SMC Networks 56-EX500-S001, 56-EX500-S101, 56-EX500-Q001, 56-EX500-Q101 Installation & Maintenance Manual

Design and selection
Operate the unit only within the specified supply voltage limits.
If the supply voltage exceeds the rated voltage limits the unit and connected equipment might malfunction or could be damaged. It could also become a fire hazard.
Do not operate beyond specification range.
Fire, malfunction or unit and connected equipment damage can result.
Please construct a backup system, such as making the equipment or unit a multiple system, or designing a fail-safe in advance to prevent damage due to the breakdown and the malfunction of this product. Mount the emergency stop outside of the enclosure so that it can stop the system operation immediately and intercept the power supply. These instructions must be followed when using the Gateway unit in an interlocking circuit:
Provide valve interlocking by another system such as
mechanical protection.
Check the Gateway unit regularly to ensure mechanical
protection. There is a risk of getting injured if the interlock does not operate correctly.
Wiring
Perform wiring correctly.
There is a possibility that a unit and connected equipment will be destroyed if incorrectly wired.
Do not perform wiring while power is on.
If there is an explosive atmosphere present there is a risk of an explosion. There is also a possibility of failure of operation due to the damage of a unit and connected equipment.
Do not lay wires or cables with power cable or high-voltage cable in the same wiring route.
There is a possibility of failure of operation due to electrical noise on the signal cable or a surge in the power cable. Separate the wiring of reduced wiring system from power cables.
Confirm proper insulation of wiring.
With insulation failure (contact with other circuits, insulation failure between terminals, etc), there is a risk of explosion if an explosive atmosphere is present. There is also a possibility of damage to a unit and connected equipment due to the applied excess pressure or current.
Operating environment
Do not use in an environment where water, chemicals, or oil are present. Prevent dust and particles collecting on or around the unit.
It will cause failure or malfunction.
Do not use in an area where a magnetic field is generated.
It will cause malfunction.
Do not connect or disconnect cables when the unit is powered.
Fire or an explosion may result if an explosive or combustible gas is present.
Do not use in an environment with temperature cycle.
Heat cycles other than that of daily change of the temperature can effect inside of the units.
Do not expose the wiring system to heat radiation from a heat source located nearby.
It will cause failure or malfunction.
Do not use in an environment where a surge source more than the CE marking standard allow is present.
Internal circuit elements can deteriorate or break when equipment generating a large surge (electromagnetic lifter, high frequency induction furnace, motor, etc.) is located near the wiring system. Provide surge preventives, and avoid interface.
Use the wiring system equipment with surge absorber when a surge-generating load such as relay or solenoid valve is driven directly. Do not expose the wiring system to vibration and impact.
It will cause failure or malfunction.
Adjustment and Operation
Do not allow short circuit of loads.
Connected equipment may be damaged by excess current flow if a load is short circuit. Input unit fuse will break. Output and SI unit have protective function for excess current flow, but it is possible that they will be damaged, as the protective function does not cover all modes.
The SI unit should be used within the range of specifications given below and in the product catalogue.
If labelled with X: special conditions apply:
1. Protect the SI unit from sources of heat which can generate surface temperatures higher than the ATEX temperature classification.
2. Protect the SI unit and cables against all impact or mechanical damage using a suitable ATEX compliant enclosure.
3. Protect the SI unit from direct sunlight or UV light using a suitable protective cover.
4. Do not disconnect the M12 connectors before first switching off the power supply.
5. Use only ATEX approved M12 connectors and use only shielded cable to provide grounding.
6. Use only a damp cloth to clean the SI unit body, to avoid an electrostatic charge.
Mounting
Do not drop, bump or apply excessive impacts while handling.
Otherwise it can result in damage to the SI unit causing failure or malfunction.
Hold the body for handling.
Otherwise it can result in damage to the SI unit causing failure or malfunction.
Mount units using the proper tightening torque.
If a unit is tightened beyond the range of tightening torque, the mounting screws, mounting brackets or unit may be damaged
Do not mount the unit where it may be stepped on. If the unit is stepped on it will be damaged.
Wiring
Avoid repeatedly bending or stretching the lead wires.
Do not crush or strain the wire. It will cause the wire to break and make the unit malfunction
Ground the reduced wiring system to a secure, safe and noise-proof place
Grounding should be performed near the unit to shorten the grounding distance.
Maintenance
Only clean the product with a damp cloth.
Do not wipe the product with chemicals such as benzene or thinners. It will cause damage to the product.
Installation & Maintenance Manual
SI Unit
Series 56-EX500-S001/S101
Read this manual before using this product.
For future reference, please keep this manual in a safe place.
This manual should be read in conjunction with the current catalogue.
General recommendation
These safety instructions are intended to prevent a hazardous situation and/or equipment damage. These instructions indicate the level of potential hazard by label of "Caution", "Warning" or "Danger".
Operator error could result in injury or equipment damage.
Operator error could result in serious injury or loss of life.
In extreme conditions, there is a possible result of serious injury or loss of life.
A system designer or a person who decides a system
specification should judge the compatibility of a reduced wiring system.
Since the products specified here are used in various operating conditions,their compatibility for the specific
wire saving
system must be based on specifications or after analysis and/or tests to meet your specific requirements.
Only trained personnel should operate pneumatically operated
machinery and equipment.
Compressed air can be dangerous if an operator is unfamiliar with it Assembly, handling or repair of wire savingsystems should be performed by trained and experienced operators.
Do not service machinery/equipment or attempt to remove
component until safety is confirmed.
1) Inspection and maintenance of machinery/equipment should only be performed after confirmation of safe locked-out control positions.
2) When equipment is to be removed, confirm the safety process as mentioned above. Switch off air and electrical supplies.
3) Before machinery/equipment is re-started, ensure all safety measures to prevent sudden movement of actuators etc. (Supply air into the system gradually to create backpressure, i.e. incorporate a soft-start valve).
Contact SMC if the product is to be used in any of the following
conditions:
1) Conditions and environments beyond the given specifications, or if product is used outdoors.
2) Installations in conjunction with atomic energy, medical equipment, food and beverage, or safety equipment.
3) Applications which have the possibility of having negative effects on people, property or animals. Special safety analysis is required.
Do not carry out operation or setting of this equipment with wet hands.
It may cause an electric shock to the operator.
Maintenance
Do not disassemble, modify (including change of printed circuit board) or repair.
An injury or failure can result.
Perform the following maintenance periodically in order to prevent possible danger due to the unexpected.
Confirm wiring and screws are not loose. Loose screws or wires may cause unintentional malfunction.
These instructions must be followed while in maintenance:
Turn off the power supply.
Stop the supplied fluid, exhaust the residual pressure and verify
the
release of fluid before performing maintenance.
Otherwise it can cause injury.
56-EX500-Q 01
SI Unit for SV series Manifold Valve
SI Unit for VQC series Manifold Valve
EX500-TFJ09GB-B
Safety Instructions
Safety Instructions (continue)
Model Indication Method
Intended conditions of use
Design and selection
Ensure there is sufficient clearance for maintenance activities.
When designing an application, be sure to allow sufficient clearance for maintenance and inspections.
The direct current power supply to be used should be UL1310 class 2 power supply when conformity to UL is necessary.
56-EX500-S 01
:n
:n
:
Caution
Warning
Danger
Output specification 0 NPN output (+ COM.) 1 PNP output ( - COM.)
Output specification 0 NPN output (+ COM.) 1 PNP output ( - COM.)
ATEX Category 3
ATEX Category 3
II 3G Ex nA II T5 X 5ºCTa45ºC II 3D tD A22 IP67 T52ºC X
C`
ATEX Marking Description
II 3G Ex nA II T5 X 5ºCTa45ºC II 3D tD A22 IP67 T??ºC X
Equipment Group II
Category 3
Gas (G) and Dust (D) environment
Ex - European standards apply
nA - Non-sparking apparatus
II - for all types of gas
T5 - temperature classification
tD - protected by enclosure
A22 - for zone 22
IP67 - Protection structure
Ta - Ambient temperature
T??ºC - Max. surface temperature
X - special conditions apply, see
instructions
Series 56-EX500-Q001/Q101
II 3G Ex nA II T5 X 5ºCTa45ºC II 3D tD A22 IP67 T54ºC X
C`
Tighten the screws which hold the SI unit to the SUP / WXH Block assembly, with specified tightening torque (0.6Nm).
Refer to IMM of SV and VQC series for further details.
C
OM
P
W
R
C1
C2
56-EX500-S001/101
56-EX500-Q001/101
56-EX500-S001/101
56-EX500-Q001/101
EX500-TFJ09GB-B
Names and Functions of individual parts
Installation Outline with Dimensions
C
ommunication connector
M12 connector (8 pin, socket) : Connecting with Input Unit.
M
12 connector (8 pin, plug) : Connecting with Gateway Unit.
Connecting block
Solenoid valve (Single, Double)
R
ated voltage
2
4VDC
Current consumption
1
00mA or less (at rated voltage)
Ambient temperature /
humidity
+5 to 45 / 35% to 85%RH (without
c
ondensation)
Protection structure IP67
C
urrent supply for block
0
.3A Max.
W
eight
56-EX500-S001/101 : 115g
56-EX500-Q001/101 : 105g
56-EX500-S001/101 56-EX500-Q001/101
N
umber of connecting
block
Double solenoid valve : 8 block Max.
S
ingle solenoid valve : 16 block Max.
Specification
SUP/EXH Block Ass’y
M3X10: 2 pcs
Power Save Block
SI Unit for VQC series Manifold
Power LED
Communication LED
Communication connector
Connect to Input Unit
Connect to Gateway Unit
Communication connector
Power LED
Communication LED
Communication connector
Connect to Input Unit
Communication connector
Connect to Gateway Unit
SI Unit for VQC series Manifold
SI Unit for SV series Manifold
S
UP/EXH Block Ass’y
SI Unit for SV series Manifold
M3X30 : 4 pcs
AUSTRIA (43) 2262 62280 NETHERLANDS (31) 20 531 8888 BELGIUM (32) 3 355 1464 NORWAY (47) 67 12 90 20 CZECH REP.
(420) 541 424 611
POLAND (48) 22 211 9600 DENMARK (45) 7025 2900 PORTUGAL (351) 21 471 1880 FINLAND (358) 207 513513 SLOVAKIA (421) 2 444 56725 FRANCE (33) 1 6476 1000 SLOVENIA (386) 73 885 412 GERMANY (49) 6103 4020 SPAIN (34) 945 184 100 GREECE (30) 210 271 7265 SWEDEN (46) 8 603 1200 HUNGARY (36) 23 511 390 SWITZERLAND (41) 52 396 3131 IRELAND (353) 1 403 9000 UNITED KINGDOM (44) 1908 563888 ITALY (39) 02 92711
URL http://www.smcworld.com (Global) http://www.smceu.com (Europe)
Specifications are subject to change without prior notice from the manufacturer. © 2009 SMC Corporation All Rights Reserved.
Contact
P
ollution Degree
Pollution Degree 2
Loading...