SMC Networks EX250-SCF1-X200 Operation Manual

Page 1
No.EX※※-OMU1012
PRODUCT NAME
SI unit for CC-Link IE Field
MODEL / Series / Product Number
EX250-SCF1-X200
Page 2
-1-
No.EX※※-OMU1012
Table of Contents
Safety Instructions 2 Product Summary 7 Model Indication and How to Order 8 Summary of Product elements 8 Mounting and Installation 9
Wiring 9 Setting 13 Maintenance 18 Troubleshooting 19 Specification 22
Specifications 22
Dimensions 24 Option 25
Refer to the operation manual EX250-IE1/-IE2/-IE3 for the input block specifications, and EX9-OET1/-OET2/-OEP1/-OEP2/-PE1 for the output block and power block specifications.
Page 3
-2-
No.EX※※-OMU1012
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or equipment damage. These instructions indicate the level of potential hazard with the labels of "Caution", "Warning" or "Danger". They are all important notes for safety and must be followed in addition to International Standards (ISO/IEC)*1), and other safety regulations.
*1) ISO 4414: Pneumatic fluid power -- General rules relating to systems.
ISO 4413: Hydraulic fluid power -- General rules relating to systems. IEC 60204-1: Safety of machinery -- Electrical equipment of machines .(Part 1: General requirements) ISO 10218-1992: Manipulating industrial robots -Safety. etc.
Caution
Caution indicates a hazard with a low level of risk which, if not avoided, could
result in minor or moderate injury.
Warning
Warning indicates a hazard with a medium level of risk which, if not avoided,
could result in death or serious injury.
Danger
Danger indicates a hazard with a high level of risk which, if not avoided, will
result in death or serious injury.
Warning
1. The compatibility of the product is the responsibility of the person who designs the equipment or decides its specifications.
Since the product specified here is used under various operating conditions, its compatibility with specific equipment must be decided by the person who designs the equipment or decides its specifications based on necessary analysis and test results. The expected performance and safety assurance of the equipment will be the responsibility of the person who has determined its compatibility with the product. This person should also continuously review all specifications of the product referring to its latest catalog information, with a view to giving due consideration to any possibility of equipment failure when configuring the equipment.
2. Only personnel with appropriate training should operate machinery and equipment.
The product specified here may become unsafe if handled incorrectly. The assembly, operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced.
3. Do not service or attempt to remove product and machinery/equipment until safety is confirmed.
1. The inspection and maintenance of machinery/equipment should only be performed after measures to
prevent falling or runaway of the driven objects have been confirmed.
2. When the product is to be removed, confirm that the safety measures as mentioned above are
implemented and the power from any appropriate source is cut, and read and understand the specific product precautions of all relevant products carefully.
3. Before machinery/equipment is restarted, take measures to prevent unexpected operation and malfunction.
4. Contact SMC beforehand and take special consideration of safety measures if the product is to be used in any of the following conditions.
1. Conditions and environments outside of the given specifications, or use outdoors or in a place
exposed to direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space, shipping,
vehicles, military, medical treatment, combustion and recreation, or equipment in contact with food and beverages, emergency stop circuits, clutch and brake circuits in press applications, safety equipment or other applications unsuitable for the standard specifications described in the product catalog.
3. An application which could have negative effects on people, property, or animals requiring special
safety analysis.
4. Use in an interlock circuit, which requires the provision of double interlock for possible failure by using
a mechanical protective function, and periodical checks to confirm proper operation.
Page 4
-3-
No.EX※※-OMU1012
Safety Instructions
Caution
1.The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in manufacturing industries. If considering using the product in other industries, consult SMC beforehand and exchange specifications or a contract if necessary. If anything is unclear, contact your nearest sales branch.
Limited warranty and Disclaimer/Compliance Requirements
The product used is subject to the following "Limited warranty and Disclaimer" and "Compliance Requirements". Read and accept them before using the product.
Limited warranty and Disclaimer
1. The warranty period of the product is 1 year in service or 1.5 years after the product is delivered,whichever is first.2) Also, the product may have specified durability, running distance or replacement parts. Please consult your nearest sales branch.
2. For any failure or damage reported within the warranty period which is clearly our responsibility, a replacement product or necessary parts will be provided. This limited warranty applies only to our product independently, and not to any other damage incurred due to the failure of the product.
3. Prior to using SMC products, please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products.
2) Vacuum pads are excluded from this 1 year warranty.
A vacuum pad is a consumable part, so it is warranted for a year after it is delivered. Also, even within the warranty period, the wear of a product due to the use of the vacuum pad or failure due to the deterioration of rubber material are not covered by the limited warranty.
Compliance Requirements
1. The use of SMC products with production equipment for the manufacture of weapons of
mass destruction (WMD) or any other weapon is strictly prohibited.
2. The exports of SMC products or technology from one country to another are govemed by the
relevant security laws and regulation of the countries involved in the transaction. Prior to the shipment of a SMC product to another country, assure that all local rules goveming that export are known and followed.
Page 5
-4-
No.EX※※-OMU1012
Operator
This operation manual is intended for those who have knowledge of machinery using pneumatic
equipment, and have sufficient knowledge of assembly, operation and maintenance of such equipment. Only those persons are allowed to perform assembly, operation and maintenance.
Read and understand this operation manual carefully before assembling, operating or providing
maintenance to the product.
Safety Instructions
Warning
Do not disassemble, modify (including changing the printed circuit board) or repair.
An injury or failure can result.
Do not operate the product outside of the specifications.
Do not use for flammable or harmful fluids. Fire, malfunction, or damage to the product can result. Verify the specifications before use.
Do not operate in an atmosphere containing flammable or explosive gases.
Fire or an explosion can result. This product is not designed to be explosion proof.
If using the product in an interlocking circuit:
Provide a double interlocking system, for example a mechanical system.
Check the product regularly for proper operation.
Otherwise malfunction can result, causing an accident.
The following instructions must be followed during maintenance:
Turn off the power supply.
Stop the air supply, exhaust the residual pressure and verify that the air is released before
performing maintenance.
Otherwise an injury can result.
Caution
After maintenance is complete, perform appropriate functional inspections.
Stop operation if the equipment does not function properly. Safety cannot be assured in the case of unexpected malfunction.
Provide grounding to assure the noise resistance of the Serial System.
Individual grounding should be provided close to the product with a short cable.
Page 6
-5-
No.EX※※-OMU1012
NOTE
Follow the instructions given below when designing, selecting and handling the product.
The instructions on design and selection (installation, wiring, environment, adjustment, operation,
maintenance, etc.) described below must also be followed.
Product specifications
When conformity to UL is required, the SI unit should be used with a UL1310 Class 2 power supply.
The SI unit is a UL approved product only if they have a mark on the body.
Use the specified voltage.
Otherwise failure or malfunction can result.
Reserve a space for maintenance.
Allow sufficient space for maintenance when designing the system.
Do not remove any nameplates or labels.
This can lead to incorrect maintenance, or misreading of the operation manual, which could cause damage or malfunction to the product. It may also result in non-conformity to safety standards.
Product handling
Installation
Do not drop, hit or apply excessive shock to the fieldbus system.
Otherwise damage to the product can result, causing malfunction.
Tighten to the specified tightening torque.
If the tightening torque is exceeded the mounting screws may be broken. IP67 protection cannot be guaranteed if the screws are not tightened to the specified torque.
Never mount a product in a location that will be used as a foothold.
The product may be damaged if excessive force is applied by stepping or climbing onto it.
Wiring
Avoid repeatedly bending or stretching the cables, or placing heavy load on them.
Repetitive bending stress or tensile stress can cause breakage of the cable.
Wire correctly.
Incorrect wiring can break the product.
Do not perform wiring while the power is on.
Otherwise damage to the fieldbus system and/or I/O device can result, causing malfunction.
Do not route wires and cables together with power or high voltage cables.
Otherwise the fieldbus system and/or I/O device can malfunction due to interference of noise and surge voltage from power and high voltage cables to the signal line. Route the wires (piping) of the fieldbus system and/or I/O device separately from power or high voltage cables.
Confirm proper insulation of wiring.
Poor insulation (interference from another circuit, poor insulation between terminals, etc.) can lead to excess voltage or current being applied to the product, causing damage.
Take appropriate measures against noise, such as using a noise filter, when the fieldbus system is
incorporated into equipment.
Otherwise noise can cause malfunction.
Page 7
-6-
No.EX※※-OMU1012
Environment
•Select the proper type of protection according to the environment of operation.
IP67 protection is achieved when the following conditions are met.
(1) The units are connected properly with fieldbus cable with M12 connector and power cable with M12/M8
connector.
(2) Suitable mounting of each unit and manifold valve.
If using in an environment that is exposed to water splashes, please take measures such as using a cover.
•Do not use in a place where the product could be splashed by oil or chemicals.
If the product is to be used in an environment containing oils or chemicals such as coolant or cleaning solvent, even for a short time, it may be adversely affected (damage, malfunction etc.).
•Do not use the product in an environment where corrosive gases or fluids could be splashed.
Otherwise damage to the product and malfunction can result.
•Do not use in an area where surges are generated.
If there is equipment which generates a large amount of surge (solenoid type lifter, high frequency induction furnace, motor, etc.) close to the SI unit, this may cause deterioration or breakage of the internal circuit of the SI unit. Avoid sources of surge generation and crossed lines.
•When a surge-generating load such as a relay or solenoid is driven directly, use an SI unit with a built-in surge absorbing element.
Direct drive of a load generating surge voltage can damage the SI unit.
•The product is CE marked, but not immune to lightning strikes. Take measures against lightning strikes
in the system.
•Prevent foreign matter such as remnant of wires from entering the SI unit to avoid failure and malfunction.
Otherwise failure or malfunction can result.
•Mount the product in a place that is not exposed to vibration or impact.
Otherwise failure or malfunction can result.
•Do not use the product in an environment that is exposed to temperature cycle.
Heat cycles other than ordinary changes in temperature can adversely affect the inside of the product.
•Do not expose the product to direct sunlight.
If using in a location directly exposed to sunlight, shade the product from the sunlight. Otherwise failure or malfunction can result.
•Keep within the specified ambient temperature range.
Otherwise malfunction can result.
•Do not operate close to a heat source, or in a location exposed to radiant heat.
Otherwise malfunction can result.
Adjustment and Operation
•Set the switches by using a sharp-pointed screwdriver etc.
It may damage set switches.
•Perform settings suitable for the operating conditions.
Incorrect setting can cause operation failure. For details of each setting, refer to page 14 of this manual.
•Please refer to the PLC manufacturer's manual etc. for details of programming and addresses.
For the PLC protocol and programming refer to the relevant manufacturer's documentation.
Maintenance
Turn off the power supply, stop the supplied air, exhaust the residual pressure and verify the release of air before performing maintenance.
There is a risk of unexpected malfunction.
Perform regular maintenance and inspections.
There is a risk of unexpected malfunction.
After maintenance is complete, perform appropriate functional inspections.
Stop operation if the equipment does not function properly. Otherwise safety is not assured due to an unexpected malfunction or incorrect operation.
Do not use solvents such as benzene, thinner etc. to clean the each unit.
They could damage the surface of the body and erase the markings on the body. Use a soft cloth to remove stains. For heavy stains, use a cloth soaked with diluted neutral detergent and fully squeezed, then wipe up the stains again with a dry cloth.
Page 8
-7-
No.EX※※-OMU1012
Product Summary
System configuration
This system realizes the reduce wiring between the input and output equipment by connecting to CC-Link IE Field. CC-Link IE Field and the input and output equipment communicate through the SI unit. Up to 32 inputs can be connected to the SI unit using Input blocks. Up to 32 outputs  from combined EX9 Output blocks and valve manifolds can be connected to the SI unit.
1: The maximum output point is 24 when the Power block is connected. 2: Refer to the operation manual EX※※-OME0002 for the input block specifications, and EX※※-OMH0005 for the output block and
power block specifications.
Page 9
-8-
No.EX※※-OMU1012
Model Indication and How to Order
EX250-SCF1-X200
Special product
Communication protocol
CF
CC-Link IE Field
Summary of Product elements
No.
Element
Description
1
Communication connector (PORT1 (P1))
Connect with CC-Link IE Field communication line. 1
2
Communication connector (PORT2 (P2))
3
Power supply connector
Supplies power to the solenoid valve, the output block, SI unit and the input block.
1
4
Input block connector
Connects the input block.
5
Output block connector
Connects the solenoid valve, output block and etc.
6
Display
LED display shows the SI unit status. 2
7
Switch protective cover
Set Station no. and Network No. by using the switches under the cover. 2
8
Ground terminal (FE)
Used for grounding.
1: Refer to page 9 for Wiring. 2: Refer to page 13 for the Setting.
Page 10
-9-
No.EX※※-OMU1012
Mounting and Installation
Wiring
Power supply wiring
Power supply line inside the SI unit has individual power supplies for solenoid valve actuation (SV power supply) and for control parts and input block (SW power supply). Supply 24 VDC for each of them.
: In case of single power supply, pay attention to the range of each supply voltage.
Power for sensor is supplied to sensor connected with input block. Select sensor concerning voltage drop up to maximum 1 V inside the unit at this moment. If sensor requires 24 V, it is necessary to lower power supply voltage for sensor slightly or secure power supply for sensor separately without going through SI unit so that sensor input voltage can be 24 V with actual loading (allowable voltage of power supply: 19.2 to 28.8 V).
Page 11
-10-
No.EX※※-OMU1012
○Ground terminal
Connect the ground terminal to ground. Resistance to ground should be 100 ohms or less.
Page 12
-11-
No.EX※※-OMU1012
Communication connector
PORT1 (P1)/PORT2 (P2): M12 8pin socket X-Coding (CAT5e or more)
No.
Description
Function
1
TRD+ (0)
Data 0 is sent and received. (+)
2
TRD- (0)
Data 0 is sent and received. (-)
3
TRD+ (1)
Data 1 is sent and received. (+)
4
TRD- (1)
Data 1 is sent and received. (-)
5
TRD+ (3)
Data 3 is sent and received. (+)
6
TRD- (3)
Data 3 is sent and received. (-)
7
TRD- (2)
Data 2 is sent and received. (-)
8
TRD+ (2)
Data 2 is sent and received. (+)
Example of the cable with connector: NBC-MSX/1,0-94F SCO (Order No.1407467), 1 m
: NBC-MSX/2,0-94F SCO (Order No.1407468), 2 m : NBC-MSX/5,0-94F SCO (Order No.1407469), 5 m etc.
(PHOENIX CONTACT)
○Power supply connector
PWRM12 5pin Plug B-code
No.
Description
Function
1
SV24 V
+24 V power supply for solenoid valve
2
SV0 V
0 V power supply for solenoid valve
3
SW24 V
+24 V for power supply for control and input block
4
SW0 V
0 V for power supply for control and input block
5 E Earth
Example of the cable with connector: EX9-AC010-1 (1 m)
EX9-AC030-1 (3 m) EX9-AC050-1 (5 m) etc. (manufactured by SMC)
Page 13
-12-
No.EX※※-OMU1012
○Maintenance
Addition of input block
Remove the screws from the end plate to remove the plate.
Mount the additional tie rods (supplied with the input block).
Connect additional input block.
Re-mount the end plate that was removed, and tighten the screws to the specified tightening torque.
(0.6 Nm)
Replacing the SI unit
Remove the screws from the end plate and release the connection with the valve unit.
Replace the SI unit. (There is no need to remove the tie rod.)
Re-mount the input block and end plate that was removed, and tighten the screws to the specified
tightening torque. (0.6 Nm)
Precautions for maintenance (1) Turn off the power supply completely. (2) Check that there is no foreign matter inside the unit. (3) Check that there is no damage and no foreign matter on the gasket. (4) Tighten the screws to the specified torque.
If the unit is not assembled correctly, this may cause product failure due to foreign matter such as liquid and dust which may get into the unit.
○Assembly and disconnection of unit
Page 14
-13-
No.EX※※-OMU1012
Setting
LED indication
LED indication
LED status
Description
PW(V)
(Green)
ON
Normal power supply for solenoids
OFF
Insufficient power supply for solenoids (19 V or less)
PW
(Green)
ON
Normal mode Normal power supply for control and input
OFF
Insufficient power supply for control and input
Flickering
Unit test mode Test mode
ON
Test normal mode end
RUN
(Green)
ON
Operating normally
OFF
Node alarm occurs
D LINK (Green)
ON
Cyclic transmission being performed
OFF
Cyclic transmission stopped
ERR
(Red)
ON
Disconnected, test failure end (Unit test mode)
OFF
Operating normally
P1
LINK
(Green)
ON
Link-up
OFF
Link-down
L ER
(Red)
ON
Error frame received
OFF
Normal frame received
P2
LINK
(Green)
ON
Link-up
OFF
Link-down
L ER
(Red)
ON
Error frame received
OFF
Normal frame received
Page 15
-14-
No.EX※※-OMU1012
Switch setting
Station No., Network No. are set by the switch inside of the SI unit cover. Set parameters while the power of SI unit is OFF. The setting of each switches can be fixed after power is ON.
Station number setting
Setting
Setting range
x10
0 to C
x1
0 to 9
: The station number should be set within the range of 01 to C0 (120).
If the number is set to 00, or to C1 (121) or above, the “ERR” LED will turn on. Turn the power off, and correct the setting.
: "ERR" display blinks if the switch is operated which the power is ON.
Network No. setting
Setting
Description
Value
ON
1
Fixed value: 1
OFF
EEPROM SETTING
Set value
※:The value at shipment from the factory is “OFF”. ※:The value at shipment from the factory of EEPROM SETTING is “1”.
Page 16
-15-
No.EX※※-OMU1012
○I/O memory map and diagnostic information
(1) Occupation point of device parameter
Device type
Device name
Occupation size
Remote input
RX
32 points
Remote output
RY
32 points
Remote register
RWw
4 words
Remote register
RWr
4 words
Page 17
-16-
No.EX※※-OMU1012
(2) bit/word Area
bit area
RX
Description
RY
Description
RX0
Input signal 0
RY0
Output signal 0
RX1
Input signal 1
RY1
Output signal 1
RX2
Input signal 2
RY2
Output signal 2
: : : : RX1F
Input signal 31
RY1F
Output signal 31
word area
RWr
Details
RWw
Details
RWr0
System input
RWw0
Unused
RWr1
Error diagnostics (severe)
RWw1
Unused
RWr2
Error diagnostics (moderate)
RWw2
Unused
RWr3
Error diagnostics (light)
RWw3
Unused
Diagnostics information details
Register
BitNo.
Description
RWr0
0
Reserved
: 9 10
Error generation state flag
11
Remove READY
12
Reserved
:
15
RWr1
0
Unit internal error
:
15
RWr2
0
Unit internal error
1 2 3
Node number address setting out-of-range
4
Reserved
:
15
RWr3
0
Node number change
1
Abnormal power supply for output
2
Abnormal power supply for input
3
Latest parameter not-reflected
4
Network number change
5
Reserved
:
15
Page 18
-17-
No.EX※※-OMU1012
Output number assignment
Combinations of output data and valve manifold
: The output numbering refers to the solenoid position on the manifold and starts at zero. : Standard wiring of the manifold is for double-solenoid valves and the output number starts at the A side and then B side in that order
as shown in the figure a.
If a single-solenoid valve is mounted on the standard wiring manifold, the output number for the B side valve is skipped.
: Custom wiring for mixed mounting single-solenoid valves and double-solenoid valves can be specified with a Wiring Specification
Sheet. Example wiring is shown in the figure b.
: Bit status “0” and ”1” in the data corresponds to solenoid valve status OFF and ON (0: OFF, 1: ON), and the output number starts at
zero from LSB (least significant bit).
○Input number assignment
Input numbers start from 0, and will be assigned to the input blocks in order from the SI unit mounted side.
Page 19
-18-
No.EX※※-OMU1012
Maintenance
Mounting and wiring
Item to inspect
Criteria
Countermeasure
Confirm the connectors (communication, power supply) of SI unit securely connected.
No looseness.
Tighten the resistance. Confirm the connecting cable broken.
No appearance error
If any error is found on the appearance, replace the cable.
Replacement parts
Item to inspect
Criteria
Countermeasure
CC-Link IE Field applicable cable for moving part (when used)
No error on the appearance and conductive resistance value
If any error is found on the appearance or the conductive resistance, replace the cable. See the specification of a cable to be used for the conductive resistance.
SI unit
No error in operation and display
If any error is found in the operation or on the display, replace the unit.
Power supply
Item to inspect
Criteria
Countermeasure
Confirm the voltage satisfy the specified range. Measure the voltages at the both sides of the power supply for control and input block.
24 VDC ±20%
Investigate into the cause of voltage fluctuation, and take a countermeasure against it.
Confirm the voltage satisfy the specified range. Measure the voltages at the both sides of the power supply for solenoid valves.
24 VDC +10%/-5%
(Refer to “Electrical and
communication specifications”
on page 22.)
Investigate into the cause of voltage fluctuation, and take a countermeasure against it.
Page 20
-19-
No.EX※※-OMU1012
Troubleshooting
When SI unit does not operate properly, follow the flow chart below and resolve it.
SI unit
malfunction
Refer to fault
No.1
SI unit
PW(V) LED is OFF
SI unit
PW LED is OFF
SI unit
RUN LED is OFF
SI unit
D LINK LED is OFF
Refer to fault
No.2
Refer to fault
No.4
Refer to fault
No.5
SI unit
P1/P2 LINK LED
is OFF
Refer to fault
No.3
Yes No
Only the output
of the low-order bit
is not operating
Refer to fault
No.6
Solenoid valves not
operating correctly.
LED is OFF
Refer to fault
No.7
Refer to fault
No.8
Solenoid valves not
operating correctly.
LED is ON
Page 21
-20-
No.EX※※-OMU1012
Failure Problem
Fault No.1
Problem
Possible cause
Investigation method
Countermeasures
SI unit PW LED is OFF
Incorrect wiring of the power supply for CC-Link IE Field
Check the power supply cable connections and check for broken wires.
Tighten the power supply cable connection. (If the cable has a broken wire, replace the cable).
Correct the wiring of the power supply cable.
Failure of the power supply for CC-Link IE Field
Check the power supply voltage of the CC-Link IE Field power supply.
Supply 24 VDC ±20% to the power supply for the SI unit control unit.
Fault No.2
Problem
Possible cause
Investigation method
Countermeasures
SI unit PW (V) LED is OFF
Wiring of the solenoid valve power supply is defective
Check the power supply cable connections and check for broken wires.
Tighten the power supply cable connection. (If the cable has a broken wire, replace the cable).
Correct the wiring of the power supply cable.
Solenoid valve power supply failure
Check proper supply voltage of solenoid valve power supply.
Supply 24 VDC 10%/-5% to the solenoid valve power supply.
Fault No.3
Problem
Possible cause
Investigation method
Countermeasures
SI unit P1/P2 LINK LED turned OFF
CC-Link IE Field
communication
error with the CC-Link IE Field device one level above
Check the condition of the CC-Link IE Field device one level above.
Check and Supply power to the CC-Link IE Field device one level above.
Check the BUS IN side communication cable connections and check for broken wires.
Additionally tighten the communication cable wiring. (Replace the cable if it is broken.)
Check that there are no high voltage cables or equipment that generates noise around the communication cable and SI unit.
Take measures to keep the communication cable and SI unit away from noise sources.
Fault No.4
Problem
Possible cause
Investigation method
Countermeasures
SI unit RUN LED is OFF
SI unit failure
Replace the SI unit with a new one and operate to check the normal operation recovers.
Replace the SI unit with a new one.
Page 22
-21-
No.EX※※-OMU1012
Fault No.5
Problem
Possible cause
Investigation method
Countermeasures
SI unit D LINK LED turned OFF
Out of node number setting range
Check if the node number is outside of the node number setting range.
Set the node number within the setting range.
Node number setting duplication
Check if the node number is duplicated.
Set the node number so that it is not duplicated.
Construction of the PLC program and the connected model is different.
Check that the program construction of the PLC and the connected model is the same.
Align the model setting to the PLC program construction.
Node number not assigned
The node numbers assigned to the SI units are not registered in the PLC program.
Assign the SI unit node numbers to the PLC unit or connect the SI unit which is assigned in the PLC.
Fault No.6
Problem
Possible cause
Investigation method
Countermeasures
Only the output of the low-order bit is not operating.
No. of solenoids has exceeded the allowable number
Check that the number of solenoids has not exceeded the allowable number. The allowable number depends on the SI unit model and solenoid valve series.
Number of solenoids that can be mounted:
SY/SV/SO700 series: 32 points VQC series: 24 points
Change the number of solenoids to within the specification.
Fault No.7
Problem
Possible cause
Investigation method
Countermeasures
Solenoid valves do not operate correctly, solenoid valve LED is OFF
Defective connection between the SI unit and solenoid valve manifold
Check that the screws which connect the SI unit and the solenoid valve are not loose.
Tighten the screws while holding the SI unit and the solenoid valve manifold so that there is no gap between them. Tighten the screws to the specified torque. (Tighten the screws: 0.6 Nm)
Polarity of the solenoid valve and the SI unit output are not compatible
Check that the solenoid valve polarity specification and output polarity of the SI unit are compatible.
Use a solenoid valve polarity compatible with the output polarity of the SI unit.
Solenoid valve failure
Refer to the troubleshooting of the solenoid valve.
Refer to the troubleshooting of the solenoid valve.
Fault No.8
Problem
Possible cause
Investigation method
Countermeasures
Solenoid valves do not operate correctly, solenoid valve LED is ON
Polarity of the solenoid valve and the SI unit output are not compatible
Check that the solenoid valve polarity specification and output polarity of the SI unit are compatible.
Use a solenoid valve polarity compatible with the output polarity of the SI unit.
Page 23
-22-
No.EX※※-OMU1012
Specification
Specifications
General specification
Item
Specifications
Ambient temperature
-10 to 50 oC
Ambient humidity
35 to 85% RH (no condensation)
Storage temperature
-20 to 60 oC
Withstand voltage
500 VAC applied for 1 minute
Insulation resistance
500 VDC, 10 MΩ or more
Operating atmosphere
No corrosive gas
Enclosure
IP65
Standard
CE marked
Weight
800 g or less
Electrical Communication specification
Item
Specifications
Applicable system
CC-Link IE Field
Station type
Remote device station
Baud rate
1 Gbps
Station number assignment range
1 to 120
Network number assignment range
1 to 239
Configuration file
CSP+
Power supply voltage
Power supply for control and input block
19.2 to 28.8 VDC (24 VDC±20) Solenoid valve
22.8 to 26.4 VDC(24 VDC+10/-5)
Input specification
Input points
32 points
Applicable block
Input block 1
Power supply for block
Max.1 A
Output specification
Output points
32 points
Output type
Source / PNP (negative common)
Applicable block
Solenoid valve with surge voltage suppressor of 24 VDC and
1.5 W or less (manufactured by SMC) Output component 1
Residual voltage
0.3 VDC or less
Load current
Max. 2 A
Internal current consumption(Unit)
0.3 A or less
Page 24
-23-
No.EX※※-OMU1012
1: Applicable block
Part number
Remarks
Input block EX250-IE1
M12 connector, 2 inputs
EX250-IE2
M12 connector, 4 inputs
EX250-IE3
M12 connector, 2 inputs
Output component
EX9-OET1 2
M12 connector, 2 outputs, source / PNP (negative common) low wattage load
EX9-OEP1
M12 connector, 2 outputs, source / PNP (negative common) high wattage load
EX9-PE1 2
M12 connector, power block
2: Applicable output component to one station on U side.
Part number
Remarks
EX9-OET1-X31
CC-Link IE Field compatible EX9-PE1-X31
Applicable solenoid valves
Representative series
Applicable series
SY series
SY3000, SY5000, SY7000
VQC series
VQC1000, VQC2000, VQC4000
SV series
SV1000, SV2000, SV3000 (Tie rod base manifold)
S0700 series
S0700
Page 25
-24-
No.EX※※-OMU1012
Dimensions
Page 26
-25-
No.EX※※-OMU1012
Option
1. Power supply cable
Cable outer diameter
6.4
Wire gauge
0.3 mm2/AWG22
Wire outer diameter
1.65 mm
Minimum bending radius
40 mm (Fixed)
2. End plate (Input block side)
EX250-EA1
EX250-EA2
3. End Plate R (Output side)
EX9-EA03
EX9-EA04
Page 27
-26-
No.EX※※-OMU1012
4. Waterproof cap
Mounted on the unused ports of the Input block, Output block and Power block. Proper use of this waterproof cap can achieve IP67 enclosure. (The waterproof caps are delivered together with the Power block as accessories.)
Note
Tighten the waterproof cap with the specified tightening torque. (0.05 Nm for M8,0.1 Nm for M12)
Page 28
No.EX※※-OMU1012
Revision history
4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021 JAPAN Tel: + 81 3 5207 8249 Fax: +81 3 5298 5362 URL http://www.smcworld.com
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2016 SMC Corporation All Rights Reserved.