SMA SSM-U-1615 User Manual

OperatingManual
SMAString-Monitor SSM-U-1615 / SSM-U-2415 / SSM­U-3215
SSMUXX15-BE-en-10 | Version 1.0
ENGLISH
Legal Provisions
SMA Solar Technology AG
Legal Provisions
The information contained in these documents is property of SMA Solar Technology AG. Any publication, whether in whole or in part, requires prior written approval by SMA Solar Technology AG. Internal reproduction used solely for the purpose of product evaluation or other proper use is allowed and does not require prior approval.
SMA Warranty
You can download the current warranty conditions from the Internet at www.SMA-Solar.com.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. A lack of identification does not mean that a product or symbol is not trademarked.
The BLUETOOTH® word mark and logos are registered trademarks of BluetoothSIG,Inc. and any use of these marks by SMASolarTechnologyAG is under license.
Modbus® is a registered trademark of Schneider Electric and is licensed by the Modbus Organization, Inc.
QR Code is a registered trademark of DENSO WAVE INCORPORATED. Phillips® and Pozidriv® are registered trademarks of Phillips Screw Company. Torx® is a registered trademark of Acument Global Technologies, Inc.
SMASolarTechnologyAG
Sonnenallee 1 34266 Niestetal Germany Tel. +49 561 9522-0 Fax +49 561 9522-100 www.SMA.de E-mail: info@SMA.de © 2004 to 2015SMASolarTechnologyAG. All rights reserved.
Operating ManualSSMUXX15-BE-en-102
SMA Solar Technology AG
Table of Contents
Table of Contents
1 Information on this Document ................................................. 6
1.1 Validity................................................................................................ 6
1.2 Target Group...................................................................................... 6
1.3 Additional Information....................................................................... 6
1.4 Symbols .............................................................................................. 6
1.5 Typographies...................................................................................... 7
1.6 Nomenclature..................................................................................... 7
2 Safety......................................................................................... 8
2.1 Intended Use ...................................................................................... 8
2.2 Safety Information.............................................................................. 9
2.3 Personal Protective Equipment........................................................... 11
3 Scope of Delivery...................................................................... 12
4 Product Overview..................................................................... 13
4.1 SMA String-Monitor........................................................................... 13
4.2 External View of the DC Subdistribution........................................... 14
4.3 Components of the DC Subdistribution ............................................ 15
4.4 Terminals on the Electronic Assembly............................................... 17
4.5 Type Label .......................................................................................... 18
4.6 Symbols on the Product ..................................................................... 19
4.7 LEDs on the Electronic Assembly....................................................... 20
5 Mounting ................................................................................... 21
5.1 Selecting the Mounting Location....................................................... 21
5.2 Mounting the SMA String-Monitor on the Wall............................... 23
6 Installation................................................................................. 25
6.1 Overview of the Connection Area of the SMA String-Monitor....... 25
6.2 Grounding ......................................................................................... 27
6.2.1 Information on Grounding............................................................. 27
6.2.2 Grounding the Electronic Assembly.............................................. 27
6.2.3 Grounding the DC Surge Arrester ................................................ 27
6.3 Installation of the DC Main Cables .................................................. 28
Operating Manual 3SSMUXX15-BE-en-10
Table of Contents
6.3.1 Safety during Installation of the DC Main Cables....................... 28
6.3.2 Options for Installation of the DC Main Cables .......................... 28
6.3.3 Connecting the DC Main Cables to the Busbar using Terminal
Lugs................................................................................................. 29
6.3.4 Connecting the DC Main Cables to the Busbar using V Box
Terminals......................................................................................... 32
6.3.4.1 Requirements and Conditions................................................. 32
6.3.4.2 Installing the Box Terminal on the Busbar.............................. 33
6.3.4.3 Connecting Copper Cables to V-Box Terminal...................... 34
6.3.4.4 Connecting Aluminum Cables to V Box Terminal.................. 35
SMA Solar Technology AG
6.4 Connecting the Ethernet Cables........................................................ 36
6.5 Connection of Sensors....................................................................... 39
6.5.1 Connecting Temperature Sensors ................................................. 39
6.5.2 Connecting an Irradiation Sensor or Anemometer to the
Analog Input................................................................................... 39
6.6 Connecting the Remote Terminal to the Digital Input....................... 40
6.7 Connecting the Remote Terminal to the Digital Output ................... 41
6.8 Installation of the String Cables ........................................................ 42
6.8.1 Requirements for Installation of the String Cables ....................... 42
6.8.2 Installing the String Cables............................................................ 42
7 Commissioning the DC Subdistribution................................... 45
8 Disconnecting and Reconnecting............................................. 46
8.1 Safety When Disconnecting and Reconnecting Voltage Sources .. 46
8.2 Disconnecting the DC Subdistribution............................................... 47
8.3 Switching the DC Subdistribution Back On...................................... 47
9 Troubleshooting ........................................................................ 49
9.1 LED States........................................................................................... 49
9.1.1 Status LEDs of the SMA String-Monitor ........................................ 49
9.1.2 LEDs of the Network Connection.................................................. 50
9.2 Performing an Update ....................................................................... 51
10 Maintenance ............................................................................. 52
10.1 Safety during Maintenance............................................................... 52
10.2 Maintenance Schedule and Consumables ...................................... 53
Operating ManualSSMUXX15-BE-en-104
SMA Solar Technology AG
10.2.1 Notes on Maintenance Work....................................................... 53
10.2.2 Maintenance Work Every 24 Months.......................................... 53
Table of Contents
10.3 Maintenance Work............................................................................ 54
10.3.1 Checking the DC Load-Break Switch............................................ 54
10.3.2 Checking the Protective Covers..................................................... 55
10.3.3 Performing the Visual Inspection ................................................... 55
10.3.4 Checking the Condensate Drain................................................... 56
10.3.5 Checking the Vent Plug.................................................................. 56
10.3.6 Checking the Seals ........................................................................ 56
10.3.7 Checking the Labels....................................................................... 57
10.3.8 Checking the LEDs.......................................................................... 58
10.3.9 Checking the Bolted, Clamp and Plug Connections.................... 58
10.3.10 Checking the Inline Fuse Connectors............................................ 59
10.3.11 Checking the Ground Connection ................................................ 59
10.4 Completing Maintenance Work ....................................................... 59
11 Decommissioning ...................................................................... 60
11.1 Decommissioning the DC Subdistribution......................................... 60
11.2 Disassembling the DC Subdistribution from the Wall...................... 60
11.3 Packing the DC Subdistribution......................................................... 61
11.4 Storing the DC Subdistribution.......................................................... 61
11.5 Disposing of the DC Subdistribution................................................. 61
12 Periodic Actions......................................................................... 62
12.1 Inserting the Cables ........................................................................... 62
12.1.1 Leading Cables through Enclosure Opening with Membrane.... 62
12.1.2 Leading Cables through Enclosure Opening with Cable Gland 62
12.2 Disassembling and Mounting the Protective Covers........................ 63
13 Technical Data........................................................................... 65
14 Accessories ................................................................................ 72
15 Contact....................................................................................... 74
Operating Manual 5SSMUXX15-BE-en-10

1 Information on this Document

SMA Solar Technology AG
1 Information on this Document

1.1 Validity

This document is valid for the SMAString-Monitor of the following device types from production version A1:
• SSM-U-1615
• SSM-U-2415
• SSM-U-3215

1.2 Target Group

The tasks described in this document must only be performed by qualified persons. Qualified persons must have the following skills:
• Knowledge of how the product works and is operated
• Training in how to deal with the dangers and risks associated with installing and using electrical devices and systems
• Training in the installation and commissioning of electrical devices and systems
• Knowledge of all applicable standards and directives
• Knowledge of and adherence to this manual and all safety precautions

1.3 Additional Information

Links to additional information can be found at www.SMA-Solar.com.

1.4 Symbols

Symbol Explanation
Indicates a hazardous situation which, if not avoided, will result in death or serious injury
Indicates a hazardous situation which, if not avoided, can result in death or serious injury
Indicates a hazardous situation which, if not avoided, can result in minor or moderate injury
Indicates a situation which, if not avoided, can result in property damage
Information that is important for a specific topic or goal, but is not safety-relevant
Indicates a requirement for meeting a specific goal
Desired result
A problem that might occur
Operating ManualSSMUXX15-BE-en-106
SMA Solar Technology AG
1 Information on this Document

1.5 Typographies

Typographies Use Example
bold
>
[Button/Key]
• Display messages
• Elements on a user interface
• Terminals
• Slots
• Elements to be selected
• Elements to be entered
• Connects several elements to be selected
• Button or key to be selected or pressed
• Set parameter WGra to
0.2.
• Select PV system > Detect.
• Select [Start detection].

1.6 Nomenclature

In this document, the SMAString‑Monitor is also referred to as "DC subdistribution" or "product".
Operating Manual 7SSMUXX15-BE-en-10

2 Safety

SMA Solar Technology AG
2 Safety

2.1 Intended Use

The SMAString‑Monitor is a PV array junction box to which several strings can be connected in parallel. The SMAString-Monitor monitors the input currents of the strings and detects failures, thus helping to minimize power and yield losses.
The SMAString‑Monitor can be operated in large-scale PV power plants with central inverters from SMA Solar Technology AG or other PV inverters.
The maximum current values for the SMAString-Monitor must not be exceeded. The SMAString-Monitor should only be operated when the strings are fuse protected. SMA Solar
Technology AG guarantees safe operation of the SMAString-Monitor with inline fuse connectors as string fuses, providing that the inline fuse connectors are connected directly to the DC connectors of the string cables on the DC subdistribution. For any other type or location of the string fusing, SMA Solar Technology AG cannot guarantee safe operation of the SMAString-Monitor or compliance with the required thresholds. The inline fuse connectors are available as accessories.
The product is suitable for indoor and outdoor use. All work on the product must only be performed using appropriate tools and in compliance with the
ESD protection regulations. The installation of SMA accessories in the product is permissible without specific approval by SMA
Solar Technology AG, providing that the product supports the given SMA accessories (see Section14, page72).
The product must only be used in countries for which it is approved or released by SMA Solar Technology AG and the grid operator.
Use this product only in accordance with the information provided in the enclosed documentation and with the locally applicable standards and directives. Any other application may cause personal injury or property damage.
Alterations to the product, e.g. changes or modifications, are only permitted with the express written permission of SMA Solar Technology AG. Unauthorized alterations will void guarantee and warranty claims and usually void the operating license. SMA Solar Technology AG shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as appropriate.
The enclosed documentation is an integral part of this product. Keep the documentation in a convenient place for future reference and observe all instructions contained therein.
The type label must remain permanently attached to the product.
Operating ManualSSMUXX15-BE-en-108
SMA Solar Technology AG
2 Safety

2.2 Safety Information

This section contains safety information that must be observed at all times when working on or with the product. To prevent personal injury and property damage and to ensure long-term operation of the product, read this section carefully and observe all safety information at all times.
Danger to life from electric shock due to live voltage
High voltages are present in the live components of the product. Touching live components results in death or serious injury due to electric shock.
• Wear suitable personal protective equipment for all work on the product.
• Do not touch any live components.
• Unless live voltage is absolutely necessary, always disconnect the product from voltage sources before performing any work (see Section8 "Disconnecting and Reconnecting", page46).
Danger to life from electric shock due to live DC cables
DC cables connected to PV modules that are exposed to sunlight are energized. Touching live cables results in death or serious injury due to electric shock.
• Prior to assembling the DC cables, ensure that the DC cables are voltage-free.
• Wear suitable personal protective equipment for all work on the product.
Danger to life from electric shock due to ground fault
If there is a ground fault, system components that are supposedly grounded may in fact be live. Touching incorrectly grounded components results in death or serious injuries from electric shock.
• Before working on the system, ensure that no ground fault is present.
• Wear suitable personal protective equipment for all work on the product.
Danger to life from electric shock due to damaged product
Operating a damaged product can lead to hazardous situations that result in death or serious injuries due to electric shock.
• Only operate the product when it is in a flawless technical condition and safe to operate.
• Check the product regularly for visible damage.
• Make sure that all external safety equipment is freely accessible at all times.
• Make sure that all safety equipment is in good working order.
• Wear suitable personal protective equipment for all work on the product.
Operating Manual 9SSMUXX15-BE-en-10
2 Safety
SMA Solar Technology AG
Danger to life from electric shock if the product is not locked
If the product is not locked, unauthorized persons will have access to live components carrying lethal voltages. Touching live components can result in death or serious injury due to electric shock.
• Always close and lock the product.
• Remove the keys.
• Store the keys in a safe place.
• Ensure that no unauthorized persons have access to the closed electrical operating area.
Danger to life from electric shock if the DC load-break switch is damaged
Switching the DC load-break switch at temperatures belowthe specified threshold may damage the DC load-break switch. The threshold is: ‒25°C. In this case, reliable disconnection can no longer be guaranteed.
If the DC load-break switch is switched in spite of visible damage, again the reliable disconnection function cannot be guaranteed.
High voltages are present in components that are not properly disconnected. Touching live components can result in death or serious injury due to electric shock.
• Do not switch the DC load-break switch at temperatures below the specified threshold. The threshold is: ‒25°C.
• Do not switch the DC load-break switch if it is visibly damaged.
Risk of burns due to hot components
Some components of the product can get very hot during operation. Touching these components can cause burns.
• Observe the warnings on all components.
• During operation, do not touch any components marked with such warnings.
• Wear suitable personal protective equipment for all work on the product.
Damage to the PV system due to incorrectly rated fuses
If fuses are incorrectly rated, excessive reverse currents can destroy the PV modules.
• Observe the maximum current values for the product when rating the fuses.
Operating ManualSSMUXX15-BE-en-1010
SMA Solar Technology AG
Property damage due to dust intrusion and moisture penetration
Dust or moisture intrusion can damage the product and impair its functionality.
• Do not open the enclosure during rainfall or when humidity exceeds the specified threshold. The threshold for humidity is: 95 %.
• Only perform maintenance work when the environment is dry and free of dust.
• Operation of the product is only permitted when it is closed.
• If the installation or commissioning process is interrupted, mount all panels.
• Close and lock the enclosure.
• The product must always be closed for storage.
• Store the product in a dry and covered location.
• Temperature at the storage location must be in the specified range. The temperature range is: ‒40°Cto+70°C.
Damage to electronic components due to electrostatic discharge
Electrostatic discharge can damage or destroy electronic components.
• Observe the ESD safety regulations when working on the product.
• Wear suitable personal protective equipment for all work on the product.
• Discharge electrostatic charge by touching grounded elements. Only then is it safe to touch electronic components.
2 Safety

2.3 Personal Protective Equipment

Always wear suitable protective equipment
When working on the product, always wear the appropriate personal protective equipment for the specific job.
The following personal protective equipment is regarded to be the minimum requirement:
☐ In a dry environment, safety shoes of categoryS3 with perforation-proof soles and steel toe
caps
☐ During precipitation or on moist ground, safety boots of categoryS5 with perforation-proof
soles and steel toe caps ☐ Tight-fitting work clothes made of 100%cotton ☐ Suitable work pants ☐ Individually fitted hearing protection ☐ Safety gloves
Any other prescribed protective equipment must also be used.
Operating Manual 11SSMUXX15-BE-en-10

3 Scope of Delivery

SMA Solar Technology AG
3 Scope of Delivery
Check the scope of delivery for completeness and any externally visible damage. Contact your distributor if the scope of delivery is incomplete or damaged.
Figure 1: Components included in the scope of delivery
Position Quantity Designation
A 1 SMAString-Monitor B 1 Switch cabinet key C 4 Size-reducing seal inserts D 1 Operating manual and circuit diagram
Operating ManualSSMUXX15-BE-en-1012
SMA Solar Technology AG

4 Product Overview

4 Product Overview
4.1 SMAString-Monitor
The SMAString‑Monitor is a PV array junction box to which several strings can be connected in parallel. The SMAString‑Monitor can be operated in large-scale PV power plants with central inverters from SMA Solar Technology AG or other PV inverters.
The essential tasks performed by the SMAString-Monitor are:
• to bundle the input currents of the strings
• to measure the input currents of the strings and transfer these to the inverter
• to transmit information on the input currents of the strings This enables failures to be recognized and power and yield losses to be minimized.
Principle of a grid-tie PV system with SMAString-Monitor
Figure 2: Principle of a grid-tie PV system with SMAString-Monitor
Position Designation
A PV array B SMAString-Monitor C Sunny Central D Transformer E Utility grid
Operating Manual 13SSMUXX15-BE-en-10
4 Product Overview

4.2 External View of the DC Subdistribution

Figure 3: External view of the DC subdistribution
Position Designation
A Lock cylinder B Wall bracket lugs C Vent plug D Enclosure openings for introducing the cables
SMA Solar Technology AG
Operating ManualSSMUXX15-BE-en-1014
SMA Solar Technology AG

4.3 Components of the DC Subdistribution

4 Product Overview
Figure 4: Components of the DC subdistribution
Position Designation
A DC overvoltage protection B DC Load-Break Switch C Terminal for connection of the DC overvoltage protection unit to the functional
grounding
Operating Manual 15SSMUXX15-BE-en-10
4 Product Overview
Position Designation
D Rotary handle of the DC load-break switch E Electronic assembly
Protective covers
SMA Solar Technology AG
Figure 5: Position of the protective covers
Position Designation
A Top protective cover B Bottom protective cover
Operating ManualSSMUXX15-BE-en-1016
1 2 3 4 5 6 7 8 9 1112 14
A
B
C
D
E F
G H
K
L
M
N
OP
Q
I
SMA Solar Technology AG
4 Product Overview

4.4 Terminals on the Electronic Assembly

Figure 6: Terminals on the electronic assembly
Position Designation Explanation
A Connection of string cable harnesses (PV+) and, depend-
ing on the version, of the plug-in board (MEU) for the num-
ber of PV inputs (factory installed) B X1 Analog current input C X2 Analog input temperature sensor external 1 (EXT 1) D X3 Analog input temperature sensor external 2 (EXT 2) E X4 Digital customer input F X5 Digital input surge arrester DC G X6 Status alarm contact DC load-break switch H X7 Ethernet communication output LAN OUT I X8 Terminal for the functional grounding cable of the elec-
tronic assembly K X9 Ethernet communication input LAN IN L LWLPB 1 Slot for the OF interface module (communication input
LWL IN) M LWLPB 2 Slot for the OF interface module (communication output
LWL OUT) N Digital output of potential-free change-over contact
Operating Manual 17SSMUXX15-BE-en-10
4 Product Overview
Position Designation Explanation
O Slot for the power supply assembly for external 230V
supply voltage to the SMAString-Monitor via the inverter P Terminal for supply voltage of the SMAString-Monitor
from the PV field (PV-) (factory installed) Q Fuse for the supply voltage of the SMAString-Monitor
from the PV field
SMA Solar Technology AG
AC

4.5 Type Label

The type label clearly identifies the product. You will require the information on the type label to use the product safely and when seeking
customer support from Service (see Section15, page74). The type label must remain permanently attached to the product.
SMAString-Monitor
There are two type labels attached to the SMAString‑Monitor. The type labels are located on the inside of the right-hand door and on the right-hand outside panel of the SMAString‑Monitor.
You can read off the following data from the type label:
• Date of manufacture (Fabrication Date)
• Serial number (SER)
• Device type (SSM-U-XXXX XX/XX/XX)
• Device-specific characteristics
Electronic assembly
There is one type label attached to the electronic assembly. The type label is located at the top left of the electronic assembly.
You can read off the following data from the type label:
• Production version (FA)
• Serial number (SER)
• Assembly type and version (SSM30BASE.XXX)
Plug-in board (MEU) for the number of PV inputs
There is one type label attached to the plug-in board. You can read off the following data from the type label:
• Production version (FA)
• Serial number (SER)
• Assembly type and version (SSM30MEU.XXX)
Operating ManualSSMUXX15-BE-en-1018
SMA Solar Technology AG
4 Product Overview

4.6 Symbols on the Product

The following gives an explanation of all the symbols found on the SMAString-Monitor and on the type label.
Symbol Designation Explanation
CE marking The product complies with the requirements of the applica-
ble EU directives.
DataMatrix code 2Dcode for device-specific characteristics
Degree of protec­tionIP54
Protection class II The product has a reinforced or double insulation be-
WEE marking Do not dispose of the product together with household
Beware of dangerous voltage
Beware of hot surface The product can get hot during operation. Avoid contact
Observe the documen­tation
The product is protected against interior dust deposits and
splashing water from all angles.
tween grid current circuit and output voltage.
waste but in accordance with the locally applicable dis-
posal regulations for electronic waste.
The product operates at high voltages. All work on the
product must be carried out by qualified persons only.
during operation. Allow the product to cool down suffi-
ciently before carrying out any work. Wear personal pro-
tective equipment such as safety gloves.
Observe all documentation supplied with the product.
Operating Manual 19SSMUXX15-BE-en-10
L‒L+
LK/ACT SPEED
LK/ACT SPEED
UPD ERR AL PWR COM
A
B
C
D
E
4 Product Overview
SMA Solar Technology AG

4.7 LEDs on the Electronic Assembly

Figure 7: LEDs on the electronic assembly
Position Designation Color Explanation
A UPD yellow Update status of the SMAString-Moni-
tor ERR red Error in the SMAString-Monitor AL green Firmware status of the SMAString-
Monitor PWR green Voltage supply status of the
SMAString-Monitor COM yellow Communication status of the
SMAString-Monitor
B LK/ACT green Status/activity of the network connec-
tion at the communication output
C SPEED yellow Speed of the network connection at
the communication output
D LK/ACT green Status/activity of the network connec-
tion at the communication input
E SPEED yellow Speed of the network connection at
the communication input
A description of the LED states will by given in (see Section9.1, page49).
Operating ManualSSMUXX15-BE-en-1020
SMA Solar Technology AG

5 Mounting

5 Mounting

5.1 Selecting the Mounting Location

Fire hazard due to wrong choice of mounting location
Despite careful construction, electrical devices can cause fires.
• Do not mount the DC sub-distribution on flammable construction materials.
• Do not mount the DC sub-distribution in areas containing highly flammable materials.
• Do not mount the DC sub-distribution in potentially explosive atmospheres.
Requirements for the mounting location:
☐ The mounting location can be outdoors or indoors. ☐ The mounting location must not be in a living or office area. ☐ The mounting location must not block any escape routes. ☐ The mounting location must be freely and safely accessible at all times without the necessity for
any auxiliary equipment (e.g. scaffolding or lifting platforms). Non-fulfillment of these criteria
may restrict servicing. ☐ The mounting location must be shaded, e.g. under a protective roof. ☐ The mounting location must be suitable for the weight and dimensions of the SMA
SunnyString‑Monitor. ☐ The mounting location must be suitable for the wind load. ☐ Mounting space below the SMAStringMonitor when using the inline fuse connectors:
at least 800mm.
Requirements for mounting the SMAString-Monitor
☐ Mount the SMASunnyString-Monitor so that the connection area is facing downwards. ☐ Mount the SMAString-Monitor in a horizontal position. ☐ Do not mount the SMAString Monitor in a twisted manner. ☐ Do not mount the SMASunnyString‑Monitor in a horizontal or inclined position. ☐ An external cable support rail must be provided.
Example: Mounting on PV array substructure
• If the PV array is mounted on a free-standing structure, the DC subdistribution can be fixed to this structure in a shaded position. In this case, make sure that there is no danger of rainwater flowing off the module surface and over the enclosure of the DC subdistribution.
Operating Manual 21SSMUXX15-BE-en-10
5 Mounting
Dimensions and anchoring points:
Figure 8: Dimensions and anchoring points
Position Explanation
A 630.00mm B 600.00mm C 573.00mm (space between anchoring points) D 825.60mm (space between anchoring points) E 850.00mm F 250.00mm
SMA Solar Technology AG
Operating ManualSSMUXX15-BE-en-1022
SMA Solar Technology AG
Observe minimum clearances:
Figure 9: Minimum clearances
Position Explanation
A 200mm B 650mm C 800mm D 150mm E 650mm
5 Mounting
5.2 Mounting the SMAString-Monitor on the Wall
Risk of injury when lifting the DC sub-distribution, or if it is dropped
There is risk of injury if the DC sub-distribution is lifted incorrectly or dropped while being transported or when attaching it to or removing it from the wall mounting bracket. Weight of the DC sub-distribution without installed accessories: 35 kg.
• Two persons are required for mounting and disassembling the DC sub-distribution.
• Carefully lift and transport the DC sub-distribution.
Additionally required mounting material (not included in the scope of delivery):
• For mounting the DC subdistribution on a wall: – 4 screws M6. Take the wall properties into account when selecting the screws. – 4 washers
Operating Manual 23SSMUXX15-BE-en-10
5 Mounting
SMA Solar Technology AG
– 4 screw anchors if necessary. Take the wall properties into account when selecting the
screw anchors.
• For mounting the DC subdistribution on the PV module substructure: – 4 screws M6 – 4 washers – 4 nuts
Procedure:
1. Close the DC subdistribution.
2. Mark the position of the drill holes on the wall or support structure.
3. Drill holes at the marked positions.
4. If necessary, insert screw anchors.
5. Fasten the DC subdistribution to the wall or substructure using suitable screws and washers.
6. Ensure that the DC subdistribution is securely attached.
Operating ManualSSMUXX15-BE-en-1024
SMA Solar Technology AG

6 Installation

6 Installation
6.1 Overview of the Connection Area of the SMA String­Monitor
View from Below
Figure 10: View of the SMAString-Monitor from below
Position Designation
A Enclosure opening with cable gland for the main cable DC+ B Enclosure opening with string cable harness (PV+) and DC connectors (factory pre-
assembled) C Condensate drain D Enclosure opening with string cable harness (PV‒) and DC connectors (factory pre-
assembled) E Enclosure opening with cable gland for the main cable DC‒ F Enclosure opening with membrane for the following cables:
• Communication
• Sensors
• External functional grounding for the electronic assembly
• External functional grounding for the DC surge arrester
G Enclosure opening with cable gland for the cables of the external 230VAC voltage
supply H Enclosure opening with cable gland for the external functional grounding cable of
the power supply assembly
Operating Manual 25SSMUXX15-BE-en-10
6 Installation
Interior View
SMA Solar Technology AG
Figure 11: Interior view of the DC subdistribution
Position Designation
A Busbar for connecting the main cables DC+ B Busbar for connecting the main cables DC‒ C Terminal plate for connecting external functional grounding of the DC surge
arrester
D Cable channel
Operating ManualSSMUXX15-BE-en-1026
SMA Solar Technology AG
Position Designation
E Electronic assembly F Strain relief for the cables

6.2 Grounding

6.2.1 Information on Grounding

The parts to be grounded can be connected to a joint grounding electrode.

6.2.2 Grounding the Electronic Assembly

6 Installation
Cable requirement:
☐ Conductor cross-section: 6mm
Procedure:
1. Lead the grounding cable through the corresponding enclosure opening (see Section6.1, page25) into the DC subdistribution (see Section12.1, page62).
2. Strip the grounding cable by 15mm. Make sure that no pieces of cable are dropped into the DC subdistribution.
3. Connect the grounding cable to the electronic assembly at screw terminal X8 FE (see Section4.4, page17) to ground the electronic assembly.
4. Ensure that the grounding cable is securely fixed.
5. Attach the grounding cable to the strain relief in the DC subdistribution using a cable tie.
6. Ground the grounding cable in the vicinity of the DC subdistribution, e.g. by means of a grounding electrode.
2

6.2.3 Grounding the DC Surge Arrester

In order to guarantee the function of the DC surge arrester, it must be connected to the external grounding.
Cable requirements:
☐ Conductor cross-section: 16mm2 to 35mm ☐ Recommended cable type: NYY-O
Procedure:
1. Lead the grounding cable through the corresponding enclosure opening (see Section6.1, page25) into the DC subdistribution (see Section12.1, page62).
2. Strip the grounding cable by 15mm. Make sure that no pieces of cable are dropped into the DC subdistribution.
3. Route the grounding cable in the cable channel to the connecting terminal plate for functional grounding of the DC surge arrester (see Section4.4, page17). To do this, you can remove and reattach the cover of the cable channel.
2
Operating Manual 27SSMUXX15-BE-en-10
6 Installation
4. Release the screw on the connecting terminal plate, insert the grounding cable and fasten the screw (torque: 3.2Nm).
5. Ensure that the grounding cable is securely fixed.
6. Attach the grounding cable to the strain relief in the DC subdistribution using a cable tie.
7. Ground the grounding cable in the vicinity of the DC subdistribution, e.g. by means of a grounding electrode.
SMA Solar Technology AG

6.3 Installation of the DC Main Cables

6.3.1 Safety during Installation of the DC Main Cables

Risk of fire due to failure to observe torque specifications on voltage-carrying bolted connections
Failure to follow the specified torques reduces the transmission capacity of live bolted connections and the contact resistances increase. This can cause components to overheat and catch fire.
• Ensure that live bolted connections are always tightened with the exact torque specified in this document.
• When working on the device, use suitable tools only.
• Avoid repeated tightening of live bolted connections, as this may result in inadmissibly high torques.
Damage to the electronic assembly by the DC main cables
When inserting the DC main cables into the DC subdistribution, it is possible to damage the electronic assembly.
• When inserting the DC main cables, keep them far enough away from the electronic assembly.
Failure of data transmission due to incorrect cable routing
Non-compliance with the minimum clearances between the DC main cables and the data cable may lead to failure of data transmission. This can result in yield loss.
• When laying the DC main cables, ensure that the minimum clearance of 200mm to the data cables is observed.

6.3.2 Options for Installation of the DC Main Cables

You can regularly connect up to two DC main cables per pole. The required material for the bolted connections is already preassembled on the busbar. Further material may be required depending on the connection type and the cable type.
The following options for connecting the DC main cables are available:
Operating ManualSSMUXX15-BE-en-1028
SMA Solar Technology AG
6 Installation
Connecting the DC main cables to the busbar using terminal lugs(see Section6.3.3, page29 )
• DC main cable 70mm2 to 400mm2 made of aluminum or copper – Aluminum cable: additionally required material: bimetal ring terminal lugs – Copper cable: tin-plated copper ring terminal lugs are preassembled
Connecting the DC main cables to the busbar using V box terminals(see Section6.3.4, page32)
• DC main cable 70mm2 to 300mm2 made of aluminum or copper
Additionally required material: V box terminals (see Section6.3.4.1 "Requirements and Conditions", page32) (see Section14, page72)

6.3.3 Connecting the DC Main Cables to the Busbar using Terminal Lugs

Cable requirements for connection with terminal lugs:
☐ Use copper or aluminum cables only. ☐ The cables must be designed for the maximum PV voltage. ☐ Maximum number of cables per potential: 2 ☐ Permitted cable cross-section: 70mm2 to 400 mm
Terminal lug requirements:
☐ For the connection of copper cables, use only tin-plated copper tube terminal lugs. ☐ For the connection of aluminum cables, use only bimetal tube terminal lugs. ☐ For the connection, use only the screws, nuts and washers which are preassembled on the
busbar. ☐ The terminal lugs must be designed for the given temperature. Temperature: +95°C ☐ The width of the terminal lugs must exceed the washer diameter. Washer diameter: 32mm.
This will ensure that the defined torques are effective over the whole surface. ☐ Maximum width of the terminal lugs when connecting two cables per potential: 48mm.
If using cables with small cross-sections, the cable lugs can be installed next to each other.
If using cables with large cross-sections, the cable lugs must be installed one behind the other.
Additionally required mounting material (not included in the scope of delivery):
☐ For the connection of copper cables: tin-plated copper tube terminal lugs for screw size M12 ☐ Clean cloth ☐ Ethanol cleaning agent
2
Operating Manual 29SSMUXX15-BE-en-10
6 Installation
Assembly of the Connection with One Terminal Lug
Figure 12: Assembly of the Connection with One Terminal Lug
Position Designation
A Screw M12 B Washer C Tin-plated copper busbar D Tin-plated tube terminal lug E Fender washer F Spring washer G Nut M12
SMA Solar Technology AG
Operating ManualSSMUXX15-BE-en-1030
SMA Solar Technology AG
Assembly of the Connection with Two Terminal Lugs
Position Designation
A Screw M12 B Washer C Tin-plated copper busbar D Fender washer E Spring washer F Nut M12 G Tin-plated tube terminal lug
6 Installation
Procedure:
1. Ensure that the DC subdistribution is switched off and secured against reconnection (see Section8 "Disconnecting and Reconnecting", page46).
2. Ensure that the inverter is disconnected on the DC side and secured against reconnection (see inverter manual).
3. Lead the DC main cables into the DC subdistribution through the designated enclosure opening (see Section6.1, page25) with the appropriate seal insert (see Section12.1, page
62).
4. Fit the DC main cables with tube terminal lugs. Make sure that no pieces of cable are dropped into the DC subdistribution.
5. In the DC subdistribution, remove the fastening material for the DC main cables from the busbars.
6. Clean the contact surfaces using a clean cloth and ethanol cleaning agent. Do not touch the contact surfaces after cleaning.
Operating Manual 31SSMUXX15-BE-en-10
6 Installation
SMA Solar Technology AG
7. Connect the DC main cables to the busbars for the DC main cables (torque: 60 Nm) (see Section6.1, page25). To do this, use only the fastening material already attached to the busbars and do not connect more than two DC main cables to each busbar.
8. Ensure that the DC main cables are securely attached.
9. Secure the DC main cables to the external cable support rail.

6.3.4 Connecting the DC Main Cables to the Busbar using V Box Terminals

6.3.4.1 Requirements and Conditions
Cable requirements for connection with V box terminals:
☐ Use copper or aluminum cables only. ☐ The cables must be designed for the maximum PV voltage. ☐ The cables must have double or reinforced insulation. ☐ Maximum number of cables per potential: 2 ☐ Permitted cable cross-section: 70mm2 to 300 mm ☐ Permitted conductor cross-section:
Cable type Conductor cross-section per potential
Round, single-strand 70mm2to150mm Round, multi-strand 70mm2to300mm Sectoral, single-strand 70mm2to240mm Sectoral, multi-strand 70mm2to240mm
2
2
2
2
2
Additionally required mounting material (not included in the scope of delivery):
☐ Clean cloth ☐ Ethanol cleaning agent
Operating ManualSSMUXX15-BE-en-1032
SMA Solar Technology AG
6.3.4.2 Installing the Box Terminal on the Busbar
Assembly of the Connection with One Box Terminal
Figure 13: Assembly of the Connection with One Box Terminal
Position Designation
A Screw M12 B Washer C Tin-plated copper busbar D Fender washer E Spring washer F Nut M12 G Box terminal
6 Installation
Installing the Box Terminal on the Busbar
1. Ensure that the DC subdistribution is switched off and secured against reconnection (see Section8 "Disconnecting and Reconnecting", page46).
2. Ensure that the inverter is fully disconnected from voltage sources on the DC side and secured against reconnection (see inverter manual).
3. In the DC subdistribution, remove the fastening material for the DC main cables from the busbars.
4. Clean the contact surfaces on the busbar and box terminal using a clean cloth and ethanol cleaning agent. Do not touch the contact surfaces after cleaning.
5. Mount the box terminals on the busbar (torque: 60 Nm). To do this, use only the fastening material already attached to the busbars.
Operating Manual 33SSMUXX15-BE-en-10
6 Installation
SMA Solar Technology AG
6.3.4.3 Connecting Copper Cables to V-Box Terminal
Risk of fire from contact failure
Grease on the set screw can result in failure to reach the prescribed torque. Contact failure and increased transition resistances are the result. This can cause components to overheat and catch fire.
• Insert the insulated conductors into the box terminal from below. Ensure that no grease comes into contact with the set screw.
Procedure:
1. Ensure that the DC subdistribution is switched off and secured against reconnection (see Section8 "Disconnecting and Reconnecting", page46).
2. Ensure that the inverter is fully disconnected from voltage sources on the DC side and secured against reconnection (see inverter manual).
3. Unscrew the set screw of the box terminal with an Allen key.
4. If you are using a cable with cable cross-section 185mm2 to 300mm2, remove the insert in the box terminal and reinsert it the other way round. The insert on the box terminal has a small and a large clamping area. The insert must be reinserted so that the side for the larger clamping area points towards the DC main cable to be clamped.
5. Lead the DC main cables into the DC subdistribution through the designated enclosure openings (see Section6.1, page25) with the appropriate seal insert (see Section12.1, page
62). Ensure correct polarity.
6. Strip the DC main cables by 35mm.
7. Connect one DC main cable to each box terminal. To do this, insert the conductors into the box terminal from below and fasten the set screw of the box terminal (torque: 32 Nm).
8. Ensure that the DC main cables are securely attached.
9. Secure the DC main cables to the external cable support rail.
Operating ManualSSMUXX15-BE-en-1034
SMA Solar Technology AG
6 Installation
6.3.4.4 Connecting Aluminum Cables to V Box Terminal
Upon contact with oxygen, an oxide film forms on aluminum surfaces. This oxide film increases transition resistances. For this reason, the insulated conductors of the aluminum cables must be cleaned immediately before connecting them. If they are not to be connected immediately after cleaning, the cable ends will need greasing. This prevents the formation of a new oxide film. We recommend connecting the greased conductors to the box terminals within eight hours.
Risk of fire through connection of soiled or oxidized aluminum cables
Connecting soiled or oxidized DC main cables reduces the ampacity of the live terminals, thereby increasing the transition resistances. This can cause components to overheat and catch fire.
• Only connect clean and oxide-free conductors of the aluminum cables.
• Ensure that the conductors are free of iron particles.
• Connect the insulated conductors to the terminals within ten minutes of cleaning.
Risk of fire from contact failure
Grease on the set screw can result in failure to reach the prescribed torque. Contact failure and increased transition resistances are the result. This can cause components to overheat and catch fire.
• Insert the insulated conductors into the box terminal from below. Ensure that no grease comes into contact with the set screw.
Procedure:
1. Ensure that the DC subdistribution is switched off and secured against reconnection (see Section8 "Disconnecting and Reconnecting", page46).
2. Ensure that the inverter is fully disconnected from voltage sources on the DC side and secured against reconnection (see inverter manual).
3. Unscrew the set screw of the box terminal with an Allen key.
4. If you are using a cable with cable cross-section 185mm2 to 300mm2, remove the insert in the box terminal and reinsert it the other way round. The insert on the box terminal has a small and a large clamping area. The insert must be reinserted so that the side for the larger clamping area points towards the DC main cable to be clamped.
5. Lead the DC main cables into the DC subdistribution through the designated enclosure openings (see Section6.1, page25) with the appropriate seal insert (see Section12.1, page
62). Ensure correct polarity.
6. Strip the DC main cables by 35mm.
7. Remove any oxide film from the insulated conductors of the DC main cable e.g. with a sharp knife. Do not use files, sandpaper or brushes.
8. Ensure that no further contamination builds up on the insulated conductors.
9. If you do not connect the insulated conductors within ten minutes of cleaning, grease them. This prevents the formation of an oxide film.
Operating Manual 35SSMUXX15-BE-en-10
6 Installation
SMA Solar Technology AG
10. Unscrew the set screw of the box terminal with an Allen key (AF 6).
11. Connect one DC main cable to each box terminal. To do this, insert the conductors into the box terminal from below and fasten the set screw of the box terminal (torque: 32 Nm).
12. Ensure that the DC main cables are securely attached.
13. Secure the DC main cables to the external cable support rail.

6.4 Connecting the Ethernet Cables

Up to ten SMAString-Monitors can be connected in line topology to each string monitoring communication terminal of the inverter (for number of string monitoring communication terminals, see inverter manual).
The Ethernet cables are connected to LSA+ terminals on the electronic assembly using an LSA+ insertion tool.
Interference in data transmission due to unshielded power cables
If unshielded power cables are used, they generate an electromagnetic field during operation which may induce interference in network cables during data transmission.
• When laying network cables, observe the following minimum clearances to unshielded energy cables:
– For installation without separating strip: at least 200mm – For installation with aluminum separating strip: at least 100mm – For installation with steel separating strip: at least 50mm
Requirements for Ethernet cables:
☐ Cable type: copper, two-conductor ☐ Number of insulated conductor pairs and insulated conductor cross-section: 4 x 2 x 0.125mm
2
to 0.205mm ☐ Cable type: at least Cat5 with shielding S-UTP, F-UTP or higher ☐ Maximum cable length: 100m
2
Operating ManualSSMUXX15-BE-en-1036
SMA Solar Technology AG
System topology for Ethernet communication:
Figure 14: System topology for Ethernet communication with SMAString-Monitor (example)
Position Designation
A SMAString-Monitor B Inverter (example)
6 Installation
Procedure:
1. Lead the Ethernet cable through the corresponding enclosure opening (see Section6.1, page25 ) into the DC subdistribution (see Section12.1, page62).
2. Prepare the Ethernet cable for connection as follows:
• Strip 44mm cable sheath off the end of the connection cable which is to be attached to the DC subdistribution.
• Shorten the cable shield to 15mm.
• Fold the surplus cable shield back over the cable sheath.
3. Press the Ethernet cable with the cable shield into the shield clamp. The cable shield must be clamped under the shield clamp as completely as possible.
4. Connect the Ethernet cables to the LSA+ terminals on the electronic assembly using the LSA+ insertion tool:
• To connect the communication output, connect all eight conductors of the Ethernet cable to the electronic assembly at terminal X7 (see Section4.4, page17) according to the following table. Trim any overlapping conductors.
Operating Manual 37SSMUXX15-BE-en-10
6 Installation
SMA Solar Technology AG
• To connect the communication input, connect all eight conductors of the Ethernet cable to the electronic assembly at terminal X9 (see Section4.4, page17) according to the following table. Trim any overlapping conductors.
Signal Terminal
X7 and X9
TX+ 1
EIA/TIA 568B (eight-conductor) Insulated conductor color
white/orange
(white/orange)
TX- 2
orange/white or orange
(orange/white or or­ange)
RX+ 3
white/green
(white/green)
not assigned 4
blue/white or blue
(blue/white or blue)
not assigned 5
white/blue
(white/blue)
RX- 6
green/white or green
(green/white or green)
not assigned 7
white/brown
(white/brown)
not assigned 8
brown/white or brown
(brown/white or brown)
5. Ensure that the Ethernet cables are securely connected.
6. Attach the Ethernet cables to the strain relief in the DC subdistribution using a cable tie.
7. Connect the Ethernet cable for the communication output in the inverter (see inverter manual) or in the next DC subdistribution in the communication bus.
8. Secure the Ethernet cables to the external cable support rail.
Operating ManualSSMUXX15-BE-en-1038
SMA Solar Technology AG
6 Installation

6.5 Connection of Sensors

6.5.1 Connecting Temperature Sensors

You can connect two temperature sensors, e.g., ambient temperature sensor or module temperature sensor, in the DC subdistribution. The measured values from the temperature sensors are shown on the user interface of the inverter. The sensors can be connected using two-, three- or four-conductor connection technology.
Cable requirements:
☐ Conductor cross-section: 0.08mm2 to 1.00mm ☐ External cable diameter: 3.2mm to 6.5mm
Additionally required material (not included in the scope of delivery):
☐ 1 ambient temperature sensor or 1 module temperature sensor ☐ 1 connection cable
Requirement:
☐ The sensor must be technically suitable for connection to the temperature inputs of the DC
subdistribution (see Section13, page65).
Procedure:
1. Connect the cable to the sensor (see manufacturer manual). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. Lead the other end of the cable through the corresponding enclosure opening (see Section6.1, page25) into the DC subdistribution (see Section12.1, page62).
3. Prepare the cable for connection as follows:
• Remove 40mm of cable sheath at the end of the cable.
• Strip the conductors by 6mm.
4. Lead the cable through the cable channel as far as terminal X2 or X3 (see Section4.4, page17 ) of the electronic assembly and out of one of the lateral slits in the cable channel. To do this, you can remove and reattach the cover of the cable channel.
5. Connect the cable to terminal X2 or X3 (see Section4.4, page17) of the electronic assembly according to the circuit diagram. Observe the pin assignment.
6. Attach the cable to the cable support rail in the DC subdistribution.
2

6.5.2 Connecting an Irradiation Sensor or Anemometer to the Analog Input

You can connect one irradiation sensor or one anemometer in the DC subdistribution. The measured values from the sensors are shown on the user interface of the inverter.
Cable requirements:
☐ Number of insulated conductors: at least two ☐ Shielding: yes ☐ Conductor cross-section: 0.08mm2 to 1mm
Operating Manual 39SSMUXX15-BE-en-10
2
6 Installation
SMA Solar Technology AG
☐ Maximum cable length: 30m ☐ External cable diameter: 3.2mm to 6.5mm
Additionally required material (not included in the scope of delivery):
☐ 1 irradiation sensor or 1 anemometer ☐ 1 connection cable
Requirement:
☐ The sensor must be technically suitable for connection to the analog input of the DC
subdistribution (see Section13, page65).
Procedure:
1. Connect the cable to the sensor (see manufacturer manual). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. Lead the other end of the cable through the corresponding enclosure opening (see Section6.1, page25) into the DC subdistribution (see Section12.1, page62).
3. Prepare the cable for connection as follows:
• Remove 40mm of cable sheath at the end of the cable.
• Strip the conductors by 6mm.
4. Lead the cable through the cable channel as far as terminal X1 (see Section4.4, page17) of the electronic assembly and out of one of the lateral slits in the cable channel. To do this, you can remove and reattach the cover of the cable channel.
5. Connect the cable to terminal X1 (see Section4.4, page17) of the electronic assembly according to the circuit diagram. Observe the pin assignment.
6. Attach the cable to the cable support rail in the DC subdistribution.

6.6 Connecting the Remote Terminal to the Digital Input

You can connect e.g. a remote signaling contact to the digital input of the DC subdistribution.
Cable requirements:
☐ Number of insulated conductors: at least two ☐ Conductor cross-section: 0.08mm2 to 1mm ☐ Maximum cable length: 30m ☐ External cable diameter: 3.2mm to 6.5mm
Additionally required material (not included in the scope of delivery):
☐ 1 remote terminal ☐ 1 connection cable
Requirement:
☐ The remote terminal must be technically suitable for connection to the digital input of the DC
subdistribution (see Section13, page65).
2
Operating ManualSSMUXX15-BE-en-1040
SMA Solar Technology AG
6 Installation
Procedure:
1. Connect the cable to the remote terminal (see manufacturer manual). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. Lead the other end of the cable through the corresponding enclosure opening (see Section6.1, page25) into the DC subdistribution (see Section12.1, page62).
3. Prepare the cable for connection as follows:
• Remove 40mm of cable sheath at the end of the cable.
• Strip the conductors by 6mm.
4. Lead the cable through the cable channel as far as terminal X4 (see Section4.4, page17) of the electronic assembly and out of one of the lateral slits in the cable channel. To do this, you can remove and reattach the cover of the cable channel.
5. Connect the cable to terminal X4 (see Section4.4, page17) of the electronic assembly according to the circuit diagram. Observe the pin assignment.
6. Attach the cable to the cable support rail in the DC subdistribution.

6.7 Connecting the Remote Terminal to the Digital Output

You can connect e.g. a warning light to the digital output of the DC subdistribution.
Cable requirements:
☐ Number of insulated conductors: at least two ☐ Conductor cross-section: 0.5mm2 to 6mm ☐ Maximum cable length: 30m ☐ External cable diameter: 3.2mm to 10.2mm
Additionally required material (not included in the scope of delivery):
☐ 1 remote terminal ☐ 1 connection cable
Requirement:
☐ The remote terminal must be technically suitable for connection to the digital output of the DC
subdistribution (see Section13, page65).
Procedure:
1. Connect the cable to the remote terminal (see manufacturer manual). Trim the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. Lead the other end of the cable through the corresponding enclosure opening (see Section6.1, page25) into the DC subdistribution (see Section12.1, page62).
3. Prepare the cable for connection as follows:
• Remove 80mm of cable sheath at the end of the cable.
• Strip the conductors by 12mm.
4. Connect the cable to terminal X10 (see Section4.4, page17) of the electronic assembly according to the circuit diagram. Observe the pin assignment.
5. Attach the cable to the cable support rail in the DC subdistribution.
2
Operating Manual 41SSMUXX15-BE-en-10
6 Installation
SMA Solar Technology AG

6.8 Installation of the String Cables

6.8.1 Requirements for Installation of the String Cables

Requirement:
☐ Apart from installation of the string cables, all other installation work must be completed.
Requirements for the PV modules per input:
☐ The thresholds for the input voltage and the input current of the DC subdistribution must be
adhered to (see Section13, page65).
☐ On the coldest day based on statistical records, the open-circuit voltage of the PV array must
never exceed the maximum input voltage of the DC subdistribution.
☐ The positive connection cables of the PV modules must be fitted with the positive DC
connectors (for information on assembling DC connectors, see the DC connector installation manual).
☐ The negative connection cables of the PV modules must be fitted with the negative DC
connectors (for information on assembling DC connectors, see the DC connector installation manual).
Use of Y adapters for parallel connection of strings
The Y adapters must not be used to interrupt the DC circuit under load.
• In order to interrupt the DC circuit, disconnect the DC subdistribution from all voltage sources (see Section8.2, page47).

6.8.2 Installing the String Cables

The SMAString-Monitor is supplied with string cable harnesses and DC connectors fitted at the factory.
Danger to life due to electric shock from live PV voltage
As soon as the string cables are connected, the electronic assembly and other voltage-carrying components will be energized. Touching live components results in death or serious injury due to electric shock.
• Wear suitable protective equipment for all work.
• Do not touch any live components.
• Always install string cables right at the end of the installation work.
Operating ManualSSMUXX15-BE-en-1042
SMA Solar Technology AG
6 Installation
Danger to life due to electric arc
An electric arc may occur when plugging or removing the DC connectors or the inline fuse connectors under load and in case of a reverse-poled connection of the DC connectors. Electric arcs can result in death or serious injury.
• Ensure the correct polarity of the strings before connection.
• Plug or remove DC connectors and inline fuse connectors only under load-free conditions.
• Disconnect the DC sub-distribution (see the DC sub-distribution manual).
• Wear suitable personal protective equipment.
Damage to the DC connectors due the use of contact cleaner of other cleaning agents
Some contact cleaners or other cleaning agents may contain substances that decompose the plastic of the DC connectors.
• Do not use contact cleaners or other cleaning agents for cleaning the DC connectors.
Damage to the DC subdistribution due to moisture ingress
The DC subdistribution is only properly sealed when all unused DC inputs are closed with suitable protective caps on the DC connectors.
• For any unused DC inputs of the DC subdistribution, fit appropriate protective caps of the SUNCLIX plug-in system onto the DC connectors of the string cables of the DC subdistribution. The protective caps are available from Phoenix Contact.
Cable requirements:
☐ Cable type: PV 1-F ☐ Conductor cross-section for 6mm2 DC connector: 2.5mm2 to 6.0mm
2
☐ Cable diameter for 6mm2 DC connector: 5.0mm to 8.0mm ☐ Conductor cross-section for 16mm2 DC connector: 6.0mm2 to 16.0mm
2
☐ Cable diameter for 16mm2 DC connector: 5.5mm to 10.0mm
Additionally required material (not included in the scope of delivery):
☐ For any unused DC inputs:
SUNCLIX protective caps for DC connectors
Procedure:
1. Ensure that the DC subdistribution is switched off and secured against reconnection (see Section8 "Disconnecting and Reconnecting", page46).
2. Ensure that there is no ground fault in the PV array (see service manual at www.SMA­Solar.com).
Operating Manual 43SSMUXX15-BE-en-10
6 Installation
SMA Solar Technology AG
3. On the DC subdistribution, remove the protection foil from the cable harnesses for connection of the PV strings.
4. If inline fuse connectors are used, connect the inline fuse connectors to the assembled DC connectors of the PV module string cables (see installation manual "IFCON Inline Fuse Connector Set16").
5. Connect the PV module string cables PV+ to the DC subdistribution:
• Connect the assembled DC connectors of the PV module string cables (PV+) to the string cable harnesses (PV+) of the DC subdistribution:
– If using inline fuse connectors, plug the inline fuse connectors of the PV module string
cables (PV+) into the string cable harness (PV+) of the DC subdistribution.
☑ The inline fuse connectors snap into place.
– If no inline fuse connectors are used, plug the assembled DC connectors of the PV
module string cables (PV+) into the DC connectors of the string harness (PV+) in the DC subdistribution.
☑ The DC connectors snap into place.
6. Connect the string cables PV module PV‒ to the DC subdistribution:
• Connect the assembled DC connectors of the PV module string cables (PV‒) to the string cable harness (PV‒) of the DC subdistribution:
– If using inline fuse connectors, plug the inline fuse connectors of the PV module string
cables (PV‒) into the string cable harness (PV‒) of the DC subdistribution.
☑ The inline fuse connectors snap into place.
– If no inline fuse connectors are used, plug the assembled DC connectors of the PV
module string cables (PV‒) into the DC connectors of the string cable harness (PV‒) in the DC subdistribution.
☑ The DC connectors snap into place.
7. Ensure that all DC connectors are securely connected.
8. Close any unused terminals on the string cable harnesses of the DC subdistribution with protective caps of the SUNCLIX plug-in system for DC connectors. This will seal the DC connectors.
9. Fasten the string cables to the external cable support rail.
Operating ManualSSMUXX15-BE-en-1044
SMA Solar Technology AG

7 Commissioning the DC Subdistribution

7 Commissioning the DC Subdistribution
The commissioning report of the inverter must be completed during commissioning.
Requirements:
☐ The DC load-break switch must be switched off. ☐ The DC main cables must be connected to the inverter or DC main distribution box and
disconnected from voltage sources.
☐ There is no reverse voltage from the inverter. ☐ Voltage supply to the DC subdistribution must be present. ☐ All connections must have been executed in accordance with this manual (see Section6,
page25).
☐ The correct polarity of all connections must be ensured and documented. ☐ The floor around the DC subdistribution must be firm and freely accessible.
Procedure:
1. Complete the commissioning report
2. Switch the DC subdistribution on (see Section8.3, page47).
Operating Manual 45SSMUXX15-BE-en-10

8 Disconnecting and Reconnecting

SMA Solar Technology AG
8 Disconnecting and Reconnecting

8.1 Safety When Disconnecting and Reconnecting Voltage Sources

Danger to life from electric shock due to live voltage
High voltages are present in the live components of the DC subdistribution. Touching live components results in death or serious injury due to electric shock.
• Wear suitable personal protective equipment for all work on the product.
• Do not touch any live components.
• Observe all warning messages on the product and in the documentation.
• Observe all safety information issued by the module manufacturer.
• Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
Danger to life from electric shock if the DC load-break switch is damaged
Switching the DC load-break switch at temperatures belowthe specified threshold may damage the DC load-break switch. The threshold is: ‒25°C. In this case, reliable disconnection can no longer be guaranteed.
If the DC load-break switch is switched in spite of visible damage, again the reliable disconnection function cannot be guaranteed.
High voltages are present in components that are not properly disconnected. Touching live components can result in death or serious injury due to electric shock.
• Do not switch the DC load-break switch at temperatures below the specified threshold. The threshold is: ‒25°C.
• Do not switch the DC load-break switch if it is visibly damaged.
Risk of burns due to hot inline fuse connectors
During operation, the temperature of the inline fuse connectors can reach up to 90°C. Touching the inline fuse connectors can result in burns.
• Only touch the inline fuse connectors wearing suitable personal protective equipment.
• Position hot, removed inline fuse connectors in such a way that they cannot be touched inadvertently.
• Mount the inline fuse connectors in such a way that air can circulate around them. Cooling the inline fuse connectors by the ambient air is absolutely necessary.
• Mount the inline fuse connectors in such a way that they cannot be touched inadvertently. Ensure that air circulation around the inline fuse connectors is not prevented.
Operating ManualSSMUXX15-BE-en-1046
SMA Solar Technology AG
8 Disconnecting and Reconnecting

8.2 Disconnecting the DC Subdistribution

1. Disconnect the inverter DC side from voltage sources and secure against inadvertent reconnection (see inverter manual).
2. If available, disconnect the external supply voltage of the DC subdistribution (see manual of the inverter or manual of the external voltage source).
3. Disconnect all DC subdistributions that are connected in parallel in the DC connection area and secure against inadvertent reconnection (see manual of the respective DC subdistribution). How to disconnect the DC subdistribution specified in this manual is described in the following steps.
4. Open the door of the DC subdistribution.
5. Switch the DC load-break switch off by turning the rotary handle on the DC load-break switch to 0 (OFF, green zone). This disconnects the PV array connected to the DC subdistribution from the inverter.
☑ The arrow on the rotary handle is pointing to 0 (OFF, green zone). The handle is in a
horizontal position.
6. Secure the DC load-break switch against reconnection. You can do this by attaching a padlock (diameter: max. 6mm) to the red inner section of the handle. You can push the red inner section out from below.
7. Ensure that the string inputs are load-free.
8. Release and remove all DC connectors. To do this, insert a regular or angled screwdriver (blade width: 3.5mm) into one of the slide slots and pull the DC connectors straight out. Do not pull on the cable.
9. Ensure that no voltage is present in the DC subdistribution. Tip: Use the voltage test points in the protective cover to measure the voltage in the DC subdistribution.
10. If the work can be carried out with the door of the DC subdistribution closed, close the door.
11. If the work to be carried out requires the door of the DC subdistribution to be open, secure the door so that it cannot slam shut.

8.3 Switching the DC Subdistribution Back On

1. Open the door of the DC subdistribution.
2. Ensure that the DC load-break switch in the DC subdistribution is switched off and secured against reconnection.
Operating Manual 47SSMUXX15-BE-en-10
8 Disconnecting and Reconnecting
SMA Solar Technology AG
3. Ensure that there is no ground fault in the PV array (see service manual at www.SMA­Solar.com).
4. Remount the protective covers on the DC subdistribution (see Section12.2, page63).
5. Connect all the DC connectors to the DC subdistribution.
6. If an anti-reconnection lock has been installed on the rotary handle of the DC load-break switch, remove the lock.
7. Switch the DC load-break switch on by turning the rotary handle to I (ON, red zone).
☑ The arrow on the rotary handle is pointing to I (ON, red zone). The handle is now in a
vertical position.
8. Close the door of the DC subdistribution.
9. Switch all other DC subdistributions back on (see DC subdistribution manual).
10. Switch the inverter back on (see inverter manual).
11. If available, reconnect the external supply voltage of the DC subdistribution (see manual of the inverter or manual of the external voltage source).
Operating ManualSSMUXX15-BE-en-1048
SMA Solar Technology AG
9 Troubleshooting

9.1 LED States

9.1.1 Status LEDs of the SMAString-Monitor
An overview of the LEDs can be found in Section4.7, page20.
LED Status Cause and corrective measure
UPD (yellow) Off* No update in progress at present.
flashing Update in progress at present.
ERR (red) On The electronic assembly is defective.
Corrective measures:
• Contact the Service (see Section15, page74).
Off Normal operation
AL (green) Off* The firmware is faulty.
Corrective measures:
• Update the firmware of the SMAString-Monitor (see inverter manual).
On The firmware is faulty.
Corrective measures:
• Update the firmware of the SMAString-Monitor (see inverter manual).
flashing The firmware is OK.
PWR (green) Off Supply voltage is too low or too high.
Corrective measures:
• Make sure that the supply voltage to the DC subdistribution is OK.
– If you are using the power supply assembly
for the external power supply (available as an accessory), ensure that the external 230V supply voltage is correctly connected (see manual "Power Supply Assembly for External Power Supply of SMAString-Monitors").
– Ensure that the supply voltage of the DC
subdistribution from the PV field is correctly connected.
On The supply voltage is OK.

9 Troubleshooting

AC
Operating Manual 49SSMUXX15-BE-en-10
9 Troubleshooting
SMA Solar Technology AG
LED Status Cause and corrective measure
COM (yellow) Off* At present no data exchange in progress.
On At present data exchange in progress. flashing At present no data exchange in progress.
* If the LED ERR is on, an error has occurred.

9.1.2 LEDs of the Network Connection

LED Status Cause and corrective measure
LK/ACT (green) Off No network connection established.
The DC subdistribution is not connected to the volt­age supply.
Corrective measures:
• Connect the DC subdistribution to the voltage supply.
No network connection established. The network cable is not properly connected to the
DC subdistribution or other devices in the communica­tion bus.
Corrective measures:
• Ensure that the network cables are correctly connected to the DC subdistribution (see Section6.4, page36).
• Ensure that the network cables are correctly connected to the other devices in the communication bus.
No network connection established. One or more network components, network cables or
connectors are defective or damaged.
Corrective measures:
• Replace the defective or damaged network components, network cables or connectors.
on Network connection established. flashing Network connection established.
Data is being sent or received.
SPEED (yellow) Off Network connection established.
The data transfer rate is up to 10Mbit/s.
on Network connection established.
The data transfer rate is up to 100Mbit/s.
Operating ManualSSMUXX15-BE-en-1050
SMA Solar Technology AG
9 Troubleshooting

9.2 Performing an Update

SMAString-Monitor updates are carried out via the SMA inverter (see inverter manual).
Operating Manual 51SSMUXX15-BE-en-10

10 Maintenance

SMA Solar Technology AG
10 Maintenance

10.1 Safety during Maintenance

Danger to life from electric shock due to live voltage
High voltages are present in the live components of the product. Touching live components results in death or serious injury due to electric shock.
• Wear suitable personal protective equipment for all work on the product.
• Do not touch any live components.
• Unless live voltage is absolutely necessary, always disconnect the product from voltage sources before performing any work (see Section8 "Disconnecting and Reconnecting", page46).
Risk of burns due to hot components
Some components of the product can get very hot during operation. Touching these components can cause burns.
• Observe the warnings on all components.
• During operation, do not touch any components marked with such warnings.
• Wear suitable personal protective equipment for all work on the product.
Property damage due to dust intrusion and moisture penetration
Dust or moisture intrusion can damage the product and impair its functionality.
• Do not open the enclosure during rainfall or when humidity exceeds the specified threshold. The threshold for humidity is: 95 %.
• Only perform maintenance work when the environment is dry and free of dust.
• Operation of the product is only permitted when it is closed.
• If the installation or commissioning process is interrupted, mount all panels.
• Close and lock the enclosure.
• The product must always be closed for storage.
• Store the product in a dry and covered location.
• Temperature at the storage location must be in the specified range. The temperature range is: ‒40°Cto+70°C.
Operating ManualSSMUXX15-BE-en-1052
SMA Solar Technology AG
Damage to electronic components due to electrostatic discharge
Electrostatic discharge can damage or destroy electronic components.
• Observe the ESD safety regulations when working on the product.
• Wear suitable personal protective equipment for all work on the product.
• Discharge electrostatic charge by touching grounded elements. Only then is it safe to touch electronic components.
10 Maintenance

10.2 Maintenance Schedule and Consumables

10.2.1 Notes on Maintenance Work

Adverse ambient conditions reduce maintenance intervals
Location and ambient conditions influence the maintenance intervals. Note that cleaning and corrosion protection may be required more frequently depending on the conditions at the installation site.
• If the DC subdistribution is subject to adverse ambient conditions, it is recommended to shorten the maintenance intervals.
• SMA recommends an optical inspection every six months to determine the maintenance requirements.
Consumables and maintenance materials
Only those consumables and maintenance materials not normally included in the standard equipment of an electrically qualified person are listed. It is taken for granted that standard tools and materials such as torque wrenches, one-contact voltage testers and wrenches will be available for all maintenance operations.
Spare parts
Spare parts can be identified via the reference designation and the circuit diagram. The spare­parts list includes the article numbers of each spare part. For information on a specific article number, contact us (see Section15 "Contact", page74).

10.2.2 Maintenance Work Every 24 Months

Required maintenance materials and tools:
☐ Talcum, petroleum jelly or wax for maintaining the seals ☐ Abrasive cloth ☐ Degreaser ☐ A surge arrester testing device approved by the surge arrester manufacturer
Maintenance with DC voltage present
Task See
Checking the DC load-break switch Section10.3.1, page54
Operating Manual 53SSMUXX15-BE-en-10
10 Maintenance
Maintenance under voltage-free conditions
Task See
Checking the protective covers Section10.3.2, page55 Performing the visual inspection Section10.3.3, page55 Checking the condensate drain Section10.3.4, page56 Checking the vent plug Section10.3.5, page56 Checking the seals Section10.3.6, page56 Checking the labels Section10.3.7, page57 Checking the LEDs Section10.3.8, page58 Checking the bolted, clamp and plug connections Section10.3.9, page58 Checking the inline fuse connectors* Installation manual of the inline fuse con-
nector
Checking the ground connection Section10.3.11, page59
* available as an accessory
SMA Solar Technology AG

10.3 Maintenance Work

10.3.1 Checking the DC Load-Break Switch

1. Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
2. Check whether the DC load-break switch has disconnected the contacts as follows:
• If you are using the alarm contact set (see Section14, page72), check on the user interface of the inverter whether the switching state of the DC load-break switch is displayed correctly.
• If no alarm contact set is in use, check in the inspection window of the DC load-break switch whether the switch is open.
or
Use a continuity tester to perform a continuity check.
Operating ManualSSMUXX15-BE-en-1054
SMA Solar Technology AG
10 Maintenance

10.3.2 Checking the Protective Covers

Danger to life from electric shock due to live voltage
High voltages are present in the live components of the DC subdistribution. Touching live components results in death or serious injury due to electric shock.
• Disconnect the inverter from all voltage sources on the DC side (see the inverter manual).
• Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
• Disconnect all DC sub-distributions that are connected in parallel in the DC connection area (see the manual of the respective DC sub-distribution).
Procedure:
1. Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
2. Check whether the covers are damaged. Position of the covers Section4.3, page15. Replace the covers if they are damaged. If the covers are loose, fasten the screws tightly.
3. Check whether the covers are firmly attached. If not, fasten the screws of the covers tightly.

10.3.3 Performing the Visual Inspection

Danger to life from electric shock due to live voltage
High voltages are present in the live components of the DC subdistribution. Touching live components results in death or serious injury due to electric shock.
• Disconnect the inverter from all voltage sources on the DC side (see the inverter manual).
• Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
• Disconnect all DC sub-distributions that are connected in parallel in the DC connection area (see the manual of the respective DC sub-distribution).
Procedure:
1. Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
2. On the DC subdistribution and any used string cable inline fuse connectors, check whether there are any foreign materials or objects that are flammable or that could otherwise endanger operational safety. Remove any such materials or objects.
3. Check whether there are any objects in the installation compartment of the DC subdistribution. Remove any such objects from the installation compartment.
Operating Manual 55SSMUXX15-BE-en-10
10 Maintenance
4. Check the enclosure of the DC subdistribution for defects or leaks, e.g. soiled or damaged areas. Remove any soiling with a non-abrasive damp cloth. If damage is detected which impairs the function of the DC subdistribution or causes the enclosure to leak, contact Service (see Section15, page74).
5. Check whether the door hinges of the DC subdistribution are soiled. Remove any soiling with a non-abrasive damp cloth.
SMA Solar Technology AG

10.3.4 Checking the Condensate Drain

Procedure:
• Check whether there is any internal or external clogging of the condensate drain (see Section6.1, page25) in the connection area of the DC subdistribution. If so, unscrew the condensate drain, rinse out with water and refasten to the enclosure.

10.3.5 Checking the Vent Plug

Danger to life from electric shock due to live voltage
High voltages are present in the live components of the DC subdistribution. Touching live components results in death or serious injury due to electric shock.
• Disconnect the inverter from all voltage sources on the DC side (see the inverter manual).
• Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
• Disconnect all DC sub-distributions that are connected in parallel in the DC connection area (see the manual of the respective DC sub-distribution).
Procedure:
1. Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
2. Remove protective covers in the DC subdistribution (see Section12.2, page63).
3. Check whether the vent plug (see Section4.2, page14) on the enclosure of the DC subdistribution is soiled on the outside or inside. Remove any soiling with a non-abrasive damp cloth.

10.3.6 Checking the Seals

Required maintenance material (not included in the scope of delivery):
☐ A suitable water-free, heat-resistant lubricant ☐ Talcum, petroleum jelly or wax for maintaining the seals
Operating ManualSSMUXX15-BE-en-1056
LL+
LL+
A B C
F
E
D
SMA Solar Technology AG
10 Maintenance
Procedure:
1. Check whether the seals around the edges of the DC subdistribution door show any damage. If seals are damaged, contact Service (see Section15 "Contact", page74).
2. Apply talcum, petroleum jelly or wax to seals. This will prevent frost damage.
3. Check whether the seals of the cable glands in the connection area of the DC subdistribution show any damage. If seals are damaged, contact Service (see Section15, page74).

10.3.7 Checking the Labels

Position of the labels
Figure 15: Position of the labels on the front panel, on the protective covers and on the inside of the door of the SMAString-Monitor
Position SMA order number Designation
A 86-051489 Symbol "Dangerous voltage" B de/en/fr: 86-106900.01* C Risk of burns due to hot components
es/en/pt: 86-107000.01* it/en/ro: 86-107100.01*
D Danger to life due to electric shock
Operating Manual 57SSMUXX15-BE-en-10
el/en/ko: 86-107200.01*
Danger to life due to electric shock
10 Maintenance
Position SMA order number Designation
E 86-104500.03 Reference designation label F 86-116100.01 Symbol "Hot components"
* Includes the three given labels in the appropriate languages.
Procedure:
1. Check whether any warning message or label is damaged or missing.
2. Replace any warning messages and labels which are missing or illegible. If necessary, you can order the labels using the order number stated above. Contact the Service (see Section15, page74).
SMA Solar Technology AG

10.3.8 Checking the LEDs

Procedure:
• Check the status of the LEDs (see Section9.1, page49) and eliminate the errors.

10.3.9 Checking the Bolted, Clamp and Plug Connections

Danger to life from electric shock due to live voltage
High voltages are present in the live components of the DC subdistribution. Touching live components results in death or serious injury due to electric shock.
• Disconnect the inverter from all voltage sources on the DC side (see the inverter manual).
• Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
• Disconnect all DC sub-distributions that are connected in parallel in the DC connection area (see the manual of the respective DC sub-distribution).
Procedure:
1. Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
2. Remove protective covers in the DC subdistribution (see Section12.2, page63).
3. Ensure that the bolted connections of the power cabling are securely in place.
4. Check whether there is any discoloration or change in appearance of the bolted or clamp connections at the insulation or terminals. If bolted or clamp connections show any such discoloration or change, replace them.
5. Ensure that all connectors are intact and securely in place.
Operating ManualSSMUXX15-BE-en-1058
SMA Solar Technology AG
10 Maintenance

10.3.10 Checking the Inline Fuse Connectors

Danger to life due to electric arc
An electric arc may occur when plugging or removing the DC connectors or the inline fuse connectors under load and in case of a reverse-poled connection of the DC connectors. Electric arcs can result in death or serious injury.
• Ensure the correct polarity of the strings before connection.
• Plug or remove DC connectors and inline fuse connectors only under load-free conditions.
• Disconnect the DC sub-distribution (see the DC sub-distribution manual).
• Wear suitable personal protective equipment.
The inline fuse connectors are available as accessories (see Section14, page72). A description of how to check the inline fuse connectors can be found in the installation manual
"IFCON Inline Fuse Connector Set16".

10.3.11 Checking the Ground Connection

Danger to life from electric shock due to live voltage
High voltages are present in the live components of the DC subdistribution. Touching live components results in death or serious injury due to electric shock.
• Disconnect the inverter from all voltage sources on the DC side (see the inverter manual).
• Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
• Disconnect all DC sub-distributions that are connected in parallel in the DC connection area (see the manual of the respective DC sub-distribution).
Procedure:
1. Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
2. Remove protective covers in the DC subdistribution (see Section12.2, page63).
3. Ensure that the ground connection and the contact resistance to the ground potential are correct.

10.4 Completing Maintenance Work

1. Remount the protective covers in the DC subdistribution (see Section12.2, page63).
2. Switch the DC subdistribution back on (see Section8.3, page47).
Operating Manual 59SSMUXX15-BE-en-10

11 Decommissioning

SMA Solar Technology AG
11 Decommissioning

11.1 Decommissioning the DC Subdistribution

Danger to life from electric shock due to live voltage
High voltages are present in the live components of the DC subdistribution. Touching live components results in death or serious injury due to electric shock.
• Disconnect the inverter from all voltage sources on the DC side (see the inverter manual).
• Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
• Disconnect all DC sub-distributions that are connected in parallel in the DC connection area (see the manual of the respective DC sub-distribution).
Procedure:
1. Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
2. Remove protective covers in the DC subdistribution (see Section12.2, page63).
3. Remove all cables leading into the DC subdistribution.
4. Close the enclosure openings for the cables and seal with suitable material (e.g., filler plugs).
5. Dismantle the DC subdistribution as follows:
• Disassemble the DC subdistribution from the pole (see installation manual "Pole Mounting Set for SMAString-Monitors").
or
• Disassemble the DC subdistribution from the wall or substructure of the PV modules (see Section11.2, page60).
6. Remount the protective covers on the DC subdistribution (see Section12.2, page63).
7. Close the DC subdistribution.

11.2 Disassembling the DC Subdistribution from the Wall

Danger to life from electric shock due to live voltage
High voltages are present in the live components of the DC subdistribution. Touching live components results in death or serious injury due to electric shock.
• Disconnect the inverter from all voltage sources on the DC side (see the inverter manual).
• Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
• Disconnect all DC sub-distributions that are connected in parallel in the DC connection area (see the manual of the respective DC sub-distribution).
Operating ManualSSMUXX15-BE-en-1060
SMA Solar Technology AG
Risk of injury when lifting the DC sub-distribution, or if it is dropped
There is risk of injury if the DC sub-distribution is lifted incorrectly or dropped while being transported or when attaching it to or removing it from the wall mounting bracket. Weight of the DC sub-distribution without installed accessories: 35 kg.
• Two persons are required for mounting and disassembling the DC sub-distribution.
• Carefully lift and transport the DC sub-distribution.
Procedure:
1. Decommission the DC subdistribution (see Section11.1, page60).
2. Remove the screws from the mounting brackets of the DC subdistribution. Take care not to drop the DC subdistribution.
3. Remove the DC subdistribution from the wall or substructure.
11 Decommissioning

11.3 Packing the DC Subdistribution

• If available, use the original packaging of the product.
• If the original packaging is not available, use a cardboard box suitable for the weight and size of the product.

11.4 Storing the DC Subdistribution

• Store the product in a dry and covered location.
• Temperature at the storage location must be in the specified range. The temperature range is: ‒40°Cto+70°C.
• Always store the product in a horizontal position with the door facing upwards.
• The product must always be closed for storage.

11.5 Disposing of the DC Subdistribution

Dispose of the product at the end of its service life in accordance with the electronic waste disposal regulations that currently apply at your installation site.
Operating Manual 61SSMUXX15-BE-en-10

12 Periodic Actions

SMA Solar Technology AG
12 Periodic Actions

12.1 Inserting the Cables

12.1.1 Leading Cables through Enclosure Opening with Membrane

Property damage due to dust intrusion and moisture penetration
Excessively large or redundant holes in the membranes of the cable feed-through plate can cause dust or moisture to penetrate the DC subdistribution.
• Only pierce as many holes in the membrane as you need for the cables.
• The hole in the membrane must be smaller than the diameter of the cable to be led through.
Procedure:
1. Pierce the appropriate membrane.
2. Insert the cable through the membrane.
3. Cut the cable to length.

12.1.2 Leading Cables through Enclosure Opening with Cable Gland

Seal insert for cable glands for DC main cables:
Cable glands for the DC main cables are each supplied with two seal inserts for different cable sizes.
Cable diameter Seal insert
24.0 mm to 38.5 mm Use mounted seal insert.
17.0 mm to 31.0 mm Replace seal insert for the seal insert supplied in the scope of delivery.
Procedure:
1. Release cable gland.
2. Remove the filler plug from the cable gland.
3. When inserting the DC main cables, replace the seal insert with the insert in the scope of delivery if necessary (see above table).
4. Lead the cable through the swivel nut of the cable gland. Ensure that the thread of the swivel nut is facing upwards.
5. Lead the cable through the seal insert.
6. Insert the seal insert into the cable gland together with the cable.
7. Cut the cable to length.
8. Tighten the cable gland with the appropriate torque:
Operating ManualSSMUXX15-BE-en-1062
SMA Solar Technology AG
12 Periodic Actions
• Cable gland for DC main cable: 7.5Nm
• Cable gland for external voltage supply: 4.0Nm
• Cable gland for external functional grounding of the AC Piggy-Back: 2.5Nm

12.2 Disassembling and Mounting the Protective Covers

Figure 16: Position of the protective covers
Position Designation
A Top protective cover B Bottom protective cover
Danger to life from electric shock due to live voltage
High voltages are present in the live components of the DC subdistribution. Touching live components results in death or serious injury due to electric shock.
• Disconnect the inverter from all voltage sources on the DC side (see the inverter manual).
• Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
• Disconnect all DC sub-distributions that are connected in parallel in the DC connection area (see the manual of the respective DC sub-distribution).
Operating Manual 63SSMUXX15-BE-en-10
12 Periodic Actions
SMA Solar Technology AG
Disassembling the protective covers
1. Disconnect the DC subdistribution from voltage sources (see Section8.2, page47)
2. To disassemble the bottom protective cover:
• Release the five knurled nuts on the bottom protective cover and retain them for later use.
• Pull bottom protective cover towards you until it comes off the spacer bolts.
3. To disassemble the top protective cover:
• Release the five knurled nuts on the top protective cover and retain them for later use.
• Pull top protective cover towards you until it comes off the spacer bolts and lift off.
Mounting the protective covers
1. To mount the top protective cover:
• Slide the top protective cover from above underneath the DC load-break switch and position on the spacer bolts.
• Fasten the five knurled nuts to the spacer bolts.
2. To mount the bottom protective cover:
• Position the bottom protective cover on the spacer bolts.
• Fasten the five knurled nuts to the spacer bolts.
Operating ManualSSMUXX15-BE-en-1064
SMA Solar Technology AG

13 Technical Data

13 Technical Data
Enclosure
Outdoor installation Shaded Material Glass-fiber reinforced plastic Combustion properties Self-extinguishing, halogen-free IP degree of protection in accordance with
IEC60529 IK degree of protection in accordance with
IEC62262 Protection class in accordance with IEC 60529 II Pollution degree in accordance with
IEC61010-1 Color RAL7035 UV resistance in accordance with IEC 61439-1 Yes Wall mounting Yes Pole mounting* Yes Lock cylinder Double-bit key for switch cabinet Cable support rail** Yes
* available as an accessory (see Section14, page72)
** to be provided by the customer
Mechanical Data
Enclosure width 600mm Enclosure with including vent plug 630mm Enclosure height including wall bracket lugs 850mm Enclosure height including string cable harness 1,055mm Enclosure depth 300mm Enclosure depth including wall bracket lugs 320mm Enclosure depth including wall bracket lugs and
pole mounting bracket* Maximum weight** 34kg
IP54
IK10
2
385mm
Operating Manual 65SSMUXX15-BE-en-10
13 Technical Data
SMA Solar Technology AG
Mechanical Data
Weight of pole mounting bracket* 2.1kg Minimum clearance between enclosure and
800mm floor if inline fuse connectors are installed under­neath the SMAString-Monitor
* available as an accessory (see Section14, page72)
** depending on the number of string inputs of the SMAString-Monitor, without accessories
Electrical Data
PV array Negatively grounded/positively grounded/
insulated
Rated voltage At installation altitudes over 2,000m, an addi-
tional reduction factor must be taken into ac­count.
2,001m to 3,000m reduction by 1.0% per 100m
3,001m to 4,000m reduction by 1.2% per
1,500V
DC
100m Rated current (I Rated current (I Rated current per measuring input* 17.5A
) at 50°C* 315A
DCmax
) at above 50°C* Reduction by 2.5% per K
DCmax
DC
DC
Fuse characteristics gPV Number of string inputs per potential 16 / 24 / 32 DC supply voltage from PV array +200 VDC to +1,500 V
DC
External AC supply voltage** 230VAC ±20% DC load-break switch 400 A
DC
DC load-break switch - actuation under load Max. 200 switching cycles DC load-break switch - actuation
Max. 100 switching cycles
at ‒40°C Surge arrester DC Type 2 (monitored)
I
= 20kA
nom
I
= 40kA
max
Overvoltage category II
* Maximum continuous operating current up to the specified ambient temperature, taking a maximum
irradiation up to 1,200W/m2 into account (hourly average value of the horizontal global radiation). In case the irradiation is higher, the rated current must be adapted linearly downwards.
** available as an accessory (see Section14, page72)
Current Measurement
Number of measuring channels 16 / 24 / 32
Operating ManualSSMUXX15-BE-en-1066
SMA Solar Technology AG
13 Technical Data
Current Measurement
Current measurement range −2.5 A to +17.5 A Maximum error at +25°C* ±0.5% Maximum error in temperature range* ±1.0%
* based on the end value of the current measurement range
Voltage Measurement
Number of measuring channels 1 Voltage measurement range +250 VDC to +1,500 V
DC
Maximum error at +25°C* ±0.5% Maximum error in temperature range* ±1.0%
* based on the current measurement range end value
Measurement Internal Temperature SMAString-Monitor
Temperature measurement range −40°C to +100°C Accuracy ±2% of measuring range end value
DC Main Connection to Busbar
Connection via busbar Ring terminal lugs for M12 screw Maximum conductor cross-section 400mm
2
Suitable connection material Copper/aluminum* Number of cables per potential 1 / 2 Cable gland M50 Sealing range of cable glands** 17.0mm to 38.5mm
* with suitable terminal lug (see Section6.3.3, page29)
** Tightness of seal must be assured using the mounted seal insert or the size-reducing seal insert supplied
DC Main Connection to Box Terminals*
Type of terminal V-Box terminal Maximum conductor cross-section 300mm
2
Suitable connection material Copper/aluminum Number of cables per potential 1 / 2 Cable gland M50 Sealing range of cable gland** 17.0mm to 38.5mm
* available as an accessory (see Section14, page72)
** Tightness of seal must be assured using the mounted seal insert or the size-reducing seal insert supplied
Operating Manual 67SSMUXX15-BE-en-10
13 Technical Data
SMA Solar Technology AG
Connecting the String Cable to the DC Connector*
Cable type PV 1-F Conductor cross-section at 6mm2 DC connector 2.5mm2 to6.0mm
2
Cable diameter at 6mm2 DC connector 5mm to 8mm Conductor cross-section at 16mm2 DC connec-
6mm2to16mm
2
tor Cable diameter at 16mm2 DC connector 5.5mm to 10.0mm
* available as an accessory (see Section14, page72)
Connection Functional Grounding to DC Surge Arrester
Terminal Connecting terminal plate with screw connection
for grounding conductor
Conductor cross-section for surge arrester type 2 25mm2to35mm
2
Cable gland Multiple feed-through Sealing range of cable gland 5.0mm to 10.2mm Recommended cable type NYY-O
Connection Functional Grounding to Electronic Assembly
Terminal Spring-cage terminal with actuation lever on the
electronic assembly
Conductor cross-section for surge arrester type 2 6mm
2
Cable gland Multiple feed-through Sealing range of cable gland 5.0mm to 10.2mm Recommended cable type NYY-O
Interfaces for Temperature Measurement
Number (module/ambient temperature) 2 Plug-in temperature sensor PT100 and PT1000 with two-, three- and four-
wire measurement Measurement range −40°C to +100°C Maximum error at +25°C* ±0.5% Maximum error in temperature range* ±2.0% Terminal Spring-cage terminal with actuation lever on the
electronic assembly
Conductor cross-section 0.08mm2to1.00mm
2
Operating ManualSSMUXX15-BE-en-1068
SMA Solar Technology AG
13 Technical Data
Interfaces for Temperature Measurement
Cable gland Multiple feed-through Sealing range of cable gland 3.2mm to 6.5mm
* based on the measurement range end value (with four-wire measurement)
Digital Input (Customer)
Quantity 1 Supply voltage 24 VDC ±20% Maximum output current (for sensors) 150mA Switching threshold, low level V Switching threshold high level V Nominal input voltage 24V
LMAX
HMIN
3V
15V
DC
Nominal input current 5mA Terminal Spring-cage terminal with actuation lever on the
electronic assembly
Conductor cross-section 0.08mm2to1.00mm
2
Maximum cable length 30m Cable gland Multiple feed-through Sealing range of cable gland 3.2mm to 6.5mm
Digital Input for Alarm Contact* for DC Load-Break Switch
Quantity 1 Design Potential-free contact Nominal input voltage (typical) 24V
DC
Nominal input current (typical) 5mA Terminal Supplied preassembled cable with plug contact
* available as an accessory (see Section14, page72)
Analog Current Input
Quantity 1 Supply voltage 24 VDC ±20% Maximum output current (for sensors) 150mA Input measurement resistance 250Ω Current measurement range 4 mA to 20 mA Maximum error at +25°C* ±0.3%
Operating Manual 69SSMUXX15-BE-en-10
13 Technical Data
SMA Solar Technology AG
Analog Current Input
Maximum error in temperature range* ±2.0% Terminal Spring-cage terminal with actuation lever on the
electronic assembly Maximum cable length 30m Conductor cross-section 0.08mm2to1.00mm
2
Cable gland Multiple feed-through Sealing range of cable gland 3.2mmto6.5mm / 5.0mmto10.2mm
* based on the measuring range end value
Digital Output
Type Potential-free change-over contact Maximum switching power AC 250VAC / 2A Maximum switching power DC 24VDC / 2A
48VDC / 1A
Minimum electrical endurance when the maxi-
1,000,000 switching cycles mum switching voltage and maximum switching current are complied with
Terminal Spring-cage terminal with actuation lever on the
electronic assembly
Conductor cross-section 0.5mm2 to 6.0mm
2
Cable gland Multiple feed-through Sealing range of cable gland 3.2mmto6.5mm / 5.0mmto10.2mm
Data Transmission Copper Wire
Data interface Modbus (TCP) Local area network (LAN) Ethernet Connection without surge arrester LSA+ Connection with surge arrester* RJ45 Recommended cable type Cat5 cable with shielding S-UTP, F-UTP or higher Maximum cable length 100m Cable gland Multiple feed-through Sealing range of cable gland 3.2mmto6.5mm / 5.0mmto10.2mm
* available as an accessory (see Section14, page72)
Operating ManualSSMUXX15-BE-en-1070
SMA Solar Technology AG
13 Technical Data
Data Transmission Optical Fiber*
Data interface Modbus (TCP) Local area network (LAN) Ethernet Direct connection multimode optical fiber cable
SC coupling
to optical fiber Piggy-Back** Fiber type Multimode 50.0/125.0µm or 62.5/125.0µm Fiber grade OM1 or higher Connection multimode optical fiber cable to
Splicing/optical fiber pigtail SC multimode
splice box *** Cable gland Multiple feed-through Sealing range of cable gland 3.2mmto6.5mm / 5.0mmto10.2mm
* Accessory optical fiber Piggy-Back required OF Piggy-Back accessories required (see Section14, page72
)
** available as an accessory (see Section14, page72)
*** available as an accessory (see Section14, page72); optical fiber pigtail is not included in the
accessory scope of delivery
Ambient Conditions
Standard operating temperature range ‒40°C to +50°C Extended operating temperature range ‒40°C to +60°C Storage temperature ‒40°C to +70°C Relative humidity* 0% to 95% Maximum altitude above MSL 2,000m / 4,000 m (derating)
* condensation possible
Operating Manual 71SSMUXX15-BE-en-10

14 Accessories

SMA Solar Technology AG
14 Accessories
You will find the accessories for your product in the following overview. If required, these can be ordered from SMA Solar Technology AG or your distributor.
Designation Brief description SMA order number
Inline fuse connector set Inline fuse connector set consist-
ing of 16 PV inline fuse connec­tors
Y connector set (available soon)
Y connector set consisting of 16 Y connectors
PV connector set PV connector set consisting of
16 connectors for the field wiring
Optical fiber interface module for SMAString-Monitors
Optical fiber interface module with multimode SC coupling, type Piggy-Back for the SMAString-Monitor
Optical fiber splice box set for SMAString-Monitors
Optical fiber splice box set MM with two SC/SC Duplex patch cables as retrofit kit for the SMAString-Monitor
SSM-U pole mounting set Set for mounting the
SMAString-Monitor to a pole
See the Technical Information "IFCON Inline Fuse Connector Set16"
• YCON16SFMM (female/2male)
• YCON16SMFF (male/2female)
• PVCON16S06F11 (2.5mm2 to 6.0mm
2
1,100V (+))
• PVCON16S06M11 (2.5mm2 to 6.0mm
2
1,100V (‒))
• PVCON16S06F15 (2.5mm2 to 6.0mm
2
1,500V (+))
• PVCON16S06M15 (2.5mm2 to 6.0mm
2
1,500V (‒))
• PVCON16S16F15 (6.0mm2 to 16.0mm
2
1,500V (+))
• PVCON16S16M15 (6.0mm2 to 16.0mm
2
1,500V (‒))
SSM-U-FOPB
SSM-U-FOSB
SSM-U-PM
Operating ManualSSMUXX15-BE-en-1072
SMA Solar Technology AG
Designation Brief description SMA order number
Alarm Contact Kit for SMA String-Monitors
Alarm contact set 1NO (make contact) for the switch state indi-
SSM-U-AUXCONT
cator for the SMAString-Moni­tor
Ethernet overvoltage protection set for SMA String-Monitors
Overvoltage protection for the Ethernet communication of the
SSM-U-COMOVP
SMAString-Monitor
Overvoltage protection set for supply voltage 230 VAC for SMAString-Monitors
Overvoltage protection for ex­ternal 230VAC supply voltage of the SMAString-Monitor via
SSM-U-AUXPBOVP
the inverter
Power supply assembly for ex­ternal power supply of SMAString-Monitors
Assembly for external 230V supply voltage of the SMAString-Monitor via the in-
SSSM-U-AUXPB
AC
verter
V box terminal set for the SMAString-Monitors SSM-U
V box terminals with connection brackets
AFC-300
and SSMxx-21-BS
14 Accessories
Operating Manual 73SSMUXX15-BE-en-10

15 Contact

SMA Solar Technology AG
15 Contact
If you have technical problems with our products, please contact the SMAServiceLine. We need the following information in order to provide you with the necessary assistance:
• Device type
• Serial number
• Type and number of PV modules connected
• Type of communication
• Error number and error message
Australia SMA Australia Pty Ltd.
Sydney Toll free for Australia:
1800SMAAUS (1800762287)
International: +61294914200
Argentina Brasil Chile Perú
Danmark Deutschland Österreich Schweiz
SMA South America SPA Santiago +562 2820 2101
SMA Solar Technology AG Niestetal SMA Online Service Center:
www.SMA.de/Service Sunny Boy, Sunny Mini Central,
SunnyTripower: +495619522‑1499
Monitoring Systems (Kommunika­tionsprodukte): +495619522‑2499
Fuel Save Controller (PV-Diesel­Hybridsysteme): +495619522-3199
Sunny Island, Sunny Backup, Hy­dro Boy: +495619522-399
Sunny Central: +495619522-299
Belgien Belgique België Luxemburg Luxembourg Nederland
Česko Magyarország Polska România Slovensko
France SMA France S.A.S.
SMA Benelux BVBA/SPRL Mechelen +3215286 730
SMA Central & Eastern Europes.r.o.
Praha +420235010417
Lyon Sunny Boy, Sunny Mini Central,
Sunny Tripower : +33472090440
Monitoring Systems : +33472090441
Sunny Island : +33472090442
Sunny Central : +33472090443
Operating ManualSSMUXX15-BE-en-1074
5%6!78%
9:;*<+%,='3)>+%
/01,234
9:;
SMA Solar Technology AG
15 Contact
España Portugal
South Africa SMA Solar Technology South
Italia SMA Italia S.r.l.
SMA Ibérica Tecnología Solar, S.L.U.
Barcelona +34935635099
Africa Pty Ltd. Centurion (Pretoria) 08600SUNNY
(0860078669) International:
+27(12)6223000
Milano +39028934-7299
SMA Solar (Thailand) Co., Ltd.
+6626706999
SMA Middle East LLC
+9712234-6177
India SMA Solar India Pvt. Ltd.
Mumbai +912261713888
Ελλάδα Κύπρος Kıbrıs България
United King­dom
대한민국 SMA Technology Korea Co.,
Other countries International SMA Service Line
SMA Hellas AE Αθήνα +30 210 9856666
SMA Solar UK Ltd. Milton Keynes +441908304899
Ltd. 서울 +82-2-520-2666
Niestetal Toll free worldwide:
00800SMASERVICE (+8007627378423)
Operating Manual 75SSMUXX15-BE-en-10
SMA Solar Technology
www.SMA-Solar.com
Loading...