Smartflow Tracer Series Operating Instructions Manual

Tracer
Flowmeter
Operating Instructions (Ver 5.1)
®
Electronic Switching
with FCI (Fluid Characteristic Indication)
The Tracer Electronic Switching Flowmeter provides:
0 to 5V or 0 to 10V Selectable Flow Output
0 to 5V or 0 to 10V Selectable Temperature Output
1A, 30VAC/42VDC Programmable Switch for high
or low temperature and/or flow
Fluid Flow Rate Display in gallons per minute
(gpm) or liters per minute (lpm)
Fluid Temperature Display (°F or °C)
BTU’s per Minute Display
Fluid Characteristic Indication (Turbulent Flow or
“TFLOW” on display)
BTU Basics
To obtain the most accurate BTU calculation, use the Tracer to measure the supply side water temperature (in °F) before installing the Tracer in a cooling water return line.
BTU’s per minute calculation is based on the increase in water temperature multiplied by the flow rate. The Tracer Electronic Flowmeter calculates this information based on supply side temperature entered manually. Due to inherent differences in most thermometers, the most accurate BTU calculation will result from using the same thermometer (inside the Tracer) to measure supply and return line temperatures. Record the supply side temperature and enter it using the “Set BTU/m Input Temperature” instructions on page 3.
U.S. Patent No. 7,729,869
Application
Liquid running through the Tracer flowmeter should be free of metal shavings. Loose particles can interfere with moving components causing extra maintenance requirements.
Specifications
Flow
Size [NPT(F)] Range (gpm) Range (lpm)
3/8" 0.5 to 8 0 to 30 3/4" 2.0 to 20 8 to 76
1" 3.0 to 30 11 to 114
1-1/2" 6.5 to 60 25 to 228
2" 10.0 to 110 38 to 418
Accuracy ....................±5% of Full Range
Repeatability ..............±3% of Full Range
Environment
Tracer construction is water resistant, but the electronics housing is not submersible.
Turbulent Flow
“TFLOW” notification appears on the display when Turbulent Flow is likely inside the cooling circuit of the selected size. Turbulent flow is the mixing and swirling of water inside a cooling line that provides optimum heat transfer. Water flow rate greater than the point of Turbulent Flow does not provide a proportional benefit. Turbulent flow tracking allows technicians to apply mathematical cooling principles to all machines in a water system. Visit the Technical Documents section of www.smartflow-usa.com for a detailed discussion of Turbulent Flow.
Input the percentage of glycol in cooling water (0%, 10%, 20% or 30%) for accurate Turbulent Flow Indication. See Setup Mode option on page 5. Antifreeze compounds of ethylene or propylene glycol are sometimes added to cooling waer. Glycol compounds have substantially higher viscosity than water. As a result, higher flow rates are required to reach Turbulent Flow when glycol is used.
151 Memorial Drive, Unit H - Shrewsbury, MA 01545 - Phone: (888) 792-2223 - sales@plastixs.com - www.plastixs.com
Form #146 (02.16)
Temperature
Operating Range............32 to 180°F (0 to 82°C)
Accuracy........................±2% of Display Value
Repeatability..................±1% of Display Value
Component Materials
Body (3/8" model) .........Nickel-Plated Brass
Body (3/4" thru 2")........Anodized Aluminum
Stainless Steel (optional) Back Cover(3/8" only) ..Polysulfone
Impeller..........................Nylon 6/12
Magnet...........................Neodymium
Shaft...............................18-8 Stainless Steel
Electronics Cover ..........Nylon 6/6
Cable..............................9-Conductor, 24AWG
Operating
Internal Relay ................SPDT 1A, 30VAC/42VDC
Power Required .............8 to 28VDC
Maximum Pressure........100psi (7bar)
Installation Instructions
For best performance, mount the Tracer flowmeter vertically with the flow entering the meter from the bottom. This provides full flow inside the meter. We recommend a straight run of pipe equal to 10 pipe diameters on the inlet side of the Tracer flowmeter and a straight run of pipe equal to 5 pipe diameters on the outlet side of the flowmeter.
Use appropriate pipe sealant to prevent leakage on inlet and outlet sides of the flowmeter. The Tracer flowmeter can be installed in any orientation with the flow direction from either end of the flowmeter.
Attach the power and switching connections to the bare wires of the cable according to the chart at right. Individual wires are 24AWG stranded copper. Attach 8 to 28VDC power to the unit for correct operation. Power supply other than 8 to 28VDC may damage the electronics!
In normal operation, the internal relay is energized. If power to the unit is lost, or if unit is turned off, relay state changes to signal an alarm.
Operating Instructions
When power is applied to the Tracer flowmeter, the software version and the Tracer Unit Code (EP) will appear sequentially. Then the screen will be blank. Press ON to activate the display. There are three modes of operation for the Tracer Electronic Flowmeter: User Mode, Setup Mode, and Calibration Mode. User Mode displays all available process information. Setup Mode configures the flowmeter for unit selection (°F, °C, lpm, and gpm) and switching set points. Setup Mode also allows you to enter the information required to calculate BTU’s per Minute.
Wire Color Function
Black DC Ground
(Ground for Analog Output)
Yellow +DC Input (8 to 28VDC)
Red Not used
Blue Not used
Orange Flow Analog Voltage Output (+)
Violet Temp. Analog Voltage Output (+)
Green Relay Common
Brown Relay Normally Open
Gray Relay Normally Closed
Figure 1
ON
Δ
Δ
User Mode
After pressing ON, press Δ or buttons repeatedly to scroll continuously through displays of flow rate, temperature and BTU/m. BTU/m will not display until activated using the Setup Mode on page 3.
View Flow Rate
Press ON. Flow rate and units (gpm or lpm) will be displayed. See Figure 1.
View Temperature
Press Δ. Temperature and units (°F or °C) will be displayed. See Figure 2.
View BTU/m (not visible until activated)
Press Δ. BTU's and units will be displayed. See Figure 3. To activate, enter Setup Mode, and follow instructions to set input temperature found on page 3.
Figure 2
Figure 3
2
Setup Mode
Setup Mode allows the user to select English or Metric units, input BTU/m inlet temperature, and set auto shut-off time. Δ and keys scroll through all options inside each display selection. Turn the display off before entering Setup Mode.
Enter Setup Mode
The display must be off to enter Setup Mode.
and
Press and hold , then press ON. Flow rate units
ON
plus "Unit" and "SETUP" will be displayed. See Figure 4.
Select Flow Rate Units
Figure 4
ON
or
ON
ON
or
ON
ON
or
ON
Press or Δ to change units to gpm or lpm. Press
Δ
ON when the desired unit is displayed. See Figure
4. Setup Mode will continue unless you exit.
Exit Setup Mode
Δ
Press ON repeatedly until the display reads “end”, then press Δ. See figure 5. The display will read "off", then press ON and the unit will return to user mode.
Select Temperature Units
Enter Setup Mode (above). Press ON repeatedly until the display shows “°F” or °C” in the upper right corner and “unit” in the center. See Figure 6.
Δ
Press or Δ to change units. Press ON when desired unit is displayed. Setup Mode will continue unless you exit.
Set BTU/m Input Temperature
Enter Setup Mode (above). Press ON repeatedly until the display shows “BTU/m” in the upper left corner. See Figure 7. Press or Δ to change input temperature (40 to 220°F or 4.4 to 104.4°C). Press
Δ
ON when desired unit is displayed.
Note: If you set the temperature input to less than 40°F or 4.4°C, the display will show “off” and BTU/m display will deactivate.
Setup Mode will continue unless you exit.
Figure 5
Figure 6
Reactivate BTU/m
Follow the instructions to set (above) and press or Δ to display a value instead of “off”, and press ON to set.
Figure 7
3
Loading...
+ 7 hidden pages