SMC Networks PFMC7501, PFMC7202, PFMC7102 Operation Manual

No.PF※※-OMS0002-B
PRODUCT NAME
Digital Flow Switch
MODEL / Series / Product Number
PFMC7501 PFMC7102 PFMC7202
-1-
No.PF※※-OMS0002-B
Contents
Safety Instructions 2 Model Indication and How to Order 10 Summary of Product parts 11
Definition and terminology 12
Mounting and Installation 14
Installation 15 Piping 17
Wiring 18 Outline of Settings [Measurement mode] 22 Flow Setting (set value only) of OUT1 OUT2 [3 step setting mode] 23
Default settings 23
Function Setting [Function selection mode] 25
Default settings 26
F0 Reference condition/Unit selection function 27
F1 Setting of OUT1 29
F2 Setting of OUT2 37
F3 Response time 42
F10 Sub display 43
F20 External input 47
F22 Setting of analogue output 48
F30 Accumulated value hold 49
F31 Orientation correction function 50
F80 Display OFF mode 51
F81 Security code 52
F82 Line name 53
F90 Setting of all functions 54
F98 Output check 56
F99 Reset to the default settings 57 Other Functions 58 Maintenance 62 Troubleshooting 63
Error indication 65 Specification 66
Specifications 66
Characteristics data 69
Dimensions 71
-2-
No.PF※※-OMS0002-B
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or equipment damage. These instructions indicate the level of potential hazard with the labels of "Caution", "Warning" or "Danger". They are all important notes for safety and must be followed in addition to International Standards (ISO/IEC)*1), and other safety regulations.
*1) ISO 4414: Pneumatic fluid power -- General rules relating to systems.
ISO 4413: Hydraulic fluid power -- General rules relating to systems. IEC 60204-1: Safety of machinery -- Electrical equipment of machines .(Part 1: General requirements) ISO 10218: Manipulating industrial robots -Safety. etc.
Caution
Caution indicates a hazard with a low level of risk which, if not avoided, could
result in minor or moderate injury.
Warning
Warning indicates a hazard with a medium level of risk which, if not avoided,
could result in death or serious injury.
Danger
Danger indicates a hazard with a high level of risk which, if not avoided, will
result in death or serious injury.
Warning
1. The compatibility of the product is the responsibility of the person who designs the equipment or decides its specifications.
Since the product specified here is used under various operating conditions, its compatibility with specific equipment must be decided by the person who designs the equipment or decides its specifications based on necessary analysis and test results. The expected performance and safety assurance of the equipment will be the responsibility of the person who has determined its compatibility with the product. This person should also continuously review all specifications of the product referring to its latest catalog information, with a view to giving due consideration to any possibility of equipment failure when configuring the equipment.
2. Only personnel with appropriate training should operate machinery and equipment.
The product specified here may become unsafe if handled incorrectly. The assembly, operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced.
3. Do not service or attempt to remove product and machinery/equipment until safety is confirmed.
1. The inspection and maintenance of machinery/equipment should only be performed after measures to prevent falling or runaway of the driven objects have been confirmed.
2. When the product is to be removed, confirm that the safety measures as mentioned above are implemented and the power from any appropriate source is cut, and read and understand the specific product precautions of all relevant products carefully.
3. Before machinery/equipment is restarted, take measures to prevent unexpected operation and malfunction.
4. Contact SMC beforehand and take special consideration of safety measures if the product is to be used in any of the following conditions.
1. Conditions and environments outside of the given specifications, or use outdoors or in a place exposed to direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space, shipping, vehicles, military, medical treatment, combustion and recreation, or equipment in contact with food and beverages, emergency stop circuits, clutch and brake circuits in press applications, safety equipment or other applications unsuitable for the standard specifications described in the product catalog.
3. An application which could have negative effects on people, property, or animals requiring special safety analysis.
4. Use in an interlock circuit, which requires the provision of double interlock for possible failure by using a mechanical protective function, and periodical checks to confirm proper operation.
-3-
No.PF※※-OMS0002-B
Safety Instructions
Caution
1.The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in manufacturing industries. If considering using the product in other industries, consult SMC beforehand and exchange specifications or a contract if necessary. If anything is unclear, contact your nearest sales branch.
Limited warranty and Disclaimer/Compliance Requirements
The product used is subject to the following "Limited warranty and Disclaimer" and "Compliance Requirements". Read and accept them before using the product.
Limited warranty and Disclaimer
1. The warranty period of the product is 1 year in service or 1.5 years after the product is delivered, whichever is first.2) Also, the product may have specified durability, running distance or replacement parts. Please consult your nearest sales branch.
2. For any failure or damage reported within the warranty period which is clearly our responsibility, a replacement product or necessary parts will be provided. This limited warranty applies only to our product independently, and not to any other damage incurred due to the failure of the product.
3. Prior to using SMC products, please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products.
2) Vacuum pads are excluded from this 1 year warranty.
A vacuum pad is a consumable part, so it is warranted for a year after it is delivered. Also, even within the warranty period, the wear of a product due to the use of the vacuum pad or failure due to the deterioration of rubber material are not covered by the limited warranty.
Compliance Requirements
1. The use of SMC products with production equipment for the manufacture of weapons of mass destruction (WMD) or any other weapon is strictly prohibited.
2. The exports of SMC products or technology from one country to another are governed by the relevant security laws and regulation of the countries involved in the transaction. Prior to the shipment of a SMC product to another country, assure that all local rules governing that export are known and followed.
Caution
SMC products are not intended for use as instruments for legal metrology.
Products that SMC manufactures or sells are not measurement instruments that are qualified by pattern approval tests relating to the measurement laws of each country. Therefore, SMC products cannot be used for business or certification ordained by the measurement laws of each country.
-4-
No.PF※※-OMS0002-B
Operator
This operation manual is intended for those who have knowledge of machinery using pneumatic
equipment, and have sufficient knowledge of assembly, operation and maintenance of such equipment. Only those persons are allowed to perform assembly, operation and maintenance.
Read and understand this operation manual carefully before assembling, operating or providing
maintenance to the product.
Safety Instructions
Warning
Do not disassemble, modify (including changing the printed circuit board) or repair.
An injury or failure can result.
Do not operate the product outside of the specifications.
Do not use for flammable or harmful fluids. Fire, malfunction, or damage to the product can result. Verify the specifications before use.
Do not operate in an atmosphere containing flammable, explosive or corrosive gas.
Fire, explosion or corrosion can result. This product is not designed to be explosion proof.
Do not use the product for flammable fluid.
Fire or explosion can result. Only air and N2 are applicable.
Do not use the product in a place where static electricity is a problem.
Otherwise it can cause failure or malfunction of the system.
If using the product in an interlocking circuit:
Provide a double interlocking system, for example a mechanical system Check the product regularly for proper operation
Otherwise malfunction can result, causing an accident.
The following instructions must be followed during maintenance:
Turn off the power supply Stop the air supply, exhaust the residual pressure and verify that the air is released before performing
maintenance work
Otherwise an injury can result.
-5-
No.PF※※-OMS0002-B
Caution
Do not touch the terminals and connectors while the power is on.
Otherwise electric shock, malfunction or damage to the product can result.
After maintenance is complete, perform appropriate functional inspections and leak tests.
Stop operation if the equipment does not function properly or there is a leakage of fluid. When leakage occurs from parts other than the piping, the product might be faulty. Disconnect the power supply and stop the fluid supply. Do not apply fluid under leaking conditions. Safety cannot be assured in the case of unexpected malfunction.
NOTE
Follow the instructions given below when designing, selecting and handling the product.
The instructions on design and selection (installation, wiring, environment, adjustment, operation,
maintenance, etc.) described below must also be followed.
Product specifications
The direct current power supply used should be UL approved as follows.
Circuit (Class 2) of maximum 30 Vrms (42.4 V peak) or less, with UL1310 Class 2 power supply unit or UL1585 Class 2 transformer.
The product is a UL approved product only if it has a mark on the body. Use the specified voltage.
Otherwise failure or malfunction can result. Insufficient supply voltage may not drive a load due to a voltage drop inside the product. Verify the operating voltage of the load before use.
Do not exceed the specified maximum allowable load.
Otherwise it can cause damage or shorten the lifetime of the product.
Data stored by the product is not deleted, even if the power supply is cut off.
(Writing time: 1000000 cycles)
The applicable fluids are dry air and Nitrogen.
The fluid temperature range is 0 to 50 oC.
Before designing piping confirm the pressure loss at the sensor from the pressure loss graph. For the details of compressed air quality, refer to ISO 8573-1, 1.1.2 to 1.6.2. Use the specified measurement flow rate and operating pressure.
Otherwise it can cause damage to the product or inability to measure correctly.
Reserve a space for maintenance.
Allow sufficient space for maintenance when designing the system.
-6-
No.PF※※-OMS0002-B
Product handling
Installation
Tighten to the specified tightening torque.
If the tightening torque is exceeded the mounting screws, the product may damaged. If the tightening torque is insufficient, the product may be displaced and the mounting screws may come loose.
Ensure that the FG terminal is connected to ground when using a commercially available switch-mode
power supply.
Do not drop, hit or apply excessive shock to the product.
Otherwise damage to the internal parts can result, causing malfunction.
Do not pull the lead wire forcefully, or lift the product by the lead wire. (Tensile force 49 N or less)
Hold the product body when handling, to prevent damage, failure or malfunction.
For piping of the product, hold the piping with a wrench on the metal part of the product.
Holding other parts with a wrench leads to may damage the product.
Any dust left in the piping should be flushed out by air blow before connecting the piping to the product.
Otherwise damage or malfunction can result.
Refer to the flow direction of the fluid indicated on the product label for installation and piping. Do not mount the body with the bottom facing upwards.
Retention of air can cause inability to measure accurately.
Do not insert metal wires or other foreign matter into the piping port.
This can damage the sensor causing failure or malfunction.
Never mount a product in a location that will be used as a foothold.
The product may be damaged if excessive force is applied by stepping or climbing onto it.
Do not apply excessive rotational force to the monitor.
The monitor with integrated display can be rotated. It can be positioned at 45 ° and 90 ° intervals, clockwise and anti-clockwise. Rotating the display with excessive force will damage the end stop.
If there is a risk of foreign matter entering the fluid, install and pipe a filter or the mist separator at the
inlet to avoid failure and malfunction.
Otherwise failure or malfunction can result, and it can cause inability to measure accurately. It is possible to satisfy the air quality class indicated in the specification using the pneumatic circuit below.
Recommended pneumatic circuit example (Compressed air)
-7-
No.PF※※-OMS0002-B
Wiring
Do not pull the lead wires. In particular, never lift a product equipped with fitting and piping by holding the
lead wires.
Otherwise damage to the internal parts can result, causing malfunction or disconnection of the connector.
Avoid repeatedly bending or stretching the lead wire, or placing heavy loads on it.
Repeated bending stress or tensile stress can cause damage to the sheath, or breakage of the wires. If the lead wire can move, fix it near the body of the product. The recommended bend radius of the lead wire is 6 times the outside diameter of the sheath, or 33 times the outside diameter of the wire insulation material, whichever is larger. Replace any damaged lead wire with a new one.
Wire correctly.
Incorrect wiring can damage the product.
Do not perform wiring while the power is on.
Otherwise damage to the internal parts can result, causing malfunction.
Do not route wires and cables together with power or high voltage cables.
Otherwise the product can malfunction due to interference or noise and surge voltage from power and high voltage cables.
Confirm proper insulation of wiring.
Poor insulation (interference from another circuit, poor insulation between terminals, etc.) can lead to excess voltage or current being applied to the product, causing damage.
Keep wiring as short as possible to prevent interference from electromagnetic noise and surge voltage.
Do not use a cable longer than 30 m. Wire the DC (-) line (blue) as close as possible to the power supply.
When analogue output is used, install a noise filter (line noise filter, ferrite element, etc.) between the
switch-mode power supply and this product.
-8-
No.PF※※-OMS0002-B
Environment
Do not use the product in an environment that is constantly exposed to the splash of water.
Otherwise failure or malfunction can result. Take measures such as using a cover.
Do not use the product in an environment where corrosive gases or fluids could be splashed.
Otherwise damage to the product and malfunction can result.
Do not use in a place where the product could be splashed by oil or chemicals.
If the product is to be used in an environment containing oils or chemicals such as coolant or cleaning solvent, even for a short time, it may be adversely affected (damage, malfunction, or hardening of the lead wires).
Do not use the product in an area where electrical surges are generated.
If there is equipment generates large electrical surges (solenoid type lifter, high frequency induction furnace, motor, etc.) close to the product, damage or failure of the internal circuit may occur. Take measures against the surge sources, and prevent the wires from coming into close contact.
Do not use a load which generates a surge voltage.
When a surge-generating load such as a relay or solenoid is driven directly, use a product with a built-in surge absorbing element.
The product is CE marked, but not immune to lightning strikes. Take measures against lightning strikes
in the system.
Do not use the product in areas that are exposed to vibration or impact.
Otherwise failure or malfunction can result.
Do not use the product in the presence of a magnetic field.
This may lead to the malfunction of the product.
Prevent foreign matter such as wire debris from entering the product.
Otherwise failure or malfunction can result.
Do not use the product in areas subject to large temperature cycle.
Heating/cooling cycles other than ordinary changes in temperature can adversely affect the internal structure of the product.
Do not expose the product to direct sunlight.
If using in a location directly exposed to sunlight, use a suitable protective cover. Otherwise failure or malfunction can result.
Keep within the operating temperatures range.
The operating temperature range is 0 to 50 oC. Operation below the minimum temperature limit may cause damage or operation failure due to frozen moisture in the fluid or air. Protection against freezing is necessary. An air dryer is recommended for elimination of drainage and water. Avoid sudden temperature changes even within the specified temperature range.
Do not operate close to a heat source, or in a location exposed to radiant heat.
Otherwise malfunction can result.
-9-
No.PF※※-OMS0002-B
Adjustment and Operation
Connect load before turning on the power. Do not short-circuit the load.
Although an error is displayed when the product load is short circuited, excess current may cause damage to the product.
Do not press the setting buttons with a sharp pointed object.
This may damage the setting buttons.
Supply the power when there is no flow. If using the product to detect very small flow rates, warm up the product for 10 to 15 minutes first.
There will be a drift on the display or the analogue output of approximate 2 to 3% immediately after the power supply is turn on, within 10 minutes.
The output is off for 3 seconds after power is supplied. Use settings suitable for the operating conditions.
Incorrect settings can cause operational failure.
During the initial setting and any subsequent flow rate setting, the product will switch the output
according to the existing settings until the changes are complete.
Confirm the output has no adverse effect on machinery and equipment before setting. Stop the control system before setting if necessary.
Do not touch the LCD display during operation.
The display can vary due to static electricity.
Maintenance
Perform regular maintenance and inspections.
There is a risk of unexpected malfunction of components due to the malfunction of equipment and machinery.
Turn off the power supply, stop the supplied air, exhaust the residual pressure and verify the release of
air before performing maintenance.
There is a risk of unexpected malfunction.
Perform drainage regularly.
If condensate enters the outside, it can cause failure of other pneumatic equipment.
Do not use solvents such as benzene, thinner etc. to clean the product.
They could damage the surface of the body and erase the markings on the body. Use a soft cloth to remove stains. For heavy stains, use a cloth lightly dampened with diluted neutral detergent, then wipe up any residue with a dry cloth.
-10-
No.PF※※-OMS0002-B
Model Indication and How to Order
Accessories/Part numbers
If an accessory is required, order using the following part number.
Part number
Description
Note
ZS-40-A
Lead wire with M8 connector
Length: 3 m
ZS-42-A
Bracket
With mounting screws for PFMC7501/7102 (M3 x 5, 2 pcs.)
ZS-42-B
Bracket
With mounting screws for PFMC7202 (M3 x 5, 2 pcs.)
-11-
No.PF※※-OMS0002-B
Summary of Product parts
Body
Connector pin numbers
(on the product)
1
DC(+)
2
OUT2/ Analogue output/ External input
3
DC(-)
4
OUT1
Name
Description
Display
See below.
Connector
M8 connector for electrical connections.
Lead wire with M8 connector
Lead wire for power supply and outputs.
Piping port
For piping connections. Connected to the fluid inlet at IN and to the fluid outlet at OUT.
Body
The body of the product.
: A protective tape is affixed to the display. Please remove it before use.
Display
Name
Description
Main display
Displays the flow value, setting mode and error codes. (2 colour display)
Indicator LED
Displays the output status of OUT1 and OUT2. LED is ON (Orange) when the output is ON. When the accumulated pulse output mode is selected, the output display will turn OFF.
Sub display
Displays the accumulated flow, set value, peak/bottom value and line names when in the measurement mode. (1 colour display)
button (UP)
Selects the mode and the display shown on the Sub display, or increases the ON/OFF set value.
button (SET)
Press this button to change the mode and to set a value.
button (DOWN)
Selects the mode and the display shown on the Sub display, or decreases the ON/OFF set value.
Units indicator
Indicates the unit currently selected.
-12-
No.PF※※-OMS0002-B
Definition and terminology
Terminology
Definition
A
Accumulated flow
The total amount of fluid that has passed through the device. If an instantaneous flow of 10 L/min continues for 5 minutes, the accumulated flow will be 5 x 10 = 50 L.
Accumulated flow external reset
A function to reset the accumulated flow to "0" when an external signal is input.
Accumulated pulse output
A type of output where a pulse is generated every time a predefined accumulated flow passes. It is possible to calculate the total accumulated flow by counting the pulses.
Accumulated value hold
A function to store the accumulated flow value in the internal memory. The flow value will be stored at a set time interval of either 2 or 5 minutes. When the power supply is turned on, the stored accumulated flow value will be displayed and accumulated flow will continue from that point.
Analogue output
A type of variable output that has a value proportional to the measured quantity. When the analogue output is in the range of 1 to 5 V or 4 to 20 mA, it will vary continuously, following the change of flow.
C
Chattering
The problem of the switch output turning ON and OFF repeatedly around the set value at high frequency due to the effect of pulsation.
D
Display flow range
The range which can be displayed by the product with a digital display.
F
F.S. (Full span, Full scale)
Stands for "full span" or "full scale", and indicates varied analogue output range at rated value. For example, when analogue output is 1 to 5 V, F.S. = 5[V] - 1[V] = 4[V], (ref. 1%F.S. = 4[V] x 1% = 0.04[V]) The maximum measuring range or change in analogue output over the maximum measurement range.
H
Hysteresis
The difference between ON and OFF points used to prevent chattering. Hysteresis can be effective in avoiding the effects of pulsation.
Hysteresis mode
Mode where the switch output will turn ON when the flow is greater than the set value, and will turn OFF when the flow falls below the set value by the amount of hysteresis or more.
I
Instantaneous flow
The volume of flow per unit of time. If it is 10 L/min, there is a flow of 10 L passing through the device in 1 minute.
Internal voltage drop
The voltage drop across the product (and therefore not applied to the load), when the switch output is ON. The voltage drop will vary with load current, and ideally should be 0 V.
K
Key-lock function
A function that locks the set buttons so that no accidental setting changes can be made.
-13-
No.PF※※-OMS0002-B
Terminology
Definition
M
Minimum setting unit
The resolution of set and display values. If the minimum setting unit is 1 L/min, the flow can be displayed in 1 L/min units, i.e. 10, 11, 12.
N
Normal condition (NOR)
Reference condition for volumetric flow: 101.3 kPa, 0 °C The flow measurement which is converted at normal atmospheric pressure conditions at 0 C.
O
Operating fluid temperature
The fluid temperature range within which the product will meet all published specifications.
Operating humidity range
The ambient humidity range within which the product will meet all published specifications.
Operating pressure range
The pressure range within which the product will meet all published specifications.
Operating temperature range
The ambient temperature range within which the product will meet all published specifications.
P
Part in contact with fluid
A part that comes into physical contact with the fluid.
Pressure characteristics
The amount of variation in the analogue output or display value when the supply pressure is changed.
Proof pressure
The pressure beyond which the product will be damaged.
R
Rated flow range
The flow range within which the product will meet all published specifications.
Repeatability
Reproducibility of the display or analogue output value, when the flow is repeatedly changing.
Response time (analogue output)
The time from when the flow is applied as a step input (when the flow rate changes from 0% to 100% instantaneously) until the switch output turns ON (OFF) at 90% of the rated flow rate.
Response time (switch output)
The time from when the flow is applied as a step input (when the flow rate changes from 0% to 100% instantaneously) until the analogue output (voltage or current) reaches 90% of the actual flow rate.
Ripple
Indicates pulsation.
S
Set flow range
The range of ON/OFF threshold values that can be set for products with a switch output.
Standard condition (ANR)
Reference condition for volumetric flow: 101.3 kPa, 20 C, 65%RH The flow measurement which is converted at normal atmospheric pressure conditions at 20 C, 65%R.H.
Switch output
An output type that has only 2 conditions, ON or OFF. In the ON condition an indicator LED will turn on, and any connected load will be powered. In the OFF condition, there will be no indicator LED and no power is supplied to the load.
T
Temperature characteristic
The amount of variation in the analogue output or display value when the ambient temperature is changed.
U
Unit selection function
Function to change the unit in which the value of flow is displayed. Only a product with this function can change the unit. A product with unit selection function cannot be purchased if it is used within Japan. Flow is indicated only by SI units in Japan.
W
Window comparator mode
An operating mode in which the switch output is turned on or off depending on whether the flow is within the range of 2 set values.
-14-
No.PF※※-OMS0002-B
Mounting and Installation
Mounting
Never mount the product in a place where it will be used as a mechanical support. Mount the product so that the fluid flows in the direction indicated by the arrow on the side of the body. The monitor with integrated display can be rotated. It can be positioned at 45 ° and 90 ° intervals, clockwise
and anti-clockwise. Rotating the display with excessive force will damage the end stop.
-15-
No.PF※※-OMS0002-B
Installation
Bracket mounting
Mount the bracket to the product using the mounting screws (2 pcs.). Fasten the bracket mounting screws to a torque of 0.5 to 0.7 Nm.
Mount the product with bracket using M4 screws (4 pcs.) or equivalent. Screw is prepared by customer. Refer to the dimension drawing (page 71) for the bracket thickness and mounting hole dimensions.
-16-
No.PF※※-OMS0002-B
Direct mounting
For direct mounting use M3 screws (2 pcs.) or equivalent. Screws are prepared by customer. Refer to the dimension drawing (page 71) for the diameter and depth of the mounting screw holes. Tightening torque is 0.5 to 0.7 Nm.
-17-
No.PF※※-OMS0002-B
Piping
Never mount the product upside down. The straight piping length shall be 8 cm or longer.
Otherwise, if a straight section of piping is not installed, the accuracy varies by approximately 2%F.S. Refer to the straight inlet piping length and accuracy graph (page 70).
Avoid sudden changes in the piping size on the IN side of the product. Do not release the OUT side piping port of the product directly to the atmosphere without the piping
connected. If the product is used with the piping port released to atmosphere, the accuracy may vary.
Piping for the metal body
Tighten to the specified torque. Refer to the table below for the required torque values. If the tightening torque is exceeded, the product can be broken.
If the tightening torque is insufficient, the fitting may become loose.
Avoid any sealing tape getting inside the flow path. Ensure there is no leakage after piping. When mounting the fitting, a spanner should be used on the metal body of the fitting only.
Holding other parts of the product with a spanner may damage the product. Specifically, make sure that the spanner does not damage the connector.
Nominal thread size
Required torque
Piping port size
Width across flats of attachment
Rc1/2, NPT1/2Rc3/4, NPT3/4
28 to 30 Nm
1/2
30 mm
3/4
35 mm
Piping for the One-touch fitting
For the one-touch fitting, use tubing with a tube inside diameter of 9 mm or more.
Accuracy can vary approximately 2%F.S. when such tubing is not used.
-18-
No.PF※※-OMS0002-B
Wiring
Connection
Connections should only be made with the power supply turned off. Use a separate route for the product wiring and any power or high voltage wiring. Otherwise, malfunction
may result due to noise.
Ensure that the FG terminal is connected to ground when using a commercially available switch-mode
power supply. When a switch-mode power supply is connected to the product, switching noise will be superimposed and the product specification can no longer be met. This can be prevented by inserting a noise filter, such as a line noise filter and ferrite core, between the switch-mode power supply and the product or by using a series power supply instead of a switch-mode power supply.
Connecting/Disconnecting
Align the lead wire connector with the connector key groove, and insert it straight in. When the knurled part
is fully tightened. Check that the connection is not loose.
When removing the connector, unlock the knurled part and pull out the connector straight.
Connector pin numbers (lead wire)
Connector pin numbers
Wire colour
Description
1
Brown
DC(+) 2 White
OUT2/Analogue output/External input
3
Blue
DC(-) 4 Black
OUT1
-19-
No.PF※※-OMS0002-B
Internal circuit and wiring examples
NPN (2 outputs) type
PFMC7--A-
Maximum applied voltage: 28 V Maximum load current: 80 mA Internal voltage drop: 1 V or less
NPN (1 output) + Analogue (1 to 5 V) output type
PFMC7--C-
NPN (1 output) + Analogue (4 to 20 mA) output type
PFMC7--D-
Maximum applied voltage: 28 V Maximum load current: 80 mA Internal voltage drop: 1 V or less C: Analogue output: 1 to 5 V
Output impedance: 1 kΩ
D: Analogue output: 4 to 20 mA
Maximum load impedance: 600 Ω Minimum load impedance: 50 Ω
NPN (1 output) + External input type
PFMC7--G-
Maximum applied voltage: 28 V Maximum load current: 80 mA Internal voltage drop: 1 V or less External input: Input voltage 0.4 V or less (reed or solid state input) for 30 msec. or longer
-20-
No.PF※※-OMS0002-B
PNP (2 outputs) type
PFMC7--B-
Maximum load current: 80 mA Internal voltage drop: 1.5 V or less
PNP (1 output) + Analogue (1 to 5 V) output type
PFMC7--E-
PNP (1 output) + Analogue (4 to 20 mA) output type
PFMC7--F-
Maximum load current: 80 mA Internal voltage drop: 1.5 V or less E: Analogue output: 1 to 5 V
Output impedance: 1 kΩ
F: Analogue output: 4 to 20 mA
Maximum load impedance: 600 Ω Minimum load impedance: 50 Ω
PNP (1 output) + External input type
PFMC7--H-
Maximum load current: 80 mA Internal voltage drop: 1.5 V or less External input: Input voltage 0.4 V or less (reed or solid state input) for 30 msec. or longer
-21-
No.PF※※-OMS0002-B
Example of wiring for accumulated pulse output
NPN (2 outputs) type
PFMC7--A-
NPN (1 output) + Analogue output type
PFMC7--C- PFMC7--D-
NPN (1 output) + External input type
PFMC7--G-
PNP (2 outputs) type
PFMC7--B-
PNP (1 output) + Analogue output type
PFMC7--E- PFMC7--F-
PNP (1 output) + External input type
PFMC7--H-
-22-
No.PF※※-OMS0002-B
Outline of Settings [Measurement mode]
Power is supplied
The output will not operate for 3 seconds after supplying power.
The identification code of the product is displayed.
[Measurement mode]
Measurement mode is the condition where the flow is detected and displayed, and the switch function is operating. This is the basic mode; other modes should be selected for set-point changes and other function settings.
Sub display
In measurement mode, the sub display can be temporarily changed (for 30 seconds) by pressing the or button.
: Example for 500 L/min type : The set values of OUT2 and the accumulated value of OUT2 cannot be displayed. : To display other indications than "Set values" normally, perform settings referring to the function selection mode [F10]
(page 43).
Press the
button
once.
Press the button for 2 seconds or longer.
Flow Setting
[3 step setting mode]
(Refer to page 23.)
Function Setting
[Function selection mode]
(Refer to page 25.)
Other Functions
(Refer to page 58.)
: The outputs will continue to operate during setting. : If a button operation is not performed for 30 seconds during the setting, the display will flash (This is to prevent the setting from
remaining incomplete if, for instance, an operator were to leave during setting).
: 3 step setting mode and Function selection mode are reflected on each other.
Loading...