Refrigerated Air Dryer
Operation Manual for Option
IDF22E-20-T, IDF22E-30-T IDF37E-20-T, IDF37E-30-T IDF55E-30-T
IDF75E-30-T
- For the other option specifications, refer to the operation manuals corresponding to the option number.
-For the other parts than the options, refer to the standard operation manual.
1. Safety instructions When handling the product, take care to the following precautions.
2. Specification
- Mounting remote signal terminal (Running and Alarm)
- The Running (terminal 1-2) is in a short circuit state during operation.
- The Alarm (terminal 2-3) is in a short circuit state during alarm.
Max. Load: AC220V, 5A (Running) DC24V, 5A (Alarm) Min. Current: 5mA
For IDF22E-20-T, IDF37E-20-T and IDF75E-30-T, even if the over load relay operates,
the Alarm is not output.
3. Remote operation
- Turn on switch with lamp and ON/OFF power supply for remote operation.
- Start operation after stopping for 3 minutes or more.
- In addition, frequency of start/stop shall not be more than 5 times per hour.
(for preventing compressor motor trouble.)
Only qualified person must perform wiring and obserbing the following points.
1. Be sure to shut off the power supply before wiring. For safety, do not perform any work on the unit
with the power supply on. The power supply cannot be completely shut off just by turning off the
illuminated switch. Be sure to turn off all power lines connected to the product.
2. Supply the power from a stable source, free from surges.
3. Be sure to mount the Ground Fault Circuit Interrupter (GFCI) with adequate sensitivity and load
capacity to prevent electrical shock and protect the refrigerating compressor motor from burning out.
4. Provide the power suitable for the product specifications.
5. Be sure to ground the product for the safety. Without grounding, the GFCI can not operate normally.
6. Do not ground to water pipe, gas tube or lightening rod line.
7. Do not connect too many wires to the same outlet, which could results in heat generation and fire.
8. Do not retrofit the wiring of the dryer and the power supply line.
9. For the use of the product in Europe, mount the breaker compatible to IEC standard to the power
supply for the product.
Warning
IDX-OM-K052-A
- 2 -
Rubber Grommet
Power cord outlet
Detail of terminal block
Grommet
Signal cord outlet
4. Installation
- Remove the Front panel.
- Insert the power cord through the Rubber Grommet and connect it to terminal block.
- Insert the signal cord through the Grommet and connect it to terminal block.
- Install Front panel.
Connections for customer Terminal screw : M3 (Tighten torque 0.6 Nm to 1.0Nm) Connecter width: 6.5mm or less Suitable wire Power cord: 1.25mm
2
to 2mm2
Signal cord: 0.5 mm
2
to 2mm2
Front panel
L
NPE1 2
3
Power Source
Alarm
Ground
Running
For IDF22E-20-T For IDF22E-30-T,IDF37E-30-T, and IDF37E-20-T  IDF55E-30-T and IDF75E-30-T
L1
L2 PE 1 2
3
Power Source
Alarm
Ground
Running