Note: This manual is subject to possible change without prior notice.
Thank you for purchasing SMC’s Thermo chiller (hereinafter referred to as the “product”).
For safety and long life of the product, be sure to read this operation manual (hereinafter referred to as the
“manual”) and clearly understand the contents.
Be sure to read and follow all instructions noted with “Warning” or “Caution” in this manual.
This manual is intended to explain the installation and operation of the product. Only people who
understand the basic operation of the product through this manual or who perform installation and
operation of or have basic knowledge about industrial machines are allowed to work on the product.
This manual and other documents attached to the product do not constitute a contract, and will not
affect any existing agreements or commitments.
It is strictly prohibited to copy this manual entirely or partially for the use by a third party without prior
Before using the product be sure to read and understand all the
important actions highlighted in this manual.
This sign indicates actions that must be followed.
This sign indicates prohibited actions.
Chapter 1 Safety Instructions
1.1 Before using the product
This chapter is intended to specifically describe the safety related issues
for handling the product. Read this before handling the product.
The product is a cooling device using circulating fluid. SMC does not take
any responsibility for any problems that may arise from using the product
for other purposes.
This product is not designed for a clean room. It generates dust from the
internal components such as pump and fan motor.
The product is operated at high voltage and contains components which
become hot and rotate. If a component needs to be replaced or repaired,
contact a specialized vendor for parts and service.
HRX-OM-R026
All personnel who work with or around the product should read and
understand the safety related information in this manual carefully before
starting work.
The safety manager is responsible for strictly observing safety standards,
but responsibility in respect to safety standards during daily work resides
with each individual operator and maintainance personnel.
Do not use the materials that rust or corrode for the circulating fluid
and facility water circuits. Using the materials that tend to rust or
corrode may cause clogs or/and leakages of the circulating fluid and
facility water circuits. In case of using these kind of materials, consider
and carry out some prevention against the rusting or corrosion by the
customer side.
This manual must be kept available to operators whenever necessary.
1.2 Reading the Manual
This manual contains symbols to help identify important actions when
installing, operating or maintaining the product.
HRSH Series 1.1Before using the product
HRX-OM-R026
1-2
“WARNING”: Hazard that MAY cause serious personal injury or death during
operation.
“DANGER”: Hazard that WILL cause serious personal injury or death during
operation.
“CAUTION”: Hazard that MAY cause minor personal injury.
“CAUTION without exclamation symbol”: Hazard that MAY cause damage or failure
of the product, facility, devices, ect.
Chapter 1 Safety Instructions
1.3 Hazards
1.3.1 Level of hazards
The instructions given in this manual aim to assure the safe and correct
operation of the product, and to prevent injury of operators or damage to the
product. These instructions are grouped into three categories, Danger,
Warning and Caution, which indicate the level of hazard, damage and also
the degree of emergency. All safety critical information should be carefully
observed at all times.
“DANGER”, “WARNING” and “CAUTION” signs are in order according to
severity (DANGER> WARNING> CAUTION).
1.3.2 Definition of “Serious injury” and “Minor injury”
“Serious injury”
This term describes injuries that result in after effects including loss of
eyesight, burns, electrical shock, fracture, poisoning, etc. and requires
long-term treatment or hospitalization.
“Minor injury”
This term describes injuries that do not need long-term treatment or
hospitalization. (Others excluded from serious injury.)
1.3 Hazards HRSH Series
1-3
1.4 Product Label
R
y
001
Year
Symbol
Remarks
Month
Symbol
Remarks
Serial
no.
2013
R
Repeated
from
A to Z in
alphabetical
order
1
O
Repeated from
O to Z in alphabetical
order, with O for
January and Z for
December
---
2014 S 2
P
2015 T 3
Q
↓ ↓ ↓
↓
Model number
Serial number
Kind and amount
of refrigerant
* (An example of "HRSH090-A-20" model.)
"3~" stands for "3 inter phase".
(IEC 60417-5032-1)
* In case of option S, the bellow label put near
the product label. CE mark is printed in the
product label.
Information about the product, such as Serial No. and Model No. can be
found on the model label. This information is needed when contacting an
SMC sales distributor.
HRX-OM-R026
Chapter 1 Safety Instructions
How to see the serial number Ry001(November 2013)
Fig. 1-1 Position of product label
HRSH Series 1.4Product Label
HRX-OM-R026
1-4
Always use safety shoes, gloves and head protection when
transporting, installing or uninstalling the product.
Always use safety shoes, gloves, mask, apron and eye protection
when handling the circulating fluid.
Always use safety shoes and gloves when operating the product.
Follow the instructions below when using the product. Failure to
follow the instructions may cause an accident and injury.
Chapter 1 Safety Instructions
1.5 Safety Measures
1.5.1 Safety Instructions for Use
Read and understand this manual carefully before using the product.
Before starting maintenance of the product, be sure to lock out and tag out the
breaker of the user's power supply.
If operating the product during maintenance, be sure to inform all workers nearby.
Use only the correct tools and procedure when installing or maintaning the product.
Use personal protective equipment where specified (“1.5.2Personal Protective
Equipment”)
Check all parts and screws are fitted correctly and securely after maintenance.
Avoid working in a drunken or sick condition, which might cause an accident.
Do not remove the panels except for the cases permitted in this manual.
Do not remove the panels during operation.
1.5.2 Personal Protective Equipment
This manual specifies personal protective equipment for each work.
Transport, Installing and Uninstalling
Handling of circulating fluid
Operation
1.5 Safety Measures HRSH Series
1-5
1.6 Emergency Measures
Only maintenance personnel or qualified people are allowed to
open the cover panels of the product.
Do not mix the compressor oil with domestic waste for disposal.
Also, the disposal of the waste must only be conducted by specific
facilities that are permitted for that purpose.
Even when the power supply swich is turned off, some of the internal
circuits are still energized, unless the user’s power supply is shut off.
Be sure to shut off the breaker of the user’s power supply.
Comply with the laws and regulations in each country for the
disposal of refrigerant and compressor oil.
The release of refrigerant in to the atmosphere is banned by law.
Recover it with specific equipment and dispose of it correctly.
Only people who have sufficient knowledge and experience about
the product and its accessories are allowed to recover the
refrigerant and compressor oil.
When emergency conditions such as natural disaster, fire and earthquake,
or injury occurs, shut off the breaker of the user’s power supply that supplies
the power to the product.
HRX-OM-R026
Chapter 1 Safety Instructions
1.7 Waste disposal
1.7.1 Disposal of refrigerant and compressor oil
The product uses hydro fluorocarbon type refrigerant (HFC) and
compressor oil. Comply with the laws and regulations in each country for the
disposal of refrigerant and compressor oil. The type and quantity of
refrigerant is described on the 1.4 Product Label.
If these fluids need to be recovered, read and understand the instructions
below carefully. If there is any unclear point, contact an SMC's sales
distributor.
1.7.2 Disposal of product
The disposal of the product must be handled by a specialized industrial
waste disposal agency in accordance with local laws and regulations.
HRSH Series 1.6Emergency Measures
HRX-OM-R026
1-6
Chapter 1 Safety Instructions
1.8 Material Safety Data Sheet (MSDS)
If the material safety data sheets of chemicals used in this product are
needed, contact an SMC's sales distributor.
Any chemicals used by the user must be accompanied by an MSDS.
1.8 Material Safety Data Sheet (MSDS) HRSH Series
HRX-OM-R026
2-1
HRSH090
①Cooling capacity
②Cooling method
③Piping thread type
④Power supply
---
⑤Option
AAir-cooled refrigeration
None
Nill
Earth leakage breaker
B
1
Nil
Rc
FG (Rc-G thread adapter set is included)
N
NPT (Rc-NPT thread adapter set is included)
A
20
0909.5kW
20
AC200V/200-230V(50/60Hz)
3phase
40
AC380-415V(50/60Hz)
3phase
1: In case of power supply '40' and option S,
this is standard.
2: Power supply '20' only.
WWater-cooled refrigeration
DI water (pure water) pipingM
Automatic water-fillJ
CE / ULS
1
Chapter 2 Name and Function of Parts
Chapter 2 Name and Function of Parts
2.1 Model number of product
The product can be ordered with the model number configured as shown
below.
The product needs to be handled in different ways depending on the part
number. Refer to “1.4 Product Label”and check the part number of the
product.
Fig. 2-1 Model number of product
HRSH Series 2.1Model number of product
HRX-OM-R026
2-2
1
Alarm cord list label
2pcs.
(English 1pc. /Japanese 1pc.)
2
Operation manual
2pcs.
(English 1pc./Japanese 1pc.)
3
Y strainer (40meshes) 25A
1pc.
4
Barrel nipple 25A
1pc.
5
Anchor brackets
※The anchor bolts are not attached
2pc.
6
For HRSH090-AF-
G thread adapter set (HRS-EP019)
1set
For HRSH090-AN-
NPT thread adapter set (HRS-EP018)
1set
For HRSH090-AF-J
G thread adapter set (HRS-EP021)
1set
For HRSH090-AN-J
NPT thread adapter set (HRS-EP020)
1set
Chapter 2 Name and Function of Parts
2.2 Name and Function of Parts
2.2.1 HRSH090-A-20/40-(In case of air cooled type)
Fig. 2-2 Names of each part
Table 2-1 Accessory list
2.2 Name and Function of Parts HRSH Series
Chapter 2 Name and Function of Parts
2-3
1
Alarm cord list label
2pcs.
(English 1pc. /Japanese 1pc.)
2
Operation manual
2pcs.
(English 1pc./Japanese 1pc.)
3
Y strainer (40meshes) 25A
1pc.
4
Barrel nipple 25A
1pc.
5
Anchor brackets
※The anchor bolts are not attached
2pc.
6
For HRSH090-WF-
G thread adapter set (HRS-EP023)
1set
For HRSH090-WN-
NPT thread adapter set (HRS-EP022)
1set
For HRSH090-WF-J
G thread adapter set (HRS-EP025)
1set
For HRSH090-WN-J
NPT thread adapter set (HRS-EP024)
1set
2.2.2 HRSH090-W-20/40-(In case of water cooled type)
Fig. 2-3 Names of each part
Table 2-2 Accessory list
HRX-OM-R026
HRSH Series 2.2Name and Function of Parts
HRX-OM-R026
2-4
Name
Function
Operation display panel
Runs and stops the product and performs settings such as the circulating
fluid temperature.
For details, refer to ’’2.4 Operation display panel’’.
Fluid level gauge
Indicates the circulating fluid level of the tank. For details, refer to “3.5Fill of
circulating fluid”.
Model label
Shows the product information such as model number and serial number.
For details, refer to ‘’1.4 Product Label’’.
Circulating fluid outlet port
The circulating fluid flows out from the outlet port.
Circulating fluid return port
The circulating fluid returns to the return port.
Tank drain port
This drain port to drain the circulating fluid out of the tank.
Automatic fluid fill port
Piping to the automatic fluid filling port enables easy supply of the circulating
fluid through the ball tap in the reservoir.The supply pressure should be
within the range of 0.2 to 0.5MPa.
Overflow port
Be sure to connect piping from this port to sump pit to discharge the exsess
circulating fluid that caused by fluid level rising.
Dust-proof filter
Inserted to prevent that the dust and contamination are clung on the air
cooled condensers directly. For details, refer to “8.2.2Monthly check”.
Power cable entry
Insert the power cable to the power cable entry and connect it to the power
terminal. For details, refer to “3.3.2Electrical wiring” and “3.3.3Preparation
and wiring of power supply cable”.
Power terminal
Signal cable entry
Insert the signal cable to the signal cable entry and connect it to the signal
connectors. For details, refer to “3.3.4Contact input/output communicatin
wiring”, “3.3.6Wiring of Run/stop signal input・Remote signal input”, “3.3.8Wiring of external switch signal input”, “3.3.9Wiring of operation signal
output and alarm signal output”, “3.3.8RS-485 Communication wiring” , “3.3.9RS-232C Communication wiring or the Operation manual
Communication function.
Signal connecors
Earth leakage breaker
(When option B [Earth leakage
breaker]I is selected.
Shuts off the power supply to the internal eqipment of product.
(Parts energized remained in the product)
Refer to “3.3.2Electrical wiring” for the earth leakage breaker.
Facility water inlet port
Supply facility water to inlet port.
Facility water outlet port
Facility water out from outlet port and return to customer’s facility water
system.
Automatic water-fill port
(When automatic fluid filling
[Option J] is selected.)
Piping to the automatic fluid filling port enables easy supply of the circulating
fluid through the built-in solenoid valve.The supply pressure should be in a
range of 0.2 to 0.5MPa.
Overflow port
(When automatic fluid filling
[Option J] is selected.)
This is necessary when automatic fluid filling function.Discharge excess
circulating fluid when the fluid level in the tank rises.
Chapter 2 Name and Function of Parts
2.3 Function of Parts
The function of parts is as follows.
Table 2-3 Function of parts
2.3 Function of Parts HRSH Series
2-5
2.4 Operation display panel
No
Description
Function
Reference
page
①
Digital display
(7 segment,
4 digits)
PV
Displays the temperature and pressure of the circulating
fluid and alarm codes.
5.3
SV
Displays the set temperature of the circulating fluid and
the set values of other menus.
②
[ oC oF ] lamp
Displays the unit of display temperature (oC or oF).
5.13
③
[MPa PSI] lamp
Displays the unit of display pressure (MPa or PSI).
5.14
④
[REMOTE] lamp
Lights up during remote operation by communication.
5.21
⑤
[RUN] lamp
・Lights up when the product is started and in operation. Goes off when the
product is stopped.
・Blinks during stand-by for stop (Interval 0.5 seconds).
・ Blinks during independent operation of the pump (Interval 0.3
seconds).
・Blinks during anti-freezing function (At standby: Interval 2 seconds, At
operation: Interval 0.3 seconds).
・Blinks during warming up function (At standby: lit on for 0.5 seconds
and off for 3 seconds, At operation: interval 0.3 seconds.)
4.4
⑥
[ALARM] lamp
Flashes with buzzer when alarm occurs (Interval 0.3 seconds).
5.4
⑦
[ ] lamp
Lights up when the fluid level lowers.
4.3 ⑧ [ ] lamp
Lights up while the run timer or stop timer function is working.
5.7
⑨
[ ] lamp
Lights up when the product is in automatic operation.
5.10
⑩
[RUN/STOP] key
Makes the product start or stop.
4.4
⑪
[MENU] key
Shifts the main menu (display screen of temperature) the other
menu (entry of set values and monitor screen).
5.2
⑫
[SEL] key
Changes the item in menu and enters the set value.
⑬
[▼] key
Decreases the set value.
-
⑭
[▲] key
Increases the set value.
⑮
[PUMP] key
When the [MENU] and [RUN/STOP] keys are held down
simultaneously, the pump starts running independently.
4.3
⑯
[RESET] key
Press the [▼] and [▲] keys simultaneously. This will stop the alarm
buzzer and reset the [ALARM] lamp.
7.3
Keep the [▼] and [▲] keys pressed down simultaneously for 3
seconds to reset AL46 and AL48.(After resetting AL48,
WAIT() will be displayed and the product cannot run for 40
seconds. Restart 40 seconds later after resetting.
The operation panel on the front of the product controls the basic operation
of the product.
HRX-OM-R026
Chapter 2 Name and Function of Parts
Fig. 2-4 Operation display panel
Table 2-4 Operation display panel
HRSH Series 2.4Operation display panel
HRX-OM-R026
2-6
Chapter 2 Name and Function of Parts
2.4 Operation display panel HRSH Series
HRX-OM-R026
3-1
When the product is carried by using a forklift, make sure that the
fork does not damage the cover panel, piping port, or caster.
Do not manipulate the fork in the range outside the label at the
bottom of the side surface of the product.
Drain the residual fluid from the piping as much as possible to
prevent any spillage.
Only persons who have sufficient knowledge and experience
about the product and system are allowed to transport and set up
the product.
Especially pay attention to personal safety.
Never lay the product on its side.
The compressor oil will leak in to the refrigerant piping, which may
cause early failure of the compressor.
When moving the product by a folklift, insert the fork into the right
psitions refering to 3.1.1
Moving by forklift.
Moving by forklift should be done by persons who have the
licenses.
Chapter 3 Transport and Setting Up
Chapter 3 Transport and Setting Up
3.1 Transport
The product is heavy and has potential danger at transport. Also, to prevent
damage and breakage of the product, be sure to follow these instructions for
transport.
HRSH Series 3.1Transport
HRX-OM-R026
3-2
Model
Weight kg
HRSH090-A--
Approx. 130
HRSH090-W*-*-*
Approx. 121
The product are heavy object. (Refer to Table 3-1 Weight of the
product)
Moving by forklift should be done by persons who have the
licenses.
Fork Insert position
Fork insert position
Chapter 3 Transport and Setting Up
3.1.1 Moving by forklift
Fig 3-1 Fork insert and slinging position)
Table 3-1 Weight of the product
3.1 Transport HRSH Series
3-3
3.1.2 Moving by casters
The product are heavy object. (Refer to Table 3-1 Weight of the
product).
Moving the product by casters should be done by 2 persons or
more.
Release the lock lever of the front casters and push the corner of
the product. Do not grip the piping or the handles of the panel. The
piping or panel may be damaged.
Do not hold the product by the cap to move it. This will apply
excess force to the piping of internal parts which may lead to
malfunctions such as fluid leakage.
Remove the anchor bolt fixtures.
Press
Unlocking
Tank lid
Corners
HRX-OM-R026
Chapter 3 Transport and Setting Up
Fig. 3-2 Transportation using casters
HRSH Series 3.1Transport
HRX-OM-R026
3-4
Do not set up the product in places possibly exposed to leakage of
flammable gas. Should any flammable gas stay around the
product, the product may cause a fire.
Do not use the product outdoors. If the product subjected to rain
orwater splash it may cause electrical shock, fire or failure.
Keep the product horizontal to a rigid and flat floor which can
resist the weight of the product, and take measures to prevent the
product from tipping over. Improper installation may cause water
leakage, tipping, damage of the product or injure the operator.
Keep the ambient temperature of the product between 5 to 45oC.
Operation out of this ambient temperature range may cause a
malfunction of the product.
The installer/end user is responsible for carrying
out a acoustic noise risk assessment on the equipment after
installation and taking appropriate measures as required.
Chapter 3 Transport and Setting Up
3.2 Installation
3.2.1 Environment
The product must not be operated, installed, stored or transported in the
following conditions. Potential malfunction or damage to the product may
occur if these instructions are disregarded.
The product does not conform to any clean room specifications. The pump
and ventilating fan inside the product generate particles.
In a location that is exposed to water, water vapor, steam, salt water or oil.
Location that is exposed to dust or powder material.
Location that is exposed to corrosive gas, organic solvent, chemical
solution, or flammable gas (the product is not explosion-proof)
Location where the ambient temperature is out of the following range:
In transportation and In storage 0 to 50°C
(Should not be water or circulating fluid circuit in the product)
In operation 5 to 45°C(Use 15% ethylene glycol
aqueous solution if operating in a place where the circulating fluid temp. or
ambient temperature is lower than 10 °C.)
Location where condensation forms on the inside electrical parts.
Location that is exposed to direct sunlight or heat radiation.
Location that is near heat sources and poor in ventilation.
Location that is subjected to abrupt changes in temperature.
Location that is subjected to strong electromagnetic noise (intense electric
field, intense magnetic field, or surges).
Location that is subjected to static electricity, or conditions where static
electricity can discharge to the product.
3.2 Installation HRSH Series
Location that is subjected to strong high frequencies raditation
(microwaves).
Location that is subjected to potential lightning srtike.
HRX-OM-R026
3-5
Altitude [m]
1. Max. ambient temp. [oC]
2. Cooling capacity
coefficient
Less than 1000m
45
1.00
Less than 1500m
42
0.85
Less than 2000m
38
0.80
Less than 2500m
35
0.75
Less than 3000m
32
0.70
Chapter 3 Transport and Setting Up
Location at altitude of 3000m or higher (except during product storage and
transport).
Because of lower air density, the heat radiation efficiencies of the devices
in the product will be lower in the location at altitude of 1000m or higher.
Therefore, the maximum ambient temperature to use and the cooling
capacity will lower according to the descriptions in the table below. Please
select the thermo chiller considering the descriptions.
1. Max. ambient temp.: Use the product in lower ambient temperature than
the described value at each altitude.
2. Cooling capacity coefficient: The product’s cooling capacity will lower to
one that multiplied by the described value at each altitude.
Bevelled place.
Location where the product is affected by strong vibrations or impacts.
Condition that applies external force or weight causing the product to be
damaged.
Location without adequate space for maintenance as required.
Location that is outside.
HRSH Series 3.2Installation
HRX-OM-R026
3-6
Model
Heat
radiation kW
Required ventilation amount m3/min
Differential temp. of
3 oC between inside
and outside of
installation area
Differential temp. of
6 oC between inside
and outside of
installation area
HRSH090-A--
Approx.18
305
155
Model
Heat
radiation kW
Facility water specifications
HRSH090-W-20/40-
Approx. 20
Refer to [9.1 Specifications].
The water cooled product radiates heat to the facility water.
It is necessary to supply the facility water. Please prepare the facility
water system that satisfies the heat radiation and the facility water
specifications below.
The air cooled product radiates heat from the air vent of the cooling fan.
If the product is operated with insufficient air ventilation the internal
temperature can exceed 45oC, which can cause an affect the
performance and life of the product. To prevent this ensure that
suitable ventilation is available (see below).
Do not install in a location which can be subjected to any of the
conditions in 3.2.1 Environment.
Chapter 3 Transport and Setting Up
3.2.2 Location
Installation of multiple products
Keep sufficient space between products so that the air vented from one product will not be taken
in by other products.
Installation at indoor site
1. In case of facility having a large installation area (that can vent the air naturally)
Make an air outlet on a wall at a high level and air inlet on a wall at a low level, to allow for
adequate airflow.
2. In case of facility having a small installation area (that can not vent the air naturally)
Make a forced air exhaust vent on a wall at a high level and an air inlet on a wall at a low level.
3. Using duct to exhaust the air
In case the indoor site cannot accept the exhausted air from the product or/and is air
conditioned, ventilate by installing a duct on the outlet ventilation of the product. Do not fasten
the duct on the outlet ventilation of the product directly. Have the space at least the dust’s
diameter apart. Use a fan for the duct that considered the ventilation resistance of the duct.
Table 3-2 Amount of radiation and required ventilation
Required facility water system
Table 3-3 Heat radiation
3.2 Installation HRSH Series
3-7
3.2.3 Installation and Maintenance Space
Have an enough space for the ventilation for the product. Otherwise it
may cause a lack of cooling capacity or/and stoppage of the product.
Have an enough space for maintenance.
Top
Front
It is recommended to keep the space around the product shown in Fig. 3-3.
Fig. 3-3 Installation space
HRX-OM-R026
Chapter 3 Transport and Setting Up
HRSH Series 3.2Installation
HRX-OM-R026
3-8
Install the product on the horizontal floor.
Prepare the M10 anchor bolts that are appropriate to the material of
the floor that the product will be installed. Drive the anchor bolts at
least at two places of the left and right side of the product each (totally
four places). Refer to the “8.2 Outline dimensions” for the dimensions
for the position of the anchor bolts.
Lock
Chapter 3 Transport and Setting Up
3.3 Installation
3.3.1 Installation
How to mount the product
1. Move the product to the installation area.
2. After moving, lock the front casters again.
Fig. 3-4 Installation procedures
3.3 Installation HRSH Series
3-9
Fixture
Holding screw
(2 pieces)
Fixture
Holding screw
(2 pieces)
Wooden box at the bottom of the product
HRX-OM-R026
Chapter 3 Transport and Setting Up
Use the fixtures and holding screws (for holding the product) fixed to the
wooden box at the bottom of the product to fix the product to the floor using
anchor bolts.
Fig. 3-5 Fixtures and holding screws
1. Install anchor bolts on the levelled floor with dimensions below.
Fig. 3-6 Installation of anchor bolts
2. Set the fixture from the top of the anchor bolts.
HRSH Series 3.3Installation
HRX-OM-R026
3-10
Chapter 3 Transport and Setting Up
3. Set hexagon screws to the anchor bolts and screw the holding screws into the product to
settle the product to the floor. Fixture is mounted to the front and the rear surface of the
product. (2 places)
【Tips】
SMC Foundations bolt set [IDF-AB500] (SUS M10x50mm) is applicable.
Fig. 3-7 Settlement to the floor
3.3 Installation HRSH Series