SMA STP 10000TL-10 Installation

Page 1
EN
PV Inverter
SUNNY TRIPOWER 10000TL / 12000TL / 15000TL / 17000TL
Installation Manual
STP10-17TL-IA-en-32 | Version 3.2
Page 2
Page 3
SMA Solar Technology AG Table of Contents
Table of Contents
1 Information on this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.1 Validity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Target Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Additional Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4 Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1 Appropriate Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3 Explanation of Symbols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3.1 Symbols on the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3.2 Symbols on the Type Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.1 Bluetooth. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2 Communication Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Multi-Function Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.4 SMA OptiTrac Global Peak . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.5 Surge Arrester Type II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.6 Intelligent String Failure Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.7 Electronic String Fuse. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.8 Grid Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4 Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.1 Scope of Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.2 Identifying the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.1 Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.2 Selecting the Mounting Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.3 Mounting the Inverter with Rear Panel. . . . . . . . . . . . . . . . . . . . . . . . 23
Page 4
Table of Contents SMA Solar Technology AG
6 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.1 Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.2 Overview of the Connection Area. . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.3 Connecting the Electricity Grid (AC) . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.3.1 Conditions for the AC Connection . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.3.2 AC Connection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.3.3 Connecting the Second Protective Conductor . . . . . . . . . . . . . . . . . 34
6.4 Connecting the PV Array (DC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.4.1 Conditions for DC Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.4.2 Assembling the DC Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.4.3 Opening the DC Connector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.4.4 Connecting the PV Array (DC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.5 Setting the Country Standard and Display Language . . . . . . . . . . . . 44
6.5.1 Checking the Country Standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6.5.2 Extension of the Deactivation Limits . . . . . . . . . . . . . . . . . . . . . . . . . 50
6.5.3 Setting the Country Standard and Language Using the
Rotary Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.6 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.6.1 Bluetooth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.7 Retrofitting a Surge Arrester Type II. . . . . . . . . . . . . . . . . . . . . . . . . . 53
7 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.1 Commissioning the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.2 Display Messages during the Start Phase . . . . . . . . . . . . . . . . . . . . . 58
8 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
8.1 Changing the System Time and System Password. . . . . . . . . . . . . . . 59
8.2 Activating and Setting SMA OptiTrac Global Peak . . . . . . . . . . . . . 59
8.3 Activating the Intelligent String Failure Detection. . . . . . . . . . . . . . . . 60
9 Disconnecting the Inverter from Voltage Sources . . . . . . . . . . 61
9.1 Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
9.2 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
4 STP10-17TL-IA-en-32 Installation Manual
Page 5
SMA Solar Technology AG Table of Contents
10 Maintenance and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
10.1 Cleaning the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
10.2 Checking Heat Dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
10.2.1 Cleaning the Ventilation Grids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
10.2.2 Cleaning the Fan at the Bottom of the Inverter
(STP 15000TL and STP 17000TL only) . . . . . . . . . . . . . . . . . . . . . . 67
10.2.3 Cleaning the Fan on the Left-Hand Side of the Inverter Enclosure . . 68
10.2.4 Checking the Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
10.3 Checking the Electronic Solar Switch (ESS) for Wear . . . . . . . . . . . . 70
11 Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
11.1 Event Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
11.2 Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
12 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
12.1 Sunny Tripower is Beeping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
12.2 Checking the PV Array for Earth Faults . . . . . . . . . . . . . . . . . . . . . . . 83
12.3 Checking the Function of the Varistors. . . . . . . . . . . . . . . . . . . . . . . . 85
12.4 Replacing Surge Arresters Type II . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
13 Decommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
13.1 Dismantling the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
13.2 Replacing the Enclosure Lid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
13.3 Packing the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
13.4 Storing the Inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
13.5 Disposing of the Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
14 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
14.1 Sunny Tripower 10000TL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
14.2 Sunny Tripower 12000TL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
14.3 Sunny Tripower 15000TL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
14.4 Sunny Tripower 17000TL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
15 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
16 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Page 6
Table of Contents SMA Solar Technology AG
6 STP10-17TL-IA-en-32 Installation Manual
Page 7
SMA Solar Technology AG 1 Information on this Manual

1 Information on this Manual

1.1 Validity

This manual describes the procedure for mounting, installation, commissioning, maintenance and troubleshooting of the following SMA inverters:
• Sunny Tripower 10000TL (STP 10000TL-10)
• Sunny Tripower 12000TL (STP 12000TL-10)
• Sunny Tripower 15000TL (STP 15000TL-10)
• Sunny Tripower 17000TL (STP 17000TL-10)
Store this manual where it will be accessible at all times.

1.2 Target Group

This manual is for the use of electrically skilled persons. The tasks described in this manual may be performed by electrically skilled persons only.

1.3 Additional Information

You will find further information on special topics such as the design of a miniature circuit-breaker or the description of the parameters and measured values at www.SMA-Solar.com.
Refer to the user manual provided for detailed information on how to operate the inverter.
Page 8
1 Information on this Manual SMA Solar Technology AG

1.4 Symbols Used

The following types of safety precautions and general information appear in this document:
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE indicates a situation which, if not avoided, could result in property damage.
Information
An Information block provides valuable hints for the efficient installation and operation of your product.
☑ This symbol indicates the result of an action.
8 STP10-17TL-IA-en-32 Installation Manual
Page 9
SMA Solar Technology AG 2 Safety

2 Safety

2.1 Appropriate Usage

The Sunny Tripower is a PV inverter which converts the direct current of a PV array into alternating current and feeds this into the electricity grid.
Principle of a PV system with the Sunny Tripower
String connections Sunny Tripower 10000TL and 12000TL
The Sunny Tripower 10000TL and 12000TL only have four string connections at input A.
The Sunny Tripower must only be operated with PV arrays of protection class II, in accordance with IEC 61730, application class A. Do not connect any energy sources other than PV modules to the Sunny Tripower.
Capacitive leakage currents
PV modules with large capacities relative to earth, such as thin-film PV modules with cells on a metal substrate, may only be used if their coupling capacity does not exceed 2.55 μF.
During feed-in operation, a leakage current flows from the cells to earth, the size of which depends on the manner in which the PV modules are installed (e.g. foil on metal roof) and on the weather (rain, snow). This "normal" leakage current must not exceed 90 mA, as otherwise the inverter would automatically disconnect from the electricity grid as a protective measure. For further information on this subject, see the technical information "Capacitive Leakage Currents" at www.SMA-Solar.com.
When designing the PV system, ensure that the permitted operating range of all components is complied with at all times. The free design programme "Sunny Design", version 2.0 or higher (see www.SMA-Solar.com/SunnyDesign), will assist you in this. The manufacturer of the PV modules must have approved the PV modules for use with the Sunny Tripower. You must also ensure that all measures recommended by the module manufacturer for the long-term maintenance of the module properties are taken (see also technical information "Module Technology" at www.SMA-Solar.com).
Do not use the Sunny Tripower for purposes other than those described here. Alternative uses, modifications to the Sunny Tripower or the installation of components not expressly recommended or sold by SMA Solar Technology AG void the warranty claims and operation permission.
Page 10
2 Safety SMA Solar Technology AG

2.2 Safety Precautions

Danger to life due to high voltages in the inverter
When exposed to sunlight, the PV array generates dangerous DC voltage which is present in the DC conductors and the live components of the inverter. Touching the DC conductors or the live components can lead to lethal electric shocks.
• Do not touch the DC conductors.
• Do not touch any live components of the inverter.
• Prior to performing any work on the inverter, disconnect it from all voltage sources as described in this document (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
Risk of burns due to hot enclosure parts
During operation, the upper enclosure lid and the enclosure body may get hot.
• Only touch the lower enclosure lid during operation.
Possible damage to health due to radiation effects
• Maintain a distance of at least 20 cm from the inverter whenever possible.
Earthing of the PV array
Comply with the local regulations for earthing the modules and the PV array. SMA Solar Technology AG recommends the continuously conductive connection and earthing of the array frame and other electrically conductive surfaces in order to ensure maximum protection for property and persons.
10 STP10-17TL-IA-en-32 Installation Manual
Page 11
SMA Solar Technology AG 2 Safety

2.3 Explanation of Symbols

This section gives an explanation of all the symbols found on the inverter and on the type label.

2.3.1 Symbols on the Inverter

Symbol Description Explanation
Inverter This symbol defines the function of the green LED.
The green LED indicates the operating state of the inverter.
Observe the documentation
Bluetooth This symbol defines the function of the blue LED.
QR Code
®
This symbol defines the function of the red LED which indicates a fault or disturbance. Read the manual to remedy the fault or disturbance.
The blue LED indicates that communication via Bluetooth is activated.
Links to additional information on the inverter can be found at www.SMA-Solar.com.
Danger to life due to high voltages in the inverter
Stickers on the ESS When the Electronic Solar Switch is
Installation Manual STP10-17TL-IA-en-32 11
The capacitors in the inverter may be charged with very high voltages.
• Disconnect the inverter from all voltage sources (see Section 9) and wait 20 minutes before opening the upper enclosure lid in order to allow the capacitors to discharge.
plugged in, the DC circuit is closed.
To interrupt the DC circuit and safely disconnect the inverter when under load, you must first remove the Electronic Solar Switch and then all DC connectors (see Section9 "Disconnecting the Inverter from Voltage Sources", page61). Only unplug the Electronic Solar Switch if the inverter is not displaying any error message prohibiting the removal of the ESS and the inverter is not beeping.
Page 12
2 Safety SMA Solar Technology AG

2.3.2 Symbols on the Type Label

Symbol Description Explanation
Danger to life due to high voltages
The product operates at high voltages. All work on the inverter must be carried out by skilled persons only.
Risk of burns from hot surfaces
The product can get hot during operation. Avoid contact during operation.
Allow the product to cool down sufficiently before carrying out any work. Wear personal protective equipment such as safety gloves.
Observe the documentation Observe all doc ume ntation tha t is sup plied
with the product.
Danger Observe the connection requirements for
the second protective conductor (see Section6.3.3 "Connecting the Second Protective Conductor", page34).
Without transformer The product does not have a transformer.
DC Direct current
AC Three-phase alternating current with
neutral conductor
Degree of protection The product is protected against dust
intrusion and water jets from any angle.
Outdoor The product is suitable for outdoor
installation.
WEEE designation Do not dispose of the product together with
the household waste but only in accordance with the locally applicable regulations for disposal of electronic waste.
CE marking The product complies with the requirements
of the applicable EC directives.
12 STP10-17TL-IA-en-32 Installation Manual
Page 13
SMA Solar Technology AG 2 Safety
Symbol Description Explanation
Device class ID The product is equipped with a wireless
component and complies with device class 2.
RAL quality mark for solar products
The product complies with the requirements of the German Institute for Quality Assurance and Certification.
Certified safety The product is VDE-tested and complies
with the requirements of the German Equipment and Product Safety Act.
C-Tick The product complies with the
requirements of the applicable Australian EMC standards.
Korean mark of conformity The product complies with the
requirements of the applicable Korean directives.
Installation Manual STP10-17TL-IA-en-32 13
Page 14
3 Product Description SMA Solar Technology AG

3 Product Description

The Sunny Tripower is a multi-string inverter which converts the direct current of a PV array into alternating current. To do this, the Sunny Tripower is equipped with two separate MPP trackers which can be connected to the different PV modules. The inverter performs three-phase feed-in of electricity into the electricity grid. Cooling is effected via the OptiCool active cooling system.
In addition, Sunny Tripower is equipped with the features described below.

3.1 Bluetooth

The inverter is equipped with a serial Bluetooth interface and can communicate with special SMA communication products and other inverters (for information on supported products, see www.SMA-Solar.com).
If you wou ld like t o co mmunica te v ia Bluetooth, you can protect the inverter with one system password for the user and one system password for the installer. All inverters are delivered with a standard system password for the user (0000) and a standard system password for the installer (1111).
To protect the system from unauthorised access, you must change the system passwords using Sunny Explorer (for information on changing the system password, refer to the Sunny Explorer help).
If you do not want to communicate via Bluetooth, deactivate Bluetooth communication (see Section6.6.1 "Bluetooth", page52).

3.2 Communication Interface

The inverter can optionally be fitted with an extra communication interface (e.g., RS485). This communication interface enables the inverter to communicate with special SMA communication products or other inverters (for information on supported products, see www.SMA-Solar.com).
The interface can either be retrofitted or installed at the factory according to a specific order. You can only set the operating parameters of the inverter via SMA communication products.
You can set the country data set of the inverter via the two rotary switches in the inverter only prior to commissioning or within the first ten operating hours.
Depending on the type of communication, RS485 or Bluetooth or Speedwire, the parameters and messages are displayed differently in the communication products.
Example: How the country data set parameter is displayed
• For communication with RS485: CntrySet parameter
•If you are using Bluetooth or Speedwire: parameter Set country standard
14 STP10-17TL-IA-en-32 Installation Manual
Page 15
SMA Solar Technology AG 3 Product Description

3.3 Multi-Function Interface

The inverter is equipped with a slot for multi-function interfaces. This slot is designed to connect a simple multi-function relay or an SMA Power Control Module. The interface can either be retrofitted or installed at the factory according to a specific order.
Multi-Function Relay
You can configure the multi-function relay for various operating modes. The multi-function relay is us ed, for exa mpl e, t o switch fau lt i ndi cat ors on o r of f (f or i nformation on installation and configuration, see installation manual of the multi-function relay).
Error message required by technical standards
In some countries the indication of errors is mandatory in order to comply with the requirements of a technical standard, e.g. IEC 62109-2.
To meet the requirements of IEC 62109-2, you must either connect an indicator to the multi-function relay to report an error or register the inverter in the Sunny Portal. If you register the inverter in the Sunny Portal, you can activate the error alarm (for information on error alarm via Sunny Portal, see the Sunny Portal user manual at www.SMA-Solar.com).
SMA Power Control Module
The SMA Power Control Module enables the inverter to implement grid management services and is equipped with an additional multi-function relay (for information on installation and configuration, see installation manual of the SMA Power Control Module).

3.4 SMA OptiTrac Global Peak

SMA OptiTrac Global Peak is a more advanced form of the MPP tracking tool SMA OptiTrac. MPP tracking is a feature that determines the highest usable power in the PV system at any given time.
The power generated by the PV array depends on the level of solar irradiation and the temperature of the PV modules. As a result, the optimum operating point for maximum power (MPP) changes constantly throughout the day.
SMA OptiTrac ensures that the operating point of the inverter always coincides exactly with the MPP. In addition, with the aid of SMA OptiTrac Global Peak, the inverter can detect the presence of several maximum power points in the available operating range, such as may occur particularly with partially shaded PV strings. By this means, almost the entire available power of partially shaded PV strings can be fed into the electricity grid.
SMA OptiTrac Global Peak is deactivated by default. In the case of partially shaded PV modules, it should be activated and set via a communication product (see Section8.2 "Activating and Setting SMA OptiTrac Global Peak", page59).
Installation Manual STP10-17TL-IA-en-32 15
Page 16
3 Product Description SMA Solar Technology AG

3.5 Surge Arrester Type II

Along with the thermally monitored varistors which are integrated as standard, the Sunny Tripower is equipped with module slots for the additional installation of surge arresters of Type II. If the modules are connected, they will be monitored. If a module has tripped, a warning is issued via the display or external communication (e.g. Sunny WebBox or Sunny Explorer). This makes it easy to integrate the Sunny Tripower into a lightning protection concept. The required modules are available as retrofit kits for input A or input A+B.

3.6 Intelligent String Failure Detection

The Sunny Tripower is equipped with a system that recognises the total failure of individual strings or partial strings (see the diagram below). With a PV module current of approx. 1 A, monitoring of up to six partial strings per string input is possible. The prerequisite for the reliable functioning of the intelligent string failure detection is an identical alignment of the connected PV array at input A and input B. For the learning phase, the Sunny Tripower needs approximately 14 days at moderate irradiation after successful activation. One advantage of this system is that its auto-adaptive function completely eliminates the necessity of any configuration. In the event of a string failure, a warning message is issued on the display or via external communication (e.g. Sunny WebBox or Sunny Explorer). Note that extreme shading and snow-covered PV modules trip warning messages.
16 STP10-17TL-IA-en-32 Installation Manual
Page 17
SMA Solar Technology AG 3 Product Description

3.7 Electronic String Fuse

The Sunny Tripower is equipped with an electronic string fuse. This prevents dangerous reverse currents in the PV array and thus plays a key role in fire prevention. Reverse currents can occur as a result of reverse poling during installation or module defects during operation. The electronic string fuse recognises these defects and shorts the PV array. This prevents the occurrence of reverse currents and thus safeguards both the PV system and the Sunny Tripower. An advantage of this method is that conventional fuses at the DC inputs are not necessary. The electronic solution is entirely maintenance-free and does not require any dimensioning.
In order to make optimum use of this function, particular care must be taken during commissioning (see Section6.4 "Connecting the PV Array (DC)", page35). The Sunny Tripower signals dangerous conditions by beeping and issuing warnings in the display or external communication (see Section12.1 "Sunny Tripower is Beeping", page82). If electrical installation takes place under conditions of insufficient irradiation (PV voltage less than 188 V), the Sunny Tripower will not have power supply which means that the protective functions described above will not be active during installation.

3.8 Grid Management

The inverter is equipped with grid management functions. Depending on the requirements of the network operator, you can activate and configure the
functions (e.g. provision of reactive power, active power limitation) via operating parameters (for information on the functions and operating parameters, see the Technical Description "Measured Values and Parameters" at www.SMA-Solar.com).
Installation Manual STP10-17TL-IA-en-32 17
Page 18
4 Unpacking SMA Solar Technology AG

4 Unpacking

4.1 Scope of Delivery

Check the delivery for completeness and for any visible external damage. Contact your specialist dealer if anything is damaged or missing.
Object Quantity Description
A 1 Sunny Tripower B 1 Electronic Solar Switch (ESS) C 1 Rear panel (wall mounting bracket) D 1 Set of documents with explanations and certificates E 1 Installation manual, including user manual F 1 Supplementary sheet with inverter default settings
--- 1 Installation manual for RS485 communication module (optional) G 10/12 DC connector
Sunny Tripower 10000TL / 12000TL: 10 each (5 x positive, 5 x negative) Sunny Tripower 15000TL / 17000TL: 12 each (6 x positive, 6 x negative)
18 STP10-17TL-IA-en-32 Installation Manual
Page 19
SMA Solar Technology AG 4 Unpacking
Object Quantity Description
H 10/12 Sealing plug
Sunny Tripower 10000TL / 12000TL: 10 each
Sunny Tripower 15000TL / 17000TL: 12 each I 1 Eye bolt (M8) for fastening the Sunny Tripower to the rear panel K 2 Cylinder screws (M5x10) for fastening the enclosure to the rear panel L 1 Cable gland for AC connection M 1 Counter nut for cable gland at AC connection N 1 Clamping bracket (M6) for additional earthing O 1 Cheese-head screw (M6) for earth terminal P 1 Conical spring washer (M6) for earth terminal Q 2 Cheese-head screws (M5x20) for upper enclosure lid (spares) R 2 Conical spring washers (M5) for enclosure lid screws (spares)

4.2 Identifying the Inverter

You can identify the inverter by the type label. The type label is located on the right-hand side of the enclosure.
The inverter serial number (Serial No.), the type (Type/Model) and other device-specific characteristics are specified on the type label.
Installation Manual STP10-17TL-IA-en-32 19
Page 20
5 Mounting SMA Solar Technology AG

5 Mounting

5.1 Safety

Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
• Do not mount the inverter on flammable construction materials.
• Do not mount the inverter in areas where highly flammable materials are stored.
• Do not mount the inverter in a potentially explosive atmosphere.
Risk of injury due to the heavy weight of the inverter (approximately 65 kg)
• Take the weight of the inverter into account during transport.
• Select a suitable mounting location and mounting surface.
• When mounting the rear panel, use fastening material suitable for the mounting surface.
• Two people are needed to mount the inverter.
Risk of burns due to hot enclosure parts
• Mount the inverter in such a way that it cannot be touched inadvertently.
20 STP10-17TL-IA-en-32 Installation Manual
Page 21
SMA Solar Technology AG 5 Mounting
max. 15°

5.2 Selecting the Mounting Location

Take the following requirements into consideration when selecting the mounting location:
• The mounting method and location must be suitable for the weight and size of the inverter (see Section14 "Technical Data", page92).
• Mount on a solid surface.
• The mounting location must be clear and safely accessible at all times without the use of additional aids such as scaffolding or lifting platforms. If this is not the case, service work may be restricted.
• Mount vertically or tilted backwards by max. 15°.
• The connection area must point downwards.
• Never mount the device with a forward tilt.
• Never mount the device with a sideways tilt.
• Do not mount horizontally.
• Mount the inverter at eye level. Given the weight of the device, this will facilitate disassembly if service work is necessary.
• The ambient temperature should be below 40°C to ensure optimum operation.
• Do not expose the inverter to direct solar irradiation as this could cause power derating due to overheating.
• In order to avoid audible vibrations in living areas, do not mount the unit on plasterboard walls or similar. When in operation, the inverter emits noise which may be perceived as annoying in living areas.
Installation Manual STP10-17TL-IA-en-32 21
Page 22
5 Mounting SMA Solar Technology AG
• Observe the recommended clearances to walls, other inverters or other objects, as shown in the diagram. That ensures sufficient heat dissipation and gives you enough space to unplug the Electronic Solar Switch.
• If multiple inverters are mounted in areas with high ambient temperatures, allow more than the recommended clearances between the inverters and ensure an adequate fresh-air supply. This prevents a reduction in inverter power as a result of high temperatures (details on temperature derating can be found in the Technical Information "Temperature Derating" at www.SMA-Solar.com).
22 STP10-17TL-IA-en-32 Installation Manual
Page 23
SMA Solar Technology AG 5 Mounting
Display

5.3 Mounting the Inverter with Rear Panel

1. Use the rear panel as a drilling template and mark the positions of the drill holes.
2. Mount the rear panel. To do this, use one upper hole on the right and one
on the left plus the hole in the middle.
Installation Manual STP10-17TL-IA-en-32 23
Page 24
5 Mounting SMA Solar Technology AG
A
3. Hook the inverter into the rear panel, ensuring that the inverter enclosure is positioned flush against the rear panel.
– For two peop le t o trans por t th e in ver ter, hol d th e
inverter by the recessed grips at the bottom and the top edge of the enclosure lid.
– For transport by crane, you can attach two ring
bolts to the top of the inverter (see A: M10, diameter = 10 mm). To do this, remove the filler-plugs and screw in the ring bolts as far as they will go.
4. Remove the ring bolts after transport and re-attach the filler-plugs.
5. Release all six captive screws of the lower enclosure lid.
6. To remove the lower enclosure lid, lift it from the bottom.
7. Screw the supplied eye bolt into the hole provided in order to secure the enclosure from being dislodged. The eye bolt only needs to be fastened hand-tight.
24 STP10-17TL-IA-en-32 Installation Manual
Page 25
SMA Solar Technology AG 5 Mounting
8. In order to secure the enclosure on the rear panel, fasten it at the bottom with the two M5x10 cheese-head screws supplied (torque: max. 3.5 Nm).
9. Check to ensure that the inverter is securely in place.
☑ The inverter is now securely mounted to the wall.
If the inverter is not to be connected immediately, re-attach the lower enclosure lid: – Dock the lower enclosure lid at an angle and
attach. The captive screws must protrude.
– Pre-fasten all six screws and then tighten
them in the sequence shown on the right (torque: 2.0 Nm).
Installation Manual STP10-17TL-IA-en-32 25
Page 26
5 Mounting SMA Solar Technology AG
Optional Anti-Theft Protection
To protect the inverter from theft, you can secure it to the rear panel with a padlock. The padlock must meet the following requirements:
•Size: A: 6 mm to 8 mm diameter B: 23 mm to 29 mm C: 23 mm to 28 mm D: 39 mm to 50 mm E: 13 mm to 18 mm
•Stainless
• Hardened shackle
• Protected lock cylinder
Storage of the key
Keep the key in a safe place in case it is needed for service purposes.
1. Put the shackle of the padlock through the eye of the previously mounted eye bolt and close the padlock.
☑ The inverter is now protected against theft.
26 STP10-17TL-IA-en-32 Installation Manual
Page 27
SMA Solar Technology AG 6 Electrical Connection

6 Electrical Connection

6.1 Safety

Electrostatic discharge can damage the inverter
Internal components of the inverter can be irreparably damaged by electrostatic discharge.
• Earth yourself before touching any components.

6.2 Overview of the Connection Area

Object Description A DC lid (slots for surge arresters and varistors are located here) B Plug for connecting the multi-function relay (optional) C Plug for connecting the RS485 communication module (optional) D Terminal for grid connection E Jumper for setting the language to English F Rotary switch for setting the Bluetooth NetID G Screw for releasing and raising the display H Rotary switches for setting the country standard and display language I Cable entry for the multi-function relay (M20, 5 mm to 13 mm) K Slot for SD card (for service purposes only)
Installation Manual STP10-17TL-IA-en-32 27
Page 28
6 Electrical Connection SMA Solar Technology AG
Object Description A Electronic Solar Switch (ESS) socket B Enclosure opening for the multi-function relay (M20, 5 mm to 13 mm) C Enclosure openings for communication via RS485 (M32) (optional) D Additional enclosure opening (M20) E Enclosure opening for grid connection (AC) (M32, 14 mm to 25 mm) F DC connectors for connecting the strings (input area B) G DC connectors for connecting the strings (input area A)
(for Sunny Tripower 10000TL / 12000TL only four devices)
28 STP10-17TL-IA-en-32 Installation Manual
Page 29
SMA Solar Technology AG 6 Electrical Connection

6.3 Connecting the Electricity Grid (AC)

6.3.1 Conditions for the AC Connection

You must comply with the connection requirements of your network operator.
Residual Current Device
The inverter is equipped with an integrated all-pole-sensitive residual-current monitoring unit. The inverter can automatically differentiate between residual currents and normal leading leakage currents.
If an external RCD or residual-current device is strictly required, you must use a switch that trips at a residual current of 100 mA or higher.
You will find further information for using an RCD in the technical information "Criteria for Selecting an RCD" at www.SMA-Solar.com.
Overvoltage Category
The inverter can be deployed in grids of installation category III or lower, as defined under IEC 60664-1. This means that it can be permanently connected at the grid-connection point in a building. In installations involving long outdoor cable routes, additional overvoltage-reducing measures must be taken so that the overvoltage category is reduced from IV to III (for further information, see the Technical Information "Overvoltage Protection" at www.SMA-Solar.com).
Cable Dimensioning
The cable must be dimensioned in accordance with any local and national directives on cable dimensions which specify requirements for the minimum conductor cross-section. Cable dimensioning factors are e.g.: nominal AC current, type of cable, type of routing, cable bundling, ambient temperature and maximum specified line losses (for calculation of line losses, see design software "Sunny Design" with software version 2.0 or higher at www.SMA-Solar.com).
Installation Manual STP10-17TL-IA-en-32 29
Page 30
6 Electrical Connection SMA Solar Technology AG
Cable Requirements
Position Description Value
A Cable diameter 14 mm to 25 mm B Conductor
cross-section
1.5 mm² to 16 mm², with bootlace ferrule
maximum 10 mm² C Stripping length approximately 12 mm The PE wire must be 5 mm longer than the L and N wires.
Connection of a Second Protective Conductor
In some installation countries, a second protective conductor is required in order to prevent a contact current in the event of failure of the original protective conductor.
For installation countries falling within the scope of validity of the IEC standard 62109, the following requirements are applicable:
• Installation of protective conductor at the AC terminal with a conductor cross-section of at least 10 mm² Cu.
or
• Installation of a second protective conductor at the earth terminal with the same cross-section as the original protective conductor at the AC terminal (see Section6.3.3 "Connecting the Second Protective Conductor", page34).
You must always observe the applicable regulations in the country of installation.
30 STP10-17TL-IA-en-32 Installation Manual
Page 31
SMA Solar Technology AG 6 Electrical Connection
Load Disconnection Unit
You must install a separate miniature circuit-breaker for each inverter in order to ensure that the inverter can be securely disconnected under load. You should use a three-pole miniature circuit-breaker. If you are using a single-pole miniature circuit-breaker, a residual voltage from the inverter may be present on the relevant cable after disconnection (maximum permissible fuse protection (see Section14 "Technical Data", page92)).
Danger to life due to fire
When more than one inverter is connected in parallel to the same miniature circuit-breaker, the protective function of the miniature circuit-breaker is no longer guaranteed. This could result in a cable fire or destruction of the inverter.
• Never connect several inverters to a single miniature circuit-breaker.
• Observe the maximum permissible fuse protection of the inverter when selecting the miniature circuit-breaker.
Danger to life due to fire
When a generator (inverter) and a load are connected to the same miniature circuit-breaker, the protective function of the miniature circuit-breaker is no longer guaranteed. The currents from the inverter and the electricity grid can accumulate to form overcurrents which are not detected by the miniature circuit-breaker.
• Never connect loads between the inverter and the miniature circuit-breaker without fuse protection.
• Always protect loads separately.
Damage to the inverter by use of screw-type fuses as switch-disconnectors
A screw-type fuse, e.g. DIAZED fuse or NEOZED fuse, is not a switch-disconnector and thus may not be used as a load disconnection unit. A screw-type fuse only acts as cable protection.
If the inverter is disconnected under load using a screw-type fuse, the inverter may be damaged.
• Use only a switch-disconnector or a miniature circuit-breaker as a load disconnection unit.
Installation Manual STP10-17TL-IA-en-32 31
Page 32
6 Electrical Connection SMA Solar Technology AG

6.3.2 AC Connection Procedure

1. Check the mains voltage and compare it with the permissible voltage range (see Section14 "Technical Data", page92).
2. Disconnect the miniature circuit-breaker from all three phases and secure against reconnection.
3. Release all six captive screws of the lower enclosure lid.
4. To remove the lower enclosure lid, lift it from the bottom.
5. Check that the country setting of the inverter is correct using the supplementary sheet provided with the default settings.
If the inverter is not set to the desired country standard, adjust the country standard by means of the rotary switches (see Section6.5.3 "Setting the Country Standard and Language Using the Rotary Switch", page51).
6. Remove the adhesive tape from the AC enclosure opening.
32 STP10-17TL-IA-en-32 Installation Manual
Page 33
SMA Solar Technology AG 6 Electrical Connection
L1 L2 L3 N
N
PE
L3
L1
L2
7. Insert the AC cable gland from the outside into the cable entry and tighten it from the inside with the counter nut.
8. Pull the cable through.
9. Raise the terminals of the AC clamp terminal as far as they will go.
Risk of fire if two conductors are connected
If two conductors are connected to one terminal, a poor electrical contact may present a risk of overheating or fire.
• Never connect more than one conductor per terminal.
10. Connect L1, L2, L3, N and the protective conductor (PE) to the AC terminal in accordance with the labelling.
– The PE conductor must be 5 mm longer than the
L and N conductors. – L and N must not be swapped. – The direction of rotation of L1, L2 and L3 is not
relevant.
Danger of crushing when terminals snap shut
The terminals close by snapping down fast and hard.
• P res s th e te rmi nal s do wn w ith you r th umb , do not g rip the sid es o f th e te rmi nal bet ween fin ger s and thumb.
• Keep fingers away from the terminals.
11. Close all terminals of the AC terminal until they snap into place.
Installation Manual STP10-17TL-IA-en-32 33
Page 34
6 Electrical Connection SMA Solar Technology AG
12. Screw the cap nut of the cable gland down tightly on the enclosure opening.
Danger to life due to high voltages in the inverter
• Do not switch on the miniature circuit-breaker until the PV array has been connected and the inverter is securely closed.

6.3.3 Connecting the Second Protective Conductor

If req uir ed b y th e in sta lla tio n, t he e arth ter min al c an b e us ed to connect a second protective conductor or as equipotential bonding.
Procedure
1. Take t he cla mping brac ket, cheese-he ad screw M6 and conical spring washer M6 out of the accessory kit.
2. Insert the stripped earthing cable (D) under the clamping bracket (C) (cross-section: max. 16 mm²).
3. Screw the terminal (C) tight with the screw (A). The toothing of the conical spring washer (B) must face toward the clamping bracket.
34 STP10-17TL-IA-en-32 Installation Manual
Page 35
SMA Solar Technology AG 6 Electrical Connection

6.4 Connecting the PV Array (DC)

6.4.1 Conditions for DC Connection

The inverter has two input areas "A" and "B", each with its own MPP tracker.
Up to four strings (Sunny Tripower 10000TL / 12000TL) or five strings (Sunny Tripower 15000TL / 17000TL) can be connected at input area A. One string can be connected at input area B.
• For input area A, the PV modules must meet the following requirements: – same type – same number of in-series-connected PV modules – identical alignment – identical tilt
• For the activation of the intelligent string failure detection, the PV modules at input A and B must be identically aligned.
• The connecting cables of the PV modules must be equipped with connectors. The connectors required for DC connection are included in the scope of delivery.
Installation Manual STP10-17TL-IA-en-32 35
Page 36
6 Electrical Connection SMA Solar Technology AG
Use of Y adaptors for the parallel connection of strings
Y adaptors must not be visible or freely accessible in close proximity to the inverter.
• The DC electric circuit must not be interrupted by Y adaptors.
• Observe the procedure for disconnecting the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
• The following thresholds at the DC input of the inverter must not be exceeded:
Sunny Tripower
Maximum input voltage
(DC)
Maximum input current
(MPP) (DC)
Maximum
short-circuit current per
string input (DC)
Input area A/B A1 to A5 / B
10000TL 1,000 V 22.0 A / 11.0 A 33 A / 12.5 A 12000TL 1,000 V 22.0 A / 11.0 A 33 A / 12.5 A 15000TL 1,000 V 33.0 A / 11.0 A 40 A / 12.5 A 17000TL 1,000 V 33.0 A / 11.0 A 40 A / 12.5 A
• On the coldest day based on statistical records, the open-circuit voltage of the PV array must never exceed the maximum input voltage of the inverter.
Risk of fire as a result of overcurrent on the string input
Destruction of the inverter
Since the electronic string fuse shorts the PV array in the event of a fault, the thresholds for the maximum short-circuit current per string input given in the table above must not be exceeded. If a string input is overloaded, it can result in an electric arc and hence a risk of fire.
• Make sure that the thresholds specified in the table above are not exceeded.
• Check whether the short-circuit currents of the connected PV modules are in compliance with the thresholds given in the table above.
36 STP10-17TL-IA-en-32 Installation Manual
Page 37
SMA Solar Technology AG 6 Electrical Connection
Function of the Electronic String Fuse
The electronic string fuse prevents reverse currents in the PV array. Activation of the electronic string fuse is only possible if the following conditions are met:
• During installation, the DC input voltage must be at least 188 V (see Section14 "Technical Data", page92) in order to activate the protective function of the integrated electronic string fuse, otherwise, a reversed polarity at the DC connection or a defective string will not be recognised by the inverter.
Risk of fire in the PV array due to non-recognition of reverse currents
The integrated electronic string fuse monitors the PV array and protec ts it ag ainst dangerou s rever se currents. In order to activate the electronic string fuse, you must observe the following during connection of the strings:
• If more than two strings are connected to the inverter, ALWAYS connect the first string to input B. If no string is connected at input B, the string fuse will not be active.
• Each string must be clearly assigned to the correct string input. D o not cr oss-wire or bun dle the string cables. See the diagram in Section 6.4.1 for the correct assignment of the strings.
Use of external string collection boxes
If string collection boxes are used, the functionality of the electronic string fuse may be limited.

6.4.2 Assembling the DC Connectors

For connection to the inverter, all connection cables of the PV modules must be equipped with the DC connectors provided.
Assemble the DC connectors as follows. Be sure to observe the correct polarity. The DC connectors are marked with the symbols "+" and " − ".
Cable Requirements
• Use a PV1-F cable.
Installation Manual STP10-17TL-IA-en-32 37
Page 38
6 Electrical Connection SMA Solar Technology AG
Procedure
1. Lead the stripped cable all the way into the plug.
2. Push the clamping bracket down. ☑ The clamping bracket clicks audibly into place.
3. Ensure that the cable is correctly positioned:
Result Measure
☑ If the stranded wire is visible in the
chamber of the clamping bracket, the cable is correctly positioned.
• Proceed to step 4.
☑ If the stranded wire is not visible in the
chamber, the cable is not correctly positioned.
• Release the clamping bracket. To do so, insert a screwdriver into the clamping bracket and lever it open (blade width: 3.5 mm).
• Remove the cable and go back to step 1.
38 STP10-17TL-IA-en-32 Installation Manual
Page 39
SMA Solar Technology AG 6 Electrical Connection
4. Push the swivel nut up to the thread and tighten (torque: 2.0 Nm).
☑ The DC connectors are assembled and ready for connection to the inverter (see Section6.4.4
"Connecting the PV Array (DC)", page40).

6.4.3 Opening the DC Connector

1. Unscrew the swivel nut.
2. To release the DC connector: Insert a 3.5 mm screwdriver into the snap slot on the side and lever it open.
3. Carefully pull the DC connector apart.
4. Release the clamping bracket. To do this, use a 3.5 mm screwdriver.
5. Remove the cable.
☑ The cable is now detached from the DC connector.
Installation Manual STP10-17TL-IA-en-32 39
Page 40
6 Electrical Connection SMA Solar Technology AG

6.4.4 Connecting the PV Array (DC)

Danger to life due to high voltages in the inverter
• Before connecting the PV array, ensure that the AC miniature circuit-breaker is switched off for all three phase conductors.
Risk of electric arc if the DC connectors are pulled out while the Sunny Tripower is beeping
The integrated electronic string fuse monitors the PV array. In case of incorrect installation (e.g. reverse polarity) or a faulty string, the electronic string fuse short-circuits the PV array and the Sunny Tripower starts to beep.
•Do NOT pull the DC connector out as this could trip an electric arc.
•Do NOT pull out the Electronic Solar Switch as otherwise the entire reverse current will flow through the defective string which could result in a fire.
• Further procedure (see Section12.1 "Sunny Tripower is Beeping", page82).
Destruction of the inverter due to overvoltage
If the voltage of the PV modules exceeds the maximum input voltage of the inverter, it could be destroyed by overvoltage. This will void all warranty claims.
• Do not connect any strings to the inverter which have an open-circuit voltage greater than the maximum input voltage of the inverter.
•Check the system design.
Excessive voltages can destroy the multimeter
• Only use multimeters with a DC input voltage range up to at least 1,000 V.
40 STP10-17TL-IA-en-32 Installation Manual
Page 41
SMA Solar Technology AG 6 Electrical Connection
1. Check the connection cables of the PV modules for correct polarity and make sure that the maximum input voltage of the inverter is not exceeded.
At an ambient temperature over 10°C, the open-circuit voltage of the PV modules should not exceed 90% of the maximum input voltage of the inverter. If this is not the case, review the system design and the PV module circuitry.
Otherwise, the maximum inverter input voltage may be exceeded at low ambient temperatures.
2. Check strings for earth faults (see Section12.2 "Checking the PV Array for Earth Faults", page83).
3. Check the Electronic Solar Switch for wear, as described in Section 10.3. Providing it is in perfect condition, plug the Electronic Solar Switch in right up to the stop. The Electronic Solar Switch must be aligned parallel to and flush with the enclosure.
Only plug the Electronic Solar Switch during installation when the enclosure lid is open. This is necessary in order to activate the protective function of the integrated electronic string fuse.
Risk of fire in the PV array due to non-recognition of reverse currents
The integrated electronic string fuse monitors the PV array and protec ts it ag ainst dangerou s rever se currents. In order to activate the electronic string fuse, you must observe the following during connection of the strings:
• If more than two strings are connected to the inverter, ALWAYS connect the first string to input B. If no string is connected at input B, the string fuse will not be active.
• Each string must be clearly assigned to the correct string input. D o not cr oss-wire or bun dle the string cables. See the diagram in Section 6.4.1 for the correct assignment of the strings.
Use of external string collection boxes
If string collection boxes are used, the functionality of the electronic string fuse may be limited.
Installation Manual STP10-17TL-IA-en-32 41
Page 42
6 Electrical Connection SMA Solar Technology AG
4. If more than two strings are to be connected, check the first assembled DC connector to ensure correct polarity and connect to input B of the inverter.
☑The DC connector clicks audibly into place.
To release the DC connector 6.4.3.
5. After connecting the string, watch out for messages in the display and any acoustic signals. Only continue if the following conditions are fulfilled: – The green LED is glowing or flashing. – There is NO acoustic signal after 30 seconds. – NONE of the error messages 40, 64 or 82 are shown in the display. Otherwise, follow the relevant instructions in the following table:
Event Measure
After 60 seconds, the display is blank and the Sunny Tripower is not beeping although the DC input voltage is over 188 V.
There is a fault in the Sunny Tripower.
• Ensure that the DC cables have not been reverse poled.
•Ensure that DC input voltage of over 188 V is present.
• Contact the SMA Service Line (see Section16 "Contact", page111)
The Sunny Tripower starts beeping.
The Sunny Tripower short-circuits the PV array.
On no account disconnect the Electronic Solar Switch or the DC connectors. Wait until the Sunny Tripower stops beeping (after dark).
Pu lli ng t he D C co nnector s ca use s a r isk of a rci ng, sin ce t he Sunny Tripower short-circuits the PV array in order to prevent reverse currents through individual strings. Depending on the level of irradiation, this could trigger high current flows. However, the PV array and the Sunny Tripower are in a safe state.
• Before leaving the Sunny Tripower, install a contact barrier (e.g., fence) and moisture protection (e.g., tarpaulin).
• Wait until dark before pulling out the Electronic Solar Sw itc h and al l DC con nec tor s, and o nly the n elimin ate any errors (reversed pole or defective string).
42 STP10-17TL-IA-en-32 Installation Manual
Page 43
SMA Solar Technology AG 6 Electrical Connection
Event Measure
The display is showing the error message 40, 64 or
• Follow the instructions on the display (see Section11.2 "Error Messages", page72).
82.
6. Follow the same procedure to connect all further strings.
It is no longer necessary to wait 60 seconds.
7. Ensure that all DC connectors are securely in place.
Number of Strings - Sunny Tripower 10000TL / 12000TL
The Sunny Tripower models 10000TL / 12000TL only have four strings at input A.
8. In order to seal the inverter, all DC inputs that are not required have to be closed as follows:
– Insert the sealing plugs provided into the
DC connectors that are not required. Do not insert sealing plugs into the DC inputs on the inverter.
– Insert the DC connectors with sealing plugs into
the corresponding DC inputs on the inverter.
Installation Manual STP10-17TL-IA-en-32 43
Page 44
6 Electrical Connection SMA Solar Technology AG
9. If the Sunny Tripower does not beep or display an error message, disconnect the Electronic Solar Switch.
☑ The display switches off.
☑ You can now commission the inverter (see Section7 "Commissioning", page56). The following
connections and settings are optional.

6.5 Setting the Country Standard and Display Language

The inverter can be configured for various countries. This is carried out via the two rotary switches in the inverter prior to commissioning, or by configuring the "CntrySet" or "Set country standard" parameter via a communication product (e.g. Sunny WebBox or Sunny Explorer) once you have commissioned the inverter.
The switch position 0/0 indicates the state upon delivery. The country settings were preset at the factory via a communication product if you ordered the inverter with specific country settings. In this case, you will not be able to recognise the current setting by the switch position. If changes are made via the rotary switches or via a communication product, the default grid parameters are overwritten. They cannot be restored, and must be re-entered via a communication product. The display language ca n be cha nge d at any tim e us ing the rota ry s wit che s, i nde pen dent of the grid parameters. This means that the default grid parameters remain unchanged, but the display messages are shown in the set language. For devices ordered without any specified country of installation, the standard setting is "VDE0126-1-1" and the language is German.
Changes will be accepted immediately after switching the miniature circuit-breaker on. If a non-programmed switch setting is selected, the inverter issues an error message on the display and the last valid setting is retained.
44 STP10-17TL-IA-en-32 Installation Manual
Page 45
SMA Solar Technology AG 6 Electrical Connection
SMA Grid Guard Protected Country Data Sets
In some countries, the local connection conditions demand a mechanism which prevents the feed-in parameters from being changed. Therefore, some country data sets are protected and can only be unlocked with a personal access code, the SMA Grid Guard code.
SMA Grid Guard protected country data sets are automatically blocked for ten feed-in hours after commissioning, or after the last alteration. If the country data set is changed after these ten feed-in hours, the inverter will not accept the changes and display the error message "Grid parameter locked". If, however, a later change to the country data set only relates to a change of the display language via the rotary switches in the inverter, this change is immediately applied.
It is also p ossible to conf igure country data s ets (parameter "CntrySet" or "Set country standard"), and to lock or unlock these manually via a communication product. To lock a data set, enter the digit sequence "54321" instead of the password in the SMA Grid Guard code field. The data set can only be unlocked by entering a personal, ten-digit SMA Grid Guard code which is valid for a maximum of ten feed-in hours. The application form for the personal access code is available at www.SMA-Solar.com in the "Certificate" category of the respective inverter. The language can be configured without a password, regardless of the country data set.
Changing parameters in SMA Grid Guard protected country data sets
If the para meter s withi n protec ted cou ntry da ta sets are chan ged, t hes e ar e no long er p rot ect ed and instead of the standard, "ADJ" or "Special setting" is displayed. In this case, a change to parameters is not locked automatically after ten feed-in hours, but has to be locked manually. To manually lock the parameters, set the SMA Grid Guard Code to "54321".
Further information on parameter settings
You will find information on making adjustments and changing parameters in the user manual for your software.
The last change (executed via rotary switch or communication product) is always verified and activated if applicable. Consequently, the switch position may not necessarily show the actual country setting.
Installation Manual STP10-17TL-IA-en-32 45
Page 46
6 Electrical Connection SMA Solar Technology AG

6.5.1 Checking the Country Standard

Check whether the inverter is set to the country of installation.
Before commissioning:
• Check that the country standard of the inverter is correct by comparing the default settings of the inverter listed on the supplementary sheet provided.
After commissioning:
• Check that the country standard is correct by checking the display message during (re-)commissioning (see Section7 "Commissioning", page56).
or
• Check that the country standard is correct using the "SMA grid guard" measuring channel via a communication product.
Display language
Once you have set the country standard, you can always set the display language later using rotary switch B. However, you have to then set rotary switch A to "0" in order to keep the country data set.
The settings of each country data set are specified in the operating parameters. The parameters can be read out using a communication product. The description of the operating parameters is available at www.SMA-Solar.com in the category "Technical Description" of the respective inverter.
(A) (B) Country data set Display language Grid Guard
protection
0 0 default settings default settings dependent on
parameter set
0 1 retained English dependent on
parameter set
0 2 retained German dependent on
parameter set
0 3 retained French dependent on
parameter set
0 4 retained Spanish dependent on
parameter set
0 5 retained Italian dependent on
parameter set
0 6 retained not assigned* dependent on
parameter set
46 STP10-17TL-IA-en-32 Installation Manual
Country
dependent on parameter set
dependent on parameter set
dependent on parameter set
dependent on parameter set
dependent on parameter set
dependent on parameter set
dependent on parameter set
Page 47
SMA Solar Technology AG 6 Electrical Connection
(A) (B) Country data set Display language Grid Guard
Country
protection
0 7 retained not assigned* dependent on
parameter set
0 A retained Dutch dependent on
parameter set
1 2 VDE-AR-N4105
a)
1 4 VDE-AR-N4105-MP 1 6 VDE-AR-N4105-HP
German yes Germany
b)
German yes Germany
c)
German yes Germany
dependent on parameter set
dependent on parameter set
1 0 VDE0126-1-1 German yes Germany,
Switzerland
1 8 VDE0126-1-1 French yes Switzerland,
France 1 9 VDE0126-1-1/UTE French yes France 2 0 VDE0126-1-1 Italian yes Switzerland 2 8 AS4777.3 English no Australia 3 2 CEI0-21Ext
d)
Italian no Italy 4 0 RD1699* Spanish yes Spain 4 1 RD1663/661 Spanish yes Spain 48PPC not assigned* no Greece 4 9 PPC English no Greece 5 1 KEMCO 501/2009 English no South Korea 5 8 G83 English no England 5 A G59/2 English no England 6 0 EN50438 German yes various 6 1 EN50438 English yes
EU countries
6 2 EN50438 French yes 6 3 EN50438 Italian yes 6 4 EN50438 Spanish yes 6 5 EN50438 not assigned* yes 6 6 EN50438 not assigned* yes 6 E NEN-EN50438 Dutch yes Netherlands 7 4 PPDS not assigned* yes Czech
Republic
Installation Manual STP10-17TL-IA-en-32 47
Page 48
6 Electrical Connection SMA Solar Technology AG
(A) (B) Country data set Display language Grid Guard
Country
protection
7 5 PPDS English yes Czech
Republic
7 6 PPDS German yes Czech
Republic 7 8 C10/11/2012 French yes Belgium 7 9 C10/11/2012 English yes Belgium 7 A C10/11/2012 German yes Belgium 7 B C10/11/2012 Dutch yes Belgium A 0 MVtg-Directive German yes Germany A 1 MVtg-Directive English yes flexible A 2 MVtg-Directive French yes France A 3 MVtg-Directive Spanish yes Spain A 4 MVtg-Directive not assigned* yes Czech
Republic A8CN/CGC/
English no China
GF001:2009** A C SI 4777 English yes Israel B 0 MVtg-Directive int German yes Germany B 1 MVtg-Directive int English yes flexible B 2 MVtg-Directive int French yes France B 3 MVtg-Directive int Spanish yes Spain B 4 MVtg-Directive int not assigned* yes Czech
Republic C0Customer English no flexible C 1 Customer German no flexible C 2 Customer French no flexible C 3 Customer Spanish no flexible C 4 Customer Italian no flexible C 5 Customer not assigned* no flexible C 6 Customer not assigned* no flexible D 0 Off-Grid60 English no flexible D 1 Off-Grid60 German no flexible
48 STP10-17TL-IA-en-32 Installation Manual
Page 49
SMA Solar Technology AG 6 Electrical Connection
(A) (B) Country data set Display language Grid Guard
Country
protection
D 2 Off-Grid60 French no flexible D 3 Off-Grid60 Spanish no flexible D 4 Off-Grid60 Italian no flexible D 5 Off-Grid60 not assigned* no flexible D 6 Off-Grid60 not assigned* no flexible E 0 Off-Grid50 English no flexible E 1 Off-Grid50 German no flexible E 2 Off-Grid50 French no flexible E 3 Off-Grid50 Spanish no flexible E 4 Off-Grid50 Italian no flexible E 5 Off-Grid50 not assigned* no flexible E 6 Off-Grid50 not assigned* no flexible F0SD-Card SD-Card no flexible
a) Configurable from Firmware Version 2.31. Setting in accordance with VDE-ARN-4105 (Germany) for PV systems
< 3.68 kVA
b) Configurable from Firmware Version 2.31. Setting in accordance with VDE-ARN-4105 (Germany) for PV systems
> 3.68 kVA and < 13.8 kVA
c) Configurable from Firmware Version 2.31. Setting in accordance with VDE-ARN-4105 (Germany) for PV systems
> 13.8 kVA
d) Configurable from Firmware Version 2.50. Setting according to CEI 0-21 for PV systems with external grid and
system protection > 6 kVA (Italy)
* Currently not assigned. The previously configured display language is maintained.
If the inverter is not set to the country of installation, there are several ways of configuring the required country standard:
• Setting via the two rotary switches (see Section6.5.3 "Setting the Country Standard and Language Using the Rotary Switch", page51).
• Alternatively, you can carry out the settings via the "CntrySet" or "Set country standard" parameters using a communication product, once you have commissioned the inverter.
•If you require adjusted parameter settings for your installation site, you can change these with the help of a communication product.
Installation Manual STP10-17TL-IA-en-32 49
Page 50
6 Electrical Connection SMA Solar Technology AG

6.5.2 Extension of the Deactivation Limits

The deactivation criteria (voltage, frequency) are specified by the country parameters. Sunny Tripower inverters have the additional country data set "MVtgDirective". This parameter
expands the deactivation limits of the inverter for voltage and frequency to a maximum/minimum. This country setting may only be selected if the system or the inverter is operated with external three-phase decoupling protection, which will automatically disconnect the inverter from the electricity grid if non-permissible voltage and frequency values occur. Device protection is still guaranteed.
Danger to life due to electric shock if external decoupling protection is missing
With the country setting "MVtgDirective", the inverter may only be operated with an external three-phase decoupling protection device which complies with the country-specific requirements.
Without such external decoupling protection, the inverter will not disconnect from the electricity grid when the standard requirement is exceeded.
• Install external three-phase decoupling protection.
50 STP10-17TL-IA-en-32 Installation Manual
Page 51
SMA Solar Technology AG 6 Electrical Connection

6.5.3 Setting the Country Standard and Language Using the Rotary Switch

1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
2. Set the arrows on the rotary switches (A and B) to the required position using a screwdriver (see Section6.5.1 "Checking the Country Standard", page46). Use a screwdriver with blade width 2.5 mm.
Jumper for English language
You can also adjust the language to English by means of a jumper (e.g. for service purposes).
• To do so, plug the jumper onto the upper two pins as shown on the right.
3. Restart the inverter (see Section7 "Commissioning", page56).
Installation Manual STP10-17TL-IA-en-32 51
Page 52
6 Electrical Connection SMA Solar Technology AG

6.6 Communication

6.6.1 Bluetooth

Communication via Bluetooth with a communication product is activated by default. Networking with other inverters via Bluetooth is deactivated by default.
The following setting options are possible via a rotary switch:
Switch position (NetID)
0Off 1 Communication via Bluetooth with communication product possible,
2 to F Networking with other inverters
In order to restrict communication via Bluetooth between the inverters of your system and those of neighbouring systems, you can assign an individual NetID to the inverters of your system (switch position 2 to F). However, this is only necessary if neighbouring systems are situated within a radius of 500 m.
All inverters in your system must have the same NetID in order to be detected by your communication product.
System password for user and installer
If you are using Bluetooth communication, you can protect the inverter with a system password for the user and a system password for the installer. All inverters are delivered with the same default system password. To protect the system from unauthorised access, you must change system passwords using a communication product.
If you are not using Bluetooth communication, deactivate it. This will protect your system from unauthorised access.
Changing the system time
If communication is effected via Bluetooth and Sunny Explorer, you must change the system time (date and time) via a communication product after commissioning. This will prevent disturbances when retrieving saved events.
Setting
no networking with other inverters (default setting)
52 STP10-17TL-IA-en-32 Installation Manual
Page 53
SMA Solar Technology AG 6 Electrical Connection
To do this, proceed as follows:
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
2. Set the arrow on the rotary switch (C) to the required position with a screwdriver. Use a screwdriver with blade width 2.5 mm.
3. Restart the inverter (see Section7 "Commissioning", page56).
Activation of settings
The Bluetooth settings will only be activated after the miniature circuit-breaker has been switched on, the PV array connected and the Electronic Solar Switch plugged in.

6.7 Retrofitting a Surge Arrester Type II

The inverter can be equipped ex works with surge arresters, or they can be retrofitted at a later time. The order numbers for both retrofit kits (1 for input A only, 1 for input A and B) can be found in Section 15.
To carry out retrofitting, proceed as follows:
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
Danger to life due to high voltages in the inverter
Death from electric shock
There is residual voltage in the inverter. The inverter takes 20 minutes to discharge.
• Wait 20 minutes before you open the upper enclosure lid or the DC lid.
Installation Manual STP10-17TL-IA-en-32 53
Page 54
6 Electrical Connection SMA Solar Technology AG
2. Unscrew the captive screws of the DC lid on the left-hand side of the connection area.
3. Lift the DC lid up from the bottom to remove it.
4. Plug all surge arresters into the slots provided until they snap into place with the side latches. – The surge arrester marked "PE 500" must be
inserted in the bottom slot.
– If surge arresters are only required for input A,
the two surge arresters must be mounted on the two upper slots.
– If input B is also to be protected, surge arresters
must be plugged into all slots.
54 STP10-17TL-IA-en-32 Installation Manual
Page 55
SMA Solar Technology AG 6 Electrical Connection
– A green strip in the window (A) indicates that
the surge arrester is fully functional. A red strip in the win dow indi cat es t hat the surg e ar rest er i s faulty. In this case, a warning also appears in the display with the event number "83".
5. Dock the DC lid at an angle, and attach. The captive screws must protrude.
6. Pre-screw all four screws of the DC lid and then tighten them (torque: 3.5 Nm).
☑ The surge arresters are now installed and the inverter can be re-commissioned
(see Section7 "Commissioning", page56).
Installation Manual STP10-17TL-IA-en-32 55
Page 56
7 Commissioning SMA Solar Technology AG

7 Commissioning

7.1 Commissioning the Inverter

1. Check that the device is fixed securely to the wall (see Section5 "Mounting", page20).
2. Check that the country configuration is correct (see Section6.5 "Setting the Country Standard and Display Language", page44).
3. Check that the AC grid cable is connected correctly (see Sect ion6.3 "Connecting the Electricity Grid (AC)", page29).
4. Check that the DC cables (PV strings) are connected correctly (see Section6.4 "Connecting the PV Array (DC)", page35).
5. Close unused DC inputs with the appropriate DC connectors and sealing plugs (see Section6.4.4 "Connecting the PV Array (DC)", page40).
6. Close all enclosure openings.
7. Dock the lower enclosure lid at an angle and attach. The captive screws must protrude.
8. Pre-screw all six screws and then tighten them in the sequence shown on the right (torque: 2.0 Nm).
56 STP10-17TL-IA-en-32 Installation Manual
Page 57
SMA Solar Technology AG 7 Commissioning
9. Plug the Electronic Solar Switch in firmly right up to the stop.
10. Switch on the miniature circuit-breaker.
11. If a multi-function relay is connected, switch on the supply voltage.
12. Check whether the display and LEDs are indicating a normal operating state.
LED Colour Meaning A Green Glowing: operation
Flashing: waiting for sufficient irradiation
B Red Disturbance C Blue Bluetooth communication
is active
☑ If the inverter has been commissioned successfully, the green LED should be on or flashing,
provided there is sufficient solar irradiation. The significance of a glowing red LED and of the event numbers on the display is described in
Section 11.2.
Installation Manual STP10-17TL-IA-en-32 57
Page 58
7 Commissioning SMA Solar Technology AG
Language english

7.2 Display Messages during the Start Phase

Illustrated display messages
The display messages illustrated in this section serve as examples and, depending on the country setting, may differ from the actual display messages on your inverter.
• The firmware version of the internal processors appears first in the text line.
• A fte r an int erv al o f fi ve s eco nds , or afte r ta ppi ng o n the enclosure lid, the serial number (or designation of the inverter) and the NetID for communication via Bluetooth wil l ap pear. Th e de sig nat ion of th e in ver ter can b e ch ang ed with a com mun ica tio n product.
• After a further five seconds or a further tap, the configured country standard is displayed (example: "VDE0126-1-1").
• After a further five seconds or another tap, the configured language is displayed (example: "Language English").
• During normal operation, the text line of the display will subsequently be blank. See Section 11 for event messages which may be displayed in the text line and their meaning.
Showing display messages again (valid from Firmware Version 2.33)
If you want to view the display messages of the start-up phase again during normal operation, tap the enclosure lid twice in quick succession.
58 STP10-17TL-IA-en-32 Installation Manual
Page 59
SMA Solar Technology AG 8 Configuration

8 Configuration

8.1 Changing the System Time and System Password

Requirements:
•A computer with Bluetooth interface must be available.
• Sunny Explorer with software version 1.04 or higher must be installed on the computer.
• The system must be logged in Sunny Explorer.
1. Change the standard system password (see Sunny Explorer help). This will protect your system from unauthorised access.
2. Change the system time (see Sunny Explorer help).

8.2 Activating and Setting SMA OptiTrac Global Peak

With partially shaded PV modules, you should activate SMA OptiTrac Global Peak and set the time interval in which the inverter will optimise the MPP of the PV system.
Requirements:
• A communication product that is appropriate for the type of communication used must be available.
1. Access the user interface of the communication product and log in as an installer.
2. Select the parameter Power limit of the OptiTrac Global Peak and set to On.
3. Select the parameter Cycle time of the OptiTrac Global Peak algorithm an d se t th e de sired time interval. Hint: The ideal time interval is normally six minutes. This value should only be increased if the shading situation changes extremely slowly.
☑ The inverter optimises the MPP of the PV system at the specified time interval.
Installation Manual STP10-17TL-IA-en-32 59
Page 60
8 Configuration SMA Solar Technology AG

8.3 Activating the Intelligent String Failure Detection

The intelligent string failure detection process is deactivated by default. You can activate the string failure detection by setting a parameter via communication (e.g. Sunny WebBox or Sunny Explorer). To do this, you will need the installer password.
Activating or Deactivating String Failure Detection
Parameter Setting Description
Op.PvProMod/ Operating mode of string failure detection
Resetting the Operating Data for String Failure Detection
Parameter Description
Op.PvValRsIstl/ Reset operating data for string failure detection
Stop String failure detection deactivated StrgFltDet/
Detect string failures PaStrgFltDet/
Detect sub-string failures
Restart of learning phase Operating data for string failure detection are reset.
String-failure detection activated
String and sub-string failure detection activated
60 STP10-17TL-IA-en-32 Installation Manual
Page 61
SMA Solar Technology AG 9 Disconnecting the Inverter from Voltage Sources

9 Disconnecting the Inverter from Voltage Sources

9.1 Safety

Danger to life due to high voltages in the inverter
Death from electric shock
The inverter operates at high voltages and must be disconnected prior to carrying out work on the device. Furthermore, if the DC connectors are pulled out without first unplugging the Electronic Solar Switch, a dangerous electric arc can occur.
• Disconnect the inverter as described in the following section.
Risk of burns due to hot DC lid
During operation, the DC lid on the left-hand side of the connection area can get hot.
• Take care not to touch the DC lid when working in the connection area.
Electrostatic discharge can damage the inverter
Internal components of the inverter can be irreparably damaged by electrostatic discharge.
• Earth yourself before touching any components.
Installation Manual STP10-17TL-IA-en-32 61
Page 62
9 Disconnecting the Inverter from Voltage Sources SMA Solar Technology AG

9.2 Procedure

1. Disconnect the miniature circuit-breaker from all three phases and secure against reconnection.
2. If a multi-function relay is connected, disconnect its supply voltage and ensure that it cannot be reconnected.
3. Check the status of the Sunny Tripower:
Event Measure
The Sunny Tripower is beeping or there is an error message on the display prohibiting the removal of the Electronic Solar Switch.
The Sunny Tripower is not beeping and there is no error message on the display.
4. Wait until the LEDs, display and fault indicator have gone out.
5. Release all six captive lid screws.
• Wait until the Sunny Tripower stops beeping (after dark) and only then disconnect the Electronic Solar Switch and the DC connectors.
• Correct the error (see Section 12.1 or Section 11.2).
• Remove the Electronic Solar Switch.
• Proceed to step 4.
6. To remove the lower enclosure lid, lift it up from the bottom.
62 STP10-17TL-IA-en-32 Installation Manual
Page 63
SMA Solar Technology AG 9 Disconnecting the Inverter from Voltage Sources
PE
PE
7. Use a suitable multimeter to verify the absence of voltage for L1, L2 and L3 to N at the AC terminal. The maximum diameter of the test probe is 2 mm.
☑If voltage is present, check the installation.
8. Verify the absence of voltage in L1, L2 and L3 to PE at the AC terminal.
☑If voltage is present, check the installation.
9. Verify the absence of voltage in the multi-function relay to PE at all terminals.
☑If voltage is present, check the installation.
Installation Manual STP10-17TL-IA-en-32 63
Page 64
9 Disconnecting the Inverter from Voltage Sources SMA Solar Technology AG
10. Release and disconnect all DC connectors. To do this, insert a flat-blade screwdriver (b lad e wi dth : 3. 5 m m) i nto one of the si de s lot s an d pull the DC connectors out straight. Do NOT PULL ON THE CABLE.
☑ All DC connectors are disconnected from the
inverter. The inverter is completely disconnected from the PV array.
Danger to life due to high voltages in the inverter
There is residual voltage in the inverter. The inverter takes 20 minutes to discharge.
• Wait 20 minutes before you open the upper enclosure lid or the DC lid.
☑ The inverter is now voltage-free and work can be carried out.
64 STP10-17TL-IA-en-32 Installation Manual
Page 65
SMA Solar Technology AG 10 Maintenance and Cleaning

10 Maintenance and Cleaning

10.1 Cleaning the Inverter

Damage to the display by use of cleaning agents
• If the inverter is dirty, clean the enclosure lid, the display and the LEDs using only clear water and a cloth.

10.2 Checking Heat Dissipation

If the inverter regularly goes into derating due to excessive heat (temperature symbol on the display illuminates), this may be due to one of the following reasons:
• The ventilation grids on the sides are clogged with dirt. Clean the ventilation grids as described in the following.
• One of the fans is clogged. The inverter has two integrated fans for cooling. One of these is located at the bottom of the
inverter next to the connection area and the other on the left-hand side of the enclosure under the ventilation grid.
If the fan enclosure is just covered in loose dust you can clean it with a vacuum cleaner. If you do not achieve satisfactory results with a vacuum cleaner, you can dismantle the fan for cleaning, as described in the following sections.
Installation Manual STP10-17TL-IA-en-32 65
Page 66
10 Maintenance and Cleaning SMA Solar Technology AG

10.2.1 Cleaning the Ventilation Grids

The inverter takes cooling air in from underneath on the left side and blows it out again through the ventilation grids at the top. Clean the ventilation grids if they are dirty.
Procedure
1. Turn the rotary fastener of the ventilation grid in the direction of the arrow until the notch is in a vertical position.
2. Remove the ventilation grid.
3. Clean the ventilation grid with a soft brush, a paint brush or compressed air.
4. Re-attach the ventilation grid to the inverter.
5. Turn the notch of the rotary fastener back 90° to a horizontal position.
Risk of damage to the inverter through intrusion of insects
• The ventilation grids must not be removed permanently, because otherwise the device will not be protected against the intrusion of insects.
66 STP10-17TL-IA-en-32 Installation Manual
Page 67
SMA Solar Technology AG 10 Maintenance and Cleaning

10.2.2 Cleaning the Fan at the Bottom of the Inverter (STP 15000TL and STP 17000TL only)

1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
2. Wait for the fan to stop rotating.
Cleaning the Fan Guards
3. To dismantle the fan guard: – Use a screwdriver to press both latches at the
right edge of the fan guard to the right and dislodge it from the retainer.
– Carefully remove the fan guard.
4. Clean the fan guard with a soft brush, a paint brush, a cloth or compressed air.
Cleaning the Fans
5. Press the latches in towards the centre.
6. Remove the fan by pulling it slowly and carefully downwards.
7. Release and remove the plug. Th e fa n cable s ar e lo ng enoug h to let you lif t th e fan
out sufficiently to disconnect the plugs inside the inverter.
8. Remove the fan and clean it with a soft brush, a paint brush or a cloth and water.
Damage to the fan through use of compressed air
• Do not use compressed air to clean it. This could damage the fan.
Installation Manual STP10-17TL-IA-en-32 67
Page 68
10 Maintenance and Cleaning SMA Solar Technology AG
9. After cleaning, reassemble everything in reverse order.
10. Check that the fan is functional (see Section10.2.4 "Checking the Fans", page69).

10.2.3 Cleaning the Fan on the Left-Hand Side of the Inverter Enclosure

1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
2. Turn the rotary fastener of the ventilation grid in the direction of the arrow until the notch is in a vertical position.
3. Remove the ventilation grid.
4. Wait for the fan to stop rotating.
5. Press the latches in towards the centre.
6. Remove the fan by pulling it slowly and carefully out sideways.
68 STP10-17TL-IA-en-32 Installation Manual
Page 69
SMA Solar Technology AG 10 Maintenance and Cleaning
7. Release and remove the plug. Th e fa n cable s ar e lo ng enoug h to let you lif t th e fan
out sufficiently to disconnect the plugs inside the inverter.
8. Remove the fan and clean it with a soft brush, a paint brush or a cloth and water.
Damage to the fan through use of compressed air
• Do not use compressed air to clean it. This could damage the fan.
9. After cleaning, reassemble everything in reverse order.
10. Check that the fans are functional (see Section10.2.4 "Checking the Fans", page69).

10.2.4 Checking the Fans

Checking the fans
To test the fans you wil l need a special data capture dev ice (e.g., Sunny WebBox) or a PC with appropriate software (e.g., Sunny Explorer) so that you can change the parameters of the inverter.
You will also need the installer password to access the installer mode.
1. Enter the installer password.
2. Set the parameters "CoolSys.FanTst" or "Fan test" to "On" in the installer mode.
3. Check the air flow in both fans. The inverter takes cooling air in from underneath on the left side and blows it out again through
the ventilation grids at the top. Listen for any unusual noise, which could indicate incorrect installation or a fault in the fans.
4. After the test, set the parameter "CoolSys.FanTst" or "Fan test" back to the "Off" position.
☑ The fan test is now complete.
Installation Manual STP10-17TL-IA-en-32 69
Page 70
10 Maintenance and Cleaning SMA Solar Technology AG

10.3 Checking the Electronic Solar Switch (ESS) for Wear

Check the Electronic Solar Switch for wear before plugging it in. To do this, check whether the metal tongues (A) inside the plug display any brown discolouration.
If the metal tongues are discoloured or burnt right through (B), the Electronic Solar Switch can no longer perform reliable disconnection of the DC side.
You must replace the handle of the Electronic Solar Switch before restarting the inverter. You can obtain replacement handles for the Electronic Solar Switch from your specialist dealer (see Section15 "Accessories", page110).
70 STP10-17TL-IA-en-32 Installation Manual
Page 71
SMA Solar Technology AG 11 Messages

11 Messages

No display messages if no DC voltage present
Measurements and the display of messages are only possible when there is sufficient DC voltage (green LED flashing or glowing).

11.1 Event Messages

During an update, the relevant display message is shown in the text line of the display.
Message Description
< Inst. code valid > The SMA Grid Guard code entered is valid.
The configured country data set is now unlocked and can be changed.
If the configured country data set is protected, the unlocking is valid for a maximum of ten feed-in hours.
< No new update SDcard > There is no relevant update file for this Sunny Tripower on
the SD card, or the present update has already been executed.
< Grid param.unchanged > The selected switch setting is not programmed or there is
no country data set available on the SD card.
< Parameters set successfully > All parameters of the SD card, e.g. country data set,
have been successfully adopted. < SD card is read > The inverter is currently reading the SD card. < Set parameter > The inverter is configuring the parameters from the
SD card settings. < Self-test > The inverter is carrying out the self-test. < Update completed > The inverter has successfully completed the update. < Update Bluetooth > Update of the Bluetooth component successful. < Update display > Update of the display successful. < Update main CPU > Update of the inverter component successful. < Update communication > Update of communication component successful. < Update string fuse > Update of electronic string fuse successful. < Update RS485I module > Update of communication interface successful. < Upd. language table > Update of language table successful. < Update file OK > The update file found is valid.
Installation Manual STP10-17TL-IA-en-32 71
Page 72
11 Messages SMA Solar Technology AG

11.2 Error Messages

The text line on the display shows the relevant display messages whenever an error occurs. Two-digit event numbers corresponding to the displayed messages are shown above the text line, and three-digit or four-digit event numbers in the text line directly in front of the display message. You can scroll down multi-line messages by tapping on the lower enclosure lid.
If the error exists over a long period of time, the red LED lights up and the multi-function relay is activated.
In addition, depending on the severity of the disturbance the "spanner" or "telephone receiver" symbol on the display will light up.
• Spanner: signifies a disturbance which can be remedied on-site (see table below).
• Telephone receiver: signifies device disturbance. Contact SMA Service Line.
Event no. Display message and cause Corrective measures
101 to 103
202 to 203
< Grid fault > The mains voltage has exceeded the
permissible range. This error can have the following causes:
• The mains voltage at the termination point of the inverter is too high.
• The grid impedance at the connection point of the inverter is too high.
The inverter disconnects from the electricity grid for safety reasons.
< Grid fault > The mains voltage has fallen below the
permissible range. This error can have the following causes:
• Electricity grid disconnected
• AC cable damaged
• The mains voltage at the termination point of the inverter is too low.
The inverter disconnects from the electricity grid for safety reasons.
• Check the mains voltage and grid connection on the inverter.
If the mains voltage is outside the permissible range due to local grid conditions, ask your network operator if the voltage can be adjusted at the feed-in point or if it would be acceptable to change the monitored operating limits.
If the mains voltage is within the tolerance range, yet this error is still displayed, contact the SMA Service Line.
• Check the tripping of the miniature circuit-breaker.
• Check the mains voltage and grid connection on the inverter.
If the mains voltage is outside the permissible range due to local grid conditions, ask your network operator if the voltage can be adjusted at the feed-in point or if it would be acceptable to change the monitored operating limits.
If the mains voltage is within the tolerance range, yet this error is still displayed, contact the SMA Service Line.
72 STP10-17TL-IA-en-32 Installation Manual
Page 73
SMA Solar Technology AG 11 Messages
Event no. Display message and cause Corrective measures
301 < Grid fault >
The ten-minute-average mains voltage is no longer within the permissible range.
This can be caused by one of the following:
• The mains voltage at the termination point of the inverter is too high.
• The grid impedance at the connection point of the inverter is too high.
The inverter disconnects from the grid to
• Check the mains voltage at the connection point of the inverter:
If, due to local grid conditions, the mains voltage exceeds the configured threshold, ask the network operator whether the voltage can be adjusted at the feed-in point, or whether it would be acceptable to modify the s.o. for power quality monitoring.
If the mains voltage is continually within the tolerance range, and this error is still displayed, contact the SMA Service Line.
maintain power quality.
401, 404 < Grid fault >
The inverter is no longer in grid-parallel operation and has stopped feed-in for
• Check the grid connection for strong, short-term frequency variations.
safety reasons.
501 < Grid fault >
The mains frequency is not within the permissible range. The inverter disconnects from the electricity grid for safety reasons.
• If possible, check the mains frequency and observe how often major fluctuations occur.
If there are frequent fluctuations and this error occurs as a result, ask your network operator if it would be acceptable to change the operating parameters.
Discuss the proposed parameters with the SMA Service Line.
601 < Grid fault >
The internal monitoring function of the inverter has detected an excessively high proportion of direct current in the line current.
• Check the grid connection for direct current.
• If this event occurs often, check with the network operator whether it is possible to raise the threshold for monitoring.
Installation Manual STP10-17TL-IA-en-32 73
Page 74
11 Messages SMA Solar Technology AG
Event no. Display message and cause Corrective measures
701 < Frq. not permitted >
< Check parameter > The power frequency is outside the
permissible range. The inverter disconnects from the electricity grid for safety reasons.
• As far as possible, check the mains frequency and observe how often major fluctuations occur.
If there are frequent fluctuations and this error occurs as a result, ask your network operator if it would be acceptable to change the operating parameters.
Discuss the proposed parameters with the SMA Service Line.
1302 < Waiting for grid voltage > or
< Installation failure grid connection > < Check grid and fuses >
The inverter has detected an error in the AC cabling and cannot connect to the electricity grid. The reason for this could be an incorrect country setting.
• Check AC installation
• Eliminate connection error (see Section6.3 "Connecting the Electricity Grid (AC)", page29).
• Check that the country setting is correct:
– Via rotary switch
(s ee Secti on 6.5 .1 "Che cki ng t he Country Standard", page46)
– Via communication: set the
parameter "CntrySet" or "Set country standard"
1501 < Reconnection fault grid >
The measured voltage or frequency is too high or too low for connection to the electricity grid.
Possibly, a changed country data set or changed parameters do not correspond to the local requirements for connecting to the electricity grid.
• Check that the country setting is correct:
– Via rotary switch
(s ee Secti on 6.5 .1 "Che cki ng t he Country Standard", page46)
– Via communication: set the
parameter "CntrySet" or "Set country standard"
• Check whether the voltage and frequency of the electricity grid are within the limits of the configured country data set.
• If individual parameters within a country data set have been changed, re-select the original country data set for the country of installation.
74 STP10-17TL-IA-en-32 Installation Manual
Page 75
SMA Solar Technology AG 11 Messages
Event no. Display message and cause Corrective measures
3301 to 3303
3401, 3402
< Unstable operation > There is not enough power at the DC input
of the inverter for stable operation. This may be caused by snow on the PV modules.
< DC overvoltage > < Disconnect generator >
The DC input voltage connected to the inverter is too high.
• Wait until irradiation is higher.
• If this event recurs at medium irradiation levels, check the PV system design and the correct circuitry of the PV array.
Disconnect the inverter from the
PV array immediately (see Section9 "Disconnecting the Inverter from Voltage Sources", page61). The inverter may otherwise be destroyed.
• Check that the DC voltage of the strings adheres to the maximum input voltage of the inverter before reconnecting the inverter to the PV array.
3501 < Insul. resistance >
< Check generator > The inverter has detected an earth fault in
the PV array.
• Check strings for earth faults (see Section12.2 "Checking the PV Array for Earth Faults", page83).
• The installer of the PV array must remedy any earth faults before the affected string is reconnected.
3601 < High discharge curr. >
< Check generator > The leakage current from the inverter and
the PV array is too high. This may be caused by a sudden earth
fault, a residual current or malfunction, or the earth capacitance of the PV system is too high.
• Check strings for earth faults (see Section12.2 "Checking the PV Array for Earth Faults", page83).
• The installer of the PV array must remedy any earth faults before the affected string is reconnected.
• Check whether the leakage current from the PV modules is too high.
The inverter interrupts feed-in operation immediately after exceeding a threshold and then automatically reconnects to the electricity grid.
3701 < Resid.curr.too.high >
< Check generator > The inverter has detected a residual
current through brief earthing of the PV array.
• Check strings for earth faults (see Section12.2 "Checking the PV Array for Earth Faults", page83).
• The installer of the PV array must remedy any earth faults before the affected string is reconnected.
Installation Manual STP10-17TL-IA-en-32 75
Page 76
11 Messages SMA Solar Technology AG
Event no. Display message and cause Corrective measures
3801, 3802
< DC overcurrent > < Check generator >
On the DC side of the inverter, an
If this event occurs frequently:
• Check the design and the circuitry of the PV array.
overcurrent has been detected and the inverter has briefly interrupted feed-in.
3901, 3902
< Waiting for DC start conditions > < Start cond. not met >
The input power or input voltage of the PV modules is insufficient for feeding into the electricity grid.
• Wait until irradiation is higher.
• If necessary, increase the voltage limit for the start of feed-in if the event occurs frequently in the morning (parameter setting via communication).
• If this event recurs at medium irradiation levels, check the PV system design and the correct circuitry of the PV array.
4001 < String X defect. >
< Do not disconn. ESS > The "X" stands for the affected string.
There are either reverse currents in the string or the string polarity is reversed. Further strings may also be affected. The PV array is short circuited.
In exceptional circumstances, this error message may be triggered by soiling or shading of the modules (e.g., by leaves or snow).
• Disconnect the inverter after dark (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
• Check the design and the circuitry of the PV array (see Section6.4.1 "Conditions for DC Connection", page35).
• If irradiation is sufficient, check whether the same voltage is present at the string inputs A1 to A5.
If not, one of the PV modules is possibly defective.
4002 < String X low power >
• Check the string indicated.
< Check generator > String monitoring has detected a
non-functioning or weak string.
76 STP10-17TL-IA-en-32 Installation Manual
Page 77
SMA Solar Technology AG 11 Messages
Event no. Display message and cause Corrective measures
4003 < String X defect. >
< Check generator > String monitoring has detected a
non-functioning or weak substring.
• Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
• Check the design and the circuitry of the PV array (see Section6.4.1 "Conditions for DC Connection", page35).
• Check whether the same voltage is present at the strings inputs A1 to A5.
• If not, one of the PV modules is possibly defective.
4005 < Part.str. X low p. >
• Check the part string indicated.
< Check generator > The "X" stands for the affected substring
The string monitoring has either failed or detected a weak substring.
6001 to 6009, 6101 to
< Self diagnosis > or < Interference device >
• Contact the SMA Service Line (see Section16 "Contact", page111)
6112, 6201 to 6203, 6301, 6304 to 6306, 6401 to 6411, 6415, 6416, 6422, 6433, 6437, 6438
6429 < ESS Relay fault Input X >
X stands for the affected input.
Contact the SMA Service Line (see Section16 "Contact", page111)
The ESS relay or ESS-IGBT cannot be switched on or off.
Installation Manual STP10-17TL-IA-en-32 77
Page 78
11 Messages SMA Solar Technology AG
Event no. Display message and cause Corrective measures
6430 < Relay control defective input X >
X stands for the affected input. The relay
Contact the SMA Service Line (see Section16 "Contact", page111)
control at the affected input is defective.
6432 < HSS-IGBT defective input X >
HSS-IGBT cannot be switched on or off.
6439 < Varistor monitoring defective >
The varistor monitoring is defective.
6501, 6502, 6509
< Self diagnosis > or < Overtemperature >
The inverter switches off due to excessive temperature.
6603, 6604
< Self diagnosis > or < Overload >
Contact the SMA Service Line (see Section16 "Contact", page111)
Contact the SMA Service Line (see Section16 "Contact", page111)
• Ensure sufficient ventilation.
• Check heat dissipation (see Section10.2 "Checking Heat Dissipation", page65).
• Contact the SMA Service Line (see Section16 "Contact", page111)
6701, 6702
6801, 6802
< Comm. disturbed > A fault has occurred in the internal
communication of the inverter. However, the inverter continues feeding into the grid.
< Self-diagnosis > or < Input A defective >
If this event occurs frequently:
• Contact the SMA Service Line (see Section16 "Contact", page111)
• Contact the SMA Service Line (see Section16 "Contact", page111)
6901, 6902
< Self-diagnosis > or < Input B defective >
• Contact the SMA Service Line (see Section16 "Contact", page111)
7001, 7002, 7007
< Sensor fault fan permanently on > Overtemperature in the inverter or sensor
defective.
• Contact the SMA Service Line (see Section16 "Contact", page111)
7101 < SD card defective > Re-format the SD card.
• Cancel write protection on SD card.
• Re-save the files to the SD card.
7102 < Parameter file not found or defective > • Copy the parameter file into the
SD card drive :\PARASET directory.
7105 < Param. setting failed > • Check whether the parameters of
the SD card are valid.
•Ensure change rights via SMA Grid Guard code.
78 STP10-17TL-IA-en-32 Installation Manual
Page 79
SMA Solar Technology AG 11 Messages
Event no. Display message and cause Corrective measures
7106 < Update file defect. > • Re-format the SD card.
• Re-save the files to the SD card.
7110 < No update file found > • Copy the update file into the
SD card drive :\UPDATE directory.
7201, 7202
7303 < Update main CPU failed >
< Data storage not possible > An internal device fault that does not
prevent the inverter from feeding power to the grid.
Internal device fault.
•If this error occurs frequently, contact the SMA Service Line (see Section16 "Contact", page111).
• Contact the SMA Service Line (see Section16 "Contact", page111)
7305 < Update RS485i module failed >
An internal device fault that does not prevent the inverter from feeding power to the grid.
• Re-try update.
• If th is error oc curs ag ain, c ontact the SMA Service Line (see Section16 "Contact", page111).
7307 < Update BT failed >
An internal device fault that does not prevent the inverter from feeding power to the grid.
7309 < Upd. display failed >
An internal device fault that does not prevent the inverter from feeding power to the grid.
7311 < Update language table failed >
An internal device fault that does not prevent the inverter from feeding power to the grid.
7324 < Wait for update conditions > • Ensure that there is DC supply to the
inverter and that it feeds more than 1,000 W into the electricity grid for over one minute.
7401 < Varistor defective >
At least one of the thermally monitored varistors is defective.
7501 < Fan fault >
< Clean fan > One of the internal fans is blocked.
• Check varistors (see Section12.3 "Checking the Function of the Varistors", page85).
• Check heat dissipation (see Section10.2 "Checking Heat Dissipation", page65).
Installation Manual STP10-17TL-IA-en-32 79
Page 80
11 Messages SMA Solar Technology AG
Event no. Display message and cause Corrective measures
7508 < Fan fault >
< Clean fan > One of the external fans is blocked.
7701 to 7703
< Self diagnosis > or < Interference device >
• Check heat dissipation (see Section10.2 "Checking Heat Dissipation", page65).
• Contact the SMA Service Line (see Section16 "Contact", page111)
8001 < Derating occurred >
The power supplied by the inverter has been reduced to below the nominal power for more than ten minutes due to excessive temperature.
8201, 8203
< Interference device > < Do not pull ESS >
If this event occurs frequently:
• Ensure sufficient ventilation.
• Check heat dissipation (see Section10.2 "Checking Heat Dissipation", page65).
• Disconnect the inverter after dark (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
• Contact the SMA Service Line (see Section16 "Contact", page111)
8202 < Connect ESS, do not open cover >
Device disturbance or reverse current in the PV array.
Wait until dark before disconnecting the PV array from the inverter in order to prevent the risk of an electric arc occurring
• Plug the Electronic Solar Switch on right up to the stop.
• Disconnect the inverter after dark (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
when the DC connectors are pulled out.
8301, 8302
< Lightn.prot.inactive > < Chk lightn.prot.A/PE > < Chk lightn.prot.B/PE >
• Replace surge arrester (see Section12.4 "Replacing Surge Arresters Type II", page88).
At least one surge arrester is defective.
8401 < Overheating >
< Disconn. device from generator and grid >
• Contact the SMA Service Line (see Section16 "Contact", page111)
Device disturbance due to overheating in the inverter. The inverter disconnects on the AC and DC sides.
9002 < Inst. code invalid >
• Enter a valid SMA Grid Guard code.
The SMA Grid Guard code entered (personal installer password) is not valid.
80 STP10-17TL-IA-en-32 Installation Manual
Page 81
SMA Solar Technology AG 11 Messages
Event no. Display message and cause Corrective measures
9003 < Grid param. locked >
The current country data set is locked.
9005 < Changing grid param. not possible >
< Ensure DC supply >
• DC voltage at the DC input is not sufficient to run the main CPU.
• The selected rotary switch setting for the language settings is not
• E nte r a v ali d SM A Gr id G uar d co de for changing the country data set.
• Ensure that sufficient DC voltage is available (green LED glowing or flashing).
• Check the rotary switch setting (see Section 6.5.1).
• Enter the SMA Grid Guard code.
programmed.
• The parameters to be changed are protected.
9007 < Abort self-test >
There is either an error in the AC installation or the configured voltage and frequency limits do not comply with the requirements of the Italian electricity grids.
• Check AC installation.
• Eliminate connection error (see Section6.3 "Connecting the Electricity Grid (AC)", page29).
• Check that the country setting is correct (see Section6.5 "Setting the Country Standard and Display Language", page44).
The self-test is only required for installations in Italy.
Installation Manual STP10-17TL-IA-en-32 81
Page 82
12 Troubleshooting SMA Solar Technology AG

12 Troubleshooting

12.1 Sunny Tripower is Beeping

Electric shock due to electric arc when pulling out the DC connectors Death or serious burns
The Sunny Tripower has short-circuited the PV array to avoid reverse currents.
• Strictly adhere to the procedure as described in the following table.
Cause Event number on
the display
Installation fault
(reverse polarity of a string or connection of strings with different numbers of modules)
OR
Reverse current in the PV system (defective string)
The Sunny Tripower short-circuits the PV array to avoid reverse currents through individual strings. Depending on the level of irradiation, this could trigger high current flows. However, the PV array and the Sunny Tripower are in a safe state.
Sunny Tripower is defective 64xx or 8201 to
4001 to 4003 or 4005
8203
Measure
On no account pull the Electronic Solar Switch or DC connectors out. Wait until the Sunny Tripower stops beeping (after dark).
If you pul l th e DC conn ect ors , th ere is a risk of electric arcing.
• With an open Sunny Tripower: Prior to leaving the Sunny Tripower, install contact protection (e.g., fence) and moisture protection (e.g., tarpaulin).
•Wait until dark before pulling out the Electronic Solar Switch and all DC connectors, and only then eliminate any errors (reversed-pole or defective string).
• Contact the SMA Service Line (see Section16 "Contact", page111)
82 STP10-17TL-IA-en-32 Installation Manual
Page 83
SMA Solar Technology AG 12 Troubleshooting

12.2 Checking the PV Array for Earth Faults

If the inverter displays event numbers "3501", "3601" or "3701", there is a high probability of an earth fault in the PV array.
Check the strings for earth faults as described below:
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
Danger to life due to live PV array
• Only touch the cables of the PV array by their insulation.
• Do not connect strings with earth faults to the inverter.
Excessive voltages can destroy the multimeter
• Only use multimeters with a DC input voltage range up to at least 1,000 V.
2. Measure the voltages between the positive pole of each string and the earth potential (PE).
3. Measure the voltages between the negative pole of each string and the earth potential (PE).
4. Measure the voltages between the positive and negative poles of each string.
Installation Manual STP10-17TL-IA-en-32 83
Page 84
12 Troubleshooting SMA Solar Technology AG
☑ An earth fault is present if the measured voltages are stable and the sum of the voltages of
the positive pole against earth potential and the negative pole against earth potential of a string is approximately equal to the voltage between the positive and negative poles.
Result Measure
☑ You have detected an earth fault. • The installer of the PV array must remedy
the earth fault in the affected string. You can determine the location of the earth fault as described below.
Do not reconnect the faulty string.
• Restart the inverter (see Section7 "Commissioning", page56).
☑You have not detected any earth fault. It is likely that one of the thermally monitored
varistors is defective.
• Check varistors (see Section12.3 "Checking the Function of the Varistors", page85).
Location of the Earth Fault
The approximate location of the earth fault can be calculated from the ratio of the voltages measured between plus and earth potential and minus and earth potential.
Example:
In this case, the earth fault is between the second and third PV modules.
☑ The earth fault check is now complete.
84 STP10-17TL-IA-en-32 Installation Manual
Page 85
SMA Solar Technology AG 12 Troubleshooting

12.3 Checking the Function of the Varistors

If the inverter displays event number "7401", one of the varistors is probably defective. Varistors are wear parts. Their functional efficiency diminishes with age or following repeated
responses as a result of overvoltages. It is therefore possible that one of the thermally monitored varistors has lost its protective function.
Check the varistors as described below:
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources", page61).
Danger to life due to high voltages in the inverter
Death from electric shock
There is residual voltage in the inverter. The inverter takes 20 minutes to discharge.
• Wait 20 minutes before you open the upper enclosure lid or the DC lid.
Risk of burns due to hot components inside the inverter
• Wait until the components inside the inverter have cooled down.
2. Release the captive screws of the DC lid on the left-hand side of the connection area.
3. Lift the DC lid up and off.
Installation Manual STP10-17TL-IA-en-32 85
Page 86
12 Troubleshooting SMA Solar Technology AG
4. Remove all varistors by pulling them upwards. If you have not received an insertion tool for
operating the terminals with the replacement varistors, contact SMA Solar Technology AG.
5. Use a multimeter to check each varistor for a conductive connection between terminals 2 and 3.
Result Measure
☑There is a conductive
connection.
Presumably there is a different error in the inverter.
• Proceed to step 8.
• Contact the SMA Service Line (see Section16 "Contact", page111)
☑There is no conductive
connection.
The respective varistor is defective and must be replaced. Varistor failure is due to influences which affect all varistors
similarly (temperature, age, induced overvoltages). SMA Solar Technology AG recommends replacing all varistors.
The varistors are specially manufac tured fo r use in t he i nverter and are not commercially available. You will need to order replacement varistors directly from SMA Solar Technology AG (see Section15 "Accessories", page110). Only use original varistors that are sold by SMA Solar Technology AG.
• To replace the varistors, proceed to step 6.
Destruction of the inverter due to overvoltage
If varistors are missing, the inverter is no longer protected against overvoltages.
• Replacement varistors should be obtained as soon as possible.
• In PV systems with a high risk of overvoltages, never operate the inverter without varistors.
86 STP10-17TL-IA-en-32 Installation Manual
Page 87
SMA Solar Technology AG 12 Troubleshooting
6. Insert an insertion tool into the openings of the terminal contacts.
7. Insert new varistors into the slots by pushing them down into the slots (as shown in the adjacent diagram).
Make sure that the labelling is pointing to the front, i.e. towards the insertion tool.
8. Dock the DC lid an at angle and then push on. The captive screws must protrude.
9. Pre-screw all four screws of the DC lid and then tighten them (torque: 3.5 Nm).
10. Restart the inverter (see Section7 "Commissioning", page56). ☑ The varistors have now been replaced and the inverter is back in operation.
Installation Manual STP10-17TL-IA-en-32 87
Page 88
12 Troubleshooting SMA Solar Technology AG

12.4 Replacing Surge Arresters Type II

If the inverter is displaying event number "8301" or "8302", presumably at least one surge arrester is defective.
Surge arresters are wear parts. Their functional efficiency diminishes with age or following repeated responses as a result of overvoltages. It is therefore possible that one of the surge arresters has lost its protective function.
SMA Solar Technology AG therefore recommends replacing all surge arresters, since the failure of one surge arrester is usually due to influences which affect all surge arresters in the same manner (temperature, age, induced overvoltages). You will find the order numbers for both retrofit kits (one for input A and one for input B) in Section 15.
Replace the surge arresters as described below:
1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources",
page61).
Danger to life due to high voltages in the inverter
Death from electric shock
There is residual voltage in the inverter. The inverter takes 20 minutes to discharge.
• Wait 20 minutes before you open the upper enclosure lid or the DC lid.
2. Release the captive screws of the DC lid on the
left-hand side of the connection area.
3. Lift the DC lid up and off.
88 STP10-17TL-IA-en-32 Installation Manual
Page 89
SMA Solar Technology AG 12 Troubleshooting
4. Rem ove all sur ge a rre ste rs f rom t he s lot s. T o do thi s,
compress the grooved areas on either side.
☑ If a green strip is visible in the window (A),
the surge arrester is in perfect working order.
☑ If a red strip is visible in the window (A),
the surge arrester is defective.
5. Install new surge arresters (see Section6.7 "Retrofitting a Surge Arrester Type II", page53).
Installation Manual STP10-17TL-IA-en-32 89
Page 90
13 Decommissioning SMA Solar Technology AG

13 Decommissioning

13.1 Dismantling the Inverter

1. Disconnect the inverter (see Section9 "Disconnecting the Inverter from Voltage Sources",
page61).
2. Remove any connected communication cables from the inverter.
Risk of burns due to hot enclosure parts
• Wait 30 minutes for the enclosure to cool down before disassembling.
3. Screw off all projecting cable glands.
4. If necessary, open the anti-theft lock.
5. Lift the inverter off the rear panel and unscrew and remove rear panel as necessary.

13.2 Replacing the Enclosure Lid

In the event of a fault, your inverter may need to be replaced. If this is the case, you will receive a replacement device fitted with transport lids.
Danger to life due to electric shock
During operation, there are high voltages present in the inverter.
• Do not operate the inverter without the upper and lower enclosure lid in place.
Dismantling Surge Arresters Type II
If you have retrofitted your inverters with surge arresters Type II, they must be dismantled before returning the inverter to SMA Solar Technology AG (see Section12.4 "Replacing Surge Arresters Type II", page88).
Prior to returning your inverter to SMA Solar Technology AG, you will need to replace the upper and lower enclosure lids with the corresponding transport lids.
Danger to life due to high voltages in the inverter
Death from electric shock
After disconnecting the inverter, there is residual voltage in the inverter. The inverter takes 20 minutes to discharge.
• Wait 20 minutes before you open the upper enclosure lid or the DC lid.
90 STP10-17TL-IA-en-32 Installation Manual
Page 91
SMA Solar Technology AG 13 Decommissioning
1. Dismantle the inverter (see Section13.1 "Dismantling the Inverter", page90).
2. Release all the screws on the upper enclosure lid
and remove it by pulling it towards you.
3. Do the same with the transport lid of the
replacement device.
4. Pre-screw the transport lid of the replacement
device with the six enclosure lid screws and corresponding conical spring washers to your original inverter and then screw down tight in the sequence shown on the right (torque: 6.0 Nm).
The toothing of the conical spring washers must point towards the enclosure lid. This ensures proper earthing of the enclosure lid.
The scope of delivery of the inverter includes a spare screw and conical spring washer.
5. Screw the lower enclosure lid down tight.
☑ The original inverter is now ready for return shipment to SMA Solar Technology AG.
6. Now mount the upper enclosure lid from the original inverter onto the replacement device in the
same manner.
7. Mount the replacement device (see Section5.3 "Mounting the Inverter with Rear Panel",
page23) and connect it (see Section6 "Electrical Connection", page27).

13.3 Packing the Inverter

• If the original packaging is available, the inverter should be packed in its original packaging and secured with tension straps.
• If the original packaging is not available, use a cardboard box suitable for the weight and size of the inverter.

13.4 Storing the Inverter

Store the inverter in a dry place where the ambient temperature is always between −25°C and +60°C.

13.5 Disposing of the Inverter

At the end of its service life, dispose of the inverter according to the current locally applicable disposal regulations for electronic waste. Alternatively, send it back to SMA Solar Technology AG with shipping paid by sender and labelled "ZUR ENTSORGUNG" ("FOR DISPOSAL") (contact see page 111).
Installation Manual STP10-17TL-IA-en-32 91
Page 92
14 Technical Data SMA Solar Technology AG

14 Technical Data

14.1 Sunny Tripower 10000TL

DC Input
Maximum DC power at cos φ = 1 10,200 W Maximum input voltage 1,000 V MPP voltage range 320 V to 800 V Rated input voltage 600 V Minimum input voltage 150 V Initial input voltage 188 V Maximum feedback current 2 A Maximum input current, input A 22.0 A Maximum input current, input B 11.0 A Maximum input current per string input A* 33.0 A Maximum input current per string input B* 12.5 A Number of independent MPP inputs 2 Strings per MPP input, input A 4 Strings per MPP input, input B 1
* To be observed in the event of short-circuit of the electronic string fuse
AC Output
Rated power at 230 V, 50 Hz 10,000 W Maximum apparent AC power cos φ = 1 10,000 VA Rated grid voltage 3/N/PE, 230 V/400 V AC voltage range* 160 V to 280 V Nominal AC current at 230 V 14.5 A Maximum output current 16.0 A Maximum output current in the event of an error 0.05 kA Total harmonic factor of output current at
AC voltage < 2% and AC power > 0.5% of nominal AC power
Maximum residual output current 96 mA
92 STP10-17TL-IA-en-32 Installation Manual
≤3%
Page 93
SMA Solar Technology AG 14 Technical Data
Rated mains frequency 50 Hz AC mains frequency* 50 Hz/60 Hz Operating range at AC mains frequency 50 Hz 44 Hz to 55 Hz Operating range at AC mains frequency 60 Hz 54 Hz to 65 Hz Displacement power factor, adjustable 0.8
overexcited
to 1 to 0.8
underexcited
Feed-in phases 3 Connection phases 3 Overvoltage category as per IEC 60664-1 III
* Depending on country setting
Protective Devices
DC reverse polarity protection Short-circuit diode, electronic string fuse Protection against module reverse currents Electronic string fuse Input-side disconnection device Electronic Solar Switch, SUNCLIX DC connector DC overvoltage protection Thermally monitored varistors
optional: surge arrester type II AC short-circuit current capability Current control Grid monitoring SMA Grid Guard 4 Maximum permissible fuse protection 50.0 A Earth fault monitoring insulation monitoring R All-pole sensitive residual-current monitoring unit available String-failure detection available
> 550 k Ω
iso
General Data
Width x height x depth with Electronic Solar Switch
Weight 59 kg Length x width x height of packaging 780 mm x 380 mm x 790 mm Transport weight 65 kg Climatic class in accordance with
IEC 60721-3-4 Environment category Outdoors Degree of pollution outside the enclosure 3 Degree of pollution inside the enclosure 2
Installation Manual STP10-17TL-IA-en-32 93
665 mm x 690 mm x 265 mm
4K4H
Page 94
14 Technical Data SMA Solar Technology AG
Operating temperature range − 25°C to +60°C Maximum permissible value for relative humidity,
100%
non-condensing Maximum operating altitude above MSL 3,000 m Power loss in night mode < 1 W Topology transformerless Cooling concept OptiCool: temperature-controlled fan Fan connection designed for safe disconnection in accordance
with DIN EN 50178:1998-04 Degree of protection according to IEC 60529 IP65 Protection class (according to IEC 62103) I Country standards, as of 04/2013* VDE-AR-N4105, VDE 0126-1-1, AS4777,
C10/11, PPDS, GBT19939-2005, UTE C15-712-1, PPC, NRS 97-2-1, EN50438, RD661/2007, IEC 61727, G59/2, CEI 0-21,
BDEW 2008, RD1699:2011, SI4777,
NEN EN 50438, DIN EN 62109-1,
IEC 62109-2
* VDE-AR-N-4105: valid from Firmware Version 2.31. Setting in accordance with VDE-ARN-4105 (Germany) NRS 97-2-1: This standard stipulates that a special sticker be attached to the AC distribution to draw attention to the AC-side disconnection of the inverter in case of grid failure (for more details, see NRS 97-2-1, Sec. 4.2.7.1 and 4.2.7.2)
C10/11: Only possible if the three-phase nominal voltage of the phase conductor is 400 V EN 50438: Does not apply to all country standard deviations of EN 50438. IEC 62109-2: This standard requires either that the multi-function relay is used as a fault indicator or that the inverter is registered
with the Sunny Portal and the error alarm is activated in the Sunny Portal.
Climatic Conditions in Accordance with IEC 60721-3-4, Installation Type C, Class 4K4H
Extended temperature range − 25°C to +60°C Extended humidity range 0% to 100% Extended air pressure range 79.5 kPa to 106 kPa
Climatic Conditions in Accordance with IEC 60721-3-4, Transport Type E, Class 2K3
Temperature range − 25°C to +70°C
94 STP10-17TL-IA-en-32 Installation Manual
Page 95
SMA Solar Technology AG 14 Technical Data
Features
DC connection SUNCLIX DC connector AC connection spring clamp terminal Display LC graphic display Bluetooth as standard RS485, galvanically isolated optional Speedwire/Webconnect optional Multi-function relay optional Power Control Module optional
Electronic Solar Switch
Electrical endurance in the event of a short
at least 50 switching processes
circuit, at nominal current of 33 A Maximum switching current 33.0 A Maximum switching voltage 1,000 V Maximum PV power 20 kW Degree of protection when plugged in IP65 Degree of protection when not plugged in IP21
Torques
Upper enclosure lid screws 6.0 Nm Lower enclosure lid screws 2.0 Nm DC lid screws 3.5 Nm Additional earth terminal 6.0 Nm Cheese-head screws (M5x10) for securing the
enclosure to the rear panel SUNCLIX swivel nut 2.0 Nm RS485 communication connection 1.5 Nm Terminal for multi-function relay 0.5 Nm
3.5 Nm
Installation Manual STP10-17TL-IA-en-32 95
Page 96
14 Technical Data SMA Solar Technology AG
Grid Configuration
TN-C network suitable TN-S network suitable TN-C-S network suitable TT grid suitable
Data Storage Capacity
Daily energy yield performance 63 days Daily yields 30 years Event messages for users 250 events Event messages for installers 250 events
Efficiency
Maximum efficiency, η
max
European weighted efficiency, η
EU
98.1%
97.7%

14.2 Sunny Tripower 12000TL

DC Input
Maximum DC power at cos φ = 1 12,250 W Maximum input voltage 1,000 V MPP voltage range 380 V to 800 V Rated input voltage 600 V Minimum input voltage 150 V Initial input voltage 188 V Maximum feedback current 2 A Maximum input current, input A 22.0 A Maximum input current, input B 11.0 A Maximum input current per string input A** 33.0 A Maximum input current per string input B** 12.5 A Number of independent MPP inputs 2 Strings per MPP input, input A 4 Strings per MPP input, input B 1
** To be observed in the event of short-circuit of the electronic string fuse.
96 STP10-17TL-IA-en-32 Installation Manual
Page 97
SMA Solar Technology AG 14 Technical Data
AC Output
Rated power at 230 V, 50 Hz 12,000 W Maximum apparent AC power cos φ = 1 12,000 VA Rated grid voltage 3/N/PE, 230 V/400 V AC voltage range* 160 V to 280 V Nominal AC current at 230 V 17.4 A Maximum output current 19.2 A Maximum output current in the event of an error 0.05 kA Total harmonic factor of output current at
AC voltage < 2% and AC power > 0.5% of nominal AC power
Maximum residual output current 96 mA Rated mains frequency 50 Hz AC mains frequency* 50 Hz/60 Hz Operating range at AC mains frequency 50 Hz 44 Hz to 55 Hz Operating range at AC mains frequency 60 Hz 54 Hz to 65 Hz Displacement power factor, adjustable 0.8
overexcited
Feed-in phases 3 Connection phases 3 Overvoltage category as per IEC 60664-1 III
* Depending on country setting
≤3.6%
to 1 to 0.8
underexcited
Protective Devices
DC reverse polarity protection Short-circuit diode, electronic string fuse Protection against module reverse currents Electronic string fuse Input-side disconnection device Electronic Solar Switch, SUNCLIX DC connector DC overvoltage protection Thermally monitored varistors
optional: surge arrester type II AC short-circuit current capability Current control Grid monitoring SMA Grid Guard 4 Maximum permissible fuse protection 50.0 A Earth fault monitoring Insulation monitoring R All-pole sensitive residual-current monitoring unit available String-failure detection available
Installation Manual STP10-17TL-IA-en-32 97
> 458.7 k Ω
iso
Page 98
14 Technical Data SMA Solar Technology AG
General Data
Width x height x depth with
665 mm x 690 mm x 265 mm
Electronic Solar Switch Weight 59 kg Length x width x height of packaging 780 mm x 380 mm x 790 mm Transport weight 65 kg Climatic class in accordance with
4K4H
IEC 60721-3-4 Environment category Outdoors Degree of pollution outside the enclosure 3 Degree of pollution inside the enclosure 2 Operating temperature range − 25°C to +60°C Maximum permissible value for relative humidity,
100%
non-condensing Maximum operating altitude above MSL 3,000 m Power loss in night mode < 1 W Topology transformerless Cooling concept OptiCool: temperature-controlled fan Fan connection designed for safe disconnection in accordance
with DIN EN 50178:1998-04 Degree of protection according to IEC 60529 IP65 Protection class (according to IEC 62103) I Country standards, as of 04/2013* VDE-AR-N4105, VDE 0126-1-1, AS4777,
C10/11, PPDS, GBT19939-2005, UTE C15-712-1, PPC, NRS 97-2-1, EN50438, RD661/2007, IEC 61727, G59/2, CEI 0-21,
BDEW 2008, RD1699:2011, SI4777,
NEN EN 50438, DIN EN 62109-1,
IEC 62109-2
* VDE-AR-N-4105: valid from Firmware Version 2.31. Setting in accordance with VDE-ARN-4105 (Germany) NRS 97-2-1: This standard stipulates that a special sticker be attached to the AC distribution to draw attention to the AC-side disconnection of the inverter in case of grid failure (for more details, see NRS 97-2-1, Sec. 4.2.7.1 and 4.2.7.2)
C10/11: Only possible if the three-phase nominal voltage of the phase conductor is 400 V EN 50438: Does not apply to all country standard deviations of EN 50438. IEC 62109-2: This standard requires either that the multi-function relay is used as a fault indicator or that the inverter is registered
with the Sunny Portal and the error alarm is activated in the Sunny Portal.
98 STP10-17TL-IA-en-32 Installation Manual
Page 99
SMA Solar Technology AG 14 Technical Data
Climatic Conditions in Accordance with IEC 60721-3-4, Installation Type C, Class 4K4H
Extended temperature range − 25°C to +60°C Extended humidity range 0% to 100% Extended air pressure range 79.5 kPa to 106 kPa
Climatic Conditions in Accordance with IEC 60721-3-4, Transport Type E, Class 2K3
Temperature range − 25°C to +70°C
Features
DC connection SUNCLIX DC connector AC connection spring clamp terminal Display LC graphic display Bluetooth as standard RS485, galvanically isolated optional Speedwire/Webconnect optional Multi-function relay optional Power Control Module optional
Electronic Solar Switch
Electrical endurance in the event of a short circuit, at nominal current of 33 A
Maximum switching current 33.0 A Maximum switching voltage 1,000 V Maximum PV power 20 kW Degree of protection when plugged in IP65 Degree of protection when not plugged in IP21
Installation Manual STP10-17TL-IA-en-32 99
at least 50 switching processes
Page 100
14 Technical Data SMA Solar Technology AG
Torques
Upper enclosure lid screws 6.0 Nm Lower enclosure lid screws 2.0 Nm DC lid screws 3.5 Nm Additional earth terminal 6.0 Nm Cheese-head screws (M5x10) for securing the
3.5 Nm
enclosure to the rear panel SUNCLIX swivel nut 2.0 Nm RS485 communication connection 1.5 Nm Terminal for multi-function relay 0.5 Nm
Grid Configuration
TN-C network suitable TN-S network suitable TN-C-S network suitable TT grid suitable
Data Storage Capacity
Daily energy yield performance 63 days Daily yields 30 years Event messages for users 250 events Event messages for installers 250 events
Efficiency
Maximum efficiency, η European weighted efficiency, η
100 STP10-17TL-IA-en-32 Installation Manual
max
EU
98.1%
97.7%
Loading...