM B side
• Applicable terminal: 1.25-3, 1.25-3S,1.25Y-3N, 1.25Y-3S
• Plugging COM bridge (Part No. AXT625-73) in between each +COM on the block board will make the specifications of all the stations +COM and enables you to rationalise the wiring process.
• No polarity.
Leakage voltage (Fig 12)
Note that when using a C-R device (surge voltage suppressor) for contact protection, the voltage leakage may increase due to the current leakage flowing through the C-R device.
Suppress residual voltage leakage as follows: DC Coil 3% or less of rated voltage AC Coil 20% or less of rated voltage
Lubrication
These valves have been lubricated for life during manufacture and as such require no further lubrication.
CAUTION
However,if a lubricant is to be used with a rubber seal type, a turbine oil type #1,(ISO VG32) should be used, continuous lubrication must be carried out as the original lubricant will be washed away.
Manual override operation (Fig 13)
WARNING
Exercise EXTREME CAUTION when operating a solenoid manual override as connected equipment will commence operation. Ensure all safety measures are in place.
Non-locking push type (Fig 13, 13a)
1. Push down the manual override button (Orange), until it stops, using a small-bladed screwdriver.
2. Hold this position for the duration of the check (ON position)
3. Release the button and the override will re-set to the OFF position.
Slotted locking type (Fig 13b)
To lock
1. Insert a small-bladed screwdriver into the slot.
2. Turn the override through 90° (ON position).
3. Remove screwdriver
WARNING
In this position the manual override is in the locked 'ON' position.
To unlock
1. Insert small-bladed screwdriver into the slot of the manual override.
2. Turn the screwdriver 90° in the reverse direction.
Maintenance
WARNING
Ensure air and electrical supplies are isolated before commencing any maintenance work.
after a Standard Filter (Series AF).Also selecting a compressor oil with minimal oxidisation characteristics would elevate any such problems.
2. Should the valve and sleeve adhere to each other then disassem­ble the valve and clean the assembly in a solvent based chemical taking care not to contaminate any O-rings with cleaning agent.
Mounting
When disassembling and reassembling ensure that all components are in their proper positions. Prevent gaskets from moving and torque screws down equally.
Pilot operator assembly: SF4-u-u
Set screw Correct clamping torque kgf-cm (N-m)
M3 4.5~6(0.45~0.6)
Solenoid valve body
Set screw Correct clamping torque kgf-cm (N-m)
M3 6~10(0.6~1) M4 14~25(1.4~2.5) M5 28~50(2.8~5)
Single solenoid operated valves may be mounted in any attitude.However, in environments that subject the valves to vibration double solenoid oper­ated valves should be aligned perpendicular to the vibration. Never use in conditions where vibrations exceed 5G.
How to remove/replace base mounted type
1. Loosen 3 set screws (hexagonal socket head cap screws M3x31) and pull solenoid valve out vertically. Failing to do so may result in damage to the solenoid valve.
2. When mounting solenoid valve on to the base, engage plug (underside of valve) and socket (top face of base) before replac­ing and tightening screws.
Accessories
Individual supply spacer
An individual supply spacer complete with gasket may be fixed between valve and subplate so as to provide an individual pressure supply to any valve.
Individual exhaust spacer
An individual exhaust spacer complete with gasket may be fixed between valve and subplate so as to provide an individual exhaust for any valve.
Exhaust block disk
If valve exhaust affects the function of other valves on the manifold then an exhaust block disks may be fitted between the sub plates so as to occlude exhaust galleries.
Fig 9
Fig 10
Fig 13a,b
Fig 15
Fig 14
Fig 11
Fig 12
Switching element
Leakage current
Leakage current
Source
Valve
OFF
Wiring area
Markings
* Special order.
Non-locking push type (flush type)
*A - Non-locking push type (extended type)
*B - Lock type (tool type)
a b
K 2
M
1
3
J 7
5
4
6
L
89
Parts list
No. Description Material
1 Metal joint A Steel plate 2 Metal joint B Steel plate 3 Gasket A NBR 4 Gasket B NBR 5 O-ring NBR 6 O-ring NBR 7 O-ring NBR 8 Terminal assembly - 9 Junction cover assembly -
End plate (D side)
End plate (U side)
For increasing the manifold bases,please pre­pare the manifold block assembly No.of the principal part assembly J. Plug-in type:The manifold base with terminal stand (integral type with a junction cover) is required with the 9 junction cover assembly. Note: Manifold base/construction: Plug-in type with terminal block board.
Manifold base construction/plug-in type/non plug-in type (Fig 15)
Fig 16
Fig 17
Fig 18
When you enquire about the product, please contact the following
SMC Corporation: ENGLAND Phone 01908-563888 GERMANY Phone 6103-402-0 ITALY Phone 02-92711 FRANCE Phone 1-64-76-10-00 HOLLAND Phone 020-5318880 SWEDEN Phone 08-603-07-00 SWITZERLAND
Phone 052-34-0022 AUSTRIA Phone 02262-62-280 SPAIN Phone 945-290600 IRELAND Phone 01-4501822 GREECE Phone 01-3426076 DENMARK Phone 8738-0800 FINLAND Phone 9-68-10-21 NORWAY Phone 67-12-90-20 BELGIUM Phone 03-3551464 POLAND Phone 48-22-6131847 TURKEY Phone 212-2211512
2
1
3
4
1
Loading...