SMA Solar Technology AG1 Information on this Manual
1 Information on this Manual
1.1 Validity
This manual describes the procedure for mounting, installation, commissioning, maintenance and
troubleshooting of the following SMA inverters:
• Sunny Tripower 8000TL (STP 8000TL-10)
• Sunny Tripower 10000TL (STP 10000TL-10)
• Sunny Tripower 12000TL (STP 12000TL-10)
• Sunny Tripower 15000TL (STP 15000TL-10)
• Sunny Tripower 17000TL (STP 17000TL-10)
Store this manual where it will be accessible at all times.
1.2 Target Group
This manual is for the use of electrically skilled persons. The tasks described in this manual may be
performed by electrically skilled persons only.
1.3 Additional Information
You will find further information on special topics such as the sizing of a miniature circuit-breaker or
the description of the parameters and measured values at www.SMA.de/en.
Refer to the user manual provided for detailed information on how to operate the inverter.
Installation ManualSTP8-17TL-IA-en-317
Page 8
1 Information on this ManualSMA Solar Technology AG
1.4 Symbols Used
The following types of safety precautions and general information appear in this document:
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate
injury.
NOTICE indicates a situation which, if not avoided, could result in property damage.
Information
An Information block provides valuable hints for the efficient installation and operation of your
product.
☑This symbol indicates the result of an action.
8STP8-17TL-IA-en-31Installation Manual
Page 9
SMA Solar Technology AG2 Safety
2 Safety
2.1 Intended Use
The Sunny Tripower is a PV inverter which converts the direct current of a PV array into alternating
current and feeds this into the electricity grid.
Principle of a PV plant with the Sunny Tripower
String connections on Sunny Tripower 8000TL, 10000TL and 12000TL
The Sunny Tripower 8000TL, 10000TL and 12000TL only have 4 string connections at input A.
The Sunny Tripower may only be operated with PV arrays (PV modules and cabling) of protection
class II. Do not connect any energy sources other than PV modules to the Sunny Tripower.
Capacitive leakage currents
PV modules with large capacities relative to earth, such as thin-film PV modules with cells on a
metal substrate, may only be used if their coupling capacity does not exceed 2.55 μF.
During feed-in operation, a leakage current flows from the cells to earth, the size of which
depends on the manner in which the PV modules are installed (e.g. foil on metal roof) and on
the weather (rain, snow). This "normal" leakage current must not exceed 90 mA, as otherwise
the inverter would automatically disconnect from the electricity grid as a protective measure.
For further information on this subject see the Technical Information "Capacitive Leakage
Currents" at www.SMA.de/en.
Installation ManualSTP8-17TL-IA-en-319
Page 10
2 SafetySMA Solar Technology AG
When designing the PV plant, ensure that the permitted operating range of all components is
complied with at all times. The free design program "Sunny Design", version 2.0 or higher
(see www.SMA.de/en/SunnyDesign) will assist you in this. The manufacturer of the PV modules must
have approved the PV modules for use with the Sunny Tripower. You must also ensure that all
measures recommended by the module manufacturer for the long-term maintenance of the module
properties are taken (see also Technical Information "Module Technology" at www.SMA.de/en).
Do not use the Sunny Tripower for purposes other than those described here. Alternative uses,
modifications to the Sunny Tripower or the installation of components not expressly recommended or
sold by SMA Solar Technology AG void the warranty claims and operation permission.
2.2 Safety Precautions
Danger to life due to high voltages in the inverter
• All work on the inverter must be carried out by skilled persons only.
Risk of burns due to hot enclosure parts
During operation, the upper enclosure lid and the enclosure body may get hot.
• Only touch the lower enclosure lid during operation.
Possible damage to health due to radiation effects
• Maintain a distance of at least 20 cm from the inverter whenever possible.
Earthing of the PV array
Comply with the local regulations for earthing the modules and the PV array.
SMA Solar Technology AG recommends the continuously conductive connection and earthing
of the array frame and other electrically conductive surfaces in order to ensure maximum
protection for property and persons.
10STP8-17TL-IA-en-31Installation Manual
Page 11
SMA Solar Technology AG2 Safety
2.3 Explanation of Symbols
This section gives an explanation of all the symbols found on the inverter and on the type label.
2.3.1 Symbols on the Inverter
SymbolDescriptionExplanation
InverterThis symbol defines the function of the green LED.
The green LED indicates the operating state of
the inverter.
Observe the
documentation
BluetoothThis symbol defines the function of the blue LED.
®
QR Code
Bonus Program
for SMA
This symbol defines the function of the red LED
which indicates a fault or disturbance. Read the
manual to remedy the fault or disturbance.
The blue LED indicates that communication via
Bluetooth is activated.
For information on the SMA bonus programme,
see www.SMA-Bonus.com.
Danger to life due to
high voltages in the
inverter
Stickers on the ESS• When the Electronic Solar Switch is
Installation ManualSTP8-17TL-IA-en-3111
The capacitors in the inverter may be charged
with very high voltages.
• Disconnect the inverter from all voltage
sources (see Section 9) and wait
20 minutes before opening the upper
enclosure lid, in order to allow the
capacitors to discharge.
plugged in, the DC circuit is closed.
• To interrupt the DC circuit and safely
disconnect the inverter when under load,
you must first remove the Electronic Solar
Switch and then all DC connectors
(see Section9 "Disconnecting the Inverter
from Voltage Sources", page63). Only
unplug the Electronic Solar Switch If the
inverter is not displaying any error
message prohibiting the removal of the
ESS and the inverter is not beeping.
Page 12
2 SafetySMA Solar Technology AG
2.3.2 Symbols on the Type Label
SymbolDescriptionExplanation
Danger to l ife due to high
voltages
The product operates at high voltages. All
work on the inverter must be carried out by
skilled persons only.
Risk of burns from hot
surfaces
The product can get hot during operation.
Avoid contact during operation.
Allow the product to cool down sufficiently
before carrying out any work. Wear personal
protective equipment such as safety gloves.
Observe the
documentation
Observe all documentation that is supplied
with the product.
DangerObserve the connection requirements for the
second protective conductor (see
Section6.3.3 "Connecting the Second
Protective Conductor", page33).
Without transformerThe product does not have a transformer.
DCDirect current
ACThree-phase alternating current with neutral
conductor
Degree of protectionThe product is protected against dust intrusion
and water jets from any angle.
OutdoorThe product is suitable for outdoor installation.
WEEE designationDo not dispose of the product together with the
household waste but only in accordance with
the locally applicable regulations for disposal
of electronic waste.
CE markingThe product complies with the requirements of
the applicable EC directives.
Device class IDThe product is equipped with a wireless
component and complies with device class 2.
12STP8-17TL-IA-en-31Installation Manual
Page 13
SMA Solar Technology AG2 Safety
SymbolDescriptionExplanation
RA L qu ali ty m ark for solar
products
The product complies with the requirements of
the German Institute for Quality Assurance
and Certification.
Certified safetyThe product is VDE-tested and complies with
the requirements of the German Equipment
and Product Safety Act.
C-TickThe product complies with the requirements of
the applicable Australian EMC standards.
Korean mark of
conformity
The product complies with the requirements of
the applicable Korean directives.
Installation ManualSTP8-17TL-IA-en-3113
Page 14
3 Product DescriptionSMA Solar Technology AG
3 Product Description
The Sunny Tripower is a multi-string inverter which converts the direct current of a PV array into
alternating current. To do this, the Sunny Tripower is equipped with two separate MPP trackers which
can be connected to the different PV modules. The inverter performs three-phase feed-in of electricity
into the electricity grid. Cooling is effected via the OptiCool active cooling system.
In addition, Sunny Tripower is equipped with the features described below.
3.1 Bluetooth
The inverter is equipped with a serial Bluetooth interface and can communicate with special
SMA communication products and other inverters (for information on supported products,
see www.SMA-Solar.com).
If you would like to communicate via Bluetooth, you can protect the inverter with one plant password
for the user and one plant password for the installer. All inverters are delivered with a standard plant
password for the user (0000) and a standard plant password for the installer (1111).
To protect the plant from unauthorized access, you must change the plant passwords using
Sunny Explorer (for information on changing the plant password, refer to the Sunny Explorer help).
If you do not want to communicate via Bluetooth, deactivate Bluetooth communication
(see Section6.6.1 "Bluetooth", page53).
3.2 Communication Interface
The inverter can optionally be fitted with an extra communication interface (e.g., RS485).
This communication interface enables the inverter to communicate with special SMA communication
products or other inverters (for information on supported products, see www.SMA-Solar.com).
The interface can either be retrofitted or installed at the factory according to a specific order.
You can only set the operating parameters of the inverter via SMA communication products. You can
set the country data set of the inverter via the two rotary switches in the inverter only prior to
commissioning or within the first ten operating hours.
Depending on the type of communication, RS485 or Bluetooth or Speedwire, the parameters and
messages are displayed differently in the communication products.
Example: How the country data set parameter is displayed
• For communication with RS485 parameter: CntrySet
•If you are using Bluetooth or Speedwire: parameter Set country standard
14STP8-17TL-IA-en-31Installation Manual
Page 15
SMA Solar Technology AG3 Product Description
3.3 Multi-Function Interface
The inverter is equipped with a slot for multi-function interfaces. This slot is designed to connect a
simple multi-function relay or an SMA Power Control Module. The interface can either be retrofitted
or installed at the factory according to a specific order.
Multi-function relay
You can configure the multi-function relay for various operating modes. The multi-function relay is
us ed, for exa mpl e, t o switch fau lt i ndi cat ors on o r of f (f or i nformation on installation and configuration,
see installation manual of the multi-function relay).
SMA Power Control Module
The SMA Power Control Module enables the inverter to implement grid management services and is
equipped with an additional multi-function relay (for information on installation and configuration,
see installation manual of the SMA Power Control Module).
3.4 SMA OptiTrac Global Peak
SMA OptiTrac Global Peak is a more advanced form of the MPP tracking tool SMA OptiTrac.
MPP tracking is a feature that determines the highest usable power in the PV plant at any given time.
The power generated by the PV array depends on the level of solar irradiation and the temperature
of the PV modules. As a result, the optimum operating point for maximum power (MPP) changes
constantly throughout the day.
SMA OptiTrac ensures that the operating point of the inverter always coincides exactly with the MPP.
In addition, with the aid of SMA OptiTrac Global Peak, the inverter can detect the presence of several
maximum power points in the available operating range, such as may occur particularly with partially
shaded PV strings. By this means, almost the entire available power of partially shaded PV strings can
be fed into the electricity grid.
SMA OptiTrac Global Peak is deactivated by default. In the case of partially shaded PV modules, it
should be activated and set via a communication product (see Section8.2 "Activating and Setting
SMA OptiTrac Global Peak", page61).
3.5 Surge Arrester Type II
Along with the standardly integrated, thermally monitored varistors, the Sunny Tripower is equipped
with module slots for the additional installation of surge arresters Type II. If the modules are
connected, they will be monitored. If a module has tripped, a warning is issued via the display or
external communication (e.g. Sunny WebBox or Sunny Explorer). This makes it easy to integrate the
Sunny Tripower into a lightning protection concept. The required modules are available as retrofit kits
for input A or input A+B.
Installation ManualSTP8-17TL-IA-en-3115
Page 16
3 Product DescriptionSMA Solar Technology AG
3.6 Intelligent String Failure Detection
The Sunny Tripower is equipped with a system that recognizes the total failure of individual strings or
partial strings (see the diagram below). With a PV module current of approx. 1 A, monitoring of up
to six partial strings per string input is possible. The prerequisite for the reliable functioning of the
intelligent string failure detection is an identical alignment of the connected PV array at input A and
input B. For the learning phase, the Sunny Tripower needs approximately 14 days at moderate
irradiation after successful activation. One advantage of this system is that its auto-adaptive function
completely eliminates the necessity of any configuration. In the event of a string failure, a warning
message is issued on the display or via external communication (e.g. Sunny WebBox or
Sunny Explorer). Note that extreme shading and snow-covered PV modules trip warning messages.
16STP8-17TL-IA-en-31Installation Manual
Page 17
SMA Solar Technology AG3 Product Description
3.7 Electronic String Fuse
The Sunny Tripower is equipped with an electronic string fuse. This prevents dangerous reverse
currents in the PV array and thus plays a key role in fire prevention. Reverse currents can occur as a
result of reverse poling during installation or module defects during operation. The electronic string
fuse recognizes these defects and shorts the PV array. This prevents the occurrence of reverse currents
and thus safeguards both the PV plant and the Sunny Tripower. An advantage of this method is that
conventional fuses at the DC inputs are not necessary. The electronic solution is entirely
maintenance-free and does not require any dimensioning.
In order to make optimum use of this function, particular care must be taken during commissioning
(see Section6.4 "Connecting the PV Array (DC)", page34). The Sunny Tripower signals dangerous
conditions by beeping and issuing warnings in the display or external communication
(see Section12.1 "Sunny Tripower is Beeping", page84). If electrical installation takes place under
conditions of insufficient irradiation (PV voltage less than 188 V), the Sunny Tripower will not have
power supply which means that the protective functions described above will not be active during
installation.
3.8 Grid Management
The inverter is equipped with grid management functions.
Depending on the requirements of the network operator, you can activate and c onfigu re the f unctions
(e.g. provision of reactive power, active power limitation) via operating parameters (for information
on the functions and operating parameters, see the Technical Description "Measured Values and
Parameters" at www.SMA-Solar.com).
Installation ManualSTP8-17TL-IA-en-3117
Page 18
4 UnpackingSMA Solar Technology AG
4 Unpacking
4.1 Scope of Delivery
Check the delivery for completeness and for any visible external damage. Contact your specialist
dealer if anything is damaged or missing.
ObjectQuantity Description
A1Sunny Tripower
B1Electronic Solar Switch (ESS)
C1Rear panel (wall mounting bracket)
D1Set of documents with explanations and certificates
E1Installation manual, including user manual
F1Supplementary sheet with inverter default settings
‒1Installation manual for RS485 communication module (optional)
18STP8-17TL-IA-en-31Installation Manual
Page 19
SMA Solar Technology AG4 Unpacking
ObjectQuantity Description
G10/12DC connector
Sunny Tripower 8000TL/10000TL/12000TL:
10 units (5 x positive, 5 x negative)
Sunny Tripower 15000TL / 17000TL:
12 each (6 x positive, 6 x negative)
H10/12Sealing plug
Sunny Tripower 8000TL/10000TL/12000TL: 10 each
Sunny Tripower 15000TL/17000TL: 12 each
I1Eye bolt (M8) for fastening the Sunny Tripower to the rear panel
K2Cylinder screws (M5x10) for fastening the enclosure to the rear panel
L1Cable gland for AC connection
M1Counter nut for cable gland at AC connection
N1Clamping bracket (M6) for additional earthing
O1Cheese-head screw (M6) for earth terminal
P1Conical spring washer (M6) for earth terminal
Q2Cheese-head screws (M5x20) for upper enclosure lid (spares)
R2Conical spring washers (M5) for enclosure lid screws (spares)
4.2 Identifying the Inverter
You can identify the inverter by the type label. The type label is located on the right-hand side of the
enclosure.
The inverter serial number (Serial No.), the type (Type/Model) and other device-specific
characteristics are specified on the type label.
Installation ManualSTP8-17TL-IA-en-3119
Page 20
5 MountingSMA Solar Technology AG
5 Mounting
5.1 Safety
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
• Do not mount the inverter on flammable construction materials.
• Do not mount the inverter in areas where highly flammable materials are stored.
• Do not mount the inverter in a potentially explosive atmosphere.
Risk of injury due to the heavy weight of the inverter (approx. 65 kg)
• Take the weight of the inverter into account during transport.
• Select a suitable mounting location and mounting surface.
• When mounting the rear panel, use fastening material suitable for the mounting surface.
• Two people are needed to mount the inverter.
Risk of burns due to hot enclosure parts
• Mount the inverter in such a way that it cannot be touched inadvertently.
20STP8-17TL-IA-en-31Installation Manual
Page 21
SMA Solar Technology AG5 Mounting
max. 15°
5.2 Selecting the Mounting Location
Take the following requirements into consideration when selecting the mounting location:
• The mounting method and location must be suitable for the weight and size of the inverter
(see Section14 "Technical Data", page95).
• Mount on a solid surface.
• The mounting location must be clear and safely accessible at all times without the use of
additional aids such as scaffolding or lifting platforms. If this is not the case, service work may
be restricted.
• Mount vertically or tilted backwards by max. 15°.
• The connection area must point downwards.
• Never mount the device with a forward tilt.
• Never mount the device with a sideways tilt.
• Do not mount horizontally.
• Install the inverter at eye level. Given the weight of the device, this will facilitate disassembly for
service work.
• The ambient temperature should be below 40°C to ensure optimum operation.
• Do not expose the inverter to direct solar irradiation as this could cause power derating due to
overheating.
• In order to avoid audible vibrations in living areas, do not mount the unit on plasterboard walls
or similar. When in operation, the inverter emits noise which may be perceived as annoying in
living areas.
Installation ManualSTP8-17TL-IA-en-3121
Page 22
5 MountingSMA Solar Technology AG
• Observe the recommended clearances to walls,
other inverters or other objects, as shown in the
diagram. That ensures sufficient heat dissipation
and gives you enough space to unplug the
Electronic Solar Switch.
• If multiple inverters are mounted in areas with high
ambient temperatures, allow more than the
recommended clearances between the inverters
and ensure an adequate fresh-air supply. This will
prevent the inverter from reducing its power as a
result of high temperatures (details on temperature
derating can be found in the Technical Information
"Temperature Derating" at www.SMA.de/en).
5.3 Mounting the Inverter with Rear Panel
1. Use the rear panel as a drilling template and mark the positions of the drill holes.
22STP8-17TL-IA-en-31Installation Manual
Page 23
SMA Solar Technology AG5 Mounting
Display
2. Mount the rear panel.
To do this, use one upper hole on the right and one
on the left plus the hole in the middle.
Installation ManualSTP8-17TL-IA-en-3123
Page 24
5 MountingSMA Solar Technology AG
A
3. Hook the inverter into the rear panel, ensuring that
the inverter enclosure is positioned flush against the
rear panel.
– For two peop le t o trans por t th e in ver ter, hol d th e
inverter by the recessed grips at the bottom and
the top edge of the enclosure lid.
– For transport by crane, you can attach 2 ring
bolts to the top of the inverter (see A: M10,
diameter = 10 mm). To do this, remove the
filler-plugs and screw in the ring bolts as far as
they will go.
4. Remove the ring bolts after transport and re-attach
the filler-plugs.
5. Release all 6 captive screws of the lower enclosure
lid.
6. To remove the lower enclosure lid, lift it from the
bottom.
24STP8-17TL-IA-en-31Installation Manual
Page 25
SMA Solar Technology AG5 Mounting
7. Screw the supplied eye bolt into the hole provided
in order to secure the enclosure from being
dislodged. The eye bolt only needs to be fastened
hand-tight.
8. In order to secure the enclosure on the rear panel,
fasten it at the bottom with the two M5x10
cheese-head screws supplied
(torque: max. 3.5 Nm).
9. Check to ensure that the inverter is securely in place.
☑ The inverter is now securely mounted to the wall.
If the inverter is not to be connected immediately, re-attach the lower enclosure lid:
– Dock the lower enclosure lid at an angle and
attach. The captive screws must protrude.
– Pre-fasten all six screws and then tighten them in
the sequence shown on the right
(torque: 2.0 Nm).
Installation ManualSTP8-17TL-IA-en-3125
Page 26
5 MountingSMA Solar Technology AG
Optional Anti-Theft Protection
To protect the inverter from theft, you can secure it to the rear panel with a padlock.
The padlock must meet the following requirements:
•Size:
A: 6 mm … 8 mm diameter
B: 23 mm … 29 mm
C: 23 mm … 28 mm
D: 39 mm … 50 mm
E: 13 mm … 18 mm
•Stainless
• Hardened shackle
• Protected lock cylinder
Storage of the key
Keep the key in a safe place in case it is needed for service purposes.
1. Put the shackle of the padlock through the eye of
the previously mounted eye bolt and close the
padlock.
☑ The inverter is now protected against theft.
26STP8-17TL-IA-en-31Installation Manual
Page 27
SMA Solar Technology AG6 Electrical Connection
6 Electrical Connection
6.1 Safety
Electrostatic discharge can damage the inverter
Internal components of the inverter can be irreparably damaged by electrostatic discharge.
• Earth yourself before touching any components.
6.2 Overview of the Connection Area
ObjectDescription
ADC lid (slots for surge arresters and varistors are located here)
BPlug for connecting the multi-function relay
CPlug for connecting the RS485 communication module (optional)
DTerminal for grid connection
EJumper for setting the language to English
FRotary switch for setting the Bluetooth NetID
GScrew for releasing and raising the display
HRotary switches for setting the country standard and display language
ICable entry for the multi-function relay (M20, 5 mm … 13 mm)
KSlot for SD card (for service purposes only)
Installation ManualSTP8-17TL-IA-en-3127
Page 28
6 Electrical ConnectionSMA Solar Technology AG
ObjectDescription
AElectronic Solar Switch (ESS) socket
BCable entry for the multi-function relay (M20, 5 mm … 13 mm)
CCable entries for communication via RS485 (M32) (optional)
DAdditional cable entry (M20)
ECable entry for grid connection (AC) (M32, 14 mm … 25 mm)
FDC connectors for connecting the strings (input area B)
GDC connectors for connecting the strings (input area A)
(for Sunny Tripower 8000TL/10000TL/12000TL only 4 each)
28STP8-17TL-IA-en-31Installation Manual
Page 29
SMA Solar Technology AG6 Electrical Connection
6.3 Connecting the Electricity Grid (AC)
6.3.1 Conditions for the AC Connection
You must comply with the connection requirements of your network operator.
Residual current device
The inverter is equipped with an integrated all-pole-sensitive residual-current monitoring unit.
The inverter can automatically differentiate between residual currents and normal leading leakage
currents.
If an external RCD or residual-current device is strictly required, you must use a switch that trips at a
residual current of 100 mA or higher.
You will find further information on using an RCD in the Technical Information "Criteria for Selecting
a Residual-Current Device" at www.SMA.de/en.
Cable Dimensioning
The cable must be dimensioned in accordance with any local and national directives on cable
dimensions which specify requirements for the minimum conductor cross-section. Cable dimensioning
factors are e.g.: nominal AC current, type of cable, type of routing, cable bundling, ambient
temperature and maximum specified line losses (for calculation of line losses, see design software
"Sunny Design" with software version 2.0 or higher at www.SMA-Solar.com).
Cable Requirements
PositionDescriptionValue
ACable diameter14 mm … 25 mm
BConductor
cross-section
CStripping lengthapprox. 12 mm
The PE wire must be 5 mm longer than the L and N wires.
Installation ManualSTP8-17TL-IA-en-3129
1.5 mm² … 16 mm², with bootlace ferrule maximum 10 mm²
Page 30
6 Electrical ConnectionSMA Solar Technology AG
Connection of a second protective conductor
In some installation countries, a second protective conductor is required in order to prevent a contact
current in the event of failure of the original protective conductor.
For installation countries falling within the scope of validity of the IEC standard 62109, the following
requirements are applicable:
• Installation of protective conductor at the AC terminal with a conductor cross-section of at least
10 mm² Cu.
or
• Installation of a second protective conductor at the earth terminal with the same cross-section as
the original protective conductor at the AC terminal (see Section6.3.3 "Connecting the Second
Protective Conductor", page33).
You must always observe the applicable regulations in the country of installation.
Load disconnection unit
You must install a separate miniature circuit-breaker for each inverter in order to ensure that the
inverter can be securely disconnected under load. You should use a 3-pole miniature circuit-breaker.
If you are using a 1-pole miniature circuit-breaker, a residual voltage from the inverter may be present
on the relevant cable after disconnection (maximum permissible fuse protection (see Section14
"Technical Data", page95)).
Danger to life due to fire
When more than 1 inverter is connected in parallel to the same miniature circuit-breaker, the
protective function of the miniature circuit-breaker is no longer guaranteed. This could result in a
cable fire or destruction of the inverter.
• Never connect several inverters to a single miniature circuit-breaker.
• Observe the maximum permissible fuse protection of the inverter when selecting the miniature
circuit-breaker.
Danger to life due to fire
When a generator (inverter) and a load are connected to the same miniature circuit-breaker, the
protective function of the miniature circuit-breaker is no longer guaranteed. The currents from the
inverter and the electricity grid can accumulate to form overcurrents which are not detected by the
miniature circuit-breaker.
• Never connect loads between the inverter and the miniature circuit-breaker without fuse
protection.
• Always protect loads separately.
30STP8-17TL-IA-en-31Installation Manual
Page 31
SMA Solar Technology AG6 Electrical Connection
Damage to the inverter by use of screw-type fuses as switch-disconnectors
A screw-type fuse, e.g. DIAZED fuse or NEOZED fuse, is not a switch-disconnector and thus
may not be used as a load disconnection unit. A screw-type fuse only acts as cable protection.
If the inverter is disconnected under load using a screw-type fuse, the inverter may be damaged.
• Use only a switch-disconnector or a miniature circuit-breaker as a load disconnection unit.
6.3.2 AC Connection Procedure
1. Check the line voltage and compare it with the permissible voltage range (see Section14
"Technical Data", page95).
2. Disconnect the miniature circuit-breaker from all three phases and secure against reconnection.
3. Release all 6 captive screws of the lower enclosure
lid.
4. To remove the lower enclosure lid, lift it from the
bottom.
5. Check that the country setting of the inverter is correct using the supplementary sheet provided
with the default settings.
Installation ManualSTP8-17TL-IA-en-3131
Page 32
6 Electrical ConnectionSMA Solar Technology AG
L1 L2 L3 N
N
PE
L3
L1
L2
If the inverter is not set to the desired country standard, adjust the country standard by means
of the rotary switches (see Section6.5.3 "Setting the Country Stan dar d an d La ngu age usin g th e
Rotary Switch", page52).
6. Remove the adhesive tape from the AC enclosure opening.
7. Insert the AC cable gland from the outside into the
cable entry and tighten it from the inside with the
counter nut.
8. Pull the cable through.
9. Raise the terminals of the AC clamp terminal as far
as they will go.
Risk of fire if 2 conductors are connected
If 2 conductors are connected to one terminal, a poor electrical contact may present a risk of
overheating or fire.
• Never connect more than one conductor per terminal.
10. Connect L1, L2, L3, N and the protective conductor
(PE) to the AC terminal in accordance with the
labelling.
– The PE conductor must be 5 mm longer than the
L and N conductors.
– L and N must not be swapped.
– The direction of rotation of L1, L2 and L3 is not
relevant.
Danger of crushing when terminals snap shut
The terminals close by snapping down fast and hard.
• P res s th e te rmi nal s do wn w ith you r th umb , do not g rip the sid es o f th e te rmi nal bet ween fin ger s
and thumb.
• Keep fingers away from the terminals.
11. Close all terminals of the AC terminal until they snap into place.
32STP8-17TL-IA-en-31Installation Manual
Page 33
SMA Solar Technology AG6 Electrical Connection
12. Screw the cap nut of the cable gland down tightly
on the cable entry.
Danger to life due to high voltages in the inverter
• Do not switch on the miniature circuit-breaker until the PV array has been connected and the
inverter is securely closed.
6.3.3 Connecting the Second Protective Conductor
If req uir ed b y th e in sta lla tio n, t he e arth ter min al c an b e us ed to connect a second protective conductor
or as equipotential bonding.
Procedure
1. Take t he cla mping brac ket, cheese-he ad screw M6
an d co nic al s pri ng w ash er M 6 ou t of the acc ess ory
kit.
2. Insert the stripped earthing cable (D) under the
clamping bracket (C) (cross-section: max. 16 mm²).
3. Screw the terminal (C) tight with the screw (A). The
toothing of the conical spring washer (B) must face
toward the clamping bracket.
Installation ManualSTP8-17TL-IA-en-3133
Page 34
6 Electrical ConnectionSMA Solar Technology AG
6.4 Connecting the PV Array (DC)
6.4.1 Conditions for DC Connection
The inverter has two input areas "A" and "B", each with its own MPP tracker.
Up to 4 strings (Sunny Tripower 8000TL/10000TL/12000TL) or 5 strings (Sunny Tripower 15000TL/
17000TL) can be connected at input area A. One string can be connected at input area B.
• For input area A, the PV modules must meet the following requirements:
– same type
– same number of in-series-connected PV modules
– identical alignment
– identical tilt
• For the activation of the intelligent string failure detection, the PV modules at input A and B must
be identically aligned.
• The connecting cables of the PV modules must be equipped with connectors. The connectors
required for DC connection are included in the scope of delivery.
34STP8-17TL-IA-en-31Installation Manual
Page 35
SMA Solar Technology AG6 Electrical Connection
Use of Y adaptors for the parallel connection of strings
Y adaptors must not be visible or freely accessible in close proximity to the inverter.
• The DC electric circuit must not be interrupted by Y adaptors.
• Observe the procedure for disconnecting the inverter (see Section9 "Disconnecting the
Inverter from Voltage Sources", page63).
• The following thresholds at the DC input of the inverter must not be exceeded:
Sunny
Tripower
Maximum input voltage
(DC)
Maximum input current
(MPP) (DC)
Maximum short-circuit
current per string input
(DC)
Input area A/BA1 … A5 / B
8000TL1,000 V22.0 A / 11.0 A33 A / 12.5 A
10000TL1,000 V22.0 A / 11.0 A33 A / 12.5 A
12000TL1,000 V22.0 A / 11.0 A33 A / 12.5 A
15000TL1,000 V33.0 A / 11.0 A40 A / 12.5 A
17000TL1,000 V33.0 A / 11.0 A40 A / 12.5 A
Risk of fire as a result of overcurrent on the string input
Destruction of the inverter
Since the electronic string fuse shorts the PV array in the event of a fault, the thresholds for the
maximum short-circuit current per string input given in the table above must not be exceeded.
If a string input is overloaded, it can result in an electric arc and hence a risk of fire.
• Make sure that the thresholds specified in the table above are not exceeded.
• Check whether the short-circuit currents of the connected PV modules are in compliance with
the thresholds given in the table above.
Installation ManualSTP8-17TL-IA-en-3135
Page 36
6 Electrical ConnectionSMA Solar Technology AG
Function of the electronic string fuse
The electronic string fuse prevents reverse currents in the PV array. Activation of the electronic string
fuse is only possible if the following conditions are met:
• During installation, the DC input voltage must be at least 188 V (see Section14 "Technical
Data", page95) in order to activate the protective function of the integrated electronic string
fuse. Otherwise, a reversed polarity at the DC connection or a defective string will not be
recognized by the inverter.
Risk of fire in the PV array due to non-recognition of reverse currents
The integrated electronic string fuse monitors the PV array and protec ts it ag ainst dangerou s rever se
currents. In order to activate the electronic string fuse, you must observe the following during
connection of the strings:
• If more than 2 strings are connected to the inverter, ALWAYS connect the first string to input B. If no string is connected at input B, the string fuse will not be active.
• Each string must be clearly assigned to the correct string input. D o not cr oss-wire or bun dle the
string cables. See the diagram in Section 6.4.1 for the correct assignment of the strings.
Use of external string collection boxes
If string collection boxes are used, the functionality of the electronic string fuse may be limited.
36STP8-17TL-IA-en-31Installation Manual
Page 37
SMA Solar Technology AG6 Electrical Connection
......
6.4.2 Assembling the DC Connectors
For connection to the inverter, all connection cables of the PV modules must be equipped with the
DC connectors provided.
Assemble the DC connectors as follows. Be sure to observe the correct polarity. The DC connectors
are marked with the symbols "+" and "‒".
Cable Requirements
• Use a PV1-F cable.
Procedure
1. Lead the stripped cable all the way into the plug.
2. Push the clamping bracket down.
☑ The clamping bracket clicks audibly into place.
3. Ensure that the cable is correctly positioned:
Installation ManualSTP8-17TL-IA-en-3137
Page 38
6 Electrical ConnectionSMA Solar Technology AG
ResultMeasure
☑ If the stranded wire is visible in the
• Proceed to step 4.
chamber of the clamping bracket, the
cable is correctly positioned.
☑ If the stranded wire is not visible in the
chamber, the cable is not correctly
positioned.
• Release the clamping bracket. To do so,
insert a 3.5 mm screwdriver into the
clamping bracket and lever it open.
• Remove the cable and go back to step 1.
4. Push the swivel nut up to the thread and tighten (torque: 2.0 Nm).
☑ The DC connectors are assembled and ready for connection to the inverter (see Section6.4.4
"Connecting the PV Array (DC)", page40).
38STP8-17TL-IA-en-31Installation Manual
Page 39
SMA Solar Technology AG6 Electrical Connection
6.4.3 Opening the DC Connector
1. Unscrew the swivel nut.
2. To release the DC connector: Insert a 3.5 mm
screwdriver into the snap slot on the side and lever
it open.
3. Carefully pull the DC connector apart.
4. Release the clamping bracket. To do this, use a
3.5 mm screwdriver.
5. Remove the cable.
☑ The cable is now detached from the DC connector.
Installation ManualSTP8-17TL-IA-en-3139
Page 40
6 Electrical ConnectionSMA Solar Technology AG
6.4.4 Connecting the PV Array (DC)
Danger to life due to high voltages in the inverter
• Before connecting the PV array, ensure that the AC miniature circuit-breaker is switched off for
all 3 phases.
Risk of electric arc if the DC connectors are pulled out while the Sunny Tripower is
beeping
The integrated electronic string fuse monitors the PV array. In case of incorrect installation
(e.g. reverse polarity) or a faulty string, the electronic string fuse short-circuits the PV array and the
Sunny Tripower starts to beep.
•Do NOT pull the DC connector out as this could trip an electric arc.
•Do NOT pull out the Electronic Solar Switch as otherwise the entire reverse current will flow
through the defective string which could result in a fire.
• Further procedure (see Section12.1 "Sunny Tripower is Beeping", page84).
Destruction of the inverter due to overvoltage
If the voltage of the PV modules exceeds the maximum input voltage of the inverter, it could be
destroyed by overvoltage. This will void all warranty claims.
• Do not connect any strings to the inverter which have an open-circuit voltage greater than the
maximum input voltage of the inverter.
• Check the plant design.
Excessive voltages can destroy the multimeter
• Only use multimeters with a DC input voltage range up to at least 1,000 V.
40STP8-17TL-IA-en-31Installation Manual
Page 41
SMA Solar Technology AG6 Electrical Connection
1. Check the connection cables of the PV modules for
correct polarity and make sure that the maximum
input voltage of the inverter is not exceeded.
At an ambient temperature over 10°C, the
open-circuit voltage of the PV modules should not
exceed 90% of the maximum input voltage of the
inverter. If this is not the case, review the plant
design and the PV module circuitry.
Otherwise, the maximum inverter input voltage may
be exceeded at low ambient temperatures.
2. Check strings for earth faults (see Section12.2
"Checking the PV Array for Earth Faults", page85).
3. Check the Electronic Solar Switch for wear, as
described in Section 10.3. Providing it is in perfect
condition, plug the Electronic Solar Switch in right
up to the stop. The Electronic Solar Switch must be
aligned parallel to and flush with the enclosure.
Only plug the Electronic Solar Switch during
installation when the enclosure lid is open. This is
necessary in order to activate the protective
function of the integrated electronic string fuse.
Risk of fire in the PV array due to non-recognition of reverse currents
The integrated electronic string fuse monitors the PV array and protec ts it ag ainst dangerou s rever se
currents. In order to activate the electronic string fuse, you must observe the following during
connection of the strings:
• If more than 2 strings are connected to the inverter, ALWAYS connect the first string to input B. If no string is connected at input B, the string fuse will not be active.
• Each string must be clearly assigned to the correct string input. D o not cr oss-wire or bun dle the
string cables. See the diagram in Section 6.4.1 for the correct assignment of the strings.
Installation ManualSTP8-17TL-IA-en-3141
Page 42
6 Electrical ConnectionSMA Solar Technology AG
Use of external string collection boxes
If string collection boxes are used, the functionality of the electronic string fuse may be limited.
4. If more than 2 strings are to be connected, check
the first assembled DC connector to ensure correct
polarity and connect to input B of the inverter.
☑The DC connector clicks audibly into place.
To release the DC connector (see Section6.4.3
"Opening the DC Connector", page39).
5. After connecting the string, watch out for messages
in the display and any acoustic signals.
Only continue if the following conditions are fulfilled:
– The green LED is glowing or flashing.
– There is NO acoustic signal after 30 seconds.
– NONE of the error messages 40, 64 or 82 are shown in the display.
Otherwise follow the relevant instructions in the following table:
EventMeasure
After 60 seconds, the
display is blank and the
Sunny Tripower is not
beeping although the DC
input voltage is over 188 V.
There is a fault in the Sunny Tripower.
• Ensure that the DC cables have not been reverse poled.
•Ensure that DC input voltage of over 188 V is present.
• Contact the SMA Service Line (see Section16 "Contact",
page126)
42STP8-17TL-IA-en-31Installation Manual
Page 43
SMA Solar Technology AG6 Electrical Connection
EventMeasure
The Sunny Tripower starts
beeping.
The Sunny Tripower short-circuits the PV array.
• On no account disconnect the Electronic Solar Switch or
the DC connectors. Wait until the Sunny Tripower stops
beeping (after dark).
Pu lli ng t he D C co nnector s ca use s a r isk of a rci ng, sin ce t he
Sunny Tripower short-circuits the PV array in order to
prevent reverse currents through individual strings.
Depending on the level of irradiation, this could trigger
current flows. However, the PV array and the
Sunny Tripower are in a safe state.
• Before leaving the Sunny Tripower, install a contact
barrier (e.g., fence) and moisture protection
(e.g., tarpaulin).
• Wait until dark before pulling out the Electronic Solar Switch
and all DC connectors, and only then eliminate any errors
(reversed pole or defective string).
The display is showing the
error message 40, 64 or
• Follow the instructions on the display (see Section11.2
"Error messages", page74).
82.
6. Follow the same procedure to connect all further
strings.
It is no longer necessary to wait 60 seconds.
7. Ensure that all DC connectors are securely in place.
Number of Strings - Sunny Tripower 8000TL / 1000TL / 12000TL
The Sunny Tripower 8000TL / 10000TL / 12000TL have only 4 strings at input A.
Installation ManualSTP8-17TL-IA-en-3143
Page 44
6 Electrical ConnectionSMA Solar Technology AG
8. In order to seal the inverter, all DC inputs that are
not required have to be closed as follows:
– Insert the sealing plugs provided into the DC
connectors that are not required. Do not insert
sealing plugs into the DC inputs on the inverter.
– Insert the DC connectors with sealing plugs into
the corresponding DC inputs on the inverter.
9. If the Sunny Tripower does not beep or display an
error message, disconnect the Electronic Solar
Switch.
☑ The display switches off.
☑ You can now commission the inverter (see Section7 "Commissioning", page58). The following
connections and settings are optional.
44STP8-17TL-IA-en-31Installation Manual
Page 45
SMA Solar Technology AG6 Electrical Connection
6.5 Setting the Country Standard and Display Language
The inverter can be configured for various countries. This is carried out via the two rotary switches in
the inverter prior to commissioning, or by configuring the "CntrySet" or "Set country standard"
parameter via a communication product (z. B. Sunny WebBox or Sunny Explorer) once you have
commissioned the inverter.
The switch position 0/0 indicates the state upon delivery. If you have ordered the inverter with specific
count ry settings, th ey will hav e already b een preset at the factory via a c ommunicat ion produc t. In this
case, you will not be able to recognise the current setting by the switch position. If changes are made
via the rotary switches or via a communication product, the default grid parameters are overwritten.
They cannot be restored, and must be re-entered via a communication product. The display language
ca n be cha nge d at any tim e us ing the rota ry s wit che s, i nde pen dent of the grid parameters. This means
that the default grid parameters remain unchanged, but the display messages are shown in the set
language. For devices ordered without any specified country of installation, the standard setting is
"VDE0126-1-1" and the language is German.
Changes will be accepted immediately after switching the miniature circuit-breaker on. If a
non-programmed switch setting is selected, the inverter issues an error message on the display and
the last valid setting is retained.
SMA Grid Guard-Protected Country Data Sets
In some countries, the local connection conditions demand a mechanism which prevents the feed-in
parameters from being changed. Therefore, some country data sets are protected and can only be
unlocked with a personal access code, the SMA Grid Guard code.
SMA Grid Guard protected country data sets are automatically blocked for 10 feed-in hours after
commissioning, or after the last alteration. If the country data set is changed after these 10 feed-in
hours, the inverter will not accept the changes and display the error message "Grid parameter
locked". If, however, a later change to the country data set only relates to a change of the display
language via the rotary switches in the inverter, this change is immediately applied.
Installation ManualSTP8-17TL-IA-en-3145
Page 46
6 Electrical ConnectionSMA Solar Technology AG
It is also p ossible to conf igure country data s ets (parameter "CntrySet" or "Set country standard"), and
to lock or unlock these manually via a communication product. To lock a data set, enter the digit
sequence "54321" instead of the password in the SMA Grid Guard code field. The data set can only
be unlocked by entering a personal, 10-digit SMA Grid Guard code which is valid for a maximum of
10 feed-in hours. The application form for the personal access code is available at
www.SMA.de/en, in the "Certificate" category of the respective inverter. The language can be
configured without a password, regardless of the country data set.
Changing parameters in SMA Grid Guard-protected country data sets
If the para meter s withi n protec ted cou ntry da ta sets are chan ged, t hes e ar e no long er p rot ect ed
and instead of the standard, "ADJ" or "Special setting" is displayed. In this case, a change to
parameters is not locked automatically after 10 feed-in hours, but has to be locked manually.
To manually lock the parameters, set the SMA Grid Guard Code to "54321".
Further information on parameter settings
You will find information on making adjustments and changing parameters in the user manual
for your software.
The last change (executed via rotary switch or communication product) is always verified and
activated if applicable. Consequently, the switch position may not necessarily show the actual country
setting.
46STP8-17TL-IA-en-31Installation Manual
Page 47
SMA Solar Technology AG6 Electrical Connection
6.5.1 Checking the Country Standard
Check whether the inverter is set to the country of installation.
Before commissioning:
• Check that the country standard of the inverter is correct by comparing the default settings of
the inverter listed on the supplementary sheet provided.
After commissioning:
• Check that the country standard is correct by checking the display message during
(re-)commissioning (see Section7 "Commissioning", page58).
or
• Check that the country standard is correct using the "SMA grid guard" measuring channel via
a communication product.
Display language
Once you have set the country standard, you can always set the display language later using
rotary switch B. However, you have to then set rotary switch A to "0" in order to keep the
country data set.
The settings of each country data set are specified in the operating parameters. The parameters can
be read out using a communication product. The description of the operating parameters is available
at www.SMA.de/en in the category "Technical Description" of the respective inverter.
(A) (B)Country data setDisplay language Grid Guard
protection
00default settingsdefault settingsdependent on
parameter set
01retainedEnglishdependent on
parameter set
02retainedGermandependent on
parameter set
03retainedFrenchdependent on
parameter set
04retainedSpanishdependent on
parameter set
05retainedItaliandependent on
parameter set
06retainednot assigned*dependent on
parameter set
Installation ManualSTP8-17TL-IA-en-3147
Country
dependent on
parameter set
dependent on
parameter set
dependent on
parameter set
dependent on
parameter set
dependent on
parameter set
dependent on
parameter set
dependent on
parameter set
Page 48
6 Electrical ConnectionSMA Solar Technology AG
(A) (B)Country data setDisplay language Grid Guard
Country
protection
07retainednot assigned*dependent on
parameter set
12VDE-AR-N4105
a)
14VDE-AR-N4105-MP
16VDE-AR-N4105-HP
b)
c)
GermanyesGermany
GermanyesGermany
GermanyesGermany
dependent on
parameter set
10VDE0126-1-1GermanyesGermany,
Switzerland
18VDE0126-1-1FrenchyesSwitzerland,
France
19VDE0126-1-1/UTE
d)
FrenchyesFrance
20VDE0126-1-1ItalianyesSwitzerland
28AS4777.3EnglishnoAustralia
32CEI0-21Ext
e)
ItaliannoItaly
40RD1663-ASpanishyesSpain
41RD1663/661SpanishyesSpain
48PPCnot assigned*noGreece
49PPCEnglishnoGreece
51KEMCO 501/2009EnglishnoSouth Korea
58G83EnglishnoEngland
5AG59/2EnglishnoEngland
60EN50438Germanyesvarious EU
61EN50438Englishyes
countries
62EN50438Frenchyes
63EN50438Italianyes
64EN50438Spanishyes
65EN50438not assigned*yes
66EN50438not assigned*yes
74PPDSnot assigned*yesCzech
Republic
75PPDSEnglishyesCzech
Republic
48STP8-17TL-IA-en-31Installation Manual
Page 49
SMA Solar Technology AG6 Electrical Connection
(A) (B)Country data setDisplay language Grid Guard
Country
protection
76PPDSGermanyesCzech
Republic
78C10/11FrenchyesBelgium
79C10/11EnglishyesBelgium
7AC10/11GermanyesBelgium
A0MVtg-DirectiveGermanyesGermany
A1MVtg-DirectiveEnglishyesflexible
A2MVtg-DirectiveFrenchyesFrance
A3MVtg-DirectiveSpanishyesSpain
A4MVtg-Directivenot assigned*yesCzech
Republic
A8CN/CGC/
EnglishnoChina
GF001:2009**
ACSI 4777EnglishyesIsrael
B0MVtg-Directive intGermanyesGermany
B1MVtg-Directive intEnglishyesflexible
B2MVtg-Directive intFrenchyesFrance
B3MVtg-Directive intSpanishyesSpain
B4MVtg-Directive intnot assigned*yesCzech
Republic
C0CustomerEnglishnoflexible
C1CustomerGermannoflexible
C2CustomerFrenchnoflexible
C3CustomerSpanishnoflexible
C4CustomerItaliannoflexible
C5Customernot assigned*noflexible
C6Customernot assigned*noflexible
D0Off-Grid60Englishnoflexible
D1Off-Grid60Germannoflexible
D2Off-Grid60Frenchnoflexible
D3Off-Grid60Spanishnoflexible
D4Off-Grid60Italiannoflexible
Installation ManualSTP8-17TL-IA-en-3149
Page 50
6 Electrical ConnectionSMA Solar Technology AG
(A) (B)Country data setDisplay language Grid Guard
Country
protection
D5Off-Grid60not assigned*noflexible
D6Off-Grid60not assigned*noflexible
E0Off-Grid50Englishnoflexible
E1Off-Grid50Germannoflexible
E2Off-Grid50Frenchnoflexible
E3Off-Grid50Spanishnoflexible
E4Off-Grid50Italiannoflexible
E5Off-Grid50not assigned*noflexible
E6Off-Grid50not assigned*noflexible
F0SD-CardSD-Cardnoflexible
a)Configurable from Firmware Version 2.31. Setting in accordance with VDE-ARN-4105
(Germany) for PV plants < 3.68 kVA
b)Configurable from Firmware Version 2.31. Setting in accordance with VDE-ARN-4105
(Germany) for PV plants > 3.68 kVA and < 13.8 kVA
c)Configurable from Firmware Version 2.31. Setting in accordance with VDE-ARN-4105
(Germany) for PV plants > 13.8 kVA
d)Special setting: Bluetooth transmission power reduced (in accordance with French standards)
e)Configurable from Firmware Version 2.50. Setting according to CEI 0-21 for PV plants with external grid and plant
protection > 6 kVA (Italy)
*Currently not assigned. The previously configured display language is maintained.
**Planned
If the inverter is not set to the country of installation, there are several ways of configuring the required
country standard:
• Setting via the two rotary switches (see Section6.5.3 "Setting the Country Standard and
Language using the Rotary Switch", page52).
• Alternatively, you can carry out the settings via the "CntrySet" or "Set country standard"
parameters using a communication product, once you have commissioned the inverter.
•If you require adjusted parameter settings for your installation site, you can change these with
the help of a communication product.
50STP8-17TL-IA-en-31Installation Manual
Page 51
SMA Solar Technology AG6 Electrical Connection
6.5.2 Extension of the Deactivation Limits
The deactivation criteria (voltage, frequency) are specified by the country parameters.
Sunny Tripower inverters have the additional country data set "MVtgDirective". This parameter
expands the deactivation limits of the inverter for voltage and frequency to a maximum/minimum. This
country setting may only be selected if the plant or the inverter is operated with external three-phase
decoupling protection, which will automatically disconnect the inverter from the electricity grid if
non-permissible voltage and frequency values occur. Device protection is still guaranteed.
Danger to life due to electric shock if external decoupling protection is missing
With the country setting "MVtgDirective", the inverter may only be operated with an external
three-phase decoupling protection device which complies with the country-specific requirements.
Without such external decoupling protection, the inverter will not disconnect from the electricity grid
when the standard requirement is exceeded.
6.5.3 Setting the Country Standard and Language using the
Rotary Switch
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources",
page63).
2. Set the arrows on the rotary switches (A and B) to
the required position using a screwdriver
(see Section6.5.1 "Checking the Country
St and ard", pa ge47). Use a screw dri ver with bla de
width 2.5 mm.
Jumper for English language
You can also adjust the language to English by
means of a jumper (e.g. for service purposes).
• To do so, plug the jumper onto the upper two
pins as shown on the right.
3. Restart the inverter (see Section7 "Commissioning", page58).
52STP8-17TL-IA-en-31Installation Manual
Page 53
SMA Solar Technology AG6 Electrical Connection
6.6 Communication
6.6.1 Bluetooth
Communication via Bluetooth with a communication product is activated by default. Networking with
other inverters via Bluetooth is deactivated by default.
The following setting options are possible via a rotary switch:
Switch position
(NetID)
0Off
1Communication via Bluetooth with communication product possible, no
2 … FNetworking with other inverters
In order to restrict communication via Bluetooth between the inverters of your plant and those of
neighbouring plants, you can assign an individual NetID to the inverters of your plant (switch position
2 … F). However, this is only necessary if neighbouring plants are situated within a radius of 500 m.
So that all inverters in your plant are detected by your communication product, all inverters must have
the same NetID.
Plant password for user and installer
If you are using Bluetooth communication, you can protect the inverter with a plant password
for the user and a plant password for the installer. All inverters are delivered with the same
default plant password. To protect the plant from unauthorized access, you must change plant
passwords using a communication product.
If you are not using Bluetooth communication, deactivate it. This will protect your plant from
unauthorized access.
Changing the plant time
If communication is effected via Bluetooth and Sunny Explorer, you must change the plant time
(date and time) via a communication product after commissioning. This will prevent
disturbances when retrieving saved events.
Setting
networking with other inverters (default setting)
Installation ManualSTP8-17TL-IA-en-3153
Page 54
6 Electrical ConnectionSMA Solar Technology AG
To do this, proceed as follows:
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources",
page63).
2. Set the arrow on the rotary switch (C) to the
required position with a screwdriver. Use a
screwdriver with blade width 2.5 mm.
3. Restart the inverter (see Section7 "Commissioning", page58).
Activation of settings
The Bluetooth settings will only be activated after the miniature circuit-breaker has been
switched on, the PV array connected and the Electronic Solar Switch plugged in.
54STP8-17TL-IA-en-31Installation Manual
Page 55
SMA Solar Technology AG6 Electrical Connection
6.7 Retrofitting a Surge Arrester Type II
The inverter can be equipped ex works with surge arresters, or they can be retrofitted at a later time. The
order numbers for both retrofit kits (1 for input A only, 1 for input A and B) can be found in Section 15.
To carry out retrofitting, proceed as follows:
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources",
page63).
Danger to life due to high voltages in the inverter
Death from electric shock
There is residual voltage in the inverter. The inverter takes 20 minutes to discharge.
• Wait 20 minutes before you open the upper enclosure lid or the DC lid.
2. Unscrew the captive screws of the DC lid on the
left-hand side of the connection area.
3. Lift the DC lid up from the bottom to remove it.
4. Plug all surge arresters into the slots provided until
they snap into place with the side latches.
Installation ManualSTP8-17TL-IA-en-3155
Page 56
6 Electrical ConnectionSMA Solar Technology AG
– The surge arrester marked "PE 500" must be
inserted in the bottom slot.
– If surge arresters are only required for input A,
the two surge arresters must be mounted on the
two upper slots.
– If input B is also to be protected, surge arresters
must be plugged into all slots.
– A green strip in the window (A) indicates that
the surge arrester is fully functional. A red strip
in the win dow indi cat es t hat the surg e ar rest er i s
faulty. In this case, a warning also appears in
the display with the event number "83".
5. Dock the DC lid at an angle, and attach. The
captive screws must protrude.
56STP8-17TL-IA-en-31Installation Manual
Page 57
SMA Solar Technology AG6 Electrical Connection
6. Pre-screw all 4 screws of the DC lid and then tighten
them (torque: 3.5 Nm).
☑ The surge arresters are now installed and the inverter can be re-commissioned (see Section7
"Commissioning", page58).
Installation ManualSTP8-17TL-IA-en-3157
Page 58
7 CommissioningSMA Solar Technology AG
7 Commissioning
7.1 Commissioning the Inverter
1. Check that the device is fixed securely to the wall (see Section5 "Mounting", page20).
2. Check that the country configuration is correct (see Section6.5 "Setting the Country Standard
and Display Language", page45).
3. Check that the AC grid cable is connected correctly (see Sect ion6.3 "Connecting the Electricity
Grid (AC)", page29).
4. Check that the DC cables (PV strings) are connected correctly (see Section6.4 "Connecting the
PV Array (DC)", page34).
5. Close unused DC inputs with the appropriate DC connectors and sealing plugs
(see Section6.4.4 "Connecting the PV Array (DC)", page40).
6. Close all enclosure entries.
7. Dock the lower enclosure lid at an angle and
attach. The captive screws must protrude.
8. Pre-screw all six screws and then tighten them in the
sequence shown on the right (torque: 2.0 Nm).
58STP8-17TL-IA-en-31Installation Manual
Page 59
SMA Solar Technology AG7 Commissioning
9. Plug the Electronic Solar Switch in firmly right up to
the stop.
10. Switch on the miniature circuit-breaker.
11. If a multi-function relay is connected, switch on the supply voltage.
12. Check whether the display and LEDs are indicating a normal operating state.
LEDColourMeaning
AGreenGlowing: operation
Flashing: waiting for
sufficient irradiation
BRedDisturbance
CBlueBluetooth communication is
active
☑ If the inverter has been commissioned successfully, the green LED should be on or flashing,
provided there is sufficient solar irradiation.
The significance of a glowing red LED and of the event numbers on the display is described in
Section 11.2.
Installation ManualSTP8-17TL-IA-en-3159
Page 60
7 CommissioningSMA Solar Technology AG
Language english
7.2 Display Messages during the Start Phase
Illustrated display messages
The display messages illustrated in this section serve as examples and, depending on the
country setting, may differ from the actual display messages on your inverter.
• The firmware version of the internal processors
appears first in the text line.
• After an interval of 5 seconds, or after tapping on
the enclosure lid, the serial n umb er (o r de sig nat ion )
of the inverter and the NetID for communication via
Bluetooth will appear. The designation of the
inverter can be changed with a communication
product.
• After a further 5 seconds or a further tap, the
configured country standard is displayed
(example: "VDE0126-1-1").
• After a further 5 seconds or another tap, the
configured language is displayed
(example: "Language English").
• During normal operation, the text line of the display will subsequently be blank. See Section 11
for event messages which may be displayed in the text line and their meaning.
Showing display messages again (valid from Firmware Version 2.33)
If you want to view the display messages of the start-up phase again during normal operation,
tap the enclosure lid twice in quick succession.
60STP8-17TL-IA-en-31Installation Manual
Page 61
SMA Solar Technology AG8 Configuration
8 Configuration
8.1 Changing the Plant Time and Plant Password
Requirements:
•A computer with Bluetooth interface must be available.
• Sunny Explorer with software version 1.04 or higher must be installed on the computer.
• The plant must be logged in Sunny Explorer.
1. Change the standard plant password (see Sunny Explorer help). This will protect your plant
from unauthorized access.
2. Change the plant time (see Sunny Explorer help).
8.2 Activating and Setting SMA OptiTrac Global Peak
With partially shaded PV modules, you should activate SMA OptiTrac Global Peak and set the time
interval in which the inverter will optimise the MPP of the PV plant.
Requirements:
• A communication product that is appropriate for the type of communication used must be
available.
1. Access the user interface of the communication product and log in as an installer.
2. Select the parameter Power limit of the OptiTrac Global Peak and set to On.
3. Select the parameter Cycle time of the OptiTrac Global Peak algorithm an d se t th e de sired
time interval. Hint: The ideal time interval is normally six minutes. This value should only be
increased if the shading situation changes extremely slowly.
☑ The inverter optimises the MPP of the PV plant at the specified time interval.
Installation ManualSTP8-17TL-IA-en-3161
Page 62
8 ConfigurationSMA Solar Technology AG
8.3 Activating the Intelligent String Failure Detection
The intelligent string failure detection process is deactivated by default. You can activate the string
failure detection by setting a parameter via communication (e.g. Sunny WebBox or Sunny Explorer).
To do this, you will need the installer password.
Activating or deactivating string failure detection
ParameterSettingDescription
Op.PvProMod/
Operating mode of
string failure detection
Resetting the operating data for string failure detection
ParameterDescription
Op.PvValRsIstl/
Reset operating data for
string failure detection
StopString failure detection deactivated
StrgFltDet/
Detect string failures
PaStrgFltDet/
Detect sub-string failures
Restart of learning phase
Operating data for string failure detection are reset.
String failure detection activated
String and sub-string failure detection
activated
62STP8-17TL-IA-en-31Installation Manual
Page 63
SMA Solar Technology AG9 Disconnecting the Inverter from Voltage Sources
9 Disconnecting the Inverter from Voltage Sources
9.1 Safety
Danger to life due to high voltages in the inverter
Death from electric shock
The inverter operates at high voltages and must be disconnected prior to carrying out work on the
device. Furthermore, if the DC connectors are pulled out without first unplugging the Electronic Solar
Switch, a dangerous electric arc can occur.
• Disconnect the inverter as described in the following section.
Risk of burns due to hot DC lid
During operation, the DC lid on the left-hand side of the connection area can get hot.
• Take care not to touch the DC lid when working in the connection area.
Electrostatic discharge can damage the inverter
Internal components of the inverter can be irreparably damaged by electrostatic discharge.
• Earth yourself before touching any components.
Installation ManualSTP8-17TL-IA-en-3163
Page 64
9 Disconnecting the Inverter from Voltage SourcesSMA Solar Technology AG
9.2 Procedure
1. Disconnect the miniature circuit-breaker from all three phases and secure against reconnection.
2. If a multi-function relay is connected, disconnect its supply voltage and ensure that it cannot be
reconnected.
3. Check the status of the Sunny Tripower:
EventMeasure
The Sunny Tripower is beeping or there is
an error message on the display prohibiting
the removal of the Electronic Solar Switch.
The Sunny Tripower is not beeping and
there is no error message on the display.
4. Wait until the LEDs, display and fault indicator have gone out.
5. Release all six captive lid screws.
• Wait until the Sunny Tripower stops
beeping (after dark) and only then
disconnect the Electronic Solar Switch
and the DC connectors.
• Rectify the fault (see Section12.1
"Sunny Tripower is Beeping", page84)
or (see Section11.2 "Error messages",
page74).
• Remove the Electronic Solar Switch.
• Proceed to step 4.
6. To remove the lower enclosure lid, lift it up from the
bottom.
64STP8-17TL-IA-en-31Installation Manual
Page 65
SMA Solar Technology AG9 Disconnecting the Inverter from Voltage Sources
PE
7. Use a suitable multimeter to verify the absence of
voltage for L1, L2 and L3 to N at the AC terminal.
The maximum diameter of the test probe is 2 mm.
☑If voltage is present, check the installation.
8. Verify the absence of voltage in L1, L2 and L3
against PE at the AC terminal.
☑If voltage is present, check the installation.
9. Verify the absence of voltage in the multi-function
relay against PE at all terminals.
☑If voltage is present, check the installation.
Installation ManualSTP8-17TL-IA-en-3165
Page 66
9 Disconnecting the Inverter from Voltage SourcesSMA Solar Technology AG
10. Release and disconnect all DC connectors. To do
this, insert a flat-blade screwdriver (blade width:
3.5 mm) into one of the side slots and pull the DC
connectors out straight.
Do NOT PULL ON THE CABLE.
☑ All DC connectors are disconnected from the
inverter. The inverter is completely disconnected
from the PV array.
Danger to life due to high voltages in the inverter
There is residual voltage in the inverter. The inverter takes 20 minutes to discharge.
• Wait 20 minutes before you open the upper enclosure lid or the DC lid.
☑ The inverter is now dead and work can be carried out.
66STP8-17TL-IA-en-31Installation Manual
Page 67
SMA Solar Technology AG10 Maintenance and Cleaning
10 Maintenance and Cleaning
10.1 Cleaning the Inverter
Damage to the display by use of cleaning agents
• If the inverter is dirty, clean the enclosure lid, the display and the LEDs using only clear water
and a cloth.
10.2 Checking Heat Dissipation
If the inverter regularly goes into derating due to excessive heat (temperature symbol on the display
illuminates), this may be due to one of the following reasons:
• The ventilation grids on the sides are clogged with dirt.
Clean the ventilation grids as described in the following.
• One of the fans is clogged.
The inverter has 2 integrated fans for cooling. One of these is located at the bottom of the
inverter next to the connection area and the other on the left-hand side of the enclosure under
the ventilation grid.
If the fan enclosure is just covered in loose dust you can clean it with a vacuum cleaner. If you
do not achieve satisfactory results with a vacuum cleaner, you can dismantle the fan for
cleaning, as described in the following sections.
Installation ManualSTP8-17TL-IA-en-3167
Page 68
10 Maintenance and CleaningSMA Solar Technology AG
10.2.1 Cleaning the Ventilation Grids
The inverter takes cooling air in from underneath on the left side and blows it out again through the
ventilation grids at the top. Clean the ventilation grids if they are dirty.
Procedure
1. Turn the rotary fastener of the ventilation grid in the
direction of the arrow until the notch is in a vertical
position.
2. Remove the ventilation grid.
3. Clean the ventilation grid with a soft brush, a paint
brush or compressed air.
4. Re-attach the ventilation grid to the inverter.
5. Turn the notch of the rotary fastener back 90° to a
horizontal position.
Risk of damage to the inverter through intrusion of insects
• The ventilation grids must not be removed permanently, because otherwise the device will not
be protected against the intrusion of insects.
68STP8-17TL-IA-en-31Installation Manual
Page 69
SMA Solar Technology AG10 Maintenance and Cleaning
10.2.2 Cleaning the Fan at the Bottom of the Inverter
(STP 15000TL and STP 17000TL only)
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources",
page63).
2. Wait for the fan to stop rotating.
Cleaning the fan guards
3. To dismantle the fan guard:
– Use a screwdriver to press both latches at the
right edge of the fan guard to the right and
dislodge it from the retainer.
– Carefully remove the fan guard.
4. Cl ean the fan g uard wit h a soft bru sh, a pa int bru sh,
a cloth or compressed air.
Cleaning the Fans
5. Press the latches in towards the centre.
6. Remove the fan by pulling it slowly and carefully
downwards.
7. Release and remove the plug.
Th e fa n cable s ar e lo ng enoug h to let you lif t th e fan
out sufficiently to disconnect the plugs inside the
inverter.
8. Remove the fan and clean it with a soft brush, a paint brush or a cloth and water.
Installation ManualSTP8-17TL-IA-en-3169
Page 70
10 Maintenance and CleaningSMA Solar Technology AG
Damage to the fan through use of compressed air
• Do not use compressed air to clean the fan. This could damage it.
9. After cleaning, reassemble everything in reverse order.
10. Check that the fan is functional (see Section10.2.4 "Checking the Fans", page71).
10.2.3 Cleaning the Fan on the Left-hand Side of the Inverter
Enclosure
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources",
page63).
2. Turn the rotary fastener of the ventilation grid in the
direction of the arrow until the notch is in a vertical
position.
3. Remove the ventilation grid.
4. Wait for the fan to stop rotating.
5. Press the latches in towards the centre.
6. Remove the fan by pulling it slowly and carefully
out sideways.
70STP8-17TL-IA-en-31Installation Manual
Page 71
SMA Solar Technology AG10 Maintenance and Cleaning
7. Release and remove the plug.
Th e fa n cable s ar e lo ng enoug h to let you lif t th e fan
out sufficiently to disconnect the plugs inside the
inverter.
8. Remove the fan and clean it with a soft brush, a
paint brush or a cloth and water.
Damage to the fan through use of compressed air
• Do not use compressed air to clean the fan. This could damage it.
9. After cleaning, reassemble everything in reverse order.
10. Check that the fans are functional (see Section10.2.4 "Checking the Fans", page71).
10.2.4 Checking the Fans
Checking the fans
To test the fans you wil l need a special data capture dev ice (e.g., Sunny WebBox) or a PC with
appropriate software (e.g., Sunny Explorer) so that you can change the parameters of the
inverter.
You will also need the installer password to access the installer mode.
1. Enter the installer password.
2. Set the parameters "CoolSys.FanTst" or "Fan test" to "On" in the installer mode.
3. Check the air flow in both fans.
The inverter takes cooling air in from underneath on the left side and blows it out again through
the ventilation grids at the top. Listen for any unusual noise, which could indicate incorrect
installation or a fault in the fans.
4. After the test, set the parameter "CoolSys.FanTst" or "Fan test" back to the "Off" position.
☑ The fan test is now complete.
Installation ManualSTP8-17TL-IA-en-3171
Page 72
10 Maintenance and CleaningSMA Solar Technology AG
10.3 Checking the Electronic Solar Switch (ESS) for Wear
Check the Electronic Solar Switch for wear before plugging it in.
To do this, check whether the metal tongues (A) inside the plug display any brown discolouration.
If the metal tongues are discoloured or burnt right through (B), the Electronic Solar Switch can no
longer perform reliable disconnection of the DC side.
You must replace the handle of the Electronic Solar Switch before restarting the inverter. You can
ob tai n re placeme nt h and les for the E lec tro nic So lar Swi tch from your specialist dealer (see Section15
"Accessories", page125).
72STP8-17TL-IA-en-31Installation Manual
Page 73
SMA Solar Technology AG11 Messages
11 Messages
No display messages if no DC voltage present
Measurements and the display of messages are only possible when there is sufficient
DC voltage (green LED flashing or glowing).
11.1 Event Messages
During an update, the relevant display message is shown in the text line of the display.
MessageDescription
< Inst. code valid >The SMA Grid Guard code entered is valid.
The configured country data set is now unlocked
and can be changed.
If the configured country data set is protected,
the unlocking is valid for a maximum of
10 feed-in hours.
< No new update SDcard >There is no relevant update file for this
Sunny Tripower on the SD card, or the present
update has already been executed.
< Grid param.unchanged >The selected switch setting is not programmed or
there is no country data set available on the
SD card.
< Parameters set successfully >All parameters of the SD card, e.g. country data
set, have been successfully adopted.
< SD card is read >The inverter is currently reading the SD card.
< Set parameter >The inverter is configuring the parameters from
the SD card settings.
< Self-test >The inverter is carrying out the self-test.
< Update completed >The inverter has successfully completed the
update.
< Update Bluetooth >Update of the Bluetooth component successful.
< Update display >Update of the display successful.
< Update main CPU >Update of the inverter component successful.
< Update communication >Update of communication component successful.
< Update string prot. >Update of electronic string fuse successful.
< Update RS485I module >Update of communication interface successful.
< Upd. language table >Update of language table successful.
< Update file OK >The update file found is valid.
Installation ManualSTP8-17TL-IA-en-3173
Page 74
11 MessagesSMA Solar Technology AG
11.2 Error messages
The text line on the display shows the relevant display messages whenever an error occurs. Two-digit
event numbers corresponding to the displayed messages are shown above the text line, and
three-digit or four-digit event numbers in the text line directly in front of the display message. You can
scroll down multi-line messages by tapping on the lower enclosure lid.
If the error exists over a long period of time, the red LED lights up and the multi-function relay is
activated.
In addition, depending on the severity of the disturbance
the "spanner" or "telephone receiver" symbol on the
display will light up.
• Spanner: signifies a disturbance which can be
remedied on-site (see table below).
• Telephone receiver: signifies device disturbance.
Contact SMA Service Line.
Event no. Display message and causeCorrective measures
101 …
103
202 …
203
< Grid fault >
The line voltage has exceeded the
permissible range. This error can have the
following causes:
• The line voltage at the termination
point of the inverter is too high.
• The grid impedance at the
termination point of the inverter is
too high.
The inverter disconnects from the electricity
grid for safety reasons.
< Grid fault >
The line voltage has fallen below the
permissible range. This error can have the
following causes:
• Electricity grid disconnected
• AC cable damaged
• The line voltage at the termination
point of the inverter is too low.
The inverter disconnects from the electricity
grid for safety reasons.
• Check the line voltage and grid
connection on the inverter.
If the lin e vo lta ge i s ou tsi de t he p erm iss ibl e
range due to local grid conditions, ask
your network operator if the voltage can
be adjusted at the feed-in point or if it
would be acceptable to change the
monitored operating limits.
If the line voltage is within the tolerance
range, yet this error is still displayed,
contact the SMA Service Line.
• Check the tripping of the miniature
circuit-breaker.
• Check the line voltage and grid
connection on the inverter.
If the lin e vo lta ge i s ou tsi de t he p erm iss ibl e
range due to local grid conditions, ask
your network operator if the voltage can
be adjusted at the feed-in point or if it
would be acceptable to change the
monitored operating limits.
If the line voltage is within the tolerance
range, yet this error is still displayed,
contact the SMA Service Line.
74STP8-17TL-IA-en-31Installation Manual
Page 75
SMA Solar Technology AG11 Messages
Event no. Display message and causeCorrective measures
301< Grid fault >
The 10-minute-average line voltage is no
longer within the permissible range.
This can be caused by one of the
following:
• The line voltage at the termination
point of the inverter is too high.
• The grid impedance at the
termination point of the inverter is
too high.
The inverter disconnects from the grid to
• Check the line voltage at the
termination point of the inverter:
If, due to local grid conditions, the line
voltage exceeds the configured treshold,
ask the network operator whether the
voltage can be adjusted at the feed-in
point, or whether it would be acceptable
to modify the treshold for power quality
monitoring.
If the line voltage is continually within the
tolerance range, and this error is still
displayed, contact the SMA Service Line.
maintain power quality.
401, 404 < Grid fault >
The inverter is no longer in grid-parallel
operation and has stopped feed-in for
• Check the grid connection for
strong, short-term frequency
variations.
safety reasons.
501< Grid fault >
The power frequency is not within the
permissible range. The inverter
disconnects from the electricity grid for
safety reasons.
• If possible, check the power
frequency and observe how often
major fluctuations occur.
If there are frequent fluctuations and this
error occurs as a result, ask your network
operator if it would be acceptable to
change the operating parameters.
Discuss the proposed parameters with the
SMA Service Line.
601< Grid fault >
The internal monitoring function of the
inverter has detected an excessively high
proportion of direct current in the line
current.
• Check the grid connection for direct
current.
• If this event occurs often, check with
the network operator whether it is
possible to raise the threshold for
monitoring.
Installation ManualSTP8-17TL-IA-en-3175
Page 76
11 MessagesSMA Solar Technology AG
Event no. Display message and causeCorrective measures
701< Frq. not permitted >
< Check parameter >
The power frequency is outside the
permissible range. The inverter
disconnects from the electricity grid for
safety reasons.
• As far as possible, check the power
frequency and observe how often
major fluctuations occur.
If there are frequent fluctuations and this
error occurs as a result, ask your network
operator if it would be acceptable to
change the operating parameters.
Discuss the proposed parameters with the
SMA Service Line.
The inverter has detected an error in the
AC cabling and cannot connect to the
electricity grid. The reason for this could be
an incorrect country setting.
• Check AC installation
• Eliminate connection error
(see Section6.3 "Connecting the
Electricity Grid (AC)", page29).
• Check that the country setting is
correct:
– Via rotary switch
(s ee Secti on 6.5 .1 "Che cki ng t he
Country Standard", page47)
– Via communication: set the
parameter "CntrySet" or "Set
country standard"
1501< Reconnection fault grid >
The measured voltage or frequency is too
high or too low for connection to the
electricity grid.
Possibly, a changed country data set or
changed parameters do not correspond to
the local requirements for connecting to
the electricity grid.
• Check that the country setting is
correct:
– Via rotary switch
(s ee Secti on 6.5 .1 "Che cki ng t he
Country Standard", page47)
– Via communication: set the
parameter "CntrySet" or "Set
country standard"
• Check whether the voltage and
frequency of the electricity grid are
within the limits of the configured
country data set.
• If individual parameters within a
country data set have been
changed, re-select the original
country data set for the country of
installation.
76STP8-17TL-IA-en-31Installation Manual
Page 77
SMA Solar Technology AG11 Messages
Event no. Display message and causeCorrective measures
3301 …
3303
3401,
3402
< Unstable operation >
There is not enough power at the DC input
of the inverter for stable operation. This
may be caused by snow on the PV
modules.
< DC overvoltage >
< Disconnect generator >
The DC input voltage connected to the
inverter is too high.
• Wait until irradiation is higher.
• If this event recurs at medium
irradiation levels, check the PV plant
design and the correct circuitry of
the PV array.
• Immediately disconnect the
inverter from the PV array
(see Section9 "Disconnecting
the Inverter from Voltage
Sources", page63)! The inverter
may otherwise be destroyed.
• Check that the DC voltage of the
strings adheres to the maximum
input voltage of the inverter before
reconnecting the inverter to the PV
array.
3501< Earth fault >
< Check generator >
The inverter has detected an earth fault in
the PV array.
• Check strings for earth faults (see
Section12.2 "Checking the PV
Array for Earth Faults", page85).
• The installer of the PV array must
remedy any earth faults before the
affected string is reconnected.
3601< High discharge curr. >
< Check generator >
The leakage current from the inverter and
the PV array is too high.
This may be caused by a sudden earth
fault, a residual current or malfunction, or
the earth capacitance of the PV plant is too
high.
• Check strings for earth faults
(see Section12.2 "Checking the PV
Array for Earth Faults", page85).
• The installer of the PV array must
remedy any earth faults before the
affected string is reconnected.
• Check whether the leakage current
from the PV modules is too high.
The inverter interrupts feed-in operation
immediately after exceeding a threshold
and then automatically reconnects to the
electricity grid.
3701< Resid.curr.too.high >
< Check generator >
The inverter has detected a residual
current through brief earthing of the PV
array.
• Check strings for earth faults
(see Section12.2 "Checking the PV
Array for Earth Faults", page85).
• The installer of the PV array must
remedy any earth faults before the
affected string is reconnected.
Installation ManualSTP8-17TL-IA-en-3177
Page 78
11 MessagesSMA Solar Technology AG
Event no. Display message and causeCorrective measures
3801,
3802
< DC overcurrent >
< Check generator >
On the DC side of the inverter, an
If this event occurs frequently:
• Check the design and the circuitry of
the PV array.
overcurrent has been detected and the
inverter has briefly interrupted feed-in.
3901,
3902
< Waiting for DC start conditions >
< Start cond. not met >
The input power or input voltage of the PV
modules is insufficient for feeding into the
electricity grid.
• Wait until irradiation is higher.
• If necessary, increase the voltage
limit for the start of feed-in if the event
occurs frequently in the morning
(parameter setting via
communication).
• If this event recurs at medium
irradiation levels, check the PV plant
design and the correct circuitry of
the PV array.
4001< String X defect. >
< Do not disconn. ESS >
Th e "X" sta nds for the affe cted st ring. Th ere
are either reverse currents in the string or
the string polarity is reversed. Further
strings may also be affected. The PV array
is short circuited.
In exceptional circumstances, this error
message may be triggered by soiling or
shading of the modules (e.g., by leaves or
snow).
• Disconnect the inverter after dark
(see Section9 "Disconnecting the
Inverter from Voltage Sources",
page63).
• Check the design and the circuitry of
the PV array (see Section6.4.1
"Conditions for DC Connection",
page34).
• If irradiation is sufficient, check
whether the same voltage is present
at the string inputs A1 to A5.
If not, one of the PV modules is
possibly defective.
4002< String X low power
• Check the string indicated.
< Check generator >
The "X" stands for the affected string. The
string monitoring has either failed or
detected a weak string.
78STP8-17TL-IA-en-31Installation Manual
Page 79
SMA Solar Technology AG11 Messages
Event no. Display message and causeCorrective measures
4003< String X defect. >
< Check generator >
The "X" stands for the affected string. This
string polarity is either reversed or the
string has failed. Further strings may also
be affected. The PV array is not short
circuited.
• Disconnect the inverter
(see Section9 "Disconnecting the
Inverter from Voltage Sources",
page63).
• Check the design and the circuitry of
the PV array (see Section6.4.1
"Conditions for DC Connection",
page34).
• Check whether the same voltage is
present at the strings inputs
A1 to A5.
• If not, one of the PV modules is
possibly defective.
4005< Part.str. X low p. >
• Check the part string indicated.
< Check generator >
The "X" stands for the affected substring
The string monitoring has either failed or
detected a weak substring.
6001 …
6009,
6101 …
< Self diagnosis > or
< Interference device >
• Contact the SMA Service Line
(see Section16 "Contact",
page126)
• Replace surge arrester
(see Section12.4 "Replacing Surge
Arresters Type II", page90).
At least one surge arrester is defective.
8401
< Overheating >
< Disconn. device from generator and grid >
Device disturbance due to overheating in
• Contact the SMA Service Line
(see Section16 "Contact",
page126)
the inverter. The inverter disconnects on
the AC and DC sides.
9002< Inst. code invalid >
The SMA Grid Guard code entered
• Enter a valid SMA Grid Guard
code.
(personal installer password) is not valid.
82STP8-17TL-IA-en-31Installation Manual
Page 83
SMA Solar Technology AG11 Messages
Event no. Display message and causeCorrective measures
9003< Grid param. locked >
The current country data set is locked.
9005< Changing grid param. not possible >
< Ensure DC supply >
• DC voltage at the DC input is not
sufficient to run the main CPU.
• The selected rotary switch setting for
the language settings is not
• E nte r a v ali d SM A Gr id G uar d co de
for changing the country data set.
• Ensure that sufficient DC voltage is
available (green LED glowing or
flashing).
• Check the setting of the rotary
switches (see Section 5.4.2).
• Enter the SMA Grid Guard code.
programmed.
• The parameters to be changed are
protected.
9007< Abort self-test >
There is either an error in the AC
installation or the configured voltage and
frequency limits do not comply with the
requirements of the Italian electricity grids.
• Check AC installation.
• Eliminate connection error
(see Section6.3 "Connecting the
Electricity Grid (AC)", page29).
• Check that the country setting is
correct (see Section6.5 "Setting the
Country Standard and Display
Language", page45).
The self-test is only required for
installations in Italy.
Installation ManualSTP8-17TL-IA-en-3183
Page 84
12 TroubleshootingSMA Solar Technology AG
12 Troubleshooting
12.1 Sunny Tripower is Beeping
Electric shock due to electric arc when pulling out the DC connectors
Death or serious burns
The Sunny Tripower has short-circuited the PV array to avoid reverse currents.
• Strictly adhere to the procedure as described in the following table.
CauseEvent number on
the display
Installation fault (reverse
polarity of a string or
connection of strings with
different numbers of modules)
OR
Reverse current in the PV
plant (defective string)
The Sunny Tripower
short-circuits the PV array to
avoid reverse currents through
individual strings. Depending
on the level of irradiation, this
could trigger high current flows.
However, the PV array and the
Sunny Tripower are in a safe
state.
Sunny Tripower is defective 64xx or 8201 …
4001 … 4003 or
4005
8203
Measure
• On no account pull the Electronic
Solar Switch or DC connectors out.
Wait until the Sunny Tripower stops
beeping (after dark).
If you pul l th e DC conn ect ors , th ere is a
risk of electric arcing.
• With an open Sunny Tripower: Prior to
leaving the Sunny Tripower, install
contact protection (e.g., fence) and
moisture protection (e.g., tarpaulin).
• Wait until dark before pulling out the
Electronic Solar Switch and all DC
connectors, and only then eliminate
any errors (reversed-pole or defective
string).
• Contact the SMA Service Line
(see Section16 "Contact", page126)
84STP8-17TL-IA-en-31Installation Manual
Page 85
SMA Solar Technology AG12 Troubleshooting
12.2 Checking the PV Array for Earth Faults
If the inverter displays event numbers "3501", "3601" or "3701", there is a high probability of an
earth fault in the PV array.
Check the strings for earth faults as described below:
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources",
page63).
Danger to life due to live PV array.
• Only touch the cables of the PV array by their insulation.
• Do not connect strings with earth faults to the inverter.
Excessive voltages can destroy the multimeter
• Only use multimeters with a DC input voltage range up to at least 1,000 V.
2. Measure the voltages between the positive pole of
each string and the earth potential (PE).
3. Measure the voltages between the negative pole of
each string and the earth potential (PE).
4. Measure the voltages between the positive and
negative poles of each string.
Installation ManualSTP8-17TL-IA-en-3185
Page 86
12 TroubleshootingSMA Solar Technology AG
☑ An earth fault is present if the measured voltages are stable and the sum of the voltages of
the positive pole against earth potential and the negative pole against earth potential of a
string is approximately equal to the voltage between the positive and negative poles.
ResultMeasure
☑ You have detected an earth fault.• The installer of the PV array must remedy
the earth fault in the affected string. You
can determine the location of the earth
fault as described below.
• Do not reconnect the faulty string.
• Restart the inverter (see Section7
"Commissioning", page58).
☑You have not detected any earth fault. It is likely that one of the thermally monitored
varistors is defective.
• Check varistors (see Section12.3
"Checking the Function of the Varistors",
page87).
Location of the Earth Fault
The approximate location of the earth fault can be calculated from the ratio of the voltages
measured between plus and earth potential and minus and earth potential.
Example:
In this case, the earth fault is between the 2nd and 3rd PV modules.
☑ The earth fault check is now complete.
86STP8-17TL-IA-en-31Installation Manual
Page 87
SMA Solar Technology AG12 Troubleshooting
12.3 Checking the Function of the Varistors
If the inverter displays event number "7401", one of the varistors is probably defective.
Varistors are wear parts. Their functional efficiency diminishes with age or following repeated
responses as a result of overvoltages. It is therefore possible that one of the thermally monitored
varistors has lost its protective function.
Check the varistors as described below:
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources",
page63).
Danger to life due to high voltages in the inverter
Death from electric shock
There is residual voltage in the inverter. The inverter takes 20 minutes to discharge.
• Wait 20 minutes before you open the upper enclosure lid or the DC lid.
Risk of burns due to hot components inside the inverter
• Wait until the components inside the inverter have cooled down.
2. Release the captive screws of the DC lid on the
left-hand side of the connection area.
3. Lift the DC lid up and off.
Installation ManualSTP8-17TL-IA-en-3187
Page 88
12 TroubleshootingSMA Solar Technology AG
4. Remove all varistors by pulling them upwards.
If you have not received an insertion tool for
operating the terminals with the replacement
varistors, contact SMA Solar Technology AG.
5. Use a multimeter to check each varistor for a
conductive connection between terminals 2 and 3.
ResultMeasure
☑There is a conductive
connection.
Presumably there is a different error in the inverter.
• Proceed to step 8.
• Contact the SMA Service Line (see Section16 "Contact",
page126)
☑There is no conductive
connection.
The respective varistor is defective and must be replaced.
Varistor failure is due to influences which affect all varistors
similarly (temperature, age, induced overvoltages).
SMA Solar Technology AG recommends replacing all varistors.
The varistors are specially manufac tured fo r use in t he i nverter and
are not commercially available. You will need to order
replacement varistors directly from SMA Solar Technology AG
(see Section15 "Accessories", page125). Only use original
varistors that are sold by SMA Solar Technology AG.
• To replace the varistors, proceed to step 6.
88STP8-17TL-IA-en-31Installation Manual
Page 89
SMA Solar Technology AG12 Troubleshooting
Destruction of the inverter due to overvoltage
If varistors are missing, the inverter is no longer protected against overvoltages.
• Replacement varistors should be obtained as soon as possible.
• In PV plants with a high risk of overvoltages, never operate the inverter without varistors
6. Insert an insertion tool into the openings of the
terminal contacts.
7. Insert new varistors into the slots by pushing them
down into the slots (as shown in the adjacent
diagram).
Make sure that the labelling is pointing to the front,
i.e. towards the insertion tool.
8. Dock the DC lid an at angle and then push on. The
captive screws must protrude.
9. Pre-screw all 4 screws of the DC lid and then tighten
them (torque: 3.5 Nm).
10. Restart the inverter (see Section7 "Commissioning", page58).
☑ The varistors have now been replaced and the inverter is back in operation.
Installation ManualSTP8-17TL-IA-en-3189
Page 90
12 TroubleshootingSMA Solar Technology AG
12.4 Replacing Surge Arresters Type II
If the inverter is displaying event number "8301" or "8302", presumably at least one surge arrester
is defective.
Surge arresters are wear parts. Their functional efficiency diminishes with age or following repeated
responses as a result of overvoltages. It is therefore possible that one of the surge arresters has lost its
protective function.
SMA Solar Technology AG therefore recommends replacing all surge arresters, since the failure of
one surge arrester is usually due to influences which affect all surge arresters in the same manner
(temperature, age, induced overvoltages). You will find the order numbers for both retrofit kits
(one for input A and one for input B) (see Section15 "Accessories", page125).
Replace the surge arresters as described below:
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources",
page63).
Danger to life due to high voltages in the inverter
Death from electric shock
There is residual voltage in the inverter. The inverter takes 20 minutes to discharge.
• Wait 20 minutes before you open the upper enclosure lid or the DC lid.
2. Release the captive screws of the DC lid on the
left-hand side of the connection area.
3. Lift the DC lid up and off.
90STP8-17TL-IA-en-31Installation Manual
Page 91
SMA Solar Technology AG12 Troubleshooting
4. Rem ove all sur ge a rre ste rs f rom t he s lot s. T o do thi s,
compress the grooved areas on either side.
☑ If a green strip is visible in the window (A), the
surge arrester is in perfect working order.
☑ If a red strip is visible in the window (A), the
surge arrester is defective.
5. Install new surge arresters (see Section6.7
"Retrofitting a Surge Arrester Type II", page55).
Installation ManualSTP8-17TL-IA-en-3191
Page 92
13 DecommissioningSMA Solar Technology AG
13 Decommissioning
13.1 Dismantling the Inverter
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources",
page63).
2. Remove any connected communication cables from the inverter.
Risk of burns due to hot enclosure parts
• Wait 30 minutes for the enclosure to cool down before disassembling.
3. Screw off all projecting cable glands.
4. If necessary, open the anti-theft lock.
5. Lift the inverter off the rear panel and unscrew and remove rear panel as necessary.
13.2 Replacing the Enclosure Lid
In the event of a fault, your inverter may need to be replaced. If this is the case, you will receive a
replacement device fitted with transport lids.
Danger to life due to electric shock.
During operation, there are high voltages present in the inverter.
• Do not operate the inverter without the upper and lower enclosure lid in place.
Dismantling Surge Arresters Type II
If you have retrofitted your inverters with surge arresters Type II, they must be dismantled before
returning the inverter to SMA Solar Technology AG (see Section12.4 "Replacing Surge
Arresters Type II", page90).
Prior to returning your inverter to SMA Solar Technology AG, you will need to replace the upper and
lower enclosure lids with the corresponding transport lids:
92STP8-17TL-IA-en-31Installation Manual
Page 93
SMA Solar Technology AG13 Decommissioning
Danger to life due to high voltages in the inverter
Death from electric shock
After disconnecting the inverter, there is residual voltage in the inverter. The inverter takes 20 minutes
to discharge.
• Wait 20 minutes before you open the upper enclosure lid or the DC lid.
1. Dismantle the inverter (see Section13.1 "Dismantling the Inverter", page92).
2. Release all the screws on the upper enclosure lid
and remove it by pulling it towards you.
3. Do the same with the transport lid of the
replacement device.
4. Pre-screw the transport lid of the replacement
device with the 6 enclosure lid screws and
corresponding conical spring washers to your
original inverter and then screw down tight in the
sequence shown on the right (torque: 6.0 Nm).
The toothing of the conical spring washers must
point towards the enclosure lid. This ensures proper
earthing of the enclosure lid.
The scope of delivery of the inverter includes a
spare screw and conical spring washer.
5. Screw the lower enclosure lid down tight.
☑ The original inverter is now ready for return shipment to SMA Solar Technology.
6. Now mount the upper enclosure lid from the original inverter onto the replacement device in the
same manner.
7. Mount the replacement device (see Section5.3 "Mounting the Inverter with Rear Panel",
page22) and connect it (see Section6 "Electrical Connection", page27).
Installation ManualSTP8-17TL-IA-en-3193
Page 94
13 DecommissioningSMA Solar Technology AG
13.3 Packing the Inverter
• If the original packaging is available, the inverter should be packed in its original packaging
and secured with tension straps.
• If the original packaging is not available, use a cardboard box suitable for the weight and size
of the inverter.
13.4 Storing the Inverter
Store the inverter in a dry place where the ambient temperature is always between
− 25 °C and +60 °C.
13.5 Disposing of the Inverter
At the end of it s se rvi ce l ife , di spo se o f the inv ert er a cco rding to the current locally applicable disposal
regulations for electronic waste. Alternatively, send it back to SMA Solar Technology AG with
shipping paid by sender and labelled "ZUR ENTSORGUNG" ("FOR DISPOSAL")
(contact see page 126).
94STP8-17TL-IA-en-31Installation Manual
Page 95
SMA Solar Technology AG14 Technical Data
14 Technical Data
14.1 Sunny Tripower 8000TL
DC Input
Maximum DC power at cos φ = 18,200 W
Maximum input voltage*1,000 V
MPP voltage range320 V … 800 V
Rated input voltage600 V
Minimum input voltage150 V
Initial input voltage188 V
Maximum input current, input A22.0 A
Maximum input current, input B11.0 A
Maximum input current per string input A**33.0 A
Maximum input current per string input B**12.5 A
Number of independent MPP inputs2
Strings per MPP input, input A4
Strings per MPP input, input B1
* T he ma ximu m op en-c ircu it vol tage whic h ca n occ ur at a ce ll te mperature of − 10°C must not exceed the maximum input voltage.
** To be observed in the event of short-circuit of the electronic string fuse.
Installation ManualSTP8-17TL-IA-en-3195
Page 96
14 Technical DataSMA Solar Technology AG
AC Output
Rated power at 230 V, 50 Hz8,000 W
Maximum apparent AC power8,000 VA
Rated grid voltage3/N/PE, 230 V/400 V
AC voltage range*160 V … 280 V
Nominal AC current at 230 V11.6 A
Maximum output current16.0 A
Maximum short-circuit current0.05 kA
Total harmonic factor of output current at
AC voltage < 2%
and AC power > 0.5% of nominal AC power
Maximum residual output current96 mA
Rated power frequency50 Hz
AC power frequency*50 Hz/60 Hz
Operating range at AC power frequency 50 Hz44 Hz … 55 Hz
Operating range at AC power frequency 60 Hz54 Hz … 65 Hz
Displacement power factor, adjustable0.8
overexcited
Feed-in phases3
Connection phases3
Overvoltage category as per IEC 60664-1III
* Depending on country setting
≤3%
… 0.8
underexcited
96STP8-17TL-IA-en-31Installation Manual
Page 97
SMA Solar Technology AG14 Technical Data
Protective Devices
DC reverse polarity protectionShort-circuit diode, electronic string fuse
Protection against module reverse currentsElectronic string fuse
Input-side disconnection deviceElectronic Solar Switch, SUNCLIX DC connector
DC overvoltage protectionThermally monitored varistors
optional: surge arrester type II
AC short-circuit current capabilityCurrent control
Length x width x height of packaging780 mm x 380 mm x 790 mm
Transport weight65 kg
Climatic class as per IEC 60721-2-14K4H
Operating temperature range− 25°C … +60°C
Maximum permissible value for relative humidity,
100%
non-condensing
Maximum operating altitude above MSL3,000 m
Power loss in night operation< 1 W
Topologytransformerless
Cooling conceptOptiCool: temperature-controlled fan
Fan connectiondesigned for safe disconnection
according to DIN EN 50178:1998-04
Degree of protection according to IEC 60529IP65
Protection class (according to IEC 62103)I
Installation ManualSTP8-17TL-IA-en-3197
Page 98
14 Technical DataSMA Solar Technology AG
Country standards, as per 07/2012*VDE-AR-N4105
VDE 0126-1-1
AS4777
C10/11
PPDS
GBT19939-2005
UTE C15-712-1
PPC
NRS 97-2-1
EN50438
RD661/2007
IEC 61727
G59/2
CEI 0-21
RD1699:2011
SI4777
* VDE-AR-N-4105: valid from Firmware Version 2.31. Setting in accordance with VDE-ARN-4105 (Germany)
NRS 97-2-1: This standard stipulates that a special sticker be attached to the AC distribution to draw attention to the
AC-side disconnection of the inverter in case of grid failure (for more details, see NRS 97-2-1, Sec. 4.2.7.1 and 4.2.7.2)
C10/11: Only possible if the 3-phase nominal voltage of the phase conductor is 400 V
EN 50438: Does not apply to all country standard deviations of EN 50438.
Climatic conditions in accordance with IEC 60721-3-4, Installation Type C,
Class 4K4H
Extended temperature range− 25°C … +60°C
Extended humidity range0% … 100%
Extended air pressure range79.5 kPa … 106 kPa
Climatic conditions in accordance with IEC 60721-3-4, Transport Type E,
Class 2K3
Temperature range− 25°C … +70°C
98STP8-17TL-IA-en-31Installation Manual
Page 99
SMA Solar Technology AG14 Technical Data
Features
DC connectionSUNCLIX DC connector
AC connectionspring clamp terminal
DisplayLC graphic display
Bluetoothas standard
RS485, galvanically isolatedoptional
Speedwireoptional
Speedwire with Webconnect functionoptional
Multi-function relayoptional
Power Control Moduleoptional
Electronic Solar Switch
Electrical endurance in the event of a short
at least 50 switching processes
circuit, at nominal current of 33 A
Maximum switching current33.0 A
Maximum switching voltage1,000 V
Maximum PV power20 kW
Degree of protection when plugged inIP65
Degree of protection when not plugged inIP21
Torques
Upper enclosure lid screws6.0 Nm
Lower enclosure lid screws2.0 Nm
DC lid screws3.5 Nm
Additional earth terminal6.0 Nm
Cheese-head screws (M5x10) for securing the
enclosure to the rear panel
SUNCLIX swivel nut2.0 Nm
RS485 communication connection1.5 Nm
Terminal for multi-function relay0.5 Nm
3.5 Nm
Installation ManualSTP8-17TL-IA-en-3199
Page 100
14 Technical DataSMA Solar Technology AG
Earthing systems
TN-C networksuitable
TN-S networksuitable
TN-C-S network suitable
TT gridsuitable
Data Storage Capacity
Daily energy yield performance63 days
Daily yields30 years
Event messages for users250 events
Event messages for installers250 events
Efficiency
Maximum efficiency, η
max
European weighted efficiency, η
EU
98.1%
97.5%
100STP8-17TL-IA-en-31Installation Manual
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.