SMC Networks EX260-SPR1/3, EX260-SPR2/4, EX260-SPR5/7, EX260-SPR6/8, EX260-SDN1/3 Quick Start Manual

...
Page 1
®
RoHS
IP67IP67 IP67 IP40
Top ported valve Bottom ported valve
Side ported valve
Mixed valve sizes manifold
7 mm width valve
Applicable Fieldbus protocols
Fieldbus System
(Output device for driving 5 port solenoid valves)
Daisy-chain wiring communication
Space-saving InstallationSpace-saving Installation
Compact
28
mm
IP67
For units with D-sub connector, and when connect ed to S0700 manifolds, it is IP40 .
Drives up to 32 solenoids
789
EX12
EX140
EX180
EX260
EX250
EX600
EX500
EX510
PCA EX
EX260
A
Page 2
PWR
BUS IN
BUS OUT
E
3/5
1P
E
3/5
1P
B4A2 B4A2 B4A2 B4A2 B4A2
PWR
BUS IN
BUS OUT
E
3/5
1P
E
3/5
1P
B4A2 B4A2 B4A2 B4A2 B4A2
Product Specification Variations
M12 communication connector
(PROFIBUS DP)
D-sub communication connector
(PROFIBUS DP)
28.2 mm
81 mm
Communication connector examples
Fieldbus
EX260
Manifold length is shortened by the small fieldbus output module (SI unit).
Wiring and piping from the same direction is possible.
(for side ported)
Effective for installation in locations where space is limited above the valve.
Current model EX250
External branch connector is not necessary. Daisy-chain wiring is possible. Reduced wiring space
Branch connector
Current model (EX250)
External terminating resistor is not necessary.
(Only available for M12 PROFIBUS DP, CC-Link communication connectors)
ON/OFF switching is possible with an internal terminating resistor. External terminating resistor is not necessary.
External terminating resistor
Internal terminating resistor
SI unit
16
32
PNP
NPN
M12
D-sub
16
32
PNP
NPN
M12
16
32
PNP
NPN
M12
16
32
PNP
NPN
M12
16
32
PNP
NPN
M12
Number of
outputs
Output
polarity
Communication
connector
16
32
PNP
NPN
M12
16
32
PNP
M12
790
A
Page 3
SY3000
SY5000
SY7000
S0700
SV1000
SV2000
SV3000
VQC1000
VQC2000
VQC4000
VQC5000
0.19
0.17
0.20
0.39
0.35
0.18
0.21
0.30
0.30
0.38
0.31
1.6
3.6
5.9
0.37
1.1
2.4
4.3
1.0
3.2
7.3
17
Series
Power
consumption
(W)
Enclosure Standards
Flow rate characteristics (4/25/3)
C [dm
3
/(s·bar)] b
Maximum number of solenoids
Applicable Valve Series
Note) For units with D-sub communication connector, it is IP40.
32
32
32
24
0.35 (standard)
0.1 (with power­saving circuit) [Starting 0.4,
Holding 0.1]
0.6
0.95 (standard)
0.4 (Low wattage type)
0.4 (standard)
0.35
®
IP67
IP40
IP67
IP67
Side ported
Side ported
Bottom ported
Top ported
<Example of Use>
Valve piping direction variations
SY3000/5000/7000 Series
Pressure switch
Piping is possible from 3 directions.
Mixed mounting of top ported and side ported is possible.
By mounting top ported valves on side ported and bottom ported type manifolds, it is possible to detect the output of the A/B port with a pressure switch.
Valves can be freely connected up to 24 stations.
Mixed valve sizes manifold
Valves with different sizes,
SY3000 and SY5000 or SY5000 and SY7000, can be mounted on the same manifold.
It is possible to connect only the number of valves required, from 1 to 24 stations, to suit the application. (Maximum number of solenoids connected: 32)
7 mm width valves
can be connected.
It is possible to connect only the number of 7 mm width valves required, from 1 to 24 stations. (Maximum number of solenoids connected: 32)
S0700 Series
791
EX12
EX140
EX180
EX260
EX250
EX600
EX500
EX510
PCA EX
EX260
Page 4
M12
DN1 DN2 DN3 DN4 PR1 PR2 PR3 PR4 PR5 PR6 PR7 PR8 MJ1 MJ2 MJ3 MJ4 EC1 EC2 EC3 EC4 PN1 PN2 PN3 PN4 EN1 EN2 EN3 EN4 PL1 PL3
DeviceNet™
PROFIBUS DP
EtherCAT
PROFINET
POWERLINK
SI unit output polarity
32
16
32
16
32
16
32
16
32
16
32
16
32
16
32 16
M12
M12
D-sub
Note)
M12
M12
EtherNet/IP™
M12
M12
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
Sink/NPN (Positive common)
Source/PNP (Negative common)
QAN
QA
QBN
QB
NAN
NA
NBN
NB
NCN
NC
NDN
ND
VAN
VA
VBN
VB
DAN
DA
DBN
DB
FAN
FA
FBN
FB
EAN
EA
EBN
EB GAN GBN
Communication protocol
Compact design
Compact design for space saving
Number of outputs
Each 32/16 digital output type available in the series
Enclosure
IP67 (For units with D-sub connector, and when connected with S0700 manifolds, it is IP40.)
Output polarity
Each negative common (PNP) / positive common (NPN) type available in the series (SI Unit compatible with POWERLINK is only negative common (PNP) type.)
Internal terminating resistor
ON/OFF switching is possible with an internal terminating resistor for communication. (Only for units compatible with M12 PROFIBUS DP, CC-Link communication connectors)
SY3000/5000/7000 VQC1000/2000/4000/5000 S0700 SV1000/2000/3000
D
D
D
D

How to Order SI Units

PR1
EX260 S
Note)
Note) The SY3000/5000/7000, VQC1000/2000/4000/5000, and S0700 are not yet UL-compatible.
CC-Link
®
RoHS
Protocol
Symbol
Number of outputs
Communication connector
Manifold symbol
EX260 Series
SI Unit/For Output
Note) Enclosure is IP40 when the communication connector is D-sub.
792
A
Page 5
SI Unit Specifications
Model
EX260-SPR1/3 EX260-SPR2/4 EX260-SPR5/7 EX260-SPR6/8 EX260-SDN1/3 EX260-SDN2/4 EX260-SMJ1/3 EX260-SMJ2/4
125 k/250 k/500 kbps
156 k/625 k/
2.5 M/5 M/10 Mbps
M12
Built-in
22.8 to 26.4 VDC 11 to 25 VDC
100 mA or less
Applicable system
I/O occupation area (Inputs/Outputs)
Communication speed
Power supply for control Power supply for output
Communication connector specification Terminating resistor switch
Power supply for communication
Output
Environmental resistance
Standards Weight
Mounting screw
Accessories
IP67 IP40 IP67
–10 to 50°C
35 to 85%RH (No condensation)
500 VAC for 1 minute between terminals and housing
10 M or more (500 VDC measured via megohmmeter) between terminals and housing
CE marking, UL (CSA) compatible
200 g 2 pcs.
24 VDC
Power supply voltage
Internal current consumption
Power supply voltage Power supply voltage
Internal current consumption
Protocol
Version
Note 1)
Configuration file
Note 3)
Supplied current
Output type
Number of outputs
Load Supplied voltage
Enclosure Operating temperature range Operating humidity range Withstand voltage Insulation resistance
Seal cap (for M12 connector socket)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
SPR1: 32 points SPR3: 16 points
SPR2: 32 points SPR4: 16 points
SPR5: 32 points SPR7: 16 points
SPR6: 32 points SPR8: 16 points
SDN1: 32 points SDN3: 16 points
SDN2: 32 points SDN4: 16 points
SPR1: 0/32 SPR3: 0/16
SPR2: 0/32 SPR4: 0/16
SPR5: 0/32 SPR7: 0/16
SPR6: 0/32 SPR8: 0/16
SDN1: 0/32 SDN3: 0/16
SDN2: 0/32 SDN4: 0/16
SMJ1: 32/32 SMJ3:
32/32
(1 station, remote I/O stations)
SMJ2: 32/32 SMJ4:
32/32
(1 station, remote I/O stations)
SPR1: Max. 2.0 A SPR3: Max. 1.0 A
SPR2: Max. 2.0 A SPR4: Max. 1.0 A
SPR5: Max. 2.0 A SPR7: Max. 1.0 A
SPR6: Max. 2.0 A SPR8: Max. 1.0 A
SDN1: Max. 2.0 A SDN3: Max. 1.0 A
SDN2: Max. 2.0 A SDN4: Max. 1.0 A
EX9-AWTS (1 pc.) EX9-AWTS (1 pc.)
D-sub M12
None Built-in
Volume 1(Edition 3.5) Volume 3(Edition 1.5)
9.6 k/19.2 k/45.45 k/93.75 k/
187.5 k/500 k/1.5 M/3 M/6 M/12 Mbps
21.6 to 26.4 VDC 100 mA or less
— —
21.6 to 26.4 VDC 100 mA or less
PROFIBUS DP
DeviceNet™
CC-Link
DP-V0 Ver.1.10
GSD file EDS file
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
SMJ1: 32 points SMJ3: 16 points
SMJ2: 32 points SMJ4: 16 points
SMJ1: Max. 2.0 A SMJ3: Max. 1.0 A
SMJ2: Max. 2.0 A SMJ4: Max. 1.0 A
Solenoid valve with protective circuit for surge voltage of 24 VDC/1.5 W or less (SMC)
Model
EX260-SEC1/3 EX260-SEC2/4 EX260-SPN1/3 EX260-SPN2/4 EX260-SEN1/3 EX260-SEN2/4
Applicable system
I/O occupation area (Inputs/Outputs)
Communication speed Power supply for control Power supply for output
Communication connector specification Terminating resistor switch
Power supply for communication
Output
Environmental resistance
Standards Weight
Mounting screw
Accessories
IP67
–10 to 50°C
35 to 85%RH (No condensation)
500 VAC for 1 minute between terminals and housing
CE marking, UL (CSA) compatible
200 g 2 pcs.
10 M or more (500 VDC measured via megohmmeter) between terminals and housing
24 VDC
Power supply voltage
Internal current consumption
Power supply voltage Power supply voltage
Internal current consumption
Protocol
Version
Note 1)
Configuration file
Note 3)
Supplied voltage
Output type
Number of outputs
Load
Supplied voltage
Enclosure Operating temperature range Operating humidity range Withstand voltage Insulation
resistance
Seal cap (for M12 connector socket)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
SEC1: 32 points SEC3: 16 points
SEC2: 32 points SEC4: 16 points
SPN1: 32 points SPN3: 16 points
SPN2: 32 points SPN4: 16 points
SEN1: 32 points SEN3: 16 points
SEN2: 32 points SEN4: 16 points
SEC1: 0/32 SEC3: 0/16
SEC2: 0/32 SEC4: 0/16
SPN1: 0/32 SPN3: 0/16
SPN2: 0/32 SPN4: 0/16
SEN1: 16/32 SEN3: 16/16
SEN2: 16/32 SEN4: 16/16
SEC1: Max. 2.0 A SEC3: Max. 1.0 A
SEC2: Max. 2.0 A SEC4: Max. 1.0 A
SPN1: Max. 2.0 A SPN3: Max. 1.0 A
SPN2: Max. 2.0 A SPN4: Max. 1.0 A
SEN1: Max. 2.0 A SEN3: Max. 1.0 A
SEN2: Max. 2.0 A SEN4: Max. 1.0 A
EX9-AWTS (1 pc.)
Volume 1(Edition 3.8) Volume 2(Edition 1.9)
21.6 to 26.4 VDC 100 mA or less
22.8 to 26.4 VDC
— —
M12
None (Not required)
10 M/100 Mbps
Note 2)
100 Mbps
Note 2)
EtherCAT
Note 2)
EtherNet/IP™
Note 2)
Conformance
Test Record V.1.1
XML file
PROFINET
Note 2)
PROFINET Specification
Version 2.2
GSD file EDS file
Solenoid valve with protective circuit for surge
voltage of 24 VDC/1.5 W or less (SMC)
Solenoid valve with protective circuit for surge
voltage of 24 VDC/1.0 W or less (SMC)
Solenoid valve with protective circuit for surge
voltage of 24 VDC/1.5 W or less (SMC)
EX260-SPL1 EX260-SPL3
Source/PNP
(Negative common)
32 16
16/32 16/16
Max. 2 A Max. 1 A
EPSG DS 301 Version 1.2.0
100 Mbps
Note 2)
POWERLINK
XDD file
Note 1) Please note that the version is subject to change. Note 2) Use a CAT5 or higher transmission cable for EtherCAT, PROFINET, EtherNet/IP™, POWERLINK. Note 3) Each file can be downloaded from the SMC website, http://www.smcworld.com
For Output EX260 Series
793
EX12
EX140
EX180
EX260
EX250
EX600
EX500
EX510
PCA EX
EX260
A
Page 6
D-sub communication connector typeM12 communication connector type
90.9
28.2
102.4
90.9
102.4
28.2
21 20.6 16.4 9
76.5
28.75 29.25 9
76.5
SI Unit Dimensions
Part no.
Communication protocol
EX260-SPR1/-SPR2
-SPR3/-SPR4
PROFIBUS DP
5 pins, socket, B code
5 pins, plug, B code
5 pins, plug, A code
Note) The setting switch varies depending on the model. Refer to the operation manual for details. Please download it via the SMC website, http://www.smcworld.com
EX260-SDN
DeviceNet™
5 pins, socket, A code
5 pins, plug, A code
4 pins, plug, A code
EX260-SMJ
CC-Link
EX260-SEC EX260-SPN EX260-SEN EX260-SPL
EtherCAT
PROFINET
EtherNet/IP™
POWERLINK
M3
Communication connector (M12) BUS OUT Communication connector (M12) BUS IN Ground terminal
Power connector (M12)
<Setting switch>
• Address switch
• Communication speed switch
• Terminating resistor switch
• Others
<LED indication>
• Communication state
• Unit power supply state
• Valve power supply state
Part no.
Communication protocol
EX260-SPR5/-SPR6/-SPR7/-SPR8
PROFIBUS DP
M3
9 pins, socket
5 pins, plug, A code
Ground terminal
Communication connector (D-sub) BUS IN/OUT
Power connector (M12)
D-sub communication connector type
Functions of SI Unit Parts
<Connector> M12 communication connector type
<LED indication and setting switch>
5 pins, socket, A code
Note1)
4 pins, plug, A code
5 pins, plug, B code
4 pins, socket, D code 4 pins, socket, D code
5 pins
Note2)
, 4 pins
Note3)
,
plug, A code
EX260 Series
Note 1) Recommended mating M12
4-pin plug, part no. PCA-1567717.
Note 2) For EtherCAT, PROFINET,
POWERLINK
Note 3) For EtherNet/IP™
794
A
Page 7
White/Orange Orange White/Green
Green

Accessories

q Communication cable with connector
For SI units compatible with PROFIBUS DP, DeviceNet™, CC-Link
For SI units compatible with EtherCAT, PROFINET, EtherNet/IP™, POWERLINK
Refer to page 907 for details.
020EX9 AC EN
Cable length (L)
1000 [mm] 2000 [mm] 3000 [mm] 5000 [mm] 10000 [mm]
010 020 030 050 100
PSRJ
M12 plug (straight) RJ-45 connector
PSRJ
Plug connector
pin arrangement
D code
Connections (Straight cable)
M12
RJ-45
Plug connector
pin arrangement
1 2 3 4 5 6 7 8
Terminal
no.
1 2 3 4
1 2 3 4 5 6 7 8
Terminal
no.
Shield
Pair
Pair
Core wire colors
Connector specification
For SI units compatible with EtherCAT, PROFINET, EtherNet/IP™, POWERLINK
PCA 1446566
For SI units compatible with EtherCAT, PROFINET, EtherNet/IP™, POWERLINK
PCA 1446553
5000 [mm]
1446566
Cable length
Fieldwireable connector
6.5)
50500047.3
ø14.8
Plug connector
pin arrangement
D code
12
3 4
M12
SPEEDCON
ø
17.5
ø
19
61
Width across flats 16
M12
For Output EX260 Series
12
3 4
Plug connector
pin arrangement
D code
12
3 4
1
2
3
4
White: RD+
Blue: RD–
Yellow: TD+
Orange: TD–
Connections
Terminal
no.
Wire guide color
Width across flats 13
ø6.4
(47.3) (44)
L
ø14.8
Item Specifications
Cable O.D. Nominal cross section Wire diameter (Including insulator) Min. bending radius
ø6.5 mm
AWG22
1.5 mm
45.5 mm
Applicable cable
Cable O.D. Cable cross section (Stranded wire)
4.0 to 8.0 mm
0.14 to 0.34 mm
2
/AWG26 to 22
Note) The table above shows the specifications for the applicable
cable. Adaptation for the connector may vary on account of the conductor construction of the electric wire.
795
EX12
EX140
EX180
EX260
EX250
EX600
EX500
EX510
PCA EX
EX260
A
Page 8
w Power cable with connector (for SI units)
Accessories
EX500 AP
2
4 3
Socket connector
pin arrangement
A code
Socket connector
pin arrangement
A code
1
1
2
3
4
5
Terminal
no.
Core wire colors
M12
Connections (PROFIBUS DP/EtherCAT/PROFINET/POWERLINK)
Cable length (L)
1000 [mm] 5000 [mm]
010 050
Connector specification
Straight
Angle
S A
S
050
For SI units compatible with PROFIBUS DP, DeviceNet™, EtherCAT, PROFINET, EtherNet/IP™, POWERLINK
Brown: 24 VDC +10%/–5% (Solenoid valve power supply)
White: 0 V (Solenoid valve power supply)
Blue: 24 VDC ±10% (Control power supply)
Black: 0 V (Control power supply)
Green/Yellow: Not connected
1
2
3
4
5
Terminal
no.
Core wire colors
Connections (DeviceNet, EtherNet/IP™)
Brown: Not connected
Note 1)
, 24 VDC ±10% (Control power supply)
Note 2)
White: 24 VDC +10%/–5%
(Solenoid valve power supply)
Blue: Not connected
Note 1)
, 0 V (Control power supply)
Note 2)
Black: 0 V (Solenoid valve power supply)
Green/Yellow: Not connected
Straight connector type
2
4 3
5
1
M12
Angle connector type
5
SPEEDCON
PCA
Cable length (L)
1500 [mm] 3000 [mm] 5000 [mm]
1401804 1401805 1401806
1401804
4 3
21
ø14.8
M12 SPEEDCON
44.5 L 50
ø5.0
5
Socket connector
pin arrangement
A code
Note 1) For DeviceNet™ Note 2) For EtherNet/IP™
1
2
3
4
5
Terminal
no.
Core wire colors
Connections (PROFIBUS DP/EtherCAT/PROFINET/POWERLINK)
Brown: 24 VDC +10%/–5% (Solenoid valve power supply)
White: 0 V (Solenoid valve power supply)
Blue: 24 VDC ±10% (Control power supply)
Black: 0 V (Control power supply)
Gray: Not connected
1
2
3
4
5
Terminal
no.
Core wire colors
Connections (DeviceNet, EtherNet/IP™)
Brown: Not connected
Note 1)
, 24 VDC ±10% (Control power supply)
Note 2)
White: 24 VDC +10%/–5%
(Solenoid valve power supply)
Blue: Not connected
Note 1)
, 0 V (Control power supply)
Note 2)
Black: 0 V (Solenoid valve power supply)
Gray: Not connected
Note 1) For DeviceNet™ Note 2) For EtherNet/IP™
EX260 Series
ø14.9
25.3
28.3
30
5
50
L
ø6
ø14.9
40.7
27
L
ø6
30
5
50
Item Specifications
Cable O.D. Nominal cross section Wire diameter (Including insulator) Min. bending radius
ø6 mm
AWG22
1.5 mm 40 mm
Item Specifications
Cable O.D. Nominal cross section Wire diameter (Including insulator) Min. bending radius
ø6 mm AWG22
1.5 mm 40 mm
Item Specifications
Cable O.D. Nominal cross section Wire diameter (Including insulator) Min. bending radius
ø5.0 mm
AWG22
1.27 mm
21.7 mm
796
B
Page 9
w Power cable with connector (for SI units)
Accessories
e Seal cap: For M12 connector socket
EX9 AW
Use this on ports that are not being used for communication connector (M12 connector socket). Use of this seal cap maintains the integrity of the IP67 enclosure.
Note) Tighten the seal cap with the prescribed tightening torque. (For M12: 0.1 N·m)
TS
Connector type
For M12 connector socket (10 pcs.)
For M12 connector socket
M12 x 1
14
10.2
14
For
SI units compatible with
CC-Link
Straight connector type
TS
EX9 AC 1
Cable length (L)
1000 [mm] 3000 [mm] 5000 [mm]
010 030 050
050
SPEEDCON
PCA
Cable length (L)
1500 [mm] 3000 [mm] 5000 [mm]
1401807 1401808 1401809
1401807
2
4 3
5
1
Socket connector
pin arrangement
B code
M12
48.1
L
30505
ø6.4
Connections
1
2
3
4
5
Terminal
no.
Cable core wire colors
4 3
21
M12 SPEEDCON
ø14.8
50L44.5
ø5.0
5
Socket connector
pin arrangement
B code
Brown: 24 VDC +10%/–5% (Solenoid valve power supply)
White: 0 V (Solenoid valve power supply)
Blue: 24 VDC ±10% (Control power supply)
Black: 0 V (Control power supply)
Green/Yellow: Not connected
Connections
1
2
3
4
5
Terminal
no.
Cable core wire colors
Brown: 24 VDC +10%/–5% (Solenoid valve power supply)
White: 0 V (Solenoid valve power supply)
Blue: 24 VDC ±10% (Control power supply)
Black: 0 V (Control power supply)
Gray: Not connected
For Output EX260 Series
Item Specifications
Cable O.D. Nominal cross section Wire diameter (Including insulator) Min. bending radius
ø6.4 mm
AWG22
1.65 mm 59 mm
Item Specifications
Cable O.D. Nominal cross section Wire diameter (Including insulator) Min. bending radius
ø5.0 mm
AWG22
1.27 mm
21.7 mm
797
EX12
EX140
EX180
EX260
EX250
EX600
EX500
EX510
PCA EX
EX260
A
Page 10
Design/Selection
1. Use this product within the specification range.
Using beyond the specified specifications range can cause fire, malfunction, or damage to the system. Check the specifications before operation.
2. When using for an interlock circuit:
Provide a multiple interlock system which is operated by another system (such as mechanical protection function).
Perform an inspection to confirm that it is working properly.
This may cause possible injury due to malfunction.
Warning
Mounting
4. When lifting a large size manifold solenoid valve unit, take care to avoid causing stress to the valve connection joint.
The connection parts of the unit may be damaged. Because the unit may be heavy, carrying and installation should be performed by more than one operator to avoid strain or injury.
5. When placing a manifold, mount it on a flat surface.
Torsion in the whole manifold can lead to trouble such as air leakage or defective insulation.
Wiring
1. Check the grounding to maintain the safety of the reduced wiring system and for anti-noise performance.
Provide a specific grounding as close to the unit as possible to minimize the distance to grounding.
2. Avoid repeatedly bending or stretching the cable and applying a heavy object or force to it.
Wiring applying repeated bending and tensile stress to the cable can break the circuit.
3. Avoid miswiring.
If miswired, there is a danger of malfunction or damage to the reduced wiring system.
4. Do not wire while energizing the product.
There is a danger of malfunction or damage to the reduced wiring system or output device.
5. Avoid wiring the power line and high pressure line in parallel.
Noise or surge produced by signal line resulting from the power line or high pressure line could cause malfunction.Wiring of the reduced wiring system or output device and the power line or high pressure line should be separated from each other.
6. Check the wiring insulation.
Defective insulation (contact with other circuits, improper insulation between terminals, etc.) may cause damage to the reduced wiring system or output device due to excessive voltage and current.
7. When a reduced wiring system is installed in machinery/equipment, provide adequate protection against noise by using noise filters, etc.
Noise in signal lines may cause malfunction.
1. When applicable to UL, use a Class 2 power supply unit conforming to UL1310 for direct current power supply.
2. Use this product within the specified voltage range.
Using beyond the specified voltage range is likely to cause the units and connecting devices to be damaged or to malfunction.
3. Do not install a unit in a place where it can be used as a foothold.
Applying any excessive load such as stepping on the unit by mistake or placing a foot on it, will cause it to break.
4. Keep the surrounding space free for maintenance.
When designing a system, take into consideration the amount of free space needed for performing maintenance.
5. Do not remove the name plate.
Improper maintenance or incorrect use of operation manual can cause failure and malfunction. Also, there is a risk of losing conformity with safety standards.
1. When handling and assembling units:
Do not apply excessive force to the unit when
disassembling.
The connecting portions of the unit are firmly joined with seals.
When joining units, take care not to get fingers
caught between units.
Injury can result.
2. Do not drop, bump, or apply excessive impact.
Otherwise, the unit can become damaged, malfunction, or fail to function.
3. Observe the tightening torque range.
Tightening outside of the allowable torque range will likely damage the screw.
IP67 cannot be guaranteed if the screws are not tightened to the specified torque.
Mounting
EX260 Series

Specific Product Precautions 1

Be sure to read this before handling the products. Refer to back page 50 for Safety Instructions and pages 3 to 9 for 3/4/5 Port Solenoid Valve Precautions.
Caution
Caution
Caution
Caution
798
Page 11
Wiring
Operating Environment
1. Do not use in an atmosphere containing an inflammable gas or explosive gas.
Use in such an atmosphere is likely to cause a fire or explosion. This system is not explosion-proof.
Operating Environment
2. Provide adequate protection when operating in locations such as the following.
Failure to do so may cause damage or malfunction. The effect of countermeasures should be checked in individual equipment and machine.
1) Where noise is generated by static electricity, etc.
2) Where there is a strong electric field
3) Where there is a danger of exposure to radiation
4) When in close proximity to power lines or high voltage lines
3. Do not use in an environment where oil and chemicals are used.
Operating in environments with coolants, cleaning solvents, various oils or chemicals may cause adverse effects (damage, malfunction) to the unit even in a short period of time.
4. Do not use in an environment where the product could be exposed to corrosive gas or liquid.
This may damage the unit and cause it to malfunction.
5. Do not use in locations with sources of surge generation.
Installation of the unit in an area around the equipment (electromagnetic lifters, high frequency induction furnaces, welding machine, motors, etc.), which generates the large surge voltage could cause to deteriorate an internal circuitry element of the unit or result in damage. Implement countermeasures against the surge from the generating source, and avoid touching the lines with each other.
6. The product is CE marked, but not immune to lightning strikes. Take measures against lightning strikes in your system.
7. Keep dust, wire scraps and other extraneous material from getting inside the product.
This may cause malfunction or damage.
8. Mount the unit in such locations, where no vibration or shock is affected.
This may cause malfunction or damage.
9. D o not use in places where there are cyclic temperature changes.
In case that the cyclic temperature is beyond normal temperature changes, the internal unit is likely to be adversely effec-ted.
10. Do not use in direct sunlight.
Do not use in direct sunlight. It may cause malfunction or damage.
11. Use this product within the specified ambient temperature range.
This may cause malfunction.
12. Do not use in places where there is radiated heat around it.
Such a place is likely to cause malfunction.
1. Select the proper type of enclosure according to the environment of operation.
IP67 is achieved when the following conditions are met.
1) Provide appropriate wiring between all units using electrical
wiring cables, communication connectors and cables with M12 connectors.
2) Suitable mounting of each unit and manifold valve.
3) Be sure to mount a seal cap on any unused connectors. If using in an environment that is exposed to water splashes, please take measures such as using a cover. When the enclosure is IP40, do not use in an operating environment or atmosphere where it may come in contact with corrosive gas, chemical agents, seawater, water, or water vapor. When connected to the EX260-SPR5/6/7/8, manifold enclosure is IP40.
Caution
Caution
Caution
Warning
8. When connecting wires of output device, prevent water, solvent or oil from entering inside the connector section.
This can cause damage, equipment failure or malfunction.
9. Avoid wiring patterns in which excessive stress is applied to the connector.
This may cause malfunction or damage to the unit due to contact failure.
10. Select connectors that are ø16 or less if mounting manifolds directly using fieldwireable connectors for SI unit power supply wiring.
Using large diameter connectors causes interference with the mounting surface. The following cables with connectors are recommended.
For EX260-SPR/-SDN/-SEC/-SPN/-SEN/-SPL
<Cable with connector>
EX500-AP-  PCA-1401804/-1401805/-1401806
For EX260-SMJ
<Cable with connector>
EX9-AC-1 PCA-1401807/-1401808/-1401809
EX260 Series

Specific Product Precautions 2

Be sure to read this before handling the products. Refer to back page 50 for Safety Instructions and pages 3 to 9 for 3/4/5 Port Solenoid Valve Precautions.
799
EX12
EX140
EX180
EX260
EX250
EX600
EX500
EX510
PCA EX
EX260
A
Page 12
Adjustment/Operation
Warning
1. Do not perform operation or setting with wet hands.
There is a risk of electrical shock.
Maintenance
1. Do not disassemble, modify (including circuit board replacement) or repair this product.
Such actions are likely to cause injuries or breakage.
2. When an inspection is performed,
Turn off the power supply.
Stop the air supply, exhaust the residual pressurein
piping and verify that the air is released before performing maintenance work.
Unexpected malfunction of system components and injury can result.
Trademark
DeviceNet™ is a trademark of ODVA. EtherNet/IP™ is a trademark of ODVA. EtherCAT
®
is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
1. Use a watchmakers’ screwdriver with thin blade for the setting of each switch of the SI unit. When setting the switch, do not touch other unrelated parts.
This may cause parts damage or malfunction due to a short circuit.
2.
Provide adequate setting for the operating conditions.
Failure to do so could result in malfunction. Refer to the operation manual for setting of the switches.
3. For details on programming and address setting, refer to the manual from the PLC manufacturer.
The content of programming related to protocol is designed by the manufacturer of the PLC used.
4. For the EX260-SPN, the side of the SI unit may become hot.
It may cause burns.
1. When handling and replacing the unit:
Do not apply excessive force to the unit when disassembling.
The connecting portions of the unit are firmly joined with seals.
When joining units, take care not to get fingers caught between units.
Injury can result.
2. Perform periodic inspection.
Unexpected malfunction in the system composition devices is likely to occur due to malfunction of machinery or equipment.
3. A fter maintenance, make sure to perform an appropriate functionality inspection.
In cases of abnormality such as faulty operation, stop operation. Unexpected malfunction in the system composition devices is likely to occur.
4. Do not use benzene and thinner for cleaning units.
Damage to the surface or erasure of the display can result. Wipe off any stains with a soft cloth. If the stain is persistent, wipe off with a cloth soaked in a dilute solution of neutral detergent and wrung out tightly, and then finish with a dry cloth.
Other
1. Refer to the catalog of each series for Common Precautions and Specific Product Precautions on manifold solenoid valves.
Caution
Caution
Caution
Warning
EX260 Series

Specific Product Precautions 3

Be sure to read this before handling the products. Refer to back page 50 for Safety Instructions and pages 3 to 9 for 3/4/5 Port Solenoid Valve Precautions.
800
Page 13
Contact our sales office for delivery dates and prices as this is a special model.
Specialized Product
IO-Link Compatible SI Unit
EX260-SIL1-X207/X210
IO-Link communication enables users to check
Features
PLC
unit information and monitor unit status, in addition to ON/OFF valve control.
PC
Point to Group
P. G . information
IO-Link is an open communication inter­face technology between the sensor/actu­ator and the I/O terminal that is an inter­national standard IEC61131-9.
Various fieldbusses
IO-Link master
IO-Link communication
IO-Link Compatible Device: SI Unit EX260-SIL1-X207/X210
Send and receive ON/OFF signals + unit information/status
Sending and receiving of unit information, error detection, or condition monitoring data
<Unit Information> Manufacturer’s name, product number, version information <Error Detection> Output wiring disconnection, short circuit <Conditioning Monitoring> Number of valve operations, operation threshold exceeded
Application Example
Supporting periodic cylinder maintenance
The replacement time of the cylinder connected to the valve can be predicted by counting the number of valve operation instructions. This enables periodic maintenance to be performed before any unexpected cylinder failure occurs.
Currently at 10 million
operations
Currently at 5 million
operations
Port class B compliant: X210
Port class A compliant: X207
Supports data update cycles of 1 ms or less
Shortest data update cycle: 0.8 ms
The data update cycle can be set for the IO-Link master based on the SI unit’s shortest data update cycle of 0.8 ms.
IO-Link master and SI unit can be connected with one cable
Signal wire and valve power supply wire can be connected with the same cable.
Also applicable to the types in which the signal wire and valve power supply wire are connected with individual cables. (Port class A compliant: X207 specifications)
(Port class B compliant: X210 specifications)
Uses 4-wire or 5-wire unshielded cables
Special communication cables are not necessary.
A conventional 4-wire or 5-wire unshielded cable can be used for input and output of sensors, switches, etc. (Recommended specifications: Conductor resistance 3 Ω, Wire­to-wire capacitance 3 nF or less, 20 m or less)
Caution
©2017 SMC Corporation All Rights Reserved
To ensure the safest possible operation of this product, please be sure to thoroughly read the “Safety Instructions” in our “Best Pneumatics” catalog before use.
4-14-1, SOTO-KANDA, CHIYODA-KU, TOKYO 101-0021, JAPAN
URL: http://www.smcworld.com
SP165X-022E
P: VS
Page 14
IO-Link Compatible SI Unit
EX260-SIL1-X207/X210
Specifications
Specialized Product
Point to Group
P. G . information
Item
Protocol IO-Link version 1.1
Communication speed COM2 (38.4 kbps)/COM3 (230.4 kbps) (Selected by DIP switch)
IO-Link port class (Communication connector)
IO-Link type Device
Vendor ID 131
Process data size 0 byte input/4 bytes output
Number of outputs 32 outputs
Output type PNP (Negative common)/Source
Connected load Solenoid valve with surge voltage suppressor of 24 VDC and 1.5 W or less (manufactured by SMC)
Output
Solenoid valve power supply
Residual voltage 0.4 VDC or less
Control unit power supply
Weight 200 g or less
Standards CE marking, UL/CSA
(Valve power supplied from the valve power supply connector)
EX260-SIL1-X207 EX260-SIL1-X210
Class A
(Valve power supplied from the communication connector)
22.8 to 26.4 VDC
2 A or less (according to the solenoid valve station specification)
18 to 30 VDC
0.1 A or less
Class B
IODD files are required to configure this product. Please contact SMC for the IODD files. Also, please contact SMC for the operation manual.
Wiring Specifications
Suffix Communication connector Power supply connector for solenoid valve
M12 4-pin plug, A-coded M12 5-pin plug, A-coded
No.
X207
X210
No.
1 2 3 4
M12 5-pin plug, A-coded
No.
1 2 3 4 5
Designation
L+ +24 V for control unit
Unused
L− 0 V for control unit
C/Q IO-Link communication data
Designation
L+ +24 V for control unit
SV24V +24 V for solenoid valve
L− 0 V for control unit
C/Q IO-Link communication data
SV0V 0 V for solenoid valve
Description
Description
Designation
Unused
1
SV24V +24 V for solenoid valve
2
Unused
3
Unused
4
SV0V 0 V for solenoid valve
5
Description
Page 15
Output connector (34 pins, Receptacle)
Output common (0 V)
Solenoid output 0 Solenoid output 2 Solenoid output 4 Solenoid output 6
Solenoid output 8 Solenoid output 10 Solenoid output 12 Solenoid output 14 Solenoid output 16 Solenoid output 18 Solenoid output 20 Solenoid output 22 Solenoid output 24 Solenoid output 26 Solenoid output 28 Solenoid output 30
Output common (0 V)
Solenoid output 1 Solenoid output 3 Solenoid output 5 Solenoid output 7
Solenoid output 9 Solenoid output 11 Solenoid output 13 Solenoid output 15 Solenoid output 17 Solenoid output 19 Solenoid output 21 Solenoid output 23 Solenoid output 25 Solenoid output 27 Solenoid output 29 Solenoid output 31
DescriptionDesignationNo. DescriptionDesignationNo.
Communication connector
Ground terminal (M3)
Power supply connector (PWR)
Output connector (34 pins)
IO-Link Compatible SI Unit
EX260-SIL1-X207/X210
How to Order
Specialized Product
Point to Group
P. G . information
EX260
Communication protocol
IL
Output specification
32 outputs, PNP (Negative common)/Source
1
IO-Link
1S IL
X207
IO-Link port class
X207
X210
IO-Link port Class A, Valve power supplied from another connector
IO-Link port Class B
Dimensions [mm]
EX260-SIL1-X207 (The X210 is not provided with a power supply connector.)
Caution
• For dimensions when combined with the valve manifold, use the
dimensions of the valve manifold where the standard EX260 series unit is mounted.
• Order the valve manifold separately. Specify “no SI unit” and “negative
common” for the valve manifold specifications.
Loading...