SI Unit Specifications
Model
EX260-SPR1/3 EX260-SPR2/4 EX260-SPR5/7 EX260-SPR6/8 EX260-SDN1/3 EX260-SDN2/4 EX260-SMJ1/3 EX260-SMJ2/4
125 k/250 k/500 kbps
156 k/625 k/
2.5 M/5 M/10 Mbps
M12
Built-in
—
—
22.8 to 26.4 VDC
11 to 25 VDC
100 mA or less
Applicable
system
I/O occupation area
(Inputs/Outputs)
Communication speed
Power supply
for control
Power supply for output
Communication connector specification
Terminating resistor switch
Power supply for
communication
Output
Environmental
resistance
Standards
Weight
Mounting screw
Accessories
IP67 IP40 IP67
–10 to 50°C
35 to 85%RH (No condensation)
500 VAC for 1 minute between terminals and housing
10 MΩ or more (500 VDC measured via megohmmeter) between terminals and housing
CE marking, UL (CSA) compatible
200 g
2 pcs.
24 VDC
Power supply voltage
Internal current consumption
Power supply voltage
Power supply voltage
Internal current consumption
Protocol
Version
Note 1)
Configuration file
Note 3)
Supplied current
Output type
Number of outputs
Load
Supplied voltage
Enclosure
Operating temperature range
Operating humidity range
Withstand voltage
Insulation resistance
Seal cap (for M12
connector socket)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
SPR1: 32 points
SPR3: 16 points
SPR2: 32 points
SPR4: 16 points
SPR5: 32 points
SPR7: 16 points
SPR6: 32 points
SPR8: 16 points
SDN1: 32 points
SDN3: 16 points
SDN2: 32 points
SDN4: 16 points
SPR1: 0/32
SPR3: 0/16
SPR2: 0/32
SPR4: 0/16
SPR5: 0/32
SPR7: 0/16
SPR6: 0/32
SPR8: 0/16
SDN1: 0/32
SDN3: 0/16
SDN2: 0/32
SDN4: 0/16
SMJ1: 32/32
SMJ3:
32/32
(1 station, remote I/O stations)
SMJ2: 32/32
SMJ4:
32/32
(1 station, remote I/O stations)
SPR1: Max. 2.0 A
SPR3: Max. 1.0 A
SPR2: Max. 2.0 A
SPR4: Max. 1.0 A
SPR5: Max. 2.0 A
SPR7: Max. 1.0 A
SPR6: Max. 2.0 A
SPR8: Max. 1.0 A
SDN1: Max. 2.0 A
SDN3: Max. 1.0 A
SDN2: Max. 2.0 A
SDN4: Max. 1.0 A
EX9-AWTS (1 pc.) — EX9-AWTS (1 pc.)
D-sub M12
None Built-in
Volume 1(Edition 3.5)
Volume 3(Edition 1.5)
9.6 k/19.2 k/45.45 k/93.75 k/
187.5 k/500 k/1.5 M/3 M/6 M/12 Mbps
21.6 to 26.4 VDC
100 mA or less
—
—
—
—
21.6 to 26.4 VDC
100 mA or less
PROFIBUS DP
DeviceNet™
CC-Link
DP-V0 Ver.1.10
—
GSD file EDS file
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
SMJ1: 32 points
SMJ3: 16 points
SMJ2: 32 points
SMJ4: 16 points
SMJ1: Max. 2.0 A
SMJ3: Max. 1.0 A
SMJ2: Max. 2.0 A
SMJ4: Max. 1.0 A
Solenoid valve with protective circuit for surge voltage of 24 VDC/1.5 W or less (SMC)
Model
EX260-SEC1/3 EX260-SEC2/4 EX260-SPN1/3 EX260-SPN2/4 EX260-SEN1/3 EX260-SEN2/4
Applicable
system
I/O occupation area
(Inputs/Outputs)
Communication speed
Power supply
for control
Power supply for output
Communication connector specification
Terminating resistor switch
Power supply for
communication
Output
Environmental
resistance
Standards
Weight
Mounting screw
Accessories
IP67
–10 to 50°C
35 to 85%RH (No condensation)
500 VAC for 1 minute between terminals and housing
CE marking, UL (CSA) compatible
200 g
2 pcs.
10 MΩ or more (500 VDC measured via megohmmeter) between terminals and housing
24 VDC
Power supply voltage
Internal current consumption
Power supply voltage
Power supply voltage
Internal current consumption
Protocol
Version
Note 1)
Configuration file
Note 3)
Supplied voltage
Output type
Number of outputs
Load
Supplied voltage
Enclosure
Operating temperature range
Operating humidity range
Withstand voltage
Insulation
resistance
Seal cap (for M12
connector socket)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
Source/PNP
(Negative common)
Sink/NPN
(Positive common)
SEC1: 32 points
SEC3: 16 points
SEC2: 32 points
SEC4: 16 points
SPN1: 32 points
SPN3: 16 points
SPN2: 32 points
SPN4: 16 points
SEN1: 32 points
SEN3: 16 points
SEN2: 32 points
SEN4: 16 points
SEC1: 0/32
SEC3: 0/16
SEC2: 0/32
SEC4: 0/16
SPN1: 0/32
SPN3: 0/16
SPN2: 0/32
SPN4: 0/16
SEN1: 16/32
SEN3: 16/16
SEN2: 16/32
SEN4: 16/16
SEC1: Max. 2.0 A
SEC3: Max. 1.0 A
SEC2: Max. 2.0 A
SEC4: Max. 1.0 A
SPN1: Max. 2.0 A
SPN3: Max. 1.0 A
SPN2: Max. 2.0 A
SPN4: Max. 1.0 A
SEN1: Max. 2.0 A
SEN3: Max. 1.0 A
SEN2: Max. 2.0 A
SEN4: Max. 1.0 A
EX9-AWTS (1 pc.)
Volume 1(Edition 3.8)
Volume 2(Edition 1.9)
21.6 to 26.4 VDC
100 mA or less
22.8 to 26.4 VDC
—
—
M12
None (Not required)
10 M/100 Mbps
Note 2)
100 Mbps
Note 2)
EtherCAT
Note 2)
EtherNet/IP™
Note 2)
Conformance
Test Record V.1.1
XML file
PROFINET
Note 2)
PROFINET Specification
Version 2.2
GSD file EDS file
Solenoid valve with protective circuit for surge
voltage of 24 VDC/1.5 W or less (SMC)
Solenoid valve with protective circuit for surge
voltage of 24 VDC/1.0 W or less (SMC)
Solenoid valve with protective circuit for surge
voltage of 24 VDC/1.5 W or less (SMC)
EX260-SPL1 EX260-SPL3
Source/PNP
(Negative common)
32 16
16/32 16/16
Max. 2 A Max. 1 A
EPSG DS 301 Version 1.2.0
100 Mbps
Note 2)
POWERLINK
XDD file
Note 1) Please note that the version is subject to change.
Note 2) Use a CAT5 or higher transmission cable for EtherCAT, PROFINET, EtherNet/IP™, POWERLINK.
Note 3) Each file can be downloaded from the SMC website, http://www.smcworld.com