SMC Networks HRW008-H, HRW002-H1, HRW030-H, HRW002-H, HRW008-H1 Operation Manual

...
Page 1
HRX-OM-K003
HRW002-H
HRW008-H
HRW015-H
HRW030-H
HRW002-H1
HRW008-H1
HRW015-H1
HRW030-H1
HRW002-H2
HRW008-H1
HRW015-H2
HRW030-H2
HRW002-HS
HRW008-HS
HRW015-HS
HRW030-HS
HRW002-H1S
HRW008-H1S
HRW015-H1S
HRW030-H1S
HRW002-H2S
HRW008-H1S
HRW015-H2S
HRW030-H2S
1st Edition: July 2006
Rev. G: May 2018
Operation Manual
Original Instructions
THERMO CHILLER
Save This Manual Carefully for Use at Any Time
© 2018 SMC CORPORATION All Rights Reserved
Page 2
To the Customers
Note: The contents of this manual are subject to change without notice.
Thank you for purchasing our THERMO CHILLER HRW Series (hereinafter called “This system”).
For the long-term, safe use of this system, be sure to read and understand this manual thoroughly before performing operation of this system.
Warnings and precautions defined in this manual shall be observed.
This manual provides the explanations of the installation and operation of this system. Only those who have
thorough understanding of the fundamental operating procedure or have basic knowledge and skills of handling industrial equipment for the installation and operation of this system are qualified to perform installation and operation.
The contents of this manual and related documents supplied with this system shall be neither regarded as a
provision of the contract nor utilized to correct or modify the existing agreements, commitments and relations.
Copying, duplicating or transferring any part of or whole contents of this manual without the prior written consent
of SMC Corporation is strictly prohibited.
The Service Manual is supplied in addition to this manual and provides the explanations of the inspection,
troubleshooting, and in-depth remedies of this system. The Service Manual is intended for service personnel that completed service training SMC provides. Only those who fall under the above condition are allowed to perform maintenance and repair of this system with the use of the Service Manual.
Page 3
HRX-OM-K003
TOC-1
Table of Contents
Table of Contents
Chapter 1 Safety.................................................................................... 1-1
1.1 Before Using this System ....................................................................................... 1-1
1.2 Danger, Warning, and Caution Used in This Manual............................................. 1-2
1.2.1 Hazard Levels ..................................................................................................................... 1-2
1.2.2 Definitions of “Serious injury” and “Minor injury” ................................................................. 1-2
1.2.3 Symbols ............................................................................................................................... 1-3
1.3 Hazard Warning Label ............................................................................................. 1-4
1.3.1 Type of hazard warning label .............................................................................................. 1-4
1.3.2 Location of hazard warning label ........................................................................................ 1-5
1.4 Location of Model Label ......................................................................................... 1-7
1.5 Safety Measures ...................................................................................................... 1-8
1.5.1 Safety Precautions .............................................................................................................. 1-8
1.5.2 Safety Interlock system ....................................................................................................... 1-9
1.5.3 Lockout/Tagout .................................................................................................................. 1-10
1.5.4 Protective equipment ......................................................................................................... 1-12
1.6 Emergency Measures............................................................................................ 1-13
1.6.1 Emergency off [EMO] switch ............................................................................................. 1-13
1.7 Waste Disposal ...................................................................................................... 1-15
1.7.1 Circulating fluid disposal.................................................................................................... 1-15
1.7.2 System disposal ................................................................................................................ 1-15
1.8 Material Safety Data Sheet (MSDS) ...................................................................... 1-15
Chapter 2 Name of Each Section ......................................................... 2-1
2.1 Name of Each Section ............................................................................................. 2-1
Chapter 3 Transporting and Installation .............................................. 3-1
3.1 Transporting ............................................................................................................ 3-1
3.1.1 Transporting with forklift ...................................................................................................... 3-2
3.1.2 Transporting with caster ...................................................................................................... 3-3
3.2 Installation ................................................................................................ ............... 3-3
3.2.1 Installation conditions .......................................................................................................... 3-4
3.2.2 Installation location and maintenance work area ................................................................ 3-5
3.3 Procedure for Installation ....................................................................................... 3-6
3.3.1 Installation ........................................................................................................................... 3-6
3.3.2 Procedure for system securing ........................................................................................... 3-6
3.3.3 Wiring installation ................................................................................................................ 3-7
3.3.4 Procedures for wiring installation ........................................................................................ 3-9
3.3.5 Installation of circulating fluid and facility water piping ...................................................... 3-12
HRW Series
Page 4
HRX-OM-K003
TOC-2
Table of Contents
Chapter 4 System Startup and Shutdown ............................................. 4-1
4.1 Pre-check .................................................................................................................. 4-1
4.1.1 Installation condition ............................................................................................................ 4-1
4.1.2 Cable connection ................................................................................................................. 4-1
4.1.3 Installation of circulating fluid and facility water piping ........................................................ 4-1
4.1.4 Operating signal from your system ...................................................................................... 4-1
4.1.5 Check emergency off [EMO] switch .................................................................................... 4-1
4.2 Opening of Facility water Valve .............................................................................. 4-1
4.3 Supply of Circulating Fluid ...................................................................................... 4-2
4.3.1 Preparation of circulating fluid ............................................................................................. 4-2
4.3.2 Supply of circulating fluid ..................................................................................................... 4-3
4.4 Requirement for System Startup ............................................................................ 4-4
4.4.1 Turning ON power................................................................................................................ 4-4
4.4.2 Circulating fluid temperature setting .................................................................................... 4-5
4.5 System Startup and Shutdown ............................................................................... 4-5
4.5.1 System startup ..................................................................................................................... 4-5
4.5.2 System shutdown ................................................................................................................ 4-5
Chapter 5 System Operation ................................................................ 5-1
5.1 Operation Display Panel .......................................................................................... 5-1
5.2 Flow Chart of Operation Screen.............................................................................. 5-2
5.3 Operation Screen ..................................................................................................... 5-3
5.3.1 Model Indication screen ....................................................................................................... 5-3
5.3.2 Status screen 1 .................................................................................................................... 5-3
5.3.3 Status screen 2 .................................................................................................................... 5-4
5.3.4 Status screen 3 .................................................................................................................... 5-4
5.3.5 Status screen 4 .................................................................................................................... 5-5
5.3.6 Menu screen ........................................................................................................................ 5-5
5.3.7 Setting screen ...................................................................................................................... 5-6
5.3.8 Mode Selection screen ........................................................................................................ 5-6
5.3.9 Initial Setting screen ............................................................................................................ 5-7
5.3.10 Maintenance screen ............................................................................................................ 5-9
5.3.11 Option screen ...................................................................................................................... 5-9
5.3.12 Alarm Display screen ......................................................................................................... 5-10
5.3.13 Information screen ............................................................................................................. 5-10
5.4 Examples of System Operation ............................................................................ 5-11
5.4.1 Example 1: Circulating fluid set temperature is changed from 25.0°C to 34.1°C. ............. 5-11
5.4.2 Example 2: Communication mode is switched from “DIO REMOTE” to “LOCAL”. ........... 5-13
5.4.3 Example 3: Alarm signal of contact signal is changed from “N/A” to “ALARM1”. .............. 5-14
Chapter 6 Error Message and Troubleshooting ................................. 6-1
HRW Series
Page 5
HRX-OM-K003
TOC-3
Table of Contents
6.1 Error Message ......................................................................................................... 6-1
6.2 Troubleshooting ................................ ...................................................................... 6-2
Chapter 7 System Maintenance ........................................................... 7-1
7.1 Water Quality Management ..................................................................................... 7-1
7.2 Inspection and Cleaning ......................................................................................... 7-2
7.2.1 Daily inspection ................................................................................................................... 7-2
7.2.2 Quarterly inspection ............................................................................................................ 7-3
7.3 Storage ..................................................................................................................... 7-3
7.3.1 Draining of circulating fluid out of tank ................................................................................ 7-4
7.3.2 Draining of facility water ...................................................................................................... 7-5
7.4 Periodic Replacement Parts ................................................................................... 7-6
Chapter 8 Appendix .............................................................................. 8-1
8.1 Specification ............................................................................................................ 8-1
8.1.1 System specification ............................................................................................................ 8-1
8.1.2 Communication specification............................................................................................... 8-4
8.1.3 Alarm signal selection ......................................................................................................... 8-6
8.2 Outer Dimensions ................................................................................................... 8-7
8.3 Flow Chart ................................................................................................................ 8-8
8.3.1 Part 1 ................................................................................................................................... 8-8
8.3.2 Part 2 ................................................................................................................................... 8-8
8.4 Offset Function ........................................................................................................ 8-9
8.4.1 Example of offset function ................................................................................................. 8-10
8.5 BAND/READY function ......................................................................................... 8-12
8.6 Anchor Bolt Mounting Position ............................................................................ 8-13
8.7 Compliance ............................................................................................................ 8-14
8.8 Thermo Chiller Daily Inspection Sheet ................................................................ 8-15
Product Warranty ............................................................................................................ 8-19
HRW Series
Page 6
HRX-OM-K003
TOC-4
Table of Contents
HRW Series
Page 7
1-1
Chapter 1 Safety
Be sure to read and understand the important precautions defined in this manual thoroughly prior to system use.
1.1 Before Using this System
This "Safety" chapter describes the safety-related items that users should be
aware of upon handling this system.
This system, which is operated under high voltage, is outfitted with the parts
that cause a rise in temperature and rotating parts when it is in action, All personnel who work with or around this system are required to thoroughly read and understand the safety-related items in this manual prior to working with or around this system.
This manual is not intended to be used as a manual for comprehensive safety
and hygiene education. Such a manual should be provided by a safety training manager.
HRX-OM-K003
Chapter 1 Safety
All personnel who work on or around this system are to have proper training
and education on dangers specific to this system and safety measures against potential hazards.
A safety manager is responsible for observing safety standards. Operators and
maintainers, however, are to have individual responsibilies for complying with the safety standard in his/her daily work.
Operators and maintainers must individually take account of safety and assure a
proper working area and working environment.
The relevant personnel must receive proper safety education prior to work
training on this system. Otherwise, personnel may be exposed to hazards. Never conduct work training without giving proper consideration to safety.
Save this manual at a designated place for reference when necessary.
HRW Series 1.1 Before Using this System
Page 8
HRX-OM-K003
1-2
"DANGER" denotes that there is an imminent hazard which will cause serious personal injury or death during operation.
"WARNING" denotes that there is a hazard which may cause serious personal injury or death during operation.
"CAUTION" denotes that there is a hazard which may cause minor personal injury during operation.
"CAUTION" without an exclamation symbol denotes that there is a hazard which may cause damage or failure of this system, facility, or devices.
Chapter 1 Safety
1.2 Danger, Warning, and Caution Used in This Manual
1.2.1 Hazard Levels
This system is designed with its first priority being the safety of workers and the prevention of system damage. This manual classifies the risks into the following three categories according to the severity and level of the hazard; Danger, Warning, and Caution. Read the statements carefully, thoroughly understand them before operating this system.
DANGER, WARNING and CAUTION signs are in order according to hazard severity (DANGER > WARNING > CAUTION). See below for the details.
[Tips]
Tips are provided when there is information personnel are required to be aware of for system operation and maintenance. If the task carries useful information, the relevant tips are given as well.
1.2.2 Definitions of “Serious injury” and “Minor injury”
“Serious injury”
This term describes injuries such as loss of eyesight, wound, burns, frostbite, electric shock, fracture, and toxication that leave aftereffects, and/or injury requiring hospitalization and/or prolonged staying in a hospital.
“Minor injury”
This term describes injuries that do not require hospitalization or prolonged staying in a hospital (injuries other than “serious injuries” described above).
1.2 Danger, Warning, and Caution Used in This Manual HRW Series
Page 9
1-3
1.2.3 Symbols
This symbol denotes “Don’t” item which you must not do in operation of this system.
This symbol denotes the “obligation” items which
you must follow in operation of this system.
This symbol warns you of potential electrical shock.
This symbol warns you of potential burns.
This manual provides the following symbols in addition to “Danger”, “Warning”,
and “Caution” to present the warning details in easy-to-understand manner.
Symbol of electrical hazard
Symbol of heat hazard
HRX-OM-K003
Chapter 1 Safety
Symbol of “Don’ts”
Symbol of “Dos”
HRW Series 1.2 Danger, Warning, and Caution Used in This Manual
Page 10
HRX-OM-K003
1-4
[High voltage hazard]
This warning label is affixed on the part isolated with the cover panel of the system panel in which high voltage is applied. Do not remove cover panels that are not designated in this manual.
Figure 1-1 Hazard warning label No.1
Figure 1-2 Hazard warning label No.2
Figure 1-3 Hazard warning label No.3
[Hot surface hazard]
This warning label is affixed on the surface that is at high temperatures carrying potential burns if touched. Residual heat may cause burns despite the power being turned OFF. Be sure of the surface reaching room temperature before work.
Figure 1-4 Hazard warning label No.4
Figure 1-5 Hazard warning label No.5
Chapter 1 Safety
1.3 Hazard Warning Label
The hazard warning labels are applied to the sections of this system where potential hazards are present during system operation and maintenance.
The hazard warning labels are in appropriate sizes and colors to get attention of the operator. They contain symbols in addition to the descriptions of warnings.
1.3.1 Type of hazard warning label
The hazard warning labels affixed on this system are listed below.
Labels of high voltage hazard
Labels of hot surface hazard
1.3 Hazard Warning Label HRW Series
Page 11
1-5
1.3.2 Location of hazard warning label
Figure 1-6 High Voltage Hazard
Confirm the locations of the hazard warning labels. Read the contents of the hazard warning labels carefully and keep them in
mind.
Do not peel off or deface the hazard warning labels.
Users are NOT allowed to change the locations of the hazard warning labels. Make sure to affix a new label to exactly the same location of the replaced label upon replacement of the peeled off or worn out label.
Hazard warning label No.2
Hazard warning label No.1
Front
Hazard warning label No.3
HRX-OM-K003
Chapter 1 Safety
High voltage hazard
HRW Series 1.3 Hazard Warning Label
Page 12
HRX-OM-K003
1-6
Figure 1-7 Hot Surface Hazard
Front
Rear
Hazard warning label No.4
Hazard warning label No.5
Chapter 1 Safety
Hot surface hazard
1.3 Hazard Warning Label HRW Series
Page 13
1-7
1.4 Location of Model Label
Figure 1-8 Location of Model Label
Label
Front
SERIAL NO. MODEL NO.
Rear
Information on your system such as Serial No. and Model No. need to be furnished when you contact the store you purchased from. Serial No. and model No. are listed on the label as shown below.
HRX-OM-K003
Chapter 1 Safety
HRW Series 1.4 Location of Model Label
Page 14
HRX-OM-K003
1-8
Follow the following instructions upon operation of this system. Failure to follow the instructions can lead to personal injury or hazardous accidents.
Chapter 1 Safety
1.5 Safety Measures
1.5.1 Safety Precautions
While this system is protected by various safety measures including the safety interlocks, the following basic safety precautions should be observed to assure further safe operations.
Read and understand this manual thoroughly before operation of this system.
Before operating the system during maintenance, inform all personnel who are
working in the vicinity of the system to alert them of your action.
Use appropriate tools and follow proper procedures.
See “1.5.4 Protective equipment”to wear protective equipment properly.
Refer to your safety manual for emergency evacuation.
Use assistance to carry object over 20 kg.
Check that all parts and screws are returned to the pre-work conditions at the
end of work.
Do not work when intoxicated or feeling ill. Accidents may occur if
disregarded.
Do not remove a panel unless permitted in this manual.
1.5 Safety Measures HRW Series
Page 15
1-9
1.5.2 Safety Interlock system
Figure 1-9 Front Panel
Front
Front panel
Breaker handle
Safety Interlock system
The function of the safety interlock system is not only protect personnel by restricting operation that may cause damage to this system or the facility around it but also eliminate the danger relating to safety. This system is outfitted with several interlock functions that are activated when improper operation or hazardous conditions occur. System operation shall be terminated when a safety interlock is activated
An alarm message is displayed on the LCD screen when a safety interlock is
activated. See “Chapter 6 Error Message and Troubleshooting” for details on the alarms and remedies or see section “Troubleshooting” in a separate volume of the “Service Manual”.
Front panel
System repair may require the removal of the front panel. The breaker handle operation is available only with the front panel attached.
HRX-OM-K003
Chapter 1 Safety
HRW Series 1.5 Safety Measures
Page 16
HRX-OM-K003
1-10
Figure 1-10 Lockout/Tagout
Those who engage in service of this system should build an awareness of
the importance of lockout. Thorough understanding of the procedures defined in this manual are required for system service.
Lockout is allowed only when the system come to a full stop. A supervisor should be appointed to direct all personnel if multiple
workers engage in system service. The supervisor is to perform lockout based on a full understanding of overall process conditions.
Not only all personnel but new personnel that engage in service of this
system should build an awareness of the importance of lockout and obtain thorough understanding of the lockout procedure.
Any personnel working in an area with high voltage should be assigned
with padlocks and tags. The key for the padlock is kept under the responsibility of the supervisor, and lockout release is performed upon completion of work.
Main breaker
Padlock Tag
Front
Chapter 1 Safety
1.5.3 Lockout/Tagout
Summary
Lockout in this system disables the main breaker operation to prevent electric shocks. Tagout, to be placed on a locked out main breaker, to prevent improper breaker operation (ON) conducted by other personnel. See “Lockout procedure” in the following pages for practical lockout/tagout.
1.5 Safety Measures HRW Series
Page 17
1-11
Lockout procedure
Figure 1-11 Breaker Handle at ‘OFF
Figure 1-12 Breaker Handle at ‘RESET’
Figure 1-13 Pulling-out of Lock Mounting Part
Figure 1-14 Breaker Lock
Padlock
Lock mounting part
Lock mounting part
All service personnel must observe the restrictions applied during lockout and are required to perform lockout in accordance with this procedure. No service personnel is allowed to start, energize, or use the locked out system.
1. Turn the breaker handle to ‘OFF ’.
HRX-OM-K003
Chapter 1 Safety
2. Turn the breaker handle to ‘RESET’.
Hold the breaker handle with hand.
The handle turns back to ‘OFF ’ if released.
3. Pull the lock mounting part out of the
breaker handle, and turn the breaker handle to ‘OFF ’.
The lock mounting part is to remain pulled
out.
4. Lock the lock mounting part with the
padlock.
Releasing lockout
1. Remove the padlock from the lock mounting part.
2. Turn the breaker handle to ‘RESET’.
The lock mounting part is pulled in.
The handle turns back to ‘OFF ’ if released.
HRW Series 1.5 Safety Measures
Page 18
HRX-OM-K003
1-12
Read and understand the relevant operation manual thoroughly prior to use of protective equipment.
Chapter 1 Safety
1.5.4 Protective equipment
This manual defines protective equipment according to work type. Wear proper protective equipment as shown below, according to work type.
For system transportation, installation and removal
Protective footwear Protective gloves Hard hat
For handling circulating fluid
Protective footwear Protective gloves Protective mask Protective apron Protective goggles
For system operation
Protective footwear Protective gloves
1.5 Safety Measures HRW Series
Page 19
1-13
1.6 Emergency Measures
Figure 1-15 Location of Emergency Off [EMO] Switch
1.6.1 Emergency off [EMO] switch
Press the red emergency off [EMO] switch on the front of the system only if the need to shut off the power arises due to emergency such as natural disaster, fire, earthquake or personal injury.
The emergency off [EMO] switch is a large, red mushroom-shaped push button labeled with ‘EMO’ on it. The system comes to a halt if this button is pressed.
When press the emergency off [EMO] switch, the control power for this system is shut off to bring the system to a stop. The main breaker of this system, however, is designed not to trip, which enables the motor circuit to remain partially energized. 8.1.2 Communication specification” in Chapter 8 Appendix on page 8-4 to view the circuit diagram and see how the EMO switch is interconnected to the system.
Restart of this system is enabled only when this button is reset manually.
Location of emergency off [EMO] switch
HRX-OM-K003
Chapter 1 Safety
HRW Series 1.6 Emergency Measures
Page 20
HRX-OM-K003
1-14
Figure 1-16 Emergency Off [EMO] Switch
No automatic recovery is applied to the emergency off [EMO] switch. Always eliminate the cause of activating the EMO before resetting. Potential serious accidents may occur if disregarded.
When the system is in remote mode, the remote mode is retained despite the power outage. Thus the system operation is to resume as the start signal is issued from your system.
Chapter 1 Safety
Reset of emergency off [EMO] switch
1. Before restarting, always make sure that the cause of the emergency off condition (The
reason why the EMO switch was activated) has been eliminated from the power supplies, the system and peripheral equipment.
2. With the cause completely eliminated,
turn the emergency off [EMO] switch clockwise to reset.
The EMO button returns to its original position.
3. The screen then changes from the “Model Indication screen” to “Status screen 1” as power
is being restored to the system.
1.6 Emergency Measures HRW Series
Page 21
1-15
1.7 Waste Disposal
Disposal of the fluid and system must be in accordance with regulations and rules of local authorities.
1.7.1 Circulating fluid disposal
As to the disposal of a circulating fluid (ethylene glycol solution, fluorinated fluid), consign the specialized industrial waste disposal agency with the contents detailed.
1.7.2 System disposal
As to the disposal of this system, consign the specialized industrial waste disposal agency in accordance with local laws and regulations.
HRX-OM-K003
Chapter 1 Safety
1.8 Material Safety Data Sheet (MSDS)
Material Safety Data Sheet (MSDS) is supplied separately. Contact the system supplier if you need the MSDS regarding chemicals used in this system.
For each chemical you purchased, the relevant MSDS is to be obtained under your responsibility. Keep the MSDS along with this manual in the condition that allows all personnel to check the contents anytime to gain the understanding of potential hazards.
HRW Series 1.7 Waste Disposal
Page 22
HRX-OM-K003
1-16
Chapter 1 Safety
1.8 Material Safety Data Sheet (MSDS) HRW Series
Page 23
Chapter 2 Name of Each Section
2-1
Caster w/ brake
Rotates 360°.
Operation display panel
Emergency off [EMO] switch Main breaker
Ventilating hole (intake side)
Power cable access
Ventilating fan (exhaust side)
Circulating fill port
Facility water inlet
Circulating fluid supply
Circulating fluid level gauge
Circulating fluid return
Tank drain port
Drain pan port
Facility water outlet
Chapter 2 Name of Each Section
2.1 Name of Each Section
HRX-OM-K003
[Tips]
Figure 2-1 Name of Each Section
HRW Series 2.1 Name of Each Section
The casters have built-in brakes. The disengagement of the brakes is required when transporting the system.
Page 24
HRX-OM-K003
2-2
Chapter 2 Name of Each Section
2.1 Name of Each Section HRW Series
Page 25
HRX-OM-K003
3-1
Proper procedure must be followed when using this system. Exercise caution to assure personnel safety during the installation, operation, maintenance, and inspection of the system.
Only personnel, who have adequate knowledge and experiences with not only this system but associated equipment are allowed to perform transport, installation, and maintenance involving potential hazardous task.
For transporting with the forklift, be sure to insert the fork into a designated position, referring to “3.1.1 Transporting with forklift on page 3-2.
Do not set this system on its side during transportation. Drain the remaining fluid out of the pipe as much as possible. The remaining fluid may spill if disregarded.
Exercise caution not to damage the panel and piping with the forklift when transporting the system.
Chapter 3 Transporting and Installation
Chapter 3 Transporting and Installation
3.1 Transporting
This system is heavy, which poses potential danger at transportation. When transporting this system, the following safety precautions should be observed to prevent system damage and breakdown.
HRW Series 3.1 Transporting
Page 26
HRX-OM-K003
3-2
Figure 3-1 Transport with Forklift
This system is heavy, and requires a forklift to safely move it. Forklift insertion positions are on either left or right side of this system.
Always insert the forks all the way through. Be careful not to hit the casters.
Do not set this system on its side for transportation. Potential damage to
this system carrying danger of personnel injury if disregarded.
Do not insert the fork from the back as well as front.
Rear
Front
Forklift insertion side
Forklift insertion side
Chapter 3 Transporting and Installation
3.1.1 Transporting with forklift
3.1 Transporting HRW Series
Page 27
3-3
3.1.2 Transporting with caster
This system is heavy, which requires assistance for this work. Exercise caution and look out for sloped surfaces such as ramps, etc.
Do not grab piping on the back of this system or panel handles when transporting with the casters. Potential damage to piping and panels may occur if disregarded.
System installation should be kept from areas with the potential of flammable gas leak. Ignition may occur if leaked gas is collected around the system.
This system is NOT designed for outside use. Potential electric shock, fire and system damage may occur if exposed to rain, water and dust.
This system is to be installed on a level floor that can withstand the weight of this system. Potential water leak and personal injury due to system tipping over may occur if disregarded.
3.2 Installation
HRX-OM-K003
Chapter 3 Transporting and Installation
HRW Series 3.2 Installation
Page 28
HRX-OM-K003
3-4
Chapter 3 Transporting and Installation
3.2.1 Installation conditions
System installation is not allowed outside or in the conditions described below. Potential system malfunction and damage may occur if disregarded.
Clean room specifications are not applied to this system. The pump and ventilating fan installed in this system generate particles.
Location that is exposed to water, water vapor, salt water, and oil
Location that is exposed to dust
Location that is exposed to corrosive gas, organic solvent, chemical solution,
and flammable gas (this system is not flame-proof)
Location where ambient temperature is out of the following range:
In transportation -40 to 70°C (with no water or circulating fluid in piping)
In storage 0 to 50°C (with no water or circulating fluid in piping)
In operation 10 to 35°C
Location where ambient humidity is out of the following range or where
condensation forms:
In transportation and storage 15 to 85%
In operation 30 to 70%
Location that is exposed to direct sun light or radiant heat
Location that is near heat sources and poor in ventilation
Location that is subjected to abrupt changes in temperature
Location that is subjected to intense electromagnetic noise (intense electric field,
intense magnetic field, or surges)
Location that is subjected to static electricity, or condition that discharges static
electricity to the system
Location that is subjected to strong high frequencies
Location that is subjected to potential lightning damage
Location with altitudes of 1000m or higher (except for system storage and
transport)
Location that is affected by strong vibrations or impacts
Condition that applies external force or weight causing the system deformation
Condition with no adequate space for maintenance as required
3.2 Installation HRW Series
Page 29
Chapter 3 Transporting and Installation
3-5
Front
Daily inspection area
Operation area
Front
3.2.2 Installation location and maintenance work area
This system does not have ventilating hole on the both right and left sides. Although this can be installed directly contacting to walls or devices, installation with maintenance space is recommended. (See “Figure 3-2”)
HRX-OM-K003
Figure 3-2 Recommended Installation Location
To save space, this system can be installed to allow access only in front and back for daily operation and inspection. For maintenance and repair work, additional access space is required for the left and right side of the system. We recommend a separate repair area, without taking space from installation site, to accommodate the needed extra space.
Figure 3-3 Installation Location
HRW Series 3.2 Installation
Page 30
HRX-OM-K003
3-6
Anti-seismic bracket is an optional part, which is required for the installation of this
system (HRZ-TK002).
Preparation of anchor bolts suitable for floor material is your responsibility. Prepare
M12-anchor bolts (4 pcs.) for installation. See 8.6 Anchor Bolt Mounting Position on page 8-13 for mounting of the anchor bolt.
Figure 3-4 Anti-seismic Bracket Attachment
Drain pan port is assigned to the bottom on the back of this system. Exercise caution not to damage the dain pan port when attaching the anti-seismic bracket.
Anti-seismic bracket (optional) HRZ-TK002
M8 nut (2 pcs.)
(Accessory for anti-seismic bracket)
Caster w/ brake
Front
Brake lever
M12 anchor bolt
Chapter 3 Transporting and Installation
3.3 Procedure for Installation
3.3.1 Installation
System installation should be on a vibration-free stable level plane.
See “Appendix 8.2 Outer Dimensions” in Chapter 8 on page 8-7 for the
dimensions of this system.
3.3.2 Procedure for system securing
1. Transfer this system to the installation site.
2. Lock the brakes on casters.
3. Using a13-mm open end wrench, attach the anti-seismic brackets to the front and back.
3.3 Procedure for Installation HRW Series
Page 31
3-7
3.3.3 Wiring installation
Item
Type
Power
cable
Size (recommended)
10AWG4-conductor
Crimp contact
(recommended)
Breaker
R5.5-8
Earth bar
R5.5-8
Torque
(recommended)
Breaker
12.5N•m (1.84 ft-lbf)
Earth bar
12.5N•m (9.22 ft-lbf)
Main breaker (This System)
30A
Connector
Type (for your system)
Contact signal (P1 connector)
D-Sub 25-pin (male)
Serial RS-485 (P2 connector)
D-Sub 9-pin (male)
Only designated personnel are allowed to install wiring. Be sure to turn OFF the power prior to wiring to assure safety.
Do not do any wiring when the system is energized.
The system wiring requires not only a thorough connection with the
designated cable but also securing to prevent loose connection. Poor connection and securing may cause electric shock, heat sports, fire or communication errors.
Be sure to supply the power to this system according to specifications. Supply pure AC power. Potential malfunction may occur if a rectified AC
with voltage rise (dv/dt) at zero crossing exceeds 40V /200µ sec.
Always establish a connection to a ground for safety. Be sure that no ground connection is made to
a water pipe, gas pipe and lighting rod.
V
dV
dt
dt
= Voltage ratio
on zero-cross point
dV
t
Voltage rise %
Time
Voltage
Power cable
The power cables are to be prepared under your responsibility, referring to the following table.
HRX-OM-K003
Chapter 3 Transporting and Installation
Table 3-1 Power Cable and Main Breaker (This System)
Communication connector
The communication connectors are to be prepared under your responsibility, referring to the following table.
Table 3-2 Communication Connector
HRW Series 3.3 Procedure for Installation
Page 32
HRX-OM-K003
3-8
This product is equipped with the breaker which has different operating characteristics depending on each model. For the customers equipment (primary side), use the breaker whose operating time is equal to or longer than the breaker of this product. If the breaker with shorter operating time is connected, the customers equipment could be cut off du eto the inrush current of the motor of this product.
100 135 200 300 400 500 600 700 1000 1500 2000 3000 4000 5000 7000 10000
4h 2h
1h 30min
20min 14min 10min
6min 4min
2min 1min
30s 20s
10s 5s
2s 1s
0.5s
0.2s
0.1s
0.05s
0.02s
0.01s
MAX
MIN
Current (% to the capacity of the main breaker of this product)
Operating Time
Figure 3-5 Breaker operating characteristics curve
Chapter 3 Transporting and Installation
Selection of the breaker for the customers equipment (primary side)
HRW002-H HRW008-H HRW015-H HRW030-H HRW002-H1 HRW008-H1 HR W015-H1 HRW030-H1 HRW002-H2 HRW008-H2 HRW015-H2 HRW030-H2 HRW002-HS HRW008-HS HRW015-HS HRW030-HS HRW002-H1S HRW008-H1S HRW015-H1S HRW030-H1S HRW002-H2S HRW008-H2S HRW015-H2S HRW030-H2S
3.3 Procedure for Installation HRW Series
Page 33
HRX-OM-K003
3-9
M
F
Be sure to turn OFF the factory side (primary side) power before connection to this system. Use the assigned procedure to peform lockout/tagout (Page 1-10).
Figure 3-6 Main Breaker OFF and Removal of Front Panel/Breaker Cover
Front
Front panel
Screw
Screw
OFF
Breaker cover
Breaker
Main breaker OFF
Chapter 3 Transporting and Installation
3.3.4 Procedures for wiring installation
1. Turn OFF the power breaker on customer side (primary side), and then use the assigned
procedures to peform lockout/tagout.
[Tips]
Connection of the power cable with this system must be established first. Do not connect the cable with the factory side at this point.
2. Turn OFF the main breaker of this system.
3. Undo the screws (2 pcs.) to remove the front panel.
Be sure to use a Phillips screwdriver.
4. Undo the screws (2 pcs.) to remove the breaker cover.
Be sure to use a Phillips screwdriver.
[Tips]
Make sure the breaker is at the ‘OFF’ position. Otherwise, the removal of the front panel is not possible.
HRW Series 3.3 Procedure for Installation
Page 34
HRX-OM-K003
3-10
Figure 3-7 Power Cable Insertion and Communication Cable Connection
Correct phase rotation is required when attach the power cable to the breaker terminal.
Do not drop a screw or washer in the electrical unit when attaching the breaker cover and terminal. Do not leave it in the unit if dropped in. Potential failure may occur if the power is turned ON without removing it.
Cap
Power cable
Contact signal cable
Serial RS-485 communication cable
P1 (D-sub 25P female)
P2 (D-sub 9P female)
P3 (D-sub 9P male) Not used. (Only for maintenance)
Chapter 3 Transporting and Installation
5. Loosen the cap and insert the power cable from the power cable access.
6. Connect the communication cables with P1 and P2.
[Tips]
See “Table 3-1 Power Cable and Main Breaker (This System)” on page 3-7 for the recommended cable size and crimp contact.
3.3 Procedure for Installation HRW Series
Page 35
Chapter 3 Transporting and Installation
3-11
Figure 3-8 Connection of Power Cable and Grounding Terminal
Earth bar
Main breaker
Grounding terminal
Power cable
7. Connect the power cables to the breaker terminal.
Be sure to use a Phillips screwdriver. See Table 3-1 on page 3-7 for recommended torque.
8. Connect the grounding terminal (M8) of
the power cable to the earth bar.
Be sure to use a 13-mm open end wrench. Recommended torque: 12.5 N•m (9.22 ft-lbf)
HRX-OM-K003
[Tips]
See “Table 3-1 Power Cable and Main Breaker (This System)” on page 3-7 for torque value.
9. Attach the breaker cover to the breaker.
10. Attach the front panel.
11. Connect the power cable to the power breaker on customer side (primary side).
HRW Series 3.3 Procedure for Installation
Page 36
HRX-OM-K003
3-12
Pipe
Diameter
Recommended torque (Material: SS* vs SS)
Facility water inlet
Rc3/4
28 to 30Nm
(20.7 to 22.1ft-lbf)
Facility water outlet
Rc3/4
28 to 30Nm
(20.7 to 22.1ft-lbf)
Circulating fluid supply
Rc3/4
28 to 30Nm
(20.7 to 22.1ft-lbf)
Circulating fluid return
Rc3/4
28 to 30Nm
(20.7 to 22.1ft-lbf)
Tank drain port
Rc3/8 (with valve)
Piping not necessary
Drain pan port
Rc3/8
Piping not necessary
Choose proper external piping with consideration for pressure,
temperature and compatibility with the circulating fluid. Potential pipe rupture during operation may occur if disregarded.
Always insulate external circulating piping. Potential insufficient cooling
performance due to heat absorption from the pipe surface and potential insufficient heating performance caused by thermal radiation if disregarded.
Use clean pipes and pipe fittings, free of particles, oil and moisture.
Apply air blow to the parts before using. The presence of particles, oil or moisture in the circulating fluid circuit causes system failure attributed to insufficient cooling or froths in the circulating fluid in the tank.
Install circulating fluid piping not to exceed 10m high. The maximum
amount of circulating fluid in piping, including your system, should remain under 2.5L if 7m or higher circulating fluid piping is installed (for HRW-H, -HS). An alarm may be raised, or potential fluid leak from the tank may occur at system stop if disregarded.
Be sure to choose a circulating fluid pipe capable of letting the fluid flow
at rated flow rate or better. See “Pump performance” defined in
Appendix 8.1.1 System specification” for the flow rate rating.
Have a drip pan available incase of a fluid leak. Make sure of the locations of ports for the circulating fluid supply, return,
facility water inlet, outlet and their corresponding connections are correct.
Install valves in circulating fluid piping for flow rate adjustment and
maintenance. As the value of flow rate displayed on the screen will be less than proper value when flow rate is excessive, flow rate adjustment should be started with the valves shut. See “Circulating fluid flow rate display range” defined in “Appendix 8.1.1 System specification” for the flow rate display range.
Secure the piping connector section with a pipe wrench, and provide
proper tightening to the pipe.
Avoid physical shock when securing and tightening the connectors.
Potential breakage and fluid leak may occur if disregarded.
Chapter 3 Transporting and Installation
3.3.5 Installation of circulating fluid and facility water piping
Pipe diameter
3.3 Procedure for Installation HRW Series
Table 3-3 Pipe Diameter
*: SS Stainless steel
Page 37
3-13
Procedure for piping installation
No.
Name
Size
Material
1
Valve
Rc3/4
Stainless steel
2
Y-strainer (100m)
Rc3/4
Stainless steel
3
Valve
Rc3/4
Stainless steel
4
Y-strainer (5m)
Rc3/4
Stainless steel
Figure 3-10 Recommended Piping Installation
Pipe coupling section
Figure 3-9 Pipe Tightening
System on the customer side
Circulating fluid supply
Circulating fluid return
Facility water inlet
Facility water outlet
Secure the pipe coupling section with a pipe wrench, and provide proper tightening to the pipe.
Recommended piping installation
HRX-OM-K003
Chapter 3 Transporting and Installation
Table 3-4 Recommended Pipe
HRW Series 3.3 Procedure for Installation
Page 38
HRX-OM-K003
3-14
Chapter 3 Transporting and Installation
3.3 Procedure for Installation HRW Series
Page 39
HRX-OM-K003
4-1
Only personnel, who have adequate knowledge of and experiences with not only this system but associated equipment, are allowed to implement system startup and shutdown.
Check that the facility water complies with not only the water quality standard defined in section 7.1 Water Quality Managementon page 7-1 but the requirements provided in “8.1.1 System specification” in Chapter 8 Appendix on page 8-1.
Chapter 4 System Startup and Shutdown
Chapter 4 System Startup and Shutdown
4.1 Pre-check
Check the following items prior to starting up the system.
4.1.1 Installation condition
Make sure that the system is installed in a horizontal position.
No heavy object is placed on this system. This system should not be applied
with an undue force such as caused by piping installation.
Re-check the items defined in “3.2 Installation” on page 3-3.
4.1.2 Cable connection
Make sure proper connection of the power cable, ground, and communication cables.
4.1.3 Installation of circulating fluid and facility water piping
Make sure that circulating fluid and facility water piping are installed properly.
4.1.4 Operating signal from your system
Make sure that no remote signal is being issued from your system. System startup takes effect upon power-ON if this system receives a remote signal and it is in remote mode.
4.1.5 Check emergency off [EMO] switch
Make sure of the location of the emergency off [EMO] switch before operating the system. See section 1.6.1 Emergency off [EMO] switch” in Chapter 1 Safety for details.
4.2 Opening of Facility water Valve
Open the facility water valve for water supply.
HRW Series 4.1 Pre-check
Page 40
HRX-OM-K003
4-2
Rear
Circulating fluids to use vary with system models. See section 8.1.1 System specification” in Chapter 8 for the designated circulating fluid for a specific model.
High concentration EG in the circulating fluid may cause circulating pump overload,
which triggers “Pump Breaker Trip FLT”.
Potential cooling error may occur if the circulating fluid varies in concentration.
Make sure of no oil, moisture, and other foreign materials contaminate the circulating fluid. Potential cooling error or system failure, due to contaminant freezes internally, may occur if disregarded.
Attention should be taken on water quality. Ensure water quality is within specified range, and other foreign materials contaminate the circulating fluid. Potential cooling error or system failure, due to contaminant freezes internally, may occur if disregarded.
Circulating fluid fill port
Circulating fluid level gauge
Circulating fluid specified level
Chapter 4 System Startup and Shutdown
4.3 Supply of Circulating Fluid
Figure 4-1 Circulating Fluid Fill Port and Circulating Fluid Level Gauge
4.3.1 Preparation of circulating fluid
When the circulating fluid is an ethylene glycol aqueous solution
Always check the concentration of the circulating fluid. Normal concentration: 55 to 60%
When the circulating fluid is a fluorinated fluid
When the circulating fluid is water
4.3 Supply of Circulating Fluid HRW Series
Page 41
4-3
4.3.2 Supply of circulating fluid
When supplying the circulating fluid, make sure that the fluid inside this system has dropped to room temperature for the prevention of burns.
Circulating fluid must be supplied to be in the range between “HIGH”
and “LOW”. Potential overflow of hot circulating fluid may occur due
to excessive volume. Total fluid volume use to fill up the system including initial priming should not exceed combined volume of Sub Tank and Main Tank. If level is below the “LOW” mark, this system will trigger an alarm.
Be sure to tighten the cap until it clicks after circulating fluid supply. Potential circulating fluid vaporization may occur if disregarded.
Remove the circulating fluid fill cap, and fill the circulating fluid until it reaches its specified level. The circulating fluid specified level is a range between “HIGH” and “LOW” in Figure 4-1.
Be sure to tighten the cap until it clicks after fluid supply. If the circulating fluid is supplied over the specified level, follow the procedure provided in section 7.3.1 Draining of circulating fluid out of tank on page 7-4 to drain excess fluid until it reaches the specified level.
[Tips]
Level between “HIGH” and “LOW” represent liquid level in normal running
condition. Immediately as you start filling up the chiller, the internal transferring pump start pumping fluid from the Sub Tank into the Main Tank. Thus the fluid level in the level gauge will start to drop. During initial priming of the external piping, addition fluid is needed. See section 8.1.1 System specification” on page 8-1 for Sub Tank and Main Tank capacity.
HRX-OM-K003
Chapter 4 System Startup and Shutdown
HRW Series 4.3 Supply of Circulating Fluid
Page 42
HRX-OM-K003
4-4
Figure 4-2 Main Breaker at ‘ON’
Press the emergency off [EMO] switch immediately upon ocurrence of abnormal conditions. Be sure to turn OFF the main breaker afterwards.
Front
ON
Model Indication screen
Status screen 1
Chapter 4 System Startup and Shutdown
4.4 Requirement for System Startup
4.4.1 Turning ON power
1. Make sure that the main breaker for this system is OFF, and release lockout/tagout of the
power breaker on customer side (primary side). Then, turn ON the power.
2. Turn ON the main breaker of this system.
The “Model Indication screen” are displayed in sequence on the LCD screen. The screen will change to the “Status screen 1” in approx. 20 seconds, and the system is ready to run.
4.4 Requirement for System Startup HRW Series
Page 43
Chapter 4 System Startup and Shutdown
4-5
Internal equipment may remain at elevated in temperature immediately after system shutdown. Potential burns may happen if your skin comes in contact with these surfaces. Further work is allowed only when the system reaches room temperature.
Emergency off [EMO] switch and main breaker (OFF) should not be used for system shutdown unless it is an emergency.
4.4.2 Circulating fluid temperature setting
From the “Setting screen” on the LCD screen, set the circulating fluid at any temperature. See section 5.4 Examples of System Operation” in “Chapter 5 System Operationon page 5-11 for operating procedure.
[Tips]
See section 8.1.1 System specification” in “Chapter 8 Appendix” on page 8-1 for the setting range of circulating fluid temperature.
4.5 System Startup and Shutdown
4.5.1 System startup
Press the [START/STOP] key on the operation display panel.
The RUN lamp on the operation display panel comes on, and system operation is initiated
4.5.2 System shutdown
Press the [START/STOP] key on the operation display panel.
HRX-OM-K003
RUN lamp on the operation display panel goes out, and the system comes to a halt accordingly.
HRW Series 4.5 System Startup and Shutdown
Page 44
HRX-OM-K003
4-6
Chapter 4 System Startup and Shutdown
4.5 System Startup and Shutdown HRW Series
Page 45
5-1
Chapter 5 System Operation
Be sure to use your fingers only to operate the Operation Display Panel. Using sharp object will damage the panel.
Operation Display Panel
[RESET] key
Used to stop an alarm buzzer and initialize the alarm.
“REMOTE” lamp This comes on when the system is in remote mode.
“RUN” lamp This comes on when the equipment is running.
[START/STOP] key Used to start and stop the operation.
[SEL] key Used to select the screen.
[ENT] key Used to determine a set value.
[][] key Used to move the cursor and change set values.
“LCD screen”
“ALARM” lamp
This comes on when an alarm is raised.
[ ]key Used to move the cursor when setting data.
5.1 Operation Display Panel
Use the operation display panel located in front of the system for the basic operations.
HRX-OM-K003
Chapter 5 System Operation
Figure 5-1 Operation Display Panel
HRW Series 5.1 Operation Display Panel
Page 46
HRX-OM-K003
5-2
Screen
Descriptions
Reference
Model Indication screen
Displays the model and revision No. of this system.
Page 5-3
Status screen 1, 2, 3, 4
Displays the operating condition of this system.
Page 5-3 Page 5-5
Menu screen 1, 2
Allows setting screen selection.
Page 5-5
Setting screen
Allows the setting of TEMP SP value.
Page 5-6
Mode Selection screen
Allows communication mode selelction.
Page 5-6
Initial Setting screen 1, 2, 3, 4, 5
Allows the setting of set values.
Page 5-7
Maintenance screen 1, 2
Not used during system operation. Not allowed to use unless otherwise specified.
Page 5-9
Option screen
Allows the setting of option.
Page 5-9
Alarm Display screen
The alarm message is displayed in the event of an error in this system. Not displayed if no error.
Page 5-10
Information screen
Displayed upon system power-ON. Disables system operation when displayed.
Page 5-10
Chapter 5 System Operation
5.2 Flow Chart of Operation Screen
Figure 5-2 Flow Chart of
Operation Screen
[Tips]
With the press of the [SEL] key, the screen is switched to the “Menu screen 1” regardless of the screen status.
Table 5-1 Descriptions of Operation Screens
5.2 Flow Chart of Operation Screen HRW Series
Page 47
Chapter 5 System Operation
5-3
No.
Item
Descriptions
1
-
System model 2 -
System revision No.
No.
Item
Descriptions
1
TEMP PV
Discharge temperature of the circulating fluid (A value derived according to the offset*1 if applied)
2
FLOW PV
Flow rate of the circulating fluid
3
PRESS
Discharge pressure of the circulating fluid
4
F. TEMP PV
Facility water inlet temperature
1
2
1 2 3
4
5.3 Operation Screen
5.3.1 Model Indication screen
Figure 5-3 Model Indication Screen
The “Model Indication screen” is displayed upon power-ON of this system. This screen remains ON for approx. 20 seconds and is automatically switched to the “Status screen 1”. The “Alarm Display screen” is displayed if error occurs in this system.
Table 5-2 Model Indication Screen
HRX-OM-K003
5.3.2 Status screen 1
Figure 5-4 Status Screen 1
Table 5-3 Status Screen 1
[Tips]
See Appendix 8.4 Offset Function” in Chapter 8 on page 8-9 for details on offset (*1).
HRW Series 5.3 Operation Screen
Page 48
HRX-OM-K003
5-4
No.
Item
Descriptions
1
TEMP PV
Discharge temperature of the circulating fluid (A value derived according to the offset*1 if applied)
2
TEMP SP
Set circulating fluid temperature
3
OFFSET
Set offset
4
OFFSET
The current offset mode
No.
Item
Descriptions
1
TEMP PV
Discharge temperature of the circulating fluid
2
TEMP SP
Set circulating fluid temperature
3
<<TEMP READY>>
Displays the BAND/READY [Displayed when set value conditions are satisfied*1
4
TEMP BAND
Set value of BAND range*1
1
2
3 4 1 2 3
4
Chapter 5 System Operation
5.3.3 Status screen 2
[Tips]
See “Appendix 8.4 Offset Function” in Chapter 8 on page 8-9 on offset features (*1).
5.3.4 Status screen 3
Figure 5-5 Status Screen 2
Table 5-4 Status Screen 2
Figure 5-6 Status Screen 3
Table 5-5 Status Screen 3
[Tips]
See “Appendix 8.5 BAND/READ” in Chapter 8 on page 8-12 on offset features (*1).
5.3 Operation Screen HRW Series
Page 49
5-5
5.3.5 Status screen 4
No.
Item
Descriptions
1
FLOW PV*1
Discharge flow rate of the circulating fluid
2
FLOW SP*1
Set Discharge flow rate
No.
Item
Descriptions
1
SETTING
Swicthes to the “Setting screen” with the press of the [ENT] key.
2
REMOTE/LOCAL
Swicthes to the “Mode Selection screen” with the press of the
[ENT] key.
3
INITIAL SET
Swicthes to the “Initial Setting screen 1” with the press of the
[ENT] key.
4
MAINTENANCE
Swicthes to the “Maintenance screen 1” with the press of the
[ENT] key.
5
OPTION
Swicthes to the “Option screen” with the press of the [ENT] key.
1 2 3
4 5 1
2
HRX-OM-K003
Chapter 5 System Operation
*Status screen 4 is only indicated on HRW-HS
(pump inverter type).
Figure 5-7 Status Screen 4
Table 5-6 Status Screen 4
[Tips]
When using accessory [by-pass piping set] flow becomes total of flow on customer side and flow on by-pass (*1).
5.3.6 Menu screen
Figure 5-8 Menu Screen
Table 5-7 Menu Screen
HRW Series 5.3 Operation Screen
Page 50
HRX-OM-K003
5-6
No.
Item
Setting range
1
TEMP SP
20.0 to 90.0°C
2
FLOW SP
10 to 40LPM(2.6 to 10.6GPM) FLOW SP is only indicated on HRW-HS and Setting is available*2.
No.
Item
Setting
1
MODE LOCAL
System start/stop and TEMP SP value setting are available only from the operation display panel.
DIO REMOTE
System start/stop is allowed only through contact signal. TEMP SP value setting is available only from the operation display panel.
SER REMOTE
System start/stop and TEMP SP value setting are available only through serial RS-485 communication.
1 1 2
Chapter 5 System Operation
5.3.7 Setting screen
Figure 5-9 Setting Screen
This screen enables the setting of TEMP SP value.
Not available if the communication mode is in “SER REMOTE”
Table 5-8 Setting Screen
[Tips]
See Mode Selection screen in Chapter 5 on page 5-6 for details on “SER REMOTE” (*1).
See “Appendix 8.1.1 System specification” in Chapter 8 on page 8-1 for
setting range. (*2).
5.3.8 Mode Selection screen
*1
.
Figure 5-10 Mode Selection Screen
This screen enables the selection of the communication mode. The procedures for system start/stop and TEMP SP value setting may vary with the communication mode. Other operations and settings are available only from the operation display panel.
Table 5-9 Mode Selection Screen
5.3 Operation Screen HRW Series
Page 51
5-7
5.3.9 Initial Setting screen
1 2 3 4 5 6 7 8 9
10
11
12
13
Figure 5-11 Initial Setting Screen
HRX-OM-K003
Chapter 5 System Operation
HRW Series 5.3 Operation Screen
Page 52
HRX-OM-K003
5-8
No.
Item
Setting range
Descriptions
1
TEMP BAND
1.0 to 5.0°C *1
Allows the selection of the band width for TEMP SP.
2
READY TIME
10 to 480sec*1
Allows the setting of the time from TEMP PV value reaching BAND range to TEMP READY is displayed and put out.
3
OFFSET
-20.0 to 20.0°C *2
Calibrates variations in temperature between this system and your system. (See “Appendix 8.4 Offset Function” in Chapter 8 on page 8-9 for details.)
4
OFFSET
OFF, MODE1, MODE2, MODE3
5
HIGH TEMP
20 to 93°C
Issues an alarm of “Reservoir High Temp WRN” if the
circulating fluid exceeds the set temperature.
6
LOW FLOW
HRW002-H, H*S:
0, 2~16LPM
0, 0.54.2GPM HRW008-H, -H*S HRW015-H, -H*S HRW030-H, -H*S:
0, 8~50LPM
0, 2.113.2GPM
Issues an alarm of “Return Low Flow WRN” if the
circulating fluid does not reach the set flow rate. Lift this alarm if the selection is 0.
7
FLOW UNIT
LPM, GPM
Allows the selection of the unit of flow rate.
8
PRESS UNIT
MPa, PSI
Allows the selection of the unit of pressure.
9
SLAVE ADRS.
1 to 16CH
Allows the selection of the slave address for serial RS-485 communication.
10
OUT
N/A ALARM1 to 23
Allows the selection of alarm signals for contact signal. (See Appendix 8.1.3 Alarm signal selection on page 8-6 for details.)
11
E_OUT
TEMP READY, AUTO PURGE*1
Allows the selection of EVENTOutput. (See Appendix 8.1.2 Communication specification on page 8-4 for details.)
12
F.LOW TEMP
5 to 10°C
Issues an alarm of “F.Water Low Temp WRN” if the facility water falls below the set temperature.
13
F.HIGH TEMP
35 to 50°C
Issues an alarm of “F.Water High Temp WRN” if the circulating fluid exceeds the set temperature.
Chapter 5 System Operation
This screen enables the setting of set values.
Table 5-10 Initial Setting Screen
[Tips]
Valid during option setting with 5.3.11 Option screen on page 5-9. See Appendix 8.5 BAND/READ” in Chapter 8 on page 8-12 on BAND/READY function (*1). TEMP SP+OFFSET value (*2) should be in the TEMP SP setting range defined in “Table 5-8 Setting Screen on page 5-6.
5.3 Operation Screen HRW Series
Page 53
5-9
5.3.10 Maintenance screen
No.
Item
Setting
1
VALVE OPEN
The facility water solenoid valve is opened forcefully.
CLOSE
The facility water solenoid valve is closed forcefully.
No.
Item
Setting
1
CUSTOM DIO
ON / OFF
Allows the selection of Valid / invalid. (See “Communication specifications” for details.)
2
TEMP READY
ON / OFF
Allows the selection of valid / invalid of BAND / READY function. This becomes valid after turning off the power, then supply the power again.
1
1
2
Table 5-11 Maintenance Screen
HRX-OM-K003
Chapter 5 System Operation
Figure 5-12 Maintenance Screen
[Tips]
Available only if a solenoid value (optional) is provided.
5.3.11 Option screen
Figure 5-13 Option Screen
Table 5-12 Option Screen
HRW Series 5.3 Operation Screen
Page 54
HRX-OM-K003
5-10
No.
Item
Setting
1
Initialize Mode
Displayed upon system power-ON. Disables system operation when displayed.
1
Chapter 5 System Operation
5.3.12 Alarm Display screen
Figure 5-14 Alarm Display Screen
In the event of an error in this system, the current screen is switched to the Alarm Display screen to display the relevant alarm code. And message. The Alarm Display screen is displayed only if an error is raised. See section 6.2 Troubleshooting” in “Chapter 6 Error Message and Troubleshooting” for alarm numbers and messages.
5.3.13 Information screen
Figure 5-15 Information screen
The above “Information screen” may be displayed in response to system startup and shutdown.
Table 5-13 Information screen
5.3 Operation Screen HRW Series
Page 55
HRX-OM-K003
5-11
Chapter 5 System Operation
5.4 Examples of System Operation
5.4.1 Example 1: Circulating fluid set temperature is changed from
25.0°C to 34.1°C.
Figure 5-16 Change of Set Temperature from 25.0°C to 34.1°C
1. Press the [SEL] key to display the “Menu
screen 1”.
2. With the use of the arrow keys ([], []),
move the cursor to “1. SETTING” and press the [ENT] key.
The “Setting screen” is displayed.
3. Press the [ENT] key.
Figure 5-17 Menu Screen 1
Figure 5-18 Setting Screen
The cursor is now appear on the current value for TEMP SP, which enables change of the temperature set value.
Figure 5-19 Setting Screen: Cursor Display
HRW Series 5.4 Examples of System Operation
Page 56
HRX-OM-K003
5-12
Figure 5-20 Setting Screen: Change of Set Value
Chapter 5 System Operation
4. Use the arrow keys ([], [], [ ]) to
change the temperature to 34.1°C.
[] key: Used to add one value on which the cursor is placed. [] key: Used to subtract one value on which the cursor is
placed. [ ] key: Used to move the cursor to the right.
[Tips]
To cancel a selection, press the [SEL] key, not [ENT] key. With the press of the [SEL] key, the cancellation takes effect and the screen is switched to the “Menu screen 1”.
5. Press the [ENT] key with a new set
temperature (34.1°C) entered.
The cursor goes out, and the setting takes effect.
Figure 5-21 Setting Screen: Setting Confirmation
6. Press the [SEL] key to display the “Menu screen 1”.
5.4 Examples of System Operation HRW Series
Page 57
HRX-OM-K003
5-13
Chapter 5 System Operation
5.4.2 Example 2: Communication mode is switched from “DIO REMOTE” to “LOCAL”.
Figure 5-22 Switching of Communication Mode from “DIO REMOTE” to “LOCAL”
1. Press the [SEL] key to display the “Menu
screen 1”.
2. With the use of the arrow keys ([], []),
move the cursor to “2. REMOTE/LOCAL”
and press the [ENT] key.
The “Mode Selection screen” is displayed.
The name of the current mode flashes.
3. Use the arrow keys ([], []) to select
“LOCAL”.
Figure 5-23 Menu Screen 1
Figure 5-24 Mode Selection Screen: DIO REMOTE
Figure 5-25 Mode Selection Screen: LOCAL
4. Press the [ENT] key.
The mode name stop flashing, and the selection takes effect.
Figure 5-26 Mode Selection Screen: Setting Confirmation
[Tips]
To cancel a selection, press the [SEL] key, not [ENT] key. With the press of the [SEL] key, the cancellation takes effect and the screen is switched to the “Menu screen 1”.
5. Press the [SEL] key to display the “Menu screen 1”.
HRW Series 5.4 Examples of System Operation
Page 58
HRX-OM-K003
5-14
Chapter 5 System Operation
5.4.3 Example 3: Alarm signal of contact signal is changed from “N/A” to “ALARM1”.
Figure 5-27 Change of Alarm Signal of Contact signal from “N/A” to “ALARM1”
1. Press the [SEL] key to display the “Menu
screen 1”.
2. With the use of the arrow keys ([], []),
move the cursor to “3. INITIAL SET” and
press the [ENT] key.
The “Initial Setting screen 1” is displayed.
3. Use the arrow keys ([], []) to display
the “Initial Setting screen 3”, which
prompts “OUT” to flash.
Figure 5-28 Menu Screen 1
Figure 5-29 Initial Setting Screen 1
The name of the current mode flashes.
Figure 5-30 Initial Setting Screen 3: OUT
4. Press the [ENT] key.
Only the current mode flashes.
Figure 5-31 Initial Setting Screen 3: N/A
5.4 Examples of System Operation HRW Series
Page 59
5-15
5. Use the arrow keys ([], []) to select
“ALARM1”.
6. Press the [ENT] key.
“OUT” flashes again, and the selection takes
effect.
[Tips]
To cancel a selection, press the [SEL] key, not [ENT] key. With the press of the [SEL] key, the cancellation takes effect and the screen is switched to the “Menu screen 1”.
HRX-OM-K003
Chapter 5 System Operation
Figure 5-32 Initial Setting Screen 3: ALARM1
Figure 5-33 Initial Setting Screen 3:
Setting Confirmation (OUT)
7. Press the [SEL] key to display the “Menu screen 1”.
HRW Series 5.4 Examples of System Operation
Page 60
HRX-OM-K003
5-16
Chapter 5 System Operation
5.4 Examples of System Operation HRW Series
Page 61
Chapter 6 Error Message and Troubleshooting
6-1
LCD screen
“ALARM” lamp is
ON.
Alarm Display screen (Alarm No. and alarm message)
Front
Chapter 6 Error Message and
Troubleshooting
6.1 Error Message
The following are to be performed in the event of an error in this system.
The “ALARM” lamp comes on.
Alarm buzzer comes on.
The “Alarm Display screen” is displayed on the LCD screen.
Error signal is issued through external communication.
(See section 8.1.2 Communication specification” in Chapter 8 on page 8-4 Appendix for details.)
This system is brought to a stop forcefully according to error types.
HRX-OM-K003
HRW Series 6.1 Error Message
Figure 6-1 Error Occurrence
Page 62
HRX-OM-K003
6-2
Code
Error message
System
condition
Cause
Remedies
01
Water Leak Detect FLT
Stop
The fluid is pooled at the base of this system.
Check for fluid leak.
02
Incorrect Phase Error FLT
Stop
The power phase rotation is wrong.
Check that a proper connection is established between the power cable and main breaker of this system.
05
Reservoir Low Level FLT
Stop
An insufficient amount of the circulating fluid is observed in the tank.
Replenish the circulating fluid.
06
Reservoir Low Level WRN
Continued
An insufficient amount of the circulating fluid is observed in the tank.
Replenish the circulating fluid.
07
Reservoir High Level WRN
Continued
An excessive amount of the circulating fluid is observed in the tank.
Drain the circulating fluid.
08
Temp. Fuse Cutout FLT
Stop
The circulating fluid tank was
raised in temperature.
Check the load specification. Replacement of the thermal fuse is required. Call the supplier for service.
09
Reservoir High Temp. FLT
Stop
The temperature of the circulating fluid exceeded the specified value.
Check the load specification.
10
Return High Temp. WRN
Continued
The temperature of the circulating fluid exceeded the specified value.
Check the circulating fluid flow rate and load specification.
11
Reservoir High Temp. WRN
Continued
The temperature of the circulating fluid exceeded your specified value.
Reset the setting temperature.
Chapter 6 Error Message and Troubleshooting
6.2 Troubleshooting
The procedure for error recovery varies with alarm types.
Alarm Code.01 to 08, 10 to 19, 22, 24, 29, 30:
Eliminate the error cause. Press the [RESET] key on the operation display panel or power cycle the main breaker to enable error recovery to take effect.
Alarm Code.09:
Eliminate the error cause. After replacing thermal fuse, press the [RESET] key on the operation display panel or power cycle the main breaker to enable error recovery to take effect.
Alarm Code.21:
Eliminate the error cause, and power cycle the main breaker to enable error recovery to take effect.
Alarm Code.23, 26, 27:
Automatic error recovery is implemented upon elimination of the error.
Alarm Code.18, 24, 26, 27:
This is an alarm for accessories (optional). No alarm of this type is issued if the system is outfitted with no accessories.
Alarm Code.25:
This alarm is only for HRW-HS (pump inverter type).
Table 6-1 Troubleshooting (1/2)
6.2 Troubleshooting HRW Series
Page 63
Chapter 6 Error Message and Troubleshooting
6-3
Code
Error message
System
condition
Cause
Remedies
12
Return Low Flow FLT
Stop
The flow rate of the circulating fluid falls short of the specified value.
Check that the external valve is opened.
Prepare a thicker external pipe or install bypass piping.
13
Return Low Flow WRN
Continued
The flow rate in this system falls short of your specified value.
Reset the setting flow rate.
15
Pump Breaker Trip FLT
Stop
The breaker for the circulating pump power line was tripped.
Check that the power supply to this system is compliant with the specification.
17
Interlock Fuse Cutout FLT
Stop
An overcurrent was passed through the control circuit.
Contact the system supplier for request of inspection and repair.
18
DC Power Fuse Cutout WRN
Continued
An overcurrent was passed through the solenoid valve (optional).
Contact the system supplier for request of inspection and repair.
19
FAN Motor Stop WRN
Continued
The ventilating fan came to a stop.
Check that the air vent on the back of the system is not blocked off.
21
Controller Error FLT
Stop
An error was detected in the control system.
Contact the system supplier for request of inspection and repair.
22
Memory Data Error FLT
Stop
An error was detected in data stored in the controller of this system.
Reset your specified value.
23
Communication Error WRN
Continued
An interruption of serial communication occurred between this system and your system.
Check that a signal is being issued from your system.
Check for disconnection of the communication connector from this system.
24
DI Low Level WRN
Continued
Electrical resistivity of the circulating fluid falls short of your specified value.
Lower the setting for resistivity.
Replacement of the DI filter is required.
25
Pump Inverter Error FLT
Stop
An error was detected in the system inverter.
Contact the system supplier for request of inspection and repair.
26
DNET Comm, Error FLT
Stop
An error was detected in the DeviceNet communication system.
Contact the system supplier for request of inspection and repair.
27
DNET Comm. Error WRN
Continued
DeviceNet communication was disconnected between this system and customers system.
Check that a signal is being issued from your system.
Check for disconnection of the communication connector from this system.
29
F.Water Low Temp. WRN
Continued
The temperature of facility water falled below your specified value.
Reset the setting temperature.
30
F.Water High Temp. WRN
Continued
The temperature of facility water exceeded your specified value.
Reset the setting temperature.
Table 6-1 Troubleshooting (2/2)
HRX-OM-K003
HRW Series 6.2 Troubleshooting
Page 64
HRX-OM-K003
6-4
Chapter 6 Error Message and Troubleshooting
6.2 Troubleshooting HRW Series
Page 65
Chapter 7 System Maintenance
7-1
Substance
Facility water
spec.
Circulating water
spec.
Standards
Ph (25°C)
6.5 to 8.2
6.0 to 8.0
Electrical conductivity (25°C) (µs/cm) *
100 to 800
0.5 to 300
Chloride ion (mgCl-/L)
Max. 200
Max. 50
Sulfate ion (mgSO
4
2-
/L)
Max.200
Max.50
Acid consumption (Ph4.8) (mgCaCO3/L)
Max.100
Max.50
Total hardness (mgCaCO3/L)
Max.200
Max.70
Calcium hardness (mgCaCO3/L)
Max.150
Max.50
Ionic silica (mgSiO2/L)
Max.50
Max.30
Iron (mgFe/L)
Max.1.0
Max.0.3
Copper (mgCu/L)
Max.0.3
Max.0.1
Sulfide ion (mgS2-/L)
Not be detected
Ammonium ion (mgNH
4
+
/L)
Max.1.0
Max.0.1
Residual chlorine (mgCl/L)
Max.0.3
Max.0.3
Free carbon dioxide (mgCO2/L)
Max.4.0
Max.4.0
Filtration (µm)
Max.5
If the periodic inspection finds a nonconforming substance in the facility water, clean the facility water circuit and recheck the quality of the facility water.
Only designated circulating fluid is permitted to use for this system.
Potential system failure and fluid leak may occur if disregarded, which results in electric shock, ground fault, and freeze. Be sure to use fresh water (tap water) compliant with water quality standards in the table below for ethylene glycol aqueous solution and facility water.
Keep bubbles out of the facility water circuit.
Potential large variations in temperature of the circulating fluid may occur if bubbles are present in the facility water.
Chapter 7 System Maintenance
7.1 Water Quality Management
Table 7-1 Water Quality Standards for Fresh Water (Tap Water)
HRX-OM-K003
According to the Water quality guideline for refrigeration air-conditioning
equipment: JRA-GL-02-1994
HRW Series 7.1 Water Quality Management
Page 66
HRX-OM-K003
7-2
Inspection item
Inspection method
Installation condition
Check of the condition of system installation
No heavy object is placed on this system. This system should not be subjected to external force.
Temperature and humidity fall within the specified range.
Fluid leak
Check of the piping connector section
No leak of facility water and circulating fluid from the piping connector section
Fluid level
Reading of the level of the circulating fluid
Level falls within the circulating fluid specified level between “High” and “Low”.
Operation display panel
Display check
Clarity of letters and numbers on the LCD display should be assured.
Function check
[RUN] lamp is ON.
Circulating fluid temperature
Confirm the reading on the LCD screen
Temperature should be within setpoint.
Discharge pressure of circulating fluid
Confirm the reading on the LCD screen
Reading should not have deviated much from last inspection.
Circulating fluid flow rate
Confirm the reading on the LCD screen
Reading should not have deviated much from last inspection.
Operating condition
Operating condition check
No abnormal noise, vibration, odor and smoke
Facility water
Check of the facility water
Temperature, flow rate and pressure fall within the specified range.
Circulating fluid supply port cap
Check by providing manual tightening
No looseness
Do not touch any electrical parts with wet hands.
Keep wet hands away from electrical parts. Potential electric shock can occur if disregarded.
Keep this system from water. Potential electric shock or fire can occur if
disregarded.
If the inspection and cleaning require the removal of the panel, be sure to re-attach the panel upon completion. Potential personal injury or electric shock may occur if operated with the panel opened or removed.
Chapter 7 System Maintenance
7.2 Inspection and Cleaning
7.2.1 Daily inspection
Table 7-2 Daily Inspection
7.2 Inspection and Cleaning HRW Series
Page 67
7-3
7.2.2 Quarterly inspection
Inspection item
Inspection method
Circulating fluid Circulating fluid is to be drained for check.
Fluid should be free of particles, moisture and foreign substances.
For ethylene glycol solution, confirm that the concentration falls within the specified range.
Recommended to replace the water.
Facility water
Facility water quality should fall within the standards specified.
Ventilation hole and electrical parts
No particles and dust should be present.
Quarterly inspection requires an advance lockout/tagout of this system. See section 1.5.3 Lockout/Tagout” in “Chapter 1 Safetyon page 1-10 for details.
Table 7-3 Quarterly Inspection
HRX-OM-K003
Chapter 7 System Maintenance
7.3 Storage
The following should be performed for system long-term storage.
1. Drain the circulating fluid. See section 7.3.1 Draining of circulating fluid out of tankon page 7-4 for
details.
2. Drain the facility water. See section 7.3.2 Draining of facility wateron page 7-5 for details.
3. Cover the system with a plastic sheet for storage.
HRW Series 7.3 Storage
Page 68
HRX-OM-K003
7-4
Figure 7-1 Container for Circulating Fluid Recovery
Use the clean container for circulating fluid recovery. Reuse of the
recovered circulating fluid with contaminated will cause insufficient cooling and system failure
Be sure to wait until the circulating fluid obtains room temperature for its
draining. Potential burns can occur if disregarded.
If the recovered circulating fluid is contaminated by foreign substances, completely remove them. Do not reuse comtaminated fluid. Potential insufficient cooling, system failure and froth in the circulating fluid may occur if disregarded.
Recovered circulating fluid must be sealed in a container to prevent contamination from moisture or foreign substances. Stored in a cool, dark place. Keep it from flame.
Drain port
Container for circulating fluid recovery
Circulating fluid fill port cap
Circulating fluid supply
15cm or less
Rear
Chapter 7 System Maintenance
7.3.1 Draining of circulating fluid out of tank
1. Prepare the container for circulating fluid recovery at the back of this system.
2. Connect the drain hoses to the tank
drain port. Insert the tip of the hose into the container.
Prepare a drain hose (Rc3/8-diameter) on your
responsibility.
3. Remove the cap of the circulating fluid fill port.
4. Open the valves of the tank drain port to drain the circulating fluid.
5. Apply air purge from the the circulating fluid return to push the circulating fluid remaining in
the heat exchange back in the tank and drain it.
7.3 Storage HRW Series
Page 69
Chapter 7 System Maintenance
7-5
Figure 7-2 Plug Attachment
Figure 7-3 Drain Pan Attachment
Be sure to drain the facility water only when it is at room temperature. Trapped fluid inside the system can still be hot. Potential burns can occur if disregarded.
Plug
Circulating fluid return
Facility water
inlet
Circulating fluid supply
Plug
Rear
Drain pan port
Plug
Facility
water outlet
Tank drain port
Rear
Drain pan
Facility water inlet
Facility water outlet
15cm or less
6. Upon completion of fluid draining, close the valve of the tank drain port.
7. Add plugs to seal off ports on the rear of
this system.
See section 7.3.2 Draining of facility water
on pege 7-5 for plug attachment.
HRX-OM-K003
7.3.2 Draining of facility water
1. Place the drain pan underneath the
piping connections on the rear of this system.
A 3L-capacity or bigger drain pan is required.
HRW Series 7.3 Storage
Page 70
HRX-OM-K003
7-6
Part
Recommended replacement cycle*1
Circulating pump
Every 3 yrs
Ventilating fan
Every 3 yrs
Solenoid valve assy for
facility water
Every 2 yrs
Inverter Coolong Fan*2
Every 3 yrs
Chapter 7 System Maintenance
2. Remove facility water piping.
Remove the joints such as unions if present.
3. Drain the facility water using the facility water outlet port.
7.4 Periodic Replacement Parts
Replacement of consumables listed in the following table is recommended. Contact the system supplier for request of part replacement.
Table 7-4 Periodic Replacement Part List
*1 Note: A replacement cycle may vary with your usage condition. *2 Note: Only HRW-HS is needed.
7.4 Periodic Replacement Parts HRW Series
Page 71
8-1
Chapter 8 Appendix
Model
HRW002-H
HRW002-HS
HRW008-H
HRW008-HS
HRW015-H
HRW015-HS
HRW030-H
HRW030-HS
Cooling method
Water cooling
Cooling capacity (50Hz/60Hz)
* Under conditions below
kW 2 8
15
29
Circulating fluid temp.
°C
Facility water temp. +15°C
Circulating fluid rated flow rate
L/min
4
(1.1 [gal]/min)
30
(7.9 [gal]/min)
40
(10.6 [gal]/min)
40
(10.6 [gal]/min)
Facility water minimum necessary flow rate
L/min
10
(2.6 [gal]/min)
20
(5.3 [gal]/min)
25
(6.6 [gal]/min)
40
(10.6 [gal]/min)
Operating temperature range
°C
20 to 90
Temperature stability *1
°C
± 0.3
Circulating fluid *2
Galden® HT200 or FluorinertTM FC-40
Pump capacity (50Hz/60Hz) *3
MPa
0.40 / 0.60
(At 4L/min)
(58 / 87 [PSIG]
At 1.1 [gal/min])
0.45 / 0.65
(At 30L/min)
(65 / 94 [PSIG]
At 7.9 [gal/min])
0.40 / 0.60
(At 40L/min)
(58 / 87 [PSIG]
At10.6 [gal/min])
0.40 / 0.60
(At 40L/min)
(58 / 87 [PSIG]
At10.6 [gal/min])
Circulating fluid flow rate display range
L/min
2 to 16
(0.5 to 4.2
[gal/min])
8 to 50
(2.1 to 13.2 gal/min)
Operating range of circulating fluid flow rate *4
[L/min]
3 to 16 (0.8 to
4.2[gal/min])
9 to 50
(2.4 to 13.2[gal/min])
Tank capacity *5
L
Approx. 13
(3.4 [gal])
Approx. 14 (3.7 [gal])
Tank space capacity
L
Approx. 2.5 (0.7 [gal])
Circulating fluid port
Rc 3/4
Facility water Facility water IN temp.
°C
10 to 35
Facility water IN pressure
MPa
0.3 to 0.7 (45 to 100 [PSIG])
Facility water port
Rc 3/4
Power supply
3-phase 50/60Hz AC200/200 to 208V±10%
Main breaker size
A
30
Main breaker amperes interrupting capacity
kA
50
Dimensions *6
mm
W380D665H860 (W14.96xD26.18xH33.86 [inch])
Weight (HRW-H / HRW-HS)
*7
kg
Approx. 90 (198 [lbs]) / Approx. 95 (209 [lbs])
Approx. 100 (221 [lbs]) / Approx. 105 (232 [lbs])
Communication
Serial RS-485 (Dsub-9pin), Contact signal (Dsub-25pin)
8.1 Specification
8.1.1 System specification
Specification for fluorinated fluid
Table 8-1 Specification for fluorinated fluid
HRX-OM-K003
Chapter 8 Appendix
*1: It indicates discharge temperature when connecting outlet and return of circulating fluid directly, flow rate of both
circulating fluid and facility water are rated value, installation condition, power supply and facility water are within each specifications and stable. Stability is a value after heat load is steady for 10 minutes. There are some cases
that the stability is out of +/- 0.3 deg C due to operating condition. *2: Galden® is a registered trademark of Solvay Solexis, and Fluorinert TM is a trademark of U.S. 3M. *3: The capacity is derived at the Outlet of this system when the circulating fluid is at 20°C.
Pumping capacity under 60Hz is the maximum capacity for HRW-HS (pump inverter type). *4: Applicable for HRW-HS (pump inverter type) only. According to piping specification on customer’s side, there is
the case this system cannot control the flow rate at setting value. *5: This is a minimum amount of the fluid for operation of a discrete chiller outfitted with chiller internal piping and heat
exchanger. Circulating fluid temp.: 20°C *6: This is the dimensions of panels, which is derived without protrusions such as a breaker handle. *7: This is the mass of the system when it contains no circulating fluid.
HRW Series 8.1 Specification
Page 72
HRX-OM-K003
8-2
Model
HRW002-H1
HRW002-H1S
HRW008-H1
HRW008-H1S
HRW015-H1
HRW015-H1S
HRW030-H1
HRW030-H1S
Cooling method
Water cooling
Cooling capacity (50Hz/60Hz)
* Under conditions below
kW 2 8
15
27
Circulating fluid temp.
°C
Facility water temp. +15°C
Circulating fluid rated flow rate
L/min
4
(1.1 [gal]/min)
15
(4.0 [gal]/min)
30
(7.9 [gal]/min)
40
(10.6 [gal]/min)
Facility water minimum necessary flow rate
L/min
10
(2.6 [gal]/min)
15
(4.0 [gal]/min)
25
(6.6 [gal]/min)
40
(10.6 [gal]/min)
Operating temperature range
°C
20 to 90
Temperature stability *1
°C
± 0.3
Circulating fluid
*2
Ethylene glycol solution60%
Pump capacity (50Hz/60Hz) *3
MPa
0.35 / 0.55
(At 4L/min)
(51 / 80 [PSIG]
At 1.1 [gal/min])
0.45 / 0.65
(At 15L/min)
(65 / 94 [PSIG]
At 4.0 [gal/min])
0.40 / 0.60
(At 30L/min)
(58 / 87 [PSIG]
At 7.9 [gal/min])
0.35 / 0.55
(At 40L/min)
(51 / 80 [PSIG]
At10.6 [gal/min])
Circulating fluid flow rate display range
L/min
2 to 16
(0.5 to 4.2
[gal/min])
8 to 50
(2.1 to 13.2 [gal/min])
Operating range of circulating fluid flow rate *4
[L/min]
3 to 16 (0.8 to
4.2[gal/min])
9 to 50
(2.4 to 13.2[gal/min])
Tank capacity *5
L
Approx. 13 (3.4 [gal])
Tank space capacity L Approx. 2.5 (0.7 [gal])
Circulating fluid port
Rc 3/4
Facility water Facility water IN temp.
°C
10 to 35
Facility water IN pressure
MPa
0.3 to 0.7 (45 to 100 [PSIG])
Facility water port
Rc 3/4
Power supply
3-phase 50/60Hz AC200/200 to 208V±10%
Main breaker size
A
30
Main breaker amperes interrupting capacity
kA
50
Dimensions *6
mm
W380D665H860 (W14.96xD26.18xH33.86 [inch])
Weight (HRW-H1 / HRW*H1S)
*7
kg
Approx. 90 (198 [lbs]) / Approx. 95 (209 [lbs])
Communication
Serial RS-485 (Dsub-9pin), Contact signal (Dsub-25pin)
Chapter 8 Appendix
Specification for ethylene glycol aqueous solution
Table 8-2 Specification for ethylene glycol aqueous solution
*1: It indicates discharge temperature when connecting outlet and return of circulating fluid directly, flow rate of both
circulating fluid and facility water are rated value, installation condition, power supply and facility water are within each specifications and stable. Stability is a value after heat load (no load only for HRW030-H1) is steady for 10 minutes. There are some cases that the stability is out of +/- 0.3 deg C due to operating condition.
*2: Pure ethylene glycol needs dilution with fresh water before use.
Ethylene glycol with additives such as preservatives is NOT available.
*3: The capacity is derived at the Outlet of this system when the circulating fluid is at 20°C.
Pumping capacity under 60Hz is the maximum capacity for HRW-H1S (pump inverter type).
*4: Applicable for HRW-H1S (pump inverter type) only. According to piping specification on customer’s side, there
is the case this system cannot control the flow rate at setting value.
*5: This is a minimum amount of the fluid for operation of a discrete chiller outfitted with chiller internal piping and heat
exchanger. Circulating fluid temp.: 20°C *6: This is the dimensions of panels, which is derived without protrusions such as a breaker handle. *7: This is the mass of the system when it contains no circulating fluid.
8.1 Specification HRW Series
Page 73
8-3
Specification for flesh water and DI water
Model
HRW002-H2
HRW002-H2S
HRW008-H2
HRW008-H2S
HRW015-H2
HRW015-H2S
HRW030-H2
HRW030-H2S
Cooling method
Water cooling
Cooling capacity (50Hz/60Hz)
* Under conditions below
kW 2 8
15
30
Circulating fluid temp.
°C
Facility water temp. +15°C
Circulating fluid rated flow rate
L/min
4
(1.1 [gal]/min)
15
(4.0 [gal]/min)
30
(7.9 [gal]/min)
40
(10.6 [gal]/min)
Facility water minimum necessary flow rate
L/min
10
(2.6 [gal]/min)
15
(4.0 [gal]/min)
25
(6.6 [gal]/min)
40
(10.6 [gal]/min)
Operating temperature range
°C
20 to 90
Temperature stability *1
°C
± 0.3
Circulating fluid *2
Flesh water, DI water
Pump capacity (50Hz/60Hz) *3
MPa
0.35 / 0.55
(At 4L/min)
(51 / 80 [PSIG]
At 1.1 [gal/min])
0.45 / 0.65
(At 15L/min)
(65 / 94 [PSIG]
At 4.0 [gal/min])
0.40 / 0.60
(At 30L/min)
(58 / 87 [PSIG]
At 7.9 [gal/min])
0.35 / 0.55
(At 40L/min)
(51 / 80 [PSIG]
At10.6 [gal/min])
Circulating fluid flow rate display range
L/min
2 to 16
(0.5 to 4.2
[gal/min])
8 to 50
(2.1 to 13.2 [gal/min])
Operating range of circulating fluid flow rate *4
[L/min]
3 to 16 (0.8 to
4.2[gal/min])
9 to 50
(2.4 to 13.2[gal/min])
Tank capacity *5
L
Approx. 13 (3.4 [gal])
Tank space capacity L Approx. 2.5 (0.7 [gal])
Circulating fluid port
Rc 3/4
Facility water Facility water IN temp.
°C
10 to 35
Facility water IN pressure
MPa
0.3 to 0.7 (45 to 100 [PSIG])
Facility water port
Rc 3/4
Power supply
3-phase 50/60Hz AC200/200 to 208V±10%
Main breaker size
A
30
Main breaker amperes interrupting capacity
kA
50
Dimensions *6
mm
W380D665H860 (W14.96xD26.18xH33.86 [inch])
Weight (HRW-H2 / HRW*H2S)
*7
kg
Approx. 90 (198 [lbs]) / Approx. 95 (209 [lbs])
Communication
Serial RS-485 (Dsub-9pin), Contact signal (Dsub-25pin)
Table 8-3 Specification for flesh water and DI water
HRX-OM-K003
Chapter 8 Appendix
*1: It indicates discharge temperature when connecting outlet and return of circulating fluid directly, flow rate of both
circulating fluid and facility water are rated value, installation condition, power supply and facility water are within each specifications and stable. Stability is a value after heat load (no load only for HRW030-H1) is steady for 10 minutes. There are some cases that the stability is out of +/- 0.3 deg C due to operating condition.
*2: Only a circulating fluid, which is compliant with water quality standard stipulated by The Japan Refrigeration and Air
Conditioning Industry Association (JRA GL-02-1994/cooling water – circulation – make-up water), must be used. The lower limit of the electric conductivity if improper deionized water is used: 0.5µS/cm (the upper limit of the electric resistivity: 20MΩ•cm)
*3: The capacity is derived at the thermo chiller outlet when the circulating fluid is at 20°C.
Pumping capacity under 60Hz is the maximum capacity for HRW-H2S (pump inverter type).
*4: Applicable for HRW-H2S (pump inverter type) only. According to piping specification on customer’s side, there
is the case this system cannot control the flow rate at setting value.
*5: This is a minimum amount of the fluid for operation of a discrete chiller outfitted with chiller internal piping and heat
exchanger. Circulating fluid temp.: 20°C *6: This is the dimensions of panels, which is derived without protrusions such as a breaker handle. *7: This is the mass of the system when it contains no circulating fluid.
HRW Series 8.1 Specification
Page 74
HRX-OM-K003
8-4
Item
Specification
Connector No.
P1
Connector type (this system)
D-sub25P female connector
Input signal
Insulation type
Photocoupler
Rated input voltage
DC24V
Used voltage range
DC 21.6V to 26.4V
Rated input current
5mA TYP
Input impedance
4.7k
Output signal
Rated load voltage
Max.AC48V / Max.DC30V
Max. load current
When using power source output from chiller
:DC 200mA (resistance load, inductive load)
When using power source of your system
:AC / DC 800mA (resistance load, inductive load)
Alarm signal
Rated load voltage
Max. AC48V/ Max. DC30V
Max. load current
AC/DC 800mA (resistance load, inductive load)
EMO signal
Rated load voltage
Max. AC48V/ Max. DC30V
Max. load current
AC/DC 800mA (resistance load, inductive load)
Circuit block diagram
Run/Stop signal
Run signal
14
1
DC24V output
24COM output
3
13
25
18
5
20
7
19
6
Contact output COM
EMO signal
16
4
17
8
Warning signal
Fault signal
Remote signal
Temp Ready signal
Run/Stop signal 1
Output signal 1
Alarm signal
EMO signal
DIO REMOTE
signal 1
Run/Stop signal 2
DIO REMOTE
signal 2
Output signal 2
Output signal 3
Output signal 4
Output signal 5
Factory-shipped
configuration
Customized function
Thermo Chiller
DIGITAL
circuit
DC24V
4.7kΩ
4.7kΩ
4.7kΩ
4.7kΩ
24COM
24COM
Pin No.
Your system
15
Alarm signal
Contact output COM
Input signal
Output signal
Emergency off
[EMO] SW
Chapter 8 Appendix
8.1.2 Communication specification
This section provides the general outline of communications utilized in this system.
For detail specification, we provide a separate system manual “Communication
Specification”, which is available through your local distributor.
Contact signal
Table 8-4 Contact Signal
8.1 Specification HRW Series
Page 75
8-5
Serial RS-485
Item
Specification
Connector No.
P2
Connector type (this system)
D-sub9P female connector
Standard
EIA RS485
Protocol
Modicon Modbus
Circuit block diagram
Internal
circuit
This system Your system
5
SD+
SD-
SG
7
2
HRX-OM-K003
Chapter 8 Appendix
Table 8-5 Serial RS-485
HRW Series 8.1 Specification
Page 76
HRX-OM-K003
8-6
Setting
Alarm
Alarm
N/A
Alarm signal remains ON (closed) under normal circumstances.
-
Alarm1
Water Leak Detect FLT
01
Alarm2
Incorrect Phase Error FLT
02
Alarm5
Reservoir Low Level FLT
05
Alarm6
Reservoir Low Level WRN
06
Alarm7
Reservoir High Level WRN
07
Alarm8
Temp. Fuse Cutout FLT
08
Alarm9
Reservoir High Temp. FLT
09
Alarm10
Return High Temp WRN
10
Alarm11
Reservoir High Temp. WRN
11
Alarm12
Return Low Flow FLT
12
Alarm13
Return Low Flow WRN
13
Alarm14
Heater Breaker Trip FLT
14
Alarm15
Pump Breaker Trip FLT
15
Alarm17
Interlock Fuse Cutout FLT
17
Alarm18*1
DC Power Fuse Cutout WRN
18
Alarm19
FAN Motor Stop WRN
19
Alarm21
Controller Error FLT
21
Alarm22
Memory Data Error FLT
22
Alarm23
Communication Error WRN
23
Alarm24*1
DI Low Level WRN
24
Alarm25*2
Pump Inverter Error FLT
25
Alarm26*1
DNET Comm. Error FLT
26
Alarm27*1
DNET Comm. Error WRN
27
Alarm29
F.Water Low Temp. WRN
29
Alarm30
F.Water High Temp. WRN
30
Chapter 8 Appendix
8.1.3 Alarm signal selection
User can designate one alarm signal for contact signal. See section 5.3.9 Initial Setting screen” for signal selecting. The following table presents the setting-alarm relationship. The alarm signal is turned OFF if the designated alarm detected. (Alarm signal is ON if no alarm is detected.)
Table 8-6 Alarm signal selection
Example With parameter “OUT” on the Initial Setting screen set to “Alarm1”, alarm “Water Leak Detect FLT” is detected, the alarm contact signal is switched to OFF (open).
*1: Alarm 18, 24, 26 and 27 are alarms indicating accessories (optional).
*2: Alarms 25 is only for HRW-HS (pump inverter type). As other model is assigned with no alarm,
the alarm signal always remains ON (closed).
8.1 Specification HRW Series
Page 77
8-7
8.2 Outer Dimensions
Top
Left side
Back
Front
HRX-OM-K003
Chapter 8 Appendix
Figure 8-1 Outer Dimensions
HRW Series 8.2 Outer Dimensions
Page 78
HRX-OM-K003
8-8
Temp. sensor
Solenoid valve
Heat
exchanger
Flowmeter sensor
Check valve
Temp. sensor
Press. sensor
Temp. sensor
Circulatin g fluid fill port
Circulating fluid level gauge
Facility water
bypass pipe
Temp. sensor
Level switch Leak switch (float-type)
Circulating fluid supply Rc3/4
Heater
Circulating
pump
Tank drain port Rc3/8
Drain pan port Rc3/8
Facility water inlet Rc3/4
Thermal fuse
Facility water outlet Rc3/4
Circulating fluid return Rc3/4
Circulating fluid bypass pipe
Main tank
Temp. sensor
Solenoid
valve
Heat
exchanger
Flowmeter sensor
Check valve
Temp. sensor
Press. sensor
Temp. sensor
Circulating fluid fill port
Circulating fluid level gauge
Facility water
bypass pipe
Temp. sensor
Level switch Leak switch (float-type)
Circulating fluid supply Rc3/4
Main tank
Heater
Circulating
pump
Tank drain port Rc3/8
Drain pan port Rc3/8
Facility water inlet Rc3/4
Thermal fuse
Facility water outlet Rc3/4
Circulating fluid return Rc3/4
Main tank
Chapter 8 Appendix
8.3 Flow Chart
8.3.1 Part 1
HRW002-H, -HS HRW002-H1, -H1S HRW002-H2, -H2S
8.3.2 Part 2
Figure 8-2 Flow Chart Part 1
HRW008-H, -HS HRW008-H1, -H1S HRW008-H2, -H2S HRW015-H, -HS HRW015-H1, -H1S HRW015-H2, -H2S HRW030-H, -HS HRW030-H1, -H1S HRW030-H2, -H2S
8.3 Flow Chart HRW Series
Figure 8-3 Flow Chart Part 2
Page 79
8-9
8.4 Offset Function
Potential deviations in temperature between this system and your system may be concerned depending on the installation environment. The offset function falling into three types (MODE1 to 3) is assigned to calibrate deviations in temperature. See the following descriptions for the offset function. See section 5.3.9 Initial Setting screen” for setting.
TEMP PV value, which is displayed on the Status screen, is output as circulating fluid temperature data in terms of communication.
When MODE1 is selected
This mode is used to exercise temperature control to allow the discharge temperature of the circulating fluid to be “TEMP SP value + OFFSET value”. TEMP PV value denotes the discharge temperature of the circulating fluid.
E.g.: TEMP SP value: +20°C, OFFSET value: +2°C
Circulating fluid discharge temp.: +22°C, TEMP PV: +22°C
When MODE2 is selected
This mode is used to exercise temperature control to allow the discharge
temperature of the circulating fluid to be “TEMP SP value”. TEMP PV value denotes “Circulating fluid discharge temp. value + OFFSET value”.
E.g.: TEMP SP value: +20°C, OFFSET value: +2°C
Circulating fluid discharge temp.: +20°C, TEMP PV: +22°C
HRX-OM-K003
Chapter 8 Appendix
When MODE3 is selected
This mode is used to exercise temperature control to allow the discharge temperature of the circulating fluid to be “TEMP SP value + OFFSET value”.
TEMP PV value denotes “Circulating fluid discharge temp. value - OFFSET value”.
E.g.: TEMP SP value: +20°C, OFFSET value: +2°C
Circulating fluid discharge temp.: +20°C, TEMP PV: +20°C
When OFF is selected
If no mode is selected, temperature control is conducted to allow the discharge temperature of the circulating fluid to be “TEMP SP value”.
HRW Series 8.4 Offset Function
Page 80
HRX-OM-K003
8-10
1 This system
Your system
Discharge temp.:
31
Circulating fluid temp. in
your system: 30
TEMP PV 31
TEMP SP 30
OFFSET 1
External communication
Communication data
TEMP PV 31
TEMP PV
31
Heat dissipation: 1
This system
Your system
Discharge temp.:
30
Circulating fluid temp. in
your system: 29
TEMP PV 30
TEMP SP 30
External communication
Communication data
TEMP PV 30
Heat dissipation:
Chapter 8 Appendix
8.4.1 Example of offset function
When the discharge temperature of the circulating fluid is at 30°C, heat is dissipated by 1°C to allow the circulating fluid in your system to be 29°C. Under the above condition, the following process is to be performed with the utilization of MODEs 1 to 3.
Figure 8-4 Example of Offset Function
When MODE1 is selected
This mode enables this system to exercise temperature control to obtain 31°C (TEMP SP value +OFFSET value), with OFFSET value set at 1°C. Once the discharge temperature of the circulating fluid becomes 31°C, 1°C-thermal dissipation is assured to allow the circulating fluid in your system to be 30°C. TEMP SP value is obtained for your system. Note that “31°C” is recorded in TEMP PV and communication data.
Figure 8-5 When MODE1 is selected
8.4 Offset Function HRW Series
Page 81
8-11
When MODE2 is selected
1°C
This system
Your system
Discharge temp.:
30°C Circulating fluid temp. in
your system: 29°C
TEMP PV 29°C
TEMP SP 30°C
OFFSET -1°C External communication
Communication data
TEMP PV 29°C
TEMP PV
29°C Heat dissipation:
Heat
1°C
This system
Your system
Discharge temp:
31°C
Circulating fluid temp. in
your system: 30°C
TEMP PV 30°C
TEMP SP 30°C
OFFSET 1°C
External communication
Communication data
TEMP PV 30°C
TEMP PV
30°C
dissipation:
With OFFSET value set at -1°C, TEMP PV and communication data express “29°C” (circulating fluid discharge temp. value + OFFSET value) that agrees with the temperature of the circulating fluid in your system.
HRX-OM-K003
Chapter 8 Appendix
Figure 8-6 When MODE2 is selected
When MODE3 is selected
This mode enables this system to exercise temperature control to obtain 31°C (TEMP SP value +OFFSET value), with OFFSET value set at 1°C. Once the discharge temperature of the circulating fluid becomes 31°C, 1°C-thermal dissipation is assured to allow the circulating fluid in your system to be 30°C. TEMP SP value is obtained for your system. TEMP PV and communication data also express “30°C” (circulating fluid discharge temp. value - OFFSET value) that agrees with the temperature of the circulating fluid in your system.
Figure 8-7 When MODE3 is selected
HRW Series 8.4 Offset Function
Page 82
HRX-OM-K003
8-12
BAND
TEMP SP
TEMP PV
TEMP READY not display/not output
TEMP READY display/output
READY TIME
Chapter 8 Appendix
8.5 BAND/READY function
Sets BAND to TEMP SP value, and notifies TEMP PV value reaches within BAND range by the operation display panel or the communication. See section 5.3.9 Initial Setting screen on page 5-7, “5.3.11 Option screenon page 5-9 for the procedure of the setting.
When the setting is ON
Allows the setting of the BAND and REDY TIME. Allows the setting of the communication output.
Figure 8-8 BAND/READY function
Examples of Setting
TEMP SP: 20°C BAND: 2°C READY TIME: 60sec.
TEMP READY is displayed on the operation display panel 60-sec. after TEMP PV value becomes 18°C to start output by communication. Necessary condition is that TEMP PV value after 60sec. is 20+/-2.0°C or less. See 5.3.4 Status screen 3on page 5-4 for the details of display position.
When the setting is OFF
BAND/READY function becomes invalid.
8.5 BAND/READY function HRW Series
Page 83
8-13
8.6 Anchor Bolt Mounting Position
Anti-seismic bracket (optional)
Anchor bolt (4-Ø14) Top
Anti-seismic bracket is an optional accessory, which is required for the
installation of this system (HRZ-TK002).
It is your responsibility to prepare anchor bolts suitable for your floor
material.
M12-anchor bolts (4 pcs.) are required.
Front
Anti-seismic bracket (optional)
Anchor bolt (4-Ø14)
Top
Lock the brakes on casters, and attach the anti-seismic bracket (optional: HRZ-TK002) to secure this system.
HRX-OM-K003
Chapter 8 Appendix
Figure 8-9 Anchor Bolt Mounting Position
HRW Series 8.6 Anchor Bolt Mounting Position
Page 84
HRX-OM-K003
8-14
CE Marking
EMC Directive
2004/108/EC
Low Voltage Directive
2006/95/EC
Machinery Directive
2006/42/EC
SEMATECH
S2-93, S8-95
SEMI
S2-0703, S8-0701, F47-0200
UL
E229305 / UL1995
Chapter 8 Appendix
8.7 Compliance
This system conforms to the following standards.
Table 8-7 Compliance
8.7 Compliance HRW Series
Page 85
HRX-OM-K003
8-15
To confirm daily inspection item on the Thermo Chiller, See “Table 7-2 Daily Inspection” in “7.2.1 Daily inspection” of “Chapter 7.
Circulating flui d
supply port cap
LoosenessIN press.FlowrateTemp.
Operating
condition
Error
Circulating
fluid
flowrate
Circulating flui d
outlet pres s.
Circulating
fluid temp.
Fluid Lev el
Cooling waterCirculating fluid
HumidityTemp.Date
After
installation
(initia l value)
Installation
Facili ty water
Yes/No
Yes/No
Leakage
Yes/No
Yes/No
L/min
MPa
Your na me
IN/OUT of range
Operation dis play
panel
Judgme nt
Function
Display
MPa
L/min
Thermo Chiller Daily Inspection Sheet
Model:
Serial No.
Chapter 8 Appendix
8.8 Thermo Chiller Daily Inspection Sheet
HRW Series 8.8 Thermo Chiller Daily Inspection Sheet
Page 86
Page 87
Product Warranty
1. Warranty
If a failure is observed in our Thermo Chiller, repair shall be provided in accordance with the warranty period
and preconditions defined below at SMC’s option.
Repair involves the inspection and/or replacement and/or modification of a defective part.
Removed parts shall become the possession of SMC.
2. Warranty period
The warranty period of the product is 1 year in service or 1.5 years after the product is delivered.
3. Warranty exemption
SMC’s liability under this warranty shall not be available for the following troubles and damages.
(1) Troubles or damage caused by the neglect of our designated inspection (daily inspection, periodic inspection)
(2) Troubles or damages caused by mishandling such as using improper operating procedure and using with our
specifications violated (3) Troubles or damages caused by unauthorized modification. (4) Troubles or damages caused by the use of a not-designated circulating fluid and facility water (5) Troubles or damages caused by wearing out such as fading on the coated or plated surface (6) Sensory phenomena that are considered no effect on the functions (such as noise, vibration) (7) Troubles or damages caused by natural disaster such as earthquake, typhoon, water, inevitable events and fire (8) Troubles or damages occurred under the installation conditions defined in the Operation Manual (9) Troubles or damages that are not compliant with the “5. Warranty preconditions”
4. Escape clause
(1) Expenses of daily inspection and periodic inspection (2) Expenses of repair consigned with neither SMC nor our authorized service station (3) Expenses of transport, installation, and removal of this system (4) Expenses of removal of non-genuine parts and replenishment of non-genuine fluids (5) Unavailability and loss due to this system being disabled
(such as telephone bill, leave compensation, commercial loss) (6) Expenses and compensation for terms other than provided in “1. Warranty”
5. Warranty precondition
Proper use and inspection of this system is required to assure safe use of this system. System warranty shall satisfy the following preconditions. Please take note that warranted repair shall not be available if these preconditions are disregarded. (1) System operation shall be conducted by following operating procedure defined in the Operation Manual. (2) Daily and periodic inspections designated in the Operation Manual shall be made as scheduled. (3) Inspection record shall be entered in the Daily Inspection Sheet provided in the Operation Manual.
6. Request for warranted repair
As to warranted repair, please contact the supplier you purchased this system from for service. Warranted repair shall be on request basis.
Unrequited repair shall be provided in accordance with the warranty period, preconditions and terms defined above. Therefore, the repair service shall be available on a chargeable basis if a failure is detected after the warranty period.
Page 88
4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021 JAPAN Tel: + 81 3 5207 8249 Fax: +81 3 5298 5362 URL http://www.smcworld.com
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer. © 2018 SMC Corporation All Rights Reserved
Loading...