SMA Sunny Data Control User Manual V.4.2

Sunny Data Control Management Software for Sunny Beam and Sunny Boy Control
User Manual Version 4.2 SDC-TEN080642
SMA Technologie AG Table of Contents
Table Of Contents
1 Notes on this Manual. . . . . . . . . . . . . . . . . . . . . . 9
1. 2 Validity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1. 4 Typographic Conventions . . . . . . . . . . . . . . . . . . . 10
2 Sunny Data Control . . . . . . . . . . . . . . . . . . . . . . 11
2. 1 What is new?. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2. 2 Scope of Delivery. . . . . . . . . . . . . . . . . . . . . . . . . 11
2. 3 Scope of Application . . . . . . . . . . . . . . . . . . . . . . 12
2. 4 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.4. 1 System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
2. 5 Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.5. 1 Software Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . 16
4 Connecting the PC to an Inverter . . . . . . . . . . . . 17
5 Connecting the PC to a Communication Device . 18
5. 1 Notes on the Use of Level Converters . . . . . . . . . . . 20
5. 2 Sunny Boy Control / Plus . . . . . . . . . . . . . . . . . . . 22
5.2. 1 Connection via RS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
5.2. 2 Connection via RS485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
5.2. 3 Connection via the Analog Modem NET Piggy-Back . . . . . . . . .28
5.2. 4 Connection via the ISDN NET Piggy-Back. . . . . . . . . . . . . . . . .29
5.2. 5 Connection via the GSM NET Piggy-Back. . . . . . . . . . . . . . . . .30
5.2. 6 Connection via the Ethernet NET Piggy-Back . . . . . . . . . . . . . . .31
5. 3 Sunny Boy Control Light . . . . . . . . . . . . . . . . . . . . 32
5.3. 1 Connection via RS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
5. 4 Sunny Beam . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.4. 1 Connection via USB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
User Manual SDC-TEN080642 Page 3
Table of Contents SMA Technologie AG
6 Installation of Sunny Data Control . . . . . . . . . . . 35
6. 1 Installing Sunny Data Control. . . . . . . . . . . . . . . . . 35
7 Sunny Data Control User Interface. . . . . . . . . . . 37
7. 1 Navigation Area . . . . . . . . . . . . . . . . . . . . . . . . . 38
7. 2 Plant tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7. 3 Display Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
8 Initial Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8. 1 Creating Plants. . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.1. 1 Brief Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
8.1. 2 Changing Plant Names, Creating / Deleting Plants . . . . . . . . . .42
8. 2 Loading a Plant . . . . . . . . . . . . . . . . . . . . . . . . . . 45
8.3. 1 COM1 – COM255 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
8.3. 2 Modem. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
8.3. 3 Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
8.3. 4 Sunny Beam (USB). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
8.3. 5 Setting the Transport Protocol . . . . . . . . . . . . . . . . . . . . . . . . .52
8. 4 Detecting Devices. . . . . . . . . . . . . . . . . . . . . . . . . 53
8.4. 1 Narrowing the Scope of Device Detection . . . . . . . . . . . . . . . .54
9 Setting Parameters (Installer). . . . . . . . . . . . . . . 55
10 Displaying Data . . . . . . . . . . . . . . . . . . . . . . . . . 58
10. 1 Creating a Device Overview . . . . . . . . . . . . . . . . . 59
10.1. 1 Displaying or Concealing Devices . . . . . . . . . . . . . . . . . . . . . .61
10.1. 2 Arranging the Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
10.1. 3 Displaying or Concealing the Graticule . . . . . . . . . . . . . . . . . .63
10.1. 4 Setting the Data Query Sequence . . . . . . . . . . . . . . . . . . . . . .64
10.1. 5 Maximizing the Device Overview (Online Display) . . . . . . . . . .64
10. 2 Selecting Channels for Spot Value Queries . . . . . . . 66
10. 3 Setting the Performance Display. . . . . . . . . . . . . . . 68
10. 4 Setting the Communication Quality. . . . . . . . . . . . . 70
Page 4 SDC-TEN080642 User Manual
SMA Technologie AG Table of Contents
10. 5 Changing the Color Behavior of the Device Fields . . 72
10. 6 Accessing Individual Device Information . . . . . . . . . 76
10. 7 Setting the Quick Information. . . . . . . . . . . . . . . . . 78
10. 8 Configuring the Total Overview . . . . . . . . . . . . . . . 80
10. 9 Overview Management . . . . . . . . . . . . . . . . . . . . 84
10.9. 1 Renaming a Device Overview . . . . . . . . . . . . . . . . . . . . . . . . .86
10.9. 2 Copying a Device Overview . . . . . . . . . . . . . . . . . . . . . . . . . .87
10.9. 3 Saving a Device Overview . . . . . . . . . . . . . . . . . . . . . . . . . . .88
10.9. 4 Deleting a Device Overview . . . . . . . . . . . . . . . . . . . . . . . . . .89
10.9. 5 Loading a Device Overview . . . . . . . . . . . . . . . . . . . . . . . . . .90
10. 10 Activating / Deactivating Spot Value Querying . . . . 91
11 Managing Data and Saving Data Locally . . . . . 92
11. 1 Reading Out and Saving Data from Sunny Beam. . . 92
11. 2 Saving Data in Excel Format . . . . . . . . . . . . . . . . . 93
11. 3 Saving Data in CSV Format . . . . . . . . . . . . . . . . . . 94
11.3. 1 Creating a New CSV Type . . . . . . . . . . . . . . . . . . . . . . . . . . .94
11.3. 2 Structure of the Standard CSV Format . . . . . . . . . . . . . . . . . .101
11. 4 Direct Data Acquisition from an Inverter . . . . . . . . 102
11.4. 1 Setting up the Data Filing Structure. . . . . . . . . . . . . . . . . . . . .102
11.4. 2 Saving and Viewing Data . . . . . . . . . . . . . . . . . . . . . . . . . . .106
11.4. 3 Sending Data to Sunny Portal . . . . . . . . . . . . . . . . . . . . . . . .107
11. 5 Setting up Sunny Boy Control Channel Recording . 107
11. 6 Reading Out Data Saved on the Sunny Boy Control 109
11.6. 1 Storage Time Refresh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111
11.6. 2 Setting Time Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
11.6. 3 Resetting Time Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113
11.6. 4 Channel Recording Icons . . . . . . . . . . . . . . . . . . . . . . . . . . .113
11.6. 5 Structure of the Excel Files. . . . . . . . . . . . . . . . . . . . . . . . . . .114
11. 7 Configuring the Automatic Readout . . . . . . . . . . . 116
11.7. 1 Setting a Task . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
11.7. 2 Editing/Deleting a Task . . . . . . . . . . . . . . . . . . . . . . . . . . . .119
User Manual SDC-TEN080642 Page 5
Table of Contents SMA Technologie AG
11.7. 3 Deactivating the Automatic Readout. . . . . . . . . . . . . . . . . . . .120
11. 8 Creating a Chart in Excel . . . . . . . . . . . . . . . . . . 121
11.8. 1 Automatic Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122
11.8. 2 Manual Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125
12 Transferring Data to the Internet . . . . . . . . . . . 128
12. 1 System Requirements. . . . . . . . . . . . . . . . . . . . . . 128
12. 2 Reading Out the Complete Time Range . . . . . . . . 128
12. 4 Sending Sunny Portal Mail . . . . . . . . . . . . . . . . . 132
12.4. 1 After Automatic Data Query . . . . . . . . . . . . . . . . . . . . . . . . .132
12.4. 2 After Manual Data Query . . . . . . . . . . . . . . . . . . . . . . . . . . .132
12. 5 Transferring the Device Overview to the Internet . . 133
12.5. 1 Writing the Online Data File . . . . . . . . . . . . . . . . . . . . . . . . .134
12.5. 2 Structure of the Online Data Files. . . . . . . . . . . . . . . . . . . . . .135
12. 6 Internet Server (SDC Agent). . . . . . . . . . . . . . . . . 140
12.6. 1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
12.6. 2 Configuring and Activating the Internet Server. . . . . . . . . . . . .142
12. 7 SDC Agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
12. 8 The Java Applet . . . . . . . . . . . . . . . . . . . . . . . . . 149
12.8. 1 General Applet Parameters . . . . . . . . . . . . . . . . . . . . . . . . . .150
12.8. 2 Component-specific Parameters . . . . . . . . . . . . . . . . . . . . . . .154
12.8. 3 Chart Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .157
12.8. 4 Device Field Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .161
12.8. 5 Numerical Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .162
12.8. 6 Overview of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . .164
12.8. 7 Example of an HTML Page . . . . . . . . . . . . . . . . . . . . . . . . . .167
Page 6 SDC-TEN080642 User Manual
SMA Technologie AG Table of Contents
13 Additional Functions. . . . . . . . . . . . . . . . . . . . . 169
13. 1 Replacing a Device . . . . . . . . . . . . . . . . . . . . . . 169
13.1. 1 Updating the Device Type. . . . . . . . . . . . . . . . . . . . . . . . . . .170
13. 2 Device Information . . . . . . . . . . . . . . . . . . . . . . . 171
13.2. 1 Setting the Device Name and Device ID. . . . . . . . . . . . . . . . .172
13.2. 2 Changing a Device's Network Address . . . . . . . . . . . . . . . . .175
13. 3 Removing Devices . . . . . . . . . . . . . . . . . . . . . . . 176
13. 4 Adding a Device . . . . . . . . . . . . . . . . . . . . . . . . 176
13. 5 Sorting Devices . . . . . . . . . . . . . . . . . . . . . . . . . 177
13. 6 Creating a Color Palette for Device Fields. . . . . . . 177
13. 7 Changing the Fonts of Device Fields . . . . . . . . . . . 178
13. 8 Background Images . . . . . . . . . . . . . . . . . . . . . . 179
13. 9 Packet Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . 182
13. 10 Changing the Security Level (Installer Password) . . 184
13. 11 Locking the Device Overview (Online Display) . . . 185
13. 12 Timeouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
13.12. 1 Settings at the Sunny Central Control . . . . . . . . . . . . . . . . . . .186
14 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . 187
14. 1 Errors Upon Use of Sunny Data Control . . . . . . . . 187
14. 3 Directory Structure . . . . . . . . . . . . . . . . . . . . . . . 189
14. 4 Setting the Language . . . . . . . . . . . . . . . . . . . . . 190
15 Overview of Menu Functions . . . . . . . . . . . . . . 191
16 Contact. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
User Manual SDC-TEN080642 Page 7
Table of Contents SMA Technologie AG
Page 8 SDC-TEN080642 User Manual
SMA Technologie AG N ot e s on t h is M a nu a l

1 Notes on this Manual

1. 1 Target Group

This manual is for installers as well as end users. It includes a description of the system and instructions for the commissioning and operation of the device. Some of the procedures may only be done by trained personnel, these procedures are marked with a danger symbol.

1. 2 Validity

This documentation for the Sunny Data Control is valid for software version 3.93 and higher. How to display the software version is described in chapter 2. 5 „Identification” (page 15).

1. 3 Symbols Used

To ensure optimum use of this document, note the following explanation of the symbols used.
This symbol indicates a notice which, if ignored, will make the procedure or oper­ation more difficult.
This symbol indicates an example, which serves to help explain a working step.
This symbol identifies a warning, which indicates a fact or feature which, if ignored, can cause serious damage to the device.
This symbol indicates a statement which, if ignored, could lead to serious injury or death.
User Manual SDC-TEN080642 Page 9
Notes on this Manual SMA Technologie AG

1. 4 Typographic Conventions

This user manual uses the typographic conventions indicated in the following table.
Example of the convention Description
<Ok> < > This symbol indicates a button
"Options" Menu items and commands are shown in
quotation marks (in conjunction with "Click on..." or "Select..." ).
"Options / Settings" If several menu items must be selected,
these are shown separated by a slash (in conjunction with "Click on..." or "Select..." ).
Page 10 SDC-TEN080642 User Manual
SMA Technologie AG Sunny Data Control

2 Sunny Data Control

2. 1 What is new?

The data transfer to Sunny Portal is now also possible when the inverter is directly connected to the PC.
- See chapter 12. 3 „Configuring Sunny Portal Mail” (page 129).

2. 2 Scope of Delivery

The program "Sunny Data Control" can be downloaded from www.SMA.de in the download area, or ordered as a CD: (SMA order number SMA-CDROM).
User Manual SDC-TEN080642 Page 11
Sunny Data Control SMA Technologie AG

2. 3 Scope of Application

Sunny Data Control is a PC program from SMA Technologie AG with which you can realize long-term storage of the data from your photovoltaic plant, and also visualize it. Sunny Data Control queries the data from your communication device (Sunny Boy Control and Sunny Beam) and saves it as Microsoft Excel files or CSV files on your PC.
With Sunny Data Control, for example, you can set up a complete overview of all inverter data (e.g.Pac, E-total, E-today) and display the inverter data in Excel in the form of charts. As an installer you can set the inverters' parameters, and you can send the data to Sunny Portal for visualization and storage. See www.SunnyPortal.com for more information on Sunny Portal.
With Sunny Data Control software version 3.81 and above, you can also connect an inverter directly to the PC. This connection is only permissible for the purpose of servicing, and may not be operated on a long-term basis.
Page 12 SDC-TEN080642 User Manual
SMA Technologie AG Sunny Data Control
PC Connection Possibilities
The following figure provides an overview of the connection possibilities from inverter to PC with Sunny Data Control. You can obtain further information at www.SMA.de, and in section 4 „Connecting the PC to an Inverter” (page 17).
It is only ever possible to have one type of connection between inverters, and to the communication device.
With an RS232 and USB connection, only one inverter can be connected to one communication device, or one inverter to one PC.
User Manual SDC-TEN080642 Page 13
Sunny Data Control SMA Technologie AG

2. 4 Functions

Supported Communication devices:
Sunny Boy Control/Plus/Light (starting with software version 2.0)
Sunny Central Control (starting with software version 2.0)
•Sunny Beam
Supported inverters for direct connection to the PC (Sunny Data Control software version 3.81 and above):
•Sunny Boys
Sunny Mini Centrals
Windy Boy
Possibility to connect one
inverter directly to the PC:
via USB service cable
Functions
Continuous system monitoring and acquisition of measurement data by means of accessing your Sunny Boy Control
Direct gathering of measurement data from an inverter through its direct connection to the PC
Remote monitoring via modem
Export of data for presentation of operating data on the Internet (e.g. via Sunny Portal)
Graphic PC display of all measurement data and operating modes
"Online display" with color-coded indication of the present output of each Sunny Boy in your plant
Configuration of Sunny Boys and adjustment of Sunny Boys' parameters
Page 14 SDC-TEN080642 User Manual
SMA Technologie AG Sunny Data Control

2.4. 1 System Requirements

Operating system: Windows 98 or above
Available hard disk space: at least 20 MB
RS232 interface: COM1 to COM255 (D-Sub9/25) or Ethernet
RS232
- on the PC: COM1 to COM255
- on the Sunny Boy Control: RS232 Piggy-Back
- Data cable: up to 15 m
RS485
- on the PC: Interface converter
- on the Sunny Boy Control: RS485 Piggy-Back
- Data cable: up to 1200 m
•Ethernet
- on the PC: Ethernet card
- on the Sunny Boy Control: NET socket, NET Piggy-Back
- Ethernet: up to 100 m
•USB
- on the Sunny Beam: up to 3 m

2. 5 Identification

2.5. 1 Software Version

In Sunny Data Control, you can display the Sunny Data Control software version via the menu item "?/Info..." .
This shows the following information:
1. Software version and date
2. Current security level of the user, see section 13. 10 „Changing the Security Level (Installer Pass­word)” (page 184).
User Manual SDC-TEN080642 Page 15
Safety Instructions SMA Technologie AG

3 Safety Instructions

Please follow all operating and safety instructions in this manual. Failure to follow these instructions could result in damage to the device and cause personal injury.
All work on the inverters may only be performed by qualified electricians! Follow all safety instructions contained in the inverter documentation!
With the Sunny Data Control program, your PV plant's safety-related inverter parameters can be changed. Such parameters may only be changed after consulting your energy supply company.
Operating Instructions
Data collected by Sunny Data Control regarding the power generated by your solar power plant can deviate from the electric meter. The Sunny Data Control data may not be used for billing purposes.
The PC, and thus Sunny Data Control, can be connected to the Internet via an ad­ditional router. Adequate security measures must be taken by using upstream hardware and software (firewall).
Page 16 SDC-TEN080642 User Manual
SMA Technologie AG Connecting the PC to an Inverter

4 Connecting the PC to an Inverter

A direct connection of a PC to the inverter is only intended for the purpose of servicing, and may not be operated on a long-term basis.
The direct connection is made via the SMA USB service interface with a 1.5 m cable and a USB interface for the PC connection (SMA order number: USBPBS)
For further information regarding this connection, please refer to the USB service interface's user manual.
Sunny Data Control supports the direct connection of an inverter to the PC with Sunny Data Control software version 3.81 and above.
Data Acquisition
How to gather and save data from an inverter connected directly to a PC is described in Chapter 11. 4 „Direct Data Acquisition from an Inverter” (page 102).
User Manual SDC-TEN080642 Page 17
Connecting the PC to a Communication Device SMA Technologie AG

5 Connecting the PC to a Communication Device

To connect several inverters to the PC, there are various communication devices at your disposal.
The following table shows the communication devices and the possible connection types.
Communication device Communication device's
interface
Sunny Boy Control / Plus RS232 Piggy-Back RS232 connection
RS485 Piggy-Back RS485 connection
NET Piggy-Back with
analog modem
NET Piggy-Back with ISDN
modem
NET Piggy-Back with GSM
modem
NET Piggy-Back with
Ethernet
PC's interface
RS232 to USB level converter
RS485 to USB level converter
RS485 to RS232 level converter
analog modem
ISDN modem (with CAPI driver)
GSM modem
ISDN modem
analog modem
ISDN modem (with CAPI driver)
GSM modem
Ethernet network card
Sunny Boy Control Light RS232 Piggy-Back RS232 connection
RS232 to USB level converter
Sunny Beam USB USB connection
Page 18 SDC-TEN080642 User Manual
SMA Technologie AG Connecting the PC to a Communication Device
Communication device Communication device's
PC's interface
interface
Sunny Central Control RS232 Piggy-Back RS232 connection
RS232 to USB level converter
RS485 Piggy-Back RS485 connection
RS485 to USB level converter
RS485 to RS232 level converter
NET Piggy-Back with
analog modem
analog modem
ISDN modem (with CAPI driver)
GSM modem
NET Piggy-Back with ISDN
ISDN modem
modem
NET Piggy-Back with
Ethernet network card
Ethernet
The following sections describe the various options for connection of the communication devices, provide recommendations for cabling, and include wiring diagrams.
Information on the Sunny Central Control
For a Sunny Central Control, certain settings in Sunny Data Control versions 3.5 and beyond must be adopted to exceed time limits. See Chapter 13.12. 1 „Set­tings at the Sunny Central Control” (page 186)
The Sunny Central Control is a variant of the Sunny Boy Control, which is directly built into the Sunny Central. Throughout this manual, only the Sunny Boy Control is mentioned. All sections which apply to the Sunny Boy Control also apply to the Sunny Central Control.
User Manual SDC-TEN080642 Page 19
Connecting the PC to a Communication Device SMA Technologie AG

5. 1 Notes on the Use of Level Converters

Level inverters are devices which convert data from one signal type to another, for instance from RS485 to USB. With the aid of these level converters, a Sunny Boy Control / Plus or Sunny Boy Control Light can be connected to a PC which does not have the appropriate interface.
Compatibility with all level converters available on the market cannot be guaran­teed.
SMA provides the following level converters. These level converters have been tested, and function with the Sunny Boy Control / Plus and the Sunny Boy Control Light:
RS232/RS485 to USB
- SMA order number: I-7561
RS485 to RS232
- SMA order number: I-7520
Page 20 SDC-TEN080642 User Manual
SMA Technologie AG Connecting the PC to a Communication Device
User Manual SDC-TEN080642 Page 21
Connecting the PC to a Communication Device SMA Technologie AG

5. 2 Sunny Boy Control / Plus

5.2. 1 Connection via RS232

RS232
RS232 communication characteristics:
A maximum of one Sunny Boy Control / Plus can be connected to a PC.
The PC must be equipped with an RS232 port. If it is not, please read section 5. 1 „Notes on the Use of Level Converters” (page 20).
The Sunny Boy Control / Plus requires an RS232 Piggy-Back at the PC (COM 2) port.
Alternatively, the AUX (COM 3) port on the Sunny Boy Control Plus can be used if the port is equipped with an RS232 Piggy-Back.
The maximum total cable length is 12 m
Cabling Recommendations
The connection between the Sunny Boy Control and the PC occurs by means of a commercially available null modem cable. Use the null modem cable provided.
If the length proves insufficient, use a commercially available null modem cable of the required length.
Jumper Functions at the Sunny Boy Control / Plus
With RS232 communication, no jumper must be mounted on the Sunny Boy Control / Plus at the PC (COM 2) port, or on the Sunny Boy Control Plus at the AUX (COM 3) port.
Page 22 SDC-TEN080642 User Manual
SMA Technologie AG Connecting the PC to a Communication Device
Wiring Diagram
Observe all safety instructions in the Sunny Boy Control / Plus documentation, and in the PC documentation.
Shut down the PC before you connect the Sunny Boy Control / Plus, as otherwise one or both COM ports may be damaged.
1. Use the provided null modem ca­ble, or a commercially available null modem cable of the required length.
2. Plug the 9-pin D-Sub female con­nector into a free COM port on your PC.
3. Lay the cable properly so that there is no risk of persons tripping over it.
4. Plug the 9-pin D-Sub female con­nector into the port on the Sunny Boy Control which is equipped with the RS232 interface.
Sunny Boy Control: PC (COM 2) Sunny Boy Control Plus: (COM 2)
or AUX (COM 3)
5. Make sure that jumpers A, B and C are not plugged in the port used.
Sunny Boy Control
User Manual SDC-TEN080642 Page 23
Sunny Boy Control Plus
Connecting the PC to a Communication Device SMA Technologie AG

5.2. 2 Connection via RS485

RS485
RS485 communication characteristics:
Up to 50 Sunny Boy Control / Plus devices can be connected to a PC.
The PC must be equipped with an RS485 port. If it is not, please read section 5. 1 „Notes on the Use of Level Converters” (page 20).
Each Sunny Boy Control requires an RS485 Piggy-Back at the PC (COM 2) port. Alternatively, at the Sunny Boy Control Plus, the AUX (COM 3) port can be used,
if this is equipped with an RS232 Piggy-Back.
The maximum total cable length is 1200 m
Cabling Recommendations
The cable length and quality have an effect on the signal quality. To achieve a good quality signal, observe the following instructions regarding cabling:
Use metallic D-Sub female connectors. Connectors made of plastic, or metallized plastic, can cause faulty data transfer.
For the outdoors, use a communications cable with the following important qualities:
- Cross-section: at least 2 x 2 x 0,22 mm
-shielded
-Twisted Pair
- UV-resistant We recommend the following cable types for outdoors: SMA communications cable: COMCAB-OUTxxx* *available in the following lengths xxx = 100 m/200 m/500 m und 1000 m. Lappkabel: UNITRONIC Li2YCYv 2 x 2 x 0,22 mm
2
, and at least 2 x 2 x AWG 24
2
For the outdoors you can also use a data cable designed for indoor use, if you protect it against UV radiation with an appropriate cable duct.
Page 24 SDC-TEN080642 User Manual
SMA Technologie AG Connecting the PC to a Communication Device
We recommend the following cable types for indoors: SMA data cable: COMCAB-INxxx* *available in the following lengths xxx = 100 m/200 m/500 m und 1000 m. Lappkabel: UNITRONIC Li2YCY (TP) 2 x 2 x 0,22 mm Helukabel: PAAR-TRONIC-Li-2YCY 2 x 2 x 0,22 mm
2
2
Pin Assignment of the Connection Cable
Sunny Boy Control PC
Signal Pin Pin Signal
Data + 3 Data +
Data- 8 Data-
GND 5 GND
Jumper Functions
Termination To increase the signal quality of the RS485 data bus, it must be terminated at both ends.
Each termination occurs with a 120 W resistor between the two data lines. Terminate the last Sunny Boy Control / Plus by means of a jumper. The position of the jumper is described in the user manual of the Sunny Boy Control / Plus.
Signal Biasing To increase the signal quality of the RS485 data bus, a maximum of one bias can be
connected in the data bus. We recommend connecting the bias at the PC.
User Manual SDC-TEN080642 Page 25
Connecting the PC to a Communication Device SMA Technologie AG
Wiring Diagram
Observe all safety instructions in the Sunny Boy Control / Plus documentation, and in the PC documentation.
Shut down the PC before you connect the Sunny Boy Control / Plus, as otherwise one or both COM ports may become damaged.
1. Plug the 9-pin D-Sub female con­nector into a free COM port on your PC. For the pin assignment of the RS485 connection, please re­fer to the PC's documentation, or the plug-in card's documentation. When connecting the cable, make sure that Data+ and Data- are a twisted pair. Shorten the wire of the fourth, unused conductor, so that short circuits cannot arise. Take note of the conductors' color cod­ing:
Data + ____________________
Data- ____________________
GND ____________________
2. If the PC is situated at one of the two ends of the RS485 data bus, terminate the end of the cable as described in the PC's documenta­tion, or in the plug-in card's docu­mentation.
3. Configure the RS485 data bus' bias as described in the PC's docu­mentation, or the plug-in card's documentation.
4. Lay the cable properly so that there is no risk of persons tripping over it.
Sunny Boy Control Sunny Boy Control Plus
Page 26 SDC-TEN080642 User Manual
SMA Technologie AG Connecting the PC to a Communication Device
5. Plug the 9-pin D-Sub female con­nector into the port on the Sunny Boy Control which is equipped with the RS485 interface.
Sunny Boy Control: PC (COM 2) Sunny Boy Control Plus: (COM 2)
or AUX (COM 3)
6. Connect the PC's Data+ with the Data+ of the Sunny Boy Control / Plus, and so on. The 3 connections should be made directly.
7. At the last Sunny Boy Control / Plus, jumper A must be mounted at the port used. Jumper A must not be mounted on any of the other Sunny Boy Control / Plus devices. Make sure that jumpers B and C are not mounted at the port used.
8. Connect the Data+ of the next Sun­ny Boy Control / Plus with the Da­ta+ of the Sunny Boy Control / Plus which precedes it, and so on. The 3 connections are directly intercon­nected.
9. At the last Sunny Boy Control / Plus, jumper A must be mounted at the port used. Jumper A must not be mounted on any of the other Sunny Boy Control / Plus devices. Make sure that jumpers B and C are not mounted at the port used.
Sunny Boy Control Sunny Boy Control Plus
Sunny Boy Control Sunny Boy Control Plus
User Manual SDC-TEN080642 Page 27
Connecting the PC to a Communication Device SMA Technologie AG

5.2. 3 Connection via the Analog Modem NET Piggy-Back

Analog Modem Communication Characteristics
As the connection to the Sunny Boy Control / Plus is established via the telephone network, it is only ever possible to connect one Sunny Boy Control / Plus with the PC.
The PC must be equipped with a modem (analog, ISDN with CAPI driver or GSM).
The Sunny Boy Control / Plus requires an "analog modem" version of the NET Piggy-Back.
Compatibility with all PC modems available on the market cannot be guaranteed.
Connection
1. Connect the PC to the telephone network as described in the modem's user man­ual.
2. Connect the Sunny Boy Control / Plus to the telephone network as described in the NET Piggy-Back's user manual.
3. Use the software provided with the PC operating system to establish the connection between the two devices.
Page 28 SDC-TEN080642 User Manual
SMA Technologie AG Connecting the PC to a Communication Device

5.2. 4 Connection via the ISDN NET Piggy-Back

ISDN Modem Communication Characteristics
As the connection to the Sunny Boy Control / Plus is established via the telephone network, it is only ever possible to connect one Sunny Boy Control / Plus with the PC.
The PC must be equipped with an ISDN modem.
The Sunny Boy Control / Plus requires an "ISDN" version of the NET Piggy-Back.
Compatibility with all PC modems available on the market cannot be guaranteed.
Connection
1. Connect the PC to the telephone network as described in the modem's user man­ual.
2. Connect the Sunny Boy Control / Plus to the telephone network as described in the NET Piggy-Back's user manual.
3. Use the software provided with the PC operating system to establish the connection between the two devices.
User Manual SDC-TEN080642 Page 29
Connecting the PC to a Communication Device SMA Technologie AG

5.2. 5 Connection via the GSM NET Piggy-Back

GSM Modem Communication Characteristics
As the connection to the Sunny Boy Control / Plus is established via the telephone network, it is only ever possible to connect one Sunny Boy Control / Plus with the PC.
The PC must be equipped with a modem (analog, ISDN with CAPI driver or GSM).
The Sunny Boy Control / Plus requires a "GSM" version of the NET Piggy-Back.
Compatibility with all PC modems available on the market cannot be guaranteed.
Connection
1. Connect the PC to the telephone network as described in the modem's user man­ual.
2. Connect the Sunny Boy Control / Plus to the telephone network as described in the NET Piggy-Back's user manual.
3. Use the software provided with the PC operating system to establish the connection between the two devices.
Page 30 SDC-TEN080642 User Manual
SMA Technologie AG Connecting the PC to a Communication Device

5.2. 6 Connection via the Ethernet NET Piggy-Back

Router or hub
Ethernet Network Communication Characteristics
Any number of Sunny Boy Control / Plus devices can be connected to a PC via the Ethernet network. The only limitation is the capability of the PC, whereby the main memory is the limiting factor.
A Sunny Boy Control / Plus can be connected directly to a PC.
The PC must be equipped with an Ethernet network card.
Each Sunny Boy Control / Plus requires an "Ethernet" version of the NET Piggy­Back.
Cabling Recommendations
The cable length and quality can adversely affect the signal quality. To achieve good results, observe the following instructions.
For the connection to a hub or router, you require a patch cable. For the direct connection to a PC, you require a crossover cable.
Use high quality cable, at least category 5 (STP Cat 5) or higher shielded twisted pair cable.
The maximum permitted cable length for Ethernet cable is 100 m.
User Manual SDC-TEN080642 Page 31
Connecting the PC to a Communication Device SMA Technologie AG
Connection to an Ethernet Network
1. Connect the PC to the network as described in the Ethernet network card's user manual.
2. Connect the Sunny Boy Control / Plus to the Ethernet network as described in the NET Piggy-Back's user manual.
Direct Connection to a Single PC
1. Plug one end of the crossover cable into your PC's Ethernet network card.
2. Plug the other end of the Ethernet network cable into the NET socket of the Sunny Boy Control / Plus.
3. Lay the cable properly so that there is no risk of persons tripping over it.

5. 3 Sunny Boy Control Light

5.3. 1 Connection via RS232

RS232
RS232 communication characteristics:
A maximum of one Sunny Boy Control Light can be connected to a PC.
The PC must be equipped with an RS232 port. If it is not, please read section 5. 1 „Notes on the Use of Level Converters” (page 20).
The maximum total cable length is 12 m
Cabling Recommendations
The connection between the Sunny Boy Control Light and the PC occurs by means of a commercially available null modem cable. Use the null modem cable provided.
If the length proves insufficient, use a commercially available null modem cable of the required length.
Page 32 SDC-TEN080642 User Manual
SMA Technologie AG Connecting the PC to a Communication Device
Wiring Diagram
Observe all safety instructions in the Sunny Boy Control / Plus documentation, and in the PC documentation.
Shut down the PC before you connect the Sunny Boy Control / Plus, as otherwise one or both COM ports may become damaged.
1. Use the provided null modem cable, or a com­mercially available null modem cable of the re­quired length.
2. Plug the 9-pin D-Sub female connector into a free COM port on your PC.
3. Lay the cable properly so that there is no risk of persons tripping over it.
4. Plug the 9-pin D-Sub female connector into the PC (COM2) port on the Sunny Boy Control Light.
Sunny Boy Control Light
User Manual SDC-TEN080642 Page 33
Connecting the PC to a Communication Device SMA Technologie AG

5. 4 Sunny Beam

5.4. 1 Connection via USB

USB
USB Communication Characteristics
A maximum of one Sunny Beam can be connected to a PC.
The PC must be equipped with a USB port.
The maximum total cable length is 3 m
Connection
1. Connect the Sunny Beam to the PC as described in the Sunny Beam's user manual.
Page 34 SDC-TEN080642 User Manual
SMA Technologie AG Installation of Sunny Data Control

6 Installation of Sunny Data Control

Sunny Data Control can be downloaded from the SMA web server or ordered as a CD.
Installation with Windows Vista: With Windows Vista, Sunny Data Control must be saved using a path other than
C:\Programs, for example, C:\SMA.

6. 1 Installing Sunny Data Control

1. Before installation, close all Win­dows programs on your PC.
2. Start the Sunny Data Control in­stallation program (setup file) on your PC. The Sunny Data Control installation window opens (see figure to the right).
3. Follow the program's on-screen instructions.
SDC agent
4. If you also wish to use Sunny Data Control for online presenta­tion of your PV plant, add a check mark next to "SDC Agent" (not necessary for Sunny Portal).
User Manual SDC-TEN080642 Page 35
Installation of Sunny Data Control SMA Technologie AG
Program Shortcut
5. If a program shortcut (see figure below) for Sunny Data Control is to be created on your PC, leave the check mark in place (see fig­ure to the right).
6. Once the installation is finished, you can launch Sunny Data Control.
7. When you launch Sunny Data Control for the first time, no device is as yet config­ured to be detected by Sunny Data Control.
8. If you have not yet connected a device, connect it as described in section 5 „Con­necting the PC to a Communication Device” (page 18).
9. Subsequently, create a plant and establish the communication connection as de­scribed in section 8 „Initial Settings” (page 41).
Page 36 SDC-TEN080642 User Manual
SMA Technologie AG Sunny Data Control User Interface

7 Sunny Data Control User Interface

The Sunny Data Control user interface comprises three areas:
Navigation areaIn the navigation area, you can access and use various Sunny Data Control functions.
Plant treeIn the plant tree, the currently selected plant is displayed, along with its devices which you have detected with Sunny Data Control.
Display areaIn the display area, three different views can be called up via the three tabs (see figure below).
- Spotvalues (here, the page "Device Overview" is displayed)
- Channel recording (here, the page "Archive Channels" is displayed)
- Parameters (here, the page "Parameters" is displayed)
Navigation Area
Plant tree
Tabs
Display Area (with three tabs)
User Manual SDC-TEN080642 Page 37
Sunny Data Control User Interface SMA Technologie AG

7. 1 Navigation Area

The navigation area comprises the menu bar and the menu buttons. The menu buttons correspond to the most frequently required menu items, and are thus made available to you as convenient menu buttons for quick access. You can also call up these menu items via the menu bar.
Menu bar
Menu buttons
The menu bar comprises six main menus:
1. File
2. Connection
3. Spot values
4. Options
5. Extras
6. ?
The menu buttons correspond to the most frequently required menu items:
PlantAlso accessible in the navigation area via "Options / Choose Plant".
SearchAlso accessible in the navigation area via "Options / Device Detection".
SaveThis button can only be selected if the archive channels are currently displayed in the display area. You can call up the archive channels in the display area via the "Channel recording" tab.
•Show
SettingsAlso accessible in the navigation area via "Options / Settings".
Page 38 SDC-TEN080642 User Manual
SMA Technologie AG Sunny Data Control User Interface

7. 2 Plant tree

In the plant tree, the currently selected plant is displayed, along with its devices, which you have detected with Sunny Data Control.
Here, via the plant tree menu, you can, forexample, call up the device information of the selected device, remove the selected device, add devices, sort devices, or replace devices.
Some of the actions which you can select in the plant tree menu apply to the currently selected device, while other actions apply to all devices.
You can call up the plant tree menu for the respective device by clicking on the name of the device with the right mouse button, or by clicking on the icon pictured here to the right (see also figure above):
If you call up the plant tree menu via the icon, you must first highlight the respective device by clicking on the device's name.
Expanding and Collapsing the Plant Tree
You can expand and collapse the plant tree by clicking on the nodes (+/- symbols). This function is a practical way to maintain an overview if you have a plant with many devices.
Plant tree
Collapsed plant tree
Expanded plant tree
User Manual SDC-TEN080642 Page 39
Sunny Data Control User Interface SMA Technologie AG

7. 3 Display Area

In the display area, three different pages can be called up via the three tabs (see figure below):
- Spotvalues (here, the page "Device Overview" is displayed)
- Channel recording (here, the page "Archive Channels" is displayed)
- Parameters (here, the page "Parameters" is displayed)
You can call up the Device Overview menu ("Spotvalues" tab) via the following icon:
(see also figure below), or by clicking on the field of the respective device with the right mouse button. Some of the actions which you can select in the display area menu apply to the currently selected device, while other actions apply to all devices.
Name of the current page (here: device overview).
Lock online display (device overview)
Three tabs (here: "Spotvalues" tab active)
Device overview menu ("Spotvalues" tab)
Page 40 SDC-TEN080642 User Manual
SMA Technologie AG Initial Settings

8 Initial Settings

8. 1 Creating Plants

With Sunny Data Control, you can create, manage and monitor one or more plants (e.g. as an installer). However, it is only ever possible to display and edit one a time (current plant) in the Sunny Data Control window. If you manage several plants, you must first load the respective plant (see section 8. 2 „Loading a Plant” (page 45)).
Detected devices and settings, such as the communication connection or parameters, always refer to the respective plant, and are saved as settings for the respective plant.

8.1. 1 Brief Overview

You can call up the window for creating and selecting plants via the menu item "Options / Choose Plant", or via the "Plant" icon (see figure below). By default, a plant with the name "My Plant" is always created automatically during installation.
Current plant
Currently selected plant
All plants already created
plant at
Load selected plant
Save current plant
Create copy of the selected plant
Create new plant
Rename selected plant
Delete selected plant
User Manual SDC-TEN080642 Page 41
Initial Settings SMA Technologie AG

8.1. 2 Changing Plant Names, Creating / Deleting Plants

Changing the Plant Name
By default, a plant with the name "My Plant" is always created automatically by Sunny Data Control during installation. You can change the plant name which is displayed in Sunny Data Control, create additional plants, or delete plants.
1. Select "Options / Choose Plant", or click on the "Plant" icon (see figure to the right).The "PV-Plant" window opens.
Current plant
All plants already created
2. In the "Available Plants" field, click on "My Plant", so that it is highlighted.
3. Click on <Rename>. The name of the selected plant can now be written over.
4. Type in the desired name for the plant.
5. Click on <Save> in order to save the new name, or click on the white area of the window.
Page 42 SDC-TEN080642 User Manual
SMA Technologie AG Initial Settings
Creating Plants
1. Select "Options / Choose Plant", or click on the "Plant" icon (see figure to the right).The "PV-Plant" window opens.
2. Click on <New> to create a new plant. A new plant with the name "My Plant" is created. The name can now be overwritten.
3. Type in the desired name for the plant.
4. Click on <Save> in order to save the new name, or click on the white area of the window. In this way you can create more plants
User Manual SDC-TEN080642 Page 43
Initial Settings SMA Technologie AG
Deleting Plants
If you delete a plant, the complete plant is deleted, along with all settings and de­tected devices! The saved Excel files are retained.
1. Select "Options / Choose Plant", or click on the "Plant" icon (see figure to the right).The "PV-Plant" window opens.
2. Select the plant which you wish to delete by clicking on the name of the plant.
3. The selected plant is immediately deleted, along with all settings and detected de­vices, when you click on <Delete>. In this way you can delete other plants.
Page 44 SDC-TEN080642 User Manual
SMA Technologie AG Initial Settings

8. 2 Loading a Plant

If you have created more than one plant, you must first load the plant which you wish to edit or display. It is only ever possible to display and edit one plant at a time (current plant) in the Sunny Data Control window.
1. Select "Options / Choose Plant", or click on the "Plant" icon (see figure to the right).The "PV-Plant" window opens.
2. Select the plant which you wish to load by clicking on the name of the plant.
3. Click on <Load> to load the selected plant.
User Manual SDC-TEN080642 Page 45
Initial Settings SMA Technologie AG

8. 3 Setting the Communication Connection

According to your selected type of connection to the PC, you must set the corresponding connection in Sunny Data Control.
The communication connection setting always refers to the current plant, and can be set differently for each plant.
In Sunny Data Control, you can set the connections listed below, which are described in the sections which follow.
COM1, 2, 3, etc.(here, your PC's COM ports are listed: COM1, COM2, etc.)See section 8.3. 1 „COM1 – COM255” (page 46).
"Modem"(here, the type name of the modem installed at your PC is displayed)See section 8.3. 2 „Modem” (page 48).
NetworkSee section 8.3. 3 „Network” (page 48).
Sunny Beam (USB)See section 8.3. 4 „Sunny Beam (USB)” (page 51).
8.3. 1 COM1 – COM255
1. Select "Options / Settings", or click on the "Settings" icon. The "Set­tings..." window opens.
2. Select "Communication".
Page 46 SDC-TEN080642 User Manual
SMA Technologie AG Initial Settings
3. In the drop-down list "Connection by", select the COM port, via which the Sunny Boy Control is connected to your PC. The COM ports are labeled on your PC (1, 2, 3, etc.).
4. Click on <Settings>.
5. The connection settings window opens. In the pop-up menu "Type of medium", choose the medium via which the Sunny Boy Control is connected to your PC's COM port.
The following medium types can be selected:
RS232
RS485 If you select RS485, you must first deactivate the serial port's FIFO buffer, as described in your operating system's user manual.
RS485 (auto)
Powerline (SWRCOM)
Baudrate
6. In the "Bits per second:" drop-down list, select the Baudrate.
- If an inverter is connected to the PC directly: select 1200 bits per second.
- If a Sunny Control is connected to the PC via RS232, and the length of cable
is under 15 m: select 19,200 bits per second.
7. Click on <Ok> to apply the settings.
Transport Protocol
8. In the "Using transport protocol" drop-down list, select the appropriate transport protocol for the connected device, as described in section 8.3. 5 „Setting the Transport Protocol” (page 52).
9. Click on Ok in the "Settings..." window in order to save the settings.
User Manual SDC-TEN080642 Page 47
Initial Settings SMA Technologie AG

8.3. 2 Modem

1. Select "Options / Settings", or click on the "Settings" icon (see figure to the right).The "Settings..." window opens.
2. Select "Communication".
3. In the drop-down list "Connection by", select "Modem".
4. Click on <Settings>.
5. Enter the telephone number.
6. In the "Using transport protocol" drop-down list, select the appropriate transport protocol for the connected device, as described in section 8.3. 5 „Setting the Transport Protocol” (page 52).
7. To save the settings, click on <Ok>.

8.3. 3 Network

1. Select "Options / Settings", or click on the "Settings" icon (see figure to the right).The "Settings..." window opens.
2. Select "COMMU­NICATION".
3. In the drop-down list "Connection by", se­lect "Network".
4. Click on <Settings>.
Page 48 SDC-TEN080642 User Manual
SMA Technologie AG Initial Settings
The network settings window opens.
Select whether all devices in the local network are to be detected.
Define which additional devices are to be detected (add IP addresses or DNS names of the devices).
Select whether RAS is to be used (set the telephone number of the external modem).
Local network
5. If you wish to detect all devices which are connected to your local network, add a check mark alongside "Access to all devices in the local network..." .
6. If you wish to detect additional devices, click on <Add>. The window for configuration of a new connection opens.
7. In the field "IP address or DNS name", enter the IP address or DNS name of the device in the network which you wish to detect. The de-
fault IP address of a Sunny Boy Control is 10.170.170.170.
8. Then click on <Ok>. The IP address or DNS name of the device is displayed in the "Use always additional devices:" win­dow (see the example in the illustration with IP address entered). Using <Delete> you can delete the currently selected de­vice again.
User Manual SDC-TEN080642 Page 49
Initial Settings SMA Technologie AG
RAS Connection
You can access an external modem (if access to it has been enabled for you) via an RAS connection, in order to query the data from Sunny Data Control on this connection.
If you wish to access an external modem from your PC, the RAS service must be installed and configured on your PC, and on the PC which you wish to access.
9. If you wish to detect devices via an RAS connection, place a check mark in the "Use RAS" check box. The RAS connection configuration window opens (see fig­ure below).
10. Connection name:In the field "Connection name", enter the name with which you wish to identify this connection (e.g. Smith Family). Choose a descriptive name, so that you can recognize the connection.
11. Telephone number:In the field "Telephone number", enter the telephone number of the modem (connection) which you wish to access.
12. Select the type of connection in the drop-down list "Connection via..."
13. User name:In the "User name" field, enter the user name which has been conveyed to you by the owner of the connection.
14. Password:In the "Password" field, enter the password which has been conveyed to you by the owner of the connection.
15. If you wish to test whether the connection is functioning, click on Testing connec­tion.
16. Click on Save to save the settings. The new connection is displayed in the field "Phonebook entries".
17. Click on Apply. The "Current device connections" window is displayed once more.
Page 50 SDC-TEN080642 User Manual
SMA Technologie AG Initial Settings
18. In the "Using transport protocol" drop-down list, select the appropriate transport protocol for the connected device, as described in section 8.3. 5 „Setting the Transport Protocol” (page 52).
19. Click on <Ok> to apply the settings.

8.3. 4 Sunny Beam (USB)

1. Select "Options / Settings", or click on the "Settings" icon (see figure to the right). The "Settings" window opens.
2. Select "Communica­tion".
3. In the drop-down list "Connection by", se­lect "Sunny Beam (USB)".
4. If you wish to see which Sunny Beam devices are already detected, click on Set­tings.
5. To save the settings, click on <Ok>.
User Manual SDC-TEN080642 Page 51
Initial Settings SMA Technologie AG

8.3. 5 Setting the Transport Protocol

According to whether you have connected a communication device or an inverter to the PC, set the appropriate transport protocol for the respective device type listed below.
If you are unsure which transport protocol to set, select "SMANet + SunnyNet (auto)".
Sunny Data Control then automatically searches for the correct transport protocol.
Communication Devices
Sunny Boy Control / Plus / Light
- The Sunny Boy Control can operate with either transport protocol. The default
setting in the Sunny Boy Control is SMA-Net. Select the transport protocol which is set in your Sunny Boy Control.
•Sunny Beam
-Select "SMANet".
Inverters
•SMA-Net
- Sunny Boys of type SWR, version BFR 8.22 or above
- All Sunny Boys type SB
- All Sunny Mini Central
- All Sunny Central
•Sunny-Net
- Sunny Boys of type SWR prior to version BFR 8.22
Page 52 SDC-TEN080642 User Manual
SMA Technologie AG Initial Settings

8. 4 Detecting Devices

By default, Sunny Data Control detects the following communication devices: Sunny Beam without inverters, Sunny Boy Control with the inverters to which it is connected, and an inverter connected directly to the PC. If necessary, you can narrow the scope of detection, as described in section 8.4. 1 „Narrowing the Scope of Device Detection” (page 54).
1. If you have created more than one plant, load the plant for which you wish to de­tect devices. Click on the Plant icon, and load the desired plant.
2. Select "Options / Detect Device", or click on the "Search" icon. The win­dow "Searching for Plant Devices" opens.
3. In the field "How many devices should be searched?" , enter the number of devices for which you wish to search.
4. Click on Ok. The detection process starts. The devices are searched for. Wait until the search is finished. The window (see figure below) closes when the search is complete. If you wish to cancel the search, click on Cancel.
The detected devices are shown in the plant tree (see figure to the right).
User Manual SDC-TEN080642 Page 53
Initial Settings SMA Technologie AG

8.4. 1 Narrowing the Scope of Device Detection

The scope of device detection can be limited to the communication devices and the inverters connected to them, or to an inverter connected directly to the PC.
1. Select "Options / Settings", or click on the "Settings" icon (see figure to the right).
The "Settings" window opens.
2. Select "Misc“.
3. Beneath "Device detection mode, searching for", you can select whether the scope of the search is to include data loggers (communication devices) with inverters and/or directly connected inverters.
Add or remove check marks in the appropriate fields.
4. Click on Save to save the settings.
5. Start the device detection process, as described in section 8. 4 „Detecting Devic­es” (page 53).
Page 54 SDC-TEN080642 User Manual
SMA Technologie AG Setting Parameters (Insta ller)

9 Setting Parameters (Installer)

Sunny Data Control makes it possible to set parameters for inverters and for the Sunny Boy Control, in order to specify operating modes for individual devices. The type and scope of the displayed parameters depend on the security level. If you are logged in as an installer, you can set more parameters. The security level is set via the menu item "Extras / Security Level". See section 13. 10 „Changing the Security Level (Installer Password)” (page 184). Type in the installer password there.
With the Sunny Data Control program, your PV plant's safety-related inverter parameters can be changed. Such parameters may only be changed after consulting your energy supply company.
The "Parameters" window (third tab at the bottom) shows the parameter list of the currently selected device from the plant tree.
Some parameters serve merely as information regarding the factory settings, whereas others are adjustable. If you select an adjustable parameter, you can change the present channel value in the "Channel value" field.
Brief Overview
Selected device and Channel
channel value
Apply channel value value
Apply
Search for parameter
"Parameters" tab
User Manual SDC-TEN080642 Page 55
Permanently save parameter settings in device
new channel value to all devices of the same type
Setting Parameters (Installer) SMA Technologie AG
1. Click on the "Parameters" tab at the lower edge of the screen (see figure below).
Plant tree
"Parameters" tab
2. In the plant tree (see figure above), click on the device for which you wish to adjust parameters.
3. In the "Parameters" list, click on the channel which you wish to adjust.
Page 56 SDC-TEN080642 User Manual
SMA Technologie AG Setting Parameters (Insta ller)
In the upper right-hand corner of the screen, you can check your selection by means of the displayed data (see figure below).
Enlarged section Example
Displays the name of the selected device.
Displays the name of the selected channel.
A field is only displayed here if the channel is adjustable. Here, depending on the channel type, you can either enter a value yourself, or set a channel value by selecting one from the drop-down list.
4. Set the desired value in the "Channel value" field.
5. You can now apply this channel value by means of the buttons in the lower right­hand corner of the screen.
<Set>: Apply value only to the selected device. <Set all devices>: Apply to all devices of the same type. <Refresh>: Permanently save the parameter settings in the device. If you wish to save the parameter set-
tings permanently in the device, click on <Yes>.
User Manual SDC-TEN080642 Page 57
Displaying Data SMA Technologie AG

10 Displaying Data

For display of the present operating data, various display options are at your disposal. In order to manage the copious amounts of data which arise, you can combine these options according to the overall size of your plant and the respective display requirements regarding clarity and informative value.
The following options for displaying spot values are at your disposal:
Device overview (with individual device fields)
Single Device Information
Quick information
•Overview
Device field
Device overview
Single Device Information Quick information
You can assign each individual display mode to each selected measuring channel. In so doing, it is also possible to assign several display modes to the same channel.
The following sections describe the individual steps necessary for the display of the present operating data.
Page 58 SDC-TEN080642 User Manual
Overview
SMA Technologie AG Displaying Data

10. 1 Creating a Device Overview

The "Spotvalues" window (first tab at the bottom), in which the device overviews are displayed, provides a quick and informative display of the present operating mode of your entire plant. Here, you can set up an overview of your plant's devices, and their respective operating modes.
The "Device Overview" page is subdivided into fields (see figure below). One device can be displayed in each field.
You can create and save several device overviews for each plant. This fu n c t ion is useful, for example, with plants which include many devices, because it provides a clearer overview, and different data views can be saved (see section 10. 9 „Overview Management” (page 84)).
"Spotvalues" tab
1. Simply drag and drop the device (e.g. Sunny Boy Control or inverter) onto the desired field in which the device is to be displayed.
Drag and drop: click on the name of the device with the left mouse button, hold the mouse button pressed, drag the device into the desired field, and release the mouse button.)
User Manual SDC-TEN080642 Page 59
Displaying Data SMA Technologie AG
You can only drag each device into the device overview once. You can only drop a device into an empty field.
2. If you have dragged a Sunny Boy Control into a field, a prompt window opens. If you want all of the inverters which belong to the Sunny Boy Control to be added to the overview, click on <Yes>. If, for the time being, you only wish to add the Sun­ny Boy Control, click on <No>.
Depending on whether you have clicked <Yes> or <No> in the prompt window, either just the Sunny Boy Control, or the Sunny Boy Control with all of its inverters, are added to the device overview (see figure below).
3. In this manner, you can drag the other devices from the plant tree into the device overview fields.
Repositioning the Occupied Fields
4. You can move the occupied fields in the device overview by moving the occupied field to a free one.
Page 60 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data

10.1. 1 Displaying or Concealing Devices

1. If you wish to remove (conceal) a device which is in the device overview, click on the respective device with the right mouse button.The Device Overview menu opens.
2. Select <Fade out devices>. You can now select whether you wish to conceal this device, all devices, or allof
the sametype.
3. If you wish to display the devices again, select <Fade in devices> in the Device Overview menu.
User Manual SDC-TEN080642 Page 61
Displaying Data SMA Technologie AG

10.1. 2 Arranging the Fields

If you wish to display more devices in the device overview than the number of fields allows, you must subdivide the device overview into more fields.
1. Select "Options / Settings", or click on the "Settings" icon (see figure to the right). The "Settings" window opens.
2. Select "Spotvalue Request / Arrangement“.
3. Select "Spotvalue Request / Arrangement“.
4. In the area "Arrangement of devices horizontally / vertically", enter the number of fields that you wish to have displayed beside each other (horizontal) or above each other (vertical). Up to 100x100 fields can be displayed. If you wish to in­crease the number of fields to such an extent that the devices which are already displayed will no longer have sufficient space to be fully displayed in the new de­vice overview, the adjustment of scale is ignored.
Page 62 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data

10.1. 3 Displaying or Concealing the Graticule

1. Select "Options / Settings", or click on the "Settings" icon.The "Settings" window opens.
2. Select "Spotvalue Request / Arrangement“.
3. In the "Grid Net" area, add or remove the check mark in the "visible" check box. If you add the check mark, the graticule is visible in the device overview.
User Manual SDC-TEN080642 Page 63
Displaying Data SMA Technologie AG

10.1. 4 Setting the Data Query Sequence

1. Select "Options / Settings", or click on the "Settings" icon.The "Settings" window opens.
2. Select "Spotvalue Request / Arrangement“.
3. In the "Request Direction" drop-down list, set the sequential order for data queries. Horizontal = row by row, vertical = column by column.

10.1. 5 Maximizing the Device Overview (Online Display)

You can display the device overview in an enlarged format, covering the entire screen.
1. Select "Spotvalues / Maximize online dis­play" (see figure to the right). The device over­view is shown in an enlarged format, covering the entire screen. The plant tree and the menu bar are concealed.
You can also call up the window in the follow­ing way: click on the device overview with the right mouse button. The device overview menu opens. Select "Maximize online display“.
Page 64 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data
2. To return the enlarged display to its minimized format, click on the device overview with the right mouse button. The device overview menu opens. Select "Minimize online display“.
The device overview is again displayed in its smaller format. The plant tree and menu bar are visible again.
Minimized device overview Maximized device overview
User Manual SDC-TEN080642 Page 65
Displaying Data SMA Technologie AG

10. 2 Selecting Channels for Spot Value Queries

For each device which is displayed in the device overview ("Spotvalues" tab), you can define which channels are to be displayed in the various spot value queries (see figures below). The default setting of the overview display, and of the single device view, is to display all available channels. The channel selection can be set for each device type, or for each individual device.
Various spot value queries
Overview display of a device from the device overview
Single device information
Quick information (max. 4 channels can be displayed)
Copy selected channels from the left-hand field into the respective field on the right
Copy all channels from the left-hand field into the respective field on the right
Delete selected channels from the respective field on the right
Delete all channels from the respective field on the right
To select several channels, hold down the "Ctrl" key on your keyboard, and click on the channels with the mouse.
Page 66 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data
1. In the device overview, use the right mouse button to click on the field of the device for which you wish to set the channels for spot value queries. The device overview menu opens.
2. Select "Channel Selection“. The window for setting the selected device's channels opens (see figure below).
You can also call up the window in the following way: select the device for which you wish to set the channels by clicking on the device's field with the left mouse button in the device overview. Select the menu item "Spotvalues / Channel Selec­tion“.
Selected device (clicked on previously)
Select whether the channel selection shall only apply to this device (clicked on previously), or for a particular device type.
3. Under "Channel selection is valid for" (see figure above), select whether you wish to set the channel selection for the selected device only, or for all devices of a par­ticular type.
4. Use the arrow buttons to add or remove the desired channels for the respective spot value queries.
User Manual SDC-TEN080642 Page 67
Displaying Data SMA Technologie AG

10. 3 Setting the Performance Display

The individual device fields in the device overview can change color according to the devices' calculated capacity utilization.
The capacity utilization is calculated on the basis of one channel (default channel: The color behavior of the device field during spot value querying is determined by this channel, and by the value for 100 % capacity utilization.
You can change the channel, and specify the threshold channel value, which is to indicate that the device is performing at 100 % capacity. The performance display can be defined for individual devices, or for a device type.
1. In the device overview, use the right mouse button to click on the field of the device for which you wish to configure the performance display. The device overview menu opens.
2. Select "Channel Selection“. The window for setting the selected de­vice's channels opens (see figure to the right).
You can also call up the window in the following way: select the device for which you wish to set the chan­nels by clicking on the device's field with the left mouse button in the de­vice overview.
Device overview
3. Under "Channel selection is valid for" (see figure to the right), select whether you wish to set the perfor­mance display for this device only (previously clicked on), or for all de­vices of a particular type.
Page 68 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data
z
Device field
Changes color according to the calculated capacity utili (depending on the value defined as 100 %)
Example
4. In the "Available channels" list, select the channel which is to form the basis of the capacity utilization calculation, and is to be reflected in the color behavior of the device fields.
5. Enter the chosen channel using the arrow key ">" in the area
6. In the field to the left of "= 100 %“, enter the value which is to represent 100 % capacity utilization for this channel.
7. Click on < Apply> to save your changes.
You can set the color scheme of the device fields as described in section 10. 5 „Changing the Color Behavior of the Device Fields” (page 72).
User Manual SDC-TEN080642 Page 69
Displaying Data SMA Technologie AG

10. 4 Setting the Communication Quality

In the device overview, the icon in the upper left-hand corner of each device field indicates the quality of communication from the device to the PC. Depending on the communication quality, the icon changes to the levels "Good", "Moderate", or "Poor".
The following adjustments can be made:
Changing the Icon
Changing the Visualization of Communication Quality
1. Select "Options/Settings" or click on the "Settings" icon. The window "Settings" opens.
2. Select "Spotvalue Request / Communication Performance“. The "Set­tings" window opens (see figure above).
3. In the "Type of Device" drop-down list, select the device for which you wish to make the settings.
Changing the Icon
4. Click on <change icons>. The win­dow "bitmap choices" opens.
5. Select the desired icons, and use the arrow buttons to add them to the re­spective areas (see figure to the right).
6. Click on <Ok> to adopt the changes.
Page 70 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data
Changing the Visualization of Communication Quality
7. To specify when the changes are to occur, enter the threshold val­ues in the area "Change in visualiza­tion of the communica­tion performance".
The higher value determines the boundary between "Good" and "Moderate", and the lower value the boundary between "Moderate" and "Poor".
8. Click on <ok> to save the settings.
User Manual SDC-TEN080642 Page 71
Displaying Data SMA Technologie AG

10. 5 Changing the Color Behavior of the Device Fields

The following adjustments are possible for the color behavior of the device fields:
Changing the Color Scheme The device fields change color according to capacity utilization. The capacity uti-
lization is calculated on the basis of a channel (default channel: Pac). The color behavior of the device field during spot value querying is determined by this chan­nel, and by the value for 100 % capacity utilization.
You can change the capacity utilization settings as described in section 10. 3 „Set­ting the Performance Display” (page 68).
Changing the Text Color
Changing the Border Color of the Currently Queried Device
Changing the Icon for the Currently Queried Device (default icon is a question mark, see figure below) The other icons, which are displayed if the device is not currently being queried,
indicate the quality of the communication from the device to the PC, and can also be changed, see section 10. 4 „Setting the Communication Quality” (page 70).
Icon (currently queried device)
Border color
Text color
Background color
Example currently queried device
Page 72 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data
Changing the Color Scheme
1. Select "Options/Settings" or click on the "Settings" icon. The "Settings" window opens.
2. Select "Spotvalue Request / Colored Representation". The "Settings" window opens (see figure below).
3. Click on <Load Scale>.
The "Load Palette for Performance Display" window opens.
4. Select a color palette from the list, and click on Open. To learn how to create your own color palette, see section 13. 6 „Creating a Color Palette for Device Fields” (page 177).
The "Settings" window is displayed with the selected color palette (see figure below).
User Manual SDC-TEN080642 Page 73
Displaying Data SMA Technologie AG
Changing the Text Color
You can define which of the displayed text colors is to be used until which threshold background color is reached. Observe the test text "Test adjustment color representation". You can only use the text colors shown in the test text.
5. Position the cursor over the dividing line above the color palette (see figure be­low). The cursor changes into a cross.
6. Hold down the right mouse button, and move the dividing line to the right or to the left, according to the threshold background color, up to which the displayed text color is to be used.
Changing the Border Color of the Currently Queried Device
7. Click on <Change Color>.
Page 74 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data
The "Colors" window opens (see figure to the right).
8. Click on the desired color.
9. Click on <Ok>, to confirm the settings. The "Settings" win­dow is displayed with the selected border color.
Changing the Icon for the Currently Queried Device
10. Click on <Change Icon>.
The "Bitmap Selection" window opens.
11. Click on the desired graphic.
12. Click on <Ok>. The "Set­tings" window is dis­played once more.
13. Click on <Ok> to save the settings.
User Manual SDC-TEN080642 Page 75
Displaying Data SMA Technologie AG

10. 6 Accessing Individual Device Information

1. In the device overview, click on the selected device with the right mouse button, and se­lect "Single Device Informa­tion".
The single device view is displayed (see figure below).
Drag to enlarge window
If you place the cursor on the lower edge of the window, so that the cursor changes into an arrow which points upwards and downwards, you can alter the size of the window. If all entries are displayed, the scroll bar on the side is no longer shown.
Page 76 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data
The following data are shown in the header of the single device view:
Device Name Here, the predefined inverter type, and the serial number are displayed. If you
change the device name, this name is shown here instead (to change the device name, see section 13.2. 1 „Setting the Device Name and Device ID” (page 172)).
•Serial Number Here, the inverter's serial number is displayed.
Device Type Here, the inverter's device type is displayed.
•Field Position Here, the position of the device field in the device overview is indicated.
Transmission Quality Here, the inverter's transmission quality is indicated in percent, and with the words:
-Good
-Poor
Beneath the header is a list of the channel names and their values. You can specify which channels are to be displayed in the single device view via the channel selection for spot value queries. See section 10. 2 „Selecting Channels for Spot Value Queries” (page 66).
User Manual SDC-TEN080642 Page 77
Displaying Data SMA Technologie AG

10. 7 Setting the Quick Information

If quick information is activated, it is shown in the device overview if you click on a device with the left mouse button and wait briefly.
You can specify which channels are to be shown in the quick information display (see section 10. 2 „Selecting Channels for Spot Value Queries” (page 66)). A maximum of 4 channels can be shown in the quick information display.
1. Select "Options/Settings" or click on the "Settings" icon. The window "Settings" opens.
2. Select "Spotvalue Request / Quick Information“.
Activating / Deactivating Quick Information
3. Beneath "Show quick information of a selected device" (see figure above), you can activate or deactivate the quick information display by using the radio buttons "Yes" or "No".
Page 78 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data
Changing the Properties of Quick Information Text
4. In the "Display Text" area, click on <Change>. The window for setting the font opens.
5. Set the font as desired.
6. Click on <OK> in order to return to the "Settings" window, where you can see a preview of the font (see figure below).
Default text properties
Esample: Preview with settings "Arial" and font size "12"
Click on <Ok> if you wish to apply the settings. If you wish to alter the settings, click on <Change>.
User Manual SDC-TEN080642 Page 79
Displaying Data SMA Technologie AG

10. 8 Configuring the Total Overview

The total overview provides you with a quick overview of your plant's present performance data.
The total overview is updated cyclically. You can select which data are to be displayed from the following list (max. three):
Total output at present (Pac)
Total yield (E-total)
Daily yield (E-today)(Only if a Sunny Boy Control is also selected as device type for the total overview).
Selecting Device Types
Devices are only included in the total overview if they are currently included in the device overview ("Spotvalues" tab), and only if their device type has been selected for the total overview.
1. Select "Options/Settings" or click on the "Settings" icon. The "Settings" window opens.
Enlarge the window (font size adapts automatically)
2. Select "Spotvalue Request / Total Overview".
3. In the area "Selected types of devices for total overview" (see figure above), click on <Change> in order to set the device types for compilation of the total overview.
Page 80 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data
The "Device Type Selection" window opens.
Examples
Copy selected channels from the left-hand field into the right-hand field
Copy all channels from the left-hand field into the right-hand field
Delete selected channels from the right-hand field
Delete all channels from the right-hand field
To select several channels, hold down the "Ctrl" key on your keyboard, and click on the channels with the mouse.
4. Select the desired device types, and use the arrow buttons to copy the device types into the "Selected device types" field. You can also drag and drop the device types into the fields.
5. When finished, click on <Ok> to save your settings.
User Manual SDC-TEN080642 Page 81
Displaying Data SMA Technologie AG
Configuring the Total Overview Display
Example
1. Select the values which are to be displayed. To do so, click on the check box alongside the desired value (e.g. "Show total power", "Show daily yield") and add or remove the check mark.
2. Configure the display of the total overview as desired. The following settings can be adjusted:
Text:Here, you can type in a text for the display (e.g. "Pac" for the total output, and "E-total" for the total yield).
Unit:Here, you can choose between the units W, kW and MW in the drop-down list.
Here, you can set the number of decimal places with which the values are to be displayed (# = no decimal places... #.### = three decimal places).
Factor:Here, you can enter a factor by which the calculated value is to be multiplied.
Here, you can enter a corrective value which is to be added to the calculated value.
3. When finished, click on <Ok> to save the settings.
Page 82 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data
Activate Total Overview
4. Select "Spotvalues / Activate Total Overview". Alternatively, click with the right mouse button in the device overview area, and select "Spotvalues / Activate Total Overview".
Deactivating the Total Overview
If you wish to deactivate the total overview, simply close the total overview window.
Display of Change in Measured Value via Arrow Indicator
A small icon with an arrow is situated in the upper left-hand corner of the total overview. This arrow reflects the trend of the present output (Pac) since the last data update.
The measured value has increased since the previous one.
The measured value has remained the same since the previous one.
The measured value has decreased since the previous one.
User Manual SDC-TEN080642 Page 83
Displaying Data SMA Technologie AG

10. 9 Overview Management

You can create and save several device overviews for each plant. The configuration data, e.g. devices' channel selections, the size and arrangement of the overview window, etc., are saved together with the device overview, and displayed when accessed.
Name of the current device overview (here: Online00, is preset)
The task of completely setting up an overview window with several devices can in some cases be highly complex. To ensure that this effort only needs to be made once, Sunny Data Control provides you with the option of managing different device overviews.
Page 84 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data
As described in the following sections, overview management allows the following actions to be conducted:
Renaming a Device Overview
Copying a Device Overview
Saving a Device Overview
Deleting a Device Overview
Loading a Device Overview
Brief Overview of the Functions
You can call up the overview management window (see example pictured below) via the menu item "Spotvalues / Overview Management".
Displays the name of the current plant
Loads the currently selected Overview
Copies the currently selected Overview
Saves the currently selected Overview
Here, all overviews which have already been created are listed. These overviews can be selected.
Displays the name of the currently selected overview
Deletes the currently selected Overview
Renaming of the currently selected Overview
Here, information about the currently selected overview can be entered.
User Manual SDC-TEN080642 Page 85
Displaying Data SMA Technologie AG

10.9. 1 Renaming a Device Overview

1. Open the window in which the spot value queries are displayed by clicking on the "Spotvalues" tab at the lower edge of the screen.
2. Click on "Spotvalues / Overview Management". The "Overview Management" window opens (see figure below).
You can also call up the window by clicking anywhere on the screen with the right mouse button and selecting "Overview Management".
All device overviews which have already been created are shown in the "Avail­able Plants" list. The device overview "Online00" is the default, and can be re­named.
3. Click on the name of the device overview which you would like to rename.
4. Click on <Rename>. A frame appears around the name of the plant, and it can now be written over.
5. Type in the desired name.
6. Click on <Close> to save the setting.
Page 86 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data

10.9. 2 Copying a Device Overview

1. Open the window in which the spot value queries are displayed by clicking on the "Spotvalues" tab at the lower edge of the screen.
2. Click on "Spotvalues / Overview Management". The "Overview Management" window opens (see figure below).
Example
You can also call up the window by clicking anywhere on the screen with the right mouse button and selecting "Overview Management".
All device overviews which have already been created are shown in the "Avail­able Plants" list.
3. Click on the name of the device overview which you would like to copy.
4. Click on <Save as>. The "New Over­view" window opens.
By default, the overview name shown is always "Online00", or "Online01" etc., depending on whether an overview with the name "Online00" etc. already ex­ists.
5. In the field "Name of the overview", type the desired name for the overview.
6. In the field "Description of the overview", you can type remarks about the over­view. These remarks will also be saved, and provide you with a reference point regarding the saved overview.
7. Click on <Ok> to save the setting.
User Manual SDC-TEN080642 Page 87
Displaying Data SMA Technologie AG

10.9. 3 Saving a Device Overview

If you change a device overview, you must save the settings as follows:
1. Open the window in which the spot value queries are displayed by clicking on the "Spotvalues" tab at the lower edge of the screen.
2. Click on "Spotvalues / Overview Management". The "Overview Management" window opens (see figure below).
You can also call up the window by clicking anywhere on the screen with the right mouse button and selecting "Overview Management".
All device overviews which have already been created are shown in the "Avail­able Plants" list.
3. Click on the name of the device overview for which you would like to save chang­es.
4. Click <Save>.
Page 88 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data

10.9. 4 Deleting a Device Overview

1. Open the window in which the spot value queries are displayed by clicking on the "Spotvalues" tab at the lower edge of the screen.
2. Click on "Spotvalues / Overview Management". The "Overview Management" window opens (see figure below).
You can also call up the window by clicking anywhere on the screen with the right mouse button and selecting "Overview Management".
All device overviews which have already been created are shown in the "Avail­able Plants" list.
3. Click on the name of the device overview which you would like to delete.
4. Click on <Delete>. A prompt win­dow opens.
5. Click on <Yes> to confirm the dele­tion.
The overview management window is displayed once more.
6. Click on <Close> to close the window.
User Manual SDC-TEN080642 Page 89
Displaying Data SMA Technologie AG

10.9. 5 Loading a Device Overview

1. Open the window in which the spot value queries are displayed by clicking on the "Spotvalues" tab at the lower edge of the screen.
2. Click on "Spotvalues / Overview Management". The "Overview Management" window opens (see figure below).
You can also call up the window by clicking anywhere on the screen with the right mouse button and selecting "Overview Management".
All device overviews which have already been created are shown in the "Avail­able Plants" list.
3. Click on the name of the device overview which you would like to load.
4. Click on <Load> to load the selected device overview.
Page 90 SDC-TEN080642 User Manual
SMA Technologie AG Displaying Data

10. 10 Activating / Deactivating Spot Value Querying

You can activate and deactivate the querying of spot values if at least one device is displayed in the device overview.
1. Select "Spotvalues / Spotvalue Request" and click on "Activate" or "Deac­tivate".
You can also call up the window in the following way: click on the device overview with the right mouse button. The device overview menu opens. Se­lect "Spotvalue Request" and click on "Activate" or "Deactivate".
If spot value querying is active, the icon and border of the currently queried device will flash (see figure below).
Icon (currently queried device)
Border
Example currently queried device
During spot value querying, the text shown below is displayed in the bar at the lower edge of the screen (see figure below).
User Manual SDC-TEN080642 Page 91
Managing Data and Saving Data Locally SMA Technologie AG

11 Managing Data and Saving Data Locally

With Sunny Data Control, plant data can be saved in Excel format, and in CSV format. The following sections describe the storage of data in Excel format and in CSV format. If an Inverter is connected to the PC, the data can only be saved as CSV data (SUO Format, SMA-Sunny Online). See section 11. 4 „Direct Data Acquisition from an Inverter” (page 102)

11. 1 Reading Out and Saving Data from Sunny Beam

In order to display the essential key data of a PV system, Sunny Beam has been developed as a cordless tabletop device. Initially, there were no plans for the archiving of data. Thus, as indicated below, the subsequent built-in possibility to record data using Sunny Data Control and Sunny Portal is limited.
Data Archiving with Sunny Data Control
With the Sunny Beam, the data gathered from the entire plant during one month can be archived, but not data from the individual inverters. As the values are only stored in Sunny Beam for one month, you must read out the data with Sunny Data Control once a month.
Data Period
E-day: read out once a month
Yield (EUR): read out once a month
CO2 avoided: read out once a month
Furthermore, Sunny Beam only saves the daily power output (Pac) for the present day. Once a new day begins, the previous day's Pac data are erased. Thus, Pac data must be read out every evening.
Data Period
Pac: read out every evening
(limited utilizability)
Archiving Data with Sunny Portal
With Sunny Data Control, the above-mentioned data can be transferred over to the Sunny Portal.
Because the E-total value can not be recorded using Sunny Beam, the use of this data with Sunny Portal is restricted. Nevertheless, this is indispensable for some views using Sunny Portal. For this reason, it only makes sense to graphically present Sunny Portal's daily energy values (E-day), the avoided CO2 emissions and the yield (EUR) as a monthly overview.
Page 92 SDC-TEN080642 User Manual
SMA Technologie AG Managing Data and Saving Data Locally
The visualization of the daily output (Pac) is possible. Nevertheless, as already mentioned above, the data must be read out nightly.

11. 2 Saving Data in Excel Format

Storage of data in Excel format is the default option, and can be activated and deactivated. The data are saved in the directory in which Sunny Data Control was installed. The default directory is"C:\Programs\SMA\Sunny Data Control\Plants“.
If you wish to save the data in Excel format, all that remains to be done is to select the channels which are to be recorded. This is explained in section 11. 5 „Setting up Sunny Boy Control Channel Recording” (page 107).
Activating or Deactivating Data Storage in Excel Format
1. Select "Options / Settings", or click on the "Settings" icon. The "Set­tings" window opens.
2. Select "Data Storage“.
3. Add or remove the check mark beside "Excel" (see figure above). If the check mark is in place, the data will be saved in Excel format.
4. Click on <Ok> to save the setting.
User Manual SDC-TEN080642 Page 93
Managing Data and Saving Data Locally SMA Technologie AG

11. 3 Saving Data in CSV Format

For storage of data in CSV format, various templates are at your disposal. The CSV files can also be created in a user-defined manner. The following settings are user-definable:
Storage location
•File names
Number of rows of measured values
Line break format
Delimiter symbol (cell separator)
Storage of measured values (which channel in which row, etc.)
Time stamp from time of measurement

11.3. 1 Creating a New CSV Type

The settings for a created CSV type can no longer be altered once the first data have been read and saved.
1. Select "Options/Settings" or click on the "Settings" icon. The "Settings" window opens.
2. Select "Data Storage“.
3. Click on <+> to set a new CSV type.
Page 94 SDC-TEN080642 User Manual
SMA Technologie AG Managing Data and Saving Data Locally
The window for configuration of a new CSV type opens.
4. Type the desired name for the CSV type into the "Name" field.
5. By default, the CSV files are saved in the directory:C:\Documents and Set­tings\“Name of User“\Application Data\SMA\Sunny Data Control\Plants\“Plant name“\“CSV_1 etc.“
This directory is user-specific, and is set up automatically upon creation of a new CSV type. If you wish to select a different directory, click on the folder icon, and select the desired directory.
Selecting a Template
6. Select a template in the "Template" field. The templates have the following properties:
- SMA standard format: Everything freely selectable, except for the file's column
header.
- SMA-Sunny Online (SUO):
Column header as in Excel / SUO files, predefined values, no column selection. Column header as in Sunny Data.
-Power Light:
No column header, predefined values, manual column selection.
- User-defined: Everything freely selectable.
User Manual SDC-TEN080642 Page 95
Managing Data and Saving Data Locally SMA Technologie AG
Insert Mode
Depending on which template you have selected, you can specify the method of insertion.
fixed:The "fixed" mode is used when only certain channels are to be saved. The columns are specified by the user. The selection of columns is set via the <Se-
lect columns> button, as described in the next step.
autotinsert:In "autotinsert" mode, the channels which are set under "Channel recording" are saved. The next section describes how to set the channels for channel recording. See section 11. 5 „Setting up Sunny Boy Control Channel Recording” (page 107). The columns are inserted automatically.
7. In the "Insert mode" field, select one of the two modes for writing measured values to CSV files.
Selecting Columns
Depending on which template you have selected, you can now select the columns.
8. Click on <Select columns...>. The "Select columns" window opens.
9. Click on <New> and select a column type.
Page 96 SDC-TEN080642 User Manual
SMA Technologie AG Managing Data and Saving Data Locally
There are four column types:
- <empty> = column remains empty in the CSV file.
- Channel = allocation occurs via selection of a channel.
- Text = the entered text is written in the column.
- Timestamp = the date pattern from the combination field (combo box) is written
as an absolute date.
You can insert a new column above a highlighted column with <Insert>. With <Delete>, you can delete the highlighted column. With <New>, you can add a new column beneath all the other columns. The order of the rows in the table can be changed using "drag and drop".
10. Depending on the selected column type, you can make various settings for the col­umn type in the "Description" field.
With the column type "Channel", you can select the channels in the "Description" field. For this purpose, the "Channel selection..." window opens.
You can add individual channels, or all of a node's channels together, via drag and drop. You can also click on a channel and add it via the arrow button (see figure below).
User Manual SDC-TEN080642 Page 97
Managing Data and Saving Data Locally SMA Technologie AG
11. Afterwards, click on <Apply> to save the settings. The "Select columns" window is displayed once more.
File name
12. Click on <Details>.
Page 98 SDC-TEN080642 User Manual
SMA Technologie AG Managing Data and Saving Data Locally
13. Select the desired file name pattern from the "File pattern" list, or use the input sym­bols listed below to create a new one, by writing in the "File pattern" field.
In the "Example" area, you see an exam­ple of the respective selected file name pattern.
The structure of the file names comprises
Enlarged section
the input symbols listed below, and the file suffix ".csv".
- {DD} = stands for day (01 to 31 are displayed)
- {MM} = stands for month (01 to 12 are displayed)
- {YYYY} = stands for year (if {YY} is selected, the last two digits of the year are
displayed, e.g. "07“. If {YYYY} is selected, the year is shown in full, e.g. "2007“).
- {NN} = sequential number
- {hh} = stands for hour
- {mm} = stands for minute
- {ss} = stands for second
These input symbols must be between braces { }, so that the input symbols are translated into their respective meanings (e.g. year), and thus the current year will appear at this position in the file name (e.g. {YY} = 07 and {YYYY} = 2007).
The following additional input symbols are also permissible for the file names:
-_ (underscore)
-. (period)
--- (hyphen)
User Manual SDC-TEN080642 Page 99
Managing Data and Saving Data Locally SMA Technologie AG
Further Settings
14. If you have selected the template type "Us­er defined" or "SMA-standard format", you can make the further additional settings for the CSV files. The line break format can be set for all template types.
- Line breaks:Select the line break format
for your PC's operating system:"CRLF“ (0x0d 0x0a) = Windows"LF“ (0x0a) = Mac"CR“ (0x0d) = Unix
- Cell Delimiter:Select the desired cell
delimiter symbol (semicolon, tab (tabulator), or space).
- Maximal lines:Enter the desired maximum number of lines which are to be
displayed in a CSV file. No more than 16000 lines can be written.
- Column Header Type:Select the desired column header type (only possible
with the "User defined" template).
Enlarged section
Page 100 SDC-TEN080642 User Manual
Loading...