SMC Networks IP8000-0 Series,IP8100-0 Series Installation And Maintenance Manual

IP80-TFI03GB-B
Installation and Maintenance Manual
IP8000-0##-# / IP8100-0##-# Electropneumatic Positioner
1 Safety Instructions
This manual contains essential information for the protection of users
and others from possible injury and/or equipment damage.
Keep this manual in a safe place for future reference.
These instructions indicate the level of potential hazard by label of
"DANGER", "WARNING" or "CAUTION", followed by important safety information which must be carefully followed.
To ensure safety of personnel and equipment the safety instructions in this manual and the product catalogue must be observed, along with other relevant safety practices.
WARNING
• The compatibility of pneumatic equipment is the responsibility of the person who designs the pneumatic system or decides its specifications.
Since the products specified here can be used in various operating conditions, their compatibility with the specific pneumatic system must be based on specifications or after analysis and/or tests to meet specific requirements.
• Only trained personnel should operate pneumatically operated machinery and equipment.
Compressed air can be dangerous if an operator is unfamiliar with it.
Assembly, handling or repair of pneumatic systems should be performed by trained and experienced personnel.
• Do not service machinery/equipment or attempt to remove components until safety is confirmed.
1) Inspection and maintenance of machinery/equipment should only
be performed after confirmation of safe locked-out control positions.
2) When equipment is to be removed, confirm the safety process as
mentioned above. Switch off air and electrical supplies and exhaust all residual compressed air in the system.
3) Before machinery/equipment is re-started, ensure all safety
measures to prevent sudden movement of cylinders etc. (Supply air into the system gradually to create back pressure, i.e. incorporate a soft-start valve).
• Do not use this product outside of the specifications. Contact SMC if it is to be used in any of the following conditions:
1) Conditions and environments beyond the given specifications, or if
the product is to be used outdoors.
2) Installations in conjunction with atomic energy, railway,
air navigation, vehicles, medical equipment, food and beverage, recreation equipment, emergency stop circuits, press applications, or safety equipment.
3) An application which has the possibility of having negative effects on
people, property, or animals, requiring special safety analysis.
CAUTION
Ensure that the air supply system is filtered to 5 microns..
2 Specifications
Protect the unit from impact and dropping during transfer and when mounted. It may cause failure of the unit.
• Do not use the unit in places with high humidity & temperature. It may cause malfunctions.
• Do not use this positioner outside of the range of it's specifications as this can cause failure.
*1 : 1/2 split range is possible with the standard type (by adjusting the span) *2 : The stroke is adjustable in 0~60° and 0~100°. *3 : Standard air (JIS B0120): temp.20°C, absolute press. 760mmHg,
ratio humidity 65%.
2.1 How to Order
3 Installation
WARNING
• Do not install unless the safety instructions have been read and understood.
• Since zero-point varies depending on the mounting position, the zero point should be adjusted after installation.
• Avoid hitting the product with metallic objects!
• Avoid using this product in non-explosive environments which can become explosive due to air leakage!
3.1 Environment
WARNING
• Do not use in an environment where the product is directly exposed to corrosive gases, chemicals, salt water, water or steam.
• Do not mount the product in a location where it will be subject to strong vibrations and/or shock.
• Do not mount the product in a location where it is exposed to radiant heat.
• Allow sufficient space for maintenance and adjustment around the product when mounted.
3.2 Piping
CAUTION
• Before piping make sure to clean away all chips, cutting oil, dust etc.
• When installing piping or fitting into a port, ensure that sealant material does not enter the port inside. When using seal tape, leave 1.5 to 2 threads exposed on the end of the pipe/fitting.
3.3 Lubrication
CAUTION
• The positioner has a fixed orifice and nozzle, which contain fine paths in them. Use filtered, dehydrated air and avoid the use of lubricators as this may cause malfunction of the positioner.Ensure that the air supply system is filtered to 5 micron. Setting
3.4 Handling
CAUTION
• Avoid giving impact to the body and torque motor of the positioner, and giving excessive force to the armature because this leads to failure.Handle with care during transport and operation.
• If you leave the positioner at the operation site for a long time without using it, put the cover on it so that rain water does not enter the positioner.If the atmosphere is of high temperature or humidity, take measures to avoid condensation inside. The condensation control measures must be taken thoroughly for export shipment.
• Avoid setting the positioner near magnetic fields because the characteristics are effected.
4 Mounting
4.1 Type IP8000
4.1.1 Example of attaching to actuator
The type IP8000 positioner is compatible with Type IP6000 and IP600 in the attaching pitch. If you are using IP600 and IP6000 already, the bracket for these positioner can be used to attach IP8000 to the actuator.
4.2.2 Connection with feedback shaft
4 Mounting (Continued)
4.1.2 Connection with external feedback lever
4.2 Type IP8100
4.2.1 Example of attaching to actuator
The type IP8000 positioner is compatible with type IP610 and IP6100 in the attaching pitch. If you are using IP610 or IP6100 already, the bracket can be used to attach IP8000 to the actuator. If you change from IP6100 to IP8100 and select accessory H (with external scale plate), fork lever type fitting needs to be adjusted at lower position.
Type IP8000 IP8100
Lever type lever Rotary type cam Item Single action Double action Single action Double action Input current 4~20mADC (Standard)*
1
Input resistance 235 ± 15Ω Supply air pressure 0.14~0.7MPa Standard stroke 10 ~ 85mm (External
lever allowable
runout angle 10°~ 30°) Sensitivity Within 0.1%F S Within 0.5%F S Linearity Within ± 1%F S Within ± 2%F S Hysteresis Within 0.75%F S Within 1%F S Repeatability Within ± 0.5%F S Thermal coefficient Within 0.1%F S/°C Output flow rate 80 I/min (ANR) or more (SUP=0.14MPa)*
3
Air consumption Within 5 I/min (ANR) (SUP=0.14MPa) Ambient and using fluid temperature Air connection port Rc1/4 (FEMALE) Electric wiring connection port Material Aluminium diecast for the body Mass Approx. 2.6kg with terminal box
(Approx. 2.4kg without terminal box) Classification of degree of protection
60°~ 100°*
2
-20°C ~ 80°C
JISF8007 IP65 (conform to IEC pub.529)
G1/2 (FEMALE)
I P 8 00 - 0 - - Q
TYPE
0 LEVER TYPE 1 ROTARY TYPE
PRESSURE GAUGE (SUP, OUT1)
0 None 1 0.2 MPa (R1/8) 2 0.3 MPa (R1/8) 3 1.0 MPa (R1/8)
CONSTRUCTION 0 NO TERMINAL BOX 1 WITH TERMINAL BOX
EMC CERTIFIED
NOTE:WHEN MORE THAN 2 ACCESSORIES ARE REQUIRED THE SYMBOL SHOULD BE STATED IN ALPHABETICAL ORDER
ACCESSORIES
NIL NO ACCESSORIES
(WITH STANDARD LEVER)
A WITH PILOT VALVE ADDED DIA. 0.7mm
ORIFICE FOR RESTRICTING OUTPUT.
B WITH PILOT VALVE ADDED DIA. 1.0mm
ORIFICE FOR RESTRICTING OUTPUT.
C FORK LEVER ASSEMBLY, TYPE M
(P368010-24)
D FORK LEVER ASSEMBLY, TYPE S
(P368010-25)
E WITH LEVER FEEDBACK UNIT FOR
STROKE 35 ~ 100mm, (WITHOUT STANDARD LEVER)
F WITH LEVER FEEDBACK UNIT FOR
STROKE 50 ~ 140mm, (WITHOUT STANDARD LEVER)
G WITH GAIN SUPPRESSION SPRING (A).
(WITHOUT STANDARD GAIN
SUPPRESSION SPRING) H WITH EXTERNAL SCALE PLATE UNIT J WITH OPENING CURRENT OUTPUT
(4-20mA DC)
Positioner
Bracket
Bracket
Positioner
Positioner
Bracket shape Example
Bracket shape Example
Fig.1 Example of directly attaching to diaphragm valve
Directly attach using the screw hole at the side of the positioner and the screw hole at the yoke side of the diaphragm valve.
Fig.2 Example of attaching using the L-shape bracket
Attach by using screw hole at the side of the positioner and the screw hole at the front mount of diaphragm valve.
Fig.3 Example of attaching using front bracket
Attach by using screw hole at the back of the positioner and the screw hole at the front mount of diaphragm valve.
Fig.7 Example of attaching using the positioner back screw
Attaching using the screw hole at the positioner back and the screw hole at the actuator top.
Fig.6 Example of attaching using the positioner side screw
Attaching using the screw hole of a side of the positioner and the screw hole at the actuator top.
(1) Attach to the position that the
valve stem and lever form the right angle when the input signal is 50% (distribute evenly with 50% input signal set as the reference).
(2) Attach to the position of the
runout angle is within the range of 10° to 30°.
(3) To move the valve stem
downward at the time of input current increase (normal actuation), attach to the position at which the tightening spring comes to the upper side of the connecting metal, as sho
wn in Fig 5.
T
o move the valve stem
upw
ard (reverse actuation), turn-over the feedback lever and attach to the position at which the tightening spring comes to the lower side of connecting metal.
Tighening spring
Right angle
Input 0% (or 100%) position current
Input 100% (or 0%) position current
Input 50% position current
Connecting metal
Valve stem
Positioner body
Fedd back lever
(The stem moves down as the input increases)
Stem direction
Stem direction
Turn over the feed back lever
Fig.4 Attaching the feed back lever
OUT1
OUT2
Bracket shape example
Bracket shape example
OUT1
OUT2
Fig.5 Use position for feedback lever
(1) Attach to the position at
which the positioner feed back shaft and the rotary actuator main shaft are almost concentr
ic (range in which the spring pin of feed back shaft edge enters the hole of fork lever assembly shaft edge).
(2) If the seration joint type for
IP610 is made in a special specification, it can be used for this connection.
Fork lever assembly (P368010-36)
Positionery body
Fork pin unit (P368010-23)
M8 x 1.25
Actuator main shaft
Spring pin
Fig.8 Attaching the feed back lever
DANGER
In extreme conditions, there is a possibility of serious injury or loss of life.
WARNING
If instructions are not followed there is a possibility of serious injury or loss of life.
CAUTION
If instructions are not followed there is a possibility of injury or equipment damage.
4 Mounting (Continued)
4.2.3 Cam attaching procedure
CAUTION
IP80-TFI03GB-B
Table 2
5 Adjustment
CAUTION
Check the following prior to start the adjustment. (1) Check that the pipeline is correctly connected with the pressure
supply port and OUT1 and OUT2 ports. (2) Check that the actuator and positioner are sturdily connected. (3) Check that the span adjusting lever of internal feed back (Type
IP8000) is attached to the correct (normal or reverse) position.
(Refer to Tables 2.)
5 Adjustment (Continued)
(4) Check for locking of the auto/manual changeover screw of pilot valve
(fully tightened in the clockwise direction).
(5) Check for correct use of the cam face (normal or reverse) in Type
IP8100 and that the flange nut is firmly locked. (Refer to Table 2.)
(6) Check that the wires are connected correctly with the (+), (-) and
grounding terminals.
*¹ When the span adjusting screw is turned clock-wise with a slothead(-)
screwdriver, the span increases.When it is turned counter-clockwise, the span decreases.
*² When the span adjusting screw is turned clock-wise with a slothead(-)
screwdriver, the span decreases.When it is turned counter-clockwise, the span increases.
CAUTION
(1) For this positioner, span and zero point adjustment of each actuator is
necessary. Adjustment shall be done based on each actuator size.
(2) Keep in mind that span and zero point adjustment interfere in each
other.
(3) Characteristics changes due to change of mounting position, ambient
temperature and supply pressure.
(4) If it takes along time until the operation after initial adjustment, check
and adjust this product. (5) Sensitive adjustment is effective for only double acting actuator. (6) Manual change function is effective for single acting actuator which is
controlled by using OUT1.
5.1 Electrical wiring (without terminal box)
5 Adjustment (Continued)
Connect the (+) and (-) output terminal of positioner with the (+) and (-) input terminal of positioner respectively.The input port of the electrical connection is equiped with a cable connector G 1/2 female.
5.2 Electrical wiring (with terminal box)
(1) Connect the (+) and (-) output terminals from the regulator with the (+)
and (-) input terminals, respectively, of the positioner terminal box.The port diameter at the conduction wire drawing port is the size of G1/2 parallel screw for piping and the depth is for a 16.5mm female screw.
(2) Two drawing ports, marked as Part A and Part B in Fig.14, are provided.
Use either one as fitted. (Part B is used in the figure).
6 Limitations of Use
WARNING
(1) After installation, repair and disassembly, connect compressed air and
perform a proper function test and leak test. If bleed noise is louder than the initial state, or operation is abnormal, stop operation and check if installation is correct or not.
CAUTION
(1) Check if supply air is clean or not. Inspect compressed air cleaning
system periodically so that dust, oil and humidity, which can cause malfunction and failure of the unit, do not enter the equipment
(2) If handled improperly, compressed air can be dangerous.Maintenance
and replacement of unit parts should only be performed by trained and experienced personnel for instrumentation equipment , as well as following the product specifications.
(3) Check the positioner once a year.When an excessively worn
diaphragm, O-ring or other packing of any unit that has been damaged is found, replace with new ones.Treatment at an early stage is especially important if the positioner is used in a place of severe environment, such as costal areas.
(4) Before removing the positioner for maintenance, or replacing unit parts
after installation, ensure the supply pressure is shut off and all residual air pressure is released from the piping.
(5) When the fixed orifice is clogged with carbon particles or other material,
remove the pilot valve Auto/Manual change over screw (built in fixed aperture) and clean it by inserting a 0.3mm diameter wire into the aperture.
(6) When you disassemble the pilot valve, coat the O-ring of the sliding
section with grease. (Use the TORAY SILICONE SH45 grease.)
(7) Check for air leaks from the compressed air piping. Air leaks could lower
the performance characteristics of the positioner. Air is normally discharged form a bleed port, but this is necessary air consumption based on the construction of the positioner, and is not an abnormality if the air consumption is within the specified range.
(1) Use the DA face of the cam to turn the
actuator main shaft clockwise (viewed from the positioner front cover side) at the time of input signal increase. Use the RAface to turn it counter-clockwise (reverse actuation). Correctly attach the cam to the flange part of feed back shaft.
(2) Attach the cam in the procedure of
loosening the hexagonal nut with flange first, setting the using actuatorto the starting position and then setting the cam reference line and the bearing contact point of span adjusting arm unit to the matching position.
(3) Do not apply the supply pressure when attaching the cam as otherwise it is very
dangerous.
(4) When the positioner is shipped out of our plant, the cam is tentatively tightened to the
shaft. Be sure to firmly lock the cam to the lock nut [tightening torque 2.0 ~ 2.5 Nm.
Counter­clockwise
(Re
verse actuation)
Clockwise
Cam reference
Bearing
(Nor
mal actuation)
Hex.nut with flange
Fig.9 Example of cam attaching
Single action
Reverse actuation
Normal actuation
Double action
IP8000 (Lever type)
IP8100 (Rotary type)
Actuation:The stem moves in the arrow direction when the input current increases.
Actuation:The actuator main shaft tur ns clockwise when the input signal increases.
Actuation:The stem moves in the arrow direction when the input current increases. (Reverse actuation using the normal actuation drive unit).
Actuation:The actuator main shaft tur ns counter-clockwise when the input signal increases.
OUT 1
Span adjusting lever normal position
IN
SUP
IN
IN
IN
OUT 1
Main shaft
Double action actuator
The cam should be set to DA surface.
Double action actuator
Main shaft
The cam should be set to RA surface.
OUT 2
OUT 1
OUT 2
OUT 2
Span adjusting lever normal position
SUP
OUT 2:Plug
OUT 1:Plug
Span adjustment Zero point adjustment
Type IP8000
Zero adjusting knob
Move clockwise
Move counter­clockwise
When the zero adjusting knob is turned clockwise, the starting point increases.When it is turned counter-clockwise, the starting point decreases.
Stroke
Input current
Decrease of starting points
Increase of starting points
Counter­clockwise turn
Adjusting producre
(1) Set the input current to 0% (4mADC in the
standard specification) and turn the zero adjusting knob by hand to set it to the actuator starting point.
(2) Then set the input current to 100% (20mADC in
the standard specification) and check the actuator stroke.At this point depending on the span is too large or too small, loosen the lock screw and adjust the span as shown in the illustration above.
(3) Set the input current to 0% and conduct the zero
point adjudtment, as done in Step (1) again.
(4) Repeat the above operations until the
predetermined stroke of the actuator is obtained to the input current.
(1) Set the input current to 0% (4mADC in the
standard specification) and turn the zero adjusting knob by hand to set it to the actuator starting point.
(2) Then set the input current to 100% (20mADC in
the standard specification) and check the actuator stroke.At this point depending on the span is too large or too small, loosen the lock screw and adjust the span as shown in the illustration above.
(3) Set the input current to 0% and conduct the zero
point adjudtment, as done in Step (1) again.
(4) Repeat the above operations until the
predetermined stroke of the actuator is obtained to the input current.
Too small starting point
Starting point OK
Too large starting point
to span adjustment
Span adjusting screw
Lock screw
Span adjusting screw
Move clockwise
Move counter-clockwise
Too large span
Spam OK
Too small span
Too large span
Spam OK
Too small span
Move counter-clockwise
Move clockwise
Type IP8100
Cable connector
G1/2 female
Input current
Mini-terminal unit
Twisted wire fixing screw
M4 screw for internal grounding terminal connection
Terminal lug (Use twisted wire of 2.63 to 6.64mm²)
Grounding
(Use twisted wire of
0.5 to 1.5mm²)
OUT2
Fig.14 Positioner with terminal box
2-M4 screw input terminal
M4 screw for internal grounding terminal connection
Grounding
Input current
Part B
Part A
- +
M4 screw for external grounding terminal connection
Terminal lug
(Use twisted wire of
2.63 to 6.64mm
2)
7 Contact
URL http://www.smcworld.com (Global) http://www.smceu.com (Europe)
Specifications are subject to change without prior notice from the manufacturer. The descriptions of products in this document may be used by other companies.
© SMC Corporation All Rights Reserved.
AUSTRIA (43) 2262 62280 NETHERLANDS (31) 20 531 8888 BELGIUM (32) 3 355 1464 NORWAY (47) 67 12 90 20 CZECH REP. (420) 541 424 611 POLAND (48) 22 211 9600 DENMARK (45) 7025 2900 PORTUGAL (351) 21 471 1880 FINLAND (358) 207 513513 SLOVAKIA (421) 2 444 56725 FRANCE (33) 1 6476 1000 SLOVENIA (386) 73 885 412 GERMANY (49) 6103 4020 SPAIN (34) 945 184 100 GREECE (30) 210 271 7265 SWEDEN (46) 8 603 1200 HUNGARY (36) 23 511 390 SWITZERLAND (41) 52 396 3131 IRELAND (353) 1 403 9000 UNITED KINGDOM (44) 1908 563888 ITALY (39) 02 92711