SMA STP 15000TL User Manual

Page 1
OperatingManual
SUNNYTRIPOWER15000TL/ 17000TL
STP15-17TL-10-BE-en-10 | Version 1.0
AMERICAN ENGLISH
Page 2
Legal Provisions
SMA Solar Technology AG
Legal Provisions
The information contained in these documents is property of SMA Solar Technology AG. Any publication, whether in whole or in part, requires prior written approval by SMA Solar Technology AG. Internal reproduction used solely for the purpose of product evaluation or other proper use is allowed and does not require prior approval.
SMA Warranty
You can download the current warranty conditions from the Internet at www.SMA-Solar.com.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. A lack of identification does not mean that a product or symbol is not trademarked.
The BLUETOOTH® word mark and logos are registered trademarks of BluetoothSIG,Inc. and any use of these marks by SMASolarTechnologyAG is under license.
Modbus® is a registered trademark of Schneider Electric and is licensed by the Modbus Organization, Inc.
QR Code is a registered trademark of DENSO WAVE INCORPORATED. Phillips® and Pozidriv® are registered trademarks of Phillips Screw Company. Torx® is a registered trademark of Acument Global Technologies, Inc.
SMA Solar Technology AG
Sonnenallee 1 34266 Niestetal Germany Tel. +49 561 9522-0 Fax +49 561 9522-100 www.SMA.de E-mail: info@SMA.de © 2004 to 2014 SMA Solar Technology AG. All rights reserved.
Operating ManualSTP15-17TL-10-BE-en-102
Page 3
SMA Solar Technology AG
Table of Contents
Table of Contents
1 Information on this Document ................................................. 5
1.1 Validity................................................................................................ 5
1.2 Target Group...................................................................................... 5
1.3 Additional Information....................................................................... 5
1.4 Symbols .............................................................................................. 6
1.5 Nomenclature..................................................................................... 6
2 Safety......................................................................................... 7
2.1 Intended Use ...................................................................................... 7
2.2 Safety Information.............................................................................. 7
3 Scope of Delivery...................................................................... 9
4 Product Description................................................................... 11
4.1 Sunny Tripower .................................................................................. 11
4.2 Interfaces and Functions .................................................................... 14
5 Mounting ................................................................................... 17
5.1 Requirements for Mounting ............................................................... 17
5.2 Mounting the Inverter......................................................................... 19
6 Electrical Connection................................................................. 23
6.1 Safety during Electrical Connection.................................................. 23
6.2 Overview of the Connection Area .................................................... 24
6.2.1 View from Below............................................................................ 24
6.2.2 Interior View ................................................................................... 25
6.3 AC Connection................................................................................... 25
6.3.1 Requirements for the AC Connection............................................ 25
6.3.2 Connecting the Inverter to the Utility Grid.................................... 27
6.3.3 Connecting Additional Grounding ............................................... 28
6.4 DC Connection................................................................................... 29
6.4.1 Requirements for the DC Connection............................................ 29
6.4.2 Connecting the PV Array............................................................... 30
7 Commissioning.......................................................................... 34
7.1 Commissioning Procedure ................................................................. 34
Operating Manual 3STP15-17TL-10-BE-en-10
Page 4
Table of Contents
SMA Solar Technology AG
7.2 Configuring the Country Data Set..................................................... 34
7.3 Setting the NetID................................................................................ 35
7.4 Commissioning the Inverter................................................................ 37
8 Configuration ............................................................................ 39
8.1 Configuration Procedure.................................................................... 39
8.2 Changing the Display Language ...................................................... 39
8.3 Changing Operating Parameters...................................................... 40
8.4 Activating String-Failure Detection .................................................... 41
8.5 Setting the Active Power Limitation in case of PV System Control
Failure ................................................................................................. 41
8.6 Reducing the Attenuation of Ripple Control Signals........................ 42
8.7 Setting SMA OptiTrac Global Peak ................................................. 42
9 Operation.................................................................................. 44
9.1 LED Signals......................................................................................... 44
9.2 Display Overview............................................................................... 45
9.3 Activating and Operating the Display.............................................. 47
9.4 Calling Up Display Messages of the Start-Up Phase ...................... 47
10 Disconnecting the Inverter from Voltage Sources.................. 48
11 Technical Data........................................................................... 50
12 Accessories................................................................................ 55
13 Contact....................................................................................... 56
14 EC Declaration of Conformity .................................................. 59
Operating ManualSTP15-17TL-10-BE-en-104
Page 5
SMA Solar Technology AG

1 Information on this Document

1 Information on this Document

1.1 Validity

This document is valid for the following device types:
• STP 15000TL-10 (Sunny Tripower 15000TL)
• STP 17000TL-10 (Sunny Tripower 17000TL)

1.2 Target Group

This document is intended for qualified persons and end users. Only qualified persons are allowed to perform the activities marked in this document with a warning symbol and the caption "Qualifiedperson". Tasks that do not require any particular qualification are not marked and can also be performed by end users. Qualified persons must have the following skills:
• Knowledge of how an inverter works and is operated
• Training in how to deal with the dangers and risks associated with installing and using electrical devices and installations
• Training in the installation and commissioning of electrical devices and installations
• Knowledge of the applicable standards and directives
• Knowledge of and compliance with this document and all safety information

1.3 Additional Information

Links to additional information can be found at www.SMA-Solar.com:
Document title and content Document type
Troubleshooting, Cleaning, Replacement of Varistors and Decommissioning
"Overview of the Rotary Switch Settings" Overview of the rotary switch settings for config-
uring the country data set and display language "Efficiency and Derating"
Efficiency and Derating Behavior of the Sun­nyBoy, SunnyTripower and SunnyMiniCentral Inverters
"Criteria for Selecting a Residual-Current Device" Technical Information "Circuit Breaker"
Dimensioning and Selection of a Suitable AC Circuit Breaker for Inverters under PV-Specific In­fluences
"Insulation Resistance (Riso) of Non-Galvanically Isolated PV Systems"
Service Manual
Technical Information
Technical Information
Technical Information
Technical Information
Operating Manual 5STP15-17TL-10-BE-en-10
Page 6
1 Information on this Document
Document title and content Document type
"IntegratedPlantControl and QonDe­mand24/7"
Detailed explanation of functions and descrip­tion for setting the functions
"Webconnect Systems in SunnyPortal" Registration in SunnyPortal
"Firmware Update with SD Card" Technical Description "Parameter list"
Overview of All Inverter Operating Parameters and Their Configuration Options
Technical Information
User Manual
Technical Information

1.4 Symbols

Symbol Explanation
Indicates a hazardous situation which, if not avoided, will result in death or serious injury
Indicates a hazardous situation which, if not avoided, can result in death or serious injury
Indicates a hazardous situation which, if not avoided, can result in minor or moderate injury
Indicates a situation which, if not avoided, can re­sult in property damage
Sections describing activities to be performed by qualified persons only
Information that is important for a specific topic or goal, but is not safety-relevant
Indicates a requirement for meeting a specific goal
Desired result
A problem that might occur
SMA Solar Technology AG

1.5 Nomenclature

Complete designation Designation in this document
SunnyTripower Inverter, product ElectronicSolarSwitch ESS SMA BLUETOOTH Wireless Technology BLUETOOTH
Operating ManualSTP15-17TL-10-BE-en-106
Page 7
SMA Solar Technology AG

2 Safety

2 Safety

2.1 Intended Use

The SunnyTripower is a transformerless PV inverter with two MPP trackers which converts the direct current of the PV array to grid-compliant three-phase current and feeds it into the utility grid.
The product is suitable for indoor and outdoor use. The product must only be operated with PV arrays of protection class II in accordance with
IEC61730, application class A. The PV modules must be compatible with this product. PV modules with a high capacity to ground must only be used if their coupling capacity does not
exceed 2.55 μF (for information on how to calculate the coupling capacity, see the Technical Information "Leading Leakage Currents" at www.SMA-Solar.com).
All components must remain within their permitted operating ranges at all times. The product must only be used in countries for which it is approved or released by
SMASolarTechnologyAG and the grid operator. Use this product only in accordance with the information provided in the enclosed documentation
and with the locally applicable standards and directives. Any other application may cause personal injury or property damage.
Alterations to the product, e.g. changes or modifications, are only permitted with the express written permission of SMASolarTechnologyAG. Unauthorized alterations will void guarantee and warranty claims and usually void the operation permit. SMASolarTechnologyAG shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as appropriate.
The enclosed documentation is an integral part of this product. Keep the documentation in a convenient place for future reference and observe all instructions contained therein.
The type label must remain permanently attached to the product.

2.2 Safety Information

This section contains safety information that must be observed at all times when working on or with the product.
To prevent personal injury and property damage and to ensure long-term operation of the product, read this section carefully and observe all safety information at all times.
Operating Manual 7STP15-17TL-10-BE-en-10
Page 8
2 Safety
SMA Solar Technology AG
Danger to life due to high voltages of the PV array
When exposed to sunlight, the PV array generates dangerous DC voltage which is present in the DC conductors and the live components of the inverter. Touching the DC conductors or the live components can lead to lethal electric shocks. If you disconnect the DC connectors from the inverter under load, an electric arc may occur leading to electric shock and burns.
• Do not touch uninsulated cable ends.
• Do not touch the DC conductors.
• Do not touch any live components of the inverter.
• Have the inverter mounted, installed and commissioned only by qualified persons with the appropriate skills.
• If an error occurs, have it rectified by qualified persons only.
• Prior to performing any work on the inverter, disconnect it from all voltage sources as described in this document (see Section10 "Disconnecting the Inverter from Voltage Sources", page48).
Danger to life due to electric shock
Touching an ungrounded PV module or array frame can cause a fatal electric shock.
• Connect and ground the PV modules, array frame and electrically conductive surfaces so that there is continuous conduction. Observe the applicable local regulations.
Risk of burns due to hot enclosure parts
Some parts of the enclosure can get hot during operation.
• Do not touch any parts other than the lower enclosure lid of the inverter during operation.
Damage to the seal of the enclosure lids in subfreezing conditions
If you open the upper and lower enclosure lids in subfreezing conditions, the seals on the enclosure lids can be damaged. This can lead to moisture entering the inverter.
• Do not open the inverter at ambient temperatures lower than -5°C.
• If a layer of ice has formed on the seal of the lid in subfreezing conditions, remove it prior to opening the enclosure lids of the inverter (e.g. by melting the ice with warm air). Observe the applicable safety regulations.
Damage to the display or the type label due to the use of cleaning agents
• If the inverter is dirty, clean the enclosure, the enclosure lid, the type label, the display and the LEDs with a damp cloth only.
Operating ManualSTP15-17TL-10-BE-en-108
Page 9
SMA Solar Technology AG

3 Scope of Delivery

3 Scope of Delivery
Check the scope of delivery for completeness and any externally visible damage. Contact your distributor if the scope of delivery is incomplete or damaged.
Figure 1: Components included in the scope of delivery
Position Quantity Designation
A 1 Inverter B 1 ElectronicSolarSwitch (ESS) C 1 Rear panel D 1 Operating manual, document set with declarations and
certificates, supplementary sheet with default settings, in-
stallation manual of the DC connectors E 12 Negative DC connector F 12 Positive DC connector G 12 Sealing plug H 1 Eye bolt M8 I 2 Cylindrical screw M5x10 K 1 AC cable gland L 1 Counter nut M 1 Clamping bracket N 1 Cylindrical screw M6x16 O 1 Conical spring washer M6
Operating Manual 9STP15-17TL-10-BE-en-10
Page 10
3 Scope of Delivery
Position Quantity Designation
P 2 Cylindrical screw M5x20* Q 2 Conical spring washer M5*
* Spare part for the enclosure lid
SMA Solar Technology AG
Operating ManualSTP15-17TL-10-BE-en-1010
Page 11
SMA Solar Technology AG

4 Product Description

4 Product Description
4.1 SunnyTripower
The SunnyTripower is a transformerless PV inverter with two MPP trackers which converts the direct current of the PV array to grid-compliant three-phase current and feeds it into the utility grid.
Position Explanation
A Thread for screwing in the two eye bolts for transporting the inverter with a crane B Type label
The type label uniquely identifies the inverter. You will require the information on the type label to use the product safely and when seeking customer support from Service. You will find the following information on the type label:
• Device type (Model)
• Serial number (SerialNo.)
• Date of manufacture
• Device-specific characteristics C Ventilation grid D Recessed grip E LEDs
The LEDs indicate the operating state of the inverter (see Section9.1 "LED Signals", page44).
F Display
The display shows the current operating data and events or errors (see Section9.2 "Display Overview", page45).
Operating Manual 11STP15-17TL-10-BE-en-10
Page 12
4 Product Description
Position Explanation
G ElectronicSolarSwitch (ESS)
The ESS and the DC connectors together form a DC load-break switch. When plugged in, the ESS forms a conductive path between the PV array and the inverter. Removing the ESS interrupts the DC electric circuit and removing all DC connectors
disconnects the PV array completely from the inverter. H Lower enclosure lid I Upper enclosure lid
Symbols on the inverter, the ESS and the type label
Symbol Explanation
Inverter Together with the green LED, this symbol indicates the operating state of
the inverter. Observe the documentation
Together with the red LED, this symbol indicates an error (for trou­bleshooting, see the service manual at www.SMA-Solar.com).
BLUETOOTH Together with the blue LED, the symbol indicates active communication
via BLUETOOTH. Danger
This symbol indicates that the inverter must be additionally grounded if additional grounding or equipotential bonding is required at the installa­tion site (see Section6.3.3 "Connecting Additional Grounding", page
28). QRCode
Links to additional information on the inverter can be found at www.SMA-Solar.com.
SMA Solar Technology AG
Operating ManualSTP15-17TL-10-BE-en-1012
Page 13
SMA Solar Technology AG
Symbol Explanation
Operating principle of the ESS:
If the ESS is plugged in, the DC electric circuit is closed.
• If an acoustic signals sounds and the display shows an error message that prohibits removing the ESS, wait until dark. The ESS can only be removed once it is dark.
If no acoustic signal sounds and the display does not show an error message, the DC electric circuit may be interrupted. To interrupt the DC electric circuit, you must perform the following steps in the given order:
Remove the ESS. – Unlock and remove all DC connectors.
Danger to life due to high voltages in the inverter; observe the waiting time of 20minutes.
High voltages that can cause lethal electric shocks are present in the live components of the inverter. Prior to performing any work on the inverter, disconnect it from all voltage sources as described in this document (see Section10, page48).
Danger to life due to electric shock The product operates at high voltages. All work on the product must be
carried out by qualified persons only.
Risk of burns due to hot surfaces The product can get hot during operation. Avoid contact during opera-
tion. Allow the product to cool down sufficiently before carrying out any work.
Observe the documentation Observe all documentation supplied with the product.
4 Product Description
Direct current
The product does not have a transformer.
Three-phase alternating current with neutral conductor
WEEE designation Do not dispose of the product together with the household waste but in
accordance with the locally applicable disposal regulations for electronic waste.
Operating Manual 13STP15-17TL-10-BE-en-10
Page 14
4 Product Description
Symbol Explanation
CE marking The product complies with the requirements of the applicable EU direc-
tives. Degree of protectionIP65
The product is protected against dust intrusion and water jets from any angle.
The product is suitable for outdoor installation.
Certified safety The product is VDE-tested and complies with the requirements of the Ger-
man Equipment and Product Safety Act.
RCM (Regulatory Compliance Mark) The product complies with the requirements of the applicable Australian
standards.
Korean mark of conformity The product complies with the requirements of the applicable Korean di-
rectives.
SMA Solar Technology AG

4.2 Interfaces and Functions

The inverter can be equipped or retrofitted with the following interfaces and functions:
BLUETOOTH
Via BLUETOOTH, the inverter can communicate with various BLUETOOTH devices (for information on supported SMA products, see www.SMA-Solar.com).
Speedwire/Webconnect
SMA Speedwire/Webconnect is a type of communication based on the Ethernet standard. This enables inverter-optimized 10/100Mbit data transmission between Speedwire devices in PV systems and the software Sunny Explorer. The Webconnect function enables direct data transmission between the inverters of a small-scale system and the Internet portal SunnyPortal without any additional communication device and for a maximum of four inverters per SunnyPortal system. In large-scale PV power plants, data transmission to the Internet portal Sunny Portal is carried out via the SMA Cluster Controller. You can access your SunnyPortal system from any computer with an Internet connection.
Operating ManualSTP15-17TL-10-BE-en-1014
Page 15
SMA Solar Technology AG
SMA Speedwire/Webconnect enables, for PV systems operated in Italy, the connection to or disconnection of the inverter from the utility grid and definition of the frequency limits to be used with IEC61850-GOOSE messages.
SMA Speedwire/Webconnect can be retrofitted.
4 Product Description
RS485 interface
The inverter can communicate via cables with special SMA communication products via the RS485 interface (information on supported SMAproducts at www.SMA-Solar.com). The RS485 interface can be retrofitted.
Grid Management Services
The inverter is equipped with service functions for grid management. Depending on the requirements of the grid operator, you can activate and configure the functions
(e.g. active power limitation) via operating parameters.
SMA Power Control Module
The SMAPowerControlModule enables the inverter to implement grid management services and is equipped with an additional multifunction relay (for information on installation and configuration, see the installation manual of the SMAPowerControlModule). The SMAPowerControlModule can be retrofitted.
Multifunction Relay
You can configure the multifunction relay for various operating modes. The multifunction relay is used, for example, to switch fault indicators on or off (for information on installation and configuration, see the installation manual of the multifunction relay). The multifunction relay can be retrofitted.
SMAOptiTracGlobalPeak
SMAOptiTracGlobalPeak is an advancement of SMAOptiTrac and allows the operating point of the inverter to follow the optimal operating point of the PV array (MPP) precisely at all times. In addition, with the aid of SMAOptiTracGlobalPeak, the inverter can detect the presence of several maximum power points in the available operating range, such as may occur particularly with partially shaded strings. SMA OptiTrac Global Peak is enabled by default.
String-failure detection
String-failure detection recognizes the failure of an individual string or substring. If an insulation error occurs, string-failure detection disconnects the defective string from the inverter. This avoids having to shut down the entire PV array. In order for the string-failure detection to be reliable, identically aligned PV modules must be connected to both inputs of the inverter. String-failure detection is deactivated by default and must be activated.
Surge Arrester Type II
The surge arresters monitor the PV modules and limit dangerous overvoltages. Surge arresters of typeII can be retrofitted.
Operating Manual 15STP15-17TL-10-BE-en-10
Page 16
4 Product Description
SMA Solar Technology AG
Electronic string fuse
The electronic string fuse protects the PV array against potential reverse currents. The electronic string fuse recognizes DC cables that were connected with reverse polarity or defective PV modules and short-circuits the PV array. In order for the electronic string fuse function to be reliable, the connection of the PV array must be made when there is sufficient irradiation. If the input voltage is less than 188V, the protective function of the electronic string fuse is not active when the connection is made.
QonDemand24/7
The inverter can supply reactive power by means of QonDemand24/7 covering the entire unit circle around the clock.
IntegratedPlantControl
The inverter can display the Q(V) characteristic curve specified by the grid operator by means of IntegratedPlantControl without measuring on the grid-connection point. The inverter can automatically compensate equipment installed between the inverter and the grid-connection point.
Operating ManualSTP15-17TL-10-BE-en-1016
Page 17
SMA Solar Technology AG

5 Mounting

5 Mounting

5.1 Requirements for Mounting

Requirements for the mounting location:
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
• Do not mount the inverter in areas containing highly flammable materials or gases.
• Do not mount the inverter in a potentially explosive atmosphere.
☐ Do not mount the inverter on a pillar. ☐ The mounting location must be inaccessible to children. ☐ A solid support surface must be available for mounting, e.g. concrete or masonry. When
mounted on drywall or similar materials, the inverter emits audible vibrations during operation which could be perceived as annoying.
☐ The mounting location must be suitable for the weight and dimensions of the inverter (see
Section11 "Technical Data", page50). ☐ To ensure optimum operation, the ambient temperature should be between -25°C and 40°C. ☐ The mounting location should not be exposed to direct solar irradiation. Direct solar irradiation
can cause the inverter to overheat. As a result, the inverter reduces its power output. ☐ Climatic conditions must be met (see Section11 "Technical Data", page50). ☐ The mounting location should be freely and safely accessible at all times without the need for
any auxiliary equipment (such as scaffolding or lifting platforms). Non-fulfillment of these
criteria may restrict servicing.
Operating Manual 17STP15-17TL-10-BE-en-10
Page 18
5 Mounting
Dimensions for mounting:
SMA Solar Technology AG
Figure 2: Position of the anchoring points
Recommended clearances:
If you maintain the recommended clearances, adequate heat dissipation will be ensured. Thus, you will prevent power reduction due to excessive temperature.
☐ Maintain the recommended clearances to walls as well as to other inverters or objects. ☐ If multiple inverters are mounted in areas with high ambient temperatures, increase the
clearances between the inverters and ensure sufficient fresh-air supply.
Operating ManualSTP15-17TL-10-BE-en-1018
Page 19
SMA Solar Technology AG
Figure 3: Recommended clearances
5 Mounting
Permitted and prohibited mounting positions:
☐ The inverter must be mounted in one of the permitted positions. This will ensure that no
moisture can penetrate the inverter. ☐ The inverter should be mounted in such way that display messages and LED signals can be
read without difficulty.
Figure 4: Permitted and prohibited mounting positions

5.2 Mounting the Inverter

Additionally required mounting material (not included in the scope of delivery):
☐ Three screws suitable for the support surface (size: M10 at maximum) ☐ Three washers suitable for the screws (diameter: 30mm at maximum) ☐ If necessary, three screw anchors suitable for the support surface and the screws ☐ For transporting the inverter with a crane: two eye bolts suitable for the weight of the inverter
(size: M10) ☐ To secure the inverter against theft: one padlock suitable for outdoor use
Operating Manual 19STP15-17TL-10-BE-en-10
Page 20
5 Mounting
SMA Solar Technology AG
Risk of injury when lifting the inverter, or if it is dropped
The inverter weighs 59 kg. There is risk of injury if the inverter is lifted incorrectly or dropped while being transported or when attaching it to or removing it from the wall mounting bracket.
• Carry and lift the inverter in an upright position with several people without tilting it. With one hand grasp the recessed grip, and with the other hand support the top part of the enclosure. This will prevent the inverter tipping forward.
• If the inverter is to be transported and lifted with a crane, remove the filler plugs on the top of the inverter and screw the eye bolts into the threads.
Risk of burns due to hot enclosure parts
Some parts of the enclosure can get hot during operation.
• Mount the inverter in such a way that it cannot be touched inadvertently during operation.
Procedure:
1.
Risk of injury due to damaged cables
There may be power lines or other supply lines (e.g. gas or water) routed in the wall.
• Ensure that no lines are laid in the wall which could be damaged when drilling holes.
2. Align the rear panel horizontally on the wall and use it to mark the position of the drill holes for attaching the rear panel. Use at least one hole on the upper right and the upper left and the hole in the middle of the rear panel.
Operating ManualSTP15-17TL-10-BE-en-1020
Page 21
SMA Solar Technology AG
5 Mounting
3. If the inverter is to be secured against theft, mark the drill hole for the attachment of the eye bolt.
4. Set the rear panel aside and drill the marked holes.
5. Depending on the support surface, insert the screw anchors into the drill holes for attaching the rear panel.
6. Secure the rear panel using screws and washers.
7. Hook the inverter into the rear panel. The enclosure has to be flush with the rear panel on the right-hand and on the left-hand side.
8. If the inverter has been transported with a crane, remove the eye bolts from the threads on the top of the inverter and reinsert the filler plugs.
9. Remove all six screws from the lower enclosure lid using an Allen key (AF 3).
Operating Manual 21STP15-17TL-10-BE-en-10
Page 22
5 Mounting
SMA Solar Technology AG
10. Flip the lower enclosure lid up and remove it.
11. Fasten the inverter to the rear panel. Tighten the two cylindrical screws M5x10 in the threads on the left-hand and right-hand side of the rear panel (torque: 6Nm ± 0.3Nm) using an Allen key (AF4).
12. Ensure that the inverter is securely in place.
13. If the inverter is to be protected against theft, attach the eye bolt and install the padlock:
• Screw the M8 eye bolt into the wall through the rear panel. When tightened, the eye of the bolt must be vertical to the enclosure.
• Lead the shackle of the padlock through the hole of the eye bolt.
• Close the padlock.
• Keep the key of the padlock in a safe place.
Operating ManualSTP15-17TL-10-BE-en-1022
Page 23
SMA Solar Technology AG

6 Electrical Connection

6 Electrical Connection

6.1 Safety during Electrical Connection

Danger to life due to high voltages of the PV array
When exposed to sunlight, the PV array generates dangerous DC voltage which is present in the DC conductors and the live components of the inverter. Touching the DC conductors or the live components can lead to lethal electric shocks. If you disconnect the DC connectors from the inverter under load, an electric arc may occur leading to electric shock and burns.
• Do not touch uninsulated cable ends.
• Do not touch the DC conductors.
• Do not touch any live components of the inverter.
• Have the inverter mounted, installed and commissioned only by qualified persons with the appropriate skills.
• If an error occurs, have it rectified by qualified persons only.
• Prior to performing any work on the inverter, disconnect it from all voltage sources as described in this document (see Section10 "Disconnecting the Inverter from Voltage Sources", page48).
Damage to the seal of the enclosure lids in subfreezing conditions
If you open the upper and lower enclosure lids in subfreezing conditions, the seals on the enclosure lids can be damaged. This can lead to moisture entering the inverter.
• Do not open the inverter at ambient temperatures lower than -5°C.
• If a layer of ice has formed on the seal of the lid in subfreezing conditions, remove it prior to opening the enclosure lids of the inverter (e.g. by melting the ice with warm air). Observe the applicable safety regulations.
Damage to the inverter due to electrostatic discharge
Touching electronic components can cause damage to or destroy the inverter through electrostatic discharge.
• Ground yourself before touching any component.
Operating Manual 23STP15-17TL-10-BE-en-10
Page 24
6 Electrical Connection
SMA Solar Technology AG

6.2 Overview of the Connection Area

6.2.1 View from Below

Figure 5: Connection areas and enclosure openings at the bottom of the inverter
Position Designation
A Pin connector for the ESS B Cable gland M20x1.5 for the connection cable of the multifunction relay C Enclosure opening with filler plug for the data cables and network cables D Enclosure opening with filler plug for the data cables and network cables E Enclosure opening for the AC cable F Positive and negative DC connectors, input B G Positive and negative DC connectors, input A
Operating ManualSTP15-17TL-10-BE-en-1024
Page 25
SMA Solar Technology AG
6 Electrical Connection

6.2.2 Interior View

Figure 6: Connection areas in the interior of the inverter
Position Designation
A DC protective cover B Pin connector for connecting the multifunction relay C Pin connector for connecting the communication interface for RS485 or
Speedwire/Webconnect D Connecting terminal plate for connecting the AC cable E Jumper slot for temporarily changing the display language to English (for ser-
vice purposes) F Rotary switch C for configuring the NetID G Screw for releasing and raising the display H Rotary switch A and B for setting the country data set and the display lan-
guage I Slot SD memory card

6.3 AC Connection

6.3.1 Requirements for the AC Connection

Cable requirements:
☐ External diameter: 14 mm to 25 mm ☐ Conductor cross-section: 1.5 mm² to 16 mm² ☐ Maximum conductor cross-section with bootlace ferrule: 10mm²
Operating Manual 25STP15-17TL-10-BE-en-10
Page 26
6 Electrical Connection
SMA Solar Technology AG
☐ Insulation stripping length: 12 mm ☐ The cable must be dimensioned in accordance with the local and national directives for the
dimensioning of cables. The requirements for the minimum wire size derive from these directives. Examples of factors influencing cable dimensioning are: nominal AC current, type of cable, routing method, cable bundling, ambient temperature and maximum desired line losses (for calculation of line losses, see the design software "SunnyDesign" from software version2.0 at www.SMA-Solar.com).
Load-break switch and cable protection:
Damage to the inverter due to the use of screw-type fuses as load-break switches
Screw-type fuses (e.g. DIAZED fuse or NEOZED fuse) are not load-break switches.
• Do not use screw-type fuses as load-break switches.
• Use a load-break switch or circuit breaker as a load disconnection unit (for information and design examples, see the Technical Information "Circuit Breaker" at www.SMA-Solar.com).
☐ In PV systems with multiple inverters, protect each inverter with a separate three-phase circuit
breaker. Make sure to observe the maximum permissible fuse protection (see Section11 "Technical Data", page50). This will prevent residual voltage being present at the corresponding cable after disconnection.
☐ Loads installed between the inverter and the circuit breaker must be fused separately.
Residual-current monitoring unit:
☐ If an external residual-current device is required, install a residual-current device which trips at
a residual current of 100mA or higher (for details on selecting a residual-current device, see the Technical Information "Criteria for Selecting a Residual-Current Device" at www.SMA­Solar.com).
Overvoltage category:
The inverter can be used in grids of overvoltage categoryIII or lower in accordance with IEC60664-1. That means that the inverter can be permanently connected to the grid-connection point of a building. In case of installations with long outdoor cabling routes, additional measures to reduce overvoltage categoryIV to overvoltage categoryIII are required (see the Technical Information "Overvoltage Protection" at www.SMA-Solar.com).
Additional grounding:
Safety in accordance with IEC62109
The inverter is not equipped with a grounding conductor monitoring device. In order to guarantee safety in accordance with IEC62109, you must take one of the following measures:
• Connect a grounding conductor made of copper wire with a cross-section of at least 10mm² to the connecting terminal plate for the AC cable.
• Connect additional grounding with the same cross-section as the connected grounding conductor to the connecting terminal plate for the AC cable (see Section6.3.3 "Connecting Additional Grounding", page28). This prevents touch current if the grounding conductor at the connecting terminal plate for the AC cable fails.
Operating ManualSTP15-17TL-10-BE-en-1026
Page 27
SMA Solar Technology AG
6 Electrical Connection
Connection of additional grounding
In some countries, additional grounding is generally required. In each case, observe the locally applicable regulations.
• If additional grounding is required, connect an additional grounding with the same cross­section as the connected grounding conductor to the connecting terminal plate for the AC cable (see Section6.3.3, page28). This prevents touch current if the grounding conductor at the connecting terminal plate for the AC cable fails.

6.3.2 Connecting the Inverter to the Utility Grid

☐ The connection requirements of the grid operator must be met. ☐ The grid voltage must be in the permissible range. The exact operating range of the inverter is
specified in the operating parameters.
Procedure:
1. Disconnect the circuit breaker from all three line conductors and secure against reconnection.
2. If the lower enclosure lid is mounted, loosen all screws of the lower enclosure lid using an Allen key (AF3) and lift the enclosure lid from below and remove it.
3. Remove the adhesive tape from the enclosure opening for the AC cable.
4. Insert the cable gland from the outside into the enclosure opening and tighten it from the inside with the counter nut.
5. Route the AC cable into the inverter through the cable gland. If necessary, slightly loosen the swivel nut of the cable gland.
6. Remove the sheath from the AC cable.
7. Shorten L1, L2, L3 and N by 5mm each.
8. Strip off the insulation of L1, L2, L3, N and PE by 12mm.
9. Push the safety levers of the AC connecting terminal plate right up to the stop.
Operating Manual 27STP15-17TL-10-BE-en-10
Page 28
6 Electrical Connection
SMA Solar Technology AG
10.
Risk of fire if two conductors are connected to one terminal
If you connect two conductors to a terminal, a fire can occur due to a bad electrical connection.
• Never connect more than one conductor per terminal.
11.
Danger of crushing when locking levers snap shut
The locking levers close by snapping down fast and hard.
• Press the locking levers of the connecting terminal plate for the AC cable down with your thumb only.
• Do not grip the entire connecting terminal plate for the AC cable.
• Do not place your fingers under the locking levers.
12. Connect PE, N, L1, L2 and L3 according to the labeling to the connecting terminal plate for the AC cable and push the safety levers down. The direction of the rotating magnetic field of L1, L2 and L3 is not relevant.
13. Make sure that all conductors are securely in place.
14. Tighten the swivel nut of the cable gland.

6.3.3 Connecting Additional Grounding

If additional grounding or equipotential bonding is required locally, you can connect additional grounding to the inverter. This prevents touch current if the grounding conductor at the connecting terminal plate for the AC cable fails. The required clamping bracket, the screw and the conical spring washer are part of the scope of delivery of the inverter.
Cable requirement:
☐ Grounding cable cross-section: max. 16mm²
Operating ManualSTP15-17TL-10-BE-en-1028
Page 29
SMA Solar Technology AG
Procedure:
1. Strip the grounding cable insulation.
2. Lead the clamping bracket over the grounding cable. Arrange the grounding cable on the left­hand side.
3. Screw the clamping bracket tight using the M6x16 cylindrical screw and the conical spring washer M6 (torque: 6Nm). The teeth of the conical spring washer must face the clamping bracket.

6.4 DC Connection

6 Electrical Connection

6.4.1 Requirements for the DC Connection

Requirements for the PV modules per input:
☐ All PV modules must be of the same type. ☐ All PV modules must be aligned and tilted identically. ☐ On the coldest day based on statistical records, the open-circuit voltage of the PV array must
never exceed the maximum input voltage of the inverter.
☐ The same number of series-connected PV modules must be connected to each string. ☐ The maximum input current per string must be maintained and must not exceed the through-
fault current of the DC connectors (see Section11 "Technical Data", page50).
☐ The thresholds for the input voltage and the input current of the inverter must be adhered to
(see Section11 "Technical Data", page50).
☐ The positive connection cables of the PV modules must be fitted with the positive DC
connectors (for information on assembling DC connectors, see the DC connector installation manual).
☐ The negative connection cables of the PV modules must be fitted with the negative DC
connectors (for information on assembling DC connectors, see the DC connector installation manual).
Operating Manual 29STP15-17TL-10-BE-en-10
Page 30
6 Electrical Connection
SMA Solar Technology AG
Use of Y adapters for parallel connection of strings
The Y adapters must not be used to interrupt the DC circuit.
• Do not use the Y adapters in the immediate vicinity of the inverter. The adapters must not be visible or freely accessible.
• In order to interrupt the DC circuit, always disconnect the inverter as described in this document (see Section10, page48).

6.4.2 Connecting the PV Array

Risk of fire due to electric arc when thresholds on the DC input are exceeded
The electronic string fuse recognizes when the maximum short-circuit current is exceeded and short-circuits the PV array. This can cause an electric arc and thus a risk of fire.
• Ensure that the thresholds for the input voltage, the input current and the short-circuit current of the inverter are adhered to.
Damage to the DC connectors due the use of contact cleaner of other cleaning agents
Some contact cleaners or other cleaning agents may contain substances that decompose the plastic of the DC connectors.
• Do not use contact cleaners or other cleaning agents for cleaning the DC connectors.
Limitation of the electronic string fuse by using string connection boxes
When using string connection boxes, the functionality of the electronic string fuse may be limited.
Procedure:
1. Ensure that the circuit breaker is switched off from all three line conductors and that it cannot be reconnected.
2. Ensure that there is no ground fault in the PV array (see service manual at www.SMA­Solar.com).
3. Securely plug in the ESS. The ESS must be aligned parallel to and flush with the enclosure. If the ESS is plugged in when connecting the DC connectors, the protective function of the electronic string fuse can be activated.
Operating ManualSTP15-17TL-10-BE-en-1030
Page 31
SMA Solar Technology AG
6 Electrical Connection
4.
Risk of fire due to reverse currents not being detected
The electronic string fuse monitors the PV array and protects it against dangerous reverse currents which can cause a fire. In order to activate the electronic string fuse, you must observe the following during DC connection:
• When connecting more than two strings, the first string must be connected to input B of the inverter. This activates the string fuse.
• All strings must be clearly assigned to the correct DC input. Do not cross-wire or combine the strings.
5. Check whether the DC connectors have the correct polarity. If the DC connector is equipped with a DC cable of the wrong polarity, the DC connector must
be assembled again. The DC cable must always have the same polarity as the DC connector.
6. If there are more than two strings, connect the first assembled DC connector to input B. This activates the string fuse.
☑ The green LED is flashing or glowing, no acoustic signal sounds and no error message is
displayed. The string fuse is activated and all remaining DC connectors can be connected.
✖ The display does not show any data after a waiting period of at least 60seconds and no
acoustic signal sounds? The inverter is probably defective.
• Ensure that the DC input voltage is at least 188V.
• Ensure that the DC connectors are not connected with reverse polarity.
• If the DC input voltage is sufficient and the DC connectors are connected correctly, contact Service (see Section13, page56).
✖ An acoustic signal sounds and an error message with the event number 4001 appears in
the display? The inverter short-circuits the PV array to avoid reverse currents through individual strings.
The PV array and the inverter are in a safe state.
• Do not remove the ESS and/or the DC connector under any circumstances. This prevents an electric arc from forming which can cause injuries and a fire.
• Stop working on the inverter and wait until dark and until the acoustic signal no longer sounds.
• If you would like to leave the PV system to continue work when it is dark, set up protection against contact (e.g. a fence) and protect the inverter against penetrating moisture (e.g. with tarp).
• Only remove the ESS and all DC connectors and correct the connection once it is dark.
✖ An acoustic signal sounds and an error message with the event number 6313 or 8201
appears in the display?
• Contact Service (see Section13, page56).
Operating Manual 31STP15-17TL-10-BE-en-10
Page 32
6 Electrical Connection
7. Connect the remaining assembled DC connectors to input A.
8. Ensure that all DC connectors are securely in place.
SMA Solar Technology AG
Operating ManualSTP15-17TL-10-BE-en-1032
Page 33
SMA Solar Technology AG
6 Electrical Connection
9.
Damage to the inverter due to moisture ingress
The inverter is only properly sealed when all unused DC inputs are closed with DC connectors and sealing plugs.
• Do not insert the sealing plugs directly into the DC inputs on the inverter.
• For unused DC connectors, push down the clamping bracket and push the swivel nut up to the thread.
• Insert the sealing plug into the DC connector.
• Tighten the DC connector (torque: 2Nm).
• Insert the DC connectors with sealing plugs into the corresponding DC inputs on the inverter.
☑ The DC connectors snap into place.
10. Remove the ESS. ☑ The display switches off.
Operating Manual 33STP15-17TL-10-BE-en-10
Page 34

7 Commissioning

SMA Solar Technology AG
7 Commissioning

7.1 Commissioning Procedure

Before you can commission the inverter, you must check various settings and make changes if necessary. This section describes the procedure and gives an overview of the steps, which must always be performed in the prescribed sequence.
Procedure See
1. Check which country data set the inverter is set to. Supplementary sheet with the default settings, type la­bel or display
2. If the country data set is not set correctly for your country
or your purpose, adjust to the required country data set and the corresponding display language within the first ten feed-in hours via the rotary switches in the inverter.
3. If the inverter is to communicate with several BLUETOOTH
devices, or if BLUETOOTH is not to be used as a type of communication, set the NetID.
4. Commission the inverter. Section7.4, page37
Section7.2, page34
Section7.3, page35

7.2 Configuring the Country Data Set

A display language is assigned to every country data set. Set the country data set appropriate for your country or purpose, with the corresponding display language, within the first ten feed-in hours via the rotary switches in the inverter. After the first ten feed-in hours, the country data set can only be changed by means of a communication product.
If the display language of the country data set does not match the required language, you can change it after commissioning (see Section8.2 "Changing the Display Language", page39).
The country data set must be set correctly.
If you select a country data set which is not valid for your country and purpose, it can cause a disturbance in the PV system and lead to problems with the grid operator. When selecting the country data set, you must always observe the locally applicable standards and directives as well as the properties of the PV system (e.g. PV system size, grid-connection point).
• If you are not sure which country data set is valid for your country or purpose, contact your grid operator for information on which country data set is to be configured.
Operating ManualSTP15-17TL-10-BE-en-1034
Page 35
SMA Solar Technology AG
Country data set for operation with external decoupling protection
When operating the PV system with external decoupling protection, the inverter has the additional country data set Medium-Voltage Directive (Germany) or MVtgDirective. This country data set allows you to extend the operating range of the inverter for voltage and frequency. This country data set should only be selected if the PV system is disconnected via external decoupling.
• If the country data set for operation is set with external decoupling protection, only operate the inverter with an external three-phase decoupling protection. Without external three‑phase decoupling protection, the inverter will not disconnect from the utility grid when the country-specific standard requirement is exceeded.
Procedure:
1. Determine the rotary switch position for your country and purpose. Call up the Technical Information "Overview of the Rotary Switch Settings" at www.SMA-Solar.com.
2.
Danger to life due to high voltages
• Ensure that the inverter is disconnected from all voltage sources and that the enclosure lid is removed (see Section10, page48).
3. Set the rotary switches A and B to the required position using a flat-blade screwdriver (blade width: 2.5mm).
7 Commissioning
☑ The inverter will adopt the setting after commissioning. This can take up to five minutes.

7.3 Setting the NetID

By default, the NetID is set to 1 for all SMAinverters and SMAcommunication products with BLUETOOTH. If your PV system consists of an inverter and a maximum of one further BLUETOOTH device (e.g. computer with BLUETOOTH interface or SMAcommunication product), you can leave the NetID set to 1.
Operating Manual 35STP15-17TL-10-BE-en-10
Page 36
7 Commissioning
SMA Solar Technology AG
You must change the NetID in the following cases:
• If your PV system consists of one inverter and two other BLUETOOTH devices (e.g. computer with BLUETOOTH interface and SMA communication product) or of multiple inverters with BLUETOOTH, you must change the NetID of your PV system. This will enable communication with multiple BLUETOOTH devices.
• If another PV system with BLUETOOTH is located within 500m of your PV system, you must change the NetID of your PV system. This will help keep both PV systems separate.
• If you do not wish to communicate via BLUETOOTH, deactivate the BLUETOOTH communication on your inverter. This will protect your PV system from unauthorized access.
All BLUETOOTH devices in a PV system must have the same NetID. You can set a new NetID in the inverter by means of the rotary switch C.
Figure 7: Positions of rotary switch C
Position Explanation
0 Communication via BLUETOOTH is deactivated. 1 Communication via BLUETOOTH with a further BLUETOOTH device 2 to F NetID for communication via BLUETOOTH with multiple BLUETOOTH devices
Procedure:
1.
Danger to life due to high voltages
• Ensure that the inverter is disconnected from all voltage sources (see Section10, page48 ).
Operating ManualSTP15-17TL-10-BE-en-1036
Page 37
SMA Solar Technology AG
2. To set a new NetID, set the rotary switch C to the determined NetID using a flat-blade screwdriver (blade width: 2.5mm).
3. To deactivate communication via BLUETOOTH, set the rotary switch C to position 0 using a flat­blade screwdriver (blade width: 2.5mm). This will protect your PV system from unauthorized access.
☑ The inverter will adopt the setting after commissioning. This can take up to five minutes.
7 Commissioning

7.4 Commissioning the Inverter

Requirements:
☐ The inverter must be correctly mounted. ☐ The circuit breaker must be correctly rated and mounted. ☐ All cables must be completely and correctly connected. ☐ Unused DC inputs must be sealed using the corresponding DC connectors and sealing plugs. ☐ The country data set must be set correctly for the country or the purpose.
Procedure:
1. Insert the lower enclosure lid from above and fold it down. The screws must protrude from the lower enclosure lid.
Operating Manual 37STP15-17TL-10-BE-en-10
Page 38
7 Commissioning
SMA Solar Technology AG
2. Tighten all six screws with an Allen key (AF3) in the order1 to6 (torque: 2.0Nm ± 0.3Nm). By tightening the screws in the prescribed order, you avoid warping the enclosure lid, which would keep it from sealing correctly. Useful hint: If the screws fall out of the lower enclosure lid, insert the long screw into the lower middle hole and the five short screws into the other holes.
3. Securely plug in the ESS. The ESS must be aligned parallel to and flush with the enclosure.
4. Switch on the circuit breaker of all three line conductors.
5. If the multifunction relay is used, connect the supply voltage to the load.
☑ All three LEDs start to glow and the start-up phase begins. The start-up phase may take several
minutes.
☑ The green LED is glowing and the display alternates automatically between the device type,
firmware version, the serial number or designation of the inverter, the NetID, the configured country data set and the display language.
✖ The green LED is flashing?
Possible cause of error: the DC input voltage is still too low or the inverter is monitoring the utility grid.
• Once the DC input voltage is sufficiently high and the grid connection conditions are met, the inverter will start operation.
✖ The red LED is glowing and an error message and event number appear in the display?
• Rectify the error (see the service manual at www.SMA-Solar.com).
Operating ManualSTP15-17TL-10-BE-en-1038
Page 39
SMA Solar Technology AG

8 Configuration

8 Configuration

8.1 Configuration Procedure

Once you have commissioned the inverter, you may have to adjust various settings via the rotary switches in the inverter or via a communication product. This section describes the procedure for configuration and gives an overview of the steps you must perform in the prescribed order.
Procedure See
1. If the display language is not set correctly, adjust the set­tings.
2. If the inverter is equipped with a Speedwire/Webconnect data module, integrate the inverter in a Speedwire net­work and register it in SunnyPortal, if necessary.
3. To manage the PV system data or to set the inverter pa­rameters, capture the inverter in a communication product.
4. Change the system time and system password. Manual of the communica-
5. If you would like to use the self-learning string-failure de­tection, activate the string-failure detection.
6. Set the active power limitation in case of PV system control failure.
7. Reduce the attenuation of ripple control signals. Section8.6, page42
8. For partially shaded PV modules and depending on the given shading situation, you should set the interval at which the inverter optimizes the MPP of the PV system.
Section8.2, page39
Manual of the communica­tion product at www.SMA­Solar.com
Manual of the communica­tion product at www.SMA­Solar.com
tion product at www.SMA­Solar.com
Section8.4, page41
Section8.5, page41
Section8.7, page42

8.2 Changing the Display Language

If the language for the country data set is not the language you want to use, you can change the display language as follows:
Procedure:
1.
Danger to life due to high voltages
• Disconnect the inverter from all voltage sources and open the enclosure lid (see Section10, page48).
Operating Manual 39STP15-17TL-10-BE-en-10
Page 40
8 Configuration
2. Determine the rotary switch setting for the desired display language. Call up the Technical Information "Overview of the Rotary Switch Settings" at www.SMA-Solar.com.
3. Set the rotary switch A to 0 using a flat-blade screwdriver (blade width: 2.5mm). This ensures that the selected data country set remains unchanged.
4. Set the rotary switch B to the required language using a flat-blade screwdriver (blade width:
2.5mm).
5. Recommission the inverter (see service manual at www.SMA-Solar.com).
☑ The inverter adopts the settings after commissioning. This can take up to five minutes.
SMA Solar Technology AG

8.3 Changing Operating Parameters

This section describes the basic procedure for changing operating parameters. Always change operating parameters as described in this section. Some parameters that have sensitive functions can only be viewed and changed by qualified persons (for further information on changing parameters, refer to the manual of the communication product).
The operating parameters of the inverter are set to certain values by default. To optimize inverter operation, you can change the operating parameters using a communication product.
Requirements:
☐ Depending on the type of communication, a computer with a BLUETOOTH or Ethernet
interface must be available.
☐ A communication product corresponding to the type of communication used must be
available.
☐ The inverter must be registered in the communication product. ☐ The changes to the grid-relevant parameters must be approved by the responsible grid
operator.
☐ When changing grid-relevant parameters, the SMAGridGuardcode must be available (see
"Application for SMAGridGuard Code" at www.SMA-Solar.com).
Procedure:
1. Call up the user interface of the communication product or software and log in as Installer or User.
2. If required, enter the SMAGridGuardcode.
3. Select and set the required parameter.
4. Save settings.
Operating ManualSTP15-17TL-10-BE-en-1040
Page 41
SMA Solar Technology AG
8 Configuration

8.4 Activating String-Failure Detection

Identical alignment of the PV modules with activated string-failure detection
If you would like to activate the string-failure detection, the PV modules of input A and input B must be aligned identically and the input voltage must be at least 188V. Thus, reversed polarity of the DC connection or a defective string will be recognized by the inverter.
• Ensure that all PV modules are aligned identically.
• Ensure that the input voltage is at least 188V.
If identically aligned PV modules are connected to input A and input B of the inverter, you can activate the self-learning string-failure detection and/or the substring-failure detection.
The basic procedure for changing operating parameters is explained in another section (see Section8.3 "Changing Operating Parameters", page40).
Procedure:
• To activate string-failure detection, select the parameter Operating mode of string failure detection or Op.PvProMod and set to Detect string failures or StrgFltDet.
• To activate string-failure detection and substring-failure detection, select the parameter
Operating mode of string failure detection or Op.PvProMod and set to Detect partial string failures or PaStrgFltDet.

8.5 Setting the Active Power Limitation in case of PV System Control Failure

You will need to set the active power limitation in case of PV system control failure if the active power limitation of the inverter is controlled by a communication product. By setting the active power limitation in case of PV system control failure, you ensure that the inverter will still feed the maximum permissible PV power into the utility grid, even if communication between inverter and communication product has failed.
The basic procedure for changing operating parameters is explained in another section (see Section8.3 "Changing Operating Parameters", page40).
Requirements:
☐ The parameter Operating mode Active power must be set to the value Act. power lim.
via PV system ctrl.
☐ The firmware version of the inverter must be at least 2.62.04.R. ☐ The total installed PV power must be known. ☐ The active power feed-in specified by the grid operator must be known.
Default setting:
• STP15000TL-10: 100%
• STP17000TL-10: 100%
Operating Manual 41STP15-17TL-10-BE-en-10
Page 42
8 Configuration
Procedure:
1. Ensure that the firmware version of the inverter is at least 2.62.04.R. If necessary, carry out a firmware update.
2. Select the parameter Fallback act power lmt P in % of WMax for absent act power lmt and set the required percentage.
3. Select the parameter Operating mode for absent plant control and set to Use fallback
setting.
SMA Solar Technology AG

8.6 Reducing the Attenuation of Ripple Control Signals

By setting certain parameters, the attenuation of three-phase parallel ripple control frequencies ranging from 1,000Hz to 1,100Hz can be avoided. The parameters must only be set in consultation with the responsible grid operator.
The basic procedure for changing operating parameters is explained in another section (see Section8.3 "Changing Operating Parameters", page40).
Requirement:
☐ The firmware version of the inverter must be at least 2.62.04.R.
Procedure:
• Set the following parameters:
Parameter name for RS485
RplDet-NBS-Gain Ripple control signal detection, am-
RplDet-NBS­Damp
RplDet-NBS-Hz Ripple control signal detection, fre-
Parameter name for BLUETOOTH or Speedwire/We­bconnect
plification of narrow-band backup Ripple control signal detection, at-
tenuation of narrow-band backup
quency of the narrow-band backup
Unit Range Value to be set
V/A 0 to -10 -9
p.u. - 0.1
Hz 1,000
to 1,100
Must be specified by the grid oper­ator

8.7 Setting SMA OptiTrac Global Peak

For partially shaded PV modules, you should set the interval at which the inverter is to optimize the MPP of the PV system.
The basic procedure for changing operating parameters is explained in another section (see Section8.3 "Changing Operating Parameters", page40).
Operating ManualSTP15-17TL-10-BE-en-1042
Page 43
SMA Solar Technology AG
8 Configuration
Procedure:
• Select the parameter Cycle time of the OptiTrac Global Peak algorithm or MPPShdw.CycTms and set the required time interval. The ideal time interval is usually six
minutes. This value should only be increased if the shading situation changes extremely slowly.
☑ The inverter optimizes the MPP of the PV system at the predetermined time interval.
Operating Manual 43STP15-17TL-10-BE-en-10
Page 44

9 Operation

SMA Solar Technology AG
9 Operation

9.1 LED Signals

The LEDs indicate the operating state of the inverter.
LED Status Explanation
Green LED glowing Feed-in operation
If an event occurs during feed-in operation, an event mes­sage will be shown on the display (for event messages see the service manual at www.SMA-Solar.com).
flashing The conditions for feed-in operation are not yet met. As
soon as the conditions are met, the inverter will start feed­in operation.
Red LED glowing Error
If an error occurs, the error message and the correspond­ing event number will be shown in the display. The error must be rectified by a qualified person (for troubleshoot­ing, see the service manual at www.SMA-Solar.com).
Blue LED glowing BLUETOOTH communication is activated.
Operating ManualSTP15-17TL-10-BE-en-1044
Page 45
SMA Solar Technology AG
9 Operation

9.2 Display Overview

The display shows the current operating data of the inverter (e.g. current power, daily energy, total energy) as well as events or errors. Power and energy are displayed as bars in a diagram.
Figure 8: Layout of the display (example)
Position Symbol Explanation
A - Current power B - Energy on the current day C - Total amount of energy fed in
Operating Manual 45STP15-17TL-10-BE-en-10
Page 46
9 Operation
SMA Solar Technology AG
Position Symbol Explanation
D Active BLUETOOTH connection
Quality of the BLUETOOTH connection
Active connection to a Speedwire network
Active connection to SunnyPortal
Multifunction relay is active
Power limitation due to excessive temperature
Active power limitation via PV system control
E - Line conductor to which the displayed values apply F Utility grid
G - Event number of an error on the utility grid side H - Output voltage or output current of a line conductor I - Event number of an error in the inverter K Grid relay
When the grid relay is closed, the inverter feeds into the utility grid.
When the grid relay is open, the inverter is disconnected from the utility grid.
L Inverter
M - Input voltage or input current of a line conductor N - Event number of an error on the PV array side O - Text line to display event and error messages P PV Array
Operating ManualSTP15-17TL-10-BE-en-1046
Page 47
SMA Solar Technology AG
Position Symbol Explanation
Q - Diagram with the power curve of the last 16feed-in hours or
energy yields of the last 16days
• In order to switch between diagrams, tap once on the enclosure lid.
R You can operate the display by tapping on the enclosure lid
(see Section9.3, page47).
The displayed error must be rectified on-site by a qualified per­son (for troubleshooting, see service manual at www.SMA-So­lar.com).
The displayed error cannot be rectified on-site.
• Contact Service (see Section13, page56).
9 Operation

9.3 Activating and Operating the Display

You can activate and operate the display by tapping on the enclosure lid.
Procedure:
1. Activate the display. Tap on the enclosure lid once. ☑ The backlight is switched on.
2. To move to the next line, tap on the enclosure lid once.
3. In order to switch between the power curve of the last 16feed-in hours and the energy yields
of the last 16days in the diagram, tap on the enclosure lid once.

9.4 Calling Up Display Messages of the Start-Up Phase

Various inverter information is displayed during the start-up phase that can be called up whenever required during operation.
Procedure:
• Tap on the enclosure lid twice.
☑ The display shows all messages of the start-up phase in sequence.
Operating Manual 47STP15-17TL-10-BE-en-10
Page 48

10 Disconnecting the Inverter from Voltage Sources

SMA Solar Technology AG
10 Disconnecting the Inverter from Voltage Sources
Prior to performing any work on the inverter, always disconnect it from all voltage sources as described in this section. Always adhere to the prescribed sequence.
Destruction of the measuring device due to overvoltage
• Only use measuring devices with a DC input voltage range of 1,000 V or higher.
Procedure:
1. Disconnect the circuit breaker from all three line conductors and secure against reconnection.
2. If the multifunction relay is used, switch off any supply voltage to the load.
3. Test whether there is an acoustic signal.
If an acoustic signals sounds and the display shows an error message that prohibits disconnecting the ESS, wait until dark. The ESS can only be disconnected once it is dark.
If no acoustic signal sounds and the display does not show an error message, remove the ESS.
4. Wait until the LEDs and the display have gone out.
5. Remove all six screws from the lower enclosure
lid using an Allen key (AF3).
6. Flip the lower enclosure lid up and remove it.
7.
Risk of burns when touching the DC protective cover
The DC protective cover can get hot during operation.
• Do not touch the DC protective cover.
8. Use an appropriate measuring device to ensure that no voltage is present at the AC
connecting terminal plate between L1 and N, L2 and N, and L3 and N. Insert the test probe into each round opening of the terminal.
Operating ManualSTP15-17TL-10-BE-en-1048
Page 49
SMA Solar Technology AG
10 Disconnecting the Inverter from Voltage Sources
9. Use an appropriate measuring device to ensure that no voltage is present at the AC
connecting terminal plate between L1 and PE, L2 and PE, and L3 and PE. Insert the test probe into each round opening of the terminal.
10. If you are using the multifunction relay, ensure that no voltage is present between any of the terminals on the multifunction relay and PE on the AC connecting terminal plate.
11. Use a current clamp to ensure that no current is present in the DC cables.
12. Release and remove all DC connectors. To do this, insert a flat-blade screwdriver or an angled screwdriver (blade width: 3.5mm) into one of the side slots and pull the DC connectors straight out. Do not pull on the cable.
13.
Danger to life due to high voltages in the inverter
The capacitors in the inverter take 20minutes to discharge.
• Wait 20minutes before opening the upper enclosure lid.
• Do not open the DC protective cover.
14.
Damage to the inverter due to electrostatic discharge
Touching electronic components can cause damage to or destroy the inverter through electrostatic discharge.
• Ground yourself before touching any component.
Operating Manual 49STP15-17TL-10-BE-en-10
Page 50

11 Technical Data

SMA Solar Technology AG
11 Technical Data
DC Input
STP15000TL-10 STP17000TL-10
Maximum DC power at cosφ=1 15,340W 17,410W Maximum input voltage 1,000V 1,000V MPP voltage range 360Vto800V 400Vto800V Rated input voltage 600V 600V Minimum input voltage 150V 150V Initial input voltage 188V 188V Maximum input current, input A 33A 33A Maximum input current, input B 11A 11A Maximum input current per string, input A* 40A 40A Maximum input current per string, input B* 12.5A 12.5A Maximum short-circuit current, inputA** 50 A 50 A Maximum short-circuit current, input B** 17 A 17 A Maximum reverse current from the inverter
in the system for max. 1ms Number of independent MPP inputs 2 2 Strings per MPP input, input A 5 5 Strings per MPP input, input B 1 1 Overvoltage category in accordance with
IEC60664-1
* To be observed in the event of a short circuit of the electronic string fuse.
** In accordance with IEC62109-2: I
SC PV
AC Output
0 A 0 A
II II
STP15000TL-10 STP17000TL-10
Rated power at 230V, 50Hz 15,000W 17,000W Maximum apparent AC power 15,000VA 17,000VA Rated grid voltage ∼3/N/PE, 230V /
400V
∼3/N/PE, 230V /
400V Nominal AC voltage 220V, 230V, 240V 220V, 230V, 240V AC voltage range* 160V to 280V 160V to 280V Nominal AC current at 230V 21.7A 24.6A
Operating ManualSTP15-17TL-10-BE-en-1050
Page 51
SMA Solar Technology AG
11 Technical Data
STP15000TL-10 STP17000TL-10
Maximum output current 24A 24.6A Total harmonic distortion of the output cur-
≤3% ≤2.6% rent with total harmonic distortion of the AC voltage <2%, and AC power >50% of the rated power
Inrush current < 20% of the nominal AC
current for a maximum of
10ms
Maximum output current under fault condi-
0.05kA 0.05kA
< 20% of the nominal AC
current for a maximum of
10ms
tions Rated power frequency 50Hz 50Hz AC power frequency* 50Hz / 60Hz 50Hz / 60Hz Operating range at AC power frequency
44 Hz to 55 Hz 44 Hz to 55 Hz
50Hz Operating range at AC power frequency
54 Hz to 65 Hz 54 Hz to 65 Hz
60Hz Power factor at rated power 1 1 Displacement power factor cosφ, ad-
0 leading to 0 lagging 0 leading to 0 lagging
justable Feed-in phases 3 3 Connection phases 3 3 Overvoltage category in accordance with
III III
IEC60664-1
* depending on the configured country data set
Protective Devices
DC reverse polarity protection Short-circuit diode, electronic string fuse Protection against reverse currents Electronic string fuse Input-side disconnection point Electronic Solar Switch, SUNCLIX DC connector DC overvoltage protection Thermally monitored varistors or surge arresters
type II (optional) AC short-circuit current capability Current control Grid monitoring SMAGridGuard4 Maximum permissible fuse protection 50A Ground-fault monitoring for STP15000TL-10 Insulation monitoring: R
Operating Manual 51STP15-17TL-10-BE-en-10
> 366.3kΩ
iso
Page 52
11 Technical Data
SMA Solar Technology AG
Ground-fault monitoring for STP17000TL-10 Insulation monitoring: R
> 323.4kΩ
iso
All-pole sensitive residual-current monitoring unit Available Electronic string-current monitoring Available String-failure detection Available
General Data
Width x height x depth, with Electronic Solar Switch
Weight 59kg Length x width x height of the packaging 780mmx380mmx790mm Transport weight 65 kg Climatic category in accordance with
IEC60721-3-3 Environmental category Outdoors Pollution degree outside the inverter 3 Pollution degree inside the inverter 2 Operating temperature range -25°C to +60°C Maximum permissible value for relative humid-
ity, non-condensing Maximum operating altitude above mean sea
level (MSL) Typical noise emission 51dB(A) Power loss in night mode <1W Maximum data volume per inverter with Speed-
wire/Webconnect Additional data volume when using the Sun-
nyPortal live interface Topology transformerless Cooling method SMAOptiCool Degree of protection in accordance with
IEC60529 Protection class in accordance with IEC61140 I
665mmx690mmx265mm
4K4H
100%
3,000m
550 MB/month
600 kB/hour
IP65
Operating ManualSTP15-17TL-10-BE-en-1052
Page 53
SMA Solar Technology AG
11 Technical Data
Grid configurations TN-C, TN-S, TN-C-S, TT (when V Approvals and national standards, as per
10/2014*
AS4777, BDEW2008, C10/11:2012, CE,
CEI0-16, CEI0-21, EN50438, G59/3,
IEC60068-2, IEC61727, MEA/PEA,
IEC62109-2, NEN50438, PPC, PPDS,
RD1699, RD661/2007, SI4777,
UTEC15-712-1, VDE0126-1-1, VDEAR-
N4105, VFR2013, VFR2014
* C10/11:2012: only possible if the three-phase line-to-line voltage is 400V.
EN 50438: does not apply to all national appendices of EN 50438. IEC62109-2: This standard requires that either the multifunction relay in the inverter is used as fault
indicator or that the inverter is connected to SunnyPortal and that the fault alert is activated in SunnyPortal. NRS97-2-1: This standard requires a separate label be attached to the AC distribution board to indicate the AC-side disconnection of the inverter in case of a grid failure (for further details, see NRS97-2-1, Sect. 4.2.7.1 and 4.2.7.2).
MEA/PEA: only applicable to STP17000TL-10
Climatic Conditions
Installation in accordance with IEC60721-3-3, Class4K4H
Extended temperature range -25°C to +60°C Extended humidity range 0%to100% Extended air pressure range 79.5kPato106kPa
Transport in accordance withIEC60721-3-2, Class2K3
Temperature range -25°Cto+70°C
N_PE
< 30V)
ElectronicSolarSwitch
Electrical endurance in the event of short circuit, at nominal current of 33A
Maximum switching current 33 A Maximum switching voltage 1,000 V Maximum power 20 kW Degree of protection when plugged in IP65 Degree of protection when unplugged IP21
At least 50switching operations
Features
DC Connection SUNCLIX DC connector AC connection Spring-cage terminal Display LC graphic display
Operating Manual 53STP15-17TL-10-BE-en-10
Page 54
11 Technical Data
SMA Solar Technology AG
BLUETOOTH As standard RS485, galvanically isolated Optional Speedwire/Webconnect Optional Multifunction Relay Optional SMA Power Control Module Optional
Torques
Upper enclosure lid screws 6Nm ± 0.3Nm Lower enclosure lid screws 2Nm ± 0.3Nm Screws for DC protective cover 3.5Nm Cylindrical screws M5x10 for securing the en-
3.5Nm
closure to the rear panel Additional grounding 6.0Nm SUNCLIX swivel nut 2.0Nm RS485 communication or Speedwire/Webcon-
1.5Nm
nect connection Multi-function relay connection 1.5Nm
Data Storage Capacity
Energy yields in the course of the day 63days Daily yields 30 years Event messages for users 250 events Event messages for installers 250 events
Efficiency
Maximum efficiency, η European efficiency, η
max
EU
98.2%
97.8%
Operating ManualSTP15-17TL-10-BE-en-1054
Page 55
SMA Solar Technology AG

12 Accessories

12 Accessories
You will find the accessories for your product in the following overview. If required, these can be ordered from SMASolarTechnologyAG or your distributor.
Designation Brief description SMA order number
RS485 data module RS458 interface as retrofit kit DM-485CB-10 Speedwire/Webconnect
data module SMAPowerControlModule Multifunction interface for implementing
Multifunction relay Multifunction relay as retrofit kit MFR01-10 DC surge arrester Type II surge arrester for input A and inputBDC_SPD_KIT_2-10
Speedwire/Webconnect data module as retrofit kit
grid management systems for one inverter
SWDM-10
PWCMOD-10
Operating Manual 55STP15-17TL-10-BE-en-10
Page 56

13 Contact

SMA Solar Technology AG
13 Contact
If you have technical problems with our products, please contact the SMAServiceLine. We need the following information in order to provide you with the necessary assistance:
• Inverter device type
• Inverter serial number
• Inverter firmware version
• Special country-specific settings of the inverter (if applicable)
• Type and quantity of PV modules connected
• Mounting location and altitude of the inverter
• Inverter message
• Optional equipment, e.g. communication products
• Operating mode of the multifunction relay (if present)
Australia SMA Australia Pty Ltd.
Sydney
Belgien/Bel­gique/België
Brasil Vide España (Espanha) Česko SMA Central & Eastern Europes.r.o.
Chile Ver España Danmark Se Deutschland (Tyskland) Deutschland SMA Solar Technology AG
España SMA Ibérica Tecnología Solar,
SMA Benelux BVBA/SPRL Mecheln
Praha
Niestetal
S.L.U. Barcelona
Toll free for Australia: 1800SMAAUS (1800762287)
International: +61294914200 +3215286 730
+420235010417
Sunny Boy, Sunny Mini Central, Sun­nyTripower: +495619522‑1499
Monitoring Systems (Kommunikationspro­dukte): +495619522‑2499
Fuel Save Controller (PV-Diesel-Hybridsys­teme): +495619522-3199
Sunny Island, Sunny Backup, Hydro Boy: +495619522-399
Sunny Central: +495619522-299 Online Service: www.SMA.de/Service
Llamada gratuita en España: 900142222
Internacional: +34902142424
Operating ManualSTP15-17TL-10-BE-en-1056
Page 57
SMA Solar Technology AG
13 Contact
France SMA France S.A.S.
Lyon
Sunny Boy, Sunny Mini Central, Sunny Tripower: +33472090440
Monitoring Systems: +33472090441 Sunny Island : +33472090442 Sunny Central : +33472090443
India SMA Solar India Pvt. Ltd.
+912261713888
Mumbai
Italia SMA Italia S.r.l.
+39028934-7299
Milano Κύπρος/Kıbrıs Βλέπε Ελλάδα/ Bkz. Ελλάδα (Yunanistan) Luxemburg/
Luxembourg
Siehe Belgien
Voir Belgique Magyarország lásd Česko (Csehország) Nederland zie Belgien (België) Österreich Siehe Deutschland Perú Ver España Polska Patrz Česko (Czechy) Portugal SMA Solar Technology Portugal,
Unipessoal Lda
Gratuito em Portugal: 800208987 Internacional: +351212377860
Lisboa România Vezi Česko (Cehia) Schweiz Siehe Deutschland Slovensko pozri Česko (Česká republika) South Africa SMA Solar Technology South Africa
Pty Ltd.
08600SUNNY (0860078669) International: +27(12)6431785
Centurion (Pretoria) United King-
dom
Ελλάδα SMA Hellas AE
SMA Solar UK Ltd.
Milton Keynes
Αθήνα
+441908304899
8012229222 International: +302122229222
България Вижте Ελλάδα (Гърция)
SMA Solar (Thailand) Co., Ltd. +6626706999
대한민국 SMA Technology Korea Co., Ltd.서울+82-2-520-2666
Operating Manual 57STP15-17TL-10-BE-en-10
Page 58
/01,234
9:;
5%6!78%
9:;*<+%,='3)>+%
13 Contact
+9712234-6177 SMA Middle East LLC
SMA Solar Technology AG
Other countries International SMA Service Line
Niestetal
Toll free worldwide: 00800SMASERVICE (+8007627378423)
Operating ManualSTP15-17TL-10-BE-en-1058
Page 59
SMA Solar Technology AG

14 EC Declaration of Conformity

14 EC Declaration of Conformity
within the meaning of the EC directives
• 2004/108/EG (Electromagnetic compatibility, EMC)
• 2006/95/EG (Low voltage directive)
• 1999/5/EC (Radio and Telecommunications Terminal Equipment, R&TTE)
SMASolarTechnologyAG confirms herewith that the inverters described in this document are in compliance with the fundamental requirements and other relevant provisions of the above­mentioned directives. The entire EC Declaration of Conformity can be found at www.SMA­Solar.com.
Operating Manual 59STP15-17TL-10-BE-en-10
Page 60
SMA Solar Technology
www.SMA-Solar.com
Loading...