SMC Networks HRS012-A, HRS050-A, HRS012-W, HRS018-W, HRS018-A Operation Manual

...
Page 1
HRX-OM-M091-H
1
st
edition: Jul. 2009
8
th
edition: Nov.2011
Communication function
Thermo chiller
Air-Cooled
refrigerated type
Water-Cooled
refrigerated type
HRS012-A∗-10-∗ HRS012-W∗-10-∗ HRS018-A∗-10-∗ HRS018-W∗-10-∗ HRS012-A∗-20-∗ HRS012-W∗-20-∗ HRS018-A∗-20-∗ HRS018-W∗-20-∗ HRS024-A∗-20-∗ HRS024-W∗-20-∗ HRS050-A∗-20-∗ HRS050-W∗-20-∗
Keep this manual available whenever necessary
© 2011 SMC CORPORATION All Rights Reserved
Page 2
To the users
Thank you for purchasing SMC’s Thermo chiller (hereinafter referred to as the “product”).
For safety and long life of the product, be sure to read this operation manual (hereinafter referred to as the
“manual”) and clearly understand the contents.
Be sure to read and follow all instructions noted with “Warning” or “Caution” in this manual.
This manual is intended to explain the installation and operation of the product. Only people who
understand the basic operation of the product through this manual or who performs installation and
operation of or have basic knowledge about industrial machines are allowed to work on the product.
This manual and other documents attached to the product do not constitute a contract, and will not affect
any existing agreements or commitments.
It is strictly prohibited to copy this manual entirely or partially for the use by the third party without prior
permission from SMC.
Note: This manual is subject to possible change without prior notice.
Page 3
HRX-OM-M091
Contents
HRS Series
Contents
Chapter 1 Read before using.............................................................1-1
1.1 Communication mode and operation method ........................................................1-2
1.2 Communication port..................................................................................................1-3
1.3 Key operations...........................................................................................................1-4
1.4 Parameters .................................................................................................................1-6
Chapter 2 Contact input/output communication .............................2-1
2.1 Precautions for communication...............................................................................2-1
2.1.1 Precautions wiring communication...................................................................................... 2-1
2.1.2 Precautions after wiring and before communication ........................................................... 2-1
2.2 Communication specification...................................................................................2-2
2.3 Terminal block explanation.......................................................................................2-2
2.4 Setting and checking.................................................................................................2-4
2.4.1 Setting and checking........................................................................................................... 2-4
2.4.2 Setting and checking........................................................................................................... 2-5
2.5 Contact input signal.................................................................................................2-16
2.5.1 Run/stop signalRemote signal......................................................................................... 2-16
2.5.2 Signal of the external switch ............................................................................................. 2-18
2.6 Contact output signal..............................................................................................2-19
Chapter 3 Serial communication.......................................................3-1
3.1 Precautions wiring communication .........................................................................3-1
3.2 Communication specification...................................................................................3-1
3.3 Connected explanation .............................................................................................3-2
Chapter 4 MODBUS communication function..................................4-1
4.1 Precautions for communication...............................................................................4-1
4.1.1 Precautions after wiring and before communication ........................................................... 4-1
4.1.2 Precautions for communicating........................................................................................... 4-2
4.2 Communication specification...................................................................................4-2
4.3 Setting and checking.................................................................................................4-3
4.3.1 Setting and checking items ................................................................................................. 4-3
4.3.2 Setting and checking........................................................................................................... 4-4
4.4 Communication sequence ........................................................................................4-7
4.5 Message configuration..............................................................................................4-8
4.5.1 Message format................................................................................................................... 4-8
4.5.2 Message example ............................................................................................................... 4-9
4.6 Function codes ........................................................................................................4-10
4.7 LRC............................................................................................................................4-10
4.8 Explanation of function codes................................................................................4-11
4.8.1 Function code03 Reading multiple registers ..................................................................4-11
4.8.2 Function code06 Writing registers ................................................................................. 4-12
Page 4
HRX-OM-M091 Contents
HRS Series
4.8.3 Function code16 Writing multiple registers .................................................................... 4-13
4.8.4 Function code23 Reading/writing multiple registers ......................................................4-14
4.9 Negative response...................................................................................................4-16
4.10 Register Map ............................................................................................................4-17
4.10.1 Circulating fluid discharge temperature.............................................................................4-17
4.10.2 Circulating fluid discharge pressure ..................................................................................4-17
4.10.3 Electric resistivity of the circulating fluid ............................................................................4-17
4.10.4 Status flag..........................................................................................................................4-18
4.10.5 Alarm flag........................................................................................................................... 4-19
4.10.6 Circulating fluid set temperature........................................................................................4-21
4.10.7 Operation Start Command................................................................................................. 4-21
Chapter 5 Simple communication protocol function ......................5-1
5.1 Precautions for communication...............................................................................5-1
5.1.1 Precautions after wiring and before communication ...........................................................5-1
5.1.2 Precautions for communicating ...........................................................................................5-2
5.1.3 Precautions after the completion of the communication...................................................... 5-2
5.2 Communication specification...................................................................................5-3
5.3 Setting and checking.................................................................................................5-4
5.3.1 Setting and checking items.................................................................................................. 5-4
5.3.2 Setting and checking ...........................................................................................................5-5
5.4 Communication sequence...................................................................................... 5-11
5.5 Message configuration............................................................................................5-12
5.5.1 Message format .................................................................................................................5-12
5.5.2 Message example.............................................................................................................. 5-14
5.6 BCC...........................................................................................................................5-15
5.7 Command .................................................................................................................5-15
5.8 Command explanation ............................................................................................5-16
5.8.1 Command:PV1 Circulating fluid discharge temperature ...................................................5-16
5.8.2 Command:SV1 Circulating fluid set temperature (R) ........................................................ 5-17
5.8.3 Command:SV1 Circulating fluid set temperature (W) .......................................................5-18
5.8.4 Command:LOC Key-lock setting (R) ................................................................................. 5-19
5.8.5 Command:LOC Key-lock setting (W) ................................................................................5-20
5.8.6 Command:STR Saves data (W) ........................................................................................ 5-21
5.9 Negative response...................................................................................................5-22
Chapter 6 Communication alarm function ....................................... 6-1
6.1 Communication alarm occurs ..................................................................................6-1
6.2 Communication alarm reset......................................................................................6-2
6.3 Setting and checking.................................................................................................6-2
6.3.1 Setting and checking items.................................................................................................. 6-2
6.3.2 Setting and checking ...........................................................................................................6-3
Page 5
HRX-OM-M091
Chapter 1 Read before using
HRS Series 1.1 Communication mode and operation method
1-1
Chapter 1 Read before using
The communication of this device consists of contact input/output communication and serial communication.
MODBUS communication and simple communication protocol can be selected as the serial communication protocol. Depending on the customer’s specification, communication can be changed to contact input/output communication or serial communication.
Table 1-1 Communication method
Contact input/output communication
This product is equipped with a terminal which runs/stops the product by remote control and a terminal which can pick up alarm signals. The terminals can be changed depending on the customer’s application.
MODBUS standard protocol
Serial communication (RS-485/RS232C) enables remote control of run/start of the product, temperature setting, and details of product condition and alarm condition can be obtained.
Serial communication
Simple communication protocol
Serial communication (RS-485/RS232C) enables remote control of temperature setting. This protocol complies with SMC thermo-cooler HRG, HRGC series. (We recommend using the MODBUS protocol if you are unfamiliar with using the communication function.) There are two ways to start and stop by simple communication protocol. The customer can choose between operation using the Operation display panel (simple communication protocol 1) and remote control using the contact input (simple communication protocol 2).
If using contact input/output communication, refer to chapter 2.
If using serial communication MODBUS, refer to chapter 3 for
serial communication specifications first, then refer to chapter 4 for protocol specifications.
If using simple communication protocol for serial communication, refer to chapter 3 for serial communication specifications first, then refer to chapter 5 for protocol specifications.
Page 6
HRX-OM-M091
Chapter 1 Read before using
1.1 Communication mode and operation method HRS Series
1-2
1.1 Communication mode and operation method
LOCAL, DIO and SERIAL are available as the communication modes. Table
1.1-1 explains the communication modes. The default setting is LOCAL.
The operation method depends on the communication mode. Table 1.1-2 shows how the communication mode and method of operation are related.
The operation of the product functions depends on the communication mode. Table 1.1-3 shows how the communication mode and functions of this product are related.
Table 1.1-1 Communication modes
Communication mode Explanation
LOCAL Mode allowing the product to be operated by the operation panel.
Mode allowing the product to be operated by the contact input/output communication. When the communication mode is “DIO”, operation mode automatically becomes “DIO REMOTE”. "DIO REMOTE” and “DIO LOCAL” can be selected by DIO communication signal.
DIO REMOTE
Contact input/output communication takes control of the operation of the product. The [REMOTE] lamp on the operation panel turns on.
DIO
DIO LOCAL
Operation control of the product is the same as that of LOCAL. The [REMOTE] lamp on the operation panel turns off.
SERIAL
Mode allowing the product to be operated by serial communication. MODBUS/ simple communication protocol can be selected.
Table 1.1-2 Communication mode and operation
DIO SERIAL
Simple
communication
protocol pattern
LOCAL
DIO
LOCAL
DIO
REMOTE
MODBUS
1 2
Run/Stop control with operation display panel
× × ×
Circulating fluid discharge temperature setting control with operation display panel
× ×
Except above with operation display panel Condition reading with operation display panel
Run/Stop operation by contact input/output communication
× × × ×
Condition reading by contact input/output communication
Reading of the external switch
1
1
1
Run/Stop operation by serial communication.
× × × ×
Circulating fluid discharge temperature setting control by serial communication.
× × ×
Condition reading by serial communication.
1: Only one external switch can be installed.
Table 1.1-3 Communication mode and product functions
DIO SERIAL
Simple
communication
protocol pattern
LOCAL
DIO
LOCAL
DIO
REMOTE
MODBUS
1 2
Run timer × ×
×
Stop timer × × × Recovery from power failure × × × Anti-freezing Pump accumulated operating time reset × × ×
Page 7
HRX-OM-M091
Chapter 1 Read before using
HRS Series 1.2 Communication port
1-3
1.2 Communication port
The communication port at the back of the product is used for communication. Fig 1.2-1, Fig 1.2-2 shows the location of the communication port.
Fig 1.2-1 Communication port (HRS012-∗∗-∗-∗, HRS018-∗∗-∗-∗, HRS024-∗∗-20-∗)
Fig 1.2-2 Communication port (HRS050-∗∗-20-∗)
Contact input/output(DIO) Connector for communication Used for DIO communication. Mating connector is prepared as an accessory.
Connector for
option Not used for communication.
Serial communication Connector Used for RS-485/RS-232C.
Page 8
HRX-OM-M091
Chapter 1 Read before using
1.3 Key operations HRS Series
1-4
1.3 Key operations
Fig 1.3-1 ‘’Key operation (1/2)’’ and
Fig 1.3-2 ‘’Key operation (2/2)’’ show the operation of keys of the thermo-chiller. This manual explains the “Communication setting menu”.
MENU
PV
SV
Circulating fluid outlet temperature Circulating fluid set temperature
Circulating fluid outlet pressure
Main display
Circulating fluid outlet temperature
Circulating fluid return port
Check monitor
menu
Temperature of the compressor inlet.
PV
SV
PV
SV
PV
SV
PV
SV
Circulating fluid outlet pressure
PV
SV
Pressure of higher pressure refrigerant circuit
PV
SV
Pressure of lower pressure refrigerant circuit
Accumulated operation time of the pump
Accumulated operation time of the fun motor
Accumulated operation time of the compressor
Accumulated operation time
PV
SV
PV
SV
PV
SV
PV
SV
Key-lock
Run timer
Setting menu
Stop timer
READY mode
READY band width
READY time
Offset mode
Offset temperature
Recover from power failure
Anti-freezing
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
Data reset
Pump accumulated operating time reset
Fun motor accumulated operating time reset
Compressor accumulated operating time reset
Key click sound
Temperature unit
Pressure unit
PV
SV
PV
SV
PV
SV
Alarm The latest
Alarm
Alarm display menu
Alarm
The oldest
PV
SV
PV
SV
PV
SV
Note) It changes only when the alarm is generated.
PV
SV
PV
SV
PV
SV
PV
SV
Power supply ON
PV
SV
Press the 2 sec.
PV
SV
Electric resistivity
PV
SV
SEL
Option drain pan set
PV
SV
PV
SV
Electric resistivity
Option electric resistivity sensor set
SEL
Unused
PV
SV
Unused
Unused
PV
SV
PV
SV
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
MENU
MENU
Press the 2 sec.
MENU
Press the 2 sec.
MENUMENU
MENU
Fig 1.3-1 Key operation (1/2)
Page 9
HRX-OM-M091
Chapter 1 Read before using
HRS Series 1.3 Key operations
1-5
MENU
Changing of contact input 1 signal detection
Alarm buzzer sound
Changing of low tank level
Changing of circulating fluid discharge temperature rise
Detection temperature for circulating fluid discharge temperature rise
Changing of circulating fluid discharge temperature drop
Detection temperature for circulating fluid discharge temperature drop
Changing of circulating fluid discharge pressure rise
Detection pressure for circulating fluid discharge pressure rise
Changing of communicati on error
The monitoring time of communication error
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
Changing of circulating fluid discharge pressure drop
Detection pressure for circulating fluid discharge pressure drop
PV
SV
PV
SV
PV
SV
PV
SV
Changing of contact input 2 signal detection
PV
SV
PV
SV
Changing of DI level rise
Upper limit of DI level rise
Changing of DC line fuse cut
Changing of water leakage
PV
SV
PV
SV
PV
SV
Lower limit of DI level drop
Changing of DI level drop
PV
SV
PV
SV
PV
SV
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
Press the 2 sec.
MENU
Alarm setting
menu
MENU
Communicati on mode
Serial protocol
Communication specifications
RS-485 terminal
Slave address MODBUS
Communicati on speed MODBUS
Slave address Simple communicatio n protocol
Communication speed Simple communication protocol
Response delay time Simple communication protocol
Communicati on range Simple communicati on protocol
MENU
BCC Simple communicatio n protocol
Data length Simple communicati on protocol
Parity check Simple communicati on protocol
Stop bit length Simple communicatio n protocol
Digital input signal 1
Digital input signal 1 type
Digital input signal 2
Digital input signal 2 type
Digital output 1 function
Digital output 1 operation
Digital output 1 selected alarm
Digital output 2 function
Digital output 3 selected alarm
Digital output 2 operation
Digital output 2 selected alarm
Digital output 3 function
Digital output 3 operation
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
SV
Press the 2 sec.
Contact input signal 1 Delay timer (time delay) of reading
Contact input signal 2 OFF Detection timer
PV
SV
PV
SV
Contact input signal 2 Delay timer (time delay) of reading
Contact input signal 2 OFF Detection timer
PV
SV
PV
SV
Communication
setting menu
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
PV
MENU
This manual explains the ''Co mmunication setting menu''.
SEL
PV
SV
PV
SV
SEL
PV
SV
SEL
SEL
Temperature alarm Monitoring method
Monitoring start timer
Range over Detection timer
Fig 1.3-2 Key operation (2/2)
Page 10
HRX-OM-M091
Chapter 1 Read before using
1.4 Parameters HRS Series
1-6
1.4 Parameters
Table 1.4-1 ‘’Parameters’’ explains the parameters of the 「communication setting menu」.
Table 1.4-1 Parameters
Display Item
Initial value
(Default setting)
Reference
page
Category
Communication mode LOC
2.4
4.3
5.3
Serial protocol MDBS
4.3
5.3 Communication specifications
485
4.3
5.3
RS-485 terminal OFF
4.3
5.3
Slave address 1
Mo db us
Communication speed 19.2
4.3
Slave address 1 Communication speed 9.6 BCC ON Data length 8BIT Parity check NON Stop bit length 2BIT Response delay time 0
Serial communication
Simple
communication
p
rotocol
Communication range RW
5.3
Contact input signal 1 RUN Contact input signal 1 type ALT Contact input signal 1 delay timer (time delay) of reading
0
Contact input signal 1 OFF detection timer
0
Contact input signal 2 OFF Contact input signal 2 type ALT Contact input signal 2 delay timer (time delay) of reading
0
Contact input signal 2 OFF detection timer
0
Contact output 1 function
RUN
Contact output 1 operation
A
Selected for contact output 1
AL.01
Contact output 2 function
RMT
Contact output 2 operation
A
Selected for contact output 2.
AL.01 Contact output 3 function ALM Contact output 3 operation B
Contact input/output communication
Selected for contact output 3 AL.01
2.4
Communication
setting menu
Page 11
HRX-OM-M091
Chapter 2 Contact input/output communication
HRS Series 2.1 Precautions for communication
2-1
Chapter 2 Contact input/output
communication
The device is equipped with a terminal which runs/stops the product. It is also equipped with a terminal which picks up operation signals, alarm signals and setting condition.
The device starts contact input/output communication according to the setting of the operation display panel. Contact input/output communication can be customized by changing the settings. Table 2-1 ‘’Customizable content’’ shows the contents which can be changed by the operation display panel.
Table 2-1 Customizable content
Signal Can be changed
Contact input/output signal(2pcs.) Signal configuration(Alternate/Momentary)
Contact input/output signal(3pcs.)
Type of signal, signal operationN.O type / N.C type
2.1 Precautions for communication
2.1.1 Precautions wiring communication
Communication wiring
A communication cable that connects the product and customer system is not included with the product. Please prepare a cable, referring to 2.3 ‘’Terminal block explanation (The connector is included.) In order to avoid malfunction, do not connect to any place other than those shown in 2.3 ‘’Terminal block explanation.
Power supply
To use the power of the product, the total load current must be 500mA or less.
If the load is 500mA or more, the internal fuse is cut to protect the product and the alarm [AL21 DC line fuse cut] is generated. Refer to the “Installation / Operation” of the operation manual for alarms.
Optional parts needs to be adjusted so that the total load is 500mA or less referring the table below.
Table 2-1-1 Current consumption of optional parts
No. Name
Part NO
Current
consumption
1 Drain pan set(with water leakage sensor) HRS-WL001 25mA 2 Drain pan set(with water leakage sensor) HRS-WL002 25mA 3 Electric resistivity sensor set HRS-DI001 100mA
2.1.2 Precautions after wiring and before communication
Check or set the communication mode by the operation display panel.
Communication mode shall be DIO.
Other modes can perform reading, but only DIO mode can perform writing.
Page 12
HRX-OM-M091
Chapter 2 Contact input/output communication
2.2 Communication specification HRS Series
2-2
2.2 Communication specification
Table 2.2-1 DIO Communication specification
Item Specification
Connector type (for this product) MC 1,5/12-GF-3,5
Insulation system Photo coupler Rated input voltage DC24V Used input voltage DC 21.6V to 26.4V Rated input current 5mA TYP
Contact input signal
Input signal 4.7k Rated load voltage AC48V or less/DC30V or less Contact output
signal
Maximum load current
AC/DC 500mA (Resistance load)
Output voltage
DC24V±10 0.5A MAX
2.3 Terminal block explanation
This part explains the terminal block of the contact input/output communication. A communication cable that connects the product and customer system is not included with the product. Prepare a cable, referring to Table 2.3-1 and Fig 2.3-1. Use the connector included as an accessory.
Table 2.3-1 Terminal explanation
Terminal
no
Application Division Default setting
Setting
available
1 Common of contact output signal 3 2 Contact output signal 3
Output
Alarm signalN.C type
3 Common of contact output signal 2 4 Contact output signal 2
Output
Remote signalN.O type
5 Common of contact output signal 1 6 Contact output signal 1
Output
Run status signalN.O type
7 Common of contact input signal 2 8 Contact input signal 2
Input None
9 Common of contact input signal 1
10 Contact input signal 1
Input
Run/stop signal(Alternate)
11 24V COM output Output
12 DC 24V output Output
Page 13
HRX-OM-M091
Chapter 2 Contact input/output communication
HRS Series 2.3 Terminal block explanation
2-3
4.7kΩ
This product
Your system
Internal circuit
DC24V
Contact output signal 3
10
6
Contact input signal 1
Contact output signal 1
Contact output signal 2
12
11
24VCOM
9
8
7
5
4
3
2
1
Contact input signal 2
DC24V output
24VCOM output
1kΩ
4.7kΩ
1kΩ
Alarm signal
Run/stop signal
Run status signal
Remote signal
Signal description
Default setting
Fig 2.3-1 Example of connector connection
Fig 2.3-2 Attached connector and terminal no (Example)
Fig 2.3-3 Wiring of the external switch (NPN open collector output) (Example)
Fig 2.3-4 Wiring of the external switch (PNP open collector output) (Example)
Terminal no.1
Terminal no.12
Wire the communication cable to the connector included as an accessory.
Connect the remote control cable and the switch to the connector for the contact input/output, supplied as an accessory. Then, mount the ferrite core (3 turn) supplied as an accessory. (This is an example of wiring.)
Terminal no.1
Terminal no.12
Wire the communication cable to the connector included as an accessory.
Brown (DC 24V)
Blue (DC COM)
Black (Output 1)
Flow switch
Terminal no.1
Terminal no.12
Wire the communication cable to the connector included as an accessory.
Brown (DC 24V)
Blue (DC COM)
Black (Output 1)
Flow switch
Page 14
HRX-OM-M091
Chapter 2 Contact input/output communication
2.4 Setting and checking HRS Series
2-4
2.4 Setting and checking
2.4.1 Setting and checking
The table below explains the setting items of the contact input/output signal and the initial values.
Table 2.4-1 List of set communication items
Display Item Contents
Initial value
(Default setting)
Communication mode
Sets communication mode of this product.
LOC
Contact input signal 1
Setting contact input signal 1 of the contact input/output communication.
RUN
Contact input signal 1 type
Setting input type of contact input signal 1 of the contact input/output communication. [----] is displayed when the setting of contact input signal 1 is OFF.
ALT
Contact input signal 1 delay timer of reading
Sets the delay timer of reading of contact input signal 1 of the contact input/output communication. Used when the setting of the contact input signal 1 is SW_A or SW_B. [----] is displayed when the setting of the contact input signal 1 is not SW_A or SW_B.
-
Contact input signal 1 OFF Detection timer
Sets the OFF detection timer of contact input signal 1 of the contact input/output communication. Used when the setting of the contact input signal 1 is SW_A or SW_B. [----] is displayed when the setting of the contact input signal 1 is not SW_A or SW_B.
-
Contact input signal 2
Setting contact input signal 2 of the contact input/output communication.
OFF
Contact input signal 2 type
Setting input type of contact input signal 2 of the contact input/output communication. [----] is displayed when the setting of contact input signal 2 is OFF.
ALT
Contact input signal 2 delay timer of reading
Sets the delay timer of reading of contact input signal 2 of the contact input/output communication. Used when the setting of the contact input signal 2 is SW_A or SW_B [----] is displayed when the setting of the contact input signal 2 is not SW_A or SW_B.
-
Contact input signal 2 OFF Detection timer
Sets the OFF detection timer of contact input signal 2 of the contact input/output communication. Used when the setting of the contact input signal 2 is SW_A or SW_B. [----] is displayed when the setting of the contact input signal 2 is not SW_A or SW_B.
-
Contact output 1 function
Setting output signal function of contact output 1 of the contact input/output communication.
RUN
Contact output 1 operation
Setting output signal operation of contact output 1 of the contact input/output communication.
A
Contact output 1 selected alarm
Setting selected alarm of contact output 1 of the contact input/output communication. [----] is displayed when the setting of the output signal of contact output1 is not selected alarm signal.
AL.01
Contact output 2 function
Setting output signal function of contact output 2 of the contact input/output communication.
RMT
Contact output 2 operation
Setting output signal operation of contact output 2 of the contact input/output communication.
A
Contact output 2 selected alarm
Setting selected alarm of contact output 2 of the contact input/output communication. [----] is displayed when the setting of the output signal of contact output2 is not selected alarm signal.
AL.01
Contact output 3 function
Setting output signal function of contact output 3 of the contact input/output communication.
ALM
Contact output 3 operation
Setting output signal operation of contact output 3 of the contact input/output communication.
B
Contact output 3 selected alarm
Setting selected alarm of contact output 3 of the contact input/output communication. [----] is displayed when the setting of the output signal of contact output3 is not selected alarm signal.
AL.01
Page 15
HRX-OM-M091
Chapter 2 Contact input/output communication
HRS Series 2.4 Setting and checking
2-5
If the communication mode is set to [DIO] first while the operating signal is input, the product will start and feed the circulating fluid before the details are set. For safety, set the communication mode to [DIO] after carrying out the setting
below.
2.4.2 Setting and checking
Communication mode Setting and checking
1. Press and hold the [MENU] key for 2 sec.
Repeat pressing the key until the setting screen for communication mode [
] appears
on the digital display.
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
2. SelectLOCfrom the [] key , and confirm by pressing “SEL”.
PV
SV
Table 2.4-2 List of set values
Set values Explanation
Initial value
(Default setting)
Sets LOCAL mode.
Sets DIO mode.
1
Sets SERIAL mode.
2
1:When the setting of the contact input 1 is “External switch signal”, “DIO mode”
cannot be set.
2:If the serial protocol is “Simple communication protocol 2” and the contact input 1 is
“external switch signal” or contact input 2 is “remote signal”, “SERIAL mode” cannot be set.
MENU
Press and
hold
MENU
Press and
hold
MENU
Press and
hold
MENU
Press and
hold
Page 16
HRX-OM-M091
Chapter 2 Contact input/output communication
2.4 Setting and checking HRS Series
2-6
Contact input signal1 Setting and checking
3. Display the screen of contact input signal 1 by pressing the [SEL] key several times.
The set screen of contact input signal 1 is displayed on the digital display.
PV
SV
4. Select contact input signal 1 from the table below with [] key or [] key, and confirm by
pressing “SEL”.
Table 2.4-3 List of set values
Set values Explanation
Initial value
(Default setting)
Without input signal Input of run/Stop signal
External switch signal input(N.O. type)
∗3,∗
4
External switch signal input (N.C. type)
∗3,∗
4
3When the setting of the communication mode is “DIO mode”, “External switch signal”
cannot be set.
4When the setting of the communication mode is “SEIRAL mode” and the protocol
setting is “Simplified communication protocol 2”, “External switch signal” cannot be set.
Contact input signal 1 type Setting and checking
5. Press the [SEL] key once.
The set screen of contact input signal 1 type is displayed on the digital display.
PV
SV
6. Select contact input signal 1 type from the table below with [] key or [] key, and confirm
by pressing “SEL”.
Table 2.4-4 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available if the setting of contact input signal 1 is OFF.
Alternate signal
Momentary signal Momentary signal
5
5Used when the setting of the contact input 1 is “Operation stop signal input”.
Page 17
HRX-OM-M091
Chapter 2 Contact input/output communication
HRS Series 2.4 Setting and checking
2-7
Contact input signal 1 delay timer of reading Setting and checking
7. Press the [SEL] key once.
The set screen of the contact input signal 1 delay timer of reading is displayed on the digital display.
PV
SV
8. Select contact input signal 1 delay timer of reading from the table below with [] key or [▼]
key, and confirm by pressing “SEL”.
Table 2.4-5 List of set value
Set value Explanation
Initial value
(Default setting)
Setting and checking are not available unless contact input signal 1 is external switch signal input (N.O. type or N.C. type).
to
Setting of contact input signal 1 delay timer of reading. Set range is 0 to 300 sec.
Contact input signal 1 OFF detection timer Setting and checking
9. Press the [SEL] key once.
The set screen of the contact input signal 1 OFF detection timer is displayed on the digital display.
PV
SV
10. Select contact input signal 1 OFF detection timer from the table below with [] key or [▼]
key, and confirm by pressing “SEL”.
Table 2.4-6 List of set value
Set value Explanation
Initial value
(Default setting)
Setting and checking are not available unless contact input signal 1 is external switch signal input (N.O. type or N.C. type).
to
Setting of contact input signal 1 OFF detection timer Set range is 0 to 10sec.
Page 18
HRX-OM-M091
Chapter 2 Contact input/output communication
2.4 Setting and checking HRS Series
2-8
Contact input signal 2 Setting and checking
11. Press the [SEL] key once.
The set screen of contact input signal 2 is displayed on the digital display.
PV
SV
12. Select contact input signal 2 from the table below with [] key or [] key, and confirm by
pressing “SEL”.
Table 2.4-7 List of set values
Set values Explanation
Initial value
(Default setting)
Without input signal
Input of run/stop signal External switch signal input(N.O. type) External switch signal input (N.C. type)
Remote signal
6
6When the setting of the serial protocol is “Simplified communication protocol 2”,
“Remote signal” cannot be set.
Contact input signal 2 type Setting and checking
13. Press the [SEL] key once.
The set screen of contact input signal 2 type is displayed on the digital display.
PV
SV
14. Select contact input signal 2 type from the table below with [] key or [] key, and confirm
by pressing “SEL”.
Table 2.4-8 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available if the setting of contact input signal 2 is OFF.
Alternate signal
Momentary signal
7
7:Can be set when the setting of contact input signal 2 is "Run/Stop signal input" or "Remote
signal"
Page 19
HRX-OM-M091
Chapter 2 Contact input/output communication
HRS Series 2.4 Setting and checking
2-9
Contact input signal 2 delay timer of reading Setting and checking
15. Press the [SEL] key once.
The set screen of contact input signal 2 delay timer of reading is displayed on the digital display.
PV
SV
16. Select contact input signal 2 delay timer of reading from the table below with [] key or []
key, and confirm by pressing “SEL”.
Table 2.4-9 List of set values
Set values Explanation
Initial value
(Default setting)
to
Setting of contact input signal 2 delay timer
of reading.
Set range is 0 to 300 sec.
Contact input signal 2 OFF detection timer Setting and checking
17. Press the [SEL] key once.
The set screen of contact input signal 2 OFF detection timer is displayed on the digital display.
PV
SV
18. Select contact input signal 2 OFF detection timer from the table below with [] key or [▼]
key, and confirm by pressing “SEL”.
Table 2.4-10 List of set values
Set values Explanation
Initial value
(Default setting)
Setting and checking are not available unless contact input singal 2 is external switch signal input(N.O. type or N.C. type).
to
Setting of contact input signal 2 OFF
detection timer.
Set range is 0 to 10 sec.
Page 20
HRX-OM-M091
Chapter 2 Contact input/output communication
2.4 Setting and checking HRS Series
2-10
Contact output signal 1 function Setting and checking
19. Press the [SEL] key once.
The set screen of contact output signal 1 function is displayed on the digital display.
PV
SV
20. Select contact output signal 1 function from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 2.4-11 List of set values
Set values Explanation
Initial value
(Default setting)
Without output signal Signal of operating status is output
Signal of remote status is output Signal for completion of preparation (TEMP
READY) Signal for the status of the operation stop alarm is output Signal for the status of the operation continue alarm is output Signal for the alarm status is output
Signal for selected alarm status is output Signal for Run timer set status is output Signal for Stop timer set status is output Signal for the recovery from power failure is
output Signal for anti-freezing setting is output
Pass through signal of contact input signal 1 Pass through signal of contact input signal 2
Signal output during automatic fluid filling
Contact output signal 1 operation Setting and checking
21. Press the [SEL] key once.
The set screen of contact output signal 1 operation is displayed on the digital display.
PV
SV
Page 21
HRX-OM-M091
Chapter 2 Contact input/output communication
HRS Series 2.4 Setting and checking
2-11
22. Select contact output signal 1 operation from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 2.4-12 List of set values
Set values Explanation
Initial value
(Default setting)
N.O type
N.C type
Contact output 1 selected alarm Setting and checking
23. Press the [SEL] key once.
The set screen of digital output 1 selected alarm is displayed on the digital display.
PV
SV
24. Select contact output 1 selected alarm from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 2.4-13 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the function setting of contact output 1 is selected alarm status signal.
to
Sets selection alarm. Set range is AL.01 to AL.36.
Contact output 2 function Setting and checking
25. Press the [SEL] key once.
The set screen of contact output 2 function is displayed on the digital display.
PV
SV
Page 22
HRX-OM-M091
Chapter 2 Contact input/output communication
2.4 Setting and checking HRS Series
2-12
26. Select contact output 2 function from the table below with [] key or [] key, and confirm
by pressing “SEL”.
Table 2.4-14 List of set values
Set values Explanation
Initial value
(Default setting)
Without output signal Signal of operating status is output Signal of remote status is output
Signal for completion of preparation (TEMP READY) Signal for the status of the operation stop alarm is output Signal for the status of the operation continue alarm is output Signal for the alarm status is output
Signal for selected alarm status is output Signal for Run timer set status is output Signal for Stop timer set status is output Signal for the recovery from power failure is
output Signal for anti-freezing setting is output
Pass through signal of contact input signal 1 Pass through signal of contact input signal 2
Signal output during automatic fluid filling
Contact output 2 operation Setting and checking
27. Press the [SEL] key once.
The set screen of contact output 2 operation is displayed on the digital display.
PV
SV
28. Select contact output 2 operation from the table below with [] key or [] key, and confirm
by pressing “SEL”.
Table 2.4-15 List of set values
Set values Explanation
Initial value
(Default setting)
N.O type
N.C type
Page 23
HRX-OM-M091
Chapter 2 Contact input/output communication
HRS Series 2.4 Setting and checking
2-13
Contact output 2 selected alarm Setting and checking
29. Press the [SEL] key once.
The set screen of contact output 2 selected alarm is displayed on the digital display.
PV
SV
30. Select contact output 2 selected alarm from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 2.4-16 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the function setting of contact output 2 is selected alarm status signal.
to
Sets selection alarm. Set range is AL.01 to AL.36.
Contact output 3 function Setting and checking
31. Press the [SEL] key once.
The set screen of contact output 3 function is displayed on the digital display.
PV
SV
Page 24
HRX-OM-M091
Chapter 2 Contact input/output communication
2.4 Setting and checking HRS Series
2-14
32. Select contact output 3 function from the table below with [] key or [] key, and confirm
by pressing “SEL”.
Table 2.4-17 List of set values
Set values Explanation
Initial value
(Default setting)
Without output signal Signal of operating status is output Signal of remote status is output Signal for completion of preparation (TEMP
READY) Signal for the status of the operation stop alarm is output Signal for the status of the operation continue alarm is output Signal for the alarm status is output
Signal for selected alarm status is output Signal for Run timer set status is output Signal for Stop timer set status is output Signal for the recovery from power failure is
output Signal for anti-freezing setting is output
Pass through signal of contact input signal 1 Pass through signal of contact input signal 2
Signal output during automatic fluid filling
Contact output 3 operation Setting and checking
33. Press the [SEL] key once.
The set screen of contact output 3 operation is displayed on the digital display.
PV
SV
34. Select contact output 3 operation from the table below with [] key or [] key, and confirm
by pressing “SEL”.
Table 2.4-18 List of set values
Set values Explanation
Initial value
(Default setting)
N.O type N.C type
Page 25
HRX-OM-M091
Chapter 2 Contact input/output communication
HRS Series 2.4 Setting and checking
2-15
Contact output 3 selected alarm Setting and checking
35. Press the [SEL] key once.
The set screen of contact output 3 selected alarm is displayed on the digital display.
PV
SV
36. Select contact output 3 selected alarm from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 2.4-19 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the function setting of contact output 1 is selected alarm status signal.
to
Sets selection alarm. Set range is AL.01 to AL.36.
Communication mode Setting and checking
37. Press the [SEL] key once.
The set screen of communication mode is displayed on the digital display.
PV
SV
38. Select communication mode【DIOfrom the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 2.4-20 List of set values
Set value Explanation
Initial value
(Default setting)
Sets LOCAL mode.
Sets DIO mode. Sets SERIAL mode.
Page 26
HRX-OM-M091
Chapter 2 Contact input/output communication
2.5 Contact input signal HRS Series
2-16
2.5 Contact input signal
There are two contact input signals. As the default condition, contact input signal 1 is used for run/stop signal (signal type: alternate), and contact input signal 2 is not used. The input signals can be customized depending on the customer’s application.
Table 2.5-1 Contact input signal
Class of signal Signal configuration Timer
Description Display Description Display
Delay timer of reading
OFF
detection
Default setting
Alternate ALT - -
Run/stop signal
RUN
Momentary MT - -
External switch signal input (N.O)
SW_A Alternate ALT Used Used
External switch signal input (N.C)
SW_B Alternate ALT Used Used
Contact input
signal 1
Without intput signal
OFF - -
Alternate ALT - -
Run/stop signal
RUN
Momentary MT - -
External switch signal input (N.O)
SW_A Alternate ALT Used Used
External switch signal input (N.C)
SW_B Alternate ALT Used Used
Alternate ALT - -
Remote signal RMT
Momentary MT - -
Contact input
signal 2
Without input signal
OFF - -
2.5.1 Run/stop signalRemote signal
1) Run/stop signal (Signal type: Alternate)
The product keeps operating while the input signal from the customer is ON.
OFF
ON
Run
Stop
Product condition
Run/stop signal Alternate
2)
Run/stop signal (Signal type: Momentary) The state changes when the input signal from the customer goes OFF. This signal operates while the product is stopped, and stops while the product is being operated. Maintain the ON condition for 300ms or longer.
OFF
ON
Run
Stop
Product condition
Run/stop signal Momentary
300ms 300ms
Page 27
HRX-OM-M091
Chapter 2 Contact input/output communication
HRS Series 2.5 Contact input signal
2-17
3) Remote signal (Signal type: Alternate) The product becomes DIO REMOTE while the input signal from the customer is ON.
OFF
ON
DIO REMOTE
DIO LOCAL
Product condition
Remote signal Alternate
4) Remote signal (Signal type: Momentary)
The state changes when the input signal from the customer goes OFF. If DIO LOCAL is set, it is switched to DIO REMOTE. If DIO REMOTE, it is switched to DIO LOCAL. Maintain the ON condition for 300ms or longer.
OFF
ON
DIO REMOTE
DIO LOCAL
Product condition
Run/stop signal Momentary
300ms 300ms
5) Digital input signal 1 is for Run/Stop signal (Signal type: Alternate), digital input signal 2 is for
external switch signal (N.O. type) Refer to Chapter 2.5.2 for details of the external switch.
OFF
ON
Run
Stop
Product condition
Run/Stop signal
OFF
ON
External switch signal
Delay timer of reading
OFF Detection timer
The product starts operation when the Run/Stop signal from the user is turned on.
It reads the signal of the external switch signal (N.O type) after the time which has been set for
the delay timer of reading.
The factory default setting of the delay timer of reading is 0sec. Refer to 2.4.2 for setting. .
When the external switch signal (N.O. type) has been turned off for the time set for OFF
detection timer, it is recognized as OFF.
The factory default setting of the OFF detection timer is 0sec. Refer to 1.4.2 for setting.
AL32 contact input 2 signal detection alarm is generated. The operation of the product stops.
"Operation stop" is the default setting for AL32. The product can be set to continue operation or not to detect the alarm. Refer to the “Installation / Operation” manual for details.
The product stops operation when the Run/Stop signal is turned off during operation. Afterwards,
the alarm is not generated even if the external switch signal (N.O type) is turned off.
6) Input signal is not connected to either contact input signal 1 or contact input signal 2. This product cannot be controlled by the contact input.
7) Remote signal is connected to either contact input signal 1 or contact input signal 2. This product cannot be controlled by the contact input.
Page 28
HRX-OM-M091
Chapter 2 Contact input/output communication
2.5 Contact input signal HRS Series
2-18
2.5.2 Signal of the external switch
This product can be monitored during operation by reading the signal of the external switch prepared by the customer. The product stops monitoring when it stops operation. This product generates an alarm and stops operating when a problem is detected from the external switch. Select the external switch 1 or 2 or both depending on the customer’s system. Refer to
2.4.2 for setting. The number of monitored external switches depends on the communication mode. Refer to Table 2.5-2 In the communication mode in which the external switches 1 and 2 are available, two products can be monitored simultaneously. If a problem is detected by one or both external switches, an alarm is generated and the operation stops. You can set the product to continue operation or not to detect the alarm. Refer to the “Installation / Operation” manual for details
Table 2.5-2 Cross reference of communication modes and external switch monitoring
DIO SERIAL
Simple
communication
protocol pattern
LOCAL
DIO LOCAL DIO REMOTE MODBUS
1 2
External switch 1
× × ×
External switch 2
Run status of this product
Run
Stop
External switch
CLOSE
OPEN
Operation start
Signal reading
start
Delay timer of reading
OFF detection timer
Alarm
generation
Operation stops due to the alarm.
Fig 2.5-1 Timing chart of external switch monitoring
Delay timer of reading
If the signal of the external switch prepared by the customer is not closed instantly when the product is operated, set the delay timer for reading. By setting this timer, the external switch monitoring starts after the time set by the delay time of reading since the operation start.
“0" is the default setting. Set a time which is suitable for your environment.
Example} When using a flow switch
When operation is started, it takes time for the fluid to reach the piping and the flow
switch to detect the flow. Set the time for the flow switch to start.
OFF detection timer
If you do not want the alarm to be generated instantly when the external switch prepared by the customer is in open status, but instead want the alarm to be generated after the switch has been open for a specific time (continuous open status), set the OFF detection timer.
This timer enables the alarm to be generated when the time set for OFF detection time passes after the switch is in OPEN status.
The default setting is 0 sec. Set a time which is suitable for your application.
Contact input
N.O type or N.C. type can be selected for the external switch. Set the signal which is suitable for the external switch prepared by the customer.
Page 29
HRX-OM-M091
Chapter 2 Contact input/output communication
HRS Series 2.6 Contact output signal
2-19
2.6 Contact output signal
There are three contact output signals. As the default setting, contact output signal 1 is for operating condition (N.O type), contact output signal 2 is for remote signal (N.O type), and contact output signal 3 is for alarm signal (N.C type). Refer to Table 2-6-1. .Depending on the product condition, contact output signal is turned on (closed) or turned off (open).
The signals can be customized depending on the customer’s application. The Table 2.6-2 shows operation of contact output signal.
Tips
All contact output signals are turned off (open) when the power is not supplied.
Table2.6-1 Contact output signal (Default setting)
Class of signal Signal configuration
Description Display Description Display
Remarks
Contact output signal 1 Run status signal RUN
N.O type
A
Contact output signal 2 Remote signal RMT
N.O type
A
Contact output signal 3 Alarm signal ALM
N.C type
B
Non enerationnot set
Generationset
ON
OFF
Digital output signal N.O type
Product condition    (Set condition
ON
OFF
Digital output signal N.C type
Page 30
HRX-OM-M091
Chapter 2 Contact input/output communication
2.6 Contact output signal HRS Series
2-20
Table 2.6-2 Operation of contact output signal
Class of signal
Display Function
Oper ation
Operation of contact output signal
N.O
type
Normally, output signal is OFF (open)
OFF Without output
N.C
type
Normally, output signal is ON (close)
N.O type
When the product operates, signal turns on.
RUN Run status signal
N.C
type
When the product operates, signal turns off.
N.O type
When the product becomes DIO REMOTE, signal turns on.
RMT Remote status signal
N.C
type
When the product becomes DIO LOCAL, signal turns off.
N.O type
When the product becomes completion of preparation (TEMP READY), signal turns on.
RDY
Signal for completion of preparation (TEMP READY)
N.C
type
When the product becomes completion of preparation
(TEMP READY), signal turns off. N.O type
When operation stop alarm occurs, signal turns on.
A.STP
Signal for operation stop alarm
N.C
type
When operation stop alarm occurs, signal turns off. N.O
type
When continuing operation alarm occurs, signal turns on.
A.RUN
Signal for continuing operation alarm
N.C
type
When continuing operation alarm occurs, signal turns off. N.O
type
When alarm occurs, signal turns on.
ALM
Alarm status signal
N.C
type
When alarm occurs, signal turns off. N.O
type
The signal is turned ON when the selected alarm goes off.
A.SEL
Signal for selection alarm
N.C
type
The signal is turned OFF when the selected alarm goes off. N.O
type
The signal is turned ON when the run timer is set.
ON.TM
Signal for operation start timer setting
N.C
type
The signal is turned OFF when the run timer is set. N.O
type
The signal is turned ON when the stop timer is set.
OF.TM
Signal for operation stop timer setting
N.C
type
The signal is turned OFF when the stop timer is set. N.O
type
The signal is turned ON when the power recovery is set.
P. R S T
Signal for power recovery setting
N.C
type
The signal is turned OFF when the power recovery is set. N.O
type
The signal is turned ON when the anti-freezing is set.
F. P.
Signal for anti-freezing setting
N.C
type
The signal is turned OFF when the anti-freezing is set.
N.O type
Outputs the signal which is input to the contact input signal.
Input signal is ON Æ Output signal is ON
INP1. ∗1
Pass through signal of contact input signal 1
N.C
type
Outputs the reverse of the signal which is input to the contact
input signal 2.
Input signal is OFF Æ Output signal is ON N.O
type
Outputs the signal which is input to the contact input signal.
Input signal is ON Æ Output signal is ON
INP2∗1
Pass through signal of contact input signal 2
N.C
type
Outputs the reverse of the signal which is input to the contact
input signal 2. Input signal is OFF Æ Output signal is ON N.O
type
Signal is turned ON during automatic fluid filling.
2
A.F.
Signal output during automatic fluid filling
N.C
type
Signal is turned OFF during automatic fluid filling.
2
1: The signal of the product without an option [Automatic filling] also changes. 2Signal changes even when option J [Automatic fluid filling] is not selected.
Page 31
HRX-OM-M091
Chapter 3 Serial communication
HRS Series 3.1 Precautions wiring communication
3-1
Chapter 3 Serial communication
Serial communication (RS-485/RS232C) enables the remote control of run/start of the product, temperature setting and details of product condition, and alarm condition can be obtained.
The operating state of the product (run/stop) and the temperature setting can be monitored by sending a request message made by the program of the host computer (e.g. PC).
MODBUS communication and simple communication protocol can be selected as the serial communication protocol. This chapter illustrates the common specifications of serial communication. Chapter 4 and 5 illustrate each protocol.
3.1 Precautions wiring communication
Communication wiring
A communication cable that connects the product and customer system is not included with the product. Please prepare a cable, referring to 3.3 ‘’Connected explanation’’ In order to avoid malfunction, do not connect to any place other than those shown in 3.3 ‘’Connected explanation’’.
3.2 Communication specification
Table 3.2-1 Serial communication specification
Item Specification
Connector type (for the product) D-sub9P type Female connector Standard
Select from EIA RS-485/RS-232C
Circuit type Half duplex Half duplex Transmission type Start-stop Protocol
MODBUS terminal
1
Simple communication protocol
Terminal resistance
Select from with terminal resistance(120)/Without terminal resistance
Default setting 1Refer to Modicon Co. protocol specifications "PI-MBUS-300 Rev.J".
Page 32
HRX-OM-M091
Chapter 3 Serial communication
3.3 Connected explanation HRS Series
3-2
3.3 Connected explanation
Fig 3.3-1 shows the wiring when RS-485 is selected as the communication standard. Fig 3.3-2 shows the wiring when RS-232C is selected. A communication cable that connects the product and customer system is not included with the product. Prepare a cable, referring to Fig 3.3-1 or Fig
3.3-2.
1
SD+
5
SG
9
SD-
SD+
SD- SG
Terminal
resistance
Master This product
(first slave)
1
SD+
5
SG
9
SD-
This product
second slave
1
SD+
5
SG
9
SD-
This product
31
st
slaves
Terminal
resistance120Ω
Fig 3.3-1 RS-485 connector connection
Tips
1 master : 1 product, or 1 master: N products.
In the latter case, up to 31 products can be connected.
Both ends of the communication connection (the end nodes) need to be
connected to the higher level computer.
The terminal resistance of this product can be set by the operation display
panel. Refer to ‘’4.3.2 Setting and checking’’,’’5.3.2 Setting and checking’’.
2
3
5
RD
SD
SG
2
3
5
RD
SD
SG
Master This product
Fig 3.3-2 RS-232C connector connection
Page 33
HRX-OM-M091
Chapter 4 MODBUS communication function
HRS Series 4.1 Precautions for communication
4-1
Chapter 4 MODBUS communication
function
MODBUS protocol is a communication protocol developed by Modicon. It is used to communicate with a PC or PLC.
Register content is read and written by this communication protocol.
This communication has the following features.
Controls run/stop.
Sets and reads the circulating fluid set temperature.
Reads the circulating fluid discharge temperature.
Reads the condition of the product.
Reads the alarm generating condition of the product.
Refer to “4.10 Register Map” for the register of the product.
4.1 Precautions for communication
4.1.1 Precautions after wiring and before communication
Check or set the each communication setting by the operation display
panel.
The communication specification shall be the customer’s communication
standard.
The serial protocol shall be the MODBUS.
The communication mode shall be the SERIAL mode.
Other modes can perform reading, but only SERIAL mode can perform writing.
Check or set the communication parameters using the operation display panel.
Check or set the communication speed so that the product synchronizes with the host computer (master) prepared by the customer.
Check the slave address by the operation display panel.
No response is returned when a request message is sent from a slave address other than those set in the product.
Page 34
HRX-OM-M091
Chapter 4 MODBUS communication function
4.2 Communication specification HRS Series
4-2
4.1.2 Precautions for communicating
Allow a suitable interval between requests.
To send request messages in series, wait for 100 msec. or longer after receiving a response message from the product before sending the next message.
Retry (resend request message).
The response may not be returned due to noise. If no message is returned 1sec. after sending a request message, resend the request message.
If necessary send a read request message to check if it was written correctly.
Message to notify the completion of the process is returned when the action for the written request message is completed.
Send a read request message to confirm if the setting was written as requested.
Setting limit of circulating fluid temperature
When the circulating fluid set temperature is written by communication, the data is stored in FRAM. When the product restarts, it restarts with the value which was set before the restart. The number of times it is possible to overwrite FRAM is limited. Data is only stored in FRAM when it receives a circulating fluid set temperature which is different from the previous temperatures. Please check how many times it is possible to overwrite FRAM, and avoid unnecessary changes of the circulating fluid set temperature during communication
4.2 Communication specification
Table 4.2-1 Communication specification of MODBUS communication function
Item Specification
Standard
Select from EIA RS-485/RS-232C
Communication speed
Select from 9600bps/19200bps
Databit length
7bit
Stopbit length
1bit
Data transfer direction LSB Parity Even parity Letter code ASCII mode Slave address set range Select from 1 to 99 address Error check LRC method
Default setting
Page 35
HRX-OM-M091
Chapter 4 MODBUS communication function
HRS Series 4.3 Setting and checking
4-3
4.3 Setting and checking
4.3.1 Setting and checking items
The table below explains the setting items of the MODBUS communication function and the initial values.
Table 4.3-1 Communication setting items
Display Item Contents
Initial value
(Default setting)
Communication mode Sets communication mode of this product. LOC Serial protocol Sets serial communication protocol. MDBS Communication specification
Sets standard of the serial communication. 485
RS-485 terminal Sets of the terminal of RS-485. OFF
Slave address (MODBUS)
Sets slave address of MODBUS protocol. [----] is displayed when the setting of serial protocol is not MODBUS.
1
Communication speed (MODBUS)
Sets communication speed of MODBUS protocol. [----] is displayed when the setting of serial protocol is not MODBUS.
19.2
Page 36
HRX-OM-M091
Chapter 4 MODBUS communication function
4.3 Setting and checking HRS Series
4-4
4.3.2 Setting and checking
Communication Setting and checking
1. Press and hold the [MENU] key for 2 sec.
Repeat pressing the key until the setting screen for communication mode [
] appears
on the digital display.
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
2. Select “SER” from the table below with the key, and confirm with “SEL”.
PV
SV
Table 4.3-2 List of set values
Set values Explanation
Initial value
(Default setting)
Sets LOCAL mode.
Sets DIO mode. Sets SERIAL mode.
1
1:If the serial protocol is “Simple communication protocol 2” and the contact input 1 is
“external switch signal” or contact input 2 is “remote signal”, “SERIAL mode” cannot be set.
Serial protocol Setting and checking
3. Press the [SEL] key once.
The set screen of serial protocol is displayed on the digital display.
PV
SV
MENU
Press and
hold
MENU
Press and
hold
MENU
Press and
hold
MENU
Press and
hold
Page 37
HRX-OM-M091
Chapter 4 MODBUS communication function
HRS Series 4.3 Setting and checking
4-5
4. Select serial protocol from the table below with [] key or [] key, and confirm by pressing
“SEL”.
Table 4.3-3 List of set values
Set values Explanation
Initial value
(Default setting)
MODBUS protocol
Simple communication protocol 1 Simple communication protocol 2
2
2:When the setting of the contact input 2 is “Remote signal”, “Simplified
communication protocol 2” cannot be set.
Communication specification Setting and checking
5. Press the [SEL] key once.
The set screen of communication specification is displayed on the digital display.
PV
SV
6. Select communication specification from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 4.3-4 List of set values
Set values Explanation
Initial value
(Default setting)
RS-232C standard RS-485 standard
RS-485 terminal Setting and checking
7. Press the [SEL] key once.
The set screen of RS-485 terminal is displayed on the digital display.
PV
SV
8. Select RS-485 terminal from the table below with [] key or [] key, and confirm by
pressing “SEL”.
Table 4.3-5 List of set values
Set values Explanation
Initial value
(Default setting)
Without terminal
With terminal
Page 38
HRX-OM-M091
Chapter 4 MODBUS communication function
4.3 Setting and checking HRS Series
4-6
Slave addresses(MODBUS)Setting and checking
9. Press the [SEL] key once.
The set screen of slave addresses (MODBUS) is displayed on the digital display.
PV
SV
10. Select slave addresses (MODBUS) from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 4.3-6 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the serial protocol setting is MODBUS.
to
Sets of slave addresses for MODBUS. Set range is 1 to 99.
Communication speed(MODBUS)Setting and checking
11. Press the [SEL] key once.
The set screen of communication speed (MODBUS) is displayed on the digital display.
PV
SV
12. Select communication speed (MODBUS) from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 4.3-7 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the serial protocol setting is MODBUS.
9600bps
19200bps
Page 39
HRX-OM-M091
Chapter 4 MODBUS communication function
HRS Series 4.4 Communication sequence
4-7
4.4 Communication sequence
Starts with a request message from the customer’s system (host), and
finishes with a response message from the product (slave). This product
operates as a slave. It does not send any requests.
Positive response
Based on the request message, reads
register/writes register and returns a positive
response.
Negative response
Returns a negative message when the received
request message is not normal. Refer to ‘’4.9
Negative response’’.
No response
No response is returned when there is an error in
“slave address specification” or ”LRC”.
Customer's system
(host)
This product
(slave)
R
e
q
u
e
s
t
m
e
s
s
a
g
e
P
o
s
i
t
i
v
e
r
e
s
p
o
n
s
e
R
e
q
u
e
s
t
m
e
s
s
a
g
e
N
e
g
a
t
i
ve
r
e
s
p
o
n
s
e
R
e
q
u
e
s
t
m
e
s
s
a
g
e
No response
10200ms
R
e
s
p
o
n
s
e
m
e
s
s
a
g
e
R
e
s
p
o
n
s
e
m
e
s
s
a
g
e
Page 40
HRX-OM-M091
Chapter 4 MODBUS communication function
4.5 Message configuration HRS Series
4-8
4.5 Message configuration
4.5.1 Message format
The message configuration is shown below. This product communicates in ASCII mode. ASCII mode is used from Start to End.
1) 2) 3) 4) 5) 6)
Start Slave Address Function Data LRC End
[:] XX XX XX XX XX
XX XX XX [CR] [LF]
1) Start
The start of the message. [:](3Ah)
2) Slave Address1 to 99 3031h to 3939h
This is a number to identify this product. “1" is the default setting. This can be changed by the operation display panel.
3) Function (Refer to ‘’4.6 Function codes’’.)
Command is assigned.
4) Data
Depending on the function, the address and the number of the register, the value of reading/writing are assigned.
5) LRC
LRC method
Refer to ‘’4.7 LRC’’.
6) END
The end of the message. [CR](0Dh)+[LF](0Ah)
A response message will not be returned unless the request includes [:] and [CR][LF]. This product clears all previously received code when [:] is received.
Page 41
HRX-OM-M091
Chapter 4 MODBUS communication function
HRS Series 4.5 Message configuration
4-9
The communication example is expressed in hexadecimal value with [ ]. The actual communication is performed in ASCII code. Refer to the request / response message in this section.
4.5.2 Message example
The example shows communication with the conditions below.
Slave AddressNo.1 Read seven consecutive data from register 0000h.
(Read circulating fluid discharge temperature.)
Communication example
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address 03 Function 03 Function 0000
Head address of specified register
02
Quantity of bytes to read
0001
Quantity of register to read
00EE
Information of 0000h (circulating fluid discharge temperature: 23.8
o
C)
FB
LRC
0C LRC
Request message (Master to Slave)
Start Slave Address Function Data LRC End
3A 30 31 30 33 46 42 0D 0A
Read Address Quantity to Read
Hi Lo Hi Lo
30 30 30 30 30 30 30 31
Response message (Slave to Master)
Start Slave Address Function Data LRC End
3A 30 31 30 33 30 43 0D 0A
Read Data1
Byte Count
Hi Lo
30 32 30 30 45 45
This product
(Request): 010300000001FB [CR][LF]
(Response): 01030200EE0C [CR][LF]
Your system
Data is sent and received in ASCII code.
Page 42
HRX-OM-M091
Chapter 4 MODBUS communication function
4.6 Function codes HRS Series
4-10
4.6 Function codes
Table 4.6-1 shows function codes to read or write register.
Table 4.6-1 Function codes
NO Code Name Function
1 03(03h) Read holding registers Reading multiple registers 2 06(06h) Preset single register
Writing registers
1
3 16(10h) Preset multiple registers Writing multiple registers 4 23(17h) Read/write 4x registers Reading/writing multiple registers
1Broadcast is not supported.
4.7 LRC
LRC checks the content of the message other than [:] of START and [CR][LF] of END. The sending side calculates and sets. The receiving side calculates based on the received message, and compares the calculation result with the received LRC. The received message is deleted if the calculation result and received LRC do not match.
Add up the byte number of the message consisting of 8 consecutive bits. The result except the carry (overflow) is converted to 2’s complement.
Calculation example
LRC message for calculation ]0106000B00FE Calculation
Addition 01h06h00h0Bh+00h+FEh110h Object 110h10h complement of 2 10hEFhF0h
LRC is F0h
Sending message [:]0106000B00FEF0[CR][LF]
Page 43
HRX-OM-M091
Chapter 4 MODBUS communication function
HRS Series 4.8 Explanation of function codes
4-11
4.8 Explanation of function codes
4.8.1 Function code03 Reading multiple registers
Register data of assigned points from assigned address is read.
Request message <Normal> (Master to Slave)
Start Slave Address Function Data LRC End
[:] XX XX [0] [3] XX XX [CR] [LF]
Read Address Quantity to Read
Hi Lo Hi Lo
XX XX XX XX XX XX XX XX
Response message<Normal> (Slave to Master)
Start Slave Address Function Data LRC End
[:] XX XX [0] [3] XX XX [CR] [LF]
Read Data1 Read Data n
Byte Count
Hi Lo Hi Lo
XX XX XX XX XX XX XX XX XX XX
Communication example
Slave Address: No.1 Read seven consecutive data from register 0000h.
(Read circulating fluid discharge temperature, circulating fluid discharge
pressure, status information, alarm information.)
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address 03 Function 03 Function 0000 Head address of specified register 0E Quantity of bytes to read
0007 Quantity of register to read 00D4
Information of 0000h (circulating fluid discharge temperature)
F5 LRC 0000 Information of 0001h (Reserved)
000D
Information of 0002h (circulating fluid
discharge pressure) 0000 Information of 0003h (Reserved) 0201 Information of 0004h (Status flag) 0000 Information of 0005h (Alarm flag 1) 0000 Information of 0006h (Alarm flag 2) 0A LRC
This product
(Request):010300000007F5 [CR][LF]
(Response):01030E00D40000000D00000201000000000A [CR][LF]
Your system
Data is sent and received in ASCII code.
Page 44
HRX-OM-M091
Chapter 4 MODBUS communication function
4.8 Explanation of function codes HRS Series
4-12
4.8.2 Function code06 Writing registers
Write data to assigned address.
Request message <Normal> (Master to Slave)
Start Slave Address Function Data LRC End
[:] XX XX [0] [6] XX XX [CR] [LF]
Write Address Write Data
Hi Lo Hi Lo
XX XX XX XX XX XX XX XX
Response message <Normal> (Slave to Master)
Start Slave Address Function Data LRC End
[:] XX XX [0] [6] XX XX [CR] [LF]
Write Address Write Data
Hi Lo Hi Lo
XX XX XX XX XX XX XX XX
Communication example
Slave Address: No 1
Write data to register 000Ch
(Commands to run)
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address 06 Function 06 Function 000C Address of specified register 000C Address of register to write 0001 Information written to 000Ch (Stop flag) 0001 Information of register to write EC LRC EC LRC
This product
(Request):0106000C0001EC [CR][LF]
(Response):0106000C0001EC [CR][LF]
Your system
Data is sent and received in ASCII code.
Page 45
HRX-OM-M091
Chapter 4 MODBUS communication function
HRS Series 4.8 Explanation of function codes
4-13
4.8.3 Function code16 Writing multiple registers
Register content of assigned points of assigned address is written.
Request message <Normal> (Master to Slave)
Start Slave Address Function Data LRC End
[:] XX XX [1] [0] XX XX [CR] [LF]
Write Address Quantity to Write
Hi Lo Hi Lo
XX XX XX XX XX XX XX XX
Write Data1 Write Data n
Byte Count
Hi Lo Hi Lo
XX XX XX XX XX XX XX XX XX XX
Response message <Normal> (Slave to Master)
Start Slave Address Function Data LRC End
[:] XX XX [1] [0] XX XX [CR] [LF]
Write Address Quantity to Write
Hi Lo Hi Lo
XX XX XX XX XX XX XX XX
Communication example
Slave Address: No 1 Write two consecutive data from register 000Bh.
(Commands to change of circulating fluid set temperature <39.9
o
C > and run.)
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address 10 Function 10 Function 000B Head address of specified register 000B Head address of register to write 0002 Quantity of register to write 0002 Quantity of register to write 04 Quantity of byte to read E2 LRC 018F Information written to 000Bh (Circulating
fluid set temperature) 0001 Information written to 000Ch (Stop flag) 4D LRC
(Request):0110000B000204018F00014D [CR][LF]
(Response):0110000B0002E2 [CR][LF]
Your system This product
Data is sent and received in ASCII code.
Page 46
HRX-OM-M091
Chapter 4 MODBUS communication function
4.8 Explanation of function codes HRS Series
4-14
4.8.4 Function code23 Reading/writing multiple registers
Register content of assigned points of assigned address is read. Write the register data from the specified address with specified points simultaneously.
Request message <Normal> (Master to Slave)
Start Slave Address Function Data LRC End
[:] XX XX [1] [7] XX XX [CR] [LF]
Read Address Quantity to Read Write Address Quantity to Write
Hi Lo Hi Lo Hi Lo Hi Lo
XX XX XX XX XX XX XX XX XX XX XX XX XX XX XX XX
Write Data1 Write Data n
Byte Count
Hi Lo Hi Lo
XX XX XX XX XX XX XX XX XX XX
Response message <Normal> (Slave to Master)
Start Slave Address Function Data LRC End
[:] XX XX [1] [7] XX XX [CR] [LF]
Read Data1 Read Data n
Byte Count
Hi Lo Hi Lo
XX XX XX XX XX XX XX XX XX XX
Page 47
HRX-OM-M091
Chapter 4 MODBUS communication function
HRS Series 4.8 Explanation of function codes
4-15
Communication example
Slave Address: No 1
Read three consecutive data from register 0004h, and write two
consecutive data from register 000Bh.
(Command to change the circulating fluid set temperature to <15.5
o
C>,
and read status and alarm information.)
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address 17 Function 17 Function 0004 Head address of specified register 06 Quantity of byte to read 0003 Quantity of register to read 0000
Information of 0004h (Status flag
000B Head address of specified register 0000 Information of 0005h (Alarm flag 1) 0002 Quantity of register to write 0000 Information of 0006h (Alarm flag 2) 04 Quantity of byte to write E2 LRC
009B
Information written to 000Bh (Circulating
fluid set temperature) 0001 Information written to 000Ch (Stop flag) 34 LRC
(Request):011700040003000B000204009B000134 [CR][LF]
(Response):011706000000000000E2 [CR][LF]
Your system This product
Data is sent and received in ASCII code.
Page 48
HRX-OM-M091
Chapter 4 MODBUS communication function
4.9 Negative response HRS Series
4-16
4.9 Negative response
A negative response is returned when the following request message is received.
1) When unspecified function code is used.
2) An address out of range is specified.
3) The data field is not normal.
Negative response message (Slave to Master)
1) 2) Start Slave Address Function Error Code LRC End
[:] XX XX [0] [3] XX XX XX XX [CR] [LF]
1) Function
Assign the value consisting of the request function code (hexadecimal value) plus 80h in ASCII code.
2) Error Code
Assign error code below.
01Function code of a command is outside the standard
02The specified address of register is outside the range.
03Data field of a command is not normal.
Communication example
Slave Address: No 1
Read seven consecutive data from register 0100h which is out of range.
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address 03 Function 83 Function (03h+80h)
0100 Head address of register out of range 02
Error Code (Specified register address is
out of range.) 0007 Quantity of register to read 7A LRC F4 LRC
This product
(Request):010301000007F4 [CR][LF]
(Response):0183027A [CR][LF]
Your system
Data is sent and received in ASCII code.
Page 49
HRX-OM-M091
Chapter 4 MODBUS communication function
HRS Series 4.10 Register Map
4-17
4.10 Register Map
Bit Format
Address
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
R/W
-110.0 to 150.0oC = FBB4h to 5DCh (0.1 oC /dig
0000h
Circulating fluid discharge temperature
-166.0 to 302.0
o
F = F984h to BCCh (0.1 oF /dig
0001h Reserved
0.00 to 3.00MPa = 0h to 12Ch (0.01MPa/dig
0002h
Circulating fluid discharge pressure
0 to 435PSI = 0h to 1B3h (1PSI/dig)
0003h
Electric
resistivity of the
circulating fluid
0 to 4.5MΩ・cm=0h to 2dh(0.1MΩ・cm /dig
0004h Status flag
0005h Alarm flag 1
0006h Alarm flag 2
0007h Alarm flag 3
0008h Reserved
0009h Reserved
000Ah Reserved
R
5.0 to 40.0 oC = 32h to 190h (0.1 oC /dig
000Bh
Circulating fluid set temperature
41.0 to 104.0
o
F = 19Ah to 410h (0.1 oF /dig
000Ch Reserved
1
000Dh Reserved
000Eh Reserved
000Fh Reserved
R/W
1Commands to run
4.10.1 Circulating fluid discharge temperature
Read the circulating fluid discharge temperature in the selected temperature unit (°C or °F). Read the circulating fluid discharge temperature which is displayed on the operation display panel PV. (Offset temperature is displayed if offset function is set).
4.10.2 Circulating fluid discharge pressure
Read the circulating fluid discharge pressure in the selected pressure unit (MPa or PSI).
4.10.3 Electric resistivity of the circulating fluid
Electric resistivity (DI level) of the circulating fluid is informed. The value is 0 MΩ・cm when the optional [Electric resistivity sensor] is invalid.
Page 50
HRX-OM-M091
Chapter 4 MODBUS communication function
4.10 Register Map HRS Series
4-18
4.10.4 Status flag
The status of the product is read by the following assignment.
Name Status flag
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit Name Explanation
0 Run flag
Run status (Include the independent operation of the pump) 0= Stop 1=Run
1 Operation stop alarm flag
Operation stop alarm given off status 0= Not occurred 1= Operation stop alarm given off
2
Operation continued alarm flag
Operation continued alarm given off status 0= Not occurred 1= Operation continued alarm
given off
3 Unused
4 Press Unit flag
Pressure unit set status 0=MPa 1=PSI
5 Remote status flag
Remote status 0= Other than SERIAL mode 1=SERIAL mode
6 Unused 7 Unused 8 Unused
9
Completion of preparation (TEMP READY) flag
Completion of preparation (TEMP READY) status 0= Condition isn’t formed 1= Condition is formed
10 Temperature unit flag
Temperature unit set status 0= Centigrade
o
C1= FahrenheitoF
11 Run timer flag
Run timer set status 0=Not set 1= Set
12 Stop timer flag Stop timer set status 0= Not set 1=Set
13 Reset after power failure flag
Reset after power failure set status 0= Not set 1= Set
14 Anti-freezing flag
Anti-freezing set status 0= Not set 1= Set
15 Automatic fluid filling flag
Automatic fluid filling condition 0= Stop 1= Fluid
The signal of the product without an option
[Automatic filling] also changes.
Page 51
HRX-OM-M091
Chapter 4 MODBUS communication function
HRS Series 4.10 Register Map
4-19
4.10.5 Alarm flag
Each type of alarm which occurs in the product is read with the following assignment.
Name Alarm flag 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Name Alarm flag 2
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Name Alarm flag 3
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit Name Explanation
0 Low level in tank 1
High circulating fluid discharge temp.
2
Circulating fluid discharge temp. rise
3
Circulating fluid discharge temp.
4
High circulating fluid return temp.
5
High circulating fluid discharge pressure
6
Abnormal pump operation
7
Circulating fluid discharge pressure rise
8
Circulating fluid discharge pressure drop
9
High compressor intake temp.
10
Low compressor intake temp.
11
Low super heat temperature
12
High compressor discharge pressure
13
Unused
14
Refrigerant circuit pressure (high pressure side) drop
Alarm flag 1
15
Refrigerant circuit pressure (low pressure side) rise
0
Refrigerant circuit pressure (low pressure side) drop
1
Compressor overload
2
Communication error
3
Memory error
4
DC line fuse cut
5
Circulating fluid discharge temp. sensor failure
6
Circulating fluid return temp. sensor failure
7
Compressor intake temp. sensor failure
8
Circulating fluid discharge pressure sensor failure
9
Compressor discharge pressure sensor failure
10
Compressor intake pressure sensor failure
11
Maintenance of pump
12
Maintenance of fan motor
13
Maintenance of compressor
14 Contact input 1 signal detection alarm
Alarm flag 2
15 Contact input 2 signal detection alarm
Alarm given off status 0= Not occurred 1= Occurred
Page 52
HRX-OM-M091
Chapter 4 MODBUS communication function
4.10 Register Map HRS Series
4-20
Bit Name Explanation
0 Water leakage 1 DI level rise 2 DI level drop 3 DI sensor error 4 Unused 5 Unused 6 Unused 7 Unused 8 Unused 9 Unused 10 Unused 11 Unused 12 Unused 13 Unused 14 Unused
Alarm flag 3
15 Unused
Alarm given off status 0= Not occurred 1= Occurred
The current alarm flag bit assignment will be changed in the future due to the addition of
optional functions.
Unused bit is fixed to 0.
Page 53
HRX-OM-M091
Chapter 4 MODBUS communication function
HRS Series 4.10 Register Map
4-21
4.10.6 Circulating fluid set temperature
The circulating fluid set temperature can be set by specifying the circulating fluid set temperature with the selected temperature unit (°C or °F) during SERIAL mode.
If the temperature exceeds the upper limit of the circulating fluid set temperature range, the circulating fluid set temperature is changed to the upper limit value. If it is lower than the lower limit, the circulating fluid set temperature is changed to the lower limit value.
4.10.7 Operation Start Command
The operation can be controlled by sending the operation start command during SERIAL mode.
0=Run stop 1=Run start
Page 54
HRX-OM-M091
Chapter 4 MODBUS communication function
4.10 Register Map HRS Series
4-22
Page 55
HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series 5.1 Precautions for communication
5-1
Chapter 5 Simple communication
protocol function
Data can be read / written by this communication protocol. This protocol complies with SMC thermo-cooler HRG, HRGC series.
This communication has the following features.
Sets and reads the circulating fluid set temperature.
Reads the circulating fluid discharge temperature.
5.1 Precautions for communication
5.1.1 Precautions after wiring and before communication
Check or set each communication setting by the operation display panel.
The communication specification shall be the customer’s communication
standard.
The serial protocol shall be the simple communication protocol 1 or 2.
Simple communication protocol 1Operation display panel controls
the start and stop of the product.
Simple communication protocol 2Controls the start and stop of the
product remotely.
Refer to chapter 2.4 for remote setting when this protocol is selected.
The communication mode shall be the SERIAL mode.
Other modes can perform reading, but only SERIAL mode can perform writing of values.
Check or set the communication parameters using the operation display panel.
Check or set the communication speed, the presence of BCC, data length, parity check, stop bit length, response delay time, and communication range (RO or RW) to synchronize the product with the host computer (master) prepared by the customer.
Check the slave address of this product.
No response is returned when a request message is sent from a slave address other than those set in the product.
Page 56
HRX-OM-M091
Chapter 5 Simple communication protocol function
5.1 Precautions for communication HRS Series
5-2
5.1.2 Precautions for communicating
Check the data digit number and the decimal point location when requesting to write the set value.
Allow a suitable interval between requests.
To send request messages in series, wait for 100msec. or longer after receiving a response message from the product before sending the next message.
No response is returned for a request message of a command which is not supported by the product.
Retry (resend request message).
The response may not be returned due to noise. If no message is returned after 1sec. of sending a request message, resend the request message.
If necessary send a read request message to check if it was written correctly.
Message to notify the completion of the process is returned when the action for the written request message is completed.
5.1.3 Precautions after the completion of the communication
Send the data storage request (STR) if necessary.
Data which is set by communication is stored in RAM. Set values stored in RAM are deleted when the power supplied to the product is cut. When the power is supplied again, operation starts with the values set before communication (values stored in FRAM of the product).
Store the values set by communication in FRAM (rewrite FRAM) by sending a data storage request message (STR) before cutting the power supply to the product.
Please check how many times it is possible to write to FRAM, and avoid unnecessary rewriting of the data during communication
Page 57
HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series 5.2 Communication specification
5-3
5.2 Communication specification
Table 5.2-1 Communication specification of simple communication protocol
Item Specification
Standard Select from EIA RS-485/RS-232C Communication speed Select from 1200bps/2400bps/4800bps/9600bps/19200bps Databit length
Select from 7bit/8bit
Stopbit length Select from 1bit2bit Parity Select from without parity ,odd number ,even number Letter code ASCII mode Slave address set range Select from 1 to 99 Response delay time setting Select from 0 to 250[msec]
Communication range
RO(Can read data only), Select from RW(can read and write data)
BCC Select from with BCC , without BCC
Error check
EXOR algorithm of all data from STX to ETX is read only when BCC is selected.
Default setting
Page 58
HRX-OM-M091
Chapter 5 Simple communication protocol function
5.3 Setting and checking HRS Series
5-4
5.3 Setting and checking
5.3.1 Setting and checking items
The table below explains the setting items of the simple communication protocol function and the initial values.
Table 5.3-1 Communication setting items
Display Item Contents
Initial value
(Default setting)
Communication mode Sets communication mode. LOC Serial protocol Sets serial communication protocol. MDBS
Communication specification
Sets standard of the serial communication.
485
RS-485 terminal Sets of the terminal of RS-485. OFF Slave address (Simple communication protocol)
Sets slave address of simple communication protocol. [----] is displayed when the setting of serial protocol is not simple communication protocol.
1
Communication speed (Simple communication protocol)
Sets communication speed of simple communication protocol. [----] is displayed when the setting of serial protocol is not simple communication protocol.
9.6
BCC (Simple communication protocol)
Sets error detection code of communication of simple communication protocol. [----] is displayed when the setting of serial protocol is not simple communication protocol.
ON
Data length (Simple communication protocol)
Sets data length. [----] is displayed when the setting of serial protocol is not simple communication protocol.
8BIT
Parity check (Simple communication protocol)
Sets parity check. [----] is displayed when the setting of serial protocol is not simple communication protocol.
NON
Stop bit length (Simple communication protocol)
Sets bit length. [----] is displayed when the setting of serial protocol is not simple communication protocol.
2BIT
Response delay time (Simple communication protocol)
Sets time to delay the response message of simple communication protocol. [----] is displayed when the setting of serial protocol is not simple communication protocol.
0
Communication range (Simple communication protocol)
Sets communication range of simple communication protocol. [----] is displayed when the setting of serial protocol is not simple communication protocol.
RW
Page 59
HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series 5.3 Setting and checking
5-5
5.3.2 Setting and checking
Communication mode Setting and checking
1. Press and hold the [MENU] key for 2 sec.
Repeat pressing the key until the setting screen for communication mode [
] appears
on the digital display.
PV
SV
PV
SV
PV
SV
PV
SV
PV
SV
2. Select “SER” from the table below with the [] key, and confirm with “SEL”.
PV
SV
Table 5.3-2 List of set values
Set values Explanation
Initial value
(Default setting)
Sets LOCAL mode
Set s DIO mode Sets SERIAL mode
1
1If the serial protocol is “Simple communication protocol 2” and the contact input 1 is
“external switch signal” or contact input 2 is “remote signal”, “SERIAL mode” cannot be set.
Serial protocol Setting and checking
3. Press the [SEL] key once.
The set screen of serial protocol is displayed on the digital display.
PV
SV
MENU
Press and
hold
MENU
Press and
hold
MENU
Press and
hold
MENU
Press and
hold
Page 60
HRX-OM-M091
Chapter 5 Simple communication protocol function
5.3 Setting and checking HRS Series
5-6
4. Select serial protocol from the table below with [] key or [] key, and confirm by pressing
“SEL”.
Table 5.3-3 List of set values
Set values Explanation
Initial value
(Default setting)
MODBUS protocol
Simple communication protocol Simple communication protocol 2
∗2,∗
3
2 When the setting of the contact input 2 is “Remote signal”, “Simplified
communication protocol 2” cannot be set.
3Refer to chapter 2.4 for remote setting when the communication mode is SERIAL and the
simple communication protocol 2 is selected as the serial protocol.
Communication specification Setting and checking
5. Press the [SEL] key once.
The set screen of communication specification is displayed on the digital display.
PV
SV
6. Select communication specification from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 5.3-4 List of set values
Set values Explanation
Initial value
(Default setting)
RS-232C Standard RS-485 Standard
RS-485 terminal Setting and checking
7. Press the [SEL] key once.
The set screen of RS-485 terminal is displayed on the digital display.
PV
SV
8. Select RS-485 terminal from the table below with [] key or [] key, and confirm by
pressing “SEL”.
Table 5.3-5 List of set values
Set values Explanation
Initial value
(Default setting)
Without terminal
With terminal
Page 61
HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series 5.3 Setting and checking
5-7
Slave addressessimple communication protocol Setting and checking
9. Press the [SEL] key 3 times.
The set screen of slave addresses (simple communication protocol) is displayed on the digital display.
PV
SV
10. Select slave addresses (simple communication protocol) from the table below with [] key
or [] key, and confirm by pressing “SEL”.
Table 5.3-6 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the serial protocol setting is simple communication protocol.
to
Sets of slave addresses for simple communication protocol. Set range is 1 to 99.
Communication speed (simple communication protocol) Setting and checking
11. Press the [SEL] key once.
The set screen of communication speed (simple communication protocol) is displayed on the digital display.
PV
SV
12. Select communication speed (simple communication protocol) from the table below with
[] key or [] key, and confirm by pressing “SEL”.
Table 5.3-7 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the serial protocol setting is simple communication protocol.
1200bps 2400bps 4800bps 9600bps
19200bps
Page 62
HRX-OM-M091
Chapter 5 Simple communication protocol function
5.3 Setting and checking HRS Series
5-8
BCCsimple communication protocol Setting and checking
13. Press the [SEL] key once.
The set screen of BCC (simple communication protocol) is displayed on the digital display.
PV
SV
14. Select BCC (simple communication protocol) from the table below with [] key or [] key,
and confirm by pressing “SEL”.
Table 5.3-8 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the serial protocol setting is simple communication protocol. Without BCC
With BCC
Data length (simple communication protocol) Setting and checking
15. Press the [SEL] key once.
The set screen of data length (simple communication protocol) is displayed on the digital display.
PV
SV
16. Select data length (simple communication protocol) from the table below with [] key or
[] key, and confirm by pressing “SEL”.
Table 5.3-9 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the serial protocol setting is simple communication protocol.
7 bit 8 bit
Page 63
HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series 5.3 Setting and checking
5-9
Parity check (simple communication protocol) Setting and checking
17. Press the [SEL] key once.
The set screen of parity check (simple communication protocol) is displayed on the digital display.
PV
SV
18. Select parity check (simple communication protocol) from the table below with [] key or
[] key, and confirm by pressing “SEL”.
Table 5.3-10 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the serial protocol setting is simple communication protocol.
None
Odd number
Even number
Stop bitsimple communication protocol Setting and checking
19. Press the [SEL] key once.
The set screen of stop bit (simple Communication protocol) is displayed on the digital display.
PV
SV
20. Select stop bit (simple communication protocol) from the table below with [] key or [▼]
key, and confirm by pressing “SEL”.
Table 5.3-11 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the serial protocol setting is simple communication protocol. 1 bit
2 bit
Page 64
HRX-OM-M091
Chapter 5 Simple communication protocol function
5.3 Setting and checking HRS Series
5-10
Response delay time (simple communication protocol) Setting and checking
21. Press the [SEL] key once.
The set screen of response delay time (simple communication protocol) is displayed on the digital display.
PV
SV
22. Select response delay time (simple communication protocol) from the table below with []
key or [] key, and confirm by pressing “SEL”.
Table 5.3-12 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the serial protocol setting is simple communication protocol.
to
Sets of response delay time Set range is 0 to 250m sec.
Communication range (simple communication protocol) Setting and checking
23. Press the [SEL] key once.
The set screen of communication range (simple communication protocol) is displayed on the digital display.
PV
SV
24. Select communication range (simple communication protocol) from the table below with [▲]
key or [] key, and confirm by pressing “SEL”.
Table 5.3-13 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available unless the serial protocol setting is simple communication protocol. Only reading is available
Reading and writing are available
Page 65
HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series 5.4 Communication sequence
5-11
5.4 Communication sequence
Starts with a request message from the customer’s system (host), and finishes with a response message from the product (slave). This product operates as a slave. It does not send any requests.
Positive response Based on the request message, reads/writes return a positive response.
.
Negative response
Returns a negative message when the
received request message is not normal.
Refer to “5.9 Negative response’’.
No response No response is returned when the slave address is specified or a command which is not supported is received.
Your system
Master
This product
Slave
R
e
q
u
e
s
t
m
e
s
s
a
g
P
o
s
i
t
i
v
e
r
e
s
p
o
n
s
e
R
e
q
u
e
s
t
m
e
s
s
a
g
N
e
g
a
t
i
ve
r
e
s
p
o
n
s
e
R
e
q
u
e
s
t
m
e
s
s
a
g
No response
0 to 250ms Response delay time
N
e
g
a
t
i
ve
m
e
ss
a
g
e
N
e
g
a
t
i
ve
m
e
s
s
a
g
e
10 to 200ms
Page 66
HRX-OM-M091
Chapter 5 Simple communication protocol function
5.5 Message configuration HRS Series
5-12
5.5 Message configuration
The message configuration is shown in the following. The explanation of data in message is shown in the Table 5.5-1.
This product communicates in ASCII mode. ASCII mode is used from STX to ETX. Hexadecimal value is used for BCC.
5.5.1 Message format
1) Request message format 1-1) Request message (Request to read)
STX Slave Address Request Command ETX BCC
[STX]
XX XX
[R]
XX XX XX
[ETX]
XX
1-2) Request message (Request to write)
STX Slave Address Request Command Writing data ETX BCC
[STX]
XX XX
[W]
XX XX XX XX XX XX XX XX
[ETX]
XX
1-3) Request message (Request to store the data
STX Slave Address Request Command ETX BCC
[STX]
XX XX
[W]
XX XX XX
[ETX]
XX
2) Response message format 2-1) Response message (Normal response to request to write)
STX Slave Address ACK Command Reading data ETX BCC
[STX]
XX XX
[ACK]
XX XX XX XX XX XX XX XX
[ETX]
XX
2-2) Response message (Normal response to request to write or store the data)
STX Slave Address ACK ETX BCC
[STX]
XX XX
[ACK] [ETX]
XX
2-3) Response message (Response when a receiving error occurred)
STX Slave Address NAK ETX BCC
[STX]
XX XX
[NAK]
XX
[ETX]
XX
Response is not returned unless STX and ETX (BCC) are included in the request. This product clears all previously received code when STX is received.
Exception code
Page 67
HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series 5.5 Message configuration
5-13
Table 5.5-1 Format data
NO Item Explanation
1 STX(02h)
Start text The code to specify the head of the message. Added to the head of the characters to be sent.
2 ETX(03h)
End text The code to specify the end of the message. Added to the end of the characters to be sent. Other than BCC.
3
Slave
Address
Slave address which is set to each product. Can be changed by setting.
The address to identify the device. 4 Request Request identifier. R (reading) or W (writing) 5 Command Command to reading or writing.
6
Writing
Reading
To request writing, write the data in this area to the object data.
To request reading, set the object data in this area.
7 BCC
EXOR algorithm of all characters from STX to ETX is read with the check code for
error detection.
This code (BCC) is not included in “response” if BCC check is not selected when
setting the communication.
8 ACK(06h)
Acknowledge code.
This is included in the response from the product when there is no error in the
received request.
9 NAK(15h)
Negative acknowledge code.
This is included in the response from the product when there is an error in the
received request.
10
Exception
code
Error content is included in the response when there is an error in the received
request. Refer to the table below for exception codes.
Exception code
Exception
0
Equipment malfunction Memory error
1
Out of set range Value data is out of “set range specified independently by set parameter”
2
Setting not allowed. Changing of requested communication parameter is prohibited. Or communication parameter to read does not exist. Writing of the communication mode is requested while the communication mode change is set to RO (read only) Writing to PV (measured value) is requested.
3
Abnormal code ASCII code other than numerical data is requested (specified) to the location for numerical data. ASCII code other than “0” or”-” is requested (specified) to the
location for symbol. 4 Format error 5 BCC error 6 Overrun error 7 Fleming error 8 Parity error
1Exception code “0” is included in the response regardless of the presence of the
request error because memory error is present.
2The exception with the highest number is included in the response when two or
more errors have occurred.
Page 68
HRX-OM-M091
Chapter 5 Simple communication protocol function
5.5 Message configuration HRS Series
5-14
The communication example is expressed in hexadecimal value with [ ]. The actual communication is performed with ASCII code. Refer to the request / response message in this section.
5.5.2 Message example
The example shows communication with the conditions below.
Slave AddressNo.1 Read seven consecutive data from register 0000h.
(Read circulating fluid discharge temperature.)
Communication example
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address
R Request message to read [ACK] Normal response message
PV1 Circulating fluid discharge temperature PV1 Circulating fluid discharge temperature
[65h] BCC value 00187 Read information
[0Fh] BCC value
Request message (Master to Slave)
STX
Slave
Address
Request Command ETX BCC
02 30 31 52 50 56 31 03 65
Response message (Slave to Master)
STX
Slave
Address
ACK Command Reading data ETX BCC
02 30 31 06 50 56 31 30 30 31 38 37 03 0F
This product
(Request): [STX] 01RPV1 [ETX] [65h]
(Response): [STX] 01[ACK] PV100187 [ETX] [0Fh]
Your system
Data is sent and received in ASCII code.
Page 69
HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series 5.6 BCC
5-15
5.6 BCC
EXOR algorithm of all characters from STX to ETX is read with the check code for error detection.
This BCC is not included in “response” if BCC check is not selected when setting the communication.
Displayed in one digit of ASCII code in the message frame.
Calculation example
Message for BCC
[STX] 01RPV1 [ETX]
Calculation
ASCII HEX
[STX] 02
‘0’ 30
‘1’ 31 ‘R’ 52 ‘P’ 50 ‘V’ 56
‘1’ 31
[ETX] 03
‘e’ 65
Code for EXOR from STX to ETX is BCC.
Sending message
[STX] 01RPV1 [ETX] e
5.7 Command
Table 5.7-1 shows the commands which are supported by the product. No response is returned for a request message of a command which is not in
Table 5.7-1.
Table 5.7-1 Command list
NO Command Name R/W Explanation
1 PV1
Circulating fluid discharge temperature
R
Read the circulating fluid discharge temperature in the temperature unit of the product. The circulating fluid discharge temperature (offset temperature if offset setting is selected) which is displayed on the operation display panel PV part. e.g. In case of 19.8
o
C
00198
2 SV1
Circulating fluid set temperature
R/W
Write/read the circulating fluid set temperature in the temperature unit of the product. Writing is available only in serial mode. e.g. In case of 35.8
o
C
00358
3 LOC Key-lock setting R/W
Write and read the key-lock setting. 00000Unlocked 00001All locked 00002Setting mode value is locked 00003Key lock other than for set temp. Key-lock setting of this product just receives the command. This command does not actually lock the keys. This function is to make this product interchangeable with the communication specifications of SMC’s HRG/HRGC series thermo coolers. When not using this product as a replacement for HRG/HRGC, this function is not needed.
4 STR Store the data W Store the data to the product (Write to FRAM)
Page 70
HRX-OM-M091
Chapter 5 Simple communication protocol function
5.8 Command explanation HRS Series
5-16
5.8 Command explanation
5.8.1 Command:PV1 Circulating fluid discharge temperature
Read the circulating fluid discharge temperature in the selected temperature unit (°C or °F). The circulating fluid discharge temperature (offset temperature if offset setting is selected) which is displayed on the operation display panel PV part.
Request message <Normal> (Master to Slave)
STX Slave Address Request Command ETX BCC
[STX]
XX XX
[R] [P] [V] [1] [ETX]
XX
Response message <Normal> (Slave to Master)
STX Slave Address ACK Command Reading data ETX BCC
[STX]
XX XX
[ACK] [P] [V] [1]
XX XX XX XX XX
[ETX]
XX
Communication example
Slave AddressNo 1
BCC selection
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address R Request message to read [ACK] Normal response message PV1 Circulating fluid discharge temperature PV1 Circulating fluid discharge temperature [65h] BCC value 00187 Read information (18.7oC) [0Fh] BCC value
This product
(Request) [STX] 01RPV1 [ETX] [65h]
(Response) [STX] 01[ACK] PV100187 [ETX] [0Fh]
Your system
Data is sent and received in ASCII code.
Page 71
HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series 5.8 Command explanation
5-17
5.8.2 Command:SV1 Circulating fluid set temperature (R)
Read the circulating fluid set temperature in the selected temperature unit (°C or °F).
Request message <Normal> (Master to Slave)
STX Slave Address Request Command ETX BCC
[STX]
XX XX
[R] [S] [V] [1] [ETX]
XX
Response message <Normal> (Slave to Master)
STX Slave Address ACK Command Reading data ETX BCC
[STX]
XX XX
[ACK] [S] [V] [1]
XX XX XX XX XX
[ETX]
XX
Communication example
Slave AddressNo 1
BCC selection
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address R Request message to read [ACK] Normal response message SV1 Circulating fluid set temperature SV1 Circulating fluid set temperature [66h] BCC value 00258 Read information (25.8oC) [0Dh] BCC value
Your system This product
(Request) [STX] 01RSV1 [ETX] [66h]
(Response) [STX] 01[ACK] SV100258 [ETX] [0Dh]
Data is sent and received in ASCII code.
Page 72
HRX-OM-M091
Chapter 5 Simple communication protocol function
5.8 Command explanation HRS Series
5-18
5.8.3 Command:SV1 Circulating fluid set temperature (W)
Read the circulating fluid set temperature in the selected temperature unit (°C or °F).
Request message <Normal> (Master to Slave)
STX Slave Address Request Command Writing data ETX BCC
[STX]
XX XX
[W] [S] [V] [1]
XX XX XX XX XX
[ETX]
XX
Response message <Normal> (Slave to Master)
STX Slave Address ACK ETX BCC
[STX]
XX XX
[ACK] [ETX]
XX
Communication example
Slave AddressNo 1
BCC selection
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address W Request message to write [ACK] Normal response message SV1 Circulating fluid set temperature [06h] BCC value 00258 Write information (25.8 oC) [5Ch] BCC value
Your system This product
(Request)[STX] 01WSV100258 [ETX] [5Ch]
(Response)[STX] 01[ACK] [ETX] [06h]
Data is sent and received in ASCII code.
Page 73
HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series 5.8 Command explanation
5-19
5.8.4 Command:LOC Key-lock setting (R)
Read the key-lock condition set in 5.8.5 ‘’Command: LOC’’.
It is different from the key-lock information which is set by the operation display panel.
Request message <Normal> (Master to Slave)
STX Slave Address Request Command ETX BCC
[STX]
XX XX
[R] [L] [O] [C] [ETX]
XX
Response message <Normal> (Slave to Master)
STX Slave Address ACK Command Reading data ETX BCC
[STX]
XX XX
[ACK] [L] [O] [C]
XX XX XX XX XX
[ETX]
XX
Communication example
Slave AddressNo 1
BCC selection
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address R Request message to read [ACK] Normal response message LOC Key-lock setting LOC Key-lock setting [12h] BCC value 00001
Read information(00001:All locked
[77h] BCC value
This product
(Request)STX01RLOC[ETX][12h]
(Response)STX01ACK]LOC00001[ETX][77h]
Your system
Data is sent and received in ASCII code.
Page 74
HRX-OM-M091
Chapter 5 Simple communication protocol function
5.8 Command explanation HRS Series
5-20
5.8.5 Command:LOC Key-lock setting (W)
Sets key-lock of this product. This setting is different from the key-lock information which is set by the operation display panel.
Key-lock setting of this product just receives the command. This command does not actually lock the keys.
This function is to make this product interchangeable with the communication specifications of SMC’s HRG/HRGC series thermo coolers. When not using this product as a replacement for HRG/HRGC, this function is not needed.
Request message <Normal> (Master to Slave)
STX Slave Address Request Command Writing data ETX BCC
[STX]
XX XX
[W] [L] [O] [C]
XX XX XX XX XX
[ETX]
XX
Response message <Normal> (Slave to Master)
STX Slave Address ACK ETX BCC
[STX]
XX XX
[ACK] [ETX]
XX
Communication example
Slave AddressNo 1
BCC selection
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address W Request message to write [ACK] Normal response message LOC Key-lock setting [06h] BCC value
00001
Read information(00001:All locked
[26h] BCC value
Your system This product
(Request)[STX] 01WLOC00001 [ETX] [26h]
(Response)[STX] 01[ACK] [ETX] [06h]
Data is sent and received in ASCII code.
Page 75
HRX-OM-M091
Chapter 5 Simple communication protocol function
HRS Series 5.8 Command explanation
5-21
5.8.6 Command:STR Saves data (W)
Store the circulating fluid set temperature set in 5.8.3 ‘’Command:SV1 Circulating fluid set temperature’’. Key-lock set data which is set in 5.8.5 ‘’Command:LOC Key-lock setting (W)’’ is not the object to store.
Request message <Normal> (Master to Slave)
STX Slave Address Request Command ETX BCC
[STX]
XX XX
[W] [S] [T] [R] [ETX]
XX
Response message <Normal> (Slave to Master)
STX Slave Address ACK ETX BCC
[STX]
XX XX
[ACK] [ETX]
XX
Communication example
Slave AddressNo 1
BCC selection
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address W Request message to write [ACK] Normal response message STR Saves data [06h] BCC value [02h] BCC value
Your system This product
(Response)STX01ACK][ETX][06h]
(Request)STX01WSTR[ETX][02h]
Data is sent and received in ASCII code.
Page 76
HRX-OM-M091
Chapter 5 Simple communication protocol function
5.9 Negative response HRS Series
5-22
5.9 Negative response
If the request is not normal when receiving the request, or the request cannot be received due to the state of the product, a negative response is returned. Refer to the exception codes in Table 5.5-1 for exceptions.
Response message <Normal> (Slave to Master)
STX Slave Address NAK ETX BCC
[STX]
XX XX
[NAK]
XX
[ETX]
XX
Communication example
Slave AddressNo 1
Writing of the circulating fluid set temperature when the communication
range setting is RO (read only).
Request message Response message
Code Contents Code Contents
01 Slave Address 01 Slave Address W Request message to write [NAK] Negative response message SV1 Circulating fluid set temperature 2 Exception code for setting is prohibited 00258 Write information (15.1 oC) [39h] BCC value [5Ch] BCC value
Exception code
Your system This product
(Request)STX01WSV100258[ETX][5Ch]
(Response)STX01NAK]2[ETX][39h]
Data is sent and received in ASCII code.
Page 77
HRX-OM-M091
Chapter 6 Communication alarm function
HRS Series 6.1 Communication alarm occurs
6-1
Chapter 6 Communication alarm
function
Monitors whether the serial communication is sent/received properly between the product and the customer’s device. This feature is only valid when the communication mode is set to SERIAL mode.
Abnormal signals or disconnection of the communication cable can be notified immediately by setting the alarm function to match the interval at which messages are sent from the customer device. When the communication is restored, the alarm is automatically reset.
Do not use this function when the customer device does not send messages regularly.
The default setting of this function is “off”.
6.1 Communication alarm occurs
Fig 6.1-1 shows when an alarm occurs. Refer to 6.3 ‘’Setting and checking’’ for the setting method.
Changing of communication error
Operation continues when an alarm occurs.
Time for monitoring the communication error
180 sec
When the customer's device is sending messages every 60sec, if the communication cable is disconnected and no message is received for 180sec, the product generates AL19 communication error alarm to notify the error.
This productYour system
Write or read
Write or read
60 sec.
60 sec.
60 sec.
60 sec.
Broken
wire
o r
coming
off
Passage of
180 sec.
Excess at no
communicatio
n monitoring
time.
AL19 Communication
error is generated.
Operation continues
Monitoring
time
Monitoring
time
Fig 6.1-1 Communication alarm example
Page 78
HRX-OM-M091
Chapter 6 Communication alarm function
6.2 Communication alarm reset HRS Series
6-2
6.2 Communication alarm reset
When AL19 communication error has been generated, the alarm is automatically reset when the disconnection of the communication cable is fixed, and the message from the customer is received. If operation is set to stop when a communication alarm occurs, restart the operation if necessary.
This productYour system
Write or read
Write or read
60 sec.
60 sec.
60 sec.
Broken
wire
o r
coming
off
AL19 Communication
error is generated.
Monitoring
time
Monitoring
time
Normal
connection
Communication error automatic restoration
Write or read
60 sec.
: :
Fig 6.2-1 Communication alarm restoration example
6.3 Setting and checking
6.3.1 Setting and checking items
The table below explains the setting items of the communication alarm function and default values.
Table 6.3-1 Communication setting item
Display Item Contents
Initial value
(Default setting)
Changing of communication error
Set the operation when the alarm No. AL19 “Communication error” is generated.
OFF
The monitoring time of communication error
Set the alarm monitoring time when the alarm No. AL19 “Communication error” is generated. Alarm signal is generated when the monitoring time is exceeded. Setting unit is 1 sec. [----] is displayed when the communication error setting is OFF.
30
Page 79
HRX-OM-M091
Chapter 6 Communication alarm function
HRS Series 6.3 Setting and checking
6-3
6.3.2 Setting and checking
1. Press and hold the [MENU] key for 2 sec.
Repeat pressing the key until the setting screen for alarm buzzer sound [
] appears
on the digital display.
PV
SV
PV
SV
PV
SV
PV
SV
Changing of communication error Setting and checking
2. Display the screen of the communication error by pressing the [SEL] key 10 times.
The set screen ofchanging of communication error” is displayed on the digital display.
PV
SV
3. Select changing of operation when communication error from the table below with [] key
or [] key, and confirm by pressing “SEL”.
Table 6.3-2 List of set values
Set values Explanation
Initial value
(Default setting)
This alarm signal is not detected.
Operation continues when this communication error is generated. Operation is stopped when this communication error is generated.
The monitoring time of communication error Setting and checking
4. Press the [SEL] key once.
The set screen of the “monitoring time of communication error” is displayed on the digital display.
PV
SV
MENU
Press
and hold
MENU
Press
and hold
MENU
Press
and hold
Page 80
HRX-OM-M091
Chapter 6 Communication alarm function
6.3 Setting and checking HRS Series
6-4
5. Select the monitoring time of communication error from the table below with [] key or [▼]
key, and confirm by pressing “SEL”.
Table 6.3-3 List of set values
Set values Explanation
Initial value
(Default setting)
Setting/checking are not available if the setting of the changing of communication error is OFF.
to
Sets monitoring time of communication error Setting range is 30 to 600 sec.
Page 81
Page 82
4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021 JAPAN Tel: + 81 3 5207 8249 Fax: +81 3 5298 5362 URL http://www.smcworld.com
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2011 SMC Corporation All Rights Reserved
Loading...