SMAR if303 Operation, Maintenance & Instruction Manual

IF303
VERSION 3
I F303ME
smar
Specifications and information are subject to change without notice.
Up-to-date address information is available on our website.
web: www.smar.com/contactus.asp
www.smar.com
Kpvtqfwevkqp"
"
INTRODUCTION
The IF303 is a converter mainly intended to interface analog transmitters to a Profibus PA network. The IF303 receives up to three current signal typically 4-20 mA or 0-20 mA, and makes them available to Profibus PA system. The digital technology used in the IF303 enables an easy interface between the field and the control room and it has several interesting features that reduce considerably the installation, operation and maintenance costs.
The IF303 is part of SMAR's complete 303 line of Profibus PA devices.
Profibus PA, is not only a replacement for 4-20 mA or intelligent/smart transmitter protocols, it contains much more.
The digital technology used in the IF303 enables the choice of several types of transfer functions, an easy interface between the field and the control room and several interesting features that considerably reduce the installation, operation and maintenance costs.
Some of the advantages of bi-directional digital communications are known from existing smart transmitter protocols: Higher accuracy, multi-variable access, remote configuration and diagnostics, and multi-dropping of several devices on a single pair of wires.
The system controls variable sampling, algorithm execution and communication so as to optimize the usage of the network, not loosing time. Thus, high closed loop performance is achieved.
Using Profibus technology, with its capability to interconnect several devices, very large control schemes can be constructed. In order too be user friendly the function block concept was introduced
The IF303, like the rest of the 303 family, has some Function Blocks built in, like Analog Input and Totalizer Blocks.
The need for implementation of Fieldbus in small as well as large systems was considered when developing the entire 303 line of Profibus-PA devices. They have common features and can be configured locally using a magnetic tool, eliminating the need for a configuration tool or console in many basic applications.
Get the best result of the IF303 by carefully reading these instructions.
NOTE
In case of using Simatic PDM as the configuration and parameterization tool, Smar recommends that the user does not apply the option "Download to Device". This function can improperly configure the field device. Smar recommends that user make the use of the option "Download to PG / PC" and then selecting the Device Menu, use the menus of the transducer, function and display blocks acting specifically, according to each menu and method for reading and writing.
This product is protected by US patent number 5,706,007.
KKK"
KH525"/"Qrgtcvkqp"cpf"Ockpvgpcpeg"Kpuvtwevkqp"Ocpwcn"
t
r
c
r
y
This Manual is compatible with version 3.XX, where 3 denotes software version and XX software release. The indication 3.XX means that this manual is compatible with any release of software version 3.
Waiver of responsibility
The contents of this manual abides by the hardware and software used on the current equipmen version. Eventually there may occur divergencies between this manual and the equipment. The information from this document are periodically reviewed and the necessary or identified corrections will be included in the following editions. Suggestions for their improvement are welcome.
Warning
For more objectivity and clarity, this manual does not contain all the detailed information on the product and, in addition, it does not cover every possible mounting, operation or maintenance cases.
Before installing and utilizing the equipment, check if the model of the acquired equipment complies with the technical requirements for the application. This checking is the user’s responsibility.
If the user needs more information, or on the event of specific problems not specified or treated in this manual, the information should be sought from Smar. Furthermore, the user recognizes that the contents of this manual by no means modify past or present agreements, confirmation or judicial relationship, in whole or in part.
All of Smar’s obligation result from the purchasing agreement signed between the parties, which includes the complete and sole valid warranty term. Contractual clauses related to the warranty are not limited nor extended by virtue of the technical information contained in this manual.
Only qualified personnel are allowed to participate in the activities of mounting, electrical connection, startup and maintenance of the equipment. Qualified personnel are understood to be the persons familiar with the mounting, electrical connection, startup and operation of the equipment or othe similar apparatus that are technically fit for their work. Smar provides specific training to instruct and qualify such professionals. However, each country must comply with the local safety procedures, legal provisions and regulations for the mounting and operation of electrical installations, as well as with the laws and regulations on classified areas, such as intrinsic safety, explosion proof, increased safety and instrumented safety systems, among others.
The user is responsible for the incorrect or inadequate handling of equipments run with pneumati or hydraulic pressure or, still, subject to corrosive, aggressive or combustible products, since thei utilization may cause severe bodily harm and/or material damages.
The field equipment referred to in this manual, when acquired for classified or hazardous areas, has its certification void when having its parts replaced or interchanged without functional and approval tests by Smar or any of Smar authorized dealers, which are the competent companies for certifying that the equipment in its entirety meets the applicable standards and regulations. The same is true when converting the equipment of a communication protocol to another. In this case, it is necessar sending the equipment to Smar or any of its authorized dealer. Moreover, the certificates are different and the user is responsible for their correct use.
Always respect the instructions provided in the Manual. Smar is not responsible for any losses and/or damages resulting from the inadequate use of its equipments. It is the user’s responsibility to know and apply the safety practices in his country.
NOTE
KX"
Vcdng"qh"Eqpvgpvu"
TABLE OF CONTENTS
UGEVKQP"3"/"KPUVCNNCVKQP"000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000"303"
GENERAL ..................................................................................................................................................................................... 1.1
MOUNTING .................................................................................................................................................................................. 1.1
ELECTRIC WIRING ...................................................................................................................................................................... 1.1
TOPOLOGY AND NETWORK CONFIGURATION ....................................................................................................................... 1.3
INTRINSIC SAFETY BARRIER .................................................................................................................................................... 1.4
JUMPER CONFIGURATION ........................................................................................................................................................ 1.5
POWER SUPPLY ......................................................................................................................................................................... 1.5
INPUT WIRING ............................................................................................................................................................................. 1.5
INSTALLATION IN HAZARDOUS AREAS ................................................................................................................................... 1.7
EXPLOSION/FLAME PROOF ....................................................................................................................................................... 1.7
INTRINSICALLY SAFE ................................................................................................................................................................. 1.7
UGEVKQP"4"/"QRGTCVKQP"0000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000"403"
FUNCTIONAL DESCRIPTION – ELECTRONICS .......................................................................................................................... 2.1
UGEVKQP"5"/"EQPHKIWTCVKQP"00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000"503"
TRANSDUCER BLOCK .................................................................................................................................................................. 3.1
HOW TO CONFIGURE A TRANSDUCER BLOCK......................................................................................................................... 3.1
TERMINAL NUMBER ..................................................................................................................................................................... 3.1
FUNCTIONAL DIAGRAM OF THE CURRENT TO PROFIBUS PA TRANSDUCER BLOCK ......................................................... 3.2
CURRENT TO PROFIBUS PA TRANSDUCER BLOCK GENERAL PARAMETER DESCRIPTION .............................................. 3.2
TRANSDUCER BLOCK PARAMETER ATTRIBUTES .................................................................................................................... 3.4
IF303 - CYCLIC CONFIGURATION................................................................................................................................................ 3.5
HOW TO CONFIGURE THE ANALOG INPUT BLOCK .................................................................................................................. 3.9
HOW TO CONFIGURE THE TOTALIZER BLOCK ....................................................................................................................... 3.12
CURRENT TRIM ........................................................................................................................................................................... 3.16
VIA LOCAL ADJUSTMENT .......................................................................................................................................................... 3.19
TRANSDUCER DISPLAY – CONFIGURATION ........................................................................................................................... 3.20
DISPLAY TRANSDUCER BLOCK ................................................................................................................................................ 3.21
DEFINITION OF PARAMETERS AND VALUES .......................................................................................................................... 3.21
PROGRAMMING USING LOCAL ADJUSTMENT ........................................................................................................................ 3.26
QUICK GUIDE – LOCAL ADJUSTMENT TREE ........................................................................................................................... 3.28
J1 JUMPER CONNECTIONS ....................................................................................................................................................... 3.29
W1 JUMPER CONNECTIONS ..................................................................................................................................................... 3.29
CYCLICAL DIAGNOSIS ................................................................................................................................................................ 3.31
UGEVKQP"6"/"OCKPVGPCPEG"RTQEGFWTGU0000000000000000000000000000000000000000000000000000000000000000000000000000000000000000000"603"
GENERAL ..................................................................................................................................................................................... 4.1
TROUBLESHOOTING .................................................................................................................................................................. 4.1
DISASSEMBLY PROCEDURE ..................................................................................................................................................... 4.2
REASSEMBLY PROCEDURE ...................................................................................................................................................... 4.2
BOARDS INTERCHANGEABILITY .............................................................................................................................................. 4.3
EXPLODED VIEW ........................................................................................................................................................................ 4.3
ACCESSORIES AND RELATED PRODUCTS ............................................................................................................................. 4.3
SPARE PARTS LIST .................................................................................................................................................................... 4.4
UGEVKQP"7"/"VGEJPKECN"EJCTCEVGTKUVKEU"00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000"70 3"
ORDERING CODE ......................................................................................................................................................................... 5.2
CRRGPFKZ"C"/"EGTVKHKECVKQPU"KPHQTOCVKQP"00000000000000000000000000000000000000000000000000000000000000000000000000000000000000"C03"
EUROPEAN DIRECTIVE INFORMATION ...................................................................................................................................... A.1
HAZARDOUS LOCATIONS GENERAL INFORMATION ................................................................................................................ A.1
HAZARDOUS LOCATIONS APPROVALS ..................................................................................................................................... A.2
IDENTIFICATION PLATE ............................................................................................................................................................... A.5
CONTROL DRAWING .................................................................................................................................................................... A.7
CSA (CANADIAN STANDARDS ASSOCIATION) ..................................................................................................................................... A.2
FM APPROVALS (FACTORY MUTUAL) ................................................................................................................................................... A.3
NEMKO (NORGES ELEKTRISKE MATERIELKONTROLL) ..................................................................................................................... A.3
EXAM (BBG PRÜF - UND ZERTIFIZIER GMBH) ..................................................................................................................................... A.3
CEPEL (CENTRO DE PESQUISA DE ENERGIA ELÉTRICA) ................................................................................................................. A.4
X"
KH525"/"Qrgtcvkqp"cpf"Ockpvgpcpeg"Kpuvtwevkqp"Ocpwcn"
CRRGPFKZ"D""UTH""UGTXKEG"TGSWGUV"HQTO"0000000000000000000000000000000000000000000000000000000000000000000000000000000000000"D03"
RETURNING MATERIALS ............................................................................................................................................................. B.2
KX"
"
Kpuvcnncvkqp"Hnqyejctv"
Start
Kpuvcnncvkqp"Hnqyejctv"
Was the converter
configured on the bench
to match the application?
No
Configure the engineering unit.
Configure the terminal(s)
and input scale(s) .
(Section 3 - Calibration)
Configure the LCD reading.
(Section 3 - Configuration)
Simulate the value(s) in the 4 a
20 mA input and verify the
signal(s) in Fieldbus.
Yes
Install the converter on the field following the instructions below.
Install the preferably
on wether-protected areas.
Check the area classification
Install the (mechanically
and electrically) according to the
application after checking the best
(Section 4 - Maintenance).
converter
and its practices.
converter
position for the LCD
Is the indication correct?
No
See section 4 - Maintenance
Yes
Power-up the properly.
IF303 needs a external power supply
for supply the equipment .
converter
4 - 20 mA
OK
XKK"
KH525"/"Qrgtcvkqp"cpf"Ockpvgpcpeg"Kpuvtwevkqp"Ocpwcn"
XKKK"
Section 1
General
Mounting
Electric Wiring
INSTALLATION
NOTE
The installation carried out in hazardous areas should follow the recommendations of the IEC60079-14 standard.
The overall accuracy of measurement and control depends on several variables. Although the converter has an outstanding performance, proper installation is essential, in order to maximize its performance.
Among all factors, which may affect converter accuracy, environmental conditions are the most difficult to control. There are, however, ways of reducing the effects of temperature, humidity and vibration.
Locating the converter in areas protected from extreme environmental changes can improve the converter performance.
In warm environments, the converter should be installed to avoid as much as possible, direct exposure to the sun. Installation close to lines and vessels subjected to high temperatures shou ld also be avoided.
Use of sunshades or heat shields to protect the converter from external heat sources should be considered, if necessary.
Humidity is fatal to electronic circuits. In areas subjected to high relative humidity, the O-rings for the electronics cover must be correctly placed. Removal of the electronics cover in the fiel d should be reduced to the minimum necessary, since each time it is removed the circuits are exposed to the humidity. The electronic circuit is protected by a humidity proof coatin g, but frequent exposures to humidity may affect the protection provided. It is also important to keep the covers tightened in place. Every time they are removed, the threads are exposed to corrosion, since painting cannot protect these parts. Code-approved sealing methods on conduit enteri ng the converter should be employed.
Using the bracket, the mounting may be done in several positions, as shown on Figure 1.3 ­Dimensional Drawing and Mounting Positions.
For better visibility, the digital indicator may be rot ated in steps of 90° (See Section 4 - Maintenance Procedures).
Access the wiring block by removing the Electrical Connection Cover. This cover can be locked closed by the cover locking screw (See Figure 1.1 - Cover Locking) To release the cover, rotate the locking screw clockwise.
Cable access to wiring connections is obtained by one of the two conduit outlets. Con duit threads should be sealed by means of code-approved sealing methods. The unused outlet connection should be plugged accordingly.
The wiring block has screws, on which fork or ring type terminals can be fastened, see Figure 1.2 ­Terminal
Block.
1.1
IF303 - Operation and Maintenance Instruction Manual
A
COVER LOCKING SCREW
Figure 1.1 - Cover Locking
For convenience there are three ground terminals: one inside the cover and two externa ls, located close to the conduit entries.
PROFIBUS PA
ND POWER SUPPLY
TERMINALS
GROUND TERMINAL
INPUT
TERMINALS (3)
COMUNICATION
TERMINALS
INPUT GROUND TERMINAL
Figure 1.2 - Terminal Block
The IF303 uses the 31.25 kbi t/s voltage mode option for the phys ical signaling. All other devices on the same bus must use the same signaling.
Various types of Fieldbus devices may be connected on the same bus. The IF303 is powered via the bus. The limit for such devices is according to the DP/PA coupler
limitations for one bus (one segment) for non-intrinsically safe requirement. In hazardous area, the number of devices ma y be limited by intrins ically safe restrictions, according
to the DP/PA coupler and barriers limitations. The IF303 is protected against reverse polarity, and can withstand ±35 VDC without damage, but it
will not operate when in reverse polarity.
NOTE
Please refer to the General Installation, Operation and Maintenance Procedures Manual for more details.
1.2
PLUG
ALLOW 150 MM MINIMUM FOR LOCAL ZERO AND SPAN ADJUSTMENT WITH MAGNETIC TOOL.
COMMUNICATIONS TERMINAL
PLUG
CONDUIT CONNECTION
WALL OR
PANEL MOUNTING
Installation
PIPE 2"
Figure 1.3 - Dimensional Drawing and Mounting Positions
Topology and Network Configuration
Bus topology (See Figure 1.4 - Bus Topology) and tree top ology (See Figure 1.5 - Tree Topology) are supported. Both types have a trunk cable with two terminations. The devices are c onnected to the trunk via spurs. The spurs may be integrated in the device giving zero spur length. A spur may connect more than one device, depending on the lengt h. Active couplers may be used to extend spur length.
Active repeaters may be used to extend the trunk length. The total cable length, including spurs, between any two devices in the Fieldbus sho uld not exceed
1900m. The connection of couplers should be kept less than 15 per 250m. In folowing figures DP/PA link
depends on the application needs.
MOUNTING
BRACKET
FOR WALL MOUNTING
2 EXPANSION ANCHOR ­2 HEXAGON SCREW -
FOR PANEL MOUNTING
2 BOLT AND NUTS - 1/4”X30 NOT INCLUDED
S8
3/16”X70
Figure 1.4 - Bus Topology
1.3
IF303 - Operation and Maintenance Instruction Manual
Intrinsic Safety Barrier
When the Fieldbus is in an area requiring intrinsic safety, a barrier must be inserted on the trunk between the power supply and the DP/PA coupler, when it is Non-Ex type.
Use of DF47 is recommended.
Jumper Configuration
In order to work properly, the jumpers J1 and W1 located in the IF303 main board must be correctly configured (See Table 1.1 - Description of the Jumpers).
J1 This jumper enables the simulation mode parameter in the AI block.
W1 This jumper enables the local adjustment programming tree.
Power Supply
The IF303 receives power from the bus via the si gnal wiring. The power supply may come from a separate unit or from another device such as a controller or DCS.
The voltage should be between 9 to 32 Vdc for non-intrinsic safe applications. A special requirement applies to the power supply used in an intrinsica lly safe bus and depends on
the type of barrier used. Use of PS302 is recommended as power supply.
Figure 1.5 - Tree Topology
Table 1.1 - Description of the Jumpers
1.4
Input Wiring
CO
Installation
The IF303 accepts up to three current inp uts in the range 0-20 mA or 4-20 mA. The three inputs have a common ground and they are protected from rever se polarity signal. The inputs should be connected as per Figure 1.6 - Input Wiring.
4 to 20mA
1
TRANSMITTER 1
PROFIBUS PA
+
Power Supply
-
TR = Transmitter
+
+
+
4-20mA
TR
TR
TR
2
IF303
3
4
Note that IF303 can operate with 0-20 mA or 4-20mA transmitters (See Figure 1.7 - Connection).
11
-
-
-
CHANNEL1
22
CHANNEL 2
3
CHANNEL 3
44
COMMON
Figure 1.6 - Input Wiring
TRANSMITTER 2
TRANSMITTER 3
+
0-20mA
­+
0-20mA
-
0-20mA
-
4-wire 0-20mA Transmitters or 0-20mA Current Generator
POWER SUPPLY
CHANNEL1
CHANNEL 2
3
CHANNEL 3
+
COMMON
NNECTION
Figure 1.7 - Connection
Avoid routing input wiring close to power cables or switching equipment.
WARNING
Apply in the inputs of the conversor only current levels. Don't apply tension levels, because the shunt resistors are of 100R 1W and tension above 10 Vdc it can damage them.
1.5
IF303 - Operation and Maintenance Instruction Manual
Installation in Hazardous Areas
Explosions could result in death or serious injury, besides financial damage. Installation of this converter in explosive areas must be carri ed out in accordance with the local standards and the protection type adopted .Before continuing the i nstallation make sure the certificate parameters are In accordance with the classified area where the equipment will be installed.
The instrument modification or parts replacement suppl ied by other than authorized representativ e of Smar is prohibited and will void the certification.
The converters are marked with options of the protection type. T he certification is valid only when the protection type is indicated by the user. Once a particular type of protection is selected, any other type of protection can not be used.
The electronic housing and the sensor installed in haz ardou s areas must h ave a minim um of 6 full y engaged threads. Lock the housing using the locking screw (Figure 1.1).
The cover must be tighten with at least 8 turns to avoi d the penetration of humidity or corrosive gases. The cover must be tighten until it touches the housing. Then, tight en more 1/3 turn (12 0) to guarantee the sealing. Lock the covers using the locking screw (Figure 1.1).
Consult the Appendix A for further information about certification.
Explosion/Flame Proof
In Explosion-Proof installations the cable entries must be connected or c losed using metal cable gland and metal blanking plug, both with at least IP66 and Ex-d certification.
The standard plugs provided by Smar are certifie d according to CEPEL certificate. If the plug needs to be replaced, a certified plug must be used.
The electrical connection with NPT thread must use waterproofing sealant. A non-hardening silicone sealant is recommended.
For NEMKO ATEX certificate please to follow the installation guide lines in hazardous locations below: Group II Category 2G, Ex d, Group IIC, Temperature Class T6, EPL Gb U = 28VDC Ambient Temperature: -20 to 60ºC for T6 Environmental Protection: IP66/687 or IP66W/687W The electrical connection available are ½ - 14NPT and M20x1,5.
Cable entries must be connected or closed using metal cable gland and metal blanking plug, both with at least IP66 and Ex-d certification or any appropriate ATEX approved metal cable gland and metal blanking plug. Do not remove the transmitter covers when power is ON.
Intrinsically Safe
In hazardous zones with intrinsically safe or non-incendive requirements, the circuit entity parameters and applicable installation procedures must be observed.
To protect the application the transmitter must be connected to a barrier. Match the parameters between barrier and the equipment (Consider the cable parameters). Associated apparatus ground bus shall be insulated from panels and mounting enclosures. Shield is optional. If used, be sure to insulate the end not grounded. Cable capacitance and inductance plus Ci and Li must be smaller than Co and Lo of the associated Apparatus.
It is not recommended to remove the transmitter cover when the power is ON.
WARNING
WARNING
WARNING
1.6
Section 2
OPERATION
The IF303 accepts signals from mA generators such as most conventional transmitters. It is therefore ideal for interfacing existing equipment to a Fieldbus system.
Functional Description – Electronics
See Figure 2.2 - IF303 Block Diagram. The function of each block is described below.
MUX Multiplexer
The MUX multiplexes the input terminals to ensure that all three channels reach the A/D converter.
A/D Converter
The A/D converts the input signals to a digital format for the CPU.
Signal Isolator
Its function is to isolate the data signal between the input and the CPU.
(CPU) Central Processing Unit, RAM and FLASH
The CPU is the intelligent portion of the converter, being responsible for the management and operation of block execution, self-diagnostics and comm unication. The program is stored in Flash memory. For temporary storage of data there is a RAM. The data in the RAM is lost if the po wer is switched off, however the device also has a nonvolatile EEPROM where data that must be retained are stored. Examples of such data are: calibration, configuration and identification data.
Communication Controller
It monitors line activity, modulates and demodulates the signal from network line.
Power Supply
Takes power of the loop-line to power the converter circuitry.
Power Isolation
Just like the signals from the input section, the power to the input section must be isolated.
Display Controller
Receives data from the CPU and drives the Liquid Crystal Display.
Local Adjustment
They are two switches that are magnetically activated. They can be activ ated by the magnetic tool without mechanical or electrical contact.
2.1
IF303 – Operation and Maintenance Instruction Manual
A
A
POWER SUPPLY
SIGNAL
SHAPING
Figure 2.1 - LCD Indicator
MAIN CIRCUIT BOARD INPUT CIRCUIT BOARD
POWER
ISOLATION
SUPPLY
FIRMWARE
DOWNLOAD
INTERFACE
FLASH
RAM
MODEM
LOCAL ADJUST
CPU
EEPROM
S
I G N
L
I S O L
T
I O N
(*) Resistor Shunt
(3 x 100R)
DISPLAY BOARD
DISPLAY
CONTROLLER
Apply in the inputs of the conversor only current levels. Don’t apply tensio n levels, because the shunt resistors are of 100R 1W and tension higher than 10 Vdc can damage them.
2.2
Figure 2.2 - IF303 Block Diagram
WARNING
Section 3
CONFIGURATION
One of the many advantages of using Fieldbus technologies is that device configuration is independent of the configuration software. The IF303 may be configured by a third party terminal or operator console as Smar’s configurators ProfibusView or AssetView for FDT.
The IF303 contains three input transducer blocks, one ph ysical block, on e display transdu cer block , three analog input and three totalizer function blocks.
Function Blocks are not covered in this manual. For further explanation and details of function blocks, see the “Function Blocks Manual”.
In order to assure correct values in the offline configuration, when using download function of Simatic PDM, please make sure you have done the upload firstly.
Offline Configuration
1. First run “Download to PG/PC” option to assure valid values.
2. Run after the Menu Device option to configure the required parameters using the related menus.
It is not advisable to use the “Download to Device” option. This function can misconfigure the equipment.
Transducer Block
Transducer block insulates function block from the specific I/O hardware, such as sensors and actuators. Transducer block controls access to I/O through manufacturer specific implementation. This permits the transducer block to execute as frequently as necessary to obtain good data from sensors without burdening the function blocks that use the data. It also insulates the function blocks from the manufacturer specific characteristics of certain hardware.
By accessing the hardware, the transducer block can get data from I/O or passing control data to it. The connection between Transducer block and Input/Output Function blocks is called channel. Normally, transducer blocks perform functions, such as linearization, characterization, temperature compensation, control and exchange data to/from hardware.
How to Configure a Transducer Block
The transducer block has an algorithm, a set of contained parameters and a cha nnel connecting it to a function block. The algorithm describes the behavior of the transducer as a data transfer functio n between the I/O hardware and other function block. The set of contained parameters, it means, you are not able to link them to other blocks, defines the user interface to the transducer block. They can be divided into Standard and Manufacturer Specific.
The standard parameters will be present for such class of device, as pressure, temperature, actuator, etc., whatever is the manufacturer. Oppositely, the manufacturers specific ones are defined only by its manufacturer. As common manufacturer specific parameter s, we have calibration settings, material information, linearization curve, etc.
When deforming a standard routine as a calibr ation, user is conducted step by step by a method. The method is generally defined as guide line to help the user to make common tasks. The Configuration Tool identifies each method associated to the parameters and enables the interface to it.
Terminal Number
It is the parameter, which makes reference to a physical input, which in the turn, is sent internally from the specified transducer output to function block.
It starts at channel one (1) for transducer number one until channel three (3) for transducer number three.
NOTE
3.1
IF303 – Operation and Maintenance Instruction Manual
The channel number of the AI block and TOT block is related to the transducer’s terminal number. Channel number 1, 2, 3 corresponds bi-univocally to the terminal block with the same number. Therefore, all user has to do is choosing c ombinations: (1.1), (2.2), (3,3) for (CHANNEL, BLOCK) respectively.
Functional Diagram of the Current To PROFIBUS PA Transducer Block
Figure 3.1 - Functional Diagram of the Current To PROFIBUS PA Transducer Block
Current To PROFIBUS PA Transducer Block General Parameter Description
Parameter Description
BACKUP_RESTORE
3.2
This parameter allows to save and to restore data according to factory and user calibration procedures. It has the following options:
1, "Factory Cal Restore", 2, "Last Cal Restore", 3, "Default Data Restore", 4, "Shut-Down Data Restore",
11, "Factory Cal Backup", 12, "Last Cal Backup", 14, "Shut-Down Data Backup",
Configuration
Parameter Description
0, "None".
CAL_MIN_SPAN
CAL_POINT_HI
CAL_POINT_LO
This parameter contains the minimum calibration span value allowed. This minimum span information is necessary to ensure that when calibration is done, the two calibrated points (high and low) are not too close together. Unit derives from SENSOR_UNIT.
This parameter contains the highest calibrated value. For calibration of the high limit point you give the high measurement value (pressure) to the sensor and transfer this point as HIGH to the transmitter. Unit derives from SENSOR_UNIT.
This parameter contains the lowest calibrated value. For calibration of the low limit point you give the low measurement value (pressure) to the sensor and transfer this point as LOW to the transmitter. Unit derives from SENSOR_UNIT.
Linearization Type:
LIN_TYPE
LOW_FLOW_CUT_OFF
0 – No Linearization 10 – Square Root
This is the point in percent of flow till that the output of the flow function is set to zero. It is used for suppressing low flow values. This is the point of the flow function where the curve changes from linear to square root
FLOW_LIN_SQRT_POINT
MAINT_DATE EEPROM_FLAG This parameter is used to indicate EEPROM saving process. FACTORY_GAIN_REFERENCE Factory calibration reference value. MAIN_BOARD_SN This is the main board serial number.
MAX_SENSOR_VALUE
MIN_SENSOR_VALUE
ORDERING_CODE Indicates information about the sensor and control from production factory.
PRIMARY_VALUE
PRIMARY_VALUE_TYPE
PRIMARY_VALUE_UNIT
SECONDARY_VALUE_1 This parameter contains the current value and status available to the Function Block.
SECONDARY_VALUE_1_UNIT
SECONDARY_VALUE_2
SECONDARY_VALUE_2_UNIT
SCALE_IN
SCALE_OUT
SENSOR_HI_LIM This parameter contains the sensor upper limit value. Unit derives from SENSOR_UNIT. SENSOR_LO_LIM This parameter contains the sensor lower limit value. Unit derives from SENSOR_UNIT.
SENSOR_UNIT
SENSOR_SN The serial number of sensor.
SENSOR_VALUE
TERMINAL_NUMBER
function.
The input has to be done in percent of flow.
The date of last maintenance.
Holds the maximum process SENSOR_VALUE. A write access to this parameter resets to the momentous value. The unit is defined in SENSOR_UNIT.
Holds the minimum process SENSOR_VALUE. A write access to this parameter resets to the momentous value. The unit is defined in SENSOR_UNIT.
This parameter contains the measured value and status available to the Function Block. The unit of PRIMARY_VALUE is the PRIMARY_VALUE_UNIT.
This parameter contains the application of the device. > 128: manufacturer specific This parameter contains the engineering units index code for the primary value. In this case the
unit code is mA (1211).
This parameter contains the current units of the SECONDARY_VALUE_1. In this case the unit code is mA (1211).
This parameter contains the measured value after input scaling and status available to the Function Block. The related unit is the SECONDARY_VALUE_UNIT_2. In this case the unit code is % (1342).
This parameter contains the units of the SECONDARY_VALUE_2 defined by the manufacturer. In the this case the unit code mA (1211).
This is the input conversion of the current into PRIMARY_VALUE using the high and low scale. The related unit is the PRIMARY_VALUE_UNIT.
This is the output conversion value using the high and low scale. The related unit is the PRIMARY_VALUE_UNIT.
This parameter contains the engineering units index code for the calibration values. In this case the unit code is mA (1211).
This parameter contains the raw sensor value. The uncalibrated measurement value from the sensor. Unit derives from SENSOR_UNIT.
The terminal number, which references a channel value, which is sent via internal, manufacturer­specific from AI function block to the specified transducer. It starts at one (1) for transducer
3.3
IF303 – Operation and Maintenance Instruction Manual
Parameter Description
number one until three (3) for transducer number three.
TRIMMED_VALUE
XD_ERROR
This parameter contains the sensor value after the TRIM processing. Unit derives from SENSOR_UNIT.
Indicates the condition of calibration process according to: {16, "Default value set"}, {22, "Applied process out of range"}, {26, "Invalid configuration for request"}, {27, "Excess correction"}, {28, "Calibration failed"}
Table 3.1 - Parameter Description
Transducer Block Parameter Attributes
Relative
Index
Parameter Mnemonic
8 SENSOR_VALUE Simple Float D 4 r C/a 0 - M (B)
9 SENSOR_H I_LIM Simple Float N 4 r C/a 0 - M (B) 10 SENSOR_LO_LIM Simple Float N 4 r C/a 0 - M (B) 11 CAL_POINT_HI Simple Float N 4 r,w C/a 20.0 - M (B) 12 CAL_POINT_LO Simple Float N 4 r,w C/a 4.0 - M (B) 13 CAL_MIN_SPAN Simple Float N 4 r C/a 0 - M (B) 14 MAINT_DATE Simple Octet String S 16 w,w C/a O(B) 15 SENSOR_UNIT Simple Unsigned 16 N 2 r,w C/a 1211 - M (B) 16 SENSOR_SN Simple Unsigned 32 N 4 r,w C/a - M (B) 17 TRIMMED_VALUE Record DS-33 D 5 r C/a 0.0 - M (B) 18 PRIMARY_VALUE Record DS-33 D 5 r C/a 0.0 - M (B) 1
PRIMARY_VALUE_UN
19
IT PRIMARY_VALUE_TY
20
PE SECONDARY_VALUE
21
_1 SECONDARY_VALUE
22
_1_UNIT SECONDARY_VALUE
23
_2 SECONDARY_VALUE
24
_2_UNIT
25 SCALE_IN Array Float S 8 r,w C/a
26 SCALE_OUT Array Float S 8 r,w C/a
MAX_SENSOR_VALU
27
E
Object
Type
Simple Unsigned 16 N 2 r,w C/a - - M (B)
Simple Unsigned 16 N 2 r,w C/a 255 - M (B)
Record DS-33 D 5 r C/a 0.0 - O (B)
Simple Unsigned 16 N 2 r,w C/a mA - O (B)
Record DS-33 D 5 r C/a 0 - O (B)
Simple Unsigned 16 N 2 r,w C/a % - O (B)
Simple Float N 4 r,w C/a 0.0 - O (B)
Data Type Store Size Access
... Standard Parameter 1
Additional Parameter for Transducer Block
Parameter
usage/
Type of
transport
Default
value
20.0
4.0
20.0
4.0
Down-
load
Order
Mandatory /
Optional
(Class)
- O(B)
- O(B)
View
3.4
Configuration
Relative
Index
33-40 RESERVED
Parameter Mnemonic
28 MIN_SENSOR_VALUE Simple Float N 4 r,w C/a 0.0 - O (B) 29 TERMINAL_NUMBER Simple Unsigned 8 S 1 r,w C/a 0 - O (B) 30 LIN_TYPE Simple Unsigned 8 S 1 r,w C/a 0 - O (B)
LOW_FLOW_CUT_OF
31
F FLOW_LIN_SQRT_POI
32
NT
41 BACKUP_RESTORE Simple Unsigned 8 S 1 r,w C/a 0 - O (B) 42 XD_ERROR Simple Unsigned 8 D 1 r C/a 0x10 - O (B) 43 MAIN_BOARD_SN Simple Unsigned 32 S 4 r,w C/a 0 - O (B) 44 EEPROM_FLAG Simple Unsigned 8 D 1 r C/a FALSE - O (B)
FACTORY_GAIN_REF
45
ERENCE
46 ORDERING_CODE Array Unsigned 8 S 50 r,w C/a - - O (B)
Object
Type
Simple Float S 4 r,w C/a 0 - O (B)
Simple Float S 4 r,w C/a 0 O (B)
Simple Float S 4 r,w C/a 0 - O (B)
Data Type Store Size Access
Parameter
usage/
Type of
transport
Default
value
Down-
load
Order
Mandatory /
Optional
(Class)
Table 3.2 - Parameter Attribute
See FUNCTION BLOCKS PROFIBUS PA manual for more parameters information, by visiting our web page on the Internet: http://www.smar.com.
IF303 - CYCLIC CONFIGURATION
The PROFIBUS DP and PROFIBUS PA protocols have mechanisms against communication failures between the slave device and the network master. For example, during initialization, these mechanisms are used to check these possible errors. After po wering up the field device (slave), it can cyclically exchange information with the class 1 mast er, if the parameterization for the slave is correct. This information is obtained using the GSD files (supplied by the device man ufacturer, it contains their descriptions). Through the commands below, the master executes all initialization process with the PROFIBUS PA device:
Get_Cfg: uploads the slave configuration on the master and checks network configuration; Set_Prm: writes to the slave parameters and executes the parameterization network; Set_Cfg: configures the slaves according to i ts outputs and inputs; Get_Cfg: another command, where the master checks the slave configuration.
All these services are based on the information obt ained from slave gsd files. The GSD file from IF303 shows details such as, hardware and software revision, device bus timing and i nformation about cyclic data exchange.
IF303 has 6 function blocks: 3 AIs (Analog Input) and 3 TOTs (Totalizer). It also has the empty module for applications where not all function blocks are necessary. The following cyclic order of the blocks should be respected: AI_1, AI_2, AI_3 and T OT_1, TOT_2, TOT_3. Suppose, only the AIs blocks are necessary, then configure this way: AI_1, AI_2, AI_3, EMPTY_MODULE, EMPTY_MODULE, EMPTY_MODULE.
Nevertheless, if you want to work only 1 AI and 1 TOT, configure them this way: AI_1, EMPTY_MODULE, EMPTY_MODULE and TOT_1, EMPTY_MODULE, EMPTY_MODULE.
Most PROFIBUS configuration tools use two directories where the different manufacturers’ GSD’s and BITMAPS files are stored. The GSD’s and BITMAPS for Smar devices can be obtained through the website: (https://www.smar.com), select "Download" option in the product specific page.
The following example shows the necessary steps to integrate the IF303 on a PROFIBUS system.
View
3.5
IF303 – Operation and Maintenance Instruction Manual
These steps are valid for the entire 303 line of Smar devices:
Copy the IF30 3 gsd file to the research directory of the PROFIBUS configuration tool, usually
called GSD;
Copy the IF303 b itmap file to the research director y of the PROFIBUS configuration tool usually
called BMP;
After choos ing the master, define the communication rate. Do not forget that the cou plers may
have the following fixed communication rates 45,45 kbits/s (Siemens) or 9 3,75 kbits/s (P+F) and variable comm rates up to 12 Mbit/s as instance: SK2 and SK3 from P+F, link IM157 from Siemns and Smar’s controllers with embedded couplers (DF95 or DF97);
Add the IF303 and specify its physical bus address; Choose the cyclic configuration via parameterization using the gsd file that depends on the
application, as detailed previously. For every AI (Analog Input) block, the IF303 provides the process variable to the master in 5 bytes value, being the first four according to float poin t data type and the fifth byte is the status that brings the measure quality of this information.
In the TOT (Totalizer) block, the user can choose the totalization value (Total) and the integration is made considering the operati on mode (Mode_Tot). It allows defining of how the totalization will be, with the following options: only positive value of the flow, only negative values of the flow, or both. In this block, the user can reset the totalization and configure the preset value through the Set_Tot parameter. The reset option is very used in batch processes;
It allows activating the condition of watchdog, which the device goes to a fail safe condition,
when a loss of communication is detected with the master.
Using ProfibusView, AssetView for FDT from Smar or Simatic PDM configuration software from Siemens, for instance, user may configure parameters of the Input Transducer block. See Figure 3.2
- Function and Transducers Blocks.
3.6
Figure 3.2 – Function and Transducers Blocks – ProfibusView
Configuration
Figure 3.3 – Function and Transducers Blocks – Simatic PDM
To make the configuration of Transducer Block, select on the main menu:
Figure 3.4 - Transducer Block – ProfibusView.
3.7
IF303 – Operation and Maintenance Instruction Manual
Figure 3.5 - Transducer Block - Simatic PDM
When the user chooses "Square Root", he needs to configure more two parameters: Low Flow Cutoff" and "Flow Lin Sqr Point". For details, please see last figure and the diagram of Transducer Block.
In terms of Square Root, we have the following feature:
Y
10. I (%)
Y =
Square Root
Low_Lin_Sqrt_Point = Z
Y = I (%).Q
10. Z
Q =
Z
Figure 3.6 – Square Root Calculation.
Low_Flow_Cut_Off
I (%)
3.8
How to Configure the Analog Input Block
The Analog Input block takes the input data from the Transducer block, selected by channel number, and makes it available to other function blocks at its output. T he transducer block provides the input unit of the Analog Input, and when the unit is cha nged in the transducer, the PV_SCALE unit is changed too. Optionally, a filter may be applied in the process value signal, whose time constant is PV_FTIME. Considering a step change to the input, this is the time in seconds to the PV reaches 63,2% of the final value. If the PV_FTIME value is zer o, the filter is disabled. For more details, please, see the Function Blocks Specifications.
To configure the Analog Input Block select on the main menu. Using this window, the user can configure the block mode operation, selects the channel, scales and unit for input and output value and the damping.
Configuration
Figure 3.7 – Basic Settings for Analog Input Block – ProfibusView.
3.9
IF303 – Operation and Maintenance Instruction Manual
Figure 3.8 – Basic Settings for Analog Input Block - Simatic PDM.
Selecting the page "Advanced Settings", the user can configure the conditions for alarms and warnings, as well the fail safe condition. Please, see the next window:
3.10
Figure 3.9 - Advanced Settings for Analog Input Block – ProfibusView.
Configuration
Figure 3.10 - Advanced Settings for Analog Input Block - Simatic PDM.
Figure 3.11 - Configuration for Analog Input Block – ProfibusView.
3.11
IF303 – Operation and Maintenance Instruction Manual
Figure 3.12 - Configuration for Analog Input Block - Simatic PDM.
How to configure the Totalizer Block
The Totalizer function block obtain the input data from the T ransducer block, selected by channel number, and integrates over the time. This block is normally used to totalize flow, giving total mass or volume over a certain time, or totalize power, giving the total energy.
The Totalizer Function Block integrates a variable (e.g flo w rate or power) in function of the time to the corresponding quantity (e.g., volume, mass or distance). The rate unit of the Totalizer is providing by the transducer block. Internally, the time units are converted in rate units per second. Each rate, multiplied by the block execution time, gives the mass, volume or energy incr ement per block execution.
The TOTAL is the totalized quantity. The en gineering unit used in th e output is the UNIT_TOT. The unit of the output must be compatible with the unit of t he input provided by the transducer by the channel. Then, if the input the rate is mass flow (like Kg/s, g/min, ton/h) the unit of the output must be mass (like kg, g, ton, lb, etc.). For more details, please, see the Function Blocks Specifications.
To configure the Totalizer Block select on the main menu. Using this window, the user can configure the block mode operation, selects the channel, totalizer mode and unit for the total. The user can choose up to 3 Totalizer Blocks:
3.12
Configuration
Figure 3.13 - Basic Settings for Totalizer Block – ProfibusView
Figure 3.14 - Basic Settings for Totalizer Block - Simatic PDM
3.13
IF303 – Operation and Maintenance Instruction Manual
Choosing the "Advanced Settings" window, the user can set alarm and warning limits, as well the fail safe condition:
Figure 3.15 - Advanced Settings for Totalizer Block - ProfibusView.
3.14
Figure 3.16 - Advanced Settings for Totalizer Block - Simatic PDM
Configuration
In the screen Config Block Mode the user can adjust the operation of the block.
Figure 3.17 - Totalizer Block Configuration - ProfibusView.
Figure 3.18 - Totalizer Block Configuration - Simatic PDM.
3.15
IF303 – Operation and Maintenance Instruction Manual
Current Trim
Figure 3.19 - Set/Preset Configuration for Totalizer Block - ProfibusView
Figure 3.20 - Set/Preset Configuration for Totalizer Block - Simatic PDM
The IF303 provides the capability of making a TRIM in the input channels, if necessar y. TRIM procedure is necessary if the indication readin g of the transducer block outp ut differs from the
actual physical output. The reason may be:
User's current meter differs from the factory standard.  Converter had its original characterization signal shifted by over-load or by long term drift.
3.16
Configuration
User can check the calibration of the transducer output by measuring t he actual current in the input and compare it with the indication of the device (an appropriate meter must be used). If a mismatch is detected, a TRIM can be done.
TRIM can be done in two points:
Lower TRIM: Is used to TRIM the lower value of the input range. Upper TRIM: Is used to TRIM the upper value of the input value.
These two points define the linear characteristic of the output. TRIM in one point is independent from the other. There are at least two ways of doing the T RIM: using local adjustment or using a Configuration Tool (see below examples using ProfibusView). When doing the TRIM, make sure you are using an appropriate meter (with the necessary accuracy).
Via ProfibusView, AssetView for FDT or Simatic PDM
The channel number of the AI block is related to the transducer ’s terminal block number. Channel number 1,2,3 corresponds bi-univocally to the terminal block with the same number. Therefor e, all the user has to do is to select combinations: (1, 1), (2, 2), (3, 3), for (CHANNEL, TERMINAL NUMBER).
It is possible to calibrate the current inputs of the transmitter by means of parameters CAL_POINT_LO and CAL_POINT_HI.
Let’s take the lower value as an example: Supply 4 mA or the lower value to the terminal block and wait until the readout of parameter
PRIMARY_VALUE stabilizes. Write 4.00 or the lower value in parameter CAL_POINT _LO. For each value written a calibration is
performed at the desired point.
Figure 3.21 - Lower Current Calibration - ProfibusView.
3.17
IF303 – Operation and Maintenance Instruction Manual
Figure 3.22 – Lower Current Calibration - Simatic PDM.
Let’s take the upper value as an example: Supply 20 mA or the upper value to the terminal block and wait until the readout of parameter PRIMARY_VALUE stabilizes. Write 20.00 or the upper value in parameter CAL _POINT_HI. For each value written a calibration is performed at the desired point.
The user can select Lower or Upper Trim.
The Upper Sensor Limit and the Upper Calibration Point.
The current value and status. The operation result.
3.18
Figure 3.23 - Upper Current Calibration -
ProfibusView.
Configuration
It is recommended, for every new calibration, to saving the existent TRIM data by means of parameter BACKUP_RESTORE, using option "Last Cal Backup".
Via Local Adjustment
The IF303 has 3 input transducers and it is provided by SMAR with default settings. T he factory setting establishes only the transducers #1 as default for local adjustment. In order to configure the others via local adjustment, user shall configure them in the display trans ducer via Configuration Tool, according specific instructions for this transducer block.
In order to enter the local adjustment mode, place the magnetic to ol in orifice “Z” until flag “MD” lights up in the display. Remove the magnetic tool from “Z” and place it in orifice “S” until the message “LOC ADJ” is displayed. The message will be displayed during approximately 5 s econds after the user has removed the magnetic tool from “S”. By placing the magnetic t ool t he user will be able to access the local adjustment tree in the monitoring mode.
Browse to parameter P_VAL (PRIMARY_VALUE). Supply 4.0mA or the lower value to the terminal block and wait until the read of the parameter
stabilizes in the display. Browse to parameter “LOWER”. After that, in order to start calibration, the user will act on the
parameter “LOWER” by placing the magnetic tool in “S” down to 4.0 mA. Let’s take the upper value:
Supply 20.0mA or the upper value to the terminal block and wait until the readout of parameter P_VAL stabilizes, and then actuate parameter UPPER up to 20.0.
TRIM mode exits via local adjustment automatically when the magnetic tool is not used during approximately 16 seconds.
Keep in mind that even when parameters LOWER or UPPER present the desired value, they must be actuated so that calibration is performed.
Limit Conditions for Calibration:
For every writing operation in the transducer blocks there is a code indication for the operation associated with the writing method. These codes appear in parameter XD_ERROR every time a calibration is performed. Code 16, for example, indicates a successfully performed operation.
Lower:
Figure 3.24 - Upper Current Calibration - Simatic PDM.
WARNING
NOTE
3.19
IF303 – Operation and Maintenance Instruction Manual
0.0mA < NEW_ LOWER < 9.0mA Otherwise, XD_ERROR = 22
Upper:
15.0 mA < NEW_UPPER < 22.0mA Otherwise, XD_ERROR = 22.
Codes for XD_ERROR: 16: Default Value Set 22: Out of range 26: Invalid Calibration request 27: Excessive Correction
Transducer Display – Configuration
Using the ProfibusView, AssetView for FDT, possible to configure the Display Transducer block. As d escribed above it is a transducer due the interfacing of its block with the LCD hardware.
Transducer Display is treated as a normal block by any configuration tool. It means, this block has some parameters and those ones can be configured according to customer's needs.
Customer can choose up to six parameters to be shown at LCD display, they can be parameters just for monitoring purpose or for acting locally in the fiel d devices by using a magnetic tool. The seventh parameter is used to access the physical device address. The user can change this address according to his application. To configure the Display Block select on the main menu:
NOTE
Simatic PDM or any other configuration tool is
3.20
Figure 3.25 - Display Block - ProfibusView.
Configuration
Display Transducer Block
Local adjustment is completely configured by configuration tool. It means, user can select the best options to fit his application. From factory, it is configured with the options to set the Upper and Lower TRIM, for monitoring the input transducer output and check the Tag. The converter is much better configured by configuration tool, but the local functionality of the LCD permits an easy and fast action on certain parameters, since it does not rely on communication and network wiring connections. Among the possibilities by Local Adjustment, the following options can be emphasized: Mode block, Outputs monitoring, Tag visualization and Tuning Parameters setting.
The interface is described in details on the "General Installation, Operation and Maintenance Procedures Manual". Please take a detailed look at this manual in the chapter related to "Programming Using Local Adjustment". The same handling methodology used for this transducer display can also be used for the 303 Series field devices from Smar. So, since the user has learned once, he is capable to handle all kind of field devices from SMAR.
All function block and transducers defined according PROFIBUS PA have a description of their features written by the Device Description Language.
This feature allows third-parties configuration tools, enabled by Device Description Service technology, interpreting these features and make them accessible to user Function Blocks and Transducers of 303 Series have been defined rigorously according th e PROFIBUS PA specifications in order to be interoperable to other parties.
In order to enable local adjustment using the magnetic tool, it is necessary ta previous setup of parameters related with this operation via System Configuration.
There are six groups of parameters, which one may be pre-configured by the user in order to enable, a possible configuration by means of the local adjustment. Use “NONE” option in t he "Select Block Type" parameter to hide unnecessary itens to be displayed. Doing this, device will not take the parameters related (indexed) to its Block as a valid parameter.
Definition of Parameters and Values
Select Block Type
This is the type of the block where the parameter is located. The user can choose: Transducer Block, Analog Input Block, Totalizer Block , Physical Block or None.
Select/Set Parameter Type/Index
This is the index related to the parameter to be actuated or viewed (0, 1, 2…). For each block there are some pre-defined indexes. Refer to the Function Blocks Manual to know available indexes to be used.
Figure 3.26 - Display Block - Simatic PDM.
3.21
IF303 – Operation and Maintenance Instruction Manual
Set Mnemonic
Mnemonic for the parameter identification (it is allowed a maximum of 16 characters into the alphanumeric field of the display). Choose the mnemonic, preferably with no more than 5 characters in order to avoid the display rotation.
Set Decimal Step
It is the increment and decrement in decimal units when the parameter is Float or Float Status value; integer, when the parameter is in whole units.
Set Decimal Point Place. This is the number of digits after the decimal point (0 to 3 decimal digits).
Set Access Permission
Allows user to read, in the case of the “Monitoring” option, and to write when "action" option is selected, then the display will show the increment and decrement arrows.
Set Alpha Numerical
These parameters include two options: value and mnemon ic . In option val u e, it is poss ible to displa y both data in the alphanumeric and in the numeric fields; this way, in case of a data higher than 10000, it will be shown in the alphanumeric field. It is useful when we are s howing Totalization at the LCD interface.
Selecting mnemonic, display may show the data in the numeric field and the mnemonic in the alphanumeric field.
For devices where the software version is higher or equal to 1.10, please see the configuration of local adjustment using the local adjustment, in the Installation, operation and maintenance procedures manual.
In case you wish to visualize a certain tag, opt for the index relative equal to "tag". To configur e other parameters just select "LCD-II" up to "LCD-VI" windows:
NOTE
3.22
The option "Write" should be selected in order to execute the upgrade of local adjustment programming tree. After its step all the selected parameters will be shown on the LCD display.
Figure 3.27 - Parameters for Local Adjustment Configuration - ProfibusView.
Configuration
Figure 3.28 - Parameters for Local Adjustment Configuration - Simatic PDM.
The window "Local Address Change" allows the user "enable/disable" the access to changin g the physical device address.
When the option "enable" is selected, the user can change the physical device address.
Figure 3.29 - Parameters for Address Configuration - ProfibusView
3.23
IF303 – Operation and Maintenance Instruction Manual
Figure 3.30 - Parameters for Address Configuration - Simatic PDM.
When user is in the local adjustment, he can rotate parameters using the magnet screwdrive. Normally; primary value (P_VAL) is the standard parameter to be shown. In case of setting another parameter to be displayed, user shall changue “Access Permission” to “Monitoring”. T hus the last parameter set to “Monitoring” will be displayed after removing the magnet tool.
Always on the LCD interface will be shown t wo parameters at the s ame time, s witching bet ween the configured parameter at the LCD-II and the last monitoring parameter. If user do es not want to show two parameters at the same time, it is only needed to set "none" when configure the LCD-II:
Selecting "None", only the last chosen monitoring parameter will be shown at LCD.
3.24
Figure 3.31 - Parameters for LCD-II Configuration - ProfibusView.
Configuration
Figure 3.32 - Parameters for LCD-II Configuration - Simatic PDM.
The user can select the "Mode Block" parameter at the LCD. In this case is necessar y to select the index equal to "Mode Block":
With this option, the Mode Block parameter is shown at the LCD.
Figure 3.33 - Parameters for Local Adjustment Configuration - ProfibusView.
3.25
IF303 – Operation and Maintenance Instruction Manual
Figure 3.34 - Parameters for Local Adjustment Configuration - Simatic PDM.
Programming Using Local Adjustment
The local adjustment is completely configured by configuration tool. It means, the user can select the best options to fit his application. From factory, it is configured with the options to set the Upper and Lower TRIM, for monitoring the input transducer output and check the Tag.
Normally, the converter is much better configured by configuratinon tool, but the local functionality of the LCD permits an easy and fast action on certain parameters, since it does not rely on communication and network wiring connections. Among the possibilities b y Local Adjustment, the following options can be emphasized: Mode block, Outputs monitoring, Tag visua lizati on and T uning Parameters setting.
The interface between the user is also described very detailed on the "General Installation, Operation and Maintenance Procedures Manual" Pl ease take a detailed look at this manual in the chapter related to "Programming Using Local Adjustme nt". It is significantly the resources on this transducer display, also all the 303 Series field devices from SMAR has the same methodolog y to handle with it. So, since the user has learned once, he is capable to han dle all kind of field devices from SMAR. This Local adjustment configuration is a suggestion only. The us er may choose his preferred configuration via configuration toll, simply configuring the displa y block).
The converter has two holes for magnetic switches activated by the magnetic tool located und er the identification plate. These magnetic switches are activated by one magnetic tool (see figure 3.35).
This magnetic tool enables adjustment of the most important parameters of the blocks. It also enables pre-configuration of the communication.
The jumper W1 on top of the main circuit board must be i n place for this f unction to be enab led and the converter must be fitted with the digital display for access to the loc al adjustment. Without the display the local adjustment is not possible.
3.26
Configuration
A
Fig. 3. 35 - Local Adjustment Holes
Table 3.4 shows the actions on the Z and S holes on the FY303 when Local Adjustment is enabled.
HOLE
Z Inicializes and rotates through the available functions.
S Selects the function shown in the display.
CTION
Table 3.4 - Purpose of the holes on the Housing
3.27
IF303 – Operation and Maintenance Instruction Manual
Quick Guide – Local adjustment Tree
UPDT
TGGL
ITEM
1) Browse until CONF option, select LCD2
2) Browse until BLOCK select the block that will be configured
3) Browse until PRMT and set the relative index of the parameter
4) Browse until ITEM and set the sub index ( if applicable )
5) Browse until UPDT,insert magnetic screw driver in Zero Hole
6) Reenter in Local Adjustment, browse until LCD2, now the
parameterisavailabletochange
3) HOW TO CONFIGURE A BLOCKPARAMETER
7) Repeat above steps for all the parameters to be configured
Magnetic Tool
1
S
Span Hole Zero Hole
ADDR
e
id
u
G
k
ic
u
-Q
e
re
T
2) HOW TO BROWSEAND
PRMT
AI1
AI2
PHY
TRD1
TRD2
TRD3
AI3
TOT1
TOT3
TOT2
BLOCK
LCD1
LCD2
LCD3
LCD4
LCD5
LCD6
Insert magnetic
Insert magnetic
CONF
screw driver in zero hole
and hold
screw driver in span hole
Browse:
SELECT MENU OPTIONS
Select:
and hold
UPPER ADDR
VARIABLES
UPPER ADDR
LOWER
ment
t
s
u
dj
lA
a
c
o
L
3.28
Follow Steps:
1) Insert magnetic screw driver in zero hole
2) Wait 3 seconds
3) Insert magnetics screw driver in span hole
1) HOW TO ACCESS LOCALADJUSTMENT TREE
4) Wait 3 seconds, then MD will appear on display
PVAL
LOWER
LCD1 LCD2 LCD4 LCD5
Follow Steps:
1) Browse until TGGL
2) Select 2
TIP: DISPLAY SWITCHING BETWEEN 2
3) Configure LCD 2 with the desired parameter
With TOGGLE 6
18 2 11 21
PVAL1
• CONF: option where it is possible to select the LCD to configure. Six options are available: from LCD1 up to LCD6;
• BLOCK: option where the user must select the function block that he desires to configure;
“Unit Index” and “Decimal Point”;
• PRMT: number correspondent to the relative index of the desired parameter into the chosen function block;
• ITEM: configure this option when a selected parameter has sub items to be configured, for example, the OUT_SCALE parameter is compounded by “EU at 100%”, “EU at 0%”,
• TGGL (Toggle): switches from 1 up to 6 configured parameters on the display.IfTGGLis equal to 2, for example, the display wil l switch between LCD1 and LCD2;
• UPDT: refreshes the display when one of the LCDs are configured. Finalize display configuration by setting "UPDT", after choosing the configuration for the local adjustment.
J1 Jumper Connections
If J1 (see figure 3.20) is connected to ON, then simulation mode in the AO block is enabled.
W1 Jumper Connections
If W1 (see figure 3.20) is connected to ON, the local adjustment programming tree is enabled and then important block parameters can be adjusted and communication can be pre-configured via local adjustment.
Configuration
In order to start the local adjustment, place the magnetic tool in orifice Z and wait until letters MD are displayed.
OFF ON
WR
J1
OFF ON
W1
LOC ADJ
MAIN BOARD
Fig. 3.36 - J1 and W1 Jumpers
Place the magnetic tool in orifice S and wait during 5 seconds.
Figure 3.37 - Step 1 - IF303
3.29
IF303 – Operation and Maintenance Instruction Manual
Remove the magnetic tool from orifice S.
Place the magnetic tool in orifice Z. In case this is the first configuration, the option shown on the display is the TAG with its corresponding mnemonic configured by the Configuration Tool. Otherwise, the option shown on the display will be the one configured in the prior operation. By keeping the tool inserted in this orifice, the local adjustment menu will rotate.
Insert the magnetic tool in orifice S once more and LOC ADJ should be displayed .
Figure 3.38 - Step 2 - IF303
This parameter is used to calibrate the lower current point. In order to range the lower value, simply insert the magnetic tool in orifice S as soon as lower is shown on the display. An arrow pointing
upward () increment the value and an arrow pointing downward () decrement the value. Apply the 4.00 mA current in the 1 and 4 terminals. Adjust the current showed on the display to 4.00 mA..
In order to decrement the lower value, place the magnetic tool in orifice Z to shift the arrow to the downward position and then, by inserting and keeping the tool in orifice S, it is possible to decrement the lower value.
3.30
Figure 3.39 - Step 3 - IF303
This parameter is used to calibrate the upper current point. In order to range the upper value, simply insert the magnetic tool in orifice S as soon as upper is shown on the display. An arrow pointing
upward () increment the value and an arrow pointing downward () decrement the value. Apply the 20.0 mA current in the 1 and 4 terminals. Adjust the current showed on the display to 20.0 mA.
Figure 3.40 - Step 4 - IF303
Configuration
In order to decrement the address value, place the magnetic tool in orifice Z to shift the arrow to the downward position and then, by inserting and keeping the tool in orifice S, it is possible to decrement the address value.
In order to decrement the address value, place the magnetic tool in orifice Z to shift the arrow to the downward position and then, by inserting and keeping the tool in orifice S, it is possible to decrement the address value.
Figure 3.41 - Step 5 - IF303
1
In order to change the address value, simply take off the magnetic tool from orifice Z as soon as ADDR is shown on the display. An arrow pointing
upward () increments the address and an arrow pointing
1
downward () decrements the address. In order to increment the address, insert the tool in S up to set the value desired.
Cyclical Diagnosis
Figure 3.42 - Step 6 - IF303
NOTE
This Local adjustment configuration is a suggestion only. The user may choose his preferred configuration via Configuration Tool, simply configuring the display.
Via cyclic communication is possible to verify diagnostics from the IF303 using the Profibus Master Class 1 or even via acyclic communication via Master Class 2. The Profibus-PA dev ices provide up to 4 standard diagnoses bytes via Physcial Block (see figure 3.43 and 3.44) and when the most significant bit of the fourth Byte is "1", the diagnose will extend the information in more 6 bytes. These Diagnosis bytes can also be monitored via cyclic tools.
Figure 3.43 – Cyclical Diagnosis
3.31
IF303 – Operation and Maintenance Instruction Manual
Figure 3.44 – Cyclic Diagnosis mapping for 4 bytes of Physical Block.
Unit_Diag_bit is described in the GSD file Profibus-PA device.
See below a description part of a GSD file for the 4 bytes and more detail:
;----------- Description of device related diagnosis: --------------------­;
Unit_Diag_Bit(16) = "Error appears" Unit_Diag_Bit(17) = "Error disappears" ; ;Byte 01 Unit_Diag_Bit(24) = "Hardware failure electronics" Unit_Diag_Bit(25) = "Not used 25" Unit_Diag_Bit(26) = "Not used 26" Unit_Diag_Bit(27) = "Not used 27" Unit_Diag_Bit(28) = "Memory error" Unit_Diag_Bit(29) = "Measurement failure" Unit_Diag_Bit(30) = "Device not initialized" Unit_Diag_Bit(31) = "Device initialization failed"
;Byte 02 Unit_Diag_Bit(32) = "Not used 32" Unit_Diag_Bit(33) = "Not used 33" Unit_Diag_Bit(34) = "Configuration invalid" Unit_Diag_Bit(35) = "Restart" Unit_Diag_Bit(36) = "Coldstart" Unit_Diag_Bit(37) = "Maintenance required" Unit_Diag_Bit(38) = "Characteristics invalid" Unit_Diag_Bit(39) = "Ident_Number violation"
;Byte 03 Unit_Diag_Bit(40) = "Not used 40" Unit_Diag_Bit(41) = "Not used 41" Unit_Diag_Bit(42) = "Not used 42" Unit_Diag_Bit(43) = "Not used 43" Unit_Diag_Bit(44) = "Not used 44" Unit_Diag_Bit(45) = "Not used 45" Unit_Diag_Bit(46) = "Not used 46" Unit_Diag_Bit(47) = "Not used 47"
;byte 04 Unit_Diag_Bit(48) = "Not used 48" Unit_Diag_Bit(49) = "Not used 49" Unit_Diag_Bit(50) = "Not used 50" Unit_Diag_Bit(51) = "Not used 51" Unit_Diag_Bit(52) = "Not used 52"
3.32
Configuration
Unit_Diag_Bit(53) = "Not used 53" Unit_Diag_Bit(54) = "Not used 54" Unit_Diag_Bit(55) = "Extension Available"
;Byte 05 TRD Block & PHY Block Unit_Diag_Bit(56) = "TRD Block 1 Sensor Failure" Unit_Diag_Bit(57) = "TRD Block 2 Sensor Failure" Unit_Diag_Bit(58) = "TRD Block 3 Sensor Failure" Unit_Diag_Bit(59) = "TRD Block 1 Range Violation" Unit_Diag_Bit(60) = "TRD Block 2 Range Violation" Unit_Diag_Bit(61) = "TRD Block 3 Range Violation" Unit_Diag_Bit(62) = "Calibration Error - Check XD_ERROR parameter for TRD 1 or TRD 2 or TRD 3" Unit_Diag_Bit(63) = "Device is in Writing Lock"
;byte 06 AI_1 Block Unit_Diag_Bit(64) = "Simulation Active in AI 1 Block" Unit_Diag_Bit(65) = "Fail Safe Active in AI 1 Block" Unit_Diag_Bit(66) = "AI 1 Block in Out of Service" Unit_Diag_Bit(67) = "AI 1 Block Output out of High limit" Unit_Diag_Bit(68) = "AI 1 Block Output out of Low limit" Unit_Diag_Bit(69) = "Not used 69" Unit_Diag_Bit(70) = "Not used 70" Unit_Diag_Bit(71) = "Not used 71"
;byte 07 AI_2 Block Unit_Diag_Bit(72) = "Simulation Active in AI 2 Block" Unit_Diag_Bit(73) = "Fail Safe Active in AI 2 Block" Unit_Diag_Bit(74) = "AI 2 Block in Out of Service" Unit_Diag_Bit(75) = "AI 2 Block Output out of High limit" Unit_Diag_Bit(76) = "AI 2 Block Output out of Low limit" Unit_Diag_Bit(77) = "Not used 77" Unit_Diag_Bit(78) = "Not used 78" Unit_Diag_Bit(79) = "Not used 79"
;byte 08 AI_3 Block Unit_Diag_Bit(80) = "Simulation Active in AI 3 Block" Unit_Diag_Bit(81) = "Fail Safe Active in AI 3 Block" Unit_Diag_Bit(82) = "AI 3 Block in Out of Service" Unit_Diag_Bit(83) = "AI 3 Block Output out of High limit" Unit_Diag_Bit(84) = "AI 3 Block Output out of Low limit" Unit_Diag_Bit(85) = "Not used 85" Unit_Diag_Bit(86) = "Not used 86" Unit_Diag_Bit(87) = "Not used 87"
;byte 09 TOT Block Unit_Diag_Bit(88) = "TOT Block 1 in Out of Service" Unit_Diag_Bit(89) = "Totalization 1 Out of High limit" Unit_Diag_Bit(90) = "Totalization 1 Out of Low limit" Unit_Diag_Bit(91) = "No assigned channel to TOT Block 1" Unit_Diag_Bit(92) = "TRD Block 1 - Square Root function is active" Unit_Diag_Bit(93) = "TOT Block 2 in Out of Service" Unit_Diag_Bit(94) = "Totalization 2 Out of High limit" Unit_Diag_Bit(95) = "Totalization 2 Out of Low limit"
;byte 10 Unit_Diag_Bit(96) = "No assigned channel to TOT Block 2" Unit_Diag_Bit(97) = "TRD Block 2 - Square Root function is active" Unit_Diag_Bit(98) = "TOT Block 3 in Out of Service" Unit_Diag_Bit(99) = "Totalization 3 Out of High limit" Unit_Diag_Bit(100) = "Totalization 3 Out of Low limit" Unit_Diag_Bit(101) = "No assigned channel to TOT Block 3" Unit_Diag_Bit(102) = "TRD Block 3 - Square Root function is active" Unit_Diag_Bit(103) = "Not used 103"
3.33
IF303 – Operation and Maintenance Instruction Manual
If the FIX flag is active on LCD, the IF303 is configured to "Profile Specific". When in "Manufacturer Specific", the Identifier Number is 0x0896. Once the Identifier_Number_Selector is changed from "Profile S pecific" to "Manufacturer Specific" or vice-versa, you must wait 5 seconds while it is saved and the turn off the IF303 and then the identifier is updated in the level of communication. If the equipment is in "Profile Specific" and using the GSD file Identifier Number equals 0x0896, the acyclic communication will work well with tools based on EDDL, FDT/DTM, but no cyclic communication with the Profibus-DP master will get success.
NOTE
3.34
Section 4
General
Troubleshooting
SYMPTOM PROBABLE SOURCE OF PROBLEM
No Quiescent Current
No Communications
Incorrect Input
MAINTENANCE PROCEDURES
NOTE
Equipment installed in hazardous atmospheres must be inspected in compliance with the IEC60079-17 standard.
SMAR IF303 Current to PROFIBUS PA Converters are extensively tested and inspected before
delivery to the end user. Nevertheless, during their design and development, consideration was given to the possibility of repairs by the end user, if necessary.
In general, it is recommended that the end user do not try to repair printed circuit boards. Instead, he should have spare circuit boards, which may be ordered from SMAR whenever necessary.
Converter PROFIBUS Connections
Check wiring polarity and continuity.
Power Supply
Check power supply output. The voltage at the IF303 terminals must be between 9 and 32 Vdc.
Electronic Circuit Failure
Check the boards for defect by replacing them with spare ones.
Network Connections
Check the network connections: devices, power supply, couplers, links, and terminators.
Transmitter Configuration
Check configuration of communication parameters of converter.
Network Configuration
Check communication configuration of the network.
Electronic Circuit Failure
Try to replace the converter circuit with spare parts.
Input Terminals Connection
Check wiring polarity and continuity.
Conventional Transmitter
Verify if the conventional transmitter is working properly or if it has the necessary voltage. Remember that IF303 has a 100 Ohms plus 0.8 V input impedance.
Calibration
Check calibration of IF303 and the conventional transmitters.
4.1
IF303 – Operation and Maintenance Instruction Manual
If the problem is not presented in the table above follow the Note below:
The Factory Init should be tried as a last option to recover the equipment control when the equipment presents some problem related to the function blocks or the communication. This operation must only be
carried out by authorized technical personnel and with the process offline, since the equip ment will be configured with standard and factory data.
This procedure resets all the configurations run on the equipment, after which a partial download should be performed. With exception to the equipment physical address and the gsd identifier number selector parameter. After doing this, all configurations must be remade according to their applications.
To run the factory Init, use two magnetic screwdrivers. Remove the screw on the equipment that fixes the identification tag on the carcass top to access the orifices bearing the letters “S” and “Z”.
The operations to follow are:
1) Turn off the equipment; insert the magnetic tools in each orifice (S and Z). Leave them in the orifices;
2) Power the equipment;
3) As soon as Factory Init is shown on the display, take off the tools and wait for the "5" symbol on the right upper corner of the display to unlit, thus indicating the end of the operation.
This operation has factory configuration that eliminates possible problems with the functional blocks or the transmitter communication.
Disassembly Procedure
Refer to Figure 4.1 - IF303 Exploded View Make sure to disconnect power supply before disassembling the converter.
To remove the circuit boards (5 and 7) and display (4), first loose the cover locking (8) on the side not marked “Field Terminals”, then unscrew the cover (1).
The boards have CMOS components, which may be damaged by electrostatic discharges. Observe correct procedures for handling CMOS components. It is also recommended to store the circuit boards in electrostatic-proof cases.
Loose the two screws (3) that anchor the display and the main circuit board. Gently pull out the display, and then the main board (5). To remove the input board (7), first unscrew the two screws (6) that anchors it to the housing (9), and gently pull out the board.
Reassembly Procedure
Put input board (7) into housing (9).
Anchors input board with their screws (6).
Put main board (5) into the housing, ensuring all inter connecting pins are connected.
Put display (4) into the housing, observing the four mounting positions. "" should point in the
direction desired as UP.
Anchors main board and display with their screws (3).
Fit the cover (1) and lock it using the locking screw (8).
NOTE
WARNING
4.2
Boards Interchangeability
Main and input boards are supposed to stay together, because calibration data from input board circuit is stored in EEPROM of the main board.
If, for some reason, you separate the input and the main boards, you must do a trim to guarantee precision of the inputs. With mismatched boards, the factory trim will not be as good as it was.
Exploded View
5
4
3
2
1
Maintenance Procedures
WARNING
12
11
10
9
8
7
6
15
14
16
13
Figure 4.1 - IF303 Exploded View
Accessories and Related Products
ORDERING CODE DESCRIPTION
AssetView FDT BC1 BT302 DF47-17 DF73 DF95/DF97 FDI302 PBI ProfibusView PS302/DF52 PSI302/DF53 SD1
ACCESSORIES AND RELATED PRODUCTS
Asset Management With FDT
Fieldbus/RS232 Interface
Terminator
Intrinsic Safety Barrier
HSE/PROFIBUS-DP Controller
PROFIBUS DP/PA Controller
Field Device interface
USB Profibus Interface
Profibus PA Device Parameterization Software
Power Supply
Power Supply Impedance
Magnetic Tool for Local Adjustment
4.3
IF303 – Operation and Maintenance Instruction Manual
Spare Parts List
SPARE PARTS LIST
Cover Without Window (Includes O-Ring)
Cover With Window For Indication (Includes O-Ring) O-rings (Note 2) Cover, Buna-N 2 204-0122 B
Aluminum Housing Main Board Screw
316 Stainless Steel Housing Main Board Screw Digital Indicator 4 214-0108
Main and Input Circuit Board Assembly 5 and 7 400-0311 A
Input Board Screw
Cover Locking Screw 8 204-0120
Housing, Aluminum (Note 1)
Housing, 316 SS (Note 1)
Local Adjustment Protection Cap 10 204-0114 Identification Plate Fixing Screw 11 204-0116 Terminal Insulator 12 314-0123 External Ground Screw 13 204-0124
Terminal Holding Screw
Six-Sided Plug 1/2" NPT Internal BR Ex
Six-Sided Plug 1/2" NPT Internal
Six-Sided Plug M20 X 1.5 External BR Ex d 316 Stainless Steel 16 400-0810 Six-Sided Plug PG13.5 External BR Ex d 316 Stainless Steel 16 400-0811
Mounting Bracket for 2” Pipe (Note 3)
DESCRIPTION OF PARTS POSITION CODE
Aluminum 1 and 15 204-0102 316 SS 1 and 15 204-0105 Aluminum 1 204-0103 316 SS 1 204-0106
Units With Indicator 3 304-0118 Units Without Indicator 3 304-0117 Units With Indicator 3 204-0118 Units Without Indicator 3 204-0117
Housing in Aluminum 6 314-0125 Housing in 316 Stainless Steel 6 214-0125
½ - 14 NPT 9 400-0305 M20 x 1.5 9 400-0306 PG 13.5 DIN 9 400-0307 ½ - 14 NPT 9 400-0308 M20 x 1.5 9 400-0309 PG 13.5 DIN 9 400-0310
Housing in Aluminium 14 304-0119 Housing in 316 Stainless Steel 14 204-0119 Bichromated Carbon Steel 16 400-0808 Bichromated 304 Stainless Steel 16 400-0809 Bichromated Carbon Steel 16 400-0583-11 Bichromated 304 Stainless Steel 16 400-0583-12
Carbon Steel - 214-0801 316 Stainless Steel - 214-0802 Carbon Steel Bolts, Nuts, Washers and U-clamp in Stainless Steel
- 214-0803
NOTE
1. It includes terminal holder insulator, bolts (cover lock, grounding and terminal holder insulator) and identification plate without certification.
2. O-Rings are packaged in packs of 12 units.
3. Including U-clamp, nuts, bolts and washers. Spare Parts List.
4. For category A, it is recommended to keep, in stock, 25 parts installed for each set, and for category B, 50.
CATEGORY
(NOTE 4)
4.4
Section 5
TECHNICAL CHARACTERISTICS
Functional Specifications
Input Signal (Field Values) Output Signal
(Communication) Input Impedance
Power Supply Indication
Hazardous Area Certification
Temperature Limits
Humidity Limits Turn-on Time Update Time
Configuration
Accuracy Ambient Temperature Effect Vibration Effect Electromagnetic
Interference Effect
Hardware Electrical Connection
Material of Construction Mounting
Weight
Apply in the inputs of the conversor only current levels. Don't apply tension levels, because the shunt resistors are of 100R 1W and tensi on abo ve 10 Vdc it can damage them.
0-20 mA, 4-20 mA or any within 0 and 20 mA. Reverse polarity protected (*). PROFIBUS PA, Digital only, complies with IEC 61158-2 (H1): 31.25 Kbit/s and voltage mode with
bus power. Resistive 100, plus a 0.8 V drop over diode in forward direction. Bus power 9-32 Vdc. Current consumption quiescent 12 mA. Optional 4½ digit LCD indicator. Explosion-proof and intrinsically safe (ATEX (NEMKO and DEKRA EXAM), FM, CEPEL, CSA and
NEPSI).
Designed to comply with European Regulations (ATEX 94/9/EC and LVD 2006/95/EC). Operation: Storage: Display:
0 to 100% RH. Approximately 10 seconds. Approximately 0.5 second. Basic configuration may be done using local adjustment magnetic tool if device is fitted with
display. Complete configuration is possible using PC software interface, by using a configurator (Ex.:
ProfibusView, AssetView for FDT or Simatic PDM).
0.03%. of span for 4-20 mA, 5 µA for others spans. For a 10° C variation: ± 0.05%. Complies with SAMA PMC 31.1.
Designed to comply with European Directive EMC 2004/108/EC.
Physical: according to IEC 61158-2 and conformity with the FISCO model. 1/2-14 NPT, PG 13.5 or M20 x 1.5. Injected low copper aluminum with polyester painting or 316 Stainless Steel housing, with Buna N
O-rings on cover. With an optional bracket can be installed on a 2" pipe or fixed on a wall or panel. Without display and mounting bracket: 0.80 kg. Add for digital display: 0.13 kg. Add for mounting bracket: 0.60 kg.
-40 to 85 °C (-40 to 185 °F)
-40 to 120 °C (-40 to 250 °F)
-10 to 60 °C ( 14 to 140 °F) operation
-40 to 85 °C (-40 to 185 °F) without damage.
Performance Specifications
Physical Specifications
* WARNING
5.1
IF303 – Operation and Maintenance Instruction Manual
Ordering Code
MODEL
IF303 TRIPLE CHANNEL CURRENT TO PROFIBUS CONVERTER
COD. Local Indicator
0 Without indicator 1 With indicator
COD. Mounting Bracket
0 Without Bracket 1 Carbon Steel. Accessories: Carbon Steel 2 316 Stainless Steel. Accessories: AI316 7 Carbon Steel. Accessories: AI316
COD. Electrical Connections
0 1/2" - 14 NPT 1 1/2" - 14 NPT X 3/4 NPT (AI 316) - with adapter 2 1/2" - 14 NPT X 3/4 BSP (AI 316) - with adapter 3 1/2" - 14 NPT X 1/2 BSP (AI 316) - with adapter A M20 X 1.5 B PG 13.5 DIN
SPECIAL OPTIONS COD. Housing
H0 Aluminum (IP/TYPE) H1 316 Stainless Steel (IP/TYPE) H2 Aluminum for saline atmosphere (IPW/TYPE X) H3 316 Stainless Steel for saline atmosphere (IPW/TYPE X)
COD. Identification Plate
I1 FM: XP, IS, NI, DI I3 CSA: XP, IS, NI, DI I4 EXAM (DMT): Ex-ia; NEMKO: Ex-d I5 CEPEL: EX-D, Ex-ia I6 Without Certification
IE NEPSI: Ex-ia
COD. Painting
P0 Gray Munsell N 6,5 Polyester P3 Black Polyester P4 White Epoxi P5 Yellow Polyester P8 Without Painting P9 Safety Blue Epoxy - Electrostatic Painting PC Safety Blue Polyester - Electrostatic Painting PG Safety Orange Epoxi Paint - Electrostatic Painting
COD. Input Signal
T0 3 output, 4 to 20 mA
COD. Tag Plate
J0 With tag J1 Blank
J2 According to user’s notes
COD. Special ZZ See Notes
IF303 1 1 0 * * * * * *
* Leave it blank for no optional items.
TYPICAL MODEL
5.2
Crrgpfkz"C"
CERTIFICATIONS INFORMATION
Gwtqrgcp"Fktgevkxg"Kphqtocvkqp"
Consult www.smar.com for the EC declarations of conformity for all applicable European directives and certificates.
ATEX Directive (94/9/EC) – “Electrical equipment and protective system intended for use in potential explosive atmospheres”
The EC-Type Examination Certificate had been released by Nemko AS (CE0470) and/or DEKRA EXAM GmbH (CE0158), according to European Standards. The certification body for Production Quality Assurance Notification (QAN) and IECEx Quality Assessment Report (QAR) is Nemko AS (CE0470).
LVD Directive 2006/95/EC – “Electrical Equipment designed for use within certain voltage limits”
According the LVD directive Annex II, electrical equipment for use in an explosive atmosphere is outside the scope of this directive. According to IEC standard: IEC 61010-1:2010 - Safety requirements for electrical equipment for measurement, control, and laboratory use - Part 1: General requirements.
"
EMC Directive 2004/108/EC - “Electromagnetic Compatibility”
The equipment is in compliance with the directive and EMC test was performed according to IEC standards: IEC61326-1:2005 and IEC61326-2-3:2006.
To comply with the EMC directive the installation must follow these special conditions:
Use shielded, twisted-pair cable for powering the instrument and signal wiring.  Keep the shield insulated at the instrument side, connecting the other one to the ground.
Jc|ctfqwu"Nqecvkqpu"Igpgtcn"Kphqtocvkqp"
Ex Standards:
IEC 60079-0 General Requirements IEC 60079-1 Flameproof Enclosures “d” IEC 60079-11 Intrinsic Safety “i” IEC 60079-26 Equipment with equipment protection level (EPL) Ga IEC 60529 Classification of degrees of protection provided by enclosures (IP Code)
Customer responsibility:
IEC 60079-10 Classification of Hazardous Areas IEC 60079-14 Electrical installation design, selection and erection IEC 60079-17 Electrical Installations, Inspections and Maintenance
Warning:
Explosions could result in death or serious injury, besides financial damage. Installation of this instrument in an explosive environment must be in accordance with the national standards and according to the local environmental protection method. Before proceeding with the installation match the certificate parameters according to the environmental classification.
General Notes: Maintenance and Repair
The instrument modification or replaced parts supplied by any other supplier than authorized representative of Smar Equipamentos Industriais Ltda is prohibited and will void the Certification.
Marking Label
Once a device labeled with multiple approval types is installed, do not reinstall it using any other approval types. Scratch off or mark unused approval types on the approval label.
For Ex-i protection application
- Connect the instrument to a proper intrinsically safe barrier.
C03
KH525""Qrgtcvkqp"cpf"Ockpvgpcpeg"Kpuvtwevkqp"Ocpwcn"
- Check the intrinsically safe parameters involving the barrier, equipment including the cable and connections.
- Associated apparatus ground bus shall be insulated from panels and mounting enclosures.
- When using shielded cable, isolate the not grounded cable end.
- Cable capacitance and inductance plus Ci and Li must be smaller than Co and Lo of the Associated Apparatus.
For Ex-d protection application
- Only use Explosion Proof/Flameproof certified Plugs, Adapters and Cable glands.
- In an Explosion-Proof/Flame-Proof installation, do not remove the instrument housing covers when powered on.
- Electrical Connection
In Explosion-Proof installations the cable entries must be connected through conduit with sealed unit or closed using metal cable gland or closed using metal blanking plug, all with at least IP66 and Ex-d certification. For enclosure with saline environment protection (W) and ingress protection (IP) applications, all NPT thread parts must apply a proper water-proof sealant (a non-hardening silicone group sealant is recommended).
For Ex-d and Ex-i protection application
- The transmitter has a double protection. In this case the transmitter shall be fitted with appropriate certified cable entries Ex-d and the electric circuit supplied by a certified diode safety barrier as specified for the protection Ex-ia.
Environmental Protection
- Enclosure Types (Type X): Supplementary letter X meaning special condition defined as default by Smar the following: Saline Environment approved - salt spray exposed for 200 hours at 35ºC. (Ref: NEMA 250).
- Ingress protection (IP W): Supplementary letter W meaning special condition defined as default by Smar the following: Saline Environment approved - salt spray exposed for 200 hours at 35ºC. (Ref: IEC60529).
- Ingress protection (IP x8): Second numeral meaning continuous immersion in water under special condition defined as default by Smar the following: 1 Bar pressure during 24hours. (Ref: IEC60529).
Jc|ctfqwu"Nqecvkqpu"Crrtqxcnu"
CSA (Canadian Standards Association)
Class 2258 02 – Process Control Equipment – For Hazardous Locations (CSA1002882)
Class I, Division 1, Groups B, C and D Class II, Division 1, Groups E, F and G Class III, Division 1 Class I, Division 2, Groups A, B, C and D Class II, Division 2, Groups E, F and G Class III
CLASS 2258 03 - PROCESS CONTROL EQUIPMENT – Intrinsically Safe and Non-Incendive Systems - For Hazardous Locations (CSA 1002882)
Class I, Division 2, Groups A, B, C and D
Model IF303 Converter; supply 12-42V dc, 4-20mA; Enclosure Type 4/4X; non-incendive with Fieldbus/FNICO Entity parameters @ Terminals + and - : Vmax =24V, Imax =570 mA, Pmax = 9.98 W, Ci = 5 nF, Li = 12uH; @ Terminals 1 - 4: Vmax =30V, Imax =110mA, Ci = 5 nF, Li = 12uH; when connected through CSA Certified Safety Barriers as per SMAR Installation drawing 102A0558; Temp. Code T3C.
Class 2258 04 – Process Control Equipment – Intrinsically Safe Entity – For Hazardous Locations (CSA 1002882) Class I, Division 1, Groups A, B, C and D Class II, Division 1, Groups E, F and G Class III, Division 1
Model IF303 Converter; supply 12-42V dc, 4-20mA; Enclosure Type 4/4X; Intrinsically safe with Fieldbus/FISCO Entity parameters @ Terminals + and -:
C04"
Egtvkhkecvkqpu"Kphqtocvkqp"
Vmax = 24 V, Imax = 380 mA, Pi = 5.32 W, Ci = 5 nF, Li = 12 uH; @ Terminals 1 – 4: Vmax = 30 V, Imax = 110 mA, Ci = 5nF, Li = 12 u H; when connected through CSA Certified Safety Barriers as per Smar Installation Drawing 102A0558; Code T3C. Note: Only models with stainless steel external fittings are Certified as Type 4X.
Special conditions for safe use: Temperature Class T3C Maximum Ambient Temperature: 40ºC (-20 to 40 ºC)
FM Approvals (Factory Mutual)
Intrinsic Safety (FM 3006959)
IS Class I, Division 1, Groups A, B, C and D IS Class II, Division 1, Groups E, F and G IS Class III, Division 1
Explosion Proof (FM 3006959) XP Class I, Division 1, Groups A, B, C and D
Dust Ignition Proof (FM 3006959) DIP Class II, Division 1, Groups E, F and G DIP Class III, Division 1
Non Incendive (FM 3006959) NI Class I, Division 2, Groups A, B, C and D
Environmental Protection (FM 3006959) Option: Type 4X/6/6P or Type 4/6/6P
Special conditions for safe use:
Entity Parameters Fieldbus Power Supply Input (report 3015629):
Vmax = 24 Vdc, Imax = 250 mA, Pi = 1.2 W, Ci = 5 nF, Li = 12 uH
Vmax = 16 Vdc, Imax = 250 mA, Pi = 2 W, Ci = 5 nF, Li = 12 uH
4-20 mA Current Loop:
Vmax = 30 Vdc, Imax = 110 mA, Pi = 0,825 W, Ci = 5 nF, Li = 12 uH
Temperature Class T4
Maximum Ambient Temperature: 60ºC (-20 to 60 ºC)
NEMKO (Norges Elektriske MaterielKontroll)
Explosion Proof (NEMKO 13 ATEX 1570X)
Group II, Category 2 G, Ex d, Group IIC, Temperature Class T6, EPL Gb
Ambient Temperature: -20 ºC to +60 ºC
Environmental Protection (NEMKO 03ATEX1570X) Options: IP66/68W or IP66/68
Special conditions for safe use:
Repairs of the flameproof joints must be made in compliance with the structural specifications provided by the manufacturer. Repairs must not be made on the basis of values specified in tables 1 and 2 of EN/IEC 60079-1.
The Essential Health and Safety Requirements are assured by compliance with:
EN 60079-0:2012 General Requirements EN 60079-1:2007 Flameproof Enclosures “d”
EXAM (BBG Prüf - und Zertifizier GmbH)
Intrinsic Safety (DMT 00 ATEX E 064)
Group I, Category M2, Ex ia, Group I, EPL Mb Group II, Category 2 G, Ex ia, Group IIC, Temperature Class T4/T5/T6, EPL Gb
C05"
KH525""Qrgtcvkqp"cpf"Ockpvgpcpeg"Kpuvtwevkqp"Ocpwcn"
Supply circuit for the connection to an intrinsically safe FISCO fieldbus-circuit: Ui = 24Vdc, Ii = 380 mA, Pi = 5.32 W, Ci 5 nF, Li = neg Parameters of the supply circuit comply with FISCO model according to Annex G EN 60079-11:2012, replacing EN 60079-27:
2008.
Input-signal-circuits: three 0-20 mA or 4-20 mA signal inputs with common ground Input impedance (load impedance) Ri 100 Effective internal capacitance Ci negligible Effective internal inductance Li negligible
Safety relevant maximum values for certified intrinsically safe 0-20 mA or 4-20 mA signal circuits as a function of ambient temperature and temperature class
Max. Ambient temperature Ta 60ºC T4 28 V 93 mA 750 mW 50ºC T5 28 V 93 mA 750 mW 40ºC T6 28 V 93 mA 570 mW
The signal inputs are safely galvanically separated from the fieldbus circuit.
Ambient Temperature: -40ºC Ta +60ºC
The Essential Health and Safety Requirements are assured by compliance with:
EN 60079-0:2012 + A11:2013 General Requirements EN 60079-11:2012 Intrinsic Safety “i”
CEPEL (Centro de Pesquisa de Energia Elétrica)
Intrinsic Safety (CEPEL 97.0020X)
Ex ia, Group IIC, Temperature Class T4/T5, EPL Ga
Entity Parameters: Pi = 5.32 W, Ui = 30V, Ii = 380mA, Ci = 5.0nF, Li = Neg
Ambient Temperature:
-20 to 65ºC T4
-20 to 50ºC T5
Explosion Proof (CEPEL 97.0090) Ex d, Group IIC, Temperature Class T6, EPL Gb
Maximum Ambient Temperature: 40ºC (-20 to 40 ºC)
Environmental Protection (CEPEL 97.0020X AND CEPEL 97.0090) Options: IP66/68W or IP66/68
Special conditions for safe use:
The certificate number ends with the letter "X" to indicate that for the version of Current to FIELDBUS Converter model IF303 equipped with housing made of aluminum alloy, only can be installed in "Zone 0" if is excluded the risk of occurs impact or friction between the housing and iron/steel itens.
The Essential Health and Safety Requirements are assured by compliance with:
ABNT NBR IEC 60079-0:2008 General Requirements ABNT NBR IEC 60079-1:2009 Flameproof Enclosures “d” ABNT NBR IEC 60079-11:2009 Intrinsic Safety “i” ABNT NBR IEC 60079-26:2008 Equipment with equipment protection level (EPL) Ga IEC 60079-27:2008 Fieldbus intrinsically safe concept (FISCO) ABNT NBR IEC 60529:2009 Classification of degrees of protection provided by enclosures (IP Code)
Temperature Class
Voltage DC Ui
Current Ii Power Pi
"
C06"
Kfgpvkhkecvkqp"Rncvg""
CSA (Canadian Standards Association)
Egtvkhkecvkqpu"Kphqtocvkqp"
FM Approvals (Factory Mutual)
NEMKO (Norges Elektriske MaterielKontroll) / EXAM (BBG Prüf - und Zertifizier GmbH)
C07"
KH525""Qrgtcvkqp"cpf"Ockpvgpcpeg"Kpuvtwevkqp"Ocpwcn"
CEPEL (Centro de Pesquisa de Energia Elétrica)
C08"
Eqpvtqn"Ftcykpi"
Canadian Standards Association (CSA)
Egtvkhkecvkqpu"Kphqtocvkqp"
C09"
KH525""Qrgtcvkqp"cpf"Ockpvgpcpeg"Kpuvtwevkqp"Ocpwcn"
C0:"
Factory Mutual (FM)
Egtvkhkecvkqpu"Kphqtocvkqp"
APPROVAL.
PREVIOUS MANUFACTURER
BE SUBSTITUTED WITHOUT
COMPONENTS CAN NOT
110 mA
30V
Imax
4-20mA
Vmax
Ci=5nF Li=12uH
TRANSMITTER SPECIFICATION MUST BE IN ACCORDANCE TO FM
REQUIREMENTS:
(ANSI/NFPA 70) AND ANSI/ISA-RP12.6
APPROVAL LISTING.
1 - INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE
2 -
SAFE AREA APPARATUS
UNSPECIFIED, EXCEPT THAT IT MUST NOT
BE SUPPLIED FROM, NOR CONTAIN UNDER
NON HAZARDOUS OR DIVISION 2 AREA HAZARDOUS AREA
MARCIAL
7
20
MARCIAL
6
16
MOACIR
5
07
MOACIR
4
REV.
DESIGN AREA
10 08 20
07 07 16
CASSIOLATO
05 03 07
CASSIOLATO
08
MISSAWA
MISSAWA
AND MOUNTING ENCLOSURES.
3 - ASSOCIATED APPARATUS GROUND BUS TO BE INSULATED FROM PANELS
NORMAL OR ABNORMAL CONDITIONS, A
10 08
07 07
05 03
250mA
24V
SHIELD IS OPTIONAL IF USED, BE SURE TO INSULATE THE END NOT
WIRES: TWISTED PAIR, 22AWG OR LARGER.
SMALLER THAN 1(ONE) OHM.
4 - ASSOCIATED APPARATUS GROUND BUS RESISTANCE TO EARTH MUST BE
SOURCE OF POTENTIAL IN RELATION TO
EARTH IN EXCESS OF 250VAC OR 250VDC.
5 - OBSERVE TRANSMITTER POWER SUPPLY LOAD CURVE.
6 -
ASSOCIATED APPARATUS
GROUNDED.
SMALLER THAN Ca AND La OF THE ASSOCIATED APPARATUS.
FIELDBUS
Imax
Ci=5nF Li=12uH
Vmax
110 mAIsc
30V
Voc
2W
250mA
16V
Po
Isc
Voc
1,2W
24V
250mA
Po
Isc
Voc
CLASS I,II,III DIV.1, GROUPS A,B,C,D,E,F & G
MODELS IF302 AND IF303 - SERIES
7 -
8 - CABLE CAPACITANCE AND INDUTANCE PLUS Ci AND Li MUST BE
FIELDBUS
OPTIONAL
SHIELDING
GROUND BUS
I.S.
BARRIER
FIELDBUS
FIELDBUS
I.S.
BARRIER
4 to 20mA
CLASS I,II,III DIV.1
ENTITY PARAMETERS FOR ASSOCIATED APPARATUS
ENTITY VALUES:
4-20mA
FIELDBUS
Ca CABLE CAPACITANCE +5nF
La CABLE INDUCTANCE +12uh
GROUPS A,B,C,D,E,F & G
+-
-+
POWER SUPPLY
ALT DE
ALT DE
ALT DE
ALT DE
0002000208
DRAWING DESIGN VERIFIED APPROVED
0049/08
MELONI
0004/07
28 CUSTOMER:
0043/03
EQUIPMENT: IF302/303
0015/00
APPROVAL CONTROLLED BY C.A.R.
M.MISSAWA
03
95 28
03
CONTROL DRAWING
95 28
POWER SUPPLY
PELUSOSINASTRE
03
95 28
03
95
FM
APPROVED
smar
O.S. DRAWING N.
102A0081
: SH.
REV
07
01/01APPROVED
C0;"
KH525""Qrgtcvkqp"cpf"Ockpvgpcpeg"Kpuvtwevkqp"Ocpwcn"
C032"
Appendix B
Model: IF302 ( ) IF303 ( ) Serial Number: _______________________________________________________________________________________________________
TAG: _______________________________________________________________________________________________________ How many
channels are used in IF?
Configuration: Magnetic Tool ( ) PC ( ) Software: _____________ Version: _______________________
Type/Model/Manufacturer of device connected to the channel 1: Type/Model/Manufacturer of device connected to the channel Type/Model/Manufacturer of device connected to the channel
Hazardous Area Classification:
( ) No More details: ________________________________________________________________________________________
Types of Interference presents in the area:
Ambient Temperature:
______________________________________________________________________________________________________________________
1 ( ) 2 ( ) 3 ( )
_______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________
2: 3:
( ) Yes, please specify: _______________________________________________________________________________
Without interference ( ) Temperature ( ) Vibration ( ) Others: _____________________________________
From __________ºC up to __________ºC
SRF – Service Request Form
Converter from 4-20mA to Fieldbus
GENERAL DATA
INSTALLATION DATA
PROCESS DATA
OCCURRENCE DESCRIPTION
______________________________________________________________________________________________________________________ ______________________________________________________________________________________________________________________ ______________________________________________________________________________________________________________________
SERVICE SUGGESTION
Adjustment ( ) Cleaning ( ) Preventive Maintenance ( ) Update / Up-grade ( ) Other: ___________________________________________________________ _____________________________________________________
USER INFORMATION
Company: _____________________________________________________________________________________________________________ Contact: _______________________________________________________________________________________________________________ Title: _________________________________________________________________________________________________________________ Section: ______________________________________________________________________________________________________________ Phone: _________ _________________________ _________ _________________________ Extension: ___________________________ E-mail: ________________________________________________________________________ Date: ______/ ______/ __________________
Further information about address and contacts can be found on www.smar.com/contactus.asp.
For warranty or non-warranty repair, please contact your representative.
B.1
IF303 – Operation, Maintenance and Instructions Manual
Returning Materials
Should it become necessary to return the converter to SMAR, simply contact your loc al agent or SMAR office, informing the defective instrument’s serial number, and return it to our factory.
In order to expedite analysis and solution of the problem, the defective item shoul d be returned with a description of the failure observed, with as many details as possi ble. Other informatio n concer ning to the instrument operation, such as service and process conditions, is also helpful.
B.2
Loading...