Specifi cations and inf or m ation are subject to change withou t notice.
Up-to-date address information is available on our website.
web: www.sm ar.com/contactus.asp
www.smar.com
FY400 Hart – Operation, Maintenance and Instructions Manual
This instructions manual includes information about specification, in stallation, operation and
maintenance for the Smart Valve Positioner FY400 Series. The manual describes all FY400 Smar
Valve Positioner Series functionalities.
Only qualified personnel should install, operate and perform FY400 maintenance.
Any doubt involving these instructions or (for) information not included in this manual, please contact
the Smar Marketing Department for clarifications or more information.
SMAR - MARKETING DEPARTAMENT: +55 16 3946-3519
III
FY400 Hart – Operation, Maintenance and Instructions Manual
THIS MANUAL CONTAINS:
This manual contains the sections listed below. Each section has it own index. Consult the index of
each section for a complete list of subsections.
INTRODUCTION
Informs the manual content and describes the FY400 in short.
Section 1 - INSTALLATION
Shows information about insta llation on actuators and the FY400 electric and pneumatic
connections.
Section 2 - OPERATION
Clarifies details on the operation, how the FY400 works.
Section 3 - SPECIFICATIONS
Describes the FY400 specifications and other related information.
Section 4 - LOCAL ADJUSTMENT Shows the FY400 local programming instructions.
Section 5 - CONFIGURATION
Details the FY400 configuration instructions.
Section 6 - MAINTENANCE Describes troubleshooting and their solutions, and FY400 maintenance procedures.
Section 7 - SPARE PARTS
FY400 spare parts and materials.
IV
Introduction
INTRODUCTION
The FY400 is a smart positioner for linear or rotary control valves, which may use single action
(spring return) pneumatic actuators or double action actuators.
It is based on a field-proven piezo flapper and non-contacting Hall-effect pos ition sensor that
provides reliable operation and safe performance. The digital technology used in the FY400 enables
the choice of several types of flow characterizations of the final control element. In addition, it has an
easy interface betw een the field and the control room among severa l interesting features that
considerably reduce installation, operation and maintenance costs.
The FY400, besides the normal functions offered by other conventional posit ioners, offers the
following functions:
Table – through a 16-point table, t he user may configure his ow n characterization curve, in
addition to the regular valve characterization functions, such as linear, same percentage and
quick hyperbolic opening.
Local Adjustment - not only for travel adjustment, but also flow characterization, tuning,
operation mode, indication, set point and PID (proportional, integral, and derivative) parameters.
Password - three levels for different functions.
Operation Counter - shows the number of changes in each function.
Auto Tuning - Automatic tuning of valve travel and PID parameters.
Auto Setup - It is an automatic procedure t hat allows the positioner to check the valve stroke
limits, giving, at the end of the procedure, a diagnosis indicating possible assembling problems.
Diagnostic - Permanent valve monitoring condition for preventive or predictive maintenance.
Get best results of the FY400 by carefully reading this instruction manual.
WARNING
Throughout the operation of the positioner, including self setup, do not touch the moving parts of the
valve/actuator/positioner set as they may unexpectedly move. Make sure to disconnect the air supply before
touching any moving parts.
V
FY400 Hart – Operation, Maintenance and Instructions Manual
r
r
This manual is compatible w ith version 2. XX, where 2 indicates softw are version and XX
software release. The indication 2.XX means that this manual is co mpatible with any release of
software version 2.
Waiver of responsibility
The contents of this manual abides by the hardware and software used on the current equipment
version. Eventually there may occur divergencies between this ma nual and the equipment. The
information from this document are periodically reviewed and the necessary or identified corrections
will be included in the following editions. Suggestions for their improvement are welcome.
Warning
For more obj ectivity and clarity, this man ual does not contain all the d etailed information on th e
product and, i n addition, it does not cover every possible mounting, operation or m aintenance
cases.
Before installing and utilizing the equipment, check if the model of the acquired equipment complies
with the technical requirements for the application. This checking is the user’s responsibility.
If the user needs more information, or on the event of specific problems not specified or treated in
this manual, the information should be sought from Smar. Furthermore, the user recognizes that the
contents of this manual by no means modify past or present agreements, confirmation or judicial
relationship, in whole or in part.
All of Sm ar’s obligation result from the purchasing agreement signed between the parties, which
includes the complete and sole valid warranty term. Contractual clauses related to the warranty are
not limited nor extended by virtue of the technical information contained in this manual.
Only qualified personnel are allowed to participate in the activities of mounting, electrical connection,
startup and maintenance of the equipment. Qualified personnel are understood to be the persons
familiar with the mounting, electrical connection, startup a nd operation of the equipment or othe
similar apparatus that are technically fit for their work. Smar provides specific training to instruct and
qualify such professionals. However, each country must comply with the local safet y procedures,
legal provisions and regulations for the mounting and operation of electrical installations, as well as
with the laws and regulations on classified areas, such as intrinsic safety, explosion proof, increased
safety and instrumented safety systems, among others.
The user is respons ible for the inc orrect or inadequate handling of equipments run with pneumatic
or hydraulic pressure or, still, subject to corrosi ve, aggressive or combustible products, since thei
utilization may cause severe bodily harm and/or material damages.
The field equipment referred to in this manual, when acquired for classified or hazardous areas, has
its certification void when having its parts replaced or interchanged without functional and approval
tests by Smar or any of Smar authorized dealers, which are the competent companies for certifying
that the equipment in its entirety meets the applicable standards and regulations. The same is true
when converting the equipment of a communication protocol to another. In this case, it is necessar y
sending the equipment to Smar or any of its aut horized dealer. Moreover, the certificates are
different and the user is responsible for their correct use.
Always respect the instructio ns provided in the Manual. Smar is not respons ible for an y losses
and/or damages resulting from the inadequate use of its equipments. It is the user’s responsibility to
know and apply the safety practices in his country.
GENERAL .................................................................................................................................................................... 1.1
OPTIONS OF DISPLAY ASSEMBLY ........................................................................................................................ 1.10
AIR SUPPLY .............................................................................................................................................................. 1.14
RECOMMENDATIONS FOR INSTRUMENT AIR SUPPLY SYSTEM ...................................................................... 1.14
ROTARY AND LINEAR MAGNET ............................................................................................................................. 1.15
REMOTE SENSOR POSITION ................................................................................................................................. 1.17
INSTALLATION IN HAZARDOUS AREAS ................................................................................................................ 1.18
SECTION 4 - LOCAL PROGRAMMING ...................................................................................................... 4.1
LOCAL ADJUSTMENT ................................................................................................................................................ 4.1
MAGNETIC TOOL ....................................................................................................................................................... 4.1
W1 AND W2 JUMPERS CONNECTION ..................................................................................................................... 4.1
LOCAL PROGRAMMING TREE .................................................................................................................................. 4.3
TRIM ............................................................................................................................................................................. 5.5
GENERAL INFORMATION .......................................................................................................................................... 6.1
CHECKING THE PIEZO BASE SET CALIBRATION ............................................................................................................. 6.8
MAINTENANCE - MECHANICAL PARTS ................................................................................................................. 6.10
MAINTENANCE – ELECTRONIC PARTS ................................................................................................................. 6.11
SPARE PARTS LIST ................................................................................................................................................... 7.3
FY400 Hart – Manual de Instruções, Operação e Manutenção
X
Section 1
General
Mounting
INSTALLATION
NOTE
The installation carried out in hazardous areas should follow the recommendations of the IEC60079-14 standard.
The overall accuracy of measuring and control depends on several factors. In spite of the excellent
performance, the positioner must be adequately installed so that it may work well.
Among all factors that may affect the positioner accuracy , environmental conditions are the most
difficult to control. But there are ways to reduce the effectsof temperature, humidity and vibration.
Installing the positioner in ar eas protected from extreme environmental changes can minimize
temperature fluctuation effects. In warm environments, the positioner should be installed to avoid, as
much as possible, direct exposure to the sun. Installation close to lines and vessels subjected to
high temperatures should also be avoided. If not possible to avoid it, consider using the remote
position sensor version.
Use thermal isolation to protect the positioner from external heart sources, if necessary.
Humidity is fatal to electronic circuits. In areas subjected to high relative humidity, the O-rings for the
electronic housing covers must be correctly placed and the covers must be completely closed by
tighten them by hand until y ou feel the O-rings being compressed. Do not use tools to tight the
covers. Removal of the electronics cover in the field should be reduced to the minimum necessary,
since each time it is removed; the circuits are exposed to the humidity.
The electronic circuit is protect ed by a humidity proof coating, but frequent ex posures to humidity
may affect the protection provided. It is also important to keep t he covers tightened in place. Every
time they are removed, the th reads are exposed to corrosion, si nce painting cannot protect these
parts. Sealing methods should be employed on conduit entering of the positioner.
IMPORTANT
Avoid to use thread sealant tapes on the air input and outputs connections, since small pieces of this type of
sealant may block the air flow inside the positioner, affecting the overall equipment performance.
Although the positioner is practica lly vibration resistant, it is not recommended to install it near
pumps, turbines or other equipament producing too much vibration. If not possible to avoid it,
consider using of remote position sensor version.
The FY400 mounting depends on the type of actuator, its actions, si ngle (with spring return) or
double, and the movement characteristic (linear or rotary). It requires two mounting brackets: one for
the magnet and another for t he positioner. Smar supplies both acco rding to the specified ordering
code (see Page 7.6 for mounting bracket ordering code).
Additionally, a great variety of customized mounting brackets is ava ilable, covering several control
valves models from different manufacturers.
Check the availability and select the most adequate mounting bracket to your need, by visiting our
web page on the Internet: http://www.smar.com. Select "Valve Positioner" option to access the
product specific page. After enter y our login and password, click on the Bracket for FY link and
choose the most appropriate mounting bracket to your application.
1.1
FY400 Hart – Operation, Maintenance and Instructions Manual
LINEAR MAGNET
See below an example showing the Positioner with rotary and linear magnets.
ROTARY MAGNET
OUT 2OUT 1
IN
PG 13.5
Figure 1.1 – Positioner and Linear Magnet
M20x1.5
1/2 NPT
Figure 1.2 – Positioner and Rotary Magnet
OUT 1OUT 2
IN
PG 13.5
1/2 NPT
M20x1.5
IMPORTANT
Smar web site (www.smar.com) has options of mounting brackets available for s everal actuators of s everal
manufacturers and models and the related dimensional drawings.
Rotary Movement
ROTARY MAGNET
BRACKET
ROTARY
MAGNET
POSITIONER
BRACKET
1.2
VALVE STEM
M6x1 SCREWS
(4 PLACES)
Figure 1.3 – Positioner with Rotary Actuator
NOTE
Included in the package content the centralizer device of rotary magnet. See figure 1.21-B.
POSITIONER
Section 1 - Installation
C
REMOTE POSITIONER
1/2 NPT
M20x1.5
PG 13.5
M6 x 1 SCREWS
(2 PLACES)
OUT 2
“L” BRACKET WITH “U” CLAMP
FOR REMOTE POSITIONER
IN
OUT 1
REMOTE
EXTENSION
REMOTE EXTENSION
BRA
KET
Figure 1.4 – Positioner in Rotary Actuator with Remote Position Sensor
Install the magnet on the valve stem using the its proper bracket, according to the Figure 1.3.
Then, install the positioner bracket on the actuator. Usually , the actuador is designed according to
the VDI/VDE 3845 standard, and, in this case, tight en the four screw s with their lock washeers on
the proper bracket.
NOTE
Make sure that the arrow engraved on the magnet coincides with the arrow engraved on the positioner when
the valve is in mid travel.
When mounting the magnet, be sure that:
1. There is no attrict betw een the internal magnet face and the position sensor salience during the
travel (rotary or linear), through the magnet.
2. The magnet and the salience of position sensor must not be distant.
A minimum distance of 2 mm and a maximum distance of 4mm are recommended betw een the magnet
external face and the positioner face. For that, a cent ralizer device (linear or rotary ) must be used. The
centralizer device is in the positioner packing.
Case the positioner installation or magnet change or if any other modification is done, the positioner
will require a re-calibration. See Section 5 for Auto-Setup procedure.
See item “Pneumatic Connections” as recommended practice to insta ll the positioner to the valve
type.
1.3
FY400 Hart – Operation, Maintenance and Instructions Manual
/
Linear Movement
Install the magnet on the valve stem using its proper bracket, according to Figure 1.5.
Install the positioner bracket on t he actuator. The fastening of the actuator br acket may follow the
NAMUR/IEC 60534-6-1 standard or be in accordance w ith the user specified boring. Mount the
positioner on the bracket by fastening the four screws in the holes of the pressure gauges opposite
face. Use lock washers to avoid loosening the screws.
The linear magnet movement must be orthogonal in relation to the main axis of the position
positioner. For example, if the linear magnet movement is vertical, the positioner main axis must be
horizontal, as show in Figure 1.5.
LINEAR MAGNET
BRACKET
VALV E YOKE
POSITIONER
VALV E
STEM
LINEAR
MAGNET
CENTRALIZER DEVICE
POSITIONER
OUT 1OUT 2
IN
BRACKET
M6 x 1 SCREWS
(4 PLACES)
M20x1.5
PG 13.5
1
2NPT
Figure 1.5 – Positioner in Linear Actuator
NOTE
Included in the package content the centralizer device of linear magnet. See figure 1.21-A.
1.4
VALVE YOKE
VALVE STEM
LINEAR MAGNET
CENTRALIZER DEVICE
REMOTE EXTENSION
LINEAR MAGNET
BRACKET
POSITIONER
BRACKET
M6 x 1 SCREWS
(2 PLACES)
REMOTE POSITIONER
M6 x 1 SCREWS
(2 PLACES)
“L” BRACKET WITH “U” CLAMP
FOR REMOTE POSITIONER
Section 1 - Installation
1/2 NPT
M20x1.5
PG 13.5
OUT 2
IN
OUT 1
Figure 1.6 – Positioner in Linear Actuator with Remote Position Sensor
Make sure the bracket does not obstruct the exhaust outputs.
Make sure that the arrow engraved on the magnet coincides with the arrow engraved on the positioner when
the valve is in mid travel.
When mounting the magnet, be sure that:
1. There is no attrict betw een the internal magnet face and the position sensor salience during the
2. The magnet and the salience of position sensor must not be distant.
A minimum distance of 2 mm and a maximum distance of 4mm are recommended betw een the magnet
external face and the positioner face. For that, a cent ralizer device (linear or rotary ) must be used. The
centralizer device is in the positioner packing.
Case the positioner installation or magnet change or if any other modification is done, the positioner
will require a re-calibration. See Section 5 for Auto-Setup procedure.
Pneumatic Connections
The FY400 requires instrument air quality , following the best practices for pneumatic installations.
Consult the American National St andard "Quality Standard for Instrum ent Air" (ANSI/ISA S7.0.01 -
1996) for detailed information.
The FY400 comes with input and output stainless steel air filters, but these filters do not exclude the
preliminary instrument air treatment. Periodical f ilter cleaning is recommended at every 6 months or
less, if the air quality is not good. Please, check the maintenance section for clean the filters.
The FY400 supply air pressure varies from 1.4 bar (20 psi) minimum, to 7.0 bar (100 psi) maximum.
The actuator working pressure must follow these limits. Consider the use of boosters, if required.
Pressure below this range shall affect the posit ioner performance. Pressure above this range may
damage the positioner.
The two pneumatic outputs, marked as “OUT1” and “OUT2”, work in opposite directions to open or
close the valve.
NOTE
travel (rotary or linear), through the magnet.
1.5
FY400 Hart – Operation, Maintenance and Instructions Manual
If a failure occurs on the FY400, such as power loss (4-20 mA input signal), the output marked OUT1 goes to
zero pressure and the output marked OUT2 goes to the air supply pressure value.
The positioner can have pressure gages (see the ordering code tabl e) attached to the supply air
input and in each output. The indications on gages are references only and does not have the same
overall positioner accuracy.
The pneumatic connections are marked w ith IN for the air supply and OUT1 and OUT2 for Output1
and Output2, respectively . Use 1/4 NPT connections w ith sealing material for the NPT screw
threads. Connect the air supply on the connection marked IN. Be sure the air supply does not
exceed the maximum allowed pressure of the positioner or the actuator.
When using tape sealant ty pe on the thread connections, be sure not spr ead small residues inside, since
they may clog the air flow inside the positioner and even impair the equipment efficiency.
The FY400 has five protected exhaust orif ices with filters. Do not block any of these exhaust, as the
air must circulate freely through them. If painting the positioner block, remove the filters before, to
prevent them from beign obs tructed by paint. The orifices must be inspected on a regular basis to
ensure they not blocked, granting the air to flow smothly.
Double Action – Air to open (Close on failure)
Connect the positioner OUT 1 output on the actuator connection marked with “OPEN” and connect
the positioner OUT2 output on the actuator connection marked with “CLOSE”.
Double Action – Air to close (Open on failure)
Connect the positioner OUT 2 output on the actuator connection marked with “OPEN” and connect
the positioner OUT1 output on the actuator connection marked with “CLOSE”.
Single Action
Connect the positioner OUT1 output on the actuator input. Use a plug to block OUT2. Pay attention
to the safe logic on the actuator for the specific process. If nece ssary, invert the connections. Take
into consideration that in case of power failure the output marked OUT1 goes to zero pressure and
the output marked OUT2 goes to the air supply pressure value.
IMPORTANT
IMPORTANT
1.6
(
)
(
1.95
)
j
Dimensional Drawing
95
(3.74)
OUTPUT 1
1/8-27NPT
268
(10.55)
OUTPUT 2
1/8-27NPT
OUTPUT 3
1/8-27NPT
55
(2.17)
REMOTE SENSOR POTION
TERMINAL
WIRING
45
3945
(1.53)(1.77)(1.77)
POSITIONER
125
(4.92)
SOCKET SET
PLUG
OUTPUT 2
1/4-18NPT
INPUT
PRESSURE
1/4-18NPT
OUTPUT 1
1/4-18NPT
9
(0.35)
46.5
(1.83)
DIMMENSIONS IN mm (in)
Leave, at least, a 150mm (5.8in) spa ce,
for lower and upper position ad
with the magnetic tool.
83
ELECTRICAL
(3.27)
CONNECTION
EXHAUST
ORIFICIES
THREADS FOR
2424
(0.94)(0.94)
53,3
(2.10)
M6x1
SCREWS
4 PLACES
ustments
Section 1 - Installation
24
(0.94)
55
(2.17)
49.5
Figure 1.7 – FY400 Dimensional Drawing
1.7
FY400 Hart – Operation, Maintenance and Instructions Manual
(1.97)
)
T
LINEAR MAGNE
HOLE 6.3 (0.25)Ø
(2 PLACES)
18
64.5
(2.54)
(0.71)
ROTARY MAGNET
MOUNTING HOLES FOR M6x1
SCREWS (2 PLACES)
6.5
(0.25)
22.5
(0.89)
33
(1.30)
TRAVELDIMENSION A
UP TO 15 mm (0.59)
UP TO 30 mm (1.18)
UP TO 50 mm (1.97)
UP TO 100 mm (3.94)
43 mm (1.7)
67 mm (2.64)
105 mm (4.13)
181 mm (7.12)
*ONLY FOR 50 AND 100 mm TRAVELS.
(0.59)
Figure 1.8 – Magnet Dimensional Drawing
Electronic Housing Rotation
The electronic housing can be rotated to offer a be tter Display position and/or better access to the
field cables. To rotate it loose the Housing Locking Screw as shown on Figure 1.9 below.
69
(2.72)
21
15
15 *
(0.59)
(0.83)
(0.87)13(0.51)
22
39
(1.54)
Dimensions in mm (in
O
D
E
R
E
E
H
V
P
I
L
S
A
O
M
T
T
I
A
U
C
R
E
I
V
C
I
S
N
O
L
E
P
H
X
W
E
T
H
N
I
G
I
-
T
N
P
O
E
I
E
T
K
U
A
C
A
Z
I
A
V
G
I
R
S
O
E
L
N
P
E
X
E
O
D
A
N
R
A
E
U
F
Q
S
O
O
M
D
T
A
A
T
R
M
E
E
P
-
A
O
D
A
A
H
D
I
N
U
E
C
T
N
A
M
50
24
(0.954)
1.8
HOUSING ROTATION
ADJUSTING SCREW
Figure 1.9 – Housing Rotation Adjusting Screw
Electrical Wiring
Section 1 - Installation
To access the terminals block loosen the cover locking screw to release the cover as show n in
Figure 1.10.
L
O
S
P
I
X
E
N
I
W
-
T
H
N
G
I
O
T
I
T
P
U
E
A
E
C
K
M
C
U
A
N
I
D
T
A
E
D
N
O
H
A
-
E
M
A
A
P
T
E
R
T
A
V
E
N
E
H
M
O
S
D
O
A
C
T
I
R
M
C
O
U
I
S
T
P
H
A
E
L
R
I
V
E
E
A
V
D
I
A
S
Z
I
O
L
G
P
R
X
E
E
N
A
E
R
E
F
O
D
N
A
U
Q
COVER LOCKING
SCREW
O
Figure 1.10 – Cover Locking Screw
The wiring block has screws is suitable for fork or eye terminals.
COMMUNICATION
TERMINALS
GROUND
TERMINALS
TEST
TERMINALS
Figure 1.11 – Terminal Block
The FY400 terminal block was developed to allow signal connections regardless their polarity.
Test and Communication terminals allow, respectively, to measure the current in the 4 - 20 mA loop,
without opening the circuit, and also to communicate with the Positioner via HART protocol. T he
“Test Terminals” is used to measure the current. The “COMM” terminal is used for HART
communication. The terminal block has screws where fork or ring-type terminals can be fastened.
1.9
FY400 Hart – Operation, Maintenance and Instructions Manual
For convenience, the positioner has two ground terminals: one internal and one external, both
located near the conduit inlet.
Figure 1.11-A - Conduit Installation Diagram
Use of twisted pair cables (22 AW G or greater) is recommended. F or environments with high EMI
interference levels, the use of shielded cables should be observed.
Avoid routing signal wiring near to power cables or switching equipment.
The duct threads must be sealed according to the hazardous area standards.
The unused cable entries should be plugged and sealed accordingly to avoid humidity entering,
which can cause the loss of the product’s warranty (see figure 1.12).
Options of Display Assembly
It is possible to turn the Display in four different positions, making easie r the reading. The mark ,
enrolled on the top of Display indicates the reading position. See figure 1.13 below.
After opening the electronic housing cover, release the four screw s of Display. Choose the most
appropriate position and re-assembly the whole set.
1.10
Figure 1.12 – Plug Mounting
Section 1 - Installation
B
A
C
D
Figure 1.13 – Positions four of Display
Put back the Main Electronic Circuit Board and the Display with your screws.
Typical Installation fot the Hart® Protocol
The FY400 connection should be made accordingly follwing examples.
Conect the hand held configurator to the communication terminals of positioner or at any point of the
cable.
The Hand-Held Terminal can be connected to the co mmunication terminals of the transmitter or at
any point of the signal line by using the alligator clips. It is also recommended to ground the shield of
shielded cables at only one end. The ungrounded end must be carefully isolated. On multi-drop
connections, the circuit loop integrity must be assur ed, with special care to prevent short-circuit
between the circuit loop and the housing.
CD600
THE LOOP SIGNAL CAN BE GROUNDED
(OR NOT) AT ANY POINT.
Figure 1.14 – Hart FY400 Wiring Diagram, wiht the CD600
CONFIGURATOR
1.11
FY400 Hart – Operation, Maintenance and Instructions Manual
Figure 1.16 - Connected FY400 the a Transmitter Smar working as Controller
The FY400 has an equivalent impedance of 550 Ohms. T herefore, check if t he power supply, the
DCS, CLP analog output, or single loop controller powering the positioner is capable to handle a
voltage drop of 11 V for the positioner.
1.12
Section 1 - Installation
IMPORTANT
When having tw o positioners working in the Split Range mode, connected to only one 4 to 20 mA current
source, their impedances are added, resulting 1100 Ohms (in the case of 2 Posicionadores). The maximum
voltage drop for the two positioner is 22 Volts. Be sure that the current source is able to drive the 4 o 20 mA for
both positioners.
What is a Split Range control?
That type of control involves tw o positioners c onnected in series into just one analogical output,
each one controlling its own valve. For instance:
- Positioner 1: 4 - 12 mA = 0 - 100%;
- Positioner 2: 12 - 20 mA = 0 - 100%;
The examples on Figure 1.17 and 1.18 shows a typical installation of a device driving an output of 4
to 20 mA in combination with a power distributor isolator IS400P, granting power both positioners to
work in a Split Range application.
+
OUTPUT A
OUTPUT B
1A
-
2A
+
3A
-
4A
CONFIGURATOR
1B
2B
IS400P - Power Distributor and Isolator
INPUT
POWER
SUPPLY
24VDC
ON
OFF
FUSE
0.2A
+
1B
-
2B
+
3B
-
4B
CONFIGURATOR
smar
Figure 1.17 – Potitioners Wiring Diagram with CD600, in Split Range.
1.13
FY400 Hart – Operation, Maintenance and Instructions Manual
OUTPUT A
OUTPUT B
+
1A
-
2A
+
3A
-
4A
CONFIGURATOR
1B
2B
IS400P - Power Distributor and Isolator
INPUT
POWER
SUPPLY
24VDC
ON
OFF
FUSE
0.2A
+
1B
-
2B
+
3B
-
4B
smar
Figure 1.18 - Wiring Diagram of Positioners with LC700/M501, in Split Range.
Air Supply
The FY400 is designed and manufacture to work with good quality instrumentation air. The following
issues are some recommendations based on field practices w hich will increase the FY400
performance and lifetime.
Before connecting the instrument air supply to the positioner, it is strongly recommended to open the
tubing freely for 2 to 3 minutes to blow out any possible contamination present inside the installation.
Use a white paper towel direct into the instrument air flow and check visually if there is any water, oil,
or any other undesirable material. Case the ins pection shows the presence of contaminants and/or
humidity please refers to the “Recommendations for Instrument Air Supply System” below.
Once the positioner is pressuri zed and powered, an internal air fl ow will improve protection against
corrosion and prevent the moisture getting inside it. For this reason, the air supply should always
pressurize the equipment, even when the process is not operating.
Recommendations for Instrument Air Supply System
To get the best F Y400 performance and to increase its lifetime, the instrum ent air quality shall be
superior to that of industrial compressed air. Humidity, suspended particles and oil contamination,
even lubricating oil, may impair the instrument operation, either temporarily or permanently in case
of internal parts wearing.
As per the ANSI/ISA Standard S7.0. 01 - 1996 - Quality Standard for Instrument Air, instrument air
shall the following characteristics:
Dew point
Size of particles
Oil content
Contaminants
10ºC below minimum instrument temperature.
40 µm (maximum).
1 ppm w/w (maximum).
Free of corrosive contaminants and hazardous gases.
CONFIGURATOR
1.14
COMPRESSOR
INTAKE
Section 1 - Installation
The mentioned standard recommends to place the compressor intake in an environment free from
process spills, contaminants, and to use adequate filters. Also, t he compressors must be of nonlubricated type to prevent the pres ent of lubrificants. When using lubricated compressors, the plant
must have resources to remove the lubricant from the instrument air supplied.
The Figure 1.19 shows a typical for air supply and air quality adequacy:
AFTERCOOLER
CONDESANTE
SEPARATOR
WITH DRAIN
AIR RECEIVER
WITH DRAIN
COMPRESSOR
OIL AND WATER
MIST PREFILTER
WITH DRAIN
Figure 1.20 – Air Quality Conditioning System
Rotary and Linear Magnet
The Magnet models are linear (up to 30 mm, 50 mm and 100 mm) and rotary (30º - 120º), for
utilization on linear and rotary actuators, respectively.
The white bars on the linear magnet indicate the limit for using the magnet.
Linear Magnet
Figure 1.19 – Air Supply System
AIR
DRYER
DRY AIR
AFTERFILTER
Figure 1.21 – Linear and Rotary Models
Rotary Magnet
1.15
FY400 Hart – Operation, Maintenance and Instructions Manual
Magnet Centralizer Device
NOTE
Centralizer device of linear magnet is used for all type of
linear bracket.
NOTE
Centralizer device of linear magnet is used only for
universal rotary bracket.
Figure 1.21-A – Centralizer device of linear magnet Figure 1.21-B - Centralizer device of rotary magnet
1.16
r
r
Remote Sensor Position
The remote sensor potion is an accessory recommended for high temperature and extreme vibration
applications. It prevents excessive wear of the equipment and, consequently , the reduction of its
lifetime.
For an appropriate installation of the sensor, c heck if the engraved arro w on the magnet matches
the positioner arrow when the valve is at half way course.
The magnet mounting in relation to the position sensor should follow procedure below:
1. There is no friction betw een the magnet internal face, linear of rotary , and the remote
2. The magnet and the remote sensor bulge are not too far.
It is recommended to keep a minimum 2 mm space and maximum 4 mm distance betw een the
magnet external face and the remote sensor face. There is a centralizing device, for both linear and
rotary installations, inside the positioner packing which will help you to correctly install the positioner
and remote sensor.
Section 1 - Installation
position sensor bulge when excursioning for opening or closing the valve.
Positione
Extension Cable
Remote Position Senso
Figure 1.22 – Remote Position Sensor
The electric signals in the remote sensor cable are of low intensity. Therefore, when installing the
remote sensor cable inside the conduit (maximum limit 20 meters length), w e recommend to avoid
the proximity of possible inducti on sources and/or magnetic interf erence. The supplied cable is
shielded for protection against electromagnetic interference, but despite this protection avoid the
cable sharing the same conduit with other cables. See the figure 1.6.
The connector for remote position sensor is easy handle and simple installation. See the installation
procedure as per Figures 1.23 and 1.24:
1.17
FY400 Hart – Operation, Maintenance and Instructions Manual
Figure 1.23 – Connecting the Cable to the Remote Position
Sensor
Installation in Hazardous Areas
Explosions could result in death or serious injury, besides financial damage. Installation of this positioner in
explosive areasmust be carried out in accordance with the local standards and the protection ty pe adopted.
Before continuing the installation make sure the certificate parameters are in accordance with the classified area
where the equipment will be installed.
The instrument modification or parts replacement supplied by other than authorized representative of
Smar is prohibited and will void the certification.
The positioners are marked with options of the protection type. The certification is valid only when the protection
type is indicated by the user. Once a particular ty pe of protection is selected, any other type of protection can
not be used.
The electronic housing and the position sensor installed in hazardous areas must have a minimum of 6 fully
engaged threads. Lock the housing using the locking screw (Figure 1.10).
The cover must be tighten with at least 8 turns to av oid the penetration of humidity or corrosive gases. The
cover must be tighten until it touches the housing. Then, tighten more 1/3 turn (120) to guarantee the sealing.
Lock the covers using the locking screw (Figure 1.10).
Consult the Appendix A for further information about certification.
Explosion/Flame Proof
In Explosion-Proof installations the cable entries must be connected or closed using metal cable gland and
metal blanking plug, both with at least IP66 and Ex-d certification.
As the positioner is non-ignition c apable under normal conditions, the statement “Seal not Required” could be
applied for Explosion Proof Version.
The standard plugs provided by Smar are certified according to the standards at FM, CSA and CEPEL. If the
plug needs to be replaced, a certified plug must be used.
The electrical connection with NPT thread must use waterproofing sealant. A non-hardening silicone sealant is
recommended.
Do not remove the positioner covers when power is ON.
1.18
Figure 1.24 – Connecting Cable to the Positioner
WARNING
WARNING
Section 1 - Installation
Intrinsically Safe
WARNING
In hazardous zones w ith intrinsically safe or non-incendive requirement s, the circuit entity parameters and
applicable installation procedures must be observed.
To protect the application the positioner must be connected to a barrier. Match the parameters betw een
barrier and the equipment (Consider the cable parameters). Associated apparatus ground bus shall be
insulated from panels and mounting enclosures. Shield is optional. If used, be sure to insulate the end not
grounded. Cable capacitance and inductance plus Ci and Li must be smaller than Co and Lo of the associated
Apparatus (see appendix “A” for Ci and Li values).
For free access to the Hart bus in the explosive environment, ensure the instruments in the loop are installed in
accordance with intrinsically safe or non-incendive field w iring practices. Use only Ex Hart communicator
approved according to the type of protection Ex-i (IS) or Ex-n (NI).
It is not recommended to remove the positioner cover when the power is ON.
NOTE
To obtain all the available certifications consult www.smar.com.
1.19
FY400 Hart – Operation, Maintenance and Instructions Manual
1.20
Section 2
RESTRICTION
PILOT
DIAPHRAGM
SPOOL
DIAPHRAGM
AIR SUPPLY
NOZZLE
PIEZO
VAN E
SPOOL
PILOT CHAMBER
VENT 2
OUTPUT 2
OUTPUT 1
VENT 1
SPRING
PRESSURE TRANSDUCER
OPERATIONAL
Positioner Functional Description
The FY400 Hart® senses the actual stem valve position and takes the corrective action according to
a fully user configurable strategy. The “non-contact” position sensor (Hall effect based) prevents the
inadequacy of links and levers.
Figure 2.1 – Pneumatic Transducer
The 4 to 20 mA signal (from the controller) is processed at the main digital circuit board. The analog
board gets the information from the main circuit board and generates a low power voltage signal to
a piezo electric disc in the pressure transducer. It results in a inflection in such disc, moving it
nearer or further away from a noz zle in the pressure transducer. This inflection provides a (pilot)
pressure variation proportional to the loop controller.
The diaphragm block amplifies the force related to the pilot pressure and pushes down the spool
valve, allowing the supply pressure into the valve actuator. On the other hand, the spool valve
movement reliefs the pressure from the valve actuator to the atmosphere.
The valve stem will move in response to spool valve movement up to the correct position. The
magnet sensor reads the actual valve position (Hall effect) and feed it back to the main circuit
board. With the position information (readback signal), the microprocessor will drive a signal to the
analog circuit, correcting the valve position.
2.1
FY400 Hart – Operation, Maintenance and Instructions Manual
Circuit Functiona l Description
To understand the electronic operation of the FY400 positioner, refer to the blocks as per Figure
2.2.
DISPLAY
MAIN CIRCUIT BOARD
SUPPLY
LOCAL
AJUST
POWER
SUPPLY
4-20mA
INPUT
SUPPLY
TRANSDUCER
ANALOG CIRCUIT BOARD
TEMPERATURE
19K2
PWM
4-20 mA
SENSOR
DISPLAY
CONTROLLER
HART
MODEM
D/A
FRAM
A/D
CONVERTER
P_OUT2
P_OUT1
PWM
ISOLATION
P_IN
19K2
0-100 Vdc
POSITION
SENSOR
CIRCUIT
CPU
PID
FLASH
RAM
A/D
RESTRICTION
PRESSURE SENSOR CIRCUIT BOARD
P_IN
P_OUT1
P_OUT2
2.2
PIEZZO
FLAPPER
NOZZLE
SPOOL
VALVE
POSITION
SENSOR
SENSOR
IN
SENSOR
OUT1
SENSOR
OUT2
* Optional
Figure 2.2 – FY400 Block Diagram
VALVE
P1
ACTUATOR
P2
STEM
MAGNET
VALVE
Section 2 - Operation
Current Power Supply
To power the positioner circuit , it is used a current source of 4-20 mA, in general supplied by a
controller or through a transmission line of the sign (two-cable system). It needs at least of 3,8 mA
to work properly and to drive a necessary power to maintain the current through a load of 550
ohms.
A/D
It is a digital 16-bits converter used for reading of the following signs: 4-20 mA input, position
sensor, input pressure signal, the output 1 pressure and output 2 pressure and converts them into a
digital format for the CPU.
FRAM (Ferroelectric Crystal Memory)
It is a non-volatile memory where the configuration data are stored. Examples of such data are:
calibration, diagnosis and configuration of the valve.
®
HART
Modem
The function of this component is to make possible to exchange information between the Smar
hand-held programmer and the positioner though the frequency modulation HART
®
protocol digital
communication. Thus, the positioner demodulates the digital information from the current line
transmitted by the Smar hand-held programmer and, after processing it, modulates the result on
the line again. The “1” represents 1200 Hz and t he “0” represents 2200 Hz, according to the
NAMUR NE-43 standard. The frequency signal is symmetrical and so does not affect the DC level
on the 4-20 mA current. The display controller and D/A are embodied in this component.
D/A
It communicates with the CPU and applies a voltage output on the piezoelectric disk, proportional
to the position desirable by the controller. The signal is sent via modulation by pulse (PWM) based
on a reference frequency (19K2).
Display Controller
It receives data from CPU and manages the information to the liquid crystal display (LCD).
Central Processing Unit ( CP U) , RAM, FLASH e PID
The central processing unit (CPU) is the intelligent part of the positioner, which is responsible for its
management, operation, control, self-diagnostic and communications. The firmware is stored in the
FLASH memory. For temporary data storage, the CPU has an internal RAM. The PID controls the
valve desired position.
Local Adjustment
Two keys are activated magnetically without any external contact, electric or mechanical, through a
magnetic tool.
Temperature Sensor
It measures the temperature of the transducer circuit.
Isolation
Its function is to isolate the control signal of the piezoelectric disc voltage.
Position Sensor by Hall Effect
It measures the valve real position, conditioning the signal and sending it to the CPU for the PID
control execution.
Restriction
The restriction and the nozzle form a pressure division circuit. The air is supplied for the nozzle
through a restriction.
Baffle-Nozzle
The baffle-nozzle unit converts the piezoelectric disc movement in one sign of control pressure in
the pilot chamber.
Spool Valve
The spool valve assures the fast valve positioning amplifying the air flow.
Pressure Sensors (optional)
They make the readings of the positioner input and outputs pressures for diagnostic purposes.
2.3
FY400 Hart – Operation, Maintenance and Instructions Manual
NOTE
INDICATES TABLE
INDICATES MULTIDROP
INDICATES VALVE POSITION
CURRENTLY SHOWN
Pressure Sensor Circuit Board
Sensor IN: Measures the Input pressure.
Sensor OUT1: Measures the Output 1 pressure.
Sensor OUT2: Measures the Output 2 pressure.
The Pressure Sensor Circuit Board is optional (in the ordering code, K1 option).
Display
The digital display LCD is necessary to show the information and for operation in the local
adjustment mode.
During the normal operation, the FY400 stay in the monitoring mode and the display shows the
valve position in percentage. During the configuration process, there is an option to show the
setpoint on the display. The local programming mode is activated by approximating the magnetic
tool to the hole marked by the letter "Z", on the top of the electronic housing.
The Figures 2.3 and 2.4 show the possible configuration indications and monitoring information.
When powering the FY400, the display shows the FY400 model and the firmware version (X.XX).
Monitoring
During normal operation, the FY400 remains in the monitoring mode. The display on F igure 2.3
shows the valve position percentage.
This indication changes when approaching the magnetic tool near to the hole marked with "Z"
(Local Adjustment), and shows the programming mode through local adjustment.
On the indicator, one can see the result of inserting the magnetic tool in holes marked with “Z” and
“S”, which allows, respectively, browse through the programming tree and select option. (More
details in the Section 4).
2.4
INDICATES
CONSTANT OUTPUT MODE
INDICATES ADJUSTMENT/
INDICATES SETPOINT DISPLAYED
ACTIVATED
INDICATES ACTUATION
ON AUTOMATIC
INDICATES
ACTUATION
ON MANUAL
CHANGE VARIABLE/
MODE POSSIBLE
Figure 2.3 – Typical Display
FUNCTION ACTIVATED
Fix
A
M
F (x)
SPPV
Figure 2.4 – Local Display
MODE ACTIVATED
MD
VARIABLE FIELD
%
UNIT IN PERCENT
UNIT AND FUNCTION FIELD
Section 3
TECHNICAL CHARACTERISTICS
Functional Specifications
Travel
Linear Motion: 3 - 100 mm.
Rotary Motion: 30° - 120° rotation angle.
Input and Communication Protocol
Two-wires, 4-20 mA, accordi ng to NAMUR NE43 specification, with super-imposed digital Hart®
Protocol.
Power Supply
4 to 20 mA Loop-powered. No external supply required.
Built-in circuit protection against overvoltage up to 60 Vdc.
Built-in circuit protection against overcurrent up to 25 mA.
Context saving in case of power failure. The critical variables used in the positioner are saved in the
memory, avoiding the startup being affected by missing data in the registers and positioner variables.
Input Impedance
550 .
Minimum Current
3.8 mA.
Configuration
Local Adjustment (partially) with magnetic tool. No need to open the cover.
Remotely through:
- CONF401 Windows Based configuration software;
- HPC401 PalmOS Based Configurator;
- FDT/DTM Applications (Field Device Tool/Device Type Manager)
- Asset Management Applications (AssetView);
- Other configurations tools based on EDD.
Protection against Reverse Polarity
Electrical connection without polarity.
Built-in transient protection
Supports the instantaneous maximum v oltage of 65 V
components.
Output
Output from 0% to 100% pressure supply to the actuator. Single or double action.
Pressure Supply
1,4 - 7 bar (20 - 100 psi). Free of greas e, dust and water, according to ANSI/ISA S7.0.01 – 1996
standard.
Indication
4½ - numeric al digits and 5-character alphanumerical digits Liquid Crystal Display indicator.
Function and status icon.
Temperature Limits
Operation: -40 to 85°C (-40 to 185°F)
Storage: -40 to 90°C (-40 to 194°F)
Display: -10 to 75°C ( 14 to 167°F) Operation.
-40 to 85°C (-40 to 185°F) Without damage.
Remote Sensor: -40 to 105°C (-40 to 221°F)
without damage to the electronic
peak
3.1
FY400 Hart – Operation, Maintenance and Instructions Manual
Humidity Limits
0 to 100% RH (Relative Humidity).
Flow Characterization
Linear, equal percentage, quick opening and 16 freely selectable points by operator.
Auto Setup
It is an autom atic adjustment of the positioner to the va lve and actuator set, in others words, an
auto-calibration procedure of the equipment. During this procedure, the positioner checks the 0%
and 100% of the valve stroke related to the magnet and also calculates the converter A/D gain for
position readings.
Proportional Gain, Integral and Derivative Rates
Adjustable locally or by communication.
Adjusted automatically during the Auto Tuning or Full Setup procedure.
Travel Time
Adjustable locally or by communication.
Position Sensor
Non-contact Sensor by Hall effect. It is also available for the integral or remote assembling version.
Optional 4 to 20 mA for position measurement.
Pressure Sensor (optional request in the ordering code)
0 to 100 psi range.
Performance Specifications
Resolution
0.1 % F.S.
Repeatability
0.1 % F.S.
Hysteresis
0.1 % F.S.
Consumption
0.35 Nm³/h (0.20 SCFM) to 1.4 bar @ 20 psi air supply.
1.10 Nm³/h (0.65 SCFM) to 5.6 bar @ 80 psi air supply.
Output Capacity
13.6 Nm³/h (8 SCFM) to 5.6 bar @ 80 psi air supply.
Ambient Temperature Effect
0.8%/20 °C F.S.
Pressure Supply Effect
Negligible.
Vibration Effect
± 0.3 % /g of span during the following conditions:
5-15 Hz to 4 mm constant displacement.
15-150 Hz to 2g.
150-2000 Hz to 1g.
as per the IEC60770-1 Standard.
Electromagnetic Interference Effect
Designed to comply with the IEC801 Standards and European EN50081 and EN50082 directives.
Physical Specifications
Electrical connections
½ -14 NPT, Pg 13.5 or M20 x 1.5.
Certified Hazardous Locations (CEPEL). See Appendix “A”.
3.2
Diagnostics
Section 3 - Technical Characteristics
Pneumatic Connections
Air Supply and output: 1/4 - 18 NPT.
Gage: 1/8 - 27 NPT.
NOTE
The pressure gages for input, output 1 or output 2 pressures will be supplied with the external housing in SS316
and the wet parts in brass.
Construction Material
Injected low copper aluminum with polyester painting or 316 Stainless Steel housing, with Buna N orings on covers (NEMA 4X, IP66).
Equipment Weight
Without display and mounting bracket:
- 5.8 kg (Stainless Steel);
- 2.7 kg (Aluminum).
Add for the digital display: 0.1 kg.
Add for the remote position sensor: 550 g.
Add for the c able and connectors of the remote sensor: 100 g (c able) and 45 g/m (for eac h
connector).
- What is diagnostic?
Diagnostic is a group of methods to detect, locate and eventually indicate the corrective actions for
problems or failures in the actuator-valve set.
- What’s this for?
Using the diagnostics functions, it is pos sible to monitor permanently the actu ator-valve set
condition and to configure the parameters aiming at predictiv e and proactive maintenances.
Besides, it shows the equipment general conditions, allowing preventive actions to be taken on time.
The predictive maintenance prevents malfunctions in the actuator-valve set for continuous working
equipment, in other words, the diagnostic makes the actuator-valve set more reliable, improving the
process stability and keeping it safer.
- When should I configure the diagnostic?
The diagnostics configuration can be made only once, and the positioner will run the diagnostic
procedure continually. The user can change diagnostic configuration whenever necessary, since
each diagnostic can be enabled separately.
- What tool is necessary for the diagnostic?
The diagnostic is automatically performed by the positioner and the user can enable, configure and
visualize the diagnostic parameters through a configurator such as CONF401 or HPC401, or
additionally with asset management applications existing in the market that support EDD structure.
- Is it possible to configure the diagn ostic WITH or WI THOUT configurator?
The diagnostic will only be configured via a configurator that supports the positioner. The HPC401
enables and configures the simplest diagnostics, while the CONF401 makes possible the use of the
most advanced functions, besides, with through diagnostics graphs. The diagnostics functions and
configurations can also be accessed via application software based on the FDT/DTM standard.
3.3
FY400 Hart – Operation, Maintenance and Instructions Manual
V
STROKE LIMIT & REVERSALS
Stroke Limit - Characterizes the situation which the valve (or actuator) reaches an upper or lower
position, to the maximum or minimum limits, respectively, configured by the user, ge nerating an
alarm.
Related parameters:
Parameters Description
Stroke Limit High
Stroke Limit Low
Stroke Limit Deadband
Stroke Limit Counter
Stroke Limit Counter Limit
Stroke Limit Counter Alarm
Stroke Limit Counter First
Activation
Stroke Limit Counter Last
Activation
Stroke Limit Alarm Time L imit
Stroke Limit Alarm
Stroke Limit Operation Time
Stroke Limit Measured Time
Configuration example:
Parameters
Stroke Limit High
Stroke Limit Low
Stroke Limit Deadband
Stroke Limit Counter Limit
Stroke Limit Alarm Time L imit
Following the example, when the valve position value goes smaller than 2% (Stroke Limit Low) the
equipment will consider Stroke Limit reached and it will increment by 1 (one) the counter. While the
valve position value does not arise again for an upper value to 3% (Stroke Limit Low + Stroke Limit
Deadband) the equipment will continue understanding as one Stroke only, and it won't increment
the counter. If the valve position value increases to a larger value than 3% and goes down again to
2%, the pr ocess is repe ated and Strok e Limit counters are incremented again by 1 (one). In a
similar way, when the valve position goes up to 98% (Stroke Limit High), the Stroke Limit is reached,
and also the counter is incremented by 1 (one).
Still according to the exampl e, when the value of the Stroke Lim it counter reaches 10 (ten), the
equipment will generate an alarm (Stroke Limit Counter Alarm). Similarly, when the valve set stays
in Stroke Limit for a time ove r to 60.0 seco nds, an alarm of the e xceeded time will be generated
(Stroke Limit Alarm).
Maximum limit value for the valve travel, before being
considered Stroke Limit.
Minimum limit value for the valve travel, before being
considered Stroke Limit.
Dead zone on the Stroke Limit High and Low values.
Counter of the number of times in that the Stroke Limit was
reached.
Maximum value allowed to the Stroke Limit counter, before
generating an alarm.
Generated alarm when the counter of Stroke Limit exceeds
the Counter Limit.
Time when the first occurrence of Stroke Limit happened.
Time when the last occurrence of Stroke Limit happened.
Maximum value of time in Stroke Limit allowed, before
generating an alarm.
Alarm generated when the time in Stroke Limit exceeds the
Alarm Time Limit value.
Total operation time of the Stroke Limit diagnostic.
Total time the valve set was in Stroke Limit.
alue (%)
98%
2%
1%
10
60.0 second
3.4
Section 3 - Technical Characteristics
V
Reversals - Characterizes the situation when the valve movement direction (opening - closing).
Related parameters:
ParametersDescription
Dead zone of the reversal. If the change in direction is larger
Reversal Deadband
than the value of the dead zone, the equipment will assume it
as reversion.
Actuator ou Valve Reversal
Counters
Actuator ou Valve Reversal
Counter Limits
Actuator ou Valve Reversal
Counter Alarm
Actuator ou Valve Reversal
Counter First Activation
Actuator ou Valve Reversal
Counter Last Activation
Actuator ou Valve Reversal
Operation Time
Counter that shows the number of reversals of the equipment,
for valve or actuator, separately.
Maximum value of reversals allowed to the counter before
generating an alarm. Configuration for valve or actuator,
separately.
Alarm generated when the counter of Reversals exceeds the
respective Reversal Counter Limit value.
Time when the first Reversal happened.
Time in that the last occurrence of Reversal happened.
Total operation time of the Reversal diagnostic.
alue (%)
1%
5
5
For every change in direction when the displacement is larger than 1% (Reversal Deadband), the
positioner will consider it a reversal and it will increment the respective counters by 1 (one).
When the val ue of the cou nters (Reversal Counter Limit) reaches 5 (five), the positio ner will
generate the respective alarm (Reversal Counter Alarm) for the act uator and the va lve, given that
the reversal counters of th e actuator and that of the valve are independent. The reason for th e
counters to be independent, in spite of be ing increased together is that when maintenance is done
in just one of the set of elements, the respective counter can be zeroed by the user, independently
of the other.
MILEAGE
Valve Mileage - mileage or total travel of the valve and actuator. It can adopt percentage values, of
length units or angular units. It also has a limit value for an alarm to be generated (Mileage Limit
Alarm) when its value is exceeded.
Related parameters:
ParametersDescription
Dead zone inside which a displacement is not considered as
Mileage Deadband
movement in the Mileage count. This value is always
configured in percentage.
Actuator or valve mileage. It is the sum of the displacements
Actuator ou Valve Mileage
larger than the dead zone, executed by the respective
equipment.
Actuator ou Valve Mileage
Limit
Actuator ou Valve Mileage
Limit Alarm
Maximum value allowed to Mileage, before generating an
alarm.
Alarm generated when the respective Mileage exceeds the
Mileage Limit value.
Travel measurement of the valve-actuator set, in other words,
Travel Range
total travel in engineering units. The Mileage values of the
actuator are converted into engineering units starting from this
value.
Eng. Unit
Engineering Unit in which Travel Range and Mileage will be
visualized.
3.5
FY400 Hart – Operation, Maintenance and Instructions Manual
SUPPLY PRESSURE
The pressure diagnostic checks if the p ower supply pressure of the positioner is between the limits
configured by the user. This diagnostic have two limits, one lower and another upper limit that make
possible to check if the pressure is good or generate alarms of too l ow or too high pressure in the
positioner status (Supply Pressure Status).
For this diagnostic to work correctly it is necessary to use a positioner model that has
pressure sensors installed.
Related parameters:
ParametersDescription
Supply Pressure High Limit
Supply Pressure Low Limit
Supply Pressure Status
Supply Pressure Alarm Time
Limit
Supply Pressure Alarm
Supply Pressure Problem
Counter
Supply Pressure Problem First
Activation Time
Supply Pressure Problem Last
Activation Time
Supply Pressure Problem
Accumulated Time
Supply Pressure Problem
Operation Time
PST (Partial Stroke Test) & LOAD FACTOR
PST (Partial Stroke Test) - This diagnostics executes a test to ver ify if the va lve is not locked,
besides measuring the necessary pressure for the valve to move. Durin g its exec ution, the Load
Factor is calculated.
Related parameters:
ParametersDescription
PST Mode
PST Type
PST Offset
PST Pause
PST Timeout
PST Timeout Alarm
PST Breakout Value
PST Breakout Limit
PST Breakout Alarm
PST Cycle Time
PST SP Change Alarm
PST Aborted Alarm
Valve Spring Range
3.6
Upper value limit for the supply pressure.
Lower Value limits for the supply pressure.
Indicates the actual state of the supply pressure: too low, good
or too high.
Allowed time maximum value, for the power supply pressure to
be outside the limits before generating an alarm.
Alarm generated when the time when the pressure is out of
the limits exceed the value of the Alarm Time Limit.
Total (problems in the power supply pressure.
Time of the first occurrence of a problem in the supply
pressure.
Time of the last occurrence of a problem in the supply
pressure.
Accumulated time in which the supply pressure was out of the
limits: too low or too high.
Total time of operation of the diagnostic of Supply Pressure.
It configures the valve to be tested: safety or control type.
It configures the test as valve opening or closing, in the case
of a safety valve.
Percentage displacement value of the valve position for the
test.
Time awaited by the test, after the valve starts moving, to
return to the original position.
Maximum time a waited for the test to be executed entirely,
before generating an alarm.
Alarm generated when the test time exceeds the value of PST
Timeout.
Time elapsed for the valve to leave the inertia and begin its
movement.
Maximum time allowed for the PST Breakout Value, before
generating an alarm.
Alarm generated when the Breakout Value exceeds the PST
Breakout Limit value.
Period when the equipment will execute the PST automatically
(for manual PST, this parameter should be zero).
Alarm that indicates if the Setpoint was changed during the
PST execution. The result invalidates the test.
Alarm that indicates an error in the valve positioning before
beginning the PST. The result invalidates the test.
Spring range, for simple action valves. It can be calculated
automatically by the equipment or configured by the user.
Section 3 - Technical Characteristics
When the PST Mode is configured as safety valves, the PST should be executed starting from the
position 0%, in the case of a PST Type configured to open. Or then, 100%. If the PST Type was
configured to close.
Some checks are made during the test and can generate its cancellation and a respective alarm:
time of the test exceeds PST Timeout;
PST Breakout Value exceeds PST Breakout Limit;
the initial valve position doesn't correspond to the initial position configured for the test
to begin (for safety valves);
The Setpoint is altered during the test.
Load Factor - This diagnostics attributes the percentage of the press ure used to move the va lve
from one point to another, indicating a diagnostics related to the attrition of the valve. It is calculated
during the PST.
Related parameters:
ParametersDescription
Load Factor Value
Load Factor Limit
Load Factor Alarm
Load Factor First Calculation
Time
Load Factor Last Calculation
Time
Load Factor OperationTime
Value calculated for the Load Factor.
Maximum value allowed for the Load Factor, before generating
an alarm.
Alarm generated when the Load Factor Value exceeds the
value of the Load Factor Limit.
Time of the first Load Factor calculation.
Time of the last Load Factor calculation.
Total operation time of the Load Factor diagnostics.
DEVIATION
This diagnostics indicate if the pos ition error, in relation to the Setpoi nt is above th e maximum
defined by the user.
Related parameters:
ParametersDescription
Deviation Value
Deviation Deadband
Deviation Time
Deviation Counter
Deviation Counter Limit
Deviation Counter Alarm
Deviation Counter First
Activation Time
Deviation Counter Last
Activation Time
Deviation Counter
Accumulated Time
Deviation Alarm Time Limit
Deviation Alarm
Deviation Operation Time
Deviation Measured Value
Deviation Measured Time
Maximum deviation value allowed by the user.
Dead Zone in relation to the deviation value, used to avoid
that the same deviation is counted more than once.
Necessary time for a position error to be considered as a
deviation provided that it is above the Deviation Value.
Counter of the number of times when a Deviation occurred.
Maximum value allowed to the Deviation counter, before
generating an alarm.
Alarm generated when the Deviation Counter exceeds the
Counter Limit value.
Time when the first Deviation occurred.
Time when the last Deviation occurred.
Total time when the set was in Deviation.
Maximum time value allowed in Deviation, before generating
an alarm.
Alarm generated when the time in Deviation exceeds the
Alarm Time Limit value.
Total operation time of the Deviation diagnostics.
Deviation value when the time alarm is generated.
Deviation time when the time alarm is generated.
3.7
FY400 Hart – Operation, Maintenance and Instructions Manual
ALARMS
Besides the specific alarms of each diagnostics already mentioned, some additional alarms are also
present in status format, even after the setup or during the control process.
They are:
ParametersDescription
Temperature out of range
No movement or low air supply
Fail Hall
SP out of limits
Magnet not centralized
Piezo voltage out of range
Low current supply
GRAPHS
DEVIATION GRAPH
The travel deviation indicates the difference between the Setpoint and the valve position. The user
then can configure the tolerance of acceptable deviations for his process.
The Deviation Graph shows the deviation values along the time.
Related parameters:
ParametersDescription
Graph Operation Time
Device Total Operation Time
PST GRAPH
The Partial Stroke Test verifies the valve response to a certain course, together with the necessary
pressure to execute the movement. The PST Graph illustrates the valve opening and closing test
process to the positions configured by the user.
LOAD FACTOR GRAPH
The Load Factor indicates the total valve inherent attrition. The Load Factor Graph shows the Load
Factor values calculated along the time.
Related parameters:
Graph Operation Time
Device Total Operation Time
HISTOGRAM
The Histogram indicates the amount of tim e the valve stayed in a c ertain position. It shows the
positions in intervals of 5% and the time the valve stayed in each position when the diagnostic was
enabled.
Related parameters:
Histogram Operation Time
Device Total Operation Time
VALVE SIGNATURE
The Valve Signature is a graph that shows the equipment performance curve, in relation to the used
pressure, for the whole valve course, in the valve opening and closing. Therefore, in time the user
can analyze if the system is being degraded, as well as diagnose some problem with the actuatorvalve system.
Parameters Description
Parameters Description
Indicates that the temperature is out of the acceptable e
equipment limits.
Indicates that the valve is locked or that the air supply is
insufficient.
Indicates no-reading or a reading problem with the Hall-magnet
sensor set.
Indicates that the Setpoint is out of the range specified as
useful for the user.
Indicates that the magnet is not centralized with the valve
travel.
Indicates Piezo base voltage out of calibrated range, required
for the control. Refer to section 6, in item: Checking the Calibration of the Piezo Base Set, in this manual.
Indicates insufficient electric current to supply the equipment
circuits.
Indicates the graph operation time.
Indicates the total graph operation time.
Indicates the graph operation time.
Indicates the total positioner operation time.
Indicates the total Histogram operation time.
Indicates the total positioner operation time.
3.8
Section 4
In this section the “Magnetic Tool” will be referred to as “TOOL”, and the hole identified by “S” and “Z” will be
“HOLE S” and “HOLE Z”, respectively.
Local Adjustment
LOCAL PROGRAM M ING
The FY400 positioner has under the identification plate two shallow holes, where the magnetic tool
is placed to execute the local adjustment.
Figure 4.1 – Shallow holes for Local Adjustment/Configuration and Magnetic Tool
The holes identified with Z (Zero) and S (Span) will be indicated by (Z) and (S). The table shows the
action accomplished by the magnetic tool when inserted in (Z) and (S) according to the adjustment
selected.
ORIFICE ACTION
Z
S
The digital display is necessary to visualize the programming tree via local adjustment.
Moves between the functions.
Selects the display function.
Magnetic Tool
With the magnetic tool, it is possible to configure FY400 locally, eliminating the need of additional
configurators in many basic applications.
W1 and W2 Jumpers Connection
Write Protection
- W1 Jumper connected in OFF
If the W1 jumper is connected in OFF, the write protection is disabled.
- W1 Jumper connected in ON
If the W1 jumper is connected in ON, the write protection is enabled.
NOTE
4.1
FY400 Hart – Operation, Maintenance and Instructions Manual
Local Adjustment
LOCAL ADJUSTMENT
Disabled
Enabled
WRITE PROTECTION
Enabled
Disabled
Local Adjustment
- W2 Jumper connected in OFF
If the W2 jumper is connected in OFF and the local adjustment is disabled, the programming
tree parameters cannot be modified.
- W2 Jumper connected in ON
If the W2 jumper in ON and the local adjustment is enabled, the programming tree parameters
can be modified.
Write Protection
Figure 4.2 – Main Board
To configure the local adjustment, place the main board jumpers as indicated in the Figures 4.3 and
4.4.
Figure 4.3 and 4.4 – Local Adjustment Options
To configure the write protection, place the main board jumpers as indicated in the Figures 4.5 and
4.6.
4.2
Figure 4.5 and 4.6 – Write Protection Options
S
ACTION
ROTATIONZ
ManSETUP
DISPLAY
TuneSETUP
AutoSETUPFullSETUP
AirTo
CHAR
TYPE
Td
Tr
Td
Kp
TIME
TIME
SP %
SP %
MODE
ZZZ
Z
Z
Z
Z
Z
ZZZ
Z
Z
Z
Z
Z
Sind, Sinr, Doud, Dour
S
S
Linear, EP25, EP33, EP50
HY25, HY33, HY50, Tab
S
Auto, Man
S
Open, Close
LOPOS
Z
Z
LOPOS
Tr
Kp
ZZ
UPPOS
UPPOS
Z
Z
Z
Local Programming Tree
The programming tree is structured with menus of the main software functions.
Section 4 - Local Programming
With local adjustment enabled, it is possible to travel through all the configuration options
maintaining the magnetic tool in the hole marked with "Z". To select the option, after choosing the
option by the previous way, place the tool in the hole marked with "S".
By keeping the tool in “S” hole it is possible to continuously operate the selected parameter, since
this is a numeric value. Incrementing actions are performed by repeatedly placing and removing the
magnetic tool until reaching the desired value.
Do all changes and c onfigurations very carefully since all modifications in the parameters are recorded
automatically and do not need user confirmation to save the configuration.
Adjustable Parameters
FULL SETUP
Executes the AUTO SETUP and the AUTOTUNING for full valve adjustment, including the PID
control parameters.
SETUP
AUTO
During this adjustment, the positioner checks the 0% and 100% valve travel in relation to the
magnet and then calculates the AD converter gain for position readings.
AUTOTUNING
Performs the PID control tuning through automatic selection of the Kp, Tr and Td values.
MANUAL SETUP
Executes the AUTO SETUP steps but it needs user confirmation between steps.
Figure 4.7 – Local Programming Tree
NOTE
4.3
FY400 Hart – Operation, Maintenance and Instructions Manual
ner/actuator, because they may unexpectedly move
The user must confirm the current step conclusion only when the valve is not active. The steps are
described below:
Step 1: Valve closing to check the 0% position.
Step 2: Valve opening to check the 100% position.
Step 3: Valve closing to begin calculating the AD converter gain.
Step 4: Valve opening to end the calculation of the AD converter gain
The M ANUAL SETUP is recommended in cases where it is not possible to activate the AUTO SETUP due to
very unstable environment.
Do not touch the moving parts of the valve/positio
automatically.
TYPE – Valve Type
Through this parameter, the user configures the valve type and t he type of action associated to
valve.
See valve type options:
- Sind: Single action and Direct;
- Sinr: Single action and Reverse;
- Doud: Double action and Direct;
- Dour: Double action and Reverse.
CHAR - Characterization Curves
Through this parameter, the user configures the characterization curve of the valve.
See the existing options:
- Linear: linear
- EP25; EP33; EP50: equal percentage
- QO25; QO33; QO50: hyperbolic (quick opening)
- Tab: table of 16 points (configurable)
Allows choosing the mode in operation. When activating the positioner, it will be al ways in
automatic mode.
Operation Mode options:
- Auto - Automatic Mode
In the automatic mode, the position is adjusted according to the 4 to 20 mA current signal input.
This mode does not allow the local access to the SP% parameter.
- Man - Manual Mode
In the manual mode, the position is adjusted according to the SP% parameter value,
independently of the input current. Only this mode allows the operation in the SP% parameter.
SP % - Set Point
This parameter represents the desired position value. In the “Manual” mode, this parameter may be
operated remotely, independently from the input current. The desired value from the input current
level is calculated in the “Auto” mode.
LOPOS - Lower Position adjustment
This parameter allows the user to calibrate the desired lower position, associated to the input
current. This is also useful to calibrate the lower Split Range position.
UPPOS - Upper Position Adjustment
This parameter allows the user to calibrate the desired upper position, associated to the input
current. This is also useful to calibrate the upper Split Range position..
TIME - Setpoint Variation Time
Allows to configure the Setpoint variation rate by selecting the desired time for the valve open or
close. The unit is shown in seconds.
Kp - Proportional Gain
Allows to adjust the proportional gain of the digital PID control.
Tr - Integral Time
Allows to adjust the integral time of the digital PID control.
NOTE
NOTE
4.4
Section 4 - Local Programming
Td - Derivative Time
Allows to adjust the derivative time of the digital PID control.
AIRTO - Air to Open or Air to Close
This option allows to adjust the positioner according to the valve actuation. If the actuator works
with "air to open" or "air to close", the positioner should be c onfigured for AirTo OPEN or AirTo
CLOSE, respectively.
4.5
FY400 Hart – Operation, Maintenance and Instructions Manual
4.6
Section 5
In case of a multidrop network configuration for classified areas, the entity parameters allowed for the area
NOTE
CONFIGURATION VIA HART
The positioners may be connected in a point-to-point type or multidrop network. In a point-to-point
connection, the equipment must be on "0". In a multidrop network, once the devices are recognized
by their addresses, the positioners should be configured with a network address between "1" and
"15”.
If the acknowledgement is via tag, the positioners addresses may be on "0" and keep controlling the
valve, even in a multidrop configuration.
NOTE
must be strictly observed. Therefore, the following should be checked:
Ca
Voc
Where:
Ca, La =Allowed Capacitance and Inductance on the bus;
Ci
Cc, Lc = Cable capacitance and Inductance;
V
oc
I
sc
Vmax
Imax
The FY400 Smart Valve Positioner includes a wide variety of Hart
it possible to access whatever functionality implemented on it. These commands work according to
the Hart
Commands and Specific Commands.
Smar developed configurators for its Hart
Windows or HPC401 for Palms. It provides a simple configuration, field device monitoring, and
ability to analyze data and modify field device performance.
For the user's safety the FY400 has two kinds of write protection in its memory, one hardware and
the other a software mechanism. The hardware is selected by a H-H switch with priority over the
software (See in the Section 4, Local Programming).
≥ Σ
Cij + Cc La ≥ Σ Lij + Lc
≤
min [Vmaxj] Isc ≤ min [Imaxj]
, Lij = Non -protected internal Capacitance/Inductance of positioner j (j = up to 15);
j
= open circuit tension of the intrinsic safety barrier
= short circuit current of the intrinsic safety barrier
= Maximum allowable voltage to be applied to the positioner j;
j
= Maximum allowable current to be applied to the instrument j.
j
®
protocol specifications and are grouped as Universal Commands, Common Practice
®
devices: CONF401 configurator or DDCON100 for
®
®
command functions that makes
The operation and use characteristics of each one of the configurators are in their specific manual. Consult the
configurator updates and their manuals, on http://www.smar.com.
Figures below show the front of the Palm and the CONF401 screen with active advanced
configuration.
5.1
FY400 Hart – Operation, Maintenance and Instructions Manual
See the manual in the site http://www.smarresearch.com to configure.
Figure 5.3 – DDCON 100 - DDL Based HART Configurator
Configuration Resource s
By means of the Hart® configurator, the FY400 firmware allows the following configuration features
to be accessed; see below:
- Positioner Identification and Manufacturing Data;
- Remote Setpoint;
- Special valve characterization function according to a 16-point configurable curve;
- Flow characterization (Linear, Equal percentage and Quick opening);
- Monitoring of all device variables: position, setpoint, deviation and temperature;
- Positioner diagnostic, preventive maintenance and failure determination;
- PID Controller Configuration;
- Device Configuration;
- Device Maintenance.
The configurator can be connected to the same pair of wires as the 4-20 mA signal, up t o 2
kilometers away from the positioner.
Identification and Manufact uring Data
The following information about the FY400 manufacturing and identification data is available:
TAG
8-character alphanumeric field for identification of the positioner.
DESCRIPTION
16-character alphanumeric field for additional identification of the positioner. May be used to identify
service or location.
MESSAGE
32-character alphanumeric field for any other information, such as the name of the person who
made the last calibration, some special care to be taken, or if a ladder is needed for physical access
to the positioner.
5.3
FY400 Hart – Operation, Maintenance and Instructions Manual
NOTE
WRITE PROTECTION
W1 jumper
main boardis connected to the pins over the word ON or if the protection is enabled by software.
DATE
The date may be used to identify a relevant date, such as the last calibration, the next calibration or
the installation. The date is stored in the American standard e.g.: Oct 16, 2007) and is automatically
assumed after the choice of these items.
UNIQUE ID
Used to identify the device and in the construction of the Hart® long form address.
DEVICE INFORMATION
Allows to read the equipment identification data recorded in the factory.
These items related to EQUIPMENT INFORMATION, engraved in the factory cannot be modified. They are
read directly from the circuit memory.
Monitoring
This function allows remote monitoring of positioner variables. The time to start the reading is
around 5 seconds. The values are always updated. Among others, some of the variables that can
be monitored are: valve actual position in percentage, input in percentage of the adjusted current
range (before the flow limits and linearization), input current in mA or %, device temperature in
Celsius and in Fahrenheit degrees, etc.
Device Configuration
– The configurator only shows that the writing is authorized if the
NOTE
from
Besides the equipment configuration and operation services, the FY400 allows Auto Setup
(Calibration) and Auto Tuning. See below the configuration options:
- CHARACTERIZATION FUNCTION
This function can change valve flow characteristics. For example, if an equal percentage
flow characterization is applied to a valve with linear flow characteristics, it will work as an
equal percentage valve. Manufacturer documentation contains the valve inherent
characteristic. The options for flow characterization are:
The FY400 digital display has three well-defined fields: information field with icons
informing the active status of the configuration, 4 ½ numerical digit fields for value
indication and alphanumeric field with 5-digit for status information and units. The
parameters that can be selected for visualization are showed below:
PARAMETERS DESCRIPTION
PV % Process variable in percentage.
SP % Setpoint in percentage.
- TABLE CONFIGURATION
Through this button, a flow characterization curve with up to 16 points can be configured.
This allows the construction of a special flow characterization curve, like linear
combinations and equal percentage or other characterizations.
5.4
Section 5 – Hart® Configuration
7
6
5
Linear
Equal Percentage 1:25
1:33
1:50
Equal Percentage
Equal Percentage
Quick opening 1:25
1:33
1:50
Quick opening
Quick opening
2
1
3
4
OPENING
100
80
60
40
20
0
SP
10020
30
405060708090100
7
6
5
1
2
3
4
Advanced Configurati on
This function affects valve advanced configurations. With advanced configuration it is possible to
configure the valve type, if it is air-to-open or air-to-close, valve action, setpoint limits and split
range.
Device Maintenance
This group includes maintenance services related to obtaining necessary information for the device
maintenance and performance test. Some of the available services are: position adjustment and
valve performance test, general information about the actuator and t he valve, operations count,
password level, code number model, performance and others.
Trim
There are two trim operations: current trim and temperature trim. They are configured via HPC401
for Palms or Advanced Configuration via CONF401.
−CURRENT TRIM allows to check the positioner input current reading. There are two types of
current trims available:
−TEMPERATURE TRIM is the temperature reference for the positioner temperature sensor.
Automatic Configuration
This function allows to calibrate the valve travel automatically (Auto Setup and Auto Tuning), the
points of the totally opened or totally closed stroke with higher precision (lower and higher position),
to adjust the opening and closing times and the proportional, integral, and derivative actions of the
PID (Proportional, integral, derivative) control, the state of air supply, the magnet conditions, the
position sensor, setup and the piezo voltage conditions.
Setup Stages for FY400
(Full Setup, Auto Setup, Auto Tuning)
HALL
Sends the valve to the end of travel, open or closed, depending on mounting.
(0%, 0%, - )
GAIN
Verifies if the valve movements up to the other extremity and finds the A/D gain.
(5%, 25%, - )
Table 5.1 - Valve Characteristic Curve
4 mA TRIM: is used to adjust the input current reading correspondent to 0%.
20 mA TRIM: is used to adjust the input current reading correspondent to 100%.
5.5
FY400 Hart – Operation, Maintenance and Instructions Manual
SPAN
Calibrates the valve travel, with limit values for the position sensor.
(10%, 50%, - )
SAVE
Saves calibration data in FRAM memory.
(15%, 75%, -)
TIME
Finds opening and closing times for the valve.
(20%, 100%, -)
CNTRL
Starts Auto tuning in 50% position.
(25%, - , 0%)
TUNE1
Oscillates the system for PID parameters calculation.
(55%, - , 30%)
TUNE2
Oscillation values acquisition.
(60%, - , 35%)
WAIT
Beginning of PID parameters calculation.
(65%, - , 40%)
PARAM
Saves the calculated parameters and returns to the control at the setup end (calibration).
(100%, - , 98%)
Multidrop Configuration
ADDRESSING
FY400 contains a variable that defines the device address in a Hart® network. Hart® addresses
assume values from "0" to "15", the addresses "1" to "15" being specific addresses to multidrop
connection. When the FY400 is configured for multidrop, it means that the display is showing “MD”
and the address is a value from "1" to "15". FY400 is factory-configured with address "0".
Diagnostic
This function allows engineering unit configuration, the parameters for diagnostic purposes and
shows the positioner general conditions. Consult the “Section 3” for more details about the available
functions for the diagnostic.
Pressure Sensor
This function allows pressure trim adjustment for the positioners that have optional pressure sensor.
Besides visualize the status of the applied pressure and to configure the positioner input pressure in
order to activate the alarm via Hart® communication, if the applied input pressures are not in
accordance with the configured values.
Factory
This option is used only in the factory, and the user cannot access it.
5.6
Section 6
MAINTENANCE
General Information
Equipment installed in hazardou s atmospheres must be inspected in compliance with the IEC6 0079-17
standard.
As a guarantee of quality, the FY400 Valve Positioners are extensively tested and inspected before
delivery to the end user. Nevertheless, they were designed to provide an easy periodic cleaning and
repair, when necessary.
In general, it is recommended that the end user do not tr y to repair printed circuit boards. Instead,
replace the pieces and, for this, he sh ould have spare circuit boards, which may be ordered from
Smar whenever necessary. See list of recommended spare parts on page 7.3.
The maintenance procedure is a set of tech niques with the purpose of keeping the positioners with
higher useful life, to operate in safe conditions and to promote costs reduction. The different types of
maintenance are described during this section.
The positioner should be disassembled and undergo cleaning procedures, every time the fina l
element of control is subject to maintenance.
FY400 Corrective Maintenance
Unplanned maintenance intends to locate and repair malfunction in the positioners or final elements
of control operating in continuous work, or, specifically to suppress already existing defects.
Diagnostics are a set of methods to det ect, to locate and eventually to correct errors and problems
or even verify failures in the final element of control and in the positioner.
FY400 Diagnostics without Configurator
In order to carry out the diagnostics, refer to Table 6.1.
SYMPTOM SOURCE / SOLUTION
Power Supply must be a current source
Check input signal current. Minimum current for positioner operation is 3.8
POSITION NOT ON DISPLAY
NO RESPONSE FOR THE
INPUT SIGNAL
OSCILLATING ACTUATOR
SLOW ACTUATOR
RESPONSE
ACTUATOR RESPONDS
TOO FAST
mA.
Electronic Circuit Failure
Check the boar ds for malfunctions and replace faulty boards for spare
ones.
Pressure Output Connections
Check for air leakeage.
Air Supply Pressure
Check the air supply pressure. Input pressure to the FY400 must be
Refer to t he procedures described in this Manual: OUTPUT
CONNECTION and RESTRICTION CLEANING.
Calibration
Adjust tuning parameters.
Adjustment Parameters are Too Low
Adjust tuning parameters.
Adjustment Parameters are too High
Adjust tuning parameters.
Table 6.1 - FY400 Diagnostics Without Configurator
NOTE
6.1
FY400 Hart – Operation, Maintenance and Instructions Manual
FY400 Diagnostics with Configurator
If the position er is on and with the com munication circuit and the p rocessing unit working, the
configurator can be use d for dia gnostics. The configurator should be co nnected to the positio ner
according to the wiring diagram showed on page 1.8.
Error Messages
The error messages inform which diagnostics were found through errors and m alfunctioning selfdiagnosing. When the configurator is communicating with the positioner, the user is informed on any
problem found, through the self-diagnosis. At t he FY400 positioner, the error messages always
alternate with the information on the top li ne of t he configurator display. The table list s the error
messages and more details on the corrective action.
STATUS POTENTIAL SOURCE
PARITY ERROR
OVERRUN ERROR
CHECK SUM ERROR
FRAMING ERROR
BUSY LINE
CMD NOT IMPLEMENTED
BUSY DEVICE
POSITIONER MALFUNCTION
COLD START-UP
FIXED OUTPUT
NO RESPONSE
Excessive noise or ripple in the line.
Low level signal.
damaged Interface
Power supply or battery voltage of the configurator lower than 9 V.
Other device using the line.
Software version not compatible between configurator and positioner.
Positioner carrying out an important task, e.g., local adjustment.
Disconnected Transducer.
Transducer with damage.
Stuck valve.
Start-up or power supply failure.
Operating in local mode with fixed position.
Positioner line resistance is not according to technical characteristics.
Positioner without power supply.
Interface disconnected or damaged.
Positioner configured in multidrop mode being accessed by
Interface damaged.
Power supply or battery voltage of the configurator lower than 9 V.
Table 6.2 – FY400 Diagnostics with the Configurator
Disassembly Procedure for Maintenance
1. Apply air pressure in the positioner inlet, without applying power supply. Verify if there is any air
leakage in output 1 (OUT1). In case of air leakage in outlet 1, remove power supply and check
the mechanical parts.
2. Remove the base restriction, without disassembling the transducer. Verify if the restriction is not
obstructed. (See Restriction Cleaning Procedure, page 6.11).
Have the following tools at hands:
- Allen Key
- Screwdriver
Disassemble the equipment as shown:
Removal of the Electronic Housing Transducer
Follow correctly the disassemble steps, avoiding damaged parts or equipment.
1. Disconnect the electrical connections (on the side marked: FIELD TERMINALS);
2. Remove the cover. It has a cover locking screw that needs to be rotated in a clockwise
direction to be loosened. By reversing the process the cover will be locked. See figure 6.1.
6.2
ON_LINE_ÚNICO_INSTR.
IMPORTANT
Section 6 - Maintenance
L
O
S
P
I
X
E
N
I
W
-
T
H
N
G
I
O
T
I
T
P
U
E
A
E
C
K
M
C
A
U
N
I
D
T
A
E
D
N
O
H
A
-
E
M
A
A
P
T
E
R
T
A
V
E
N
E
H
M
O
S
D
O
A
C
T
I
R
M
C
O
U
I
S
T
P
H
A
E
L
R
I
V
E
E
O
A
V
D
I
A
S
Z
I
O
L
G
P
R
X
E
E
N
A
E
R
E
F
O
D
N
A
U
Q
COVER LOCKING
SCREW
Figure 6.1 – Cover locking screw
3. Release the two screws that tighten the main board, to remove the main board and the housing
display.
4. Disconnect the power supply cable a nd the main board flat cable (It ha s two lockers, release
them to disconnect both cables easily).
Figure 6.2 – Disconnecting the main board cables
6.3
FY400 Hart – Operation, Maintenance and Instructions Manual
5. Loosen the housing rotation locking screw (rotating in a counterclockwise direction).
Not rotate the housing without loosening the rotary locking screw, because that can damage the housing
thread and consequently it will need to be changed.
IMPORTANT
S
O
M
T
T
I
A
U
C
R
E
I
V
C
I
S
N
O
L
E
P
H
X
W
E
T
H
N
I
G
I
-
N
O
D
E
R
E
E
H
V
P
I
L
A
T
P
O
E
I
E
T
K
U
A
C
A
Z
I
A
V
G
I
R
S
O
E
L
N
P
E
X
E
O
D
A
N
R
A
E
U
F
Q
S
O
O
M
D
T
A
A
T
R
M
E
E
P
-
A
O
D
A
A
H
D
I
N
U
E
C
T
N
A
M
HOUSING ROTATION
ADJUSTING SCREW
Figure 6.3 – Housing rotary locking screw
IMPORTANT
Do not rotate the electronic housing more than 270° without disconnecting the electronic circuit from the power
supply.
Figure 6.4 – Transducer rotation
Loosen carefully the electronic cover of the transduc er without twisting the flat cabl e. Remove the
housing transducer, rotating them in opposite directions and loosening the housing internal lock at
each turn.
6.4
Section 6 - Maintenance
A
A
k
Figure 6.5 – Disassembled housing with disconnected transducer
Disassembled Transducer
1. Remove anticlockwise the Allen screws that fix th e assembled connection cover (this part
cannot be washed).
IMPORTANT
Before loosening the assembled connection cover, remove the position sensor cover, at the other positioner
end. See the indicated parts in the figure below or in the drawing exploded view.
ssembled Bloc
Assembled
Connection Cover
nalog Board
2. Remove, with care, the asse mbled connection cover not to damage the main electronic circuit
board with the flat cable, because it is fragile (this part cannot be washed); See figures below:
Assembled Base
Figure 6.6 – Disassembled connection cover
Restriction
Position Sensor
Cover
6.5
FY400 Hart – Operation, Maintenance and Instructions Manual
Figure 6.7 – Loosening the Assembled Base Connection
Cover
3. Remove, with care, the main electronic circuit board, which is firmly fitted. Remove and inspect
it for damages (oxidation, etc); See figures below:
Figure 6.8 – Loosened Connection Cover
Figure 6.9 – Removing the connection cover main board Figure 6.10 – Main board loosened from the assembled base
4. Remove the flat cable from the main board. Pull the lock that fixes the position sensor to the
main circuit board, and this will loose easily. Check if the p osition sensor flat ca ble is no t
twisted, broken or oxidized, etc; See figures below:
6.6
Section 6 - Maintenance
Figure 6.11 – Pulling, with the nail, the lock that fixes the
flat cable to the main board
5. Remove the transd ucer. This part cann ot be washed It is calibrated from the factor y and is
protected with a sealing wax to avoid inadequate handling. The re-calibration can be made by
the user, see the item: Check the calibration of the piezo base set.
6. Remove the t ransducer restriction. Check if it is not blocked, see: Restriction Cleaning
Procedure.
7. Remove the diaphragm set. Check visually if the diaphragm is not damaged, with small holes or
sealing failures. Wash the parts of the diaphragm set carefully with water and neutral detergent;
then wash it with alcohol and dry well before assembling.
8. Remove the spool valve. T his spool va lve moves against a spring l ocated in the s pool valve
conditioning hole; take care when handling the block so that the spool valve spring isn’t lost
during the cleaning procedure, it is very small. Wash the spool valve with water and neutral
detergent and then with alcohol and dry the part well before re-assembling it in the pneumatic
block. This part should be set up without any lubrication.
9. Remove the position sensor cover (or trans ducer) carefully not to damage the flat ca ble (the
four screws must be rem oved when disassembling the transducer block). Inspect the part
visually, for in dications of h umidity infiltration or other fo reign element. This part cannot b e
washed.
10. Remove the hall effect position sensor with the flat cable.
11. The pneumatic block can be washed in water and neutral detergent, and then with alcohol. Be
careful not to lose the small spool valve. Blow dry compressed air in all hoses to clean any dirt.
Figure 6.12 - Flat Cable loosened from the connector
6.7
FY400 Hart – Operation, Maintenance and Instructions Manual
Figure 6.13 – Disassembled FY400
Checking the Piezo Base Set Calibration
A good FY400 performing depends on the Piezo Base calibration integrity. Due to its continuous use
is expected a small variation on the piezo work voltage. If the piezo work voltage is close to 30 V or
70 V, this may be an indication the Piezo Base needs to be recalibrated soon.
Using the Hand-Held configurator, its possible re ad the pi ezo work voltage. This should be do ne
periodically. Additionally, the FY400 monitors the piezo work voltage at intervals defined by user. By
using the CONF401 application the user can observe a graph (see Figure 6.13a) which shows the
calibration deviation trend.
Figure 6.13a – Characteristic – Piezo Voltage Trend Graph
More information on the Calibration Procedure, r efers to the F YCAL manual (Calibration Device f or Pressure
Transducer) by visiting our web page on the Internet: http://www.smar.com.
6.8
ATTENTION
1. Assemble the base in the FYCAL according to the figure 6.14:
Section 6 - Maintenance
Figure 6.14 – FYCAL – Piezoelectric calibration
6.9
FY400 Hart – Operation, Maintenance and Instructions Manual
2. Assemble the piezoelectric sensor on the jig, by tightening the four screws to ensure good
sealing.
CALIBRATION TABLE FOR FYCAL
A B C
Input Pressure (psi) Power Supply (Vdc) Pilot Pressure (psi)
20 40 7.5 to 8.5
40 40 12 to 13
60 40 16 to 17
80 40 20 to 21
100 40 24 to 25
Table 6.3 – FYCAL Calibration Table
3. Apply the appropriate (psi) input pressure – As column A;
4. According to the calibration table above, apply 40 DC Volts to th e piezoelectric sensor
(independently from the input pressure applied). With the calibration tool, turn carefully the piezo
position on the base, to get the corresponding pilot pressure on the gauge. The pilot pressure
measured on the gauge corresponds to the pilot pressure values (psi) indicated in column C in
the FYCAL calibration table.
Example: When applying 40 DC volts to the piezoelectric sensor, for an input pressure of 60 psi,
result must be a pressure between 16 to 17 psi in the pilot chamber.
5. In case the value for the pilot pressure is not a value defined in the FYCAL calibration table (as
per the Column C), adjust th e upper disk o f the piezoelectric sensor set by turning it with the
appropriate tool. Repeat the calibration procedure to obtain the v alues for the pilot p ressure
defined in Table 6.3, as expected for the required range.
After calibrating the pi ezoelectric sensor, c heck the p ositioner. Then assemble and setup th e
positioner.
If the positioner is checked while assembled with all its electronic components, the FYCAL 4 to 20
mA output may be used to power the positioner.
The FYCAL may also be used as power supply for any Smar Hart line product, as it generates a 4
to 20 mA current.
Maintenance - Mechanical Parts
1. Verify if the spool valve (28) is moving freely.
2. Verify if the spool valve is not obstructed with dirty (28).
Never use oil or grease to lubricate the spool valve; otherwise the positioner performance will be impaired.
3. Verify if there is any obstruction inside the FY pneumatic block (19 to 35) and at the exhausts.
4. Verify the diaphragm (26) integrity.
5. Verify if the transducer block (base) (24) is dirty with oil, water, etc.
6. Verify if the restriction (20) is dirty. See Restriction Cleaning Procedure.
ATTENTION
6.10
Maintenance – Electronic Parts
Electronic Circuit
The numbers indicated between parentheses refer to exploded view figure.
To remove the main board (5) and the display (4) of the circuit, first release the cover locking screw
(6) from the side not marked "Field Terminals", and after that release the cover (1).
The circuit boards have CMOS components that can be damaged by electrostatic discharges. Verify the correct
procedures to manipulate CMOS components. Also it is recommended to store the circuit boards in packings
with electrostatic load proof.
Release the two screws (3) that fix the main board and display.
Assembly the device in a valve to test it i nside a laboratory. Apply power pressure according to the
pressure of t he actuator that is being used and power on the equipment with a v ariable power
supply from 4 to 20 mA. If the device does not initialize, i.e., the display does not light on, proceed
with the following procedures:
1. Disconnect the main board from the m ain electronic circuit board, disconnecting the flat cable
connector in the housing;
2. Case the equipment initializes, change the main electronic circuit board (GLL1315) (18 - part
number 400-0914). If it does not, change the main board (GLL1314) (5 - part number 400-0909).
Proceed with full setup. After the s etup, verify if the positioner is working properly. For that, apply
12mA and be sure that the valve goes to the position correspondent to the 50% of the valve travel. If
it does not occur, do the following:
1. Apply 4 mA and verify through the configurator if SP% is equal to 0%;
2. Apply 20 mA and verify through the configurator if SP% is equal to 100%;
3. If the values above were different, execute the 4 mA and 20 mA current trim.
Via software HPC401 for Palms or CONF401 it is possible to execute the CURRENT TRIM that allows to
calibrate the positioner input current reading. There are two types of current trims available:
4 mA TRIM: is used to adjust the input current reading correspondent to 0%.
20 mA TRIM: is used to adjust the input current reading correspondent to 100%.
4. Verify the Hall-effect position sensor reading through the configurator. Apply pressure directly to
the valve actuator and check the Ha ll reading (65000 means that the hall is not being read).
Case there is no cha nge at the Hal l reading or th e value is 6 5000, the d efect can be the
GLL1314 (5 - part number 400-0909), GLL1315 (18 - part number 400-0914), GLL1316; or Hall
flat cable (GLL1019);
5. Verify the piezo base/transducer voltage in the configurator;
6. The piezo base/transducer voltage value must be between 30 and 70 Volts.
To verify the hall value and the piezo base/transducer voltage, do the following:
1. Set the valve in 50% of the opening or closing travel;
2. With the configurator, go to th e “monitoring” mode and choose two parameters: Hall value and
piezo voltage;
3. The hall values must be between 28000 a 37000;
Section 6 - Maintenance
NOTE
ATTENTION
NOTE
6.11
FY400 Hart – Operation, Maintenance and Instructions Manual
4. The Voltage values of the base or piezo transducer should be between 30 and 70 Volts. If the
tension is not among those values, to proceed to the piezo calibration using the FYCAL checking
and calibration device for Sm ar valve positioner, see item: Calibration Checking of th e Piezo
Base Set.
FY400 Preventive Maintenance
Planned Maintenance consists of a set of p rocedures and anticipated actions to keep t he device
functioning, in other words, mainly to prevent failures, through adjustments, proves and measures
according to previously specified values. The preventive maintenance is rec ommended in t he
maximum period of one (1) year, or when the process stops.
Restriction Cleaning Procedure
The instrument air flows to the nozzle through a restriction. From time to time the restriction must be
cleaned to assure good performance to the positioner.
1. Disable the positioner power supply and disconnect the instrument air pressure;
2. With an appropriate screwdriver remove the restriction screw;
3. Remove the o-ring’s with an appropriate tool;
4. Wash the part with water and neutral detergent and dry it with compressed air (apply the
compressed air directly to the smaller orifice for the air to get out through the bigger hole).
5. Insert the cl eaning needle (PN 400-0726) into the restriction hole to prevent any possible
obstructions;
6.12
Figure 6.15 – Removing the Restriction Screw
Figure 6.16 - Restriction and Restriction
Cleaning Needle
6. Mount the o-rings again and screw the restriction in the positioner;
7. The equipment can be supplied with air again.
Change of the Filters Elements
Change the positioner filter elements with a minimum stated period of 1 (one) year (See exploded
view figure (27)). The air supply must be clean, dry and non-corrosive, according standards set by
the American National Standard “Quality Standard for Instrument Air" - ANSI/ISA S7.0.01 - 1996. If
the instrumentation air does not c omply with the above mentioned standards, the user should
consider changing the positioner filter elements more frequently.
The Filtering Element has two threaded Stainless Steel mechanical parts. Inside them is the Filter Element with
an o-ring.
How to disassemble the Filtering Element?
Firstly, remove the air filter set of the positioner (See exploded view figure (30)) and then unthread
the two mechanical parts. Refer to the drawing exploded view (27) to identify the Filtering Element
that is between the two mechanical parts of the dismounted air filter.
EXHAUST OUTLETS
Air is vented to the atmosphere through an outlet located beside the restriction and 4 outlets on the
opposite side to the gauge. A foreign object interfering or blocking exhaust port provides a way to
increase the output. Cleaning by spraying it with a solvent.
Never use oil or grease to lubricate the spool valve, otherwise the positioner performance will be impaired.
Section 6 - Maintenance
Figure 6.17 - Cleaning Procedure
ATTENTION
ATTENTION
6.13
FY400 Hart – Operation, Maintenance and Instructions Manual
6.14
Section 7
Package Content
SPARE PARTS AND MATERIALS
Verify the package content. The items marked with (*) must be in accordance with the number of
positioners supplied.
FY400 Hart – Operation, Maintenance and Instructions Manual
Exploded View
4
5
6
7
8
9
6
1
2
3
14
10
11
12
13
16
25
15
17
18
19
20
21
22
23
24
26
27
28
29
30
31
23
32
19
33
34
35
36
37
38
7.2
Figure 7.1 – Exploded View
Section 7 – Spare Parts and Materials
Accessories
ACCESSORIES
ORDERING CODE DESCRIPTIONS
SD-1 Magnetic tool for configuration via local adjustment.
HPC401* PalmOS Platform, including the HPC401.installation and initialization software.
HPI311 Hart® Interface.
400-0726 Restriction Cleaning needle.
400-1176 Teflon guide for linear magnet.
400-1177 Teflon guide for rotary magnet.
* For updates of the HPC401 equipment and software, visit: http://www.smarresearch.com.
Spare Parts List
SPARE PARTS LIST
PARTS DESCRIPTION POSITION CODE
Cover with Display (O-ring included)
Cover o-ring (with and without display) NOTE 1
Main Board screw
Digital Display - includes fixation screws
Main Board
Cover locking screw
Housing Rotation Locking Screw, 316 Stainless Steel
Identification Plate screw
Housing, Aluminum (NOTE 2)
Housing, 316 Stainless Steel (NOTE 2)
Toothed Communication Terminal and Terminal Screw
Internal ground screw and square washer
Note 1 - The O-rings are packaged with 12 units.
Note 2 - Includes terminal isolator, screws (cover lock, ground and terminal isolator) and identification plate without certification.
Note 3 - Includes all transducer spare parts.
Note 4 - For category A it is recommended to keep in stock a set for each 25 parts installed and a set for each 50 for category B.
Note 5 - The pressure gages for in-let, output 1 or output 2 pressures, will be supplied with the brass.wet parts.
CATEGORY
(NOTE 4)
A
A
-
906"
Ugevkqp"9"⁄"Urctg"Rctvu"cpf"Ocvgtkcnu"
A
Qtfgtkpi"Eqfg"
MODEL
FY400 INTELLIGENT VALVE POSITIONER
COD Communication Protocol
H HART® & 4 to 20 mA
COD Safety Options
0 Standard – For use in measurement and control
COD Local display
1 With local display
COD Mounting Bracket
1 W ith mounting bracket
COD Electrical Connections
0 1/2" - 14 NPT
A M20 X 1.5
B PG 13.5 DIN
COD Type of Actuator
1 Rotary - Single Action 8 Linear up to 100 mm - Double Action
2 Rotary - Double Action
5 Linear up to 50 mm - Single Action B Linear up to 30 mm - Double Action
6 Linear up to 50 mm - Double Action
7 Linear up to 100 mm - Single Action
COD Indication Gage
0Without Gage 4 With 2 Gages - Output 1 and 2
1With 1 Gage - Input 5 W ith 3 Gages
2With 1 Gage - Output 1 Z Others - Specify
3With 2 Gages - Input and Output 1
COD Certification Type
DExplosion Proof I Intrinsic Safety
GExplosion Proof + Increased Safety N Without Certification
CODCertifying Body
0Without
5CEPEL: Ex-d, Ex-ia, Ex-dem, IP
SPECIAL OPTIONS (Leave it blank for no optional items)
COD Housing
H0Aluminum Housing (IP/Type)
H1316 SST Housing (IP/Type)
H2Aluminum Housing for saline atmosphere (IPW/Type X) (1)
H3316 SST Housing for saline atmosphere (IPW/Type X) (1)
COD Painting
P0Gray Munsell N 6.5 Polyester
P8Without Painting
P9Safety Blue Epoxy – Electrostatic Painting
PDSafety Blue Polyesters – Electrostatic Painting
PHSpecial Painting
ROIntegral Mounting
R1 Remote Sensor - 5 m Cable
R2Remote Sensor - 10 m Cable
R3Remote Sensor - 15 m Cable
R4Remote Sensor - 20 m Cable
R5 Feedback 4 to 20 mA - 5 m Cable (2)
R6 Feedback 4 to 20 mA - 10 m Cable (2)
R7 Feedback 4 to 20 mA - 15 m Cable (2)
R8 Feedback 4 to 20 mA - 20 m Cable (2)
COD Special Sensor
K0Without Pressure Sensors
K1W ith Pressure Sensors for air Input and Output
COD Optional Items
ZZLeave it blank for no optional items
FY400 - H 0 - 1 1 - 0 6 5 N 0
(1) IPW/TYPEX tested for 200 hours according to NBR 8094 / ASTM B 117 standard.
(2) Consult Smar for applications in hazardous areas. See note for mounting bracket on BFY ordering code.
Universal Rotary
Universal Linear - Yoke and Pillar Type
2
Linear - Yoke Type
3
Linear - Pillar Type
4
Others - Specify
Z
CODEMagnet Mounting Bracket
0
Without Mounting Bracket
1
Rotary
Linear up to 30 mm
2
Linear up to 50 mm
3
Linear up to 100 mm
4
Others - Specify
Z
COD. Positioner Mounting Bracket Material
7
Carbon Steel Bracket and Accessories in SST
Carbon Steel Bracket
C
Stainless Steel Bracket
I
Not applicable
N
Others - Specify
Z
COD. Magnet Bracket Material
Carbon Steel Bracket
C
Stainless Steel Bracket
I
Not applicable
N
Others - Specify
Z
COD. Optional Items
ZZ Leave it blank for no optional items
BFY - 1 0 7 C . * TYPICAL MODEL NUMBER
(1) Consult www.smar.com for customized mounting bracket.
(2) When choosing the remote sensor version, an additional “L” shape bracket is included for 2” tube mounting.
NOTES
908"
Appendix A
Basic
Standard
Performance
Criteria
CERTIFICATIONS INFORMATION
This appendix covers all the information related to the certificates for this equipment. Its content was
generated by the Smar Certification Team.
European Directive Information
European Directive Information
Authorized representative in European Community.
Smar Gmbh-Rheingaustrasse 9-55545 Bad Kreuzanach
This product complies with following European Directive:
EMC Directive (2004/108/EC) –“Electromagnetic Compatibility”
The EMC test was performed according to IEC standard: IEC61326-1:2005 and IEC61326-2-3:2006
Tests performed using twisted pair wire.
If using shielded cable, keep the shield insulated at the instrument side, connecting the other one to
the ground.
Immunity test requirements for equipment intended for use in industrial locations.
(Table 2, clause 6, IEC61326-1:2005)
PORT Phenomenon
Electrostastic discharge
Enclosure
Rated power frequency
I/o signal
/control
Emission requirements (clause 7, IEC61326-1:2005).
According to the standards: CISPR11, IEC61000-3-2, IEC61000-3-3
PORT TEST Standard Frequency Range Test Value
DC supply
Conducted
Emission
(ESD)
EM Field IEC61000-4-3
magnetic field
Burst IEC61000-4-4 1KV(5/50nS, 5KHz) B
Surge IEC61000-4-5 1KV (line to ground) B
Conducted RF IEC61000-4-6 3V (150KHz to 80MHz) A
IEC 61000-3-2
IEC 61000-3-3
CISPR11
Class A
IEC61000-4-2 6KV/8KV contact/air B
IEC61000-4-8 30A/m A
0 to 2KHz (not apply for transmitters)
150KHz to 500KHz 79dB(μv) QP, 66dB(μV) AV
500KHz to 5MHz 73dB(μV) QP, 60dB(μV) AV
5MHz to 30 MHz 73B(μV) QP, 60dB(μV) AV
Test Value
10V/m (80 to 1GHz)
3V /m (1,4GHz to 2GHz)
A
Housing
ATEX Directive (94/9/EC) – “Electrical equipment and protective system intended for use in
potential explosive atmospheres”
According to the standards: IEC60079-0:2006, IEC60079-1:2007, IEC60079-7:2001, IEC6007911:2007, IEC60079-15:2005
Notified body Nemko for QAM and QAR number CE0470
(Certification in process, declaration not issued yet )
LVD Directive 2006/95/EC – “Electrical Equipment designed for use within certain voltage
limits “ According the LVD directive Annex II the equipment under ATEX “Electrical equipment for
use in an explosive atmosphere” directive are excluded from scope from this directive.
For additional information access EST-DE-0063-10.
(Product excluded from scope, not require declaration)
Radiated
Emission
CISPR11
Class A
30MHz to 230 MHz 40dB(μV) QP (A=10m)
230MHz to 1000MHz 47dB(μV) QP (A=10m)
A.1
FY400 – Operation, Maintenance and Instructions Manual
Hazardous Locations Approvals
Warning: Explosions could result in death or serious injury, besides financial damage.
Installation of this instrument in an explosive environment must be in accordance with the national
standards and according to the local environmental protection method. Before proceeding with the
installation check the certificate parameters according to the environmental classification.
Notes:
Ingress Protection (IP)
Ingress protection (IP W): Supplementary letter W meaning special condition defined as
default by Smar the following: Saline Environment approved - salt spray exposed for 200
hours at 35ºC.
(Ref: IEC60529)
Ingress protection (Type X): Supplementary letter X meaning special condition defined as
default by Smar the following: Saline Environment approved - salt spray exposed for 200
hours at 35ºC.
(Ref: NEMA 250)
Marking Label
Once a device labeled with multiple approval types is installed, do not reinstall it using any other
approval types. Scratch off or mark unused approval types on the approval label.
Maintenance and Repair
The instrument modification or replaced parts supplied by any other supplier than authorized
representative of Smar Equipamentos Industriais Ltda is prohibited and will void the Certification.
For Ex-d protection application
Only use Explosion Proof/Flameproof certified Plugs, Adapters and Cable glands.
As the instrument is non-ignition capable under normal conditions, the statement “Seal Not
Required” could be applied for Explosion Proof version regarding to conduits connection.
(CSA Approved)
In an Explosion-Proof/ Flame-Proof installation, do not remove the instrument housing covers
when powered on.
Electrical Connection
In Explosion-Proof installations the cable entries must be connected or closed using metal
cable gland and metal blanking plug, both with at least IP66 and Ex-d certification. The
unused cable entries should be plugged and sealed accordingly to avoid humidity entering,
which can cause the loss of the product’s warranty. For water-proof applications all NPT
thread parts apply the proper water-proof sealant. (A non-hardening silicone group sealant is
recommended).
For Ex-i protection application
Connect the instrument to a proper intrinsically safe barrier.
Check the intrinsically safe parameters involving the barrier, equipment including the cable
and connections.
Associated apparatus ground bus shall be insulated from panels and mounting enclosures.
When using shielded cable, isolate the not grounded cable end.
Cable capacitance and inductance plus Ci and Li must be smaller than Co and Lo of the
For warranty or non-warranty repair, please contact your representative.
Further information about address and contacts can be found on www.smar.com/contactus.asp.
SRF – Service Request Form
FY Positioner
GENERAL DATA
FINAL CONTROL ELEMENT DATA
AIR SUPPLY
PROCESS DATA
SITUATION DESCRIPTION
SERVICE SUGGESTION
USER INFORMATION
B.1
FY400 - Operation, Maintenance and Instructions Manual
Returning Materials
If necessary to return the converter and/or configurator to SMAR, simpl y contact our office,
informing the defective instrument serial number, and return it to our factory.
In order to speed up analysis and solution of the problem, the defective item should be returned with
a description of the failure observed, with as much details as possible. Other information concerning
the instrument operation, such as service and process conditions, is also helpful.
Instruments returned or to b e revised outside the guarantee term sho uld be accompanied by a
purchase order or a quote request.
B.2
Appendix C
SMAR WARRANTY CERTIFICATE
1. SMAR guarantees its products for a period of 24 (twenty four) months, starting on the day of
issuance of the invoice. The guarantee is valid regardless of the day that the product was
installed.
2. SMAR products are guaranteed against any defect originating from manufacturing, mounting,
whether of a m aterial or manpower nature, provided that the technical analysis reveals the
existence of a quality failure liable to be classified under the meaning of the word, duly verified
by the technical team within the warranty terms.
3. Exceptions are proven cases of inappropriate use, wrong handling or lack of basic maintenance
compliant to the equipment manual provisions. SMAR does not guarantee any defect or
damage caused by an uncontrolled situation, including but not limited to negligence, user
imprudence or negligence, natural forces, wars or civil unrest, accidents, inadequate
transportation or packaging due to the user’s responsibility, defects caused by fire, theft or stray
shipment, improper electric voltage or power source connection, electric surges, violations,
modifications not described on the instructions manual, and/or if the serial number was altered
or removed, substitution of parts, adjustments or repairs carried out by non-authorized
personnel; inappropriate product use and/or application that cause corrosion, risks or
deformation on the product, damages on parts or components, inadequate cleaning with
incompatible chemical products, solvent and abrasive products incompatible with construction
materials, chemical or electrolytic influences, parts and components susceptible to decay from
regular use, use of equipment beyond operational limits (temperature, humidity, etc.) according
to the instructions manual. In addition, this Warranty Certificate excludes expenses with
transportation, freight, insurance, all of which are the customer’s responsibility.
4. For warranty or non-warranty repair, please contact your representative.
Further information about address and contacts can be found onwww.smar.com/contactus.asp
5. In cases needing technical assistance at the customer’s facilities during the warranty period,
the hours effectively worked will not be bi lled, although SMAR shall be r eimbursed from the
service technician’s transportation, meals and lodging expenses, as well dismounting/mounting
costs, if any.
6. The repair and/or substitution of defective parts do not extend, under any circumstance, the
original warranty term, unless this extension is granted and communicated in writing by SMAR.
7. No Collaborator, Representative or any third party has the right, on SMAR’s behalf, to grant
warranty or assume some responsibility for SMAR products. If any warranty would be granted
or assumed without SMAR’s written consent, it will be declared void beforehand.
8. Cases of Extended Warranty acquisition must be negotiated with and documented by SMAR.
9. If necessary to return the equipment or product for repair or analysis, contact us.
See item 4.
10. In cases of repair or analysis, the customer must fill out the Revision Requisition Form (FSR)
included in the instructions manual, which contains details on the failure observed on the field,
the circumstances it occurred, in addition to information on the installation site and process
conditions. Equipments and products excluded from the warranty clauses must be approved by
the client prior to the service execution.
11. In cases of repairs, the client shall be responsible for the proper product packaging and SMAR
will not cover any damage occurred in shipment.
C.1
FY400 - Operation, Maintenance and Instructions Manual
12. In cases of repairs under warranty, recall or outside warranty, the client is responsible for the
correct packaging and packing and SMAR shall not cover any damage caused during
transportation. Service expenses or any costs related to installing and uninstalling the product
are the client´s sole responsibility and SMAR does not assume any accountability before the
buyer.
13. It is the customer’s responsibility to clean and decontaminate products and accessories prior to
shipping them for repair, and SMAR and its dealer reserve themselves the right to refuse the
service in cases not compliant to those conditions. It is the customer’s responsibility to tell
SMAR and its dealer when the product was utilized in applications that contaminate the
equipment with harmful products during its handling and repair. Any other damages,
consequences, indemnity claims, expenses and other costs caused by the lack of
decontamination will be at tributed to the client. Kindly, fill out the Declaration of
Decontamination prior to shipping products to SMAR or its dealers, which can be accessed at
www.smar.com/doc/declarationofcontamination.pdf and include in the packaging.
14. This warranty certificate is valid only when accompanying the purchase invoice.
C.2
MOUNTING BRACKET FOR POSITI ONER – LINEAR STROKE VALVE
MOUNTING INSTRUCTIONS
1 –Attach the magnet to the magnet bracket
support before connect them to the valve
stem.
2 - The stem nuts should be used to fasten
the magnet bracket.
APPENDIX
3 – Mount the magnet assembly using the
nuts of the valve stem. The mounting
bracket has two parts that should be
mounted to the stem.
2 Mounting Instructions
CLAMPS
4 – Tighten the hex screw that join the two
parts of the magnet bracket. It will avoid
sliding of the two parts of the bracket during
the fastening of the stem nuts.
5 – Tighten the stem nuts.
6 – Attach the “clamps” to the positioner
bracket.
If your actuator is pillar type, go to step 15
to see the instructions.
BFY – MOUNTING BRACKET FOR POSITIONER FY 3
9 – Use the plate as a guidance to adjust
7 – Adjust the clamps according to the
width of the yoke and tighten the bolts
finger tight.
8 – Mount the positioner back plate. Tighten
the nuts finger tight.
the position of the positioner so that the
back plate is about 1 mm apart from the
magnet.
BACK PLATE
ADJUST
4 Mounting Instructions
2mm
to
4mm
10 – Fasten the nuts to fix the positioner
bracket to the yoke.
If the actuator is pillar type, fasten the Uclamp nuts.
11 – Mount the positioner to the plate and
tighten the hex screws. You can take the
back plate apart to facilitate the assembling.
12 – Move the positioner as to adjust the
Hall sensor tip in the center of the magnet.
Tighten the nuts after the adjustment.
A minimum distance of 2mm and a maximum
distance of 4mm is recommended between the
magnet external face and the positioner face.
For that, a centralizer device (linear or rotary)
must be used. The centralizer device is in the
positioner packing.
ATTENTION:
BFY – MOUNTING BRACKET FOR POSITIONER FY 5
13 – Put the pressure equivalent to the half
of the stem travel and adjust the height of
the bracket assembly to have the arrows
matching.
14 - Tighten the bolts to fasten the clamps
to the yoke.
If the actuator is pillar type, fasten the Uclamp nuts.
6 Mounting Instructions
MOUNTING DETAILS FOR THE PILLAR TYPE ACTUATOR
15 - This is the mounting bracket using U-
clamps to be mounted on pillar type
actuators.
16 – After assembling the U-clamps, follow
the steps 8 to 13.
ROTARY VALVE POSITIONER BRACKET
Rotary Valve Positioner Bracket Parts.
MOUNTING INSTRUCTIONS
1- Attach the clamps to the threaded
orifices existent on the actuator.
Do not tight them completely.
The bolts are not supplied with the
mounting bracket and they must be in
accordance with size and thread of the
actuator holes.
2- Attach the magnet bracket to the
Actuator extremity (NAMUR).
The end the valve shaft must comply with
Namur Standard.
2 Mounting Instructions
3 – Fasten the hex screw.
4 – Attach the magnet to the NAMUR
adapter.
Do not fasten the bolts completely, allowing
the magnet rotation.
5 – Mounting the positioner bracket
through the threaded rods.
BFY – MOUNTING BRACKET FOR POSITIONER FY 3
6 – Use the centralizer gadget to get the
bracket centralized with the magnet.
7 – Adjust the positioner bracket using the
centralizer gadget and the nuts to get the
height.
8 – Place the nut and washers.
Do not fasten the nuts completely.
4 Mounting Instructions
9 – Tighten the clamp bolts to fasten them
to the actuator.
10 – Fasten the positioner bracket bolts to
the clamps fastening.
11 – Remove the centralizer gadget and
fasten the positioner to the positioner
bracket.
BFY – MOUNTING BRACKET FOR POSITIONER FY 5
12 – Put the pressure equivalent to the half
of the stem and adjust the magnet position
to have the arrows matching.
13 – Tighten the bolts to fasten the magnet
to the magnet bracket.
6 Mounting Instructions
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.