These safety instructions are intended to prevent a hazardous situation and/or equipment damage. These instructions indicate
the level of potential hazard by label of "CAUTION" , "WARNING".
To ensure safety, be sure to observe ISO, JIS and other safety practices.
Doc.No.EX
##-OME0015
CAUTION: Operator error could result in injury or equipment damage.
WARNING: Operator error could result in serious injury or loss of life.
CAUTION
Thoroughly read this manual and operate the product within the specified range. Follow the instructions.
Do not drop or impart any impact to the product.
Use within specified voltage range. Use outside of specified voltage will cause malfunction, damage of unit, electric shock, and
fire.
Do not touch the terminal or internal circuit board while they are energized. It may cause malfunction, damage to unit, and
electric shock.
Use within operating ambient temperature. Do not use where temperature can rapidly change even thought it is within the
specifications.
Foreign objects should be prevented from entering the product. Contamination by foreign objects, such as wire chips will cause
fire, breakage, and malfunction.
Use within the operating environment of the protection structure. In case of IP20, avoid use in the place where water and oil
scatter. To realize IP65, install manifold properly and give some prevention against splash of liguid to electrical entry.
Carry out periodical checks to confirm correct operation. Safety may not be maintained by unintentional malfunction or incorrect
operation. Design must consider the space necessary for maintenance.
As the contents of this manual is sometimes changed without the previous announcement, understand them beforehand,
please.
SI unit is not explosion proof. Operation in explosive enviromment may cause explosion accident.
WARNING
The product specified here is designed to be used in standard factory automation equipment. Do not use in machinery and/or
equipment where operators may be injured, and malfunction or failure may cause loss of life.
Do not disassemble to repair or modify the product.
Connection
CAUTION
Power of the product and all other equipments should be turned off while wiring.
Tighten the wiring with connector and tarminal screw completely. Short circuit, fire, and malfunction will be caused if connector
and tarminal screw are not tightened enough.
Avoid incorrect wiring. It may damage the product and/or other equipments.
Ensure that the FG terminal is correctly grounded.
Power with correct capacity should be prepared by considering the in-rush current when starting.
Influence of noise should be avoided for the wiring. Wiring should be separated from power cables and high voltage cables.
Ensure that the power is within the specified voltage range.
Ensure that the cable is capable of supporting the solenoid valve and SI unit in terms of rating.
Applicable solenoid valves
CAUTION
SMC offers no guarantee against malfunction and damage of unit when valves not described to “2-3.Applicable solenoid
valve series” and loads which is not valve are connected.
- 3 -
Page 4
2. Specifications
2-1. General specifications
ItemSpecifications
ModelEX120
-SDN1
Operating ambient temp.0 to +55(with 8 points of valve ON)
0 to +50℃(with 16 points of valve ON)
Operating ambient humidity35 to 85%RH(No dew condensation)
Storage ambient temp.
-20 to +60℃
Vibration proof50m/s2 (comply with JIS C 0911)
Impact proof100m/s2 (comply with JIS C 0912)
Noise immunity
Normal mode ±1500 V Pulse 1µs
Common mode ±1500 V Pulse 1µs
Radiation 1000 V ±Pulse 1µs
Withstand voltageAC1000V for 1 min. between FG and external
terminal package.
Insulation resistanceDC500V, 2MΩ between FG and external terminal
package.
Operating environmentNo corrosive gas and no dust
Weight110g
or less
Protection classIP20IP65
EX121
-SDN1
140g
or less
EX122
-SDN1
130g
or less
EX124D
-SDN1
EX124U
-SDN1
240g
or less
SMC CORPORATION
Doc.No.EX
##-OME0015
2-2. Electrical and network specifications
ItemSpecifications
Applicable systemDeviceNet Release 2.0
Power supply voltage for communicationDC11V to DC25V
Power supply voltage for solenoid valveDC24V +10% -5%
Communication and
current
Internal power supply
Power supply for
Solenoid valve
Solenoid valve
Connection
Output styleNPN output (Open collector)
Connected loadDC24V, Solenoid valve with lamp-surge voltage
spec.
Insulation typeOpt-coupler insulation type
Residual voltage0.4V DC or less
Applicable DeviceNet
MAC ID setting range0 to 63 (Set by Dip switch)
Baud Rate (Transmission speed)500kbps, 250kbps, 125kbps (Set by Dip switch)
Slave (branch station) typeGroup 2 only server
Connection typeT branch type, Multi drop type
Device type16
Product code288
RevisionReferred to EDS file.
Vendor ID7
SI unitValve series
EX120VQ1000, VQ2000
EX121VQ1000, VQ2000, SX3000, SX5000
EX122SY3000, SY5000
EX124U/DVQ2000, VQ4000, VQ5000
2 byte
SMC CORPORATION
Doc.No.EX
##-OME0015
3. Wiring and Setting
3-1.Connection type
DeviceNet can be connected by T branch, Multi branch, Branch line branch and Multi drop. Total
extension length of trunk and Branch line is different for different Baud rate and thickness of
communication cable.
Main line
Terminal resistance
Multi branch
Branch
line
Node
Length of cable
Node
Node
NodeNode
Branch
line
T branch
Node
Branch
line
Terminal resistance
Branch line
branch
Node
Node
Node
Communication
distance
Thick cable
Baud rate
500 kbps 100m or less 39m or less
250 kbps 250m or less 78m or less
Total length of
trunk
branch line
6m or less
125 kbps 500m or less
Thin cable Common 100m or less
Terminal resistance 121 ohm (1/2W)
- 5 -
Length of
――――――
Total length of
branch line
156m or less
Page 6
Cable specification
Item
Conductor
cross section
ColorsBlue, W hiteRed, BlackBlue, White Red, Black
Impedance
Propagation
delay
Attenuation
rate
Conductor
resistance
Thick cable Thin cable
Communication
Signal
0.82 mm
120
2
Ω±
10%(1MHz)
Power upply
1.65 mm
――
Communication
2
10%(1MHz)
Signal
0.20 mm
Ω±
120
2
1.36ns / ft(max)――1.36ns / ft(max)
500k:0.25dB / ft
125k:0.13dB / ft
1.00M:0.40dB / ft
6.9Ω /
1000ft(max)
――
3.6Ω /
1000ft
(max)
500k:0.50dB / ft
125k:0.29dB / ft
1.00M:0.70dB / ft
28Ω /
1000ft(max)
SMC CORPORATION
Doc.No.EX
Power supply
0.33 mm
2
――
――
――
17.5Ω /
1000ft(max)
##-OME0015
CAUTION
For Multi drop connection, prepare plug connector for T branch separately.
(Example, TMSTBP 2.5...- STF -5.08 made by Phoenix Contact Corp.)
Use DeviceNet special cable for communication cable.
Be sure to connect DeviceNet special terminal resistor with both ends of trunk.
- 6 -
Page 7
Wiring of cable for solenoid valve power supply and communication
Communication connector for DeviceNet
TerminalWire colorConnected to
V-Black(-) side of power supply cable
CANLBlueLow side of communication cable
FG-Ground / Shield
CANHWhiteHigh side of communication cable
V+Red(+) side of power supply cable
SMC CORPORATION
Doc.No.EX
##-OME0015
Power supply connector for solenoid valve
TerminalWire colorConnected to
24V-(+) side of solenoid valve source supply
0V-(-) side of Solenoid valve source supply
CAUTION
• Before wiring, be sure to turn power supply off.
• Screw for connectors is M3. Tighten them properly by torque of 0.5 to 0.6 [N·m].
• SI unit isn’t available for monitoring of power supply for solenoid valve.
• Do not put cable specified by DeviceNet with/near high voltage line or strong
electric line such as driving line.
- 7 -
Page 8
3-2. Address setting
ON
Before setting of address by DIP switch, turn power supply for communication cable in SI
unit “OFF”.
Setting (binary) of following items is available by DIP switch installed to cover.
1) Node address (00 to 63)
2) Communication speed (125kbps, 250kbps, 500kbps)
<Setting of node address>
Node
address
SW1SW2SW3SW4SW5SW6
12481632
#0 000000
#1 100000
#2 010000
:
:
:
#62 011111
#63 111111
SMC CORPORATION
Doc.No.EX
##-OME0015
<Setting of communication speed>
SettingMax. transmission distance (m)
SW7SW8
00125500156
1025025078
01500125
11Not usedNot used
Communication
speed (kbps)
CAUTION
• When shipped, node address of 63 and communication speed of 125kbps are set in
advance.
• When communication error occurs, output condition is cleared.
Length of trunk
Thick
cable
Think
cable
Length
branch
line
1006
of
Total length
of
branch line
39
- 8 -
Page 9
4.LED indicator and Physical dimensions
1
1
0
8
0
32
0
0
0
1
1
STATION
ADDRESS
TRANSMIT
SPEED
125K
250K
500K
0
0
1
1
SWITCH
SETTINGS
ON
SERIAL UNIT
SMC
28.8
10.2
4-1 LED indication
SMC CORPORATION
Doc.No.EX
##-OME0015
EX120-SDN1
EX121-SDN1
EX124D-SDN1
EX124U-SDN1
EX122-SDN1
IndicationContents
PWRGreen Lights up when power for DeviceNet line is supplied.
Lights offSI unit isn’t on line or power supply for communication
line isn’t turned on.
MOD / NET
Green
flashing
Green
lights up
Red
flashing
Red
lights up
Waiting for connection (ON line)
Connection completed (ON line)
Connection time out (Minor communication error)
MAC ID duplication error or BUS OFF error
(Major communication error)
4-2 Physical dimensions
SI unit (EX120-SDN1)
SMC
SERIAL UNIT
SWITCH
SETTINGS
STATION
ADDRESS
TRANSMIT
SPEED
ON
1
1
0
2233445566778
11224488161632
0
00000000000
1100110000000
2211000000000
626211001111111
636311111111111
125K
250K
500K
000
110
001
111
10.2
28.8
- 9 -
Page 10
SI unit (EX121-SDN1)
1
1
0
8
0
32
0
0
0
1
1
STATION
ADDRESS
TRANSMIT
SPEED
125K
250K
500K
0
0
1
1
SWITCH
SETTINGS
ON
Flat cable length about 70mm
SERIAL UNIT
SMC
64
60.8
66.1
28.8
2
10.2
5.4
SMC
SERIAL UNIT
5.4
Flat cable length about 70mm
SMC CORPORATION
Doc.No.EX
##-OME0015
SWITCH
SETTINGS
STATION
ADDRESS
TRANSMIT
SPEED
66.1
60.8
64
SI unit (EX122-SDN1)
ON
1
1
0
2233445566778
11224488161632
0
00000000000
1100110000000
2211000000000
626211001111111
636311111111111
125K
250K
500K
000
110
001
111
10.2
28.8
2
- 10 -
Page 11
SI unit (EX124D-SDN1)
SI unit (EX124U-SDN1)
SMC CORPORATION
Doc.No.EX
##-OME0015
4-G(PF)1/2
19.8
19
67
(72.5)
114
5.5
53.8
11.6
- 11 -
Page 12
5.EDS (Electronic Data Sheet) File
SMC CORPORATION
Doc.No.EX
##-OME0015
The EDS File is a file which described ID information on SI unit and important information in the
operation.
The DeviceNet controller or scanner automatically recognizes the SI unit by referring to the EDS File.
* Please refer to the undermentioned list when DeviceNet controller or the scanner dose not
automatically recognize the EDS File.
$ Electronic Data Sheet File for
$ SMC EX120-SDN1 Serial Interface Unit
[File]
DescText = "SMC EX120-SDN1 EDS File";
CreateDate = 05-20-1999;$ created
CreateTime = 10:30:00;
Revision = 1.1;$ Revision of EDS
$ Cons. Cnxn=1
Input1 = 2,$ 2 byte
0,$ All bits are significant
0x0001,$ Poll Only Connection
"Solenoid Status",$ Name String
6,$ Path Size
"20 04 24 05 30 03",$ Assy Obj Inst 5 Attr 3
"";$ Help String
Output1 = 2,$ 2 byte
0,$ All bits are significant
0x0001,$ Poll Only Connection
"Solenoid Output",$ Name String
6,$ Path Size
"20 04 24 23 30 03",$ Assy Obj Inst 23 Attr 3
"";$ Help String
- 12 -
Page 13
6. Trouble Shooting
MOD/NET LED Cause & Countermeasure
Lights off PWR LED lights off
<Countermeasure>
Confirm that power for SI unit circuit is supplied.
Confirm correct wiring.
If above countermeasures do not improve status, please exchange SI unit.
PWR LED lights up
<Countermeasure>
Confirm that baud rate is set correctly.
If MOD/NET LED lights off in spite of baud rate is set correctly, change SI unit.
Green flashing Connection waiting
Shows communication waiting status between SI unit and master.
<Countermeasure>
Confirm master operate correctly.
If using scan list, ensure slave is recorded to scan list correctly.
Red flashing Communication wire disconnected error
<Countermeasure>
Confirm communication wire is not disconnected.
<Remark>
Red flashing if master power source is turned off during communication.
Red lights up Node address overlapping error
<Countermeasure>
Confirm there is no overlapping on the node address.
BUS OFF error
Detects communication error.
<Countermeasure>
Case 1
Communication error due to noise.
Confirm there is no component or high voltage cable that generate noise
around communication wire.
Make some distances between communication wire and noise source.
Case2
Communication cable problem.
Confirm terminal resistance (121ohm) connects to the both ends of
communication wire that is main wire of communication wire.
If red MOD/NET LED is still lights up in spite of above countermeasures,
change SI unit.
SMC CORPORATION
Doc.No.EX
##-OME0015
CAUTION
When red MOD/NET LED is lit, even if cause is solved, SI unit do not do auto-recovery. In
this case, please reset the power to SI unit circuit (Communication/Internal power supply).
SI unit isn’t available for monitoring of power supply for solved valve.
- 13 -