SMC Networks ITV10*0-PR*-Q Series, ITV30*0-PR*-Q Series, ITV20*0-PR*-Q Series Installation And Maintenance Manual

ITV2-PR-TFM132
Installation and Maintenance Manual
Electro-Pneumatic Regulator
(for PROFIBUS DP)
ITV10*0-PR****-Q, ITV20*0-PR****-Q, ITV30*0-PR****-Q
1 Safety Instructions
This manual contains essential information for the protection of users and others from possible injury and/or equipment damage.
Read this manual before using the product, to ensure cor rect handling, and read the manuals of related apparatus before use.
Keep this manual in a safe place for future reference.
These instructions indicate the level of potential hazard by label of
“Caution”, “Warning” or “Danger”, followed by important safety information which must be carefully followed.
To ensure safety of personnel and equipment the safety instructions in this manual and the product catalogue must be observed, along with other relevant safety practices.
Caution
Indicates a hazard with a low level of risk, which if not avoided, could result in minor or moderate injury.
Warning
Indicates a hazard with a medium level of risk, which if not avoided, could result in death or serious injury.
Danger
Indicates a hazard with a high level of risk, which if not avoided, will result in death or serious injury.
Electromagnetic compatibility:
This product is class A equipment intended for use in an industrial environment. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbances.
The compatibility of pneumatic equipmen t is the responsibility of the person who designs the pneumatic system or decides its specifications.
Since the products specified here can be used in various operating conditions, their compatibility with the specific pneumatic system must be based on specifications or after analysis and/or tests to meet specific requirements.
Only trained personnel should operate pneumatically operated machinery and equipment.
Compressed air can be dangerous if an operator is unfamiliar with it. Assembly, handling or repair of pneumatic systems should be performed by trained and experienced personnel.
Do not service machinery/equipment or attempt to remove components until safety is confirmed.
Inspection and maintenance of machinery/equipment should only be performed after confirmation of safe locked-out control positions.
When equipment is to be removed, confirm the safety process as mentioned above. Switch off air and electrical supplies and exhaust all residual compressed air in the system.
Before machinery/equipment is re-started, ensure all safety measures to prevent sudden movement of cylinders etc. (Supply air into the system gradually to create back pressure, i.e. incorporate a soft-start valve).
Do not use this product outsi de of the specificatio ns. Contact SMC if it is to be used in any of the following conditions:
Conditions and environments beyond the given specifications, or if the product is to be used outdoors.
Installations in conjunction with atomic energy, railway, air navigation, vehicles, medical equipment, food and beverage, recreation equipment, emergency stop circuits, press applications, or safety equipment.
An application, which has the possibility of having negative effects on people, property, or animals, requiring special safety analysis.
Ensure that the air supply system is filtered to 5 microns.
2 Specifications
Model ITV*010 ITV*030 ITV*050 ITV2090
Min.supply pressure (Set pressure) + 0.1 MPa
(Set pressure)
–13.3 kPa
Max.supply pressure 0.2 MPa 1.0 MPa 1.0 MPa -101 kPa Set pressure range
0.005 ~
0.1 MPa
0.005 ~
0.5 MPa
0.005 ~
0.9 MPa
-1.3 ~ -80 kPa
Supply voltage 24 VDC±10% Current consumption Max. 160 mA Input/output data 12bit/12bit (data 4095 corresponds to 100%F.S.) Linearity Max. ±1%F.S. Hysteresis Max. 0.5%F.S. Repeatability Max. ±0.5%F.S. Sensitivity Max. 0.2%F.S. Temperature characteristics
Max. ±0.12%F.S./°C Operating temperature 0~50°C (without condensation) Protection structure IP65
Model ITV10*0 ITV20*0 ITV30*0
Size (mm) 50×50×124 50×50×146
66×66×167
Weight (No option) 350 g 450 g 750 g
Table 1.
3 Operation Principle
When the input signal increases the supply solenoid valve n turns on and the exhaust solenoid valve o turns off. Supply pressure is passed to the pilot valve p through the supply solenoid valve. The pilot valve will open the main valve allowing partial supply pressure to pass to the out port. The pressure sensor q will provide output pressure feedback to the control circuit r. The control circuit will balance the input signal and output pressure to ensure that the output pressure remains proportional to the input signal.
Fig. 1 - Control diagram
Fig. 2 - Schematic diagram
4 Wiring
Connect the cable to the connector on the main unit as shown in the following diagram. Take precautions, as incorrect wiring will damage the unit. Use a DC power supply capable of supplying the necessary power requirements with minimal ripple. When 3 m straight cable connection is specified, this refers to the power supply cable, the communications cable should be ordered separately.
Item Pin assignment
Wire colour
(Note)
1. +24 V Brown
2. N.C.
3. GND Blue
Connector for power supply
4. N.C.
1. N.C.
2. RXD/TXD_N(A) Green
3. N.C.
4. RXD/TXD_P(B) Red
Connector for
communication
5. N.C.
Table 2.
Note: Wire colour when the optional cable is used.
5 LED Display and Communication Protocol
• LED Display
Fig. 3 – Features of the ITV.
ITEM LED ON LED OFF
RUN Power ON (Green) Power OFF
DIA Diagnostic error (Red) Internal operation is normal BF Profibus communication error (Red) Profibus communication is normal
Table 3.
Communication Protocol
Item Specification Remark Communication protocol
PROFIBUS DP For DP-V0
Baud rate
(Note)
9.6 k/ 19.2 k/ 45.45 k/
93.75 k/ 187.5 k/ 500 k/ 1.5 M/ 3 M/ 6 M/ 12 Mbps
Set by master
GSD-File SMC_1412.GSD Occupied area (Input/output data)
1 word / 1 word Lower 2 bits of 7 bytes of
diagnostic area are for diagnostic
information. Communication data resolution
12 bit (4096 resolution)
Address setting Switch setting /
Software setting
Switching by switch
Terminator Built into the product Switching by switch
Table 4.
Note: Baud rate relates to communication distance
6 Switch Setting
Selection of address setting mode
Node address of the product can be set by software mode (SW) or hardware mode (HW). When software mode is selected, the communication master sets the node address. Setting range is 1 to 125.
Address set switch
In hardware mode use the switches shown, to set the node address.
• Address setting range is 01 to 99.
x10 x1
6 Switch Setting (continued)
Setting the terminator
Set Profibus communication line terminator.
With terminator Without Without (factory setting) terminator terminator
When the product is connected to the Profibus communication line, ensure the switch is set to “with terminator”.
Setting the address switch requires the removal of 4 screws in the front panel of the unit (Fig 3). Take care as the panel hinges to a maximum of 90 degrees.
After setting an address, always close and fix the panel securely. Tighten the screws to torque of 0.6 – 0.8 N•m
7 Communication Data Allocation
Set target value Resolution: 12 bit (100 %F.S.), Occupied byte: 2 Byte
000*
Target value (lower 12 bits)
Target value (O area)
b15 b11 b0
Put 0 in upper 4 bits
(Note)
Monitor the output pressure Resolution: 12 bit (100 %F.S.), Occupied byte: 2 Byte
000*
Output pressure (lower 12 bits)
Output pressure (I area)
b15 b11 b0
Resolution may exceed 12bit depending on control conditions. Monitors the product error. 7 bytes are occupied for external diagnostic data. Diagnostic data allocated to byte 7, as shown below.
Byte7
000000BA
Diagnostic (DIA)
b7 b0
A. Internal diagnostic error 0: Normal 1: Error B. Over range error 0: Normal 1: Error
Note: Although 100 %F.S. for target value is 12 bit, communication is available upto 150 %F.S. (accuracy is guaranteed upto 100 %F.S.) Over range error is output when 150 %F.S. is exceeded. Output pressure at this time is controlled by the input data immediately before the error occurred. Pressure can be set by sending the input data, in which F.S. consists of 12 bits, to the E/P regulator through the master PLC (target value to word area).
Setting data 0000h 0FFFh [ ( a/ F. S. ) x 4095]
HEX
Output pressure 0 % x F.S. (=0) 100 % x F.S. a
f Pressure sensor
g Control circuit
c Supply solenoid valve
d Exhaust solenoid valve
Supply pressure
OUT
+ –
Input signal
e Pilot valve
3
2
4
5
1
Power supply line
Communication line
BF LED
RUN LED
A
ddress switch
DIA LED
OUT
SUP
N O

HW/SW
LED indicator
Power supply
Control circuit
Input signal
Exhaust solenoid valve
Supply solenoid valve
Pilot EXH
Pressure sensor
EXH
SUP OUT
Pilot valve
1
6
4
7
9
0
2 3
5
8
1
6
4
7
9
0
2 3
5
8
ITV2-PR-TFM132
8 Installation & Maintenance
• This product is pre-set at the factory and must not be dismantled by the user. Contact your local SMC office for advice.
• Ensure, when installing this product, that it is kept clear of power lines to avoid noise interference.
• Ensure that load surge protection is fitted when inductive loads are present (i.e. solenoid, relay etc.).
• Ensure precautions are in place if the product is used in a ‘free flow output ’condition. Air will continue to flow continuously.
• Do not use a lubricator on the input side of this product. If lubrication is necessary, place the lubricator on the ‘output’ side.
• Ensure all air is exhausted from the product before maintenance.
• Length of connector cable shall be 10 m maximum.
9 Contacts
AUSTRIA (43) 2262 62280 NETHERLANDS (31) 20 531 8888 BELGIUM (32) 3 355 1464 NORWAY (47) 67 12 90 20 CZECH REP. (420) 541 424 611 POLAND (48) 22 211 9600 DENMARK (45) 7025 2900 PORTUGAL (351) 21 471 1880 FINLAND (358) 207 513513 SLOVAKIA (421) 2 444 56725 FRANCE (33) 1 6476 1000 SLOVENIA (386) 73 885 412 GERMANY (49) 6103 4020 SPAIN (34) 945 184 100 GREECE (30) 210 271 7265 SWEDEN (46) 8 603 1200 HUNGARY (36) 23 511 390 SWITZERLAND (41) 52 396 3131 IRELAND (353) 1 403 9000 UNITED KINGDOM (44) 1908 563888 ITALY (39) 02 92711