Smart-UPS® RT
Uninterruptible Power Supply
SURT 8000/10000 VA
200-240 VAC
Tower/Rack-Mount 6U
English
2010 APC by Schneider Electric. APC, the APC logo, Sm art-UPS and PowerChute are own ed by Schneider Electr ic
Industries S.A.S., American Power Conversion Corporation, or affiliated companies. All other trademarks are the property of
their respective owners.
990-2689E 05/2010
Introduction
The APC® by Schneider Electric Smart-UPS® RT is a high-performance, uninterruptible power
supply (UPS) that provides protection for electronic equipment from utility power blackouts,
brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic
equipment from large disturbances by internally disconnecting from utility line power. The UPS
provides continuous power from the internal battery until utility power returns to safe levels or the
battery is fully discharged.
INSTALLATION
Read the safety information sheet before installation.
Unpacking
Inspect the UPS upon receipt. Notify the carrier
and dealer if there is damage.
The packaging is recyclable; save it for reuse or
dispose of it properly.
Check the package contents:
UPS (with batteries disconnected)
Two front bezels
Literature kit containing:
XLT/XLTW models only: Software CD
Smart-UPS User Manuals CD
XLI model only: Six output power cords
Serial cable
Product documentation, safety and
warranty i nformation
Network Management Card
documentation
Removing the Batteries
The unit is heavy. To lighten the unit, remove the batteries. Refer to the unpacking instructions on
the carton in which the unit is shipped.
Specifications
TEMPERATURE
OPERATING
TORAGE
S
MAXIMUM
ELEVATION
OPERATING
TORAGE
S
HUMIDITY 0% to 95% relative humidity, non-condensing
WEIGHT
UPS
UPS
WITH
PACKAGING
32° to 104° F (0° to 40° C)
5° to 113° F (-15 to 45 ° C) ch arge UPS battery every six months
10,000 ft (3,000 m)
50,000 ft (15,000 m)
244 lbs (111 kg)
284 lbs (129 kg)
This unit is intended for
indoor use only. Select a
location sturdy enough to
handle the weight.
Do not operate the UPS where
there is excessive dust or the
temperature and humidit y are
outside the specified limits.
Ensure the air vents on the
front and rear of the UPS
are not blocked.
1
Hardwiring
Wiring must be performed by a qualified electrician.
1. Install a utility circuit breaker in accordance with local electrical codes (see tables below) for
input wiring.
2. Switch the UPS input circuit breaker (see A) and utility circuit breakers OFF.
3. Remove the access panel (see B).
4. Remove circ ul ar knockouts.
5. Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all
national and local electrical codes. (See tables and graphics.)
6. Use appropriate strain-relief on the hardwired input and output power cables.
XLT, XLJ, AND XLTW MODELS
Input Connection Output Connection (optional)
Wire to L1, L2, and . Wire to L1A, L2A, a n d .
System Wiring Voltage
SURT8000XLJ,
SURT8000XLT,
Input &
Output
200/208/220/240 V 40 A
SURT8000XLTW
SURT10000XLJ,
SURT10000XLT,
Input &
Output
200/208/220/240 V
SURT10000XLTW
XLI MODELS
Input Connections Output Connection (optional)
Current
Full Load
(Nominal)
XLJ-50 A
XLT-48 A
XLTW-48 A
External Input Circuit
Breaker (typical)
50 A / 2-pole
for Input Wiring only
60 A or 63 A / 2-pole
for Input Wiring only
Wire Size
(typical)
10mm
#8 AWG
16mm
#6 AWG
2 *
2 *
Single-Phase: Wire to L1, N, and .
Three-Phase: Wire to L1, L2, L3, N, and
System Wiring
SURT8000XLI
Input 1 220/230/240 V 40 A 50 A / 2-pole 10mm
Input
Number
of
Phases
3+
Neutral
.
Voltage
380/400/415 V
Wire to L1A, N1, and
Current
Full Load
(Nominal)
15 A / phase when
online
.
External Input
Circuit Breaker
(typical)
50 A / 4-pole 10mm
40 A on L1 in bypass
Output 1 220/230/240 V 40 A (not required) 10mm
SURT10000XLI
Input 1 220/230/240 V 50 A 63 A / 2-pole 16mm
Input
3+
Neutral
380/400/415 V
18 A / phase when
online
63 A / 4-pole 16mm
50 A on L1 in bypass
Output 1 220/230/240 V 50 A (not required) 16mm
* Recommended wire sizes are typical. Actual wire size must comply with required ampacity
and local and national electrical codes.
2
Wire Size
(typical)
2 *
2 *
2 *
2 *
2 *
2 *
7. XLI model only: For three-phase input, set the Input Phase Selector switch (see C) to ‘3’. For
single-phase input, leave switch in default position of ‘1’.
XLT/XLJ/XLTW MODELS
OUTPUT
L1A
L2A
NPUT
I
L1
L2
B
XLI MODEL
O
UTPUT
L1A
N1
INPUT
L1
L2
L3
N
C
B
8. Switch the circuit breakers ON.
9. Check line vo l tages.
10. Replace the access panel.
3
Installing and Connecting the Batteries and Attaching the Front Bezel
n o
p q
r s
4