Note: This manual is subject to possible change without prior notice.
Thank you for purchasing SMC’s Thermo chiller (hereinafter referred to as the “product”).
For safety and long life of the product, be sure to read this operation manual (hereinafter referred to
as the “manual”) and clearly understand the contents.
Be sure to read and follow all instructions noted with “Warning” or “Caution” in this manual.
This manual is intended to explain the installation and operation of the product. Only people who
understand the basic operation of the product through this manual or who perform installation and
operation of or have basic knowledge about industrial machines are allowed to work on the product.
This manual and other documents attached to the product do not constitute a contract, and will not
affect any existing agreements or commitments.
It is strictly prohibited to copy this manual entirely or partially for the use by a third party without prior
Before using the product, be sure to read and understand all the
important actions highlighted in this manual.
This sign indicates actions that must be followed.
This sign indicates prohibited actions.
Chapter 1 Safety Instructions
1.1 Before Using the Product
● This chapter is intended to specifically describe the safety related
issues for handling the product. Read this before handling the product.
● The product is a cooling device using circulating fluid. SMC does not
take any responsibility for any problems that may arise from using the
product for other purposes.
● This product is not designed for a clean room. It generates dust from
the internal components such as pump and fan motor.
● The product is operated at high voltage and contains components
which become hot and rotate. If a component needs to be replaced or
repaired, contact a specialized vendor for parts and service.
● All personnel who work with or around the product should read and
understand the safety related information in this manual carefully
before starting work.
● The safety manager is responsible for strictly observing safety
standards, but responsibility in respect to safety standards during daily
work resides with each individual operator and maintenance personnel.
● Do not use the materials that rust or corrode for the circulating fluid and
facility water circuits. Using the materials that tend to rust or corrode
may cause clogs or/and leakages of the circulating fluid and facility
water circuits. In case of using these kind of materials, consider and
carry out some prevention against the rusting or corrosion on the
customer side.
● This manual must be kept available to operators whenever necessary.
HRX-OM-Q026
1.2 Reading the Manual
This manual contains symbols to help identify important actions when
installing, operating or maintaining the product.
HRSH Series 1.1 Before Using the Product
1-1
HRX-OM-Q026
“WARNING”: Hazard that MAY cause serious personal injury or death during
operation.
“DANGER”: Hazard that WILL cause serious personal injury or death during
operation.
“CAUTION”: Hazard that MAY cause minor personal injury.
“CAUTION without exclamation symbol”: Hazard that MAY cause damage or failure
of the product, facility, devices, etc.
Chapter 1 Safety Instructions
1.3 Hazards
1.3.1 Level of hazards
The instructions given in this manual aim to assure the safe and correct
operation of the product, and to prevent injury of operators or damage to the
product. These instructions are grouped into three categories, Danger,
Warning and Caution, which indicate the level of hazard, damage and also
the degree of emergency. All safety critical information should be carefully
observed at all times.
“DANGER”, “WARNING” and “CAUTION” signs are in order according to
severity (DANGER> WARNING> CAUTION).
1.3.2 Definition of “Serious injury” and “Minor injury”
“Serious injury”
This term describes injuries that result in after effects including loss of
eyesight, burns, electric shock, fracture, poisoning, etc. and requires
long-term treatment or hospitalization.
“Minor injury”
This term describes injuries that do not need long-term treatment or
hospitalization. (Others excluded from “Serious injury”.)
1.3 Hazards HRSH Series
1-2
1.4 Product Label
Q
Z
001
Year
Symbol
Remarks
Month
Symbol
Remarks
Serial no.
2012
Q
Repeated
from
A to Z in
alphabetic
al
order
1
O
Repeated from
O to Z in
alphabetical
order, with O for
January and Z
for
December
-
2013 R 2 P 2014 S 3
Q
↓ ↓ ↓
↓
Kind and amount
of refrigerant
Model number
Serial number
* (An example of "HRSH150-A-20-S" model.)
"3~" stands for "3 inter phase".
(IEC 60417-5032-1)
Information about the product, such as Serial No. and Model No. can be
found on the product label. This information is needed when contacting an
SMC sales distributor.
How to see the serial number QZ001 (December 2012)
HRX-OM-Q026
Chapter 1 Safety Instructions
HRSH Series 1.4 Product Label
Fig. 1-1 Position of the product label
1-3
HRX-OM-Q026
Follow the instructions below when using the product. Failure to
follow the instructions may cause an accident and injury.
Always use safety shoes and gloves when operating the product.
Always use safety shoes, gloves, mask, apron and eye protection
when handling the circulating fluid.
Always use safety shoes, gloves and head protection when
transporting, installing or uninstalling the product.
Chapter 1 Safety Instructions
1.5 Safety Measures
1.5.1 Safety instructions for use
● Read and understand this manual carefully before using the product.
● Before starting maintenance of the product, be sure to lock out and tag
out the breaker of the user's power supply.
● If operating the product during maintenance, be sure to inform all
workers nearby.
● Use only the correct tools and procedure when installing or maintaining
the product.
● Use personal protective equipment where specified (“1.5.2 Personal
protective equipment”).
● Check all parts and screws are fitted correctly and securely after
maintenance.
● Avoid working in a drunken or sick condition, which might cause an
accident.
● Do not remove the panels except for the cases permitted in this
manual.
● Do not remove the panels during operation.
● Do not handle this product by any means other than specified in this
Operation Manual; this can result in damage to the product or fire.
1.5.2 Personal protective equipment
This manual specifies personal protective equipment for each work.
Transport, Installing and Uninstalling
Handling of circulating fluid
Operation
1.5 Safety Measures HRSH Series
1-4
1.6 Emergency Measures
Only maintenance personnel or qualified people are allowed to
open the cover panels of the product.
Do not mix the compressor oil with domestic waste for disposal.
Also, the disposal of the waste must only be conducted by specific
facilities that are permitted for that purpose.
Even when the power supply swtich is turned off, some of the internal
circuits are still energized, unless the user’s power supply is shut off.
Be sure to shut off the breaker of the user’s power supply.
Comply with the laws and regulations in each country for the
disposal of refrigerant and compressor oil.
The release of refrigerant in to the atmosphere is banned by law.
Recover it with specific equipment and dispose of it correctly.
Only people who have sufficient knowledge and experience about
the product and its accessories are allowed to recover the
refrigerant and compressor oil.
When emergency conditions such as natural disaster, fire, earthquake and
injury occur, shut off the breaker of the user’s power supply that supplies
power to the product.
1.7 Waste Disposal
1.7.1 Disposal of refrigerant and compressor oil
The product uses hydro fluorocarbon type refrigerant (HFC) and
compressor oil. Comply with the laws and regulations in each country for the
disposal of refrigerant and compressor oil. The type and quantity of
refrigerant is described on the “1.4 Product Label”.
If these fluids need to be recovered, read and understand the instructions
below carefully. If there is any unclear point, contact an SMC's sales
distributor.
1.7.2 Disposal of product
HRX-OM-Q026
Chapter 1 Safety Instructions
The disposal of the product must be handled by a specialized industrial
waste disposal agency in accordance with local laws and regulations.
HRSH Series 1.6 Emergency Measures
1-5
HRX-OM-Q026
Chapter 1 Safety Instructions
1.8 Material Safety Data Sheet (MSDS)
If the material safety data sheets of chemicals used in this product are
needed, contact an SMC's sales distributor.
Any chemicals used by the user must be accompanied by an MSDS.
1.8 Material Safety Data Sheet (MSDS) HRSH Series
1-6
HRX-OM-Q026
HRSH
①Cooling capacity
②Cooling method
③Piping thread type
④Power supply
---
⑤Option
AAir-cooled refrigeration
None
Nill
Caster-adjuster foot
installed
A
*2:Manual fluid fill port that is different from
the automatic fluid-fill function.
This enables that circulating fluid can be
filled manually without removing the side panel.
(In case of without K option, circulating
fluid can be filled manually removing
the side panel.)
Nil
Rc
FG (Rc-G thread adapter set is included)
N
NPT (Rc-NPT thread adapter set is included)
A
20
10010kW
250
20020kW
25kW
20
AC200V/200-230V(50/60Hz)
3phase
40
*3
AC380-415 50/60Hz 3phase
*1:In case of power supply '40' and option S,
this is standard. (with a handle)
WWater-cooled refrigeration
15015kW
Earth leakage breakerB
*1
Fluid fill port
K
*2
Earth leakage breaker
with a handle
B1
*1
CE / ULS
*3
*3:Power supply '20' only.
300
*4
30kW
*4:Air coooled only
Fixed SI unitW
*4
*4: Unit : MPa/ ゜C (degree Celsius)
Chapter 2 Name and Function of Parts
Chapter 2 Name and Function of Parts
2.1 Model Number of Product
The product can be ordered with the model number configured as shown
below.
The product needs to be handled in different ways depending on the part
number. Refer to “1.4 Product Label" and check the part number of the
product.
Fig. 2-1 Product model number
HRSH Series 2.1 Model Number of Product
2-1
HRX-OM-Q026
①
Alarm code list label
2 pcs.
(English 1 pc. /Japanese 1 pc.)
②
Operation manual
2 copies
(English 1 copy/Japanese 1
copy)
③
Y strainer (40 mesh) 25A
1 pc.
④
Barrel nipple 25A
1 pc.
⑤
For HRSH-AF-
G thread adapter set (HRS-EP014)
1 set
For HRSH-AN-
NPT thread adapter set (HRS-EP013)
1 set
-
Anchor brackets
2 pcs.
---
(M8 bolts)
6 pcs.
Circulating fluid
outlet port Rc1
Circulating fluid
return port Rc1
Automatic fluid
fill port Rc1/2
Overflow port
Rc1
Signal cable entry
(Grommet with membrane)
Tank drain port
Rc3/4 (closed by a
ball valve)
Power cable entry
(Grommet with membrane)
Product
Fluid level
gauge
Option K
[Fluid fill port]
Option B
[Earth leakage breaker]
Inside the panel
Dust-proof
Power terminal
(Inside the
Signal connectors
(Inside the panel)
Operation
display panel
Ventilation air inlet
Ventilation air inlet
Accessories
(③, ④, ⑤)
Accessories
(①, ②)
HRSH-A-20-B1
HRSH***-A*-20-S,
HRSH-A-40-
Breaker handle
Ventilation
air outlet
Chapter 2 Name and Function of Parts
2.2 Name and Function of Parts
2.2.1 HRSH-A- (Air cooled type)
Fig. 2-2 Names of the parts (This drawing shows “HRSH250-A-20”.)
Table 2-1: Accessory list
Note) The anchor brackets (including M8 bolts) are used for fixation with the skid when this product is packed. The anchor bolts are
not attached.
2.2 Name and Function of Parts HRSH Series
2-2
2.2.2 HRSH-W- (Water cooled type)
①
Alarm code list label
2 pcs.
(English 1 pc. /Japanese 1 pc.)
②
Operation manual
2 copies
(English 1 copy/Japanese 1
copy)
③
Y strainer (40 mesh) 25A
1 pc.
④
Barrel nipple 25A
1 pc.
⑤
For HRSH-WF-
G thread adapter set (HRS-EP016)
1 set
For HRSH-WN-
NPT thread adapter set (HRS-EP015)
1 set
-
Anchor brackets
2 pcs.
---
(M8 bolts)
6 pcs.
Breaker handle
HRSH-W-20-B1
HRSH-W-20-S
HRSH-W-40-
Fig. 2-3 Names of the parts (This drawing shows “HRSH150-W-20”.)
Table 2-2: Accessory list
HRX-OM-Q026
Chapter 2 Name and Function of Parts
Note) The anchor brackets (including M8 bolts) are used for fixation with the skid when this product is packed.
The anchor bolts are not attached.
HRSH Series 2.2 Name and Function of Parts
2-3
HRX-OM-Q026
Name
Function
Operation display panel
Runs and stops the product and performs settings such as the circulating
fluid temperature.
For details, refer to ’’2.4 Operation Display Panel’’.
Fluid level gauge
Indicates the circulating fluid level of the tank. Confirm the level is between
HIGH and LOW. For details, refer to “3.5 Circulating Fluid Supply”.
Product label
Shows the product information such as model number and serial number.
For details, refer to ‘’1.4 Product Label’.
Circulating fluid outlet port
The circulating fluid flows out from the outlet port.
Circulating fluid return port
The circulating fluid returns to the return port.
Tank drain port
This drain port to drain the circulating fluid out of the tank.
Automatic water fill port
Piping to the automatic water filling port enables easy supply of the
circulating fluid through the ball tap in the reservoir. The supply pressure
should be within the range of 0.2 to 0.5 MPa.
Overflow port
Be sure to connect piping from this port to sump pit to discharge the excess
circulating fluid that is caused by fluid level rising.
Dust-proof filter
Inserted to prevent that the dust and contamination are clung on the air
cooled condensers directly. Clean the filter periodically. For details, refer to
“7.2.2 Monthly check”.
Power cable entry
Insert the power cable to the power cable entry and connect it to the power
terminal. For details, refer to “3.3.2 Electrical wiring”and “3.3.3 Preparation
and wiring of power supply cable”.
Power terminal
Signal cable entry
Insert the signal cable to the signal cable entry and connect it to the signal
connectors. For details, refer to “3.3.4 Contact input/output communicatin
wiring”, “3.3.6 Wiring of run/stop signal input and remote signal input ”, “3.3.8 Wiring of external switch signal input”, “3.3.9 Wiring of contact output
signal”, “3.3.8 RS-485 communication wiring” , “3.3.9 RS-232C
communication wiring” or the Operation Manual Communication Function.
Signal connecors
Earth leakage breaker
(When option B [Earth leakage
breaker] is selected.)
Shuts off the power supply to the internal equipment of the product.
(Parts energized remained in the product.)
Refer to “3.3.2 Electrical wiring” for the earth leakage breaker.
Shuts off the power supply to the internal equipment of the product.
(Parts energized remained in the product.)
Refer to “3.3.2 Electrical wiring” for the earth leakage breaker.
Water fill port
(When option K “Water fill
port” is selected.)
Users who will not use the automatic water fill function can fill the circulating
fluid without removing the panel.
Facility water inlet port
(For water cooled type)
Supply facility water to the inlet port.
Facility water outlet port
(For water cooled type)
Facility water is discharged from the outlet port and returns to the user’s
facility water system.
Chapter 2 Name and Function of Parts
2.3 Function of Parts
The function of parts is as follows.
Table 2-3: Function of parts
2.3 Function of Parts HRSH Series
2-4
2.4 Operation Display Panel
No
Description
Function
Reference
page
①
Digital display
(7 segment,
4 digits)
PV
Displays the temperature and pressure of the circulating
fluid and alarm codes.
5.3
SV
Displays the set temperature of the circulating fluid and the
set values of other menus.
②
[oC oF] light
Displays the unit of display temperature (oC or oF).
5.13
③
[MPa PSI] light
Displays the unit of display pressure (MPa or PSI).
5.14
④
[REMOTE] light
Turns ON during remote operation by communication.
5.22
⑤
[RUN] light
・Turns ON when the product is started and in operation. Turns OFF
when the product stops.
・Blinks during stand-by for stop (Interval 0.5 seconds).
・Blinks during independent operation of the pump (Interval 0.3
seconds).
・Blinks while the anti-freezing function is being set (During standby:
Interval 2 seconds, During operation: Interval 0.3 seconds).
・Blinks during warming up function (During standby: Turns ON for 0.5
seconds and OFF for 3 seconds, During operation: Interval 0.3
seconds.)
4.4
⑥
[ALARM] light
Blinks with buzzer when alarm occurs (Interval 0.3 seconds).
5.4
Blinks while AL25 is OFF (Turns ON for 0.5 seconds and OFF for 3
seconds.)
5.21
⑦
[ ] light
Turns ON when the fluid level lowers below “L” (low) level.
4.3
⑧
[ ] light
Turns ON while the run timer or stop timer function is working.
5.7
⑨
[ ] light
Turns ON when the product is in automatic operation.
5.10
⑩
[RUN/STOP] key
Makes the product start or stop.
4.4
⑪
[MENU] key
Moves from the main menu (display which shows circulating fluid
temperature, pressure and etc.) to the other menus (entry of set
values and monitor screen).
5.2
⑫
[SEL] key
Changes the item in menu and enters the set value.
⑬
[▼] key
Decreases the set value.
-
⑭
[▲] key
Increases the set value.
⑮
[PUMP] key
When the [MENU] and [RUN/STOP] keys are held down
simultaneously, the pump starts running independently.
4.3
⑯
[RESET] key
Press the [▼] and [▲] keys simultaneously. This will stop the alarm
buzzer and turns OFF the [ALARM] light.
6.3
Keep the [▼] and [▲] keys pressed down simultaneously for 3
seconds to reset AL46 and AL48. (After resetting AL48, WAIT””
will be displayed and the product cannot start running for 40 seconds.
Restart 40 seconds later after resetting.
The operation panel on the front of the product controls the basic operation
of the product.
Fig. 2-4 Operation display panel
Table 2-4:Operation display panel
HRX-OM-Q026
Chapter 2 Name and Function of Parts
HRSH Series 2.4 Operation Display Panel
2-5
HRX-OM-Q026
Chapter 2 Name and Function of Parts
2.4 Operation Display Panel HRSH Series
2-6
HRX-OM-Q026
Drain the residual fluid from the piping as much as possible to
prevent any spillage.
Only persons who have sufficient knowledge and experience about
the product and system are allowed to transport and set up the
product.
Especially pay attention to personal safety.
Never lay the product on its side.
The compressor oil will leak in to the refrigerant piping, which may
cause early failure of the compressor.
When the product is carried by using a forklift, make sure that the
fork does not damage the cover panel or piping port.
Be sure to use all the four eye bolts when slinging the product.
The slant angle of each rope should be 60 degrees or less.
When moving the product by a forklift, insert the fork into the right
positions referring to 3.1.1 Transportation using forklift and
hanging- Moving by forklift and slinging should be done by
persons who have the licenses.
Chapter 3 Transport and Setting Up
Chapter 3 Transport and Setting Up
3.1 Transport
The product is heavy and has potential danger at transport. Also, to prevent
damage and breakage of the product, be sure to follow the instructions
shown below for transport.
HRSH Series 3.1 Transport
3-1
HRX-OM-Q026
Model
Weight kg
HRSH250/300-A-
Approx. 280
HRSH150/200-A-
Approx. 215
HRSH100-A-
Approx. 180
HRSH150/200/250-W-
Approx. 180
HRSH100-W-
Approx. 150
This is a heavy product. (Refer to
Table 3-1 Weight of the product) Moving by forklift and slinging should be
done by persons who have the licenses.
Position to hang
60o or less
Fork inserting position
Fork inserting position
Chapter 3 Transport and Setting Up
3.1.1 Transportation using forklift and hanging
Fig. 3-1 Fork inserting and hanging position (This drawing shows “HRSH250-A-20”.)
Table 3-1 Weight of the product
3.1 Transport HRSH Series
3-2
HRX-OM-Q026
Raise the adjuster
foot.
Swivel
caster
Each swivel caster can
rotate 360 degrees freely.
Raise the adjuster feet and push the corners of the product when
moving the product using the casters.
Do not hold the piping connections or handles of the panels when
moving by casters, or it may cause damage to the product..
This is a heavy product. (Refer to Table 3-1 Weight of the product).
Moving the product by casters should be done by 2 persons or more.
Chapter 3 Transport and Setting Up
3.1.2 Transportation using casters
In case of purchasing option A or the optional accessories, “Caster
Adjuster-foot kit” (HRS-KS001/KS002) separately and after fastening it to
the product.
Fig. 3-2 Transportation using casters (This drawing shows “HRSH250-A-20”.)
HRSH Series 3.1 Transport
3-3
HRX-OM-Q026
Keep the product upright on a rigid and flat floor which can resist
the weight of the product, and take measures to prevent the
product from tipping over. Improper installation may cause water
leakage, tipping, damage of the product or injure the operator.
Keep the ambient temperature of the product between -20 to 45oC.
Operation out of this ambient temperature range may cause a
malfunction of the product. Operating the product in an
environment temperature of 45 oC may reduce the heat
discharging efficiency of the heat exchanger and the safety device
may function, resulting in the product operation stoppage.
The installer/end user is responsible for carrying
out an acoustic noise risk assessment on the equipment after
installation and taking appropriate measures as required.
Do not set up the product in places possibly exposed to leakage of
flammable gas. Should any flammable gas stay around the
product, the product may cause a fire.
Chapter 3 Transport and Setting Up
3.2 Installation
3.2.1 Environment
The product must not be operated, installed, stored or transported in the
following conditions. Potential malfunction or damage to the product may
occur if these instructions are disregarded.
This product is not designed for clean room usage. The pump and
ventilating fan inside the product generate particles.
● Location that is exposed to steam, salt water or oil.
● Location that is exposed to dust or powder material.
● Location that is exposed to corrosive gas, organic solvent, chemical
solution, or flammable gas. (The product is not explosion-proof.)
● Location where the ambient temperature is out of the following range:
During transportation or storage: -15 to 50°C (No water or circulating
fluid in the piping.)
During operation Air cooling type: -20 to 45°C
Water cooling type: 2 to 45°C
When the ambient temperature or circulating fluid temperature is
10oC or below, use the circulating fluid specified in "3.2.2 Operation
at low ambient temperature or low circulating fluid temperature".
● Location where condensation forms on the inside electrical parts.
● Location that is exposed to direct sunlight or heat radiation.
● Location that is near heat sources and poor in ventilation.
● Location that is subjected to abrupt changes in temperature.
● Location that is subjected to strong electromagnetic noise (intense
electric field, intense magnetic field, or surges).
● Location that is subjected to static electricity, or conditions where static
electricity can discharge to the product.
● Location that is subjected to strong high frequencies raditation.
● Location that is subjected to potential lightening srtike.
● Location at altitude of 3000m or higher (except during product storage
and transport). Refer to below for details.
● Location where the product is affected by strong vibrations or impacts.
3.2 Installation HRSH Series
3-4
Chapter 3 Transport and Setting Up
Altitude [m]
1. Max. ambient
temp. [oC]
2. Cooling capacity
correction coefficient
Less than 1000m
45
1.00
1000 m or more - Less than 1500 m
42
0.85
1500m or more - Less than 2000m
38
0.80
2000m or more - Less than 2500m
35
0.75
2500m or more - Less than 3000m
32
0.70
● Condition that applies external force or weight causing the product to
be damaged.
● Location without adequate space for maintenance as required.
● Location that is exposed to splash of water that is higher than IPX4.
● When the ambient temperature or circulating fluid temperature is 10°C
or below, use the circulating fluid specified in "3.2.2 Operation at low
ambient temperature or low circulating fluid temperature".
● For the product installation or operation in accordance with UL
standards, see below.
Thermo-chiller installation in high altitude of 1000 meters or more
Because of lower air density, the heat radiation efficiencies of the devices in
the product will be lower in the location at altitude of 1000m or higher. For
this reason, the maximum ambient temperature for the thermo-chiller
operation and the cooling capacity will be reduced.
For product installation at a place of high altitude of 1000 meters or more,
select a thermo-chiller of the applicable capacity referring to the table below.
1. Max. ambient temp.: Use the product in lower ambient temperature than
the described value at each altitude.
2. Cooling capacity correction coefficient: Coefficient to calculate the cooling
capacity at each altitude
HRX-OM-Q026
For the product operation at an altitude of 1800 meters, the cooling capacity
at an altitude of 1800 meters = Cooling capacity 8.4 x 0.8.
Installation/Operation in accordance with the UL standard (for the optional UL
compliant model)
For operation of the UL compliant model (available as an option,
HRSH***-*-20-*S*) in UL compliant conditions, the product cannot be used
in the environment shown below:
● Environment at an altitude of 2000 meters or more
● Environment at a pollution degree of 3 or more
● Location where the ambient humidity is out of the following range:
During transportation or storage: 15% to 85% (No condensation)
During operation: 30% to 70% (No condensation)
HRSH Series 3.2 Installation
3-5
HRX-OM-Q026
Ambient temperature (°C)
Recommended circulating fluids
10 to 45
Tap water, ethylene glycol aqueous solution 15(wt)%
-5 to 10
Ethylene glycol aqueous solution 15(wt)%
-20 to -5
Ethylene glycol aqueous solution 40(wt)%
Circulating fluid
temperature(°C)
Recommended circulating fluids
10 to 35
Tap water, ethylene glycol aqueous solution 15(wt)%
5 to 10
Ethylene glycol aqueous solution 15(wt)%
Chapter 3 Transport and Setting Up
3.2.2 Operation at low ambient temperature or low circulating fluid
temperature
(1)Circulating fluid
In order to avoid freezing of the circulating fluid, use aqueous solution of ethylene glycol.
Note 1) Concentration has to be 40(wt)% or less.
If the concentration is higher than 40(wt)%, pump will be overloaded.
Note 2) When 40% ethylene glycol aqueous solution is used, cooling capacity decreases
by 20%.
(2)And following instructions must be executed. If following instructions are not executed, not
only Thermo-chiller alarm will be generated, but also damage of the product can result.
- Power has to be supplied to the Thermo-chiller all the time.
- Turn on anti-freezing function (set parameter: SE.10) all the time.
- When the power supply to the Thermo-chiller is stopped for a long period of time,
discharge all the circulating fluid in the Thermo-chiller and customer's device and
piping. When the Thermo-chiller is refilled with the circulating fluid, supply the fluid
at normal temperature.
3.2 Installation HRSH Series
3-6
3.2.3 Location
Model
Heat
radiation
(kW)
Required ventilation amount (m3/min)
Differential temp. of
3 oC between inside
and outside of
installation area
Differential temp. of
6 oC between inside
and outside of
installation area
HRSH100-A-20/40-
Approx.18
305
155
HRSH150-A-20/40-
Approx.29
490
245
HRSH200-A-20/40-
Approx.35
590
295
HRSH250-A-20/40-
Approx.44
730
370
HRSH300-A-20/40-
Approx.45
760
380
Do not install in a location which can be subjected to any of the
conditions in “3.2.1 Environment”.
The air cooled product radiates heat from the air vent of the cooling fan.
If the product is operated with insufficient air ventilation the internal
temperature can exceed 45oC, which can cause and affect the
performance and life of the product. To prevent this ensure that
suitable ventilation is available (see below).
Installation of multiple products
Keep sufficient space between products so that the air vented from one
product will not be taken in by other products.
Installation at indoor site (for air cooled type)
HRX-OM-Q026
Chapter 3 Transport and Setting Up
1. For a facility having a large installation area (that can vent the air
naturally):
Make an air outlet on a wall at a high level and air inlet on a wall at a low
level, to allow for adequate airflow.
2. For a facility having a small installation area (that can not vent the air
naturally):
Make a forced air exhaust vent on a wall at a high level and an air inlet on a
wall at a low level.
3. Using duct to exhaust the air:
In case the indoor site cannot accept the exhausted air from the product
or/and is air conditioned, ventilate by installing a duct on the outlet
ventilation of the product. Do not fasten the duct on the outlet ventilation of
the product directly. Have the space at least the duct’s diameter apart. Use
a fan for the duct that considered the ventilation resistance of the duct.
Table 3-2 Amount of radiation and required ventilation
HRSH Series 3.2 Installation
3-7
HRX-OM-Q026
Model
Heat
radiation
(kW)
Facility water specifications
HRSH100-W-20/40-
Approx. 20
Refer to “8.1 Specifications”.
HRSH150-W-20/40-
Approx. 27
HRSH200-W-20/40-
Approx. 34
HRSH250-W-20/40-
Approx. 40
The water cooled product radiates heat to the facility water.
It is necessary to supply the facility water. Please prepare the facility
water system that satisfies the heat radiation and the facility water
specifications below.
Chapter 3 Transport and Setting Up
Required facility water system (for water cooled type)
Have an enough space for the ventilation for the product. Otherwise it
may cause a lack of cooling capacity or/and stoppage of the product.
Ensure there is enough space for maintenance.
Top
Front
800mm or more
(For water cooled type)
400mm or more
800mm or more
2000mm or more
800mm or more
800mm or more
It is recommended to keep the space around the product shown in Fig. 3-3.
Fig. 3-3 Installation space (This drawing shows “HRSH250-A-20”.)
HRX-OM-Q026
Chapter 3 Transport and Setting Up
HRSH Series 3.2 Installation
3-9
HRX-OM-Q026
Install the product on a vibration free level floor.
Prepare the M10 anchor bolts that are suitable for the material of the
floor that the product will be installed on. Drive the anchor bolts in at
least two places on the left and right sides of the product (four places
in total). Refer to “8.2 Dimensions” for the dimensions for the position
of the anchor bolts.
Floor
Anchor bolt
Nut
Base of the product
Hole for anchor bolt (12mm)
Anchor bracket
Hole for anchor
bolt (12mm)
Chapter 3 Transport and Setting Up
3.3 Installation
3.3.1 Installation
How to mount the product
1. Insert the product to the anchor bolts that were previously driven on the level floor.
2. Fasten the nuts to the anchor bolts.
3. Make sure that there is no looseness on all the anchor bolts and nuts.
[Tips]
SMC Foundations bolt set “IDF-AB500” (SUS M10x50mm) is applicable.
Please order separately.
Fig. 3-4 Installation procedures
3.3 Installation HRSH Series
3-10