SMAR TT301 Operation, Maintenance & Instruction Manual

TT301
Intelligent Temperature Transmitter
with Control Capability Optional
OPERATION & MAINTENANCE INSTRUCTIONS MANUAL
T T 3 0 1 M E
www.el-scada.ru
Introduction
INTRODUCTION
The TT301 is a transmitter mainly intended for measurement of temperature using RTDs or thermocouples, but can also accept other sensors with resistance or mV output such as: pyrometers, load cells, resistance position indicators, etc. The digital technology used in the TT301 enables the choice of several output functions, an easy interface between the field and the control room and several interesting features that reduce considerably the installation, operation and maintenance costs.
The TT301, besides the normal functions offered by other smart transmitters, offers the following functions:
SPECIAL SENSOR: the output follows a mV or Ohm input according to a 16-point linearization table.
PID OUTPUT CHARACTERIZATION: the PID output signal (MV) follows a curve determined by 16 points.
BACKUP SENSOR: the process measurement is realized by two sensors, but only one supplies the temperature. If it failure the other take its place.
INPUT SELECTOR: the selection between two sensor to obtain the measure is configured by user based in the conditions of maximum, minimum or average temperature of the sensor.
CONTROLLER: the process variable is compared to a setpoint. The deviation acts on the output signal according to a PID algorithm (Optional).
BATCH : setpoint generator allowing pre-programmed recipes of up to 2-week duration in 16 points. LOCAL ADJUST: allow to set lower and upper value, sensor type, operation mode, indication,
setpoint, PID parameters without a configurator.
PASSWORD : three configurable levels for different functions. CHANGE COUNTER: indicates the number of changes in each functions. SPECIAL- SENSOR-UNIT: allows the reading to be indicated by one of 100 standard engineering
units or any special unit with up to 5 characters.
Get the best results of the TT301 by carefully reading these instructions.
III
TT301 – Operation & Maintenance Instruction Manual
NOTE:
This Manual is compatible with version 4.XX, where 4 de notes software Version and XX software "RELEASE". The indication 4.XXmeans that this manual is compatible with any release of software version
4.
Waiver of responsibility
The contents of this manual abides by the hardware and software used on the current equipment version. Eventually there may occur divergencies between this manual and the equipment. The information from this document are periodically reviewed and the necessary or identified corrections will be included in the following editions. Suggestions for their improvement are welcome.
Warning
For more objectivity and clarity, this manual does not contain all the detailed information on the product and, in addition, it does not cover every possible mounting, operation or maintenance cases.
Before installing and utilizing the equipment, check if the model of the acquired equipment complies with the technical requirements for the application. This checking is the user’s responsibility.
If the user needs more information, or on the event of specific problems not specified or treated in this manual, the information should be sought from Smar. Furthermore, the user recognizes that the contents of this manual by no means modify past or present agreements, confirmation or judicial relationship, in whole or in part.
All of Smar’s obligation result from the purchasing agreement signed between the parties, which includes the complete and sole valid warranty term. Contractual clauses related to the warranty are not limited nor extended by virtue of the technical information contained in this manual.
Only qualified personnel are allowed to participate in the activities of mounting, electrical connection, startup and maintenance of the equipment. Qualified personnel are understood to be the persons familiar with the mounting, electrical connection, startup and operation of the equipment or other similar apparatus that are technically fit for their work. Smar provides specific training to instruct and qualify such professionals. However, each country must comply with the local safety procedures, legal provisions and regulations for the mounting and operation of electrical installations, as well as with the laws and regulations on classified areas, such as intrinsic safety, explosion proof, increased safety and instrumented safety systems, among others.
The user is responsible for the incorrect or inadequate handling of equipments run with pneumatic or hydraulic pressure or, still, subject to corrosive, aggressive or combustible products, since their utilization may cause severe bodily harm and/or material damages.
The field equipment referred to in this manual, when acquired for classified or hazardous areas, has its certification void when having its parts replaced or interchanged without functional and approval tests by Smar or any of Smar authorized dealers, which are the competent companies for certifying that the equipment in its entirety meets the applicable standards and regulations. The same is true when converting the equipment of a communication protocol to another. In this case, it is necessary sending the equipment to Smar or any of its authorized dealer. Moreover, the certificates are different and the user is responsible for their correct use.
Always respect the instructions provided in the Manual. Smar is not responsible for any losses and/or damages resulting from the inadequate use of its equipments. It is the user’s responsibility to know and apply the safety practices in his country.
IV
Table of Contents
TABLE OF CONTENTS
SECTION 1 - INSTALLATION ...................................................................................................................................... 1.1
GENERAL ..................................................................................................................................................................................... 1.1
MOUNTING ................................................................................................................................................................................... 1.1
ELECTRONIC HOUSING ............................................................................................................................................................. 1.2
WIRING ......................................................................................................................................................................................... 1.2
LOOP CONNECTIONS ................................................................................................................................................................. 1.3
INSTALLATION IN HAZARDOUS AREAS .................................................................................................................................... 1.7
EXPLOSION/FLAME PROOF ....................................................................................................................................................... 1.7
INTRINSICALLY SAFE ................................................................................................................................................................. 1.7
SECTION 2 - OPERATION ........................................................................................................................................... 2.1
FUNCTIONAL DESCRIPTION-HARDWARE ................................................................................................................................ 2.1
FUNCTIONAL DESCRIPTION - SOFTWARE .............................................................................................................................. 2.4
TEMPERATURE SENSORS ......................................................................................................................................................... 2.5
THE DISPLAY ............................................................................................................................................................................... 2.7
MONITORING ............................................................................................................................................................................... 2.7
ALARM .......................................................................................................................................................................................... 2.8
SECTION 3 - CONFIGURATION .................................................................................................................................. 3.1
CONFIGURATION RESOURCES ................................................................................................................................................ 3.3
PROGRAMMING TREE ................................................................................................................................................................ 3.3
IDENTIFICATION AND MANUFACTURING DATA – INFO .......................................................................................................... 3.4
CONFIGURATOR - CONF ............................................................................................................................................................ 3.4
CALIBRATION – RANGE .............................................................................................................................................................. 3.4
MAINTENANCE - MAINT .............................................................................................................................................................. 3.4
SENSOR TYPES - SENSOR ........................................................................................................................................................ 3.5
CONECTION AND WORK MODEL .............................................................................................................................................. 3.7
SPECIAL SENSOR CONFIGURATION ........................................................................................................................................ 3.7
PID ………………………………………………………………………………………………………………………………………………3.8
MONITORING - MONIT ................................................................................................................................................................ 3.9
CALIBRATING THE TT301 ......................................................................................................................................................... 3.10
CALIBRATION WITHOUT REFERENCE .................................................................................................................................... 3.10
CALIBRATION WITH REFERENCE ........................................................................................................................................... 3.11
UNIT ............................................................................................................................................................................................ 3.11
DAMPING ................................................................................................................................................................................... 3.11
TRIM ........................................................................................................................................................................................... 3.11
ALARM ........................................................................................................................................................................................ 3.12
ALARM CONFIGURATION ......................................................................................................................................................... 3.12
ONLINE MULTIDROP OPERATION ........................................................................................................................................... 3.12
CONFIGURATION TT301 FOR MULTIDROP ............................................................................................................................ 3.13
MULTIDROP MODE CONFIGURATION .................................................................................................................................... 3.13
SECTION 4 - PROGRAMMING USING LOCAL ADJUSTMENT ................................................................................. 4.1
THE MAGNETIC TOOL ................................................................................................................................................................ 4.1
RERANGING USING THE LOCAL ZERO AND SPAN ADJUSTMENTS IN SIMPLE MODE ....................................................... 4.2
COMPLETE LOCAL ADJUSTMENT ............................................................................................................................................. 4.3
OPERATION [OPER] .................................................................................................................................................................... 4.4
BATCH [BATCH] ................................ ................................................................ ........................................................................... 4.5
TUNING [TUNE] ............................................................................................................................................................................ 4.6
CONFIGURATION [CONF] ........................................................................................................................................................... 4.9
SECTION 5 - MAINTENANCE PROCEDURES ........................................................................................................... 5.1
GENERAL ..................................................................................................................................................................................... 5.1
DIAGNOSIS WITH SMAR CONFIGURATOR ............................................................................................................................... 5.1
ERROR MESSAGES .................................................................................................................................................................... 5.1
DIAGNOSTICS WITH THE CONFIGURATOR ............................................................................................................................. 5.1
TROUBLESHOOTING WITH TRANSMITTER .............................................................................................................................. 5.2
DISASSEMBLY PROCEDURE ..................................................................................................................................................... 5.3
REASSEMBLY PROCEDURE ...................................................................................................................................................... 5.4
INTERCHANGEABILITY ............................................................................................................................................................... 5.4
RETURNING MATERIALS ............................................................................................................................................................ 5.4
V
TT301 – Operation & Maintenance Instruction Manual
SECTION 6 - TECHNICAL CHARACTERISTIC ........................................................................................................... 6.1
ORDERING CODE ....................................................................................................................................................................... 6.5
APPENDIX A - CERTIFICATIONS INFORMATION .................................................................................................... A.1
EUROPEAN DIRECTIVE INFORMATION ................................................................................................................................... A.1
OTHER CERTIFICATIONS .......................................................................................................................................................... A.1
IP68 REPORT: ........................................................................................................................................................................................... A.1
HAZARDOUS LOCATIONS CERTIFICATIONS .......................................................................................................................... A.1
NORTH AMERICAN CERTIFICATIONS .................................................................................................................................................... A.1
EUROPEAN CERTIFICATIONS................................................................................................................................................................. A.2
SOUTH AMERICA CERTIFICATION ......................................................................................................................................................... A.2
IDENTIFICATION PLATE AND CONTROL DRAWING ............................................................................................................... A.2
IDENTIFICATION PLATE .......................................................................................................................................................................... A.2
CONTROL DRAWING ................................ ................................................................................................ ............................................... A.5
APPENDIX B – SRF – SERCIVE REQUEST FORM................................................................................................... B.1
VI
Installation Flowchart
Yes
Was the transmitter
configured on the bench
to match the application?
Configure the action and
the limit (Seção 3).alarm
Simule the value(s)
of the work range in the sensor(s)
conection terminal(s)
mV or Ohm
Start
No
No
OK
Yes
No
Yes
No
Yes
Configure the transmitter 1
and 3 - Configuration)
(Section
Section
Configure the measuring range to 0% (4mA) and 100% (20mA)
(Section 3 - Configuration)
Configure the Damping
(Section 3 - Configuration)
Configure the LCD reading
(Section 3 - Configuration)
See manual
(Section 5 - ) Maintenance
Is the reading correct?
Check the area classification
and its practices.
Install the transmitter preferably
on weather- protected areas.
Install the transmitter
(mechanically and electrically)
according to the application after
checking the best position for
the LCD (Section 5 - Maintenance)
Power the transmitter properly.
Is the transmitter
reading correct?
Do Zero and Span Trim
Did you correct the
transmitter reading?
Installation Flowchart
VII
TT301 – Operation & Maintenance Instruction Manual
VIII
Section 1
ALLOW 150 MM MINIMUM FOR LOCAL ZERO AND SPAN ADJUSTMENT WITH MAGNETIC TOOL.
COMMUNICATIONS TERMINAL
PLUG
CONDUIT CONNECTION
MOUNTING
BRACKET
PIPE 2"
PLUG
WALL OR
PANEL MOUNTING
FOR WALL MOUNTING
2 EXPANSION ANCHOR ­2 HEXAGON SCREW -
S8
3/16”X70
2 BOLT AND NUTS - 1/4”X30
NOT INCLUDED
FOR PANEL MOUNTING
General
Mounting
INSTALLATION
The overall accuracy of temperature and other measurements depends on several variables. Although the transmitter has an outstanding performance, proper installation is essential, in order to maximize its performance.
Among all factors, which may affect transmitter accuracy, environmental conditions are the most difficult to control. There are, however, ways of reducing the effects of temperature, humidity and vibration.
Temperature fluctuation effects can be minimized by locating the transmitter in areas protected from ex­treme environmental changes.
In warm environments, the transmitter should be installed to avoid, as much as possible, direct expo­sure to the sun. Installation close to lines and vessels subjected to high temperatures should also be avoided. For temperature measurements, sensors with cooling-neck can be used or the sensor can be mounted separated from the transmitter housing.
Use of sunshades or heat shields to protect the transmitter from external heat sources should be considered, if necessary.
The transmitter may be mounted in two basic ways, as follows:
Separated from the sensor, using optional mounting brackets;  Mounted on the sensor assembly.
Using the brackets, the mounting may be done in several positions, as shown on Figure 1.1. Measurement error can be decreased by using proper wires (see Section II, Operation).
Figure 1.1 - Dimensional Drawing and Mounting Positions
1.1
TT301 – Operation & Maintenance Instruction Manual
WARNING
Do not remove the graphite grease from the covers, or they may jam.
WARNING
The unused cable entries should be plugged and sealed accordingly to avoid humidity entering, which can cause the loss of the product’s warranty.
COVER LOCKING SCREW
(a) (b)
Electronic Housing
Humidity is fatal to electronic circuits. In areas subjected to high relative humidity, the O-rings for the electronics cover must be correctly placed. Removal of the electronics cover in the field should be reduced to the minimum necessary, since each time it is removed; the circuits are exposed to the humidity.
The electronic circuit is protected by a humidity proof coating, but frequent exposures to humidity may affect the protection provided. It is also important to keep the covers tightened in place. Every time they are removed, the threads are exposed to corrosion, since painting cannot protect these parts. Sealing methods should be employed on conduit entering the transmitter.
One of the conduit inlets for electrical connection is used to mount the sensor integral to the temperature transmitter (see Fig. 1.1).
For better visibility, the digital indicator may be rotated in steps of 90o (see Section 5, Maintenance). Reach the display and main board by removing the Cover with window. This cover should be locked
closed by the cover locking screw. To release the cover, rotate the locking screw clockwise. See figure
1.2.
Figure 1.2- Cover Locking and Housing Rotating Set Screw (a) Electronic Board Side
(b) Terminal Connection Side
Wiring
Access the wiring block by removing the Electrical Connection Cover. This cover can be locked closed by the cover locking screw (Figure 1.2- b). To release the cover, rotate the locking screw clockwise.
The terminals in the superior part marked with () and (−) are to receive the powering from 12 to 45 Vdc. The inferior terminals marked with the numbers from 1 to 4 they are for the connections of the different types of sensor.
Test and Communication terminals allow, respectively, to measure the current in the 4 - 20 mA loop, without opening it, and to communicate with the transmitter. To measure it, connect a multimeter in the mA scale in the "" and "" TEST terminals. To communicate with it, use a HART configurator between "" and "" COMM terminals. The wiring block has screws on which terminals type fork or ring can be fastened, see Figure. 1.3.
1.2
Installation
GROUND TERMINAL
GROUND TERMINALS
COMMUNICATION TERMINALS
TEST TERMINALS
+
+ +
1 2 3 4
C O M M
T E S T
WIRES
WARNING
Do not connect the Power Supply to the sensor terminals (Terminals 1, 2, 3 and 4).
CONFIGURATOR
250
Loop Connections
Figure 1.3 - Ground Terminal
The TT301 is protected against reversed polarity. For convenience there are three ground terminals: one inside the cover and two external, located close
to the conduit entries. Use of twisted pair (22 AWG) cables is recommended. Avoid routing signal wiring close to power cables or switching equipment.
The Figure 1.3 shows the correct installation of the conduit, in order to avoid penetration of water, or other substance, which may cause malfunctioning of the equipment.
Figure 1.4 - Conduit Installation Diagram.
Connection of the TT301 working as transmitter should be performed as in Figure 1.6.
Connection of the TT301 working as a controller (Optional) should be as indicated in Figure 1.5.
Figure 1.5 – Wiring Diagram for the TT301 Working as Transmitter
1.3
TT301 – Operation & Maintenance Instruction Manual
CONFIGURATOR
POWER
SUPPLY
250
WARNING
For proper operation, the configurator requires a minimum load of 250 Ohm between it and the power supply.
TT301
# 2
TRANSMITTER
TT301
# 3
TRANSMITTER
TT301
# 15
TRANSMITTER
POWER SUPPLY
250
CONFIGURATOR
TT301
TRANSMITTER
# 1
NOTE
Make sure that the transmitter is operating within the operating area as shown on the load diagram (Figure 1.9). Communication requires a minimum load of 250 Ohm.
Figure 1.6 – Wiring Diagram for the TT301 Working as Controller
Connection of the TT301 in multidrop configuration should be done as in Figure 1.6. Note that a maximum of 15 transmitters can be connected on the same line and that they should be connected in parallel. When many transmitters are connected to the same line, calculate the voltage drop through the 250 Ohm resistor and verify that the voltage of the power supply is enough (Figure 1.7).
Wiring diagram for the TT301 in multidrop.
Figure 1.7 - Wiring Diagram for the TT301 in Multidrop Configuration
The Configurator can be connected to the communication terminals of the transmitter or at any point of the signal line by using the interface with alligator clips.
It is also recommended to ground the shield of shielded cables at only one end. The not grounded end must be carefully isolated.
1.4
Installation
1650 1500
1000
500
0
12 20 30 40 45
250
Power Supply [ Volt ]
4-20mA only
Operating area
4-20mA and digital
communication
17
WARNING
When operating with two sensors, the sensors can not be both grounded. At least one has to be not grounded for proper operation of TT301.
Figure 1.8 – Load Curve
The sensor should be connected as per Figure 1.8.
1.5
TT301 – Operation & Maintenance Instruction Manual
2 - WIRE RTD
OR OHM INPUT
3 - WIRE RTD
OR OHM INPUT
4 - WIRE RTD
OR OHM INPUT
THERMOCOUPLE OR
MILIVOLT INPUT
DIFFERENTIAL RTD
OR OHM INPUT
BACKUP, MINIMUM,
MAXIMUM OR AVERAGE
BACKUP, MINIMUM,
MAXIMUM OR AVERAGE
1
2
1
2
1 2
3
4
1 2
3
4
1 2
3
4
1 2
3
4 1 2
3
4
1 2
3
4
1 2
3
4
+
-
DIFFERENTIAL THERMOCOUPLE
OR MILIVOLT INPUT
1 2
3
4
+
-
+ +
- -
Figure 1.9 – Sensor Wiring
1.6
Installation in Hazardous Areas
WARNING
Explosions could result in death or serious injury, besides financial damage. Installation of this transmitter in explosive areas must be carried out in accordance with the local standards and the protection type adopted .Before continuing the installation make sure the certificate parameters are I n accordance with the classified area where the equipment will be installed.
The instrument modification or parts replacement supplied by other than authorized representative of Smar is prohibited and will void the certification.
The transmitters are marked with options of the protection type. The certification is valid only when the protection type is indicated by the user. Once a particular type of protection is selected, any other type of protection can not be used.
WARNING
Only use Explosion Proof/Flameproof certified Plugs, Adapters and Cable glands. In Explosion-Proof installations the cable entries must be connected or closed using metal cable gland
and metal blanking plug, both with at least IP66 and Ex-d certification. The standard plugs provided by Smar are certified according to CEPEL certificate. If the plug needs to
be replaced, a certified plug must be used. The electrical connection with NPT thread must use waterproofing sealant. A non-hardening silicone
sealant is recommended. For NEMKO ATEX certificate please to follow the installation guidelines in hazardous locations below:
Group II Category 2G, Ex d, Group IIC, Temperature Class T6, EPL Gb U = 28VDC Ambient Temperature: -20 to 60ºC for T6 Environmental Protection: IP66/687 or IP66W/687W The electrical connection available are ½ - 14NPT and M20x1,5.
Cable entries must be connected or closed using metal cable gland and metal blanking plug, both with at least IP66 and Ex-d certification or any appropriate ATEX approved metal cable gland and metal blanking plug. Do not remove the transmitter covers when power is ON.
WARNING
In hazardous zones with intrinsically safe or non-incendive requirements, the circuit entity parameters and applicable installation procedures must be observed. To protect the application the transmitter must be connected to a barrier. Match the parameters between barrier and the equipment (Consider the cable parameters). Associated apparatus ground bus shall be insulated from panels and mounting enclosures. Shield is optional. If used, be sure to insulate the end not grounded. Cable capacitance and inductance plus Ci and Li must be smaller than Co and Lo of the associated Apparatus.
For free access to the Hart bus in the explosive environment, ensure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices. Use only Ex Hart communicator approved according to the type of protection Ex-i (IS) or Ex-n (NI).
It is not recommended to remove the transmitter cover when the power is ON.
Explosion/Flame Proof
Installation
Intrinsically Safe
1.7
TT301 – Operation & Maintenance Instruction Manual
1.8
Section 2
LOCAL ADJUST
MODEM
BELL 202
POWER SUPPLY
OUTPUT
DISPLAY
CONTROLLER
AMBIENT TEMPERATURE SENSOR
DISPLAY BOARD
SUPPLY
SUPPLY
MAIN BOARDINPUT BOARD
MUX
SIGNAL CONDI-
TIONER
TC
Ohm RTD
mV
I S O L A T O R
A/D
CONVER-
TER
D/A
CONVERTER
PROCESSING UNIT
RANGES SPECIAL FUNCTIONS PID (OPTIONAL) OUTPUT CONTROL SERIAL COMMUNICATION HART PROTOCOL
POWER
ISOLATION
OPERATION
The TT301 accepts signals from mV generators such as thermocouples or resistive sensors such as RTDs. The criterion is that the signal is within the range of the input. For mV, the range is -50 to 500 mV and for resistance, 0 to 2000 Ohm.
Functional Description-Hardware
Refer to the block diagram (Figure 2.1). The function of each block is described below.
Figure 2.1 – TT301 Block Diagram
MUX-Multiplexer
The MUX multiplexes the sensor terminals to the signal conditioning section ensuring that the voltages are measured between the correct terminals.
Signal Conditioner
Its function is to apply the correct gain to the input signals to make them suit the A/D converter.
A/D Converter
The A/D converts the input signal to a digital format for the CPU.
Isolator
Its function is to isolate the control and data signal between the input and the CPU.
CPU - Central Processing Unit & PROM
The CPU is the intelligent portion of the transmitter, being responsible for the management and operation of all other blocks: linearization, cold junction compensation and communication. The program is stored in the PROM as well as the linearization data for the temperature sensors.
For temporary storage of data, the CPU has an internal RAM, the data in the RAM is lost if the power is switched off, however the CPU also has an internal nonvolatile EEPROM where data that must be retained is stored. Examples of such data are: calibration, configuration and identification data.
D/A Converter
Converts the digital data from the CPU to an analog signal with 14-bits resolution.
Output
Controls the current in the line feeding the transmitter. It acts as a variable resistive load whose value
2.1
TT301 – Operation and Maintenance Instruction Manual
depends on the voltage from the D/A converter.
Modem
Modulates a communication signal on the current line. A "1" is represented by 1200 Hz and a "0", by 2200 Hz. These signals are symmetric and do not affect the DC level of the 4-20 mA signal.
Power Supply
Power shall be supplied to the transmitter circuit using the signal line (2-wire system). The transmitter quiescent consumption is 3.6 mA; during the operation, consumption may be as high as 21 mA, depending on the measurement and sensor status.
The TT301, in the transmitter mode, shows failure indication at 3.6 mA if configured for low signal failure; at 21 mA, if configured for high signal failure; 3.8 mA in the case of low saturation; 20.5 mA in the case of high saturation and measurements proportional to the applied temperature in the range between 3.8 mA and 20,5 mA. 4 mA corresponds to 0% of the working range and 20 mA to100 % of the working range.
Power Isolation
Its function is to isolate power supply between the input and the CPU.
Display Controller
Receives data from the CPU informing which segments of the Liquid Crystal Display, should be turned on.
Local Adjustment
Two switches that are magnetically activated. They can be activated by the magnetic tool without mechanical or electrical contact.
2.2
Operation
C TEMP. SENSOR
DIGITAL FILTER
INPUT
TRIM
RANGING
SPECIAL SENSOR
PID
AUTO/MANUAL
ACTION KP, TR, TD
A/M MV POWER-ON SAFETY-OUT
HIGH LOW OUT RATE
MV-FEEDBACK
LIMITS
( BUMPLESS A/M )
OUTPUT
4-20mA
CURRENT
TRIM
DISPLAY
INDICATOR
SPAN
PAUSE RESET
XMTR
CONST
4 mA 20 mA
1 2
OUT %
PRIMARY AND SECONDARY UNIT
DAMPING
SETPOINT
mA
SP SP TRACKING SP GENERAL SP TABLE
PID BLOCK (OPTIONAL)
OP-MODE
PID
TIME
GENERATOR
ALARM
ACTION-0 ACTION-1 ACTION-2 LIMIT-1 LIMIT-2
SP ( ENG )
ERROR %
mA
PV%
OUT%
SP %
SP ( ENG )
PV ( ENG )
T. AMB.
ERROR %
TI
STANDARD SENSOR
LINEARIZATION
& CJ COMPENSATION
INPUT
ohm / mV
TI min
PV %
URV LRV BURNOUT
PV %
TYPE / CONNECTION UNIT TABLE LRL / URL / MIN
TABLE
Figure 2.2 – Software Flow Chart
2.3
TT301 – Operation and Maintenance Instruction Manual
).
1
(
dt
dPV
Tdedt
Tr
eKpMV
Functional Description - Software
Refer to the block diagram (Figure 2.2). The function of each block is described below.
Input
Calculates the actual mV or Ohm from the value sensed by the input circuitry.
Digital Filter
The digital filter is a low-pass filter with an adjustable time constant. It is used to smooth noisy signals. The Damping value is the time required for the output to reach 63.2% for a step input of 100%.
Input Trim
Here, the value obtained by READING-TRIM is used to correct the transmitter for long term drift.
Standard Sensor Linearization & Compensation
Here, the mV and Ohm measurements are linearized and cold-junction compensated according to the sensor characteristics stored in the CPU. The CPU contains data about most standard sensors available.
Ranging
It is used to set the process values corresponding to the output 4 and 20 mA in transmitter mode or process variable 0 and 100% in PID mode. In transmitter mode the LOWER-VALUE is the point corresponding to 4 mA, and UPPER-VALUE is the point corresponding to 20 mA. In PID mode, the LOWER-VALUE corresponds PV = 0% and UPPER-VALUE corresponds to PV = 100%.
Time Generator (Optional)
Counts the time to be used by the Setpoint generator function. It may be paused by using PAUSE or set to any value inside the table.
Setpoint (Optional)
Here, the setpoint is adjusted in PID. In this block, Setpoint tracking may be activated in SP-TRACK. The setpoint may also be generated automatically by turning the SP-GENERATOR on. When running, the setpoint generator will ramp and dwell the setpoint according to a table (recipe) configured in SP­TABLE.
PID (Optional) First the error is calculated as SP-PV or PV-SP depending on which action (direct or reverse) is configured in ACTION. When Calendar Van Dussen function is used, the SP table points number is limited to 14 points instead to 16.
TABLE POINTS
This block relates the output (%) with the input (%) according to a 16 table points. The output is calculated through the interpolation of these points.
Auto/Manual (Optional)
The Auto/Manual mode is toggled in PID. In Manual, MV may be adjusted by the user in the INDIC option. The SP-POWER-ON option is used here to determine in which mode the controller should be upon powering it on.
Limits (Optional)
This block makes sure that the MV does not go beyond its minimum and maximum limits as established by the HIGH-LIMIT and LOW-LIMIT. It also makes sure that the Rate-of-Change does not exceed the value set in RATE-CHNG.
Output
Calculates the current proportional to the process variable or manipulated variable to be transmitted on the 4-20 mA output depending on the configuration in OP-MODE. This block also contains the constant current function configured in OUTPUT. The output is physically limited to 3.6 to 21 mA.
Current Trim
The 4 mA TRIM and 20 mA TRIM are used to make the transmitter current comply with a current standard, should a deviation arise.
Display
Alternates two indications as configured in DISPLAY. The engineering unit for the process variable can
2.4
be selected in UNIT.
Temperature Sensors
The TT301, as previously explained, accepts several types of sensors. The TT301 is specially designed for temperature measurement using thermocouples or thermoresistances (RTDs).
Some basic concepts about these sensors are presented below.
Thermocouples
Thermocouples are the mot widely used sensors in industrial temperature measurements. Thermocouples consist of two wires made from different metals or alloys joined at one end, called
measuring junction. The measuring junction should be placed at the point of measurement. The other end of the thermocouple is open and connected to the temperature transmitter. This point is called reference junction or cold junction.
For most applications, the Seebeck effect is sufficient to explain thermocouple behavior:
How the Thermocouple Works
When there is a temperature difference along a metal wire, a small electric potential, unique to every alloy, will occur. This phenomenon is called Seebeck effect.
When two wires of dissimilar metals are joined in one end, and left open in the other, a temperature difference between the two ends will result in a voltage since the potentials generated by the dissimilar materials are different and does not cancel each other out. Now, two important things must be noted. First: the voltage generated by the thermocouple is proportional to the difference between the measuring-junction and the cold junction temperatures. Therefore the temperature at the reference junction must be added to the temperature derived from the thermocouple output, in order to find the temperature measured. This is called cold junction compensation, and is done automatically by the TT301, which has a temperature sensor at the sensor terminals for this purpose. Secondly, if the thermocouple wires are not used all the way to the terminals of the transmitter (e.g. copper wire is used from sensor-head or marshalling box) new junctions with additional Seebeck effects will be created and ruin the measurement in most cases, since the cold-junction compensation will be done in the wrong point.
The relation between the measuring junction temperature and the generated millivoltage is tabulated in thermocouple calibration tables for standardized thermocouple types, the reference temperature being 0oC.
Standardized thermocouples which are commercially used, whose tables are stored in the memory of the TT301, are the following:
NBS (B, E, J, K, N, R, S, T) DIN (L, U) GOST (L) ASTM-E (W5Re/W26Re)
Thermoresistances (RTDs) Resistance Temperature Detectors, most commonly known as RTD's, are based on the principle that the resistance of a metal increases as its temperature increases.
Standardized RTDs, whose tables are stored in the memory of the TT301, are the following:
JIS [1604-81] (Pt50 & Pt100) IEC, DIN, JIS [1604-89] (Pt50, Pt100, Pt500, Pt1000) GE (Cu 10) Edison Curve (Ni 120) GOST (Pt50, Pt100, Cu50, Cu100) IEC 751-95 (Pt100) MILT (Ni120, Pt100)
For a correct measurement of RTD temperature, it is necessary to eliminate the effect of the resistance of the wires connecting the sensor to the measuring circuit. In some industrial applications, these wires may be hundreds of meters long. This is particularly important at locations where the ambient temperature changes a lot.
The TT301 permits a 2-wire connection which may cause measuring errors, depending on the length of connection wires and on the temperature to which they are exposed (see Figure 2.3).
Operation
2.5
TT301 – Operation and Maintenance Instruction Manual
R
V2
TRANSMITTER
2,1
3,4
R
RTD
I
R
V2
V1
TRANSMITTER
2,1
4
3
R
RTD
I
In a 2-wire connection, the voltage V2 is proportional to the RTD resistance plus the resistance of the wires.
V2 = [RTD + 2x R] x I
Figure 2.3 – Two-Wire Connection
In order to avoid the resistance effect of the connection wires, it is recommended to use a 3-wire connection (see Figure 2.4) or a 4-wire connection (see Figure 2.5).
In a 3-wire connection, terminal 3 is a high impedance input. Thus, no current flows through that wire and no voltage drop is caused. The voltage V2-V1 is independent of the wire resistances since they will be canceled out, and is directly proportional to the RTD resistance alone.
V2-V1 = [RTD + R] x I - Rx I = RTDx I
Figure 2.4 – Tree-Wire Connection
In a 4-wire connection, terminals 2 and 3 are high impedance inputs. Thus, no current flows through those wires and no voltage drop is caused. The resistances of the other two wires are not interesting since no measurement is done on them. Hence the voltage V2 is directly proportional to the RTD resistance. (V2 = RTD x I).
2.6
Operation
R
V2
2
1
+
-
3
4
R
RTD
TRANSMITTER
I
TRANSMITTER
1,3
R
R
R
2
4
V1
V2
RTD2
RTD1
I
I
NOTE
The material, the gauge, and the length should be the same connections of 3 or 4 threads.
Figure 2.5 – Four-Wire Connection
A differential connection is similar to the two-wire connection and gives the same problem (see Figure
2.6). Terminal 3 is a high impedance input. Thus, no current flow through and no voltage drop is caused, but the resistance of the other two wires will be measured and does not cancel each other out in a temperature measurement, since linearization will affect them differently.
Figure 2.6 – Differential Connection
The Display
The digital indicator is able to display one or two variables which are user selectable. When two variables are chosen, the display will alternate between the two with an interval of 3 seconds.
The different fields and status indicators are explained in Figure 2.7.
Monitoring
During normal operation, the TT301 is in the monitoring mode. In this mode, indication alternates between the primary and secondary variable as configured in DISPLAY. See Figure 2.8.
The display indicates engineering units, values and parameters simultaneously with most status indicators. The monitoring mode is interrupted in two situations:
User performs complete local adjustment. An alarm is activated.
2.7
TT301 – Operation and Maintenance Instruction Manual
* PID IS OPTIONAL
M
A
Fix
F(t)
PID
SP
F(x)
35
PV
min
ACK
INDICATES THAT THE DISPLAYED ALARM HAS NOT YET BEEN ACKNOWLEDGED
INDICATES ACTIVE SPECIAL SENSOR LINEARIZATION
( NOT USED ON TT301 )
VARIABLE FIELD
UNIT PERCENT
UNIT MINUTES
UNIT AND FUNCTION FIELD
INDICATES THAT THE PROCESS VARIABLE IS NOW DISPLAYED
INDICATES ACTIVE MULTIDROP MODE
INDICATES ACTIVE
SETPOINT GENERATOR *
INDICATE PID
CONTROLLER MODE *
INDICATES ACTIVE
CONSTANT OUTPUT MODE
INDICATES CONTROLLER
IN AUTOMATIC *
INDICATES CONTROLLER
IN MANUAL *
INDICATES POSSIBILITY
TO ADJUST / CHANGE
VARIABLE / MODE
INDICATES THAT
THE SETPOINT
Alarm
Figure 2.7 – Display
Figure 2.8 – Typical Monitoring Mode Display
The two alarms are software alarms and have no contacts available on the transmitter. The alarms are acknowledged by using the Local Adjustment or the Configurator, which can view and configure alarms as well - see further Section III. During an alarm, the display will indicate which alarm has been activated and if it has been acknowledged or not.
The transmitter display also indicates the alarms status as shown in Figure 2.9. AL H means High Alarm, AL L means Low Alarm and ALO indicates Burnout failure. The ACK indicates
that the alarm has not yet been acknowledged. When the alarm condition disappears, the "ACK" is switched off and the display returns to monitoring
mode. For further information on alarm configuration, see Section III - Programming Using Terminal.
2.8
Operation
ALARM 1
ALARM 2
Figure 2.9 – Typical Alarm Condition Display
2.9
TT301 – Operation and Maintenance Instruction Manual
2.10
Section 3
NOTE
When configured in multidrop for the classified areas the entity parameters allowed for the area must be strictly observed. So, verify that:
Ca Cij + Cc La Lij + Lc Voc min [Vmaxj] Isc min [Imaxj] Where:
Ca, La = capacitance and inductance permitted in bus; Cij, Lij = transmitter capacitance and inductance r j (j=1, 155), without internal protection; Cc, Lc = cable capacitance and inductance; Voc = open circuit tension of the intrinsic safety barrier; Isc = short circuit tension of the intrinsic safety barrier; Vmax = maximum permissible tension to be applied on the r j transmitter; Imax = maximum permissible tension to be applied on the r j transmitter.
CONFIGURATION
The Temperature Intelligent Transmitter TT301 is a digital device bearing the most advanced features a measurement apparatus can offer. A HART digital communication protocol permits the device to be connected to an external computer for a simple and complete configuration. These computers, connected to the transmitters, are called HOST computers and may be a Primary or Secondary Master type. Although HART may be a master/slave protocol, it may coexist with up to two masters in a field bus. Generally, the Primary HOST stands for a Supervisory and the Secondary HOST is used as a Configurator.
Transmitters, on the other hand, may be connected to a point-to-point or a multi-drop network. In a point-to-point network, the equipment should have its address set at “0”, so that the output current is modulated from 4 to 20 mA, according to the measurement performed. In a multidrop network, the
transmitters should be configured on a network address between “1” and “15”, if the identification
devices work via address. In this case, the transmitter’s output current must be constant, each transmitter consuming 4 mA. If the identification mechanism is done via Tag, the transmitters may be addressed at “0” and control their current output, even on a multidrop configuration.
The TT301 may be configured both for Transmitter and Controller and the HART addressing may be used as follows:
TRANSMITTER MODE: The TT301 controls the current output, while the “1” to “15” addresses
adjust the TT301 on multidrop mode setting the output current control on 4 mA.
CONTROLLER MODE: The TT301 always controls the output current according to the value
calculated for the Manipulated Variable, regardless of its address value on the net.
The TT301 Intelligent Temperature Transmitter presents a comprehensive set of HART Commands that permit accessing any implemented functionality. These commands comply with the HART protocol specifications and are grouped in Universal Commands, Common Practice Commands and Specific Commands.
Smar developed the CONF401 and HPC301 software, the first one works in Windows platform (95, 98, 2000, XP and NT) and UNIX. The second one, HPC301, works in the most recent technology in PDA´s. They bring easy configuration and monitoring of field devices, capacity to analyze data and to modify the action of these devices. The operation characteristics and use of each one of the
configurators are stated on their respective manuals.
Figures 3.1 and 3.2 show the front of the Palm and the CONF401 screen, with the active configuration.
3.1
TT301 - Operation & Maintence Instruction Manual
Figure 3.1 - Configurator
3.2
Figure 3.2 – CONF401 Screen
Configuration Resources
WARNING
All transmitters are factory-configured without passwords. To avoid faulty operation on a few critical levels on the programming tree, the configuration is recommended of all passwords before operating. See option “PASSWORD”, on the maintenance section.
INFO CONF MAINT SENSOR PID RANGE TRIM ALARM FACTORY
TT301
MULTIDROP MONIT
Through the HART configurators, the TT301 firmware allows the following configuration resources to be accessed:
Transmitter Identification and Manufacturer Data; Primary Variable Trim – Temperature; Secondary Variable Trim – Terminal Temperature; Equipment Current Trim; Transmitter Adjustment to Work range; Engineering Unit Selection; Set Point Generator Configuration; PID Controller Configuration; Equipment Configuration; Equipment Maintenance.
The operations occurring between the configurator and the transmitter do not interrupt the temperature measuring and do not disturb the output signal. The configurator may be connected on the same 4-20 mA signal cable to a maximum 2000 m distance from the transmitter.
Programming Tree
The programming tree is a structure resembling a tree, with all the resources available in the software, as shown on Figure 3.3.
DEVICE ADDRESS 0: Used when the Configurator is connected in parallel with a single transmitter and this transmitter has 0 (zero) for address.
FROM: 0 TO 15: Used when the Configurator is connected in parallel with up to 15 several transmitters and these transmitters are configured with different addresses (See Multidrop).
Programming Using Hand-Held Terminal
Figure 3.3 – Configuration Tree
INFO The main information on the transmitter may be accessed here. They include: Tag,
Description, Message and Single ID.
CONF – This option permits Burnout and Display configurations MAINT – This option tests the current loop, resets the operations equipment, sees the operations
counter and configures the password levels and ordering code.
SENSOR – This option permits configurate the sensor type and the connection to be used. PID – This option connects and disconnects the programming function and adjusts and monitors all of
the control parameters.
MONIT – The user may monitor 4 of the transmitter dynamic variables and the current output. RANGE – The following outputs related to the parameters may be configured: Lower Value, Upper
Value, Unit and damping.
TRIM – Adjusts the transmitter displaying to a current or an Ohm/mV standard. ALARM – Any of the three available types of alarm may be configured. They may be used as an alert
tool to be activated when the PV is out the configured range.
FACTORY – Contains all parameters pre-configured at plant. This procedure is in-factory performed
and may not be adjusted by the user.
3.3
TT301 - Operation & Maintence Instruction Manual
*NOTE
This item may not be modified.
MULTIDROP – The user may track the equipments connected to the loop, thus detecting their
respective addresses. Also, an address is designated to each device to be connected to the
network.
Identification and Manufacturing Data – Info
The main information on the transmitter may be obtained here. They are: Tag, Description, Message, Date and Single Identification. There is also a screen with important additional information on the equipment. They are: Manufacturer, Type of equipment, Serial Number and Transmitter Firmware Version, HART protocol Version and Hardware Revision.
The following information are available for the TT301 transmitter identification and manufacturer data:
TAG – Field with 8 alphanumerical characters for transmitter identification;  DESCRIPTION – Field with 16 alphanumerical characters for additional transmitter identification;  MESSAGE – Field with 32 alphanumerical characters for any other information, such as the name
of the last person to calibrate, some special caution to be observed or if a ladder is needed to access the transmitter, for example.
MODIFICATION DATE – The date may be used to identify a relevant date, as the last calibration,
the next calibration or installation. The date is stored in the form of bytes, where DD = [1,..31], MM = [1..12], AA = [0..255] and the effective year is calculated by [ year = 1900 + AA];
UNIQUE ID* - Information for reading only.
Configurator - Conf
This function affects the transmitter 4-20 mA output and display reading. It may alter the lower and upper burnout, select the variables to be displayed and verify the status of writing protection.
Burnout – The burnout may occur when the sensor reading is out of range or the sensor is open. In this case, the transmitter may be adjusted for maximum output limit at 21 mA, by configuring it on the upper value, or the minimum limit at 3.6 mA configured on the lower value.
Calibration – Range
The Lower and the Upper Values are calibrated in this operational range, which also selects the unit representing the process variable and the transmitter damping.
Maintenance - Maint
The maintenance option offers the user 5 choices to check his loop functionality, such as: restart the equipment, test the current loop, verify the number of configurations performed, configure passwords and verify the equipment order code. Below is a brief description of the characteristics performed by the equipment Maintenance function:
Device Reset The equipment is switched off and then on. The restarting option should be carried out as a last resort, as it may destabilize the process control.
Loop Test – The current output may be adjusted to any desired value between 3.8 and 21.0 mA regardless of the input value. There are a few stable current values for the loop test. The options available are: 4, 8, 16 or 20 mA.
Operation Counter: The operation number counting is useful to indicate if somebody altered any configuration on the equipment. Every time one of the parameters below is altered, the respective alteration counter is activated. The monitored parameters are:
3.4
Range configuration (Lower/Upper) Change to Constant Current 4 mA Trim 20 mA Trim Sensor Trim
Burnout configuration
NOTE
Contact Smar in case you forgot or lost your password.
Sensor configuration Auto/Manual shift (PID enabled) Multidrop
Passwords: The options for password configuration and access level are: Info, Trim, Conf, Maint, PID and Alarm.
There are three password levels. They are used to restrict the access to certain operations in the programming tree. In the default condition no password is configured.
Each operation item may have a specified password level. The default password level is 0 (“Zero”), but
the adjustment of Info at level “1” and Maint at level “3” are feasible. These levels may be altered by
someone who knows the level “3” password. To cancel, just delete the current password and send
another blank one. The level 3 password is hierarquically superior to the level 2 passwords, which, on its turn is superior to
level 1. Ordering code – It contains the equipment ordering code.
Sensor Types - Sensor
It configures the TT301 input for the type of sensor in use and its connecting mode. The types covered in this manual are:
RTD: Temperature Resistant Detector
Cu10 (GE) Ni120 (Edison Curve #7) Pt50, 100, 500, 1000 (IEC) Pt50, 100 (JIS) Pt50, PT100, Cu50, Cu100 (GOST) Pt100 (IEC 751-95) Ni120, Pt100 (MILT) Configurable for 2, 3 or 4 wires, differential, backup, maximum, minimum or average
TC: Thermocouples
B, E, J, K, N, R, S e T (NBS) L e U (DIN), K e S (IEC584) L (GOST) W5Re/W26Re (ASTM) Configurable for 2, 3 or 4 wires, differential, backup, maximum, minimum or average
Ohm: Resistance Measuring
0 a 100 Ohm 0 a 400 Ohm 0 a 2000 Ohm Configurable for 2, 3 or 4 wires, differential, backup, maximum, minimum or average
mV: Voltage Measuring
-6 a 22 mV
-10 a 100 mV
-50 a 500 mV Configurable for 2 wires, differential, backup, maximum, minimum or average
Special: Special Sensor
Special Ohm Special mV
It is used for special sensors like charge cells or position resistive indicators. This resource may turn the TT301 into a mass, volume, position, etc. transmitter.
Cold Junction:
This option enables or not the cold junction for TC sensors. Do not use the "send" button. The alteration is made automatically in the transmitter.
Programming Using Hand-Held Terminal
3.5
TT301 - Operation & Maintence Instruction Manual
VARIABLE
UNITS
Pressure
inH2O, InHg, ftH2O, mmH2O, mmHg, psi, bar, mbar, g/cm2, Pa, KPa,Ton, ATM
Volume Flow
ft3/min, gal/min, l/minin, Gal/min, m3/h, gal/s, l/s, Ml/d. ft/3s, ft3/d, m3/s, m3/d, Gal/h, Gal/d, ft3/h, m3/min, bbl/s, bbl/min, bbl/h, bbl/d, gal/h, Gal/s, l/h
Speed
ft/s, m/s, m/h
Temperature
ºC, ºF, ºR, K
Voltage
mV, v
Volume
gal, l, Gal, m3, bbl, bush, Yd3, ft3, In3
Level &
Length
ft, m, in, cm, mm
Time
min, sec, h, dia
Weight
(Mass)
gram, Kg, Ton, lb, Shton, LTon
Mass Flow
g/s, g/min, g/h, kg/s, kg/min, kg/h, kg/d, Ton/min, Ton/h, Ton/d, lb/s, lb/min, lb/h, lb/d, Ton/d
Temperature
SGU, g/cm3, kg/m3, g/ml, kg/l, g/l, TWARD, BRIX, Baum H, Baum L, API, % Solw, % Solv, Ball
Others
Ohm, Hz, mA, %, pH, s, cPo
Special
5 characters
Conection and Work Model
After the selection of the sensor type is necessary to choose the way how sensors work. The available options are: differential, 2 wires, 3 wires, 4 wires, backup, average, maximum and minimum. In the options 2, 3 or 4 wires, only one sensor is connected in the device terminal. In the options differential, backup, average, maximum and minimum are connected 2 sensors.
2, 3 and 4 wires: only one sensor will go to generate the process variable. If it ruptures, the burnout indication will be showed.
Differential: In this mode, the TT301 will go to work with the measure difference between the sensors. If one of them to ruptures, the burnout indication will be showed.
Backup: TT301 works with the reading of the first sensor (between 2 and 4 terminals). If this sensor brokes, the second sensor (between 3 and 4 terminals) will replace it and show the process variable reading. In this case, the reading of the first sensor will be discarded, even if this sensor returns to operate again. The first sensor will back to operate again if either gives it a reset by software or
reenergize the device again. The message “S1BAD” will appear on LCD and the HART response code
“Non-PV out of limits” is set. In case of failure of the second sensor, the transmitter will continue to operate normally but the message “S2BAD” will appear on LCD and the HART response code “Non-PV out of limits” will be set.
Average: the final reading will be the average of the signals from two sensors. If the difference between them is higher than a programmed value, an alarm will be generated. If one of them ruptures, the other continues performing the process variable reading, and an alarm will be generated to inform this
situation. The message “S1BAD” or “S2BAD” will appear on LCD and the HART response code “Non­PV out of limits” will be set.
Maximum and minimum: the process variable will be supplied by sensor that has either maximum or minimum reading, respectively. If one of them ruptures, the other continues performing the process variable reading, and an alarm will be generate to inform this situation. The message “S1BAD” or “S2BAD” will appear on LCD and the HART response code “Non-PV out of limits” will be set.
Special Sensor Configuration
The special sensor is a function that permits sensors whose typical curves are not stored in the TT301 memory to be used or linearized. Table 3.1 shows the available units for special sensors.
Any sensor may be used, provided the TT301 accepts the signal range generated by the sensor. The Ohm and mV sensors limitations may be seen on table 3.2.
To change the special sensor configuration select special on the sensor menu.
Table 3.1 – Special Sensor Available Units
3.6
Programming Using Hand-Held Terminal
WARNING
The special sensor function may not be used when the setpoint generating function is being used and vice-versa.
CONNECTION TYPE
2, 3 OR 4 WIRES
DIFFERENTIAL (each input)
Ohm
0 < X < 2000
0 < X < 1000
mV
-6 < X < 500
10 < X < 250
 
 
dt
dPV
Tdedt
Tr
eKpMV .
1
The sensor typical curve may be scheduled on the TT301 EEPROM memory as a 16-point table. These tables are usually supplied by the sensor manufacturer, but may also be obtained at a lab test.
The options for configuring the special sensor are: Range For the Ohm sensor there are 3 ranges: 0 to 100, 0 to 400 and 0 to 2000 ohm. For the mV
sensor there are also 3 ranges: -6 to 22, -10 to 100 and –50 to 500.
Connection – There are 4 options: differential, two wires, three wires and four wires. X and Y Tables – The special sensor table points are inserted here. The sensor input is stored as an
X-variable. The chosen output is stored as a Y-variable (19999 ≤ Y ≤ +19999). The X-input should always have growing values. X = Ohm or mV terminal block input. Y = Chosen output in engineering units. Watch the following limitations for the X variable values:
PID
V.INF Calibration range lower limit. The least possible value for transmitter calibration when using this special sensor.
V.SUP Calibration range upper limit. The most possible value for transmitter calibration when using this special sensor.
Minimum Span The least possible span for transmitter calibration when using this special sensor. Unit – Engineering Unit to be associated to the measured variable. If one from most of 100 units is
selected, the respective HART protocol code will be attributed to this parameter. This way, the whole supervisory system having HART protocol may access the Unit menu.
This option adjusts the PID parameters including the Setpoint, change on auto/manual mode and the tuning parameters.
The TT301 with an activated PID works as a controller/transmitter, while, deactivated, it works only as a transmitter The transmitter 4/20mA output may become a PID controller output, following the equation below:
Where: e = PV – SP (Direct) or SP – PV (Reverse)
SP = Setpoint PV = Process Variable Kp = Proportional Gain Td = Derivative Time MV = Output Tr = Integration Time
See below a list of configurations feasible on the PID function.
PID Controller – ON/OFF
Tuning Parameters – This feature configures the Kp, Tr and Td tuning parameters, as well as
Table 3.2 – Special Sensor Input Range
output limits and rate.
3.7
TT301 - Operation & Maintence Instruction Manual
VARIABLE
DESCRIPTION
CORRENTE
mA output.
*MV
Output percent.
PV
Process variable on the selected engineering unit.
TEMP
C Room temperature.
PV%
Process variable percent.
*SP%
Setpoint percent.
*SP
Setpoint on the selected engineering unit.
*TIME
Setpoint generator time in minutes.
*ER%
Deviation between SP and PV percents.
*NOTE
These items may only be selected on PID mode.
EXAMPLE
Set the first variable indication for PV percent and the second variable for current.
PV, SP, MV and Error Readings – Provides real-time variable value. SP Tracking – When in MANUAL, the setpoint follows the PV. When the controller is switched to
AUTO, the last PV value before the switch will be regarded as SP.
Control Action – This option configures the transmitter Operation Mode. The options are: Direct – The output increases when the PV rises. Reverse – The output decreases when the PV does. Control Mode – Selects Automatic and Manual. MV Configuration – Adjusts the manipulated variable. SP Configuration – The Setpoint is adjusted. Control Limits – This option switches the SP Power On to automatic, manual and last value. Safety value – The output after a power shortage or during a failure. Rate / Alteration – The maximum allowed output change. Lower Limit – The minimum allowed percent output. Upper Limit – The maximum allowed percent output. Setpoint Table – When the setpoint generator is activated, the setpoint varies according to a curve
table. The time is always read in minutes and the setpoint in percentage.
SP Generator – When activated, the setpoint varies with time according to the schedule on TABELA_SP table.
Monitoring - MONIT
This function monitors the transmitter 4 dynamic variables and the output current on the configurator display simultaneously.
Table 3.3 - Monitored Variables
The indications will always oscilate between the first and the second variable.
If the display should not indicate the oscillation, select the same indication in both variables, or select “SEM” (“without”) on the second variable.
3.8
Calibrating the TT301
A transmitter calibration consists of configuring the input values related to 4 mA and 20 mA. The TT301 may do this in 4 different methods: 1 – By using the Configurator (no-reference method) whose calibration input is not required. 2 – By using the Configurator and an input signal as reference (referenced method). 3 – Local adjustment and an input signal as reference (simple local adjustment, with reference).
4 – Local adjustment and an input signal as reference (complete local adjustment, with reference). 5 – Local adjustment (complete local adjustment, without reference).
In transmitter mode, the lower value always corresponds to 4 mA and the upper value to 20 mA. In PID mode, the lower value corresponds to PV=0 % and upper value to PV=100 %.
Calibration Without Reference
The TT301 may be configured to supply 4 to 20 mA, the equivalent to the temperature limits on the
user’s application, without the need to connecting a reference calibrating generator on its terminals.
This is possible because the TT301has linearization curves for several standard temperature sensors in its memory. Let us suppose the transmitter range is calibrated from –100 to 300o C and one must calibrate it on 0 to 100o C.
The transmitter generates a signal varying from 4 to 20 mA when the temperature oscillates between 0 and 100o C.
Watch that both the LOWER and UPPER values are entirely independent. Adjusting one does not affect the other. However, the following rule must be observed:
a) Both values should not be less than the lower limit or in excess of the upper calibration limit. b) The Upper value less Lower value span must be larger than the LOWER SPAN.
If a signal needs to be reverted, i.e., have an UPPER VALUE smaller than the LOWER VALUE, proceed as follows:
Make the inferior value as close as possible to the Superior Value or vice-versa, observing the allowed minimum span. Adjust the Superior Value with the desire value and, then, adjust the Inferior value.
Example: If the transmitter is calibration such as: LOWER VALUE = 4 mA = 0 oC UPPER VALUE = 20 mA = 100 oC and the values should change to:
LOWER VALUE = 4 mA = 100o C UPPER VALUE = 20 mA = 0o C;
Considering that the Pt100 IEC Minimum Span is 10o C, the adjustments must be altered as follows: a) LOWER VALUE = 90, or 100-10.
b) UPPER VALUE = 0 oC c) LOWER VALUE = 100 oC
The table 3.4 shows graphycaly how to do this ranging.
Programming Using Hand-Held Terminal
3.9
TT301 - Operation & Maintence Instruction Manual
1 Step 2 Step 3 Step 4 Step
Get sensor
minimum span
Do Lower
Value = 90 ºC
Do Upper
Value = 0 ºC
100 ºC
Upper Value
90 ºC
Upper Value - Span
0 ºC
Lower Value
Minimum Span = 10 ºC
100 ºC
90 ºC
100 ºC
90 ºC
100 ºC
90 ºC
0 ºC 0 ºC0 ºC
Do Lower
Value = 100 ºC
Lower Value
Lower Value Lower Value
Lower Value
Lower Value
st sd
rd
th
Upper Value
Upper Value
Upper Value Upper Value
Table – 3.4 – Procedure to Range without Reference
Calibration With Reference
This is the most convenient way to calibrate a transmitter. Apply the signal for adjusting the 4 mA point (PV=0 %). The Lower Value is altered but the span remains the same.
The same procedure is applied for the Upper Value. LOWER VALUE = 0 Ohm
UPPER VALUE = 100 Ohm Example: When measuring resistance the TT301 is calibrated as follows: After the installation is done, the potentiometer (input sensor) was found to have a 5 Ohm residual
resistance when its indicator was on a zero position. The Lower Value reference trim quickly corrects this problem, causing the Lower Value to equal 5 Ohm.
The Upper Value may be altered in the same way. As mentioned before, the Ohm or mV sensor input may differ a little from its plant standard. The Zero and Gain Trim may be used to adjust the transmitter reading to Engineering Units with its
plant standard, thus eliminating possible differences.
Unit
The Engineering Unit shown on the transmitter and the configurator displays may be altered. The units are linked to a selected process variable.
The following units are available:
- For mV input: always mV.
- For Ohm input: always Ohm.
- For Thermocouple and RTD: Celsius, Fahrenheit, Rankine and Kelvin degrees.
Damping
The DAMPING option on the RANGE function enables electronic damping adjustment.
Trim
3.10
The damping may be adjusted between 0 and 32 seconds.
The TRIM function is used to adjust resistance, voltage and current reading to user standard. To continue the TRIM adjustment, the control loop must be on MANUAL to avoid disturbances in the process.
There are two options: Current signal and input reading.
Current TRIM (4-20 mA output)
When the microprocessor generates a 0 percent signal, the Digital-to-Analogic converter and related electronic circuits must emit a 4 mA output. If the signal is 100 percent, the output must be 20 mA. Differences may occur between the SMAR standard current and the plant standard. In this case, the current TRIM adjustment should be used.
The Configurator will adjust the output signal and then it will ask again if the current is correct or not.
Input Reading TRIM
There may be differences between the SMAR resistance standard and mV and the plant standards. In this event, the user TRIM adjustment may be used. The TRIM available are: Zero trim, the Gain trim and Factory trim.
- Zero Trim – Calibrates the resistance or millivoltage lower value. The zero trim does not interfere with the gain trim.
- Gain Trim – Calibrates the resistance or milivoltage upper value.
- Factory Trim – Recovers the Zero, Gain, and temperature sensor made in factory. For zero or gain adjustment, a resistance or mV standard should be connected with a better than
0.02% accuracy. If the transmitter is configured as either differential sensor, backup, average, maximum or minimum,
that is working with two sensors simultaneously, only the zero trim is available. To perform zero trim, it should to short circuit the two sensors in the field and to enter with the value 0 (zero).
After perform the trim, remove the short circuit for the transmitter to read the sensors resistance without the influence of the lines. The line maximum resistance should be less than 32 for that zero trim would be possible.
Temperature Sensor Trim
Althouth it is not necessary to perform the temperature trim of the terminal, it is possible a little adjustment in the temperature measure through this menu.
Alarm
This function configures the three TT301 alarms, with independent configuration for alarms 1 and 2 action and limit. All the alarms may be monitored and identified through this function. Alarm zero indicates burnout and may be activated in this function.
Rec - Recognizes the alarm, while the ACK indication on the transmitter display disappears as the pending alarms are identified.
Action - Configures the alarm operation mode: low, high or off. Limit - Configures the level that the alarm is occurring.
Alarm Configuration
Low - Is activated when the PV goes below the signal configured (decreasing). High - Is activated when the PV goes above the signal configured (increasing). Off - The alarm is disabled.
Online Multidrop Operation
The multidrop connection is made up of several transmitters connected in parallel in a single communication line. The communication between the master system and the transmitters is digitally done, with the transmitter analog output deactivated (TRM mode) or activated (PID mode).
The communication between the transmitters and the master system (PROG, DCS, data acquiring system or PC) is performed through a Bell 202 modem using a HART protocol. Each transmitter is identified by a single (1 to 15) address.
Programming Using Hand-Held Terminal
3.11
TT301 - Operation & Maintence Instruction Manual
WARNING
The output current is fixed on 4 mA as soon as the transmitter address is changed, except when the transmitter is configured for PID operation mode.
Select and option before
searching for an address:
Equip. address From:
To:
Tag:..............
0
0 15
The TT301 is produced with the address equal to zero, in a point-to-point operational mode. The transmitter communicates with the configurator by overlaying the communication on the 4-20 mA signals. To operate in multidrop mode, the transmitter address must switch to a 1 to 15. This change deactivates the 4-20 mA analog output by assuming the fixed value equal to 4 mA (TRM mode), or maintains the 4-20 mA variable when the equipment is configured for PID mode.
When intrinsic safety is required, special attention must be laid on Ca, La parameters allowed for that area.
To operate in multidrop mode, search for the transmitters connected on the same line.
This operation is called “POLL” (“SEARCH”) and is automatically performed after "From 0 to 15" is
selected and the “POLL” button activated on the Palm configurator screen below:
Configuration TT301 for Multidrop
All equipments leave factory with a 0 (zero) address, unable to work in multidrop. To operate in multidrop they must be singly connected to any number between 1 and 15.
To configure the transmitter in multidrop, connect it single on the line according to figure 1.6 on section
1. After powering it, press the HPC30pt icon. The configurator will display the following screen:
Multidrop Mode Configuration
3.12
Figure 3.4 – Multidrop Configuration Screen
Select Equipment Address 0 on the first line and press the Poll button. When the configurator identifies the transmitter, select a line containing the information on the equipment. On next screen, choose the Multidrop option. Now, select the required transmitter address and press Send. See that no other required transmitter on same line has the same address, regardless of make, model and type. Repeat this procedure for all equipments connected in multidrop.
To use the configurator for communication with a specific transmitter in multidrop mode, select the second option From: 0 to 15 on the configurator screen and press the Poll button. When the configurator identifies a transmitter on the line, it will display a list with its Address, Tag and Manufacturer.
After the transmitter is selected, the main menu with all configuration options will be displayed on the configurator for handling.
Section 4
4.1
SI/COM OFF/ON
NOTE
WRITE PROTECT
SIMPLE LOCAL
ADJUSTMENT
COMPLETE
LOCAL
ADJUSTMENT
Disables
Disables
Disables
1
Enables
Disables
Disables
2
Disables
Enables
Disables
Disables
Disables
Enables
NOTE
If the hardware protection is selected, the EEPROM will be protected. The local adjustment default condition is simple enabled and write protect disabled.
ACTION / SPAN
MOVE AROUND / ZERO
The Magnetic Tool
PROGRAMMING USING LOCAL ADJUSTMENT
Smar's magnetic tool is the second man-machine interface; it compromises the advantage of the powerful Smar Configurator and the convenience of the "good-old" tool.
If the transmitter is fitted with a display, and is configured for complete - local - adjustment (using internal jumper) the magnetic tool is almost as powerful as the Configurator, eliminating the need for a Configurator in most basic applications.
If the transmitter is not fitted with a display, or is configured for simple local adjustment (using internal jumper) the adjustment capability is reduced to reranging.
To select the function mode of the magnetic switches configure the jumpers located at the top of the main circuit board as indicated below:
The transmitter has, under the identification plate, holes for two magnetic switches activated by the magnetic tool.
The holes are marked with Z (Zero) and S (Span). If "Simple Local Adjustment" is selected by the jumpers position, the switches have the following functions:
Figure 4.1 – Local Adjustment Switches
TT301 - Operation and Maintenance Instruction Manual
4.2
Transmitter mode: Z - It is used to select the Lower Range Value.
S - It is used to select the Upper Range Value.
They work exactly as the adjustment with reference of the Configurator controller mode for transmitters with digital display.
Controller mode:
Z - Moves the options (OPERATION and BATCH). S - Activates the selected function.
If "Complete Local Adjustment" is selected by the jumpers position, the switches have the following functions:
Z - Moves the options. S - Activates the selected function.
Reranging Using the Local Zero and Span Adjustments in Simple Mode
It is possible to rerange the transmitter with the local adjustment switches located on the top of the electronic housing. The switches work like the adjustment "with reference" for the Configurator.
In order to make these adjustments, the instrument must be configured as "transmitter" (XMTR). To adjust the zero of the transmitter, proceed as follows:
Apply the Lower Value, signal. Wait for the process to stabilize. Insert the magnetic tool in the ZERO adjustment hole (see Figure 4.2) Wait 2s. The transmitter should be reading 4 mA. Remove the tool.
Figure 4.2 – Local Zero and Span Adjustment
Programming Using Local Adjustment
4.3
WARNING
When programming using local adjustment, the transmitter will not prompt "Control loop should be in manual!" as it does when programming using the Configurator. Therefore it is a good idea, prior to configuration, to switch the loop to manual. And do not forget to return to auto after configuration is completed
As the reranging with reference, the span is maintained. In case you want to change the span, proceed as follows:
Apply the Upper Value, signal. Wait for the process to stabilize.
Insert the magnetic tool in the SPAN adjustment hole. Remove the tool.
Note that when zero adjustment is done, the URV can not be pushed above the URL. In this case, span is not maintained.
Complete Local Adjustment
LOCAL PROGRAMMING TREE The programming tree is a tree-shaped structure with a menu of all available software resources, as shown in Figure 4.3.
The Local Programming mode is entered by activating switch (Z). In transmitter mode, only the configuration branch of the tree is applicable, thus the first menu function will be UNIT.
Figure 4.3 - Local Adjustment Programming Tree – Main Menu
OPER (OPERATION): Is the option where the operation related parameters of the controller are configured: Auto/ Manual, Setpoint, Manual output.
BATCH: Is the option where the Setpoint generator related functions are operated: on/off, Pause, Reset and time adjustment.
TUNE (TUNING): Is the option where the PID-Algorithm related parameters are configured: Action, Kp, Tr, and Td.
CONF (CONFIGURATION): Is the option where the output and display related parameters are con­figured: unit, primary and secondary display, Lower and Upper Value, dam-ping, sensor type and operation mode.
ESC (ESCAPE): Is the option used to go back to normal monitoring mode.
TT301 - Operation and Maintenance Instruction Manual
4.4
Operation [OPER]
Z: Moves to the next branch (BATCH). S: Enters the OPERATION branch, starting with function AUTO/MANUAL.
Auto/Manual (A/M)
Z: Moves to the SETPOINT INCREASE function. S: Toggles controller status, Automatic to Manual or Manual to Automatic. A and
Mindicates status.
Setpoint Adjustment (SP)
Z: Moves to the SETPOINT DECREASE function. S: Increases the setpoint until the magnetic tool is removed or 100% is reached.
Z: Moves to the MANIPULATED VARIABLE ADJUSTMENT function. S: Decreases the setpoint until the magnetic tool is removed or 0% is reached.
Manipulated Variable Adjustment (MV)
Z: Moves to the MANIPULATED VARIABLE DECREASE function. S: Increases the control output until the magnetic tool is removed or the upper
output limit is reached.
Z: Moves to the ACK function. S: Decreases the control output until the magnetic tool is removed or the lower
output limit is reached.
Figure 4.4 – Local Adjustment Operation Tree
4.5
Batch [BATCH]
Acknowledge (ACK)
Z: Moves the SAVE function. S: Acknowledges all alarms.
Save (SAVE)
Z: Moves to ESCAPE of the operation menu. S: Saves the setpoint and manual output values in the transmitter EEPROM, for
use after power-on.
Escape (ESC)
Z: Moves to the AUTO/ MANUAL function. S: Escapes to the MAIN menu.
Programming Using Local Adjustment
Figure 4.5 – Local Adjustment Batch Tree
Z: Moves to the TUNING branch. S: Enters the BATCH branch, starting with function SPGEN on/off.
Setpoint Generator On/Off (SPGEN)
Z: Moves to the SPGEN Pause/ Run function. S: Toggles setpoint generator. On to Off or Off to On.
Setpoint Generator Pause/Run (SPGEN)
Z: Moves to the RESET function. S: Toggles setpoint generator mode, pause to run or run to pause.
TT301 - Operation and Maintenance Instruction Manual
4.6
Reset (RESET)
Z: Moves to the TIME INCREASE function. S: Resets the time register of the setpoint generator to 0.
Time (TIME)
Z: Moves to the time decrease function. S: Increases the time register for the setpoint generator until the magnetic tool is
removed or 19999 min. is reached.
Z: Selects ESCAPE of the BATCH menu. S: Decreases the time register for the setpoint generator until the magnetic tool is
Escape (ESC)
removed or the time-base register is zero.
Z: Moves to the SPGEN on/off function. S: Escapes to the MAIN menu.
Tuning [TUNE]
Figure 4.6 – Local Adjustment Tuning Tree
Z: Moves to the CONFIGURA-TION branch. S: Enters the TUNING branch, starting with function KP-ADJUSTMENT.
Programming Using Local Adjustment
4.7
Kp - Adjust (KP)
Z: Moves to the proportional gain decrease function. S: Increases the proportional gain until the magnetic tool is removed or 100 is
reached.
Z: Moves to the TR_ADJUSTMENT function. S: Decreases the proportional gain until the magnetic tool is removed or 0.0 is
reached.
Tr - Adjust (TR)
Z: Moves to the integral time decrease function. S: Increases the integral time until the magnetic tool is removed or 999 minutes are
reached.
Z: Moves to the TD_ADJUST function. S: Decreases the integral time until the magnetic tool is removed or 0 minute is
reached.
Td - Adjust (TD)
Z: Moves to the derivative time decrease function. S: Increases the derivative time until the magnetic tool is removed or 999 seconds
are reached.
Z: Moves to the ACTION function. S: Decreases the derivative time until the magnetic tool is removed or 0 second is
reached.
Action (ACT)
Z: Moves to the SAVE function. S: Toggles the action direct to reverse or reverse to direct.
The far-right character of the unit/function-field indicates the present mode: D = direct action R = reverse action
TT301 - Operation and Maintenance Instruction Manual
4.8
Save (SAVE)
Z: Moves to the ESCAPE to TUNING menu. S: Saves the KP, TR and TD constants in the transmitter EEPROM.
Escape (ESC)
Z: Moves to the KP-ADJUSTMENT function. S: Escapes to the MAIN menu.
4.9
Configuration [CONF]
Programming Using Local Adjustment
Figure 4.7 – Local Adjustment Configuration Tree
TT301 - Operation and Maintenance Instruction Manual
4.10
DISPLAY
DESCRIPTION
C
Degree Celsius
F
Degree Fahrenheit
R
Degree Rankine
K
Kelvin
mV
millivolt
Ohm
Ohm
SPEC
Special Unit
NO
No Unit
ESC
-escape-
NOTE
See special sensor in Section 3 for more information on “special unit”.
DISPLAY
DESCRIPTION
SP%
Setpoint (%)
PV%
Process Variable (%)
MV%
Output (%)
ER%
Error (%)
Nothing
TI
SP generator time
CU
Output (mA)
PV
Process Variable (eng. unit)
SP
Setpoint (eng. unit)
ESC
-escape-
Z: Selects ESCAPE of the monitoring mode.
S: Enters the CONFIGURATION branch, starting with function UNIT.
Unit (UNIT)
Z: Moves to the DISPLAY-1 function. S: Starts selection of engineering unit for process variable and setpoint indication.
After activating (S), you can move around the options available in the table below by activating (Z).
The desired unit is activated by using (S). Escape leaves unit unchanged.
Display 1 (LCD_1)
Z: Moves to the DISPLAY-2 function. S: Starts selection of variable to be indicated as primary display.
After activating (S), you can move around the options available in the following table by activating (Z).
The desired variable is activated using (A). Escape leaves primary variable unchanged.
Programming Using Local Adjustment
4.11
NOTE
In TRANSMITTER mode, only PV%, CU, PV and "none" are selectable.
Display 2 (LCD_2)
Z: Moves to the ZERO ADJUST function. S: Starts selection of variable to be indicated as secondary display.
The procedure for selection is the same as for DISPLAY_1, above.
Lower Range Value Adjustment without Reference (LRV)
Z: Moves to the LRV decrease function. S: Increases the Lower Value until the magnetic tool is removed or the maximum
for the Lower Value is reached.
Z: Moves to the URV ADJUST-MENT function. S: Decreases the Lower Value until the magnetic tool is removed or the minimum
for the Lower Value is reached.
Upper Range Value Adjust without Reference (URV)
Z: Moves to the URV decrease function. S: Increases the Upper Value until the magnetic tool is removed or the maximum
for the Upper Value is reached.
Z: Moves to the ZERO AD-JUSTMENT function. S: Decreases the Upper Value until the magnetic tool is removed or the minimum
for the Upper Value is reached.
Reranging using the LRV and URV items in the menu is the same as the keyboard rerange on the CONFIGURATOR. No input has to be applied; the range is set independent of applied input. Adjust the value indicated on the display to the desired range value. Changing one does not affect the other.
Zero Adjust with Reference (ZERO)
Z: Moves to the ZERO decrease function. S: Decreases the Lower Value (Increases output) until the magnetic tool is
removed or the minimum for the Lower Value is reached.
Z: Moves to the SPAN ADJUST function. S: Increases the Lower Value (Decreases Output) until the magnetic tool is
removed or the maximum for the Lower Value is reached.
Span Adjust with Reference (SPAN)
TT301 - Operation and Maintenance Instruction Manual
4.12
SENSOR SELECTION TABLE
DISPLAY
DESCRIPTION
mV-1
-6
to
22 mV
mV-2
-10
to
100 mV
mV-3
-20
to
500 mV
Ohm-1
0
to
100 Ohm
Ohm-2
0
to
400 Ohm
Ohm-3
0
to
2000 Ohm
RTD
RTD
TC
Thermocouple
SPEC
Special Sensor
ESC
- escape -
RTD SELECTION TABLE
DISPLAY
DESCRIPTION
DISPLAY
DESCRIPTION
Cu-10
Cu10
Mi100
MILT Pt100
Ni 120
Ni 120
Mi120
MILT Ni120
I50
IEC Pt50
IE100
IEC751-95 Pt100
I100
IEC Pt100
Go50
GOST Pt50
JI 50
JIS Pt50
Go100
GOST Pt100
JI 100
JIS Pt100
Cu50
GOST Cu50
I500
IEC Pt500
Cu100
GOST Cu100
I1000
IEC Pt1000
Esc
Escape
Z: Moves to the SPAN decrease function. S: Decreases the Upper Value (Increases Output) until the magnetic tool is
removed or the minimum for the Upper Value is reached.
Z: Moves to the SENSOR function. S: Increases the Upper Value (Decreases output) until the magnetic tool is
removed or the maximum for the Upper Value is reached.
Reranging using the ZERO and SPAN items in the menu is equivalent to the applied rerange on the Configurator. The range values are adjusted relative to the applied input. The value in the display is the applied temperature in percentage of the range. Changing the lower value shifts the upper value too, maintaining the span. Changing the upper value does not affect the lower value. For example, if you want 4 mA (0%) for the applied input, adjust until the display reads 0%. Likewise, if you want 20% (7.2 mA), adjust until the display shows 20%.
Sensor (SENS)
Z: Moves to the OPERATION MODE function. S: This function is protected by a "password", when prompted PSWD activate (S) 2
times to proceed with sensor selection.
After activating (S), you can move around the options available in the following table by activating (Z).
For all sensors, further selections must be done to determine the specific type and connection. Move around the available options - listed in the tables below - using (Z).
Programming Using Local Adjustment
4.13
OHMS & RTD CONNECTION
DISPLAY
DESCRIPTION
2 WIRE
2 - wire
3 WIRE
3 – wire
4 WIRE
4 – wire
DIFF
Differential
ESC
- escape -
THERMOCOUPLE - TYPE
DISPLAY
DESCRIPTION
DISPLAY
DESCRIPTION
B_NBS
NBS type B
WR26
ASTM W5Re/W25Re
E_NBS
NBS type E
L GOS
GOST Type L
J_NBS
NBS type J
ESC
Escape
K_NBS
NBS type K
N_NBS
NBS type N
R_NBS
NBS type R
S_NBS
NBS type S
T_NBS
NBS type T
L_DIN
DIN type L
U_DIN
DIN type U
OPERATION MODE
DISPLAY
DESCRIPTION
XMTR
Transmitter
CNTRL
Controller (Optional)
Operation Mode (MODE)
Z: Moves to the SAVE function. S: This function is protected by a "password", when prompted PSWD activate (S) 2
times to proceed. After entering the "password", you can move around the options listed in the table
below using (Z). In order to select the desired option, activate (S).
Save (SAVE)
Escape (ESC)
Z: Selects ESCAPE to CONFIGURATION mode. S: Saves lower value and upper value.
Z: Moves to the UNIT function. S: Escapes to the MAIN menu.
TT301 - Operation and Maintenance Instruction Manual
4.14
ESCAPE [ESC]
Z: Selects OPERATION branch. S: Escapes to MONITOR mode.
Section 5
> OUTPUT SATURATED <
DIAGNOSTIC MESSAGES
POTENTIAL SOURCE OF PROBLEM
PARITY ERROR
Excessive noise or ripple.
OVERRUN ERROR
Excessive noise or ripple.
CHECK SUM ERROR
Excessive noise or ripple.
FRAMING ERROR
Excessive noise or ripple.
NO RESPONSE
The line resistance is not in accordance with load curve. Transmitter not powered. Interface not connected. Transmitter configured in Multidrop mode being accessed by ON LINE
SINGLE UNIT.
Transmitter reversely powered (polarity is reversed). Interface damaged. Power supply or battery voltage of the Configurator lower than 9 V.
LINE BUSY
Other device using the line.
CMD NOT IMPLEMENTED
Software version not compatible between Configurator and transmitter. Configurator is trying to carry out a TT301 specific command in a
transmitter from another manufacturer.
TRANSMITTER BUSY
Transmitter carrying out on important task. e.g., Local Adjustment.
COLD START
Start-up or Reset due to power supply failure.
OUTPUT FIXED
Output in Constant Mode. Transmitter in Multi-drop mode.
MAINTENANCE PROCEDURES
General
Diagnosis with Smar Configurator
Error Messages
SMAR TT301 intelligent temperature transmitters are extensively tested and inspected before delivery to the end user. Nevertheless, during their design and development, consideration was given to the possibility of repairs by the end user, if necessary.
In general, it is recommended that the end user do not try to repair printed circuit boards. Instead he should have spare circuit boards, which may be ordered from SMAR whenever necessary.
Should any problem be noticed related to the transmitter’s output, investigation may be carried out by
the Configurator, as long as power is supplied and communication and the processing unit are operating normally.
The programmer should be connected to the transmitter in accordance with the wiring diagram shown on Section 1, Figures 1.4, 1.5 and 1.8.
When communicating using the Configurator the user will be informed about any problem found by the transmitters self diagnostics.
As an example, the Configurator of the display may show:
The messages are always alternated with the information on the top line. The table below lists the error messages. Refer to trouble shooting for more details on corrective action.
Diagnostics with the Configurator
5.1
TT301 - Operation and Maintenance Instruction Manual
DIAGNOSTIC MESSAGES
POTENTIAL SOURCE OF PROBLEM
OUTPUT SATURATED
Primary variable out of calibrated Span (Output current in 3.8 or 20.5 mA, XMTR mode only).
SV OUT OF LIMITS
Temperature out of operating limits. Temperature sensor damaged.
PV OUT OF LIMITS
Input signal out of operating limits. Sensor damaged. Transmitter with false configuration. PV out of range limits (see table).
Troubleshooting with Transmitter
Symptom: NO LINE CURRENT Probable Source of Trouble:  Transmitter Connections
Check wiring polarity and continuity. Check for shorts or ground loops.
Power Supply
Check power supply output. The voltage at the TT301 terminals must be between 12 and 45 Vdc,
and the ripple less than 0.4V.
Electronic Circuit Failure Check the main board for defect by replacing it with a spare one.
Symptom: NO COMMUNICATION Probable Source of Trouble: Terminal Connections
Check terminal interface connections. Check if the interface is connected to the points [COMM] and [-] or in the line between the
transmitter and the load resistor. Check if the interface is model IF2 (for HART Protocol). Transmitter Connections
Check if connections are as per wiring diagram. Check line resistance; it must be equal to or greater than 250 Ohm, between the transmitter and the
power supply. Power Supply Check output of power supply. The voltage at the TT301 terminals must be between 12 and 45V,
and ripple less than 0.4V. Electronic Circuit Failure Locate the failure by alternately replacing the transmitter circuit and the interface with spare parts. Transmitter Address In On Line Multidrop item check if the address is "0".
Table 1 - Diagnostics with the Configurator
5.2
NOTE
A 21.0 or 3.6mA current in XMTR mode indicates burnout.
WARNING:
The board has CMOS components which may be damaged by electrostatic discharges. Observe correct procedures for handling CMOS components. It is also recommended to store the circuit boards in electrostatic-proof cases.
Symptom: CURRENT OF 21.0 mA OR 3.6 mA Probable Source of Trouble: Transmitter Connection
Check if the sensor is correctly connected to the TT301 terminal block. Check if the sensor signal is reaching the TT301 terminal block by measuring it with a multimeter at
the transmitter-end. For mV and thermocouples test can be done with connected and disconnected
to the transmitter. Sensor
Check the sensor operation; it shall be within its characteristics. Check sensor type; it shall be the type and standard that the TT301 has been configured to. Check if process is within the range of the sensor and the TT301.
Symptom: INCORRECT OUTPUT Probable Source of Trouble: Transmitter Connections
Check power supply voltage. The voltage at the TT301 terminals must be between 12 and 45V, and
ripple less than 0.4V. Check for intermittent short circuits, open circuits and grounding problems.
Noise, Oscillation
Adjust damping  Check grounding of the transmitters housing, extra important for mV and thermocouple input. Check the terminal block for moisture. Check that the shielding of the wires between sensor/transmitter and transmitter/panel is grounded
only in one end. Sensor
Check the sensor operation; it shall be within its characteristics. Check sensor type; it shall be the type and standard that the TT301 has been configured to.
Electronic Circuit Failure
Check the integrity of circuit replacing it with a spare one.
Calibration
Check calibration of transmitter.
Disassembly Procedure
Refer to Figure 5.1. Make sure to disconnect power supply before disassembling the transmitter. Sensor
If the sensor is mounted on the transmitter, first disconnect the wires in order to prevent the wires from breaking. To access the terminal block, first loose the cover locking screw on the side marked "Field Terminals", then unscrew the cover.
Electronic Circuits The main board (6) and input board (9) are matched pairs and must be changed together and not mixed with others.
To remove the circuit boards (6 and 9) and display (4), first loose the cover locking (10) on the side not marked "Field Terminals" then unscrew the cover (1).
Maintenance Procedures
5.3
TT301 - Operation and Maintenance Instruction Manual
Loosen the two screws (5) that anchor the main circuit board. Gently pull out the main board (6). To remove the input board (9), first unscrew the two screws (8) that anchors it to the housing (11), gently pull out the board.
Reassembly Procedure
Put input board (9) into housing (11). Anchor input board with its screws (8). Put main board (6) into the housing, ensuring all inter connecting pins are connected. Anchor main board with their screws (5). Put display (4) into the housing, observing the four mounting positions (see Figure 5.2) "" symbol
should point in the direction desired as UP.
Anchor display with their screws (3). Fit the cover (1) and lock it using the locking screw (10).
Interchangeability
Calibration data is stored in the EEPROM of the main board, hence READING TRIM must be done if main-board or input board has been changed.
Returning Materials
Should it become necessary to return the transmitter and/or Configurator to SMAR, simply contact your local agent or SMAR office, informing the defective instrument's serial number, and return it to our factory.
In order to expedite analysis and solution of the problem, the defective item should be returned with a description of the failure observed, with as much details as possible. Other information concerning to the instrument operation, such as service and process conditions, is also helpful.
5.4
Figure 5.1 – Exploded View
NOTE
For housing in aluminium there is an insert in the position 15. This insert is used to improve the grounding.
ACCESSORY
ODERING CODE
DESCRIPTION
SD-1
Magnetic Tool for local adjustment.
Palm*
16 Mbytes Palm Handheld, Including HPC301’s initialization and installation software.
HPC301*
HART® HPI311-M5P for the Palm, including the configuration package for the Smar and generic transmitters.
HPI311-M5P*
HART® interface.
SPARE PARTS LIST FOR TRANSMITTER
DESCRIPTION OF PARTS
POSITION
CODE
CATEGORY
HOUSING, Aluminum (NOTE 2)
. See Housing Ordering Code
11
HOUSING, 316 SS (NOTE 2)
. See Housing Ordering Code
11
COVER
. See Cover Ordering Code
1 and 18
COVER WITH WINDOW FOR INDICATION
. See Cover Ordering Code
1
COVER LOCKING SCREW
10
204-0120
EXTERNAL GROUND SCREW
15
204-0124
IDENTIFICATION PLATE FIXING SCREW
13
204-0116
DIGITAL INDICATOR
3 and 4
400-0559
TERMINAL HOLDER INSULATOR
14
214-0220
BOARD GROUP GLL1403 AND GLL1436 (DISPLAY AND ASSEMBLY KIT INCLUDED); TT301.
5, 6, 7, 8
and 9
400-1300
A
BOARD GROUP GLL1403 AND GLL1436 (DISPLAY AND ASSEMBLY KIT NOT INCLUDED); TT301.
5, 6, 7, 8
and 9
400-1301
A
BOARD GROUP GLL1403 AND GLL1436 (WITHOUT DISPLAY AND WITH ASSEMBLY KIT INCLUDED); TT301.
5, 6, 7, 8
and 9
400-1302
A
BOARD GROUP GLL1403 AND GLL1436 (INCLUDED DISPLAY AND WITHOUT ASSEMBLY KIT); TT301.
5, 6, 7, 8
and 9
400-1303
A
ASSEMBLY KIT OF THE GROUP GLL1403 AND GLL1436; TT301
5, 7 and 8
400-1304
A
0-RINGS Cover, BUNA-N (NOTE 3)
2
204-0122
B
TERMINAL HOLDING SCREW
17
204-0119
CONDUIT PLUG
1/2 NPT Internal Socket Set Plug in Bichromatized Carbon Steel
16
400-0808
1/2 NPT Internal Socket Set Plug in 304 SST
16
400-0809
M20 X 1.5 External Socket Set Plug in 316 SST
16
400-0810
PG 13.5 External Socket Set Plug in 316 SST
16
400-0811
MOUNTING BRACKET FOR 2" PIPE MOUNTING (NOTE 4)
. Carbon Steel ( Accessories in Carbon Steel )
-
214-0801
. Stainless Steel 316 (Accessories in Stainless Steel 316 )
-
214-0802
. Carbon Steel ( Accessories in Stainless Steel 316 )
-
214-0803
LOCAL ADJUSTMENT PROTECTION CAP
12
204-0114
NOTE
1 - For category A, it is recommended to keep, in stock, 25 parts installed for each set, and for category B, 50. 2 - It includes terminal holder insulator, bolts (cover lock, grounding and terminal holder insulator) and identification plate without certification. 3 - 0-Rings are packaged in packs of 12 units. 4 - Including U-clamp, nuts, bolts and washers.
* For equipment updates and HPC301 software, just check: http://www.smarresearch.com.
Maintenance Procedures
5.5
TT301 - Operation and Maintenance Instruction Manual
Figure 5.2 – Four Possible Positions of the Display
5.6
400-1306
TEMPERATURE INTELLIGENT TRANSMITTER HOUSING
COD.
Communication Protocol
H
F
P
HART® FOUNDATIONTM fieldbus PROFIBUS-PA
COD.
Electrical Connection
0 A B
½ NPT M20x1,5 PG13,5
COD.
Material
H0
H1 H2 H3 H4
Aluminiumo (IP/TYPE) 316 SST (IP/TYPE) Aluminium for Saline Atmosphere (IPW/TYPEX) 316 SST for Saline Atmosphere (IPW/TYPEX) Cooper Free Aluminium for Saline Atmosphere (IPW/TYPEX)
COD.
Painting
P0
P3
P8
P9
Gray Munsell N6.5 Polyester Black Without Painting Blue Safety Base Epóxi – Electrostatic Paintig
COD.
Electronic Housing Type
E0 E1 E2
Default Smar (4-20 mA - 2 Filtros) Similar Default BASF(4-20 mA-2 Filter+Prot. ZN non-loosening) Default 0 A 20 (0 A 20 mA - 4 Filter)
400-1306
H 0 H0
P0
E0
400-1307
TEMPERATURE INTELLIGENT TRANSMITTER COVER
COD.
Type
0 1
Without Display With Display
COD.
Material
H0 H1
Aluminium (IP/TYPE) 316 SST (IP/TYPE)
COD.
Painting
P0
P3 P8 P9
Gray Munsell N6.5 Polyester Black Without Paiting Blue Safety Base Epóxi – Electrostatic Painting
400-1307
1
H0
P0
Housing Ordering Code
Maintenance Procedures
Cover Ordering Code
5.7
TT301 - Operation and Maintenance Instruction Manual
5.8
Section 6
Functional Specifications
Inputs
See table 6.1, 6.2 and 6.3
Output Signal
Two-wire, 4-20 mA with superimposed digital communication (HART Protocol Version 5.1/Transmitter/Poll-Response mode/Common 4-20 mA).
Power Supply
Bus powered: 12 - 45 Vdc.
Load Limitation
1650
1500
1000
500
0
12 20 30 40 45
250
Power Supply [ Volt ]
4-20mA only
Operating area
4-20mA and digital
communication
17
Display
Optional 4 1/2 digit LCD indicator.
Hazardous Area Certifications
Intrinsic Safety (FM, CSA, EXAM, CEPEL), Explosion Proof (FM, CSA, NEMKO, CEPEL), Dust Ignition Proof (FM), Non­incendive (FM)
European Directive Information
Authorized representative in European Community
Smar Gmbh-Rheingaustrasse 9-55545 Bad Kreuzanach
EMC Directive (2004/108/EC) – Electromagnetic Compatibility
The EMC test was performed according to IEC standard: IEC61326-1:2006, IEC61326-2-3:2006, IEC61000-6-4:2006, IEC61000-6-2:2005. For use only in industrial environment.
ATEX Directive (94/9/EC) – Equipment and protective systems intended for use in potentially explosive atmospheres.
This product was certified according European Standards at NEMKO and EXAM (former DMT). The certified body for manufacturing quality assessment is EXAM (number 0158).
LVD Directive 2006/95/EC – Electrical Equipment designed for use within certain voltage limits
According the LVD directive Annex II the equipment under ATEX “Electrical equipment for use in an explosive atmosphere” directive are excluded from scope from this directive.
Zero and Span Adjustments
No interactive, via digital communication or local adjustment.
Temperature Limits
Ambient: Storage: Display:
-40 ºC to 85 ºC
-40 ºC to 120 ºC
-20 ºC to 80 ºC
-40 ºC to 85 ºC
(-40 ºF to 185 ºF) (-40 ºF to 248 ºF) (-4 ºF to 176 ºF) (-40 ºF to 185 ºF)
(without damage)
Loss of Input (Burnout)/Failure Alarm
In case of sensor burnout or circuit failure, the self diagnostics drives the output to 3.6 or to 21.0 mA, according to the user's choice.
Humidity Limits
0 to 100% RH
Turn-on Time
Performs within specifications in less than 10 seconds after power is applied to the transmitter.
Update Time
Approximately 0.5 second.
Damping Adjustment
User configurable from 0 to 32 seconds (via digital communication).
Configuration
This is done by an external Configurator that communicates with the transmitter remote or locally using Hart Protocol. Locally the magnetic tool can be used as well. The magnetic tool can configure the majority of the items provided the transmitter is fitted with a display.
Performance Specifications
Accuracy
See tables 6.1, 6.2, 6.3 and 6.4.
Ambient Temperature Effect
For a 10 ºC variation: mV (- 6 to 22 mV), TC (NBS: B, R, S,T): ± 0.03% of the input milivoltage or 0.002 mV whichever is greater;
mV (- 10 to 100 mV), TC (NBS: E, J, K, N; DIN: L, U): ± 0.03% of the input milivoltage or 0.01 mV whichever is greater; mV (-50 to 500 mV): ± 0.03% of the input milivoltage or 0.05 mV whichever is greater;
Ohms (0 to 100Ω), RTD (GE: Cu10): ± 0.03% of the input resistance or 0.01Ω whichever is greater;
TECHNICAL CHARACTERISTIC
6.1
TT301 – Operation and Maintenance Instruction Manual
Performance Specifications
Ohms (0 to 400Ω), RTD (DIN: Ni120; IEC: Pt50, Pt100; JIS: Pt50, Pt100): ± 0.03% of the input resistance or 0.04 Ω
whichever is greater;
Ohms (0 to 2000Ω), RTD (IEC: Pt500), RTD (IEC: Pt1000): ± 0.03% of the input resistance or 0.2 Ω whichever is greater; TC: cold-junction compensation rejection 60:1 (Reference: 25.0 ± 0.3 °C).
Power Supply Effect
± 0.005% of calibrated span per volt.
Vibration Effect
Meets SAMA PMC 31.1.
Electromagnetic Interference Effect
According to IEC61326-1:2006, IEC61326-2-3:2006, IEC61000-6-4:2006, IEC61000-6-2:2005.
Physical Specifications
Electrical Connection
1/2 - 14 NPT, PG 13.5 DIN, and M20 X 1.5.
Material of Construction
Injected low copper aluminum with polyester painting or 316 Stainless Steel housing, with Buna N O’rings on cover
(NEMA 4X, IP67).
Mounting
Can be attached directly to the sensor. With an optional bracket can be installed on a 2" pipe or fixed on a wall or panel.
Approximate Weights
Without display and bracket mounting: 0.80 kg Add to the display: 0.13 kg Add to the bracket mounting : 0.60 kg
Control Characteristic
PID
PID. Proportional Gain: 0 to 100. Integral Time: 0.01 to 999 min/rep. Derivative Time: 0 to 999 s. Direct/Reverse Action. Lower and Upper output limits: -0.6 to +106.25%. Output rate-of-change limit: 0.02 to 600 %/s. Power-on safety output: -0.6 to +106.25%. Antireset windup. Bumpless Auto/Manual transfer. Setpoint Generator up to 16 points, up to 19999 minutes.
Alarm
Dual, trip levels adjustable over entire range. High or Low action. Acknowledge message.
6.2
Technical Characteristics
2, 3 or 4 wires
SENSOR
TYPE
RANGE °C
RANGE °F
MINIMUM
SPAN °C
°C DIGITAL
ACCURACY*
RTD
Cu10
GE
-20
to
250
-4
to
482
50
± 1.0
Ni120
Edison Curve #7
-50
to
270
-58
to
518 5 ± 0.1
Pt50
IEC 751-83 (0.00385)
-200
to
850
-328
to
1562
10
± 0.25
Pt100
IEC 751-83 (0.00385)
-200
to
850
-328
to
1562
10
± 0.2
Pt500
IEC 751-83 (0.00385)
-200
to
450
-328
to
842
10
± 0.2
Pt1000
IEC 751-83 (0.00385)
-200
to
300
-328
to
572
10
± 0.2
Pt50
JIS 1604-81 (0.003916)
-200
to
600
-328
to
1112
10
± 0.25
Pt100
JIS 1604-81 (0.003916)
-200
to
600
-328
to
1112
10
± 0.25
Pt100
MIL-T-24388C (0.00392)
-40
to
540
-40
to
1000
10
± 0.2
Ni120
MIL-T-24388C (0.00672)
-40
to
205
-40
to
400 5 ± 0.13
Pt100
IEC 751-95 (0.00385)
-200
to
850
-328
to
1562
10
± 0.2
Pt100
GOST 6651-09 (0.003911)
-200
to
850
-328
to
1562
10
± 0.2
Pt50
GOST 6651-09 (0.003911)
-200
to
850
-328
to
1562
10
± 0.2
Cu100
GOST 6651-09 (0.00426)
-50
to
200
-58
to
392
10
± 0.15
Cu50
GOST 6651-09 (0.00426)
-50
to
200
-58
to
392
10
± 0.15
THERMOCOUPLE
B
NBS Monograph 125
100
to
1800
212
to
3272
50
± 0.5**
E
NBS Monograph 125
-100
to
1000
-148
to
1832
20
± 0.2
J
NBS Monograph 125
-150
to
750
-238
to
1382
30
± 0.3
K
NBS Monograph 125
-200
to
1350
-328
to
2462
60
± 0.6
N
NBS Monograph 125
-100
to
1300
-148
to
2372
50
± 0.5
R
NBS Monograph 125
0
to
1750
32
to
3182
40
± 0.4
S
NBS Monograph 125
0
to
1750
32
to
3182
40
± 0.4
T
NBS Monograph 125
-200
to
400
-328
to
752
15
± 0.15
L
DIN 43710
-200
to
900
-328
to
1652
35
± 0,35
U
DIN 43710
-200
to
600
-328
to
1112
50
± 0.5
L
GOST 8.585-01
-200
to
800
-328
to
1472
60
± 0.4
W5Re/
ASTM E 988-06
0
to
2200
32
to
3992
60
± 0.5
SENSOR
RANGE
mV
MINIMUM
SPAN mV
*DIGITAL
ACCURACY %
SENSOR
RANGE
Ohm
MINIMUM
SPAN Ohm
*DIGITAL
ACCURACY %
mV
-6 to 22
0.40
± 0.02% or ± 2 µV
Ohm
0 to 100
1
± 0.02% or ± 0.01 Ohm
-10 to 100
2.00
± 0.02% or ± 10 µV
0 to 400
4
± 0.02% or ± 0.04 Ohm
-50 to 500
10.00
± 0.02% or ± 50 µV
0 to 2000
20
± 0.02% or ± 0.20 Ohm
* Accuracy of value read on display and accessed by communication. The 4-20 mA accuracy is the digital accuracy ±0.03%
** Not applicable for the first 20% of the range (up to 440 °C).
Table 6.1 - 2, 3 or 4 wires Sensor Characteristics
Table 6.2 - mV Sensor Characteristics Table 6.3 - Ohm Sensor Characteristics
* Accuracy of value read on display and accessed by communication. The 4-20 mA accuracy is the digital accuracy ±0.03% ** Not applicable for the first 20% of the range (up to 440 °C). NA Not applicable.
6.3
TT301 – Operation and Maintenance Instruction Manual
MODEL
TEMPERATURE TRANSMITTER
COD.
Local Indicator (1)
0
Without Indicator
1
With Digital Indicator
COD.
Mounting Bracket
0
1
Without Bracket Carbon Steel Bracket
2 7
316 SST Bracket Carbon Steel Bracket with 316 SST Fasteners
A
Flat, 304 SST bracket and 316 SST accessories
COD.
Electrical Connections
0
1
2
1/2 - 14 NPT (3) 1/2 - 14 NPT X 3/4 NPT (316 SST) - With adapter (4) 1/2 - 14 NPT X 3/4 BSP (316 SST) - With adapter (2)
3 A B
1/2 - 14 NPT X 1/2 BSP (316 SST) - With adapter (2) M20 x 1.5 (5) PG 13.5 DIN (6)
Z
According to user´s notes
COD.
Housing Material (8) (9)
H0
H1
H2
Aluminum (IP/TYPE) 316 SST (IP/TYPE) Aluminum for saline atmosphere (IPW/TYPEX) (10)
H3 H4
316 SST for saline atmosphere (IPW/TYPEX) (10) Copper Free Aluminum (IPW/TYPEX) (10)
COD.
Identification Plate
I1 I3
FM: XP, IS, NI, DI CSA: XP, IS, NI, DI
I4 I5
EXAM (DMT): Ex-ia; NEMKO: Ex-d
CEPEL: Ex-d, Ex-ia
I6 I7
Without Certification EXAM (DMT): Group I, M1 Ex-ia
NEPSI: Ex-ia
COD.
Tag Plate (7)
J0
J1
With tag, when specified (Default) Blank
J2
User specification
COD.
Sensor Connection
L2
L3
L4
2-wire 3-wire 4-wire
LF
LB
Differential Backup
COD.
PID Configuration
M0
With PID (default)
M1
Without PID
COD.
LCD1 Indication
Y0
Y1
Percentage (default) Current (mA)
Y3
YU
Temperature (Engineering unit) User specification
COD.
LCD2 Indication
Y0
Y4
Percentage (default) Current (mA)
Y6
YU
Temperature (Engineering unit) User specification
COD.
P0
P3
P4
P5
Gray Munsell N 6,5 Polyester (Default) Black Polyester White Epoxy Yellow Polyester
P8 P9 PC
Without Painting Safety Blue Epoxy – Electrostatic Painting Safety Blue Polyester ­Electrostatic Painting
COD.
Sensor Type
T1
T2
T3
T4
T5
T6
T7
T8
T9
TA
TB
TC
TD
TE
TF
TG
TH
RTD Cu10 - GE RTD Ni120 - DIN RTD PT50 - IEC RTD PT100 - IEC RTD PT500 - IEC RTD PT50 - JIS RTD PT100 - JIS 2K OHM 400 OHM Thermocouple type B - NBS Thermocouple type E - NBS Thermocouple type J - NBS Thermocouple type K - NBS Thermocouple type N – NBS Thermocouple type R - NBS Thermocouple type S - NBS Thermocouple type T - NBS
TK
TP TN TO TQ TR
TS
TT TU
TV
TW
TX
10
11
12
13
TZ
Thermocouple type L – DIN Thermocouple type U - DIN 100 OHM Special OHM 22 mV 100 mV 500 mV Special mV RTD PT1000 – IEC RTD PT100 - MILT RTD NI120 – MILT RTD PT100 – IEC RTD PT100 – GOST RTD PR50 – GOST CU100 – GOST CU50 – GOST Especial
TT301 1 2 0 H1
I1
JO
L2
M0
Y0
Y0
P8
T1
NOTE
(1) Values limited to 4 1/2 digits; units limited to 5 characters. (2) Options not certified for use in hazardous locations. (3) Certified for use in hazardous locations (CEPEL, CSA, FM, NEMKO, EXAM)
(4) Certified for use in hazardous locations (CEPEL, CSA, FM) (5) Certified for use in hazardous locations (CEPEL, FM, NEMKO, EXAM) (6) Certified for use in hazardous locations (CEPEL, NEPSI, EXAM) (7) Rectangular plate in 316 SST. (8) IPX8 tested in 10 meters of water column for 24 hours. (9) Ingress Protection:
Products
CEPEL
NEMKO / EXAM
FM
CSA
NEPSI
TT300
IP66/68W
IP66/68W
Type 4X/6(6P)
Type 4X
IP67
(10) IPW/Type tested for 200 hours according to NBR 8094 / ASTM B 117 standard.
Ordering Code
6.4
Appendix A
CERTIFICATIONS INFORMATION
European Directive Information
Other Certifications
Hazardous Locations Certifications
Authorized representative in European Community
Smar Gmbh-Rheingaustrasse 9-55545 Bad Kreuzanach
EMC Directive (2004/108/EC) – Electromagnetic Compatibility
The EMC test was performed according to IEC standard: IEC61326-1:2006, IEC61326-2­3:2006, IEC61000-6-4:2006, IEC61000-6-2:2005. For use only in industrial environment.
ATEX Directive (94/9/EC) – Equipment and protective systems intended for use in potentially explosive atmospheres.
This product was certified according European Standards at NEMKO and EXAM (former DMT). The certified body for manufacturing quality assessment is EXAM (number 0158).
LVD Directive 2006/95/EC – Electrical Equipment designed for use within certain voltage limits
According the LVD directive Annex II the equipment under ATEX “Electrical equipment for use in an explosive atmosphere” directive are excluded from scope from this directive.
IP68 Report:
Certifier Body: CEPEL
Tests for Ingress Protection IP68 – CEPEL DVLA – 7390/05C This report not applies to hazardous locations Ex d protection and with Drawing 101B­4740-00. For guarantee the ingress of protection IP68 in the electrical connection input with NPT thread must be applied a threadlocker like Loctite 262.
Documents for manuals:
Label Plate: 101A-8823
North American Certifications
FM Approvals Certificate N: FM 3W0A4.AX
Intrinsically Safe for use in Class I, Division 1, Groups A, B, C and D, Class II, Division 1, Groups E, F and G, Class III, Division 1; in accordance with entity requirements and control drawing 102A-0005. Entity parameter: Vmax = 30 Vdc Imax = 110 mA Ci = 5 nF Li = 8 uH. Non- incendive for Class I, Division 2, Groups A, B, C and D. Explosion-proof for Class I, Division 1, Groups A, B, C, and D; Dust-ignition proof for Class II and Class III, Division 1, Groups E, F, and G; hazardous locations. Ambient Temperature: (-20ºC < T Enclosure Type 4X/6 or Type4/6.
Canadian Standards Association (CSA) Certificate N: CSA1110996
Class 2258 02 Explosion Proof for Class I, Division 1, Groups B, C and D; Class II, Division 1, Groups E, F and G; Class III, Division 1; Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups E, F and G; Class III, conduit seal not required.
Class 2258 03 Intrinsically Safe and Non-Incendive Systems for Class I, Division 1, Groups A, B, C and D; Class II, Division 1, Groups E, F and G; Class III, Division 1
<+60ºC).
amb
A.1
Operation and Maintenance Instruction Manual – TT301
• Intrinsically safe when connected through CSA Certified Diode Safety Barrier, 28V max, 300 ohms min, per Smar Installation Drawing 102A-0436.
Class 2258 04 Intrinsically Safe, Entity – For Hazardous Locations for Class I, Division 1, Groups A, B, C and D; Class II, Division 1, Groups E, F and G; Class III, Division 1
• Intrinsically safe with entity parameters: Vmax = 28 V Imax = 110 mA Ci = 5 nF Li = 0 H, when connected through CSA Certified Safety Barriers as per Smar Installation Drawing 102A-
0436. Ambient Temperature: (-20ºC < T
Enclosure Type 4X or Type 4.
European Certifications
amb
Explosion Proof (Nemko 13 ATEX 1570)
Group II, Category 2 G, Ex d, Group IIC, Temperature Class T6, EPL Gb Ambient Temperature: -20 to 60 ºC
Environmental Protection (Nemko 13 ATEX 1570)
Options: IP66/68 or IP66W/68W The Essential Health and Safety Requirements are assured by compliance with:
EN 60079-0:2012 General Requirements EN 60079-1:2007 Flameproof Enclosures “d”
Certificate No: DMT 01 ATEX E 150
Intrinsically Safe Group I M2, Ex ia I Group II 2 G, Ex ia, IIC Temperature Class:
T4 (-40ºC< T  T5 (-40ºC< T  T6 (-40ºC< T
• Entity Parameters: Ui = 28 Vdc Ii = 93 mA Ci ≤ 5 nF Li = neg
South America Certification
INMETRO approvals
<+85ºC @ Pi=700mW)
amb
<+50ºC @ Pi=700mW )
amb
<+40ºC @ Pi=575mW )
amb
Certificate No: CEPEL-Ex-050/95
Intrinsically safe - Ex-ia IIC T5
• Entity Parameters: Ui = 30 Vdc Ii = 100 mA Ci =6,4nF Li = neg Pi=0,7W Ambient Temperature: (-20ºC < T
amb
Certificate No: CEPEL-Ex-43/96-1
Flameproof - Ex-d IIC T6 Ambient Temperature: (-20ºC < T
amb
Enclosure IP66/68 or IP66/68W.
Identification Plate and Control Drawing
Identification Plate
Identification for hazardous locations:
FM
<+40ºC).
<+65ºC).
<+40ºC).
A.2
Certifications Information
CSA
NEMKO and DMT
CEPEL
A.3
Operation and Maintenance Instruction Manual – TT301
WITHOUT APPROVAL
Identification for hazardous locations for use in saline atmosphere:
FM
CSA
NEMKO and DMT
A.4
Certifications Information
CEPEL
A.5
Operation and Maintenance Instruction Manual – TT301
Control Drawing
Factory Mutual (FM)
A.6
Certifications Information
NEMKO
A.7
Operation and Maintenance Instruction Manual – TT301
Canadian Standards Association (CSA)
A.8
Appendix B
SRF–SERVICE REQUEST FORM
Proposal No.:
Company:
Unit:
Receipt of Remittance:
Warranty
Yes ( ) Purchase Order:
No ( )
COMMERCIAL CONTACT
TECHNICAL CONTACT
Full name:
Full name:
Position:
Position:
Phone: Extension:
Phone: Extension:
Fax:
Fax:
Email:
Email:
EQUIPMENT DATA / TEMPERATURE SENSOR
Model: TT301 ( ) TT302 ( ) TT303 ( ) TT400SIS ( ) TT411 ( ) TT421 ( )
Serial Number:
Sensor Type and Connection:
Measurement type: ( ) Double Sensor ( ) Average between Sensors ( ) Differential ( ) Backup ( ) Single
INFORMATION AND DESCRIPTION OF THE FAILURE
Environment Temperature (ºC)
Work Temperature (ºC)
Calibration Range
Min:
Max:
Min :
Max:
Min:
Max:
Operation Time:
Failure Data:
IMPORTANT COMMENTS ABOUT EQUIPMENT APPLICATION AND PROCESS
(Please, inform more details about the application, installation, etc.).
FAILURE DESCRIPTION OR BAD OPERATION
(Please, describe the behavior of the fail, if it is repetitive, how it exactly happens, and so on.)
NOTES
For warranty or non-warranty repair, please contact your representative.
Further information about address and contacts can be found on www.smar.com/contactus.asp.
B.1
SRF – Service Request Form
B.2
Loading...