This manual describes the assembly, installation, commissioning and maintenance of the following
SMA inverters:
• Sunny Mini Central 6000TL (SMC 6000TL)
• Sunny Mini Central 7000TL (SMC 7000TL)
• Sunny Mini Central 8000TL (SMC 8000TL)
Store this manual where it can be accessed at all times.
1.2 Target Group
This manual is for qualified personnel.. The tasks described in this manual may only be performed by
qualified personnel.
1.3 Additional Information
You will find further information on special topics such as designing a line circuit breaker or the
description of the operating parameters in the download area at www.SMA.de/en.
Refer to the user manual for detailed information on operating the inverter.
Installation GuideSMC6-8TL-IEN1010407
Page 8
Notes on this ManualSMA Solar Technology AG
1.4 Symbols Used
The following types of safety precautions and general information are used in this manual:
DANGER!
"DANGER" indicates a hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING!
"WARNING" indicates a hazardous situation which, if not avoided, could result in death
or serious injury.
CAUTION!
"CAUTION" indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury!
NOTICE!
"NOTICE" indicates a situation that can result in property damage, if not avoided.
Information:
Information provides tips that are valuable for the optimal installation and operation of
your product.
☑This symbol indicates the result of an action.
8SMC6-8TL-IEN101040Installation Guide
Page 9
SMA Solar Technology AGSafety
2 Safety
2.1 Appropriate Usage
The Sunny Mini Central is a PV inverter, which converts the DC current of the PV generator to AC
current and feeds it into the public grid.
Operating Principle of a PV System with Sunny Mini Central
The Sunny Mini Central may only be operated with PV generators (modules and cabling) of
protection class II. Do not connect any sources of energy other than PV modules to the Sunny Mini
Central.
Capacitive Discharge Currents
PV modules with large capacities relative to ground, such as thin-film modules with cells on
a metallic substrate, are only to be implemented if their coupling capacity does not exceed
1400 nF.
During grid feeding, a discharge current flows from the cells to ground. The amount of
current depends on the manner in which the modules are installed (e.g. foil on metal roof)
and on the weather (rain, snow). This "normal" discharge current may not exceed 50 mA
due to the fact that the inverter would otherwise automatically disconnect from the grid as
a protective measure. For further information on this subject, see the technical information
"Capacitive Discharge Currents" in the download area at www.SMA.de/en.
Installation GuideSMC6-8TL-IEN1010409
Page 10
SafetySMA Solar Technology AG
When designing the PV system, ensure that the values comply with the permitted operating range of
all components at all times. The free design program "Sunny Design" (www.SMA.de/en/
SunnyDesign) will assist you. The manufacturer of the PV modules must have approved the modules
for use with this Sunny Mini Central unit. You must also ensure that all measures recommended by the
module manufacturer for long-term maintenance of the module properties are taken (see also
Technical Information "Module Technology", in the download area of www.SMA.de/en).
Do not use the inverter for purposes other than those described here. Alternative uses, modifications
to the inverter or the installation of components not expressly recommended or sold by SMA Solar
Technology AG void the warranty claims and operation permission.
Certified Countries
The Sunny Mini Central 6000TL / 7000TL / 8000TL (with according configuration) fulfill the
requirements specified in the following standards and directives (dated: March/2010):
• Kepco guide (02.2006) (only applies to SMC 8000TL-KR)
* Only possible when the phase voltage is 220 V.
** In the event of restrictions in certain regions, contact the SMA Serviceline
SMA Solar Technology AG can preset special grid parameters for other countries / installation
locations according to customer requests, after evaluation by SMA Solar Technology AG. You can
make later modifications yourself by changing software parameters with respective communication
products (e.g. Sunny Data Control or Sunny Explorer) (see section 5.7”Setting the Grid and Country
Parameters” (page45)). To change grid-relevant parameters, you need a personal access code - the
so-called SMA Grid Guard Code. The application form for the personal access code is located in the
download area at www.SMA.de/en, in the "Certificate" category for each inverter.
10SMC6-8TL-IEN101040Installation Guide
Page 11
SMA Solar Technology AGSafety
2.2 Safety Precautions
DANGER!
Danger to life due to high voltages in the inverter.
• All work on the inverter must be carried out by qualified personnel only.
• T he a ppl iance is not to b e us ed b y ch ildren o r pe rso ns w ith reduced physical, sensory
or mental capabilities, or lack of experience and knowledge, unless they have been
given supervision or instruction.
• Children should be supervised to ensure that they do not play with the appliance.
DANGER!
Danger of burn injuries due to hot enclosure parts.
• Do not touch enclosure during operation.
• Only touch the lid during operation.
NOTICE!
Foreign objects or water entering the inverter can damage the device!
Once the Electronic Solar Switch has been pulled out, the inverter only provides protection
rating IP21. The inverter is then no longer protected against water and foreign objects. In
order to keep the protection rating IP65 during temporary decommissioning, proceed as
follows:
• Unlock and disconnect all DC connectors.
• Open all DC connectors and remove the wires.
• Close all DC inputs with the corresponding DC connectors and the sealing plug
provided.
• Securely attach the Electronic Solar Switch again.
Grounding the PV Generator
Comply with the local requirem ents for groundi ng the modules an d the PV generator. SMA
Solar Technology AG recommends connecting the generator frame and other electricityconducting surfaces such that there is continuous conduction and to connect them to the
ground in order to reach maximum protection for property and persons.
Installation GuideSMC6-8TL-IEN10104011
Page 12
SafetySMA Solar Technology AG
2.3 Explanation of Symbols
This chapter contains an explanation of all symbols found on the inverter and type label.
2.3.1 Symbols on the Inverter
SymbolExplanation
Operation display.
Indicates the operation condition of the inverter.
Ground fault or varistor defective.
Read section 9.3”Red LED is Glowing Continuously” (page68).
Disturbance or fault
Read section 9”Failure Search” (page61).
Tap to switch on the display light and switch to the next display message.
Electronic Solar Switch (ESS) DC load disconnection unit
• When the Electronic Solar Switch is plugged in, the DC circuit is
closed.
• To interrupt the DC circuit and disconnect the inverter securely
under load, you have to first pull out the Electronic Solar Switch
and then remove all DC plug connectors , as described in section
7.2”Opening the Inverter” (page52).
12SMC6-8TL-IEN101040Installation Guide
Page 13
SMA Solar Technology AGSafety
2.3.2 Symbols on the Type Label
SymbolExplanation
Beware of dangerous electrical voltage.
The inverter operates at high voltages. All work on the inverter must be
carried out by qualified personnel only.
Beware of hot surface.
The inverter can become hot during operation. Avoid contact during
operation.
Observe all documentation that accompanies the inverter.
The inverter must not be disposed of with the household waste. For more
information on disposal, see section 10.4”Disposing of the Inverter”
(page73).
CE mark.
The inverter complies with the requirements of the applicable EC
guidelines.
The inverter is transformerless.
Direct Current (DC)
Alternating current (AC)
Protection rating IP65.
The inverter is protected against penetration by dust particles and water
jets from any angle.
RAL quality mark for solar products.
The inverter complies with the requirements of the German Institute for
Quality Assurance and Labeling.
Installation GuideSMC6-8TL-IEN10104013
Page 14
UnpackingSMA Solar Technology AG
3 Unpacking
3.1 Scope of delivery
Check the delivery for completeness and any visible external damage. Contact your dealer if anything
is damaged or missing.
ObjectQuantity Description
A1Sunny Mini Central
B1Air grills (right / left)
C1Wall mounting bracket
D1Electronic Solar Switch (ESS) DC load disconnection unit
E8DC plug connectors (4 x positive / 4 x negative)
F8Sealing plugs for DC plug connectors
G1Cable gland for AC connection:
H1Counter nut for cable gland at AC connection
I1Clamping clip for additional grounding
K2Tooth lock washers: 1 x for cover screws (replacement),
1 x for ground connection cable terminal
L2Cylinder head screws (M6x16): 1 x for lid (replacement),
1 x for ground connection cable terminal
M2Jumper (1x for fan test 1x for the cabling of the SMA Power Balancer)
N2Cylinder head screws (M6x8) for securing the inverter to the wall mounting
bracket
O1Silicone tube for insulating the SMA Power Balancer connection cable
P1Installation Guide
Q1User Manual
14SMC6-8TL-IEN101040Installation Guide
Page 15
SMA Solar Technology AGUnpacking
ObjectQuantity Description
R1Set of documents with explanations and certificates
S1Supplementary sheet with inverter factory settings
3.2 Identifying the Inverter
You can identify the inverter by the type label. The type label is on the right side of the enclosure.
The serial number (Serial no.) and the type (Type / Model) of the product, as well as device-specific
characteristics are specified on the type label.
Installation GuideSMC6-8TL-IEN10104015
Page 16
MountingSMA Solar Technology AG
4 Mounting
4.1 Safety
DANGER!
Danger to life due to fire or explosion!
Despite careful construction, electrical devices can cause fires.
• Do not mount the inverter on flammable construction materials.
• Do not mount the inverter in areas where highly flammable materials are stored.
• Do not mount the inverter in areas with a risk of explosion.
CAUTION!
Danger of burn injuries due to hot enclosure parts.
• Mount the inverter in such a way that it cannot be touched inadvertently.
CAUTION!
Risk of injury due to the heavy weight of the inverter.
• Take the inverter's weight of approx. 33 kg into account for mounting.
4.2 Selecting the Mounting Location
Consider the following points when selecting where to install:
• The installation method and mounting location must be suitable for the inverter's weight and
dimensions (see section 11”Technical Data” (page74)).
• Mount on a solid surface.
• The mounting location must at all times be clear and have safe access without the use of
additional aids such as scaffolding or lifting platforms. Any possible service actions are
otherwise limited.
• Vertical installation or tilted backwards by max. 45°.
• The connection area must point downward.
16SMC6-8TL-IEN101040Installation Guide
Page 17
SMA Solar Technology AGMounting
• Never install the device with a forward tilt.
• Do not install horizontally.
• Install at eye level to allow operating modes to be read at all times.
• The ambient temperature should be below 40 °C to ensure optimal operation.
• Do not expose the inverter to direct sunlight to avoid a power reduction due to excessive
heating.
• In living areas, do not mount the unit on plasterboard walls or similar in order to avoid audible
vibrations. The inverter can make noises when in use which may be perceived as a nuisance in
a living area.
• Observe the minimum clearances to walls, other
inverters, or objects as shown in the diagram in
or der to gu ara ntee suf fic ien t heat di ssi pat ion and to
have enough space for removing the Electronic
Solar Switch.
Multiple inverters installed in areas with high ambient temperatures
There must be sufficient clearance between the individual inverters to ensure the cooling air
from the adjacent inverter flows freely.
If necessary, increase the clearances and make sure there is enough ventilation to ensure
sufficient cooling of the inverters.
Installation GuideSMC6-8TL-IEN10104017
Page 18
MountingSMA Solar Technology AG
4.3 Mounting the Inverter with Wall Mounting Bracket
1. Mark the position of the drill holes using the wall mounting bracket and drill the holes. Use at
least 2 of the 6 holes, with one hole on the right and one on the left.
18SMC6-8TL-IEN101040Installation Guide
Page 19
SMA Solar Technology AGMounting
CAUTION!
Risk of injury due to the heavy weight of the inverter.
The inverter weights approx. 33 kg.
• Attach the wall mounting bracket with the corresponding mounting material
(depending on the surface).
• U se t he s ide handles (ab ove and bel ow)
or a steel rod (maximum diameter of
30 mm) for transport and mounting. The
rod must be pushed through the
enclosure openings.
2. Secure the wall mounting bracket to the wall using
appropriate screws and washers.
3. Using the mounting hole, attach the inverter to the
rear panel of the enclosure in the wall mounting
bracket.
Installation GuideSMC6-8TL-IEN10104019
Page 20
MountingSMA Solar Technology AG
4. Screw the inverter to the wall mounting bracket on
both sides using the screws (M6x8) provided.
Only tighten the screws hand-tight.
5. Check to ensure the inverter is firmly fastened.
6. Close the recessed grips with the air grills provided.
The air grills are marked "rechts/right" and "links/
left" on the interior for proper assignment.
The air grills prevent dirt and insects from entering
the device and, if necessary, can be reordered from
SMA Solar Technology AG (see section
13”Contact” (page85))
Optional Theft Protection
To protect the inverter against theft, the rear
panel can be secured to the wall at the bottom
using 2 single-use bolts.
The other two holes are spares.
20SMC6-8TL-IEN101040Installation Guide
Page 21
SMA Solar Technology AGElectrical Connection
5 Electrical Connection
NOTICE!
Electrostatic discharges can damage the inverter!
Internal components of the inverter can be irreparably damaged by static discharge.
• Ground yourself before touching a component.
5.1 Overview of the Connection Area
5.1.1 Exterior View
The following figure shows the assignment of the individual connection areas on the bottom of the
inverter.
ObjectDescription
ADC connectors for connecting the PV strings
BSocket for connecting the Electronic Solar Switch (ESS) DC load disconnection unit
CCable gland for optional communication via RS485 (PG16)
DCable gland for grid connection (AC) (12 mm … 25 mm)
ECable glands for SMA Power Balancer
Installation GuideSMC6-8TL-IEN10104021
Page 22
Electrical ConnectionSMA Solar Technology AG
5.1.2 Interior View
The following illustration shows the various components and connection areas of the open inverter.
ObjectDescription
AConnection area and sockets for communication (page 44)
BDisplay
CJumper for testing the fans (page 58)
DLEDs for displaying the operating modes (page 46)
EJumper for SMA Power Balancer (page 37)
22SMC6-8TL-IEN101040Installation Guide
Page 23
SMA Solar Technology AGElectrical Connection
ObjectDescription
FConnections terminals for SMA Power Balancer (page 37)
GFlat connector for grounding the cable shield when connecting the SMA Power
Balancer (page37)
HConnection terminals for mains cable (AC) (page 23)
ICable glands for the SMA Power Balancer (page 37)
KCable gland for grid connection (AC) (page 23)
LCable gland for communication (page 44)
MScrewing device of shield clamp for communication cable (page 44)
NDC connectors (page 30)
OConnection socket for “Electronic Solar Switch (ESS)” DC load disconnection unit
(page 30)
PMale connector for grounding the cable shield for communication (page 44)
QVaristors (page 69)
5.2 Connection to the public grid (AC)
5.2.1 Conditions for the AC Connection
Connection requirements of the utility operator
Always observe the connection requirements of your utility operator!
Cable Sizing
The conductor cross-section should be dimensioned in a way that output losses do not exceed 1 % at
nominal power. Use "Sunny Design" (www.SMA.de/en/SunnyDesign) for this.
The maximum cable lengths relative to the conductor cross-section are shown in the following table.
Conductor crosssection
10.0 mm²25 m22 m19 m
16.0 mm²41 m35 m31 m
Cut line losses in half
If three inverters with symmetrical feeding are combined to form a three-phase system, the
neutral conductor is not subjected to any load, and the line losses are halved. Thus, the
maximum possible cable length is doubled.
The conductor cross-sectional area required in individual cases depends on the following factors
among others:
• Ambient temperature,
•Routing method,
•UV resistance.
Installation GuideSMC6-8TL-IEN10104023
SMC 6000TLSMC 7000TLSMC 8000TL
Maximum cable length
Page 24
Electrical ConnectionSMA Solar Technology AG
Cable Requirements
PositionDescriptionValue
AExternal diameter12 mm … 25 mm
BConductor cross-section10 mm² … 16 mm²
CStrip insulationApprox. 16 mm
Load Disconnection Unit
You must install a separate line circuit breaker for each inverter in order to ensure that the inverter
can be securely disconnected under load. The maximum permissible rating is located in section
11”Technical Data” (page74).
De tai led inf orm ati on and ex amp les for the rat ing of a l ine cir cuit breaker can be found in the Technical
Information "Line Circuit Breaker" in the SMA Solar Technology AG download area at
www.SMA.de/en.
DANGER!
Danger to life due to fire.
When more than one inverter is connected to the same line circuit breaker, the protective
function of the line circuit breaker is no longer guaranteed. It can result in a cable fire or
the destruction of the inverter.
• Never connect several inverters to the same line circuit breaker.
• Comply with the maximum permissible fuse protection of the inverter when selecting
the circuit breaker.
24SMC6-8TL-IEN101040Installation Guide
Page 25
SMA Solar Technology AGElectrical Connection
DANGER!
Danger to life due to fire.
When a generator (inverter) and a consumer are connected to the same line circuit
breaker, the protective function of the line circuit breaker is no longer guaranteed. The
current from the inverter and the grid can accumulate to overcurrent, which is not detected
by the line circuit breaker.
• Never connect loads between the
inverter and the line circuit breaker
without protection.
• Always protect consumers separately.
NOTICE!
Damage to the inverter by using screw type fuse elements as a load
disconnection unit!
A screw type fuse element, e.g. D system (Diazed) or D0 system (Neozed) is not a load
disconnection unit, and thus may not be used as a load disconnection unit. A screw type
fuse element is only used as cable protection.
When disconnecting under load using a screw type fuse element, the inverter can be
damaged.
• U se o nly a lo ad disco nnec tin g sw itc h or a lin e ci rcu it b rea ker as a load disconnecting
unit.
Installation GuideSMC6-8TL-IEN10104025
Page 26
Electrical ConnectionSMA Solar Technology AG
5.2.2 Connecting the Inverter to the Public Grid (AC)
1. Check the grid voltage and compare with "V
The exact operating range of the inverter is specified in the operating parameters. The
corresponding document is available in the download area at www.SMA.de/en.
2. Switch off the line circuit breaker and secure it to prevent it from being reactivated.
3. Loosen all cover screws and remove the cover.
4. Remove tape on the AC enclosure opening
(see "D" on page 21).
5. Insert the AC screw clamp into the enclosure
opening from the outside and tighten it with the
counter nut from the inside.
6. Pull the cable through.
7. Connect L, N and the protective conductor (PE) to
the terminal blocks using a screwdriver in
accordance with the label.
To do this, the PE w ire must be 5 mm longe r th an the
L and N wires!
L and N must not be swapped.
" on the type label.
AC nom
8. Securely close the gland on the enclosure opening.
26SMC6-8TL-IEN101040Installation Guide
Page 27
SMA Solar Technology AGElectrical Connection
9. Secure the lid with all screws and the
corresponding lock washers.
Tighten the screws with 6 Nm torque in the order
shown on the right hand side. The toothing of the
tooth lock washers must face toward the lid.
The inverter packing list includes another spare
screw and tooth lock washer.
DANGER!
Danger to life due to live lid.
The grounding of the enclosure lid is ensured by the tooth lock washers.
• Fasten the tooth lock washers for all 6 screws with the toothing facing toward the lid.
DANGER!
Danger to life due to high voltages in the inverter.
• Do not switch on the line circuit breaker until the inverter is securely closed and the
PV generator has been connected.
☑ The inverter is now connected to the public grid (AC).
Installation GuideSMC6-8TL-IEN10104027
Page 28
Electrical ConnectionSMA Solar Technology AG
5.2.3 Additional Grounding of the Enclosure
If a second protective conductor connection is required in the country of installation, you can also
ground the inverter using a second protective conductor on the connection terminal on the enclosure.
Procedure
1. Insert the stripped grounding cable (D) under the
clamping clip (C) (max. cross-section 16 mm²).
2. Screw the clamping clip tight with screw (A) and
tooth lock washer (B).
The toothing of the tooth lock washer must face
toward the clamping clip.
☑ The inverter's enclosure is additionally grounded.
You can ground multiple inverters as shown in the diagram below:
28SMC6-8TL-IEN101040Installation Guide
Page 29
SMA Solar Technology AGElectrical Connection
5.3 Setting the Display Language
You can set the language of the display using the switches on the underside of the display assembly
inside the inverter.
Procedure
1. Open the inverter as described in section 7.2”Opening the Inverter” (page52).
2. Set the switches for the required language, as
shown below.
LanguageSwitch S2Switch S1
GermanBB
EnglishBA
FrenchAB
SpanishAA
For type SMC 6000TL-IT / 7000TL-IT / 8000TL-IT inverters, the following switch settings apply:
LanguageSwitch S2Switch S1
ItalianBA
EnglishAA
3. Close the inverter as described in section 7.3”Closing the Inverter” (page55).
☑ The display language is now set.
Installation GuideSMC6-8TL-IEN10104029
Page 30
Electrical ConnectionSMA Solar Technology AG
5.4 Connection of the PV Generator (DC)
5.4.1 Conditions for the DC Connection
Use of Adaptors
Adaptors (branch connectors) are not to be visible or freely accessible in the immediate
surroundings of the inverter.
• The DC current flow may not be interrupted via adaptors.
• Observe the procedure for disconnecting the inverter as described in section
7.2”Opening the Inverter” (page52).
• Requirements for the PV modules of the connected strings:
– Same type
–Same number
– Identical alignment
– Identical tilt
• The connecting cables from the PV modules must be fitted with plug connectors. You will find
the necessary DC plug connector for DC connection in the delivery.
• The following limiting values at the DC input of the inverter may not be exceeded:
InverterMaximum input voltageMaximum input current
SMC 6000TL700 V (DC)19.0 A (DC)
SMC 7000TL700 V (DC)22.0 A (DC)
SMC 8000TL700 V (DC)25.0 A (DC)
DANGER!
Risk of lethal electric shock or fire.
The maximum possible input current per string is limited by the plug connectors used. If the
plug connector is overloaded, an electric arc may occur and there is a fire risk.
• Ensure that the input current for each string does not exceed the maximum flow
current of the plug connectors used.
The residual current breaker
The inverter is equipped with an integrated universal current sensitive residual-current
monitoring unit. The inverter can automatically differ between real fault currents and
"normal" capacitive leakage currents.
If an external RCD or residual current breaker is strictly required, you must use a switch that
triggers at a failure current of 100 mA or higher.
30SMC6-8TL-IEN101040Installation Guide
Page 31
SMA Solar Technology AGElectrical Connection
5.4.2 Assembling the DC Plug Connectors
In order to connect to the inverter, all connecting cables of the PV modules must be equipped with the
DC plug connectors provided.
To assemble the DC plug connectors, proceed as detailed below. Ensure the plug connectors have
the correct polarity. The DC plug connectors are marked with "+" and " − ".
Cable requirements:
• Use a PV1-F cable.
Procedure
1. Insert the stripped cable into the plug connector as
far as it will go.
2. Pres s th e clampi ng c lip do wnward u nti l yo u hear an
audible click.
3. Ensure the cable is correctly in place.
ResultAction
☑ If the conductors are visible in the hollow
cavity of the clamping clip, the cable is in
the correct position.
Installation GuideSMC6-8TL-IEN10104031
• Proceed to step 4.
Page 32
Electrical ConnectionSMA Solar Technology AG
ResultAction
☑ If the conductor is not visible in the hollow
cavity of the clamp, the cable is not in the
• Loosen the clamping clip with the help of a
screwdriver.
correct position.
• Remove cable and start again from step 1.
4. Push the threaded joint to the thread and screw into place.
☑ The DC plug connectors are now assembled and can be connected to the inverters, as
described in section 5.4.4”Connecting the PV Generator (DC)” (page34).
32SMC6-8TL-IEN101040Installation Guide
Page 33
SMA Solar Technology AGElectrical Connection
5.4.3 Opening the DC Plug Connectors
1. Screw the threaded joint off.
2. To release the plug connector, slot a screw driver
into the side catch mechanism and lever out.
3. Carefully pull the DC plug connector apart.
4. Loosen the clamping clip with the help of a
screwdriver.
5. Remove the cable.
☑ The cable is now removed from the DC plug connector.
Installation GuideSMC6-8TL-IEN10104033
Page 34
Electrical ConnectionSMA Solar Technology AG
5.4.4 Connecting the PV Generator (DC)
DANGER!
Danger to life due to high voltages in the inverter.
• Before connecting the PV generator, ensure that the line circuit breaker is switched
off.
NOTICE!
Excessive voltages can destroy the measuring device.
• Only use measuring devices with a DC input voltage range of at least 700 V.
1. Disconnect the line circuit breaker and secure against re-connection.
2. Pull the Electronic Solar Switch downward, slightly
toward the wall.
3. Check the connection cables of the PV modules for
co rre ct pola rit y an d that th e ma ximum in put vo lta ge
of the inverter is not exceeded.
At an ambient temperature higher than 10 °C, the
open circuit voltage of the PV modules must not be
more than 90 % of the maximum inverter input
voltage.
Otherwise, check the system design and the PV
mo dul e co nne cti on. If thi s is not don e, t he maximu m
inverter input voltage can be exceeded at low
temperatures.
NOTICE!
Destruction of the inverter due to overvoltage.
If the voltage of the PV modules exceeds the maximum input voltage of the inverter, it can
be destroyed by the overvoltage.
All warranty claims become void.
• Do not connect strings with an open circuit voltage greater than the maximum input
voltage of the inverter.
• Check the system design.
34SMC6-8TL-IEN101040Installation Guide
Page 35
SMA Solar Technology AGElectrical Connection
4. Check the strings for ground faults, as described in section 9.3.1”Checking the PV Generator
for a Ground Fault” (page68).
5. Check the DC plug connector for correct polarity and connect it.
To release the plug connectors see section 7.2”Opening the Inverter” (page52).
6. To create the sealing on the inverter, all the DC
inputs that are not needed have to be closed as
follows:
– Insert the provided sealing plugs into the
unneeded DC plug connectors.
Do not insert the sealing plugs into the DC
inputs on the inverter.
– Insert the DC plug connectors with sealing plugs
in to t he c orre spo ndi ng D C inp uts on th e in ver ter .
7. Check the Electronic Solar Switch for wear, as
described in section 8.2”Checking the Electronic
Solar Switch (ESS) for Wear” (page60) and
attach it firmly.
Installation GuideSMC6-8TL-IEN10104035
Page 36
Electrical ConnectionSMA Solar Technology AG
NOTICE!
Manipulating the connector in the handle can damage the Electronic Solar
Switch.
The connector inside the handle must remain movable in order to ensure proper contact.
Tightening the screw voids all warranty claims and creates a fire risk.
• Do not tighten the connector screw in the Electronic Solar Switch handle.
NOTICE!
Damage to Electronic Solar Switch.
If not plugged correctly, the Electronic Solar Switch can be damaged by high voltages.
• Connect the holder firmly on to the socket of the Electronic Solar Switch.
• Make sure that the device is securely in place.
☑ The PV generator is now connected.
You can now commission the inverter as described in section 6”Commissioning” (page46).
The following connection possibilities are optional.
36SMC6-8TL-IEN101040Installation Guide
Page 37
SMA Solar Technology AGElectrical Connection
5.5 Connection of the SMA Power Balancer
The Sunny Mini Central is equipped with the SMA Power Balancer as standard. This enables a circuit
connection of 3 Sunny Mini Central to a three-phase feed-in system.
Each of the 3 Sunny Mini Central devices in a group must be conne cte d to a diffe rent pha se conduc tor
of the low-voltage grid (L1, L2 and L3)!
By activating this circuit, you can stipulate how the other two Sunny Mini Central devices are to react
if there is a device fault with the third Sunny Mini Central or there is a grid voltage fault in its phase.
Three-phase grid connection
For further information on this subject, see the Technical Information "Three phase
connection with Sunny Mini Central" in the download area at www.SMA.de/en.
The connections for the SMA Power Balancer are galvanically isola ted from th e rest of th e Sunny Mini
Central circuit.
5.5.1 Configuration
The SMA Power Balancer is deactivated at the factory using the "PowerBalancer" parameter
(parameter setting = off) and can only be activated and configured using a communication device.
To change the "PowerBalancer" parameter, you need a personal access code - the so-called SMA
Gr id G uar d Co de. The app lic ati on f orm f or t he p ers ona l ac ces s code is located in the download area
at www.SMA.de/en, in the "Certificate" category for each inverter.
The configuration options are detailed below.
Installation GuideSMC6-8TL-IEN10104037
Page 38
Electrical ConnectionSMA Solar Technology AG
Configuration Options
There are 4 different configuration options for the "PowerBalancer" parameter.
Local connection requirements
Select the respective setting and always observe the local connection requirements and
provisions of your utility operator.
•FaultGuard
This operating mode enables the implementation of three-phase grid voltage monitoring that
also reacts to device failures.
– If one of the three inverters indicates a grid voltage fault and stops feeding in, the other
two inverters also disconnect from the grid immediately.
– If one of the three inverters indicates a device fault and stops feeding in, the other two
inverters also disconnect from the grid 5 minutes later.
38SMC6-8TL-IEN101040Installation Guide
Page 39
SMA Solar Technology AGElectrical Connection
•PhaseGuard
This operating mode enables the implementation of three-phase grid voltage monitoring.
– If one of the three inverters indicates a grid voltage fault and stops feeding in, the other
two inverters also disconnect from the grid automatically.
– If one of the three inverters indicates a device fault and stops feeding in, the other two
inverters are not affected and continue to feed in at full power.
Installation GuideSMC6-8TL-IEN10104039
Page 40
Electrical ConnectionSMA Solar Technology AG
•Off
The SMA Power Balancer is deactivated (factory setting).
– In the event of a device fault or grid voltage fault at an inverter, only this inverter is
disconnected from the grid and the other two devices continue to run at an undiminished
power level.
•PowerGuard
This setting can be selected if the entire PV plant consists of only three 3 Sunny Mini Central
inverters and if, in the event of a failure, the unbalanced load should be limited to 5 kVA over
a 10-minute average.
Unbalanced load limitation for SMC 6000TL-IT / 7000TL-IT / 8000TL-IT
(applies exclusively to Italy)
For the Sunny Mini Central 6000TL-IT / 7000TL-IT / 8000TL-IT, the unbalanced load is
limited to 6 kVA.
– If one of the three inverters indicates a grid voltage fault or device fault and stops feeding
in, the other two inverters automatically limit their power to 5 kVA o ver a 10 minute average.
40SMC6-8TL-IEN101040Installation Guide
Page 41
SMA Solar Technology AGElectrical Connection
5.5.2 Cabling
Cable Requirements
For cabling the SMA Power Balancer, use a "LiYCY" cable, structured as shown here:
• Indoor: LiYCY 2 x 2 x 0.25
• Outdoor: Li-2YCYv 2 x 2 x 0.25
PositionDescription
AFlexible insulation
BShielding
CTwisted pair 2 (2 x 0.25 mm²)
DTwisted pair 1 (2 x 0.25 mm²)
Overview of the Connection Area
ObjectDescription
AScrew terminals for the wire bridge
BScrew terminals for connecting the wires
CJumper slot
1. Open the inverter as described in section 7.2”Opening the Inverter” (page52).
2. Insert the cable into each inverter.
Use one of the two cable glands (F) on the right hand side.
DANGER!
Danger to life through high voltage if there is a fault with the SMA Power
Balancer cable.
• Sheath the positive and negative cable conductors in each inverter using the
enclosed silicone tube.
• Cut the silicone tube to the required length.
• The silicone tube must completely cover the cable inside the inverter enclosure.
3. Draw the cable along the cable route (E) as far as the terminal block (B).
4. Ground the cable shield in each inverter to the PE connector (D).
5. Sheath the positive and negative cable conductors in each inverter with end sleeves.
6. Connect the positive and negative pole to the
corresponding screw terminals.
7. In order to connect the three inverters together, connect the positive and negative conductors
from the two other inverters to the terminal block of the middle inverter.
42SMC6-8TL-IEN101040Installation Guide
Page 43
SMA Solar Technology AGElectrical Connection
The cable length between two inverters may not exceed 300 m!
8. In the middle inverter only (with two wires for
each terminal), insert one of the jumpers provided
into the lowest of the three slots as shown on the
right.
Do not plug the jumpers into the lowest slot of the
two other inverters!
or
Bridge the "A" and "B" screw terminals on the
middle inverter with a wire bridge.
Do not bridge the "A" and "B" screw terminals in
the two other inverters!
9. Measure the resistance between the terminal
block's positive and negative poles in the middle
inverter.
☑ If the resistance is approximately 27.8 kOhms
(+/370 Ohms), the SMA Power Balancer has
been connected correctly. Otherwise, check the
cabling.
10. Close all inverters as described in section 7.3”Closing the Inverter” (page55).
Connection with one Sunny Mini Central 9000TL, 10000TL or 11000TL
In ord er t o be able to c onn ect the SMA Pow er B alancer wit h a S unn y Mi ni C ent ral 900 0TL,
10000TL or 11000TL, the Sunny Mini Central 6000TL, 7000TL oder 8000TL must be
equipped with a special plug. Three inverters are then connected together with a special
connection cable.
You can order the connection plug and the connection cable from SMA Solar Technology
AG or your dealer. Section 12”Accessories” (page84) contains a list of the order
numbers.
Installation GuideSMC6-8TL-IEN10104043
Page 44
Electrical ConnectionSMA Solar Technology AG
E-today 0Wh
Mode MPP
Disturbance
PowerBalance
Disturbance
Vac-Bfr
Disturbance
PowerBalance
5.5.3 Testing the Functioning
To test whether the SMA Power Balancer operates correctly, proceed as follows.
1. Select the "PhaseGuard" setting of the "PowerBalancer" parameter for all three inverters.
2. Check whether all inverters in the group are feeding the grid normally.
☑ If the green LED lights up steadily or if the
display message pictured opposite appears,
proceed with point 3.
or
☑ If all inverters in this group show the adjacent
display message: Check the installation of the
SMA Power Balancer and contact the SMA
Serviceline if necessary.
3. Switch off the line circuit breaker for one of the
three inverters.
• The inverter with a deactivated line circuit breaker
then indicates a grid voltage fault with the display
message shown opposite ("Bfr" and "Srr" are
irrelevant).
• The other two inverters then also disconnect
themselves from the grid with the display message
shown to the opposite.
• Both inverters subsequently switch to "Balanced"
mode.
☑ If the inverters react as described above, the
functionality test has been completed
successfully. Otherwise, check the
configuration.
4. If applicable, reset the "PowerBalancer" parameter to the desired setting in all inverters.
5. Switch on the line circuit breaker again.
☑ The functionality test has been completed.
5.6 Communication
The inverter is equipped with a slot for communication interfaces in orde r to communi cate wi th spec ial
data a cquisi tion de vices (e.g. Sunny WebB ox) or a PC with corr esponding software (e.g. Sunny Data
Control or Sunny Explorer).
See the respective communication interfa ce m anu al f or a d eta ile d cuircuit diagram and an installation
description for the interface.
44SMC6-8TL-IEN101040Installation Guide
Page 45
SMA Solar Technology AGElectrical Connection
5.7 Setting the Grid and Country Parameters
Changing Grid-Relevant and Country Parameters
To change grid-relevant parameters, you need a personal access code - the so-cal led SM A
Grid Guard Code. The application form for the personal access code is located in the
download area at www.SMA.de/en, in the "Certificate" category for each inverter.
Ensure that you discuss the changes to these parameters with your utility operator.
A detailed description of the operating parameters for the inverter is available in the download area
at www.SMA.de/en in the category "Technical Description" of the respective inverter.
5.7.1 Setting the Installation Country
Using the "Default" parameter you can set the installation country and/or the grid connection
standard valid for the country via a communication device (e.g. Sunny WebBox) or a PC with
appropriate software (e.g. Sunny Data Control or Sunny Explorer). This, however, is only required if
the inverter was origi nally o rdered for an other c ountry . You ca n see the standar d to wh ich the invert er
was set upon delivery from the type label and the supplementary document provided with the factory
settings.
5.7.2 Setting Stand-alone Grid Operation
To operate the inverter in a Sunny Island system, you must set the inverter via the "Default" parameter
to off-grid ("OFF-Grid") operation.
You have several possibilities to set the inverter to stand-alone grid operation:
• Setting via Sunny WebBox
or
• Setting via Sunny Data Control or Sunny Explorer.
DANGER!
Danger to life due to high voltages in the event of outage of the public grid.
If you set the inverter to stand-alone grid operation, it does not fulfill any country-specific
standards and regulations. Therefore, if there is an outage of the public grid, there is a
danger of back-feed.
• Never operate the inverter directly on the public grid when set to stand-alone grid
operation.
Installation GuideSMC6-8TL-IEN10104045
Page 46
CommissioningSMA Solar Technology AG
6 Commissioning
6.1 Commissioning the Inverter
Self test in accordance with DK 5640, Ed. 2.2 for initial commissioning (applies
to Italy only)
The Italian DK 5940 standard requires that an inverter can first operate on the public grid
when the disconnection times for overvoltage, undervoltage, minimum frequency and
maximum frequency have been checked.
Restart the self-test as described in the following section 6.2”Self-Test in accordance with
DK 5940, Ed. 2.2 (applies to Italy only)” (page47). The test takes approx. 8 minutes.
1. Check the following requirements before commissioning:
– The inverter is firmly fastened.
– Correct connection of the AC cable (grid)
– Full connection of the DC cables (PV strings)
– DC inputs that are not needed are closed with the corresponding DC plug connectors and
sealing plugs.
– The enclosure lid is securely screwed in place
– Electronic Solar Switch is securely plugged
– The line circuit breaker is laid out correctly
2. Switch on the line circuit breaker.
☑ Green LED glows: commissioning has been successful.
or
☑ Green LED flashes when there is insufficient irradiation: network connection conditions have
not yet been reached. Wait for sufficient irradiation.
or
☑ The red or yellow LED is glowing or flashing: there has been an error. Proceed to step 3.
A Green LEDOperation
B Red LEDGround fault or varistor
defective
C Yellow LEDDisturbance
3. Read section 9”Failure Search” (page61) and if necessary eliminate the fault or disturbance.
46SMC6-8TL-IEN101040Installation Guide
Page 47
SMA Solar Technology AGCommissioning
6.2 Self-Test in accordance with DK 5940, Ed. 2.2
(applies to Italy only)
6.2.1 Starting the Self-Test by Tapping
You can start the self-test by tapping on the enclosure lid. Prerequisite here is that the country
configuration of the inverter has been set to Italy (IT/DK5940) or "trimmed". Proceed as follows for
checking the disconnection times:
1. Connect the PV generator with the inverter. The inverter can only initialize if the PV generator
produces enough power. It is therefore not possible to test the disconnection times at night.
2. Connect the inverter on the AC side. For this, you have to create the AC connection (AC plug
or direct connection) and/or switch on the line circuit breaker of the grid cable (fuse or
automatic circuit breaker).
3. The inverter is now in the initialization phase, i.e. all 3 LEDs are glowing at the same time.
Start the self-test immediately after all 3 LEDS have gone out by tapping on the display of the
inverter.
4. The question on whether you would like to start the
test sequence appears in the display. Tap on the
display again within 30 seconds in order to confirm
the question.
Once you have started the test sequence, the inverter checks the disconnection times for overvoltage,
undervoltage, maximum frequency and minimum frequency one after the other. During the tests, the
inverter shows the values in the display which are described in section 6.2.2”Completion of the SelfTest” (page47).
6.2.2 Completion of the Self-Test
Note the values which are displayed during the self-test. These values must be entered into a test
pr oto col . Th e te st r esu lts of t he i ndi vid ual tes ts a re d isp lay ed 3 times one after the other. The respective
display appears for 10 seconds.
The self-test changes the upper and lower shut-down thresholds for each protective function on a
linear basis with a modification of 0.05 Hz/s and 0.05 Vn/s for the frequency and voltage
monitoring. As soon as the actual measurement value is outside the permitted range (altered shutdown threshold), the inverter disconnects itself from the grid. In this way, the inverter determines the
reaction time and checks itself.
Installation GuideSMC6-8TL-IEN10104047
Page 48
CommissioningSMA Solar Technology AG
Overvoltage Test
The inverter begins with the overvoltage test. During the
test sequence, the voltage limit applied is shown in the
display of the inverter.
The voltage limit is reduced successively until the shutdown threshold is achieved and the inverter disconnects
from the grid.
Once the inverter has disconnected from the grid, the
display successively shows the following values one after the other:
•Disconnection value,
•Calibration value,
•Reaction time,
• Present grid voltage.
48SMC6-8TL-IEN101040Installation Guide
Page 49
SMA Solar Technology AGCommissioning
Undervoltage Test
After the overvoltage test, the inverter performs the
undervoltage test. During the test sequence, the current
calibration value of the voltage limit applied is shown in
the display of the inverter.
The voltage limit is increased successively until the shutdown threshold is achieved and the inverter disconnects
from the grid.
Once the inverter has disconnected from the grid, the display successively shows the following values
one after the other:
•Disconnection value,
•Calibration value,
•Reaction time,
• Present grid voltage.
Installation GuideSMC6-8TL-IEN10104049
Page 50
CommissioningSMA Solar Technology AG
Maximum Frequency
In the thi rd s tep , the inv ert er t est s th e ma xim um f requenc y.
During the test sequence, the frequency limit applied is
shown in the display of the inverter.
The frequency limit is reduced successively until the shutdown threshold is achieved and the inverter disconnects
from the grid.
Once the inverter has disconnected from the grid, the display successively shows the following values
one after the other:
•Disconnection value,
•Calibration value,
•Reaction time,
• Present grid frequency.
50SMC6-8TL-IEN101040Installation Guide
Page 51
SMA Solar Technology AGCommissioning
Minimum Frequency
In the last step, the inverter tests the minimum frequency.
During the test sequence, the frequency limit applied is
shown in the display of the inverter.
The frequency limit is increased successively until the shutdown threshold is achieved and the inverter disconnects
from the grid.
Once the inverter has disconnected from the grid, the display successively shows the following values
one after the other:
•Disconnection value,
•Calibration value,
•Reaction time,
• Present grid frequency.
When the inverter has carried out the 4 tests, it switches to "MPP operation" mode. The original
calibration values are then re-set and the inverter automatically connects to the grid. If you would like
to carry out the test again, you have to disconnect the inverter, in other words you have to disconnect
it on the AC and DC sides and then later re-activate it. You can then restart the self-test as described
in the following section 6.2.1”Starting the Self-Test by Tapping” (page47). The inverter begins the
test sequence again, as described in section 6.2.2”Completion of the Self-Test” (page47).
Installation GuideSMC6-8TL-IEN10104051
Page 52
Opening and ClosingSMA Solar Technology AG
7 Opening and Closing
7.1 Safety
DANGER!
Risk of lethal electric shock.
Observe the following before opening the inverter:
• Ensure the AC side is not live.
• Ensure the DC side is not live.
NOTICE!
Electrostatic discharges can damage the inverter!
Internal components of the inverter can be irreparably damaged by electrostatic
discharge.
• Ground yourself before touching a component.
7.2 Opening the Inverter
1. Disconnect the line circuit breaker and secure against re-connection.
2. Pull the Electronic Solar Switch downward, slightly
toward the wall.
3. Using a current probe, ensure that there is no
current to all DC cables.
☑ If there is a current present, check the
installation.
52SMC6-8TL-IEN101040Installation Guide
Page 53
SMA Solar Technology AGOpening and Closing
4. Release all DC plug connectors with the help of a
screwdriver:
– Insert a screwdriver into one of the side slits (1).
– Lever the screwdriver upward (2) and pull out
the plug connector (3).
DANGER!
Danger to life due to high voltages in the inverter.
A secure separation from the PV generator is only guaranteed after pulling off the
Electronic Solar Switch and all DC plug connectors.
• Remove all DC plug connectors to
completely disconnect the PV generator
from the inverter.
DANGER!
Danger to life due to high voltages in the inverter.
The capacitors in the inverter require 5 minutes to discharge.
• Wait 5 minutes before opening the inverter.
Installation GuideSMC6-8TL-IEN10104053
Page 54
Opening and ClosingSMA Solar Technology AG
5. Ensure that there is no voltage at the DC plugs at
the inverter.
☑ If there is a voltage present, check the
installation.
6. Loosen all 6 lid screws and pull the lid forward to
remove it.
7. Verify the absence of voltage L with respect to N at
the AC clamp with an appropriate meter.
☑ If there is a voltage present, check the
installation.
54SMC6-8TL-IEN101040Installation Guide
Page 55
SMA Solar Technology AGOpening and Closing
8. Verify the absence of voltage L w ith respect to PE at
the AC clamp with an appropriate meter.
☑ If there is a voltage present, check the
installation.
☑ The inverter is now open and is not live.
7.3 Closing the Inverter
1. Secure the lid with the 6 screws and the
corresponding tooth lock washers.
Tighten the screws with 6 Nm torque in the order
shown on the right hand side. The toothing of the
tooth lock washers must face toward the lid.
The scope of delivery of the inverter includes
another spare screw and lock washer.
DANGER!
Danger to life due to live lid.
The grounding of the enclosure lid is ensured by the tooth lock washers.
• Fasten the tooth lock washers for all 6 screws with the toothing facing toward the lid.
1. Check the DC plug connector for correct polarity and connect it.
To release the plug connectors see section 7.2”Opening the Inverter” (page52).
Installation GuideSMC6-8TL-IEN10104055
Page 56
Opening and ClosingSMA Solar Technology AG
2. Close all unnecessary DC inputs as described in section 5.4.4”Connecting the PV Generator
(DC)” (page34) to seal the inverter.
3. Check the Electronic Solar Switch for wear, as
described in section 8.2 and attach it firmly.
NOTICE!
Manipulating the connector in the handle can damage the Electronic Solar
Switch.
The connector inside the handle must remain movable in order to ensure proper contact.
Tightening the screw voids all warranty claims and creates a fire risk.
•Do not tighten the connector screw in the Electronic Solar Switch handle.
NOTICE!
Damage to Electronic Solar Switch.
If not plugged correctly, the Electronic Solar Switch can be damaged by high voltages.
• Connect the holder firmly on to the socket of the Electronic Solar Switch.
• Make sure that the device is securely in place.
4. Switch on the line circuit breaker.
5. Check whether the display and the LEDs indicate
normal operating mode (see section
6”Commissioning” (page46)).
☑ The inverter is now closed and in operation.
56SMC6-8TL-IEN101040Installation Guide
Page 57
SMA Solar Technology AGMaintenance and Cleaning
8 Maintenance and Cleaning
8.1 Checking Heat Dissipation
8.1.1 Cleaning the Fans
If the fan grills are only soiled with loose dust, they can be cleaned using a vacuum cleaner. If you do
not achieve satisfactory results with a vacuum cleaner, dismantle the fans for cleaning.
Procedure
1. Disconnect the inverter from both the DC and AC connections as described in section
7.2”Opening the Inverter” (page52).
2. Wait for the fans to stop rotating.
Cleaning the Air Grills
3. Remove the air grills:
– P res s th e tw o la tches on the rig ht e dge of t he f an
grill to the right using a screwdriver and loosen
it from the bracket.
– Carefully remove the air grill.
4. Clean the fan grills with a soft brush, a paint brush,
a cloth or pressurized air.
Cleaning the fan
5. Press the front latches backward and the rear latch
forward.
Installation GuideSMC6-8TL-IEN10104057
Page 58
Maintenance and CleaningSMA Solar Technology AG
6. Remove the fan by pulling it slowly and carefully downward.
7. Unlock and remove the plug.
The fan cables are long enough that you can lift the fans far enough out to disconnect the
internal plug in the inverter.
8. Remove the fan.
9. Clean the fan with a soft brush, a paint brush, or a damp cloth.
NOTICE!
Damage to the fan through the use of pressurized air.
• Do not use pressurized air to clean the fan. This can damage the fan.
10. After cleaning, assemble everything in reverse order.
☑ The fans are cleaned.
11. Check the function of the fans as described in the following section.
8.1.2 Checking the Fans
You can check that the fans are working in 2 ways:
• Set the "Fan-Test" parameter to "1" in the installer mode using Sunny Data Control,
Sunny Explorer or Sunny WebBox.
or
• Plug the provided jumper into the system control board.
Setting Parameters
1. Request the installer password from the SMA Serviceline (contact: see page 85).
2. Set the "Fan-Test" parameter to "1" in the installer mode.
3. Check the fans' air flow.
The inverter sucks air in from underneath and then blows it back out on the upper sides. Listen
for any unusual noise, which could indicate incorrect installation or that the fans are faulty.
4. After checking the fans, set the "Fan-Test" parameter back to 0.
☑ The test of the fans has been completed.
Plugging the Jumper
The inverter recognizes the jumper only after the system has been restarted (i.e. all LEDs must have
gone out before a restart).
1. Open the inverter as described in section 7.2”Opening the Inverter” (page52).
2. Plug the provided jumper in the slot on the system control board as shown below.
58SMC6-8TL-IEN101040Installation Guide
Page 59
SMA Solar Technology AGMaintenance and Cleaning
3. Close the inverter as described in section 7.3”Closing the Inverter” (page55).
4. Check the fans' air flow.
The inverter sucks air in from underneath and then blows it back out on the upper sides. Listen
for any unusual noise, which could indicate incorrect installation or that the fans are faulty.
5. After checking the fans, remove the jumper. Open and close the inverter as described in section
7”Opening and Closing” (page52).
☑ The test of the fans has been completed.
8.1.3 Cleaning the Air Grills
The inverter sucks air in from underneath via the fan and blows it out again through the air grills on
the upper sides. Clean the air grills if they are dirty.
Procedure
1. Remove the air grills.
Insert your finger above in the space between the
air grills and the enclosure and remove the air grills
to the side.
2. Clean the air grills with a soft brush, a paint brush,
or pressurized air.
3. Re-attach the air grills to the inverter.
The air grills must be attached according to the
inside inscription ("links/left" and "rechts/right").
Installation GuideSMC6-8TL-IEN10104059
Page 60
Maintenance and CleaningSMA Solar Technology AG
NOTICE!
Risk of damage to the inverter if insects enter it!
• The air grills must not be removed permanently, because otherwise the device is not
protected against the entrance of insects!
8.2 Checking the Electronic Solar Switch (ESS) for Wear
Check the Electronic Solar Switch for wear before plugging it in.
ResultAction
☑ The metal tongues inside the connector are
not damaged or discolored.
1. Securely attach the Electronic Solar Switch
handle.
2. Re-commission the inverter as described in
section 6”Commissioning” (page46).
☑ The metal tongues inside the connector
have a brown discoloration or are burned
through.
Th e El ectroni c So lar Switch c an n o longer rel iab ly
disconnect the DC side.
1. Replace the Electronic Solar Switch handle
before attaching it again (for the order
number see section 12”Accessories”
(page84).
2. Re-commission the inverter as described in
section 6”Commissioning” (page46).
60SMC6-8TL-IEN101040Installation Guide
Page 61
SMA Solar Technology AGFailure Search
9 Failure Search
If the inverter displays other blink codes or error messages other than those described in the following
section, contact the SMA Serviceline
In the use r ma nual pro vid ed, you wil l al so find a des cri pti on o f the display messages during operation,
the status messages and measuring channels.
Do not try to carry out repairs other than those described here. Instead, use the SMA Solar
Technology AG 24-hour replacement service (the inverter will be ready for dispatch within 24 hours
and sent to a forwarding agency) and repair service
9.1 Blink Codes
GreenRedYellowStatus
Glows continuouslyIs not glowingIs not glowingOK (feeding operation)
Glows continuouslyIs not glowingGround fault or varistor
defective
Glows continuouslyOK (initialization)
Flashes quickly
(3 x per second)
Flashes slowly
(1 x per second)
Briefly goes out
(approx. 1 x per
second)
Is not glowingIs not glowingIs not glowingOK (disconnection)
Is not glowingIs not glowingOK (stop)
Glows continuouslyIs not glowingGround fault or varistor
defective
Is not glowingIs not glowingOK (waiting, grid
monitoring)
Glows continuouslyIs not glowingGround fault or varistor
defective
Is not glowingIs not glowingOK (derating)
Glows / flashesDisturbance
Glows continuouslyIs not glowingGround fault or varistor
defective
Glows / flashesGround fault or varistor
defective and disturbance
9.2 Error Messages
Wh en a dis tur ban ce o ccu rs, th e in verter generates a message, which dep end s on the ope rat ing mod e
and the type of disturbance detected.
Installation GuideSMC6-8TL-IEN10104061
Page 62
Failure SearchSMA Solar Technology AG
MessageDescription and corrective measure
!PV-Overvoltage!
!DISCONNECT DC!
Overvoltage at DC input.
Overvoltage can destroy the inverter.
Corrective measures
Disconnect the inverter from the grid immediately.
1. Turn off the line circuit breaker.
2. Remove the Electronic Solar Switch.
3. Disconnect all the DC plug connectors.
4. Check DC voltage:
– If the DC voltage exceeds the maximum input voltage, check the
plant design or contact the person who installed the PV
generator.
– If the DC voltage is under the maximum input voltage, reconnect
the inverter to the PV generator as described in section
5.4.4”Connecting the PV Generator (DC)” (page34).
If the message occurs again, disconnect the inverter again and contact
the SMA Serviceline (see section 13”Contact” (page85)).
ACVtgRProThe 10-minute-average grid voltage is no longer within the permissible
range. This can have the following causes:
The grid voltage at the connection point is too high.
• The grid impedance at the connection point is too high.
The inverter disconnects to assure compliance with the voltage quality of
the grid.
Corrective measures
Check the grid voltage at the connection point of the inverter:
• If, due to the local grid conditions, the grid voltage is 253 V or
more, ask the utility operator whether the voltage at the feed-in
point can be adjusted, or whether it would agree to an alteration of
the threshold value of the ACVtgRPro parameter to monitor the
voltage quality.
• If the grid voltage is continually within the acceptable range and
this error is still displayed, contact the SMA Serviceline
CANInternal communication fault.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
62SMC6-8TL-IEN101040Installation Guide
Page 63
SMA Solar Technology AGFailure Search
MessageDescription and corrective measure
DeratingThe "Derating" operating mode is a normal operating mode which may
occur occasionally and can have several causes.
If the inverter was in the "Derating" mode for at least 10 minutes, it will
display the "Derating" warning until the next total shutdown of the device
(at the end of the day).
Corrective measures
• Check heat dissipation, as described in section 8.1”Checking
Heat Dissipation” (page57).
dI-Bfr
dI-Srr
The inverter has detected a drastic change in the differential current. The
integrated differential current monitoring system plays an important part
in ensuring personal safety.
A drastic change in the differential current can be caused by a sudden
grounding fault, failure current or an actual fault in the device. The
inverter disconnects from the grid.
Corrective measures
• If the message "dI-Bfr" or "dI-Srr" appears for no obvious reason,
verify whether the plant insulation might have a ground fault, as
described in section 9.3.1”Checking the PV Generator for a
Ground Fault” (page68).
EEPROMTransition disturbance while data is being written or read from EEPROM.
The data is not relevant for safe operation
The disturbance has no effect on the performance of the inverter.
EEPROM dBhEEPROM data is defective, the device has switched off because the loss
of data has disabled important functions of the inverter.
Corrective measures
• Contact the SMA Serviceline
EeRestoreOne of the duplicate data sets in the EEPROM is defective and has been
reconstructed without loss of data.
• The error message only serves to inform you and has no effect on
the performance of the inverter.
Fac-Bfr
Fac-Srr
FacFast
The grid frequency is no longer within the permissible range ("Bfr" / "Srr"
/ "Fast" is an internal message of no relevance for the user). For safety
reasons, the inverter disconnects itself from the grid.
Corrective measures
• Check the grid connection and if necessary measure the grid
frequency.
• If the grid frequency is within the tolerance range, yet "Fac-Bfr",
"Fac-Srr" or "FacFast" faults are still being displayed, contact the
SMA Serviceline
Installation GuideSMC6-8TL-IEN10104063
Page 64
Failure SearchSMA Solar Technology AG
MessageDescription and corrective measure
Fault Curr Meas
Fault Curr Meas-Srr
Deviation in the differential current measurement / differential current
If this fault message is displayed repeatedly, it means that inverter
operation is permanently disabled.
Corrective measures
• Contact the SMA Serviceline
HW-SignalInternal measurement fault or hardware defect.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
Iac-DC_Offs-SrrA grid disturbance has occurred.
Corrective measures
• Check the grid conditions.
• Contact the SMA Serviceline if this problem occurs often or several
times in succession.
IGBTsThe internal hardware monitoring system has detected a fault in the
power electronics.
Corrective measures
• Contact the SMA Serviceline
L<->NL and N are swapped on the AC connection.
Corrective measures
• Check the grid connection.
L-Netz
L-WR
N-Netz
A grid relay is faulty. The inverter checks the relays connecting it to the
grid before feeding power into the grid. If the grid relays do not function
properly, the inverter does not connect to the grid for safety reasons.
N-WR
Corrective measures
• If this fault message is displayed repeatedly, it means that inverter
operation is permanently disabled.
• If the inverter is equipped with a communication interface, try to
rectify the fault using a communication product.
• Should this be unsuccessful, contact the SMA Serviceline
MSD-dIInternal measurement comparison fault or hardware defect.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
MSD-FacInternal measurement comparison fault or hardware defect.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
64SMC6-8TL-IEN101040Installation Guide
Page 65
SMA Solar Technology AGFailure Search
MessageDescription and corrective measure
MSD-VacInternal measurement comparison fault or hardware defect.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
MSD-TimeoutInternal measurement comparison fault or hardware defect.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
OffsetThe "Offset" operating condition is a normal operating condition that
occurs prior to grid monitoring.
If "Offset" is displayed as an error, then there is a disturbance in the data
logging.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
PowerBalanceThe inverter is part of a three-phase system with two further inverters and
equipped with the SMA Power Balancer for preventing unbalanced
loads. The operating parameter "PowerBalancer" is set to "PhaseGuard"
or "FaultGuard".
Corrective measures
• For more detailed descriptions of the operation modes
"PhaseGuard" and "FaultGuard", please refer to section
5.5”Connection of the SMA Power Balancer” (page37).
Relais2
Relais4
A grid relay is faulty. The inverter checks the relays connecting it to the
grid before feeding power into the grid. If the grid relays do not function
properly, the inverter does not connect to the grid for safety reasons.
Corrective measures
• If this fault message is displayed repeatedly, it means that inverter
operation is permanently disabled.
• If the inverter is equipped with a communication interface, try to
rectify the fault using a communication product.
• Should this be unsuccessful, contact the SMA Serviceline
RisoThe electrical insulation between the PV plant and ground is faulty. The
re sis tance be twe en the DC plu s and/or DC m inus con nec tion and ground
is outside the defined limit range.
Corrective measures
• Check the plant insulation.
• Check the plant for ground faults as described in section
9.3.1”Checking the PV Generator for a Ground Fault” (page68).
Installation GuideSMC6-8TL-IEN10104065
Page 66
Failure SearchSMA Solar Technology AG
MessageDescription and corrective measure
ROMThe inverter's firmware is faulty.
Corrective measures
• Contact the SMA Serviceline
SD-DI-WandlerThe inverter has detected an insulation fault on the DC side.
Corrective measures
• Check the plant insulation.
• Check the plant for ground faults as described in section
9.3.1”Checking the PV Generator for a Ground Fault” (page68).
SD-ImaxThe inverter has detected an overcurrent on the AC side. It disconnects
from the grid for safety reasons and then attempts to reconnect to the
grid.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
SD-WR-BrueckeThe inverter has detected a fault in the power electronics. It disconnects
from the grid and then attempts to reconnect to the grid. There could also
be a ground fault in the PV generator.
Corrective measures
• Check for ground faults in the PV generator as described in section
9.3.1”Checking the PV Generator for a Ground Fault” (page68).
• If this fault continues to occur, contact the SMA Serviceline
ShutdownTemporary inverter fault.
Corrective measures
• Contact the SMA Serviceline
STM TimeoutInternal program run fault.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
66SMC6-8TL-IEN101040Installation Guide
Page 67
SMA Solar Technology AGFailure Search
MessageDescription and corrective measure
Vac-Bfr
Vac-Srr
The grid voltage is no longer within the permissible range ("Bfr" or "Srr" is
an internal message of no relevance for the user). This code can be
caused by any of the following conditions:
• Grid disconnected (line circuit breaker, fuse),
•AC cable is broken or
• AC cable is highly resistive
For safety reasons, the inverter disconnects itself from the grid.
Corrective measures
• Check the grid current and grid connection on the inverter.
• If the grid voltage lies outside the acceptable range because of
local grid conditions, ask the utility provider if the voltage can be
adjusted at the feed-in point or if it would agree to changes in the
values of the monitored operational limits (operating parameters:
Vac-Min and Vac-Max).
• If the grid frequency is within the tolerable range, yet "Vac-Bfr," or
"Vac-Srr" faults are still being displayed, please contact the SMA
Serviceline
VpvMaxOvervoltage at DC input. The inverter may be damaged.
Corrective measures
Immediately disconnect the inverter from the grid.
1. Turn off the line circuit breaker.
2. Remove the Electronic Solar Switch.
3. Disconnect all the DC plug connectors.
4. Check DC voltage:
– If the DC voltage exceeds the maximum input voltage, check the
plant design or contact the person who installed the PV
generator.
– If the DC voltage is under the maximum input voltage, reconnect
the inverter to the PV generator as described in section
5.4.4”Connecting the PV Generator (DC)” (page34).
If the message occurs again, disconnect the inverter again and contact
the SMA Serviceline (see section 13”Contact” (page85)).
UZWK-MaxThe internal hardware monitor has detected an overvoltage condition in
the intermediate circuit of the inverter.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
Installation GuideSMC6-8TL-IEN10104067
Page 68
Failure SearchSMA Solar Technology AG
MessageDescription and corrective measure
Watchdog
Watchdog-Srr
Internal program run fault.
Corrective measures
• If this fault occurs often, contact the SMA Serviceline
9.3 Red LED is Glowing Continuously
If the red LED of the status display is continuously on during operation, there is either a ground fault
in the PV generator or at least one of the varistors for the overvoltage protection is defective.
9.3.1 Checking the PV Generator for a Ground Fault
1. Disconnect the inverter from both the DC and AC connections as described in section
7.2”Opening the Inverter” (page52).
NOTICE!
Excessive voltages can destroy the measuring device.
• Only use measuring devices with a DC input voltage range up to at least 700 V.
2. Measure the voltages between the plus pole of an
individual string and minus pole of an individual
string against the ground potential.
☑ If voltage is found, there is a ground fault in the
corresponding string.
DANGER!
Risk of lethal electric shock.
If a ground fault occurs, the PV generator may carry high voltages.
• Do not touch the frame of the PV generator.
• Wait until no voltage can be measured.
• Do not connect strings with ground faults to the inverter.
68SMC6-8TL-IEN101040Installation Guide
Page 69
SMA Solar Technology AGFailure Search
The approximate position of the ground fault can be determined from the ratio of the measured
voltages between plus against ground potential and minus against ground potential.
Example:
The ground fault is between the second and third module in this case.
3. Repeat step 2 for each string.
ResultAction
☑ You have found a ground fault.• The installer of the PV generator must remedy the
ground fault in the affected string before you may
reconnect the string to the inverter.
•Do not reconnect the faulty string.
• Restart the inverter as described in section
7.3”Closing the Inverter” (page55), but without
reconnecting the faulty string.
☑You have found no ground fault. It is likely that one of the thermally monitored varistors is
defective.
• Check the varistors as described in section
9.3.2”Checking the Functioning of the Varistors”
(page69).
☑ The ground fault check is finished.
9.3.2 Checking the Functioning of the Varistors
Varistors are wearing parts. Their functional efficiency diminishes with age or following repeated
responses as a result of overvoltages. It is therefore possible that one of the thermally monitored
varistors has lost its protective function.
Installation GuideSMC6-8TL-IEN10104069
Page 70
Failure SearchSMA Solar Technology AG
Position of Varistors
You can determine the position of the varistors with the help of the illustration below.
Observe the following allocation of the
terminals:
• Terminal A: outer terminal (varistor
connection with loop [crimp])
• Terminal B: middle terminal
• Terminal C: outer terminal (varistor
connection without loop [crimp])
You can check the varistors as follows:
1. Open the inverter as described in section 7.2”Opening the Inverter” (page52).
2. Use a Multimeter to ensure that both varistors in the
installed state have a conducting connection
between connectors B and C.
ResultAction
☑There is a conductive connection. There is probably a different fault in the inverter.
• Close the inverter as described in section
7.3”Closing the Inverter” (page55).
• Contact the SMA Serviceline (see section
13”Contact” (page85)).
☑There is no conductive
connection.
The respective varistor is defective and must be replaced.
Varistor failure is generally due to influences which affect
all varistors similarly (temperature, age, induced
overvoltage). SMA Solar Technology AG recommends
that you replace both varistors.
The varistors are specially manufactured for use in the
inverter and are not commercially available. You must
order replacement varistors directly from SMA Solar
Technology AG (see section 12”Accessories”
(page84)).
• To replace the varistors, proceed to step 3.
70SMC6-8TL-IEN101040Installation Guide
Page 71
SMA Solar Technology AGFailure Search
NOTICE!
Destruction of the inverter due to overvoltage.
If varistors are missing, the inverter is no longer protected against overvoltages.
•Do not operate the inverter wi thout varistors in plants with a high risk of overvoltages.
• Replacement varistors should be obtained as soon as possible.
3. Insert an insertion tool into the openings of the
terminal contacts (1).
☑ This releases the terminals.
If you do not receive an insertion tool for operating
the terminal clamps with your replacement
varistors, please contact SMA Solar Technology
AG. As an alternative, the terminal contacts can be
operated using a 3.5 mm wide screwdriver.
4. Remove the varistor (2).
5. Insert new varistor (3).
The pole with the small loop (crimp) must be fitted
to terminal A (3) when remounting.
6. Close the inverter as described in section
7.3”Closing the Inverter” (page55).
☑ The check and replacement of the varistors is completed.
Installation GuideSMC6-8TL-IEN10104071
Page 72
DecommissioningSMA Solar Technology AG
10 Decommissioning
10.1 Dismantling the Inverter
1. Open the inverter as described in section 7.2”Opening the Inverter” (page52).
2. Remove all cables from the inverter.
3. Close the inverter with the 6 screws and the
corresponding tooth lock washers.
4. Remove the air grills from both sides.
5. Remove the two screws on the left and right side of
the inverter that attach it to the wall bracket.
6. Disconnect the anti-theft protection, if applicable.
7. Remove the inverter upward from the wall mounting
bracket.
72SMC6-8TL-IEN101040Installation Guide
Page 73
SMA Solar Technology AGDecommissioning
8. Use the side handles (above and below) or a steel
rod (maximum diameter 30 mm) to transport the
inverter. The rod must be pushed through the
enclosure openings.
☑ The inverter is dismantled.
10.2 Packing the Inverter
If possible, always pack the inverter in its original packaging. If it is no longer available, you can also
use an equivalent box. The carton must be completely closeable, have a handle system and be made
to support both the weight and size of the inverter.
10.3 Storing the Inverter
Store the inverter in a dry place where ambient temperatures are always between − 25 °C and
+60 °C.
10.4 Disposing of the Inverter
Dispose of the inverter at the end of its service life in accordance with the disposal regulations for
electronic waste which apply at the installation site at that time. Alternatively, send it back to SMA
Solar Technology AG with shipping paid by sender, and labeled "ZUR ENTSORGUNG"
("for disposal") (contact see page 85).
Installation GuideSMC6-8TL-IEN10104073
Page 74
Technical DataSMA Solar Technology AG
11 Technical Data
11.1 Sunny Mini Central 6000TL
DC Input
Maximum DC power at cos ϕ = 1P
Maximum DC voltage *U
MPP voltage rangeU
DC nominal voltageU
Minimum DC voltageU
Start voltage, adjustable U
Maximum input currentI
DC
DC max
PV
DC nom
DC min
PV Start
PV max
6,200 W
700 V
333 V … 500 V
350 V
330 V
400 V
19.0 A
Number of MPP trackers1
Maximum number of parallel strings4
Voltage ripple of input voltageU
pp
<10%
Internal consumption during operation< 10 W
* The maximum open circuit voltage, which can occur at a cell temperature of -10 °C, may not exceed the maximum input voltage.
AC Output
AC nominal power at 230 V AC, 50 HzP
Maximum AC apparent powerS
Nominal AC currentI
Maximum output currentI
AC nom
AC max
AC nom
AC max
Maximum fuse protection50 A
Harmonic distortion of output current at
K
IAC
AC THD voltage < 2 %,
AC power > 0.5 AC nominal power
Nominal AC voltageU
AC voltage rangeU
AC grid frequencyf
Operating range at AC grid frequencyf
AC nom
AC
AC nom
AC
50 Hz: 45.5 Hz … 54.5 Hz
60 Hz: 55.5 Hz … 64.5 Hz
Power factor at nominal AC powercos ϕ1
Supply phases1
Connection phases1
Overvoltage category as per
AUS/NZS 60950.1:2003
Overvoltage category as per EN 50178:1998III
6,000 W
6,000 VA
27 A
27 A
< 3 %
220 V / 230 V / 240 V
180 V … 260 V
50 Hz / 60 Hz
II
74SMC6-8TL-IEN101040Installation Guide
Page 75
SMA Solar Technology AGTechnical Data
Test voltage (DC)2.15 kV
Test surge voltage 4 kV
Surge testing voltage with serial interface6 kV
Internal consumption in night mode0.25 W
Mechanical data
Width x height x depth468 mm x 613 mm x 242 mm
Weight31 kg
Climatic Conditions
Extended temperature range *− 25 °C … +60 °C
Extended humidity range *0 % … 100 %
Extended air pressure range *79.5 kPa … 106 kPa
Temperature range **− 25 °C … +70 °C
Operation temperature range− 25 °C … +60 °C
Maximum operating altitude above mean sea
3,000 m
level
* according to DIN EN 50178:1998-04, installation type C, class 4K4H
** according to DIN EN 50178:1998-04, transport type E, class 2K3
Features
TopologyTransformerless
Cooling conceptOptiCool
Fan connectionDesigned for safe disconnection
All-pole DC switch-disconnectorElectronic Solar Switch,
DC plug system SUNCLIX
DC overvoltage protectionThermally monitored varistors
Personal protection (R
> 1 M Ω )Insulation monitoring
iso
Pole confusion protectionShort circuit diode
AC short circuit protectionCurrent control
All-pole AC disconnection unitAutomatic disconnection device
SMA Grid Guard 2.1
Communication Interfaces
®
Bluetooth
Wireless TechnologyOptional
RS485, galvanically isolatedOptional
Electronic Solar Switch
Electrical servic e life in the event of a short circuit,
A minimum of 50 switching operations
with a nominal current of 35 A
Maximum switching current35 A
Maximum switching voltage800 V
Maximum PV power12 kW
Protection rating when pluggedIP65
Protection rating when unpluggedIP21
76SMC6-8TL-IEN101040Installation Guide
Page 77
SMA Solar Technology AGTechnical Data
Efficiency
Peak efficiencyη
European efficiencyη
Installation GuideSMC6-8TL-IEN10104077
max
euro
98 %
97.7 %
Page 78
Technical DataSMA Solar Technology AG
11.2 Sunny Mini Central 7000TL
DC Input
Maximum DC power at cos ϕ = 1P
DC
Maximum DC voltage *UDC
MPP voltage rangeU
DC nominal voltageU
Minimum DC voltageU
Start voltage, adjustable U
Maximum input currentI
PV
DC nom
DC min
PV Start
PV max
max
7,200 W
700 V
333 V … 500 V
350 V
330 V
400 V
22 A
Number of MPP trackers1
Maximum number of parallel strings4
Voltage ripple of input voltageU
pp
<10%
Internal consumption during operation< 10 W
* The maximum open circuit voltage, which can occur at a cell temperature of -10 °C, may not exceed the maximum input voltage.
AC Output
AC nominal power at 230 V AC, 50 HzP
Maximum AC apparent powerS
Nominal AC currentI
Maximum output currentI
AC nom
AC max
AC nom
AC max
Maximum fuse protection50 A
Harmonic distortion of output current at
voltage < 2 %,
AC T
HD
K
IAC
AC power > 0.5 AC nominal power
Nominal AC voltageU
AC voltage rangeU
AC grid frequencyf
Operating range at AC grid frequencyf
AC nom
AC
AC nom
AC
50 Hz: 45.5 Hz … 54.5 Hz
60 Hz: 55.5 Hz … 64.5 Hz
Power factor at nominal AC powercos ϕ1
Supply phases1
Connection phases1
Overvoltage category as per
AUS/NZS 60950.1:2003
Overvoltage category as per EN 50178:1998III
Test voltage (DC)2.15 kV
Test surge voltage 4 kV
7,000 W
7,000 VA
31 A
31 A
< 3 %
220 V / 230 V / 240 V
180 V … 260 V
50 Hz / 60 Hz
II
78SMC6-8TL-IEN101040Installation Guide
Page 79
SMA Solar Technology AGTechnical Data
Surge testing voltage with serial interface6 kV
Internal consumption in night mode0.25 W
Mechanical data
Width x height x depth468 mm x 613 mm x 242 mm
Weight32 kg
Climatic Conditions
Extended temperature range *− 25 °C … +60 °C
Extended humidity range *0 % … 100 %
Extended air pressure range *79.5 kPa … 106 kPa
Temperature range **− 25 °C … +70 °C
Operation temperature range− 25 °C … +60 °C
Maximum operating altitude above mean sea
3,000 m
level
* according to DIN EN 50178:1998-04, installation type C, class 4K4H
** according to DIN EN 50178:1998-04, transport type E, class 2K3
Features
TopologyTransformerless
Cooling conceptOptiCool
Fan connectionDesigned for safe disconnection
All-pole DC switch-disconnectorElectronic Solar Switch,
DC plug system SUNCLIX
DC overvoltage protectionThermally monitored varistors
Personal protection (R
Pole confusion protectionShort circuit diode
AC short circuit protectionCurrent control
All-pole AC disconnection unitAutomatic disconnection device
Electrical servic e life in the event of a short circuit,
A minimum of 50 switching operations
with a nominal current of 35 A
Maximum switching current35 A
Maximum switching voltage800 V
Maximum PV power12 kW
Protection rating when pluggedIP65
Protection rating when unpluggedIP21
Efficiency
Peak efficiencyη
European efficiencyη
80SMC6-8TL-IEN101040Installation Guide
max
euro
98 %
97.7 %
Page 81
SMA Solar Technology AGTechnical Data
11.3 Sunny Mini Central 8000TL
DC Input
Maximum DC power at cos ϕ = 1P
DC
Maximum DC voltage *UDC
MPP voltage rangeU
DC nominal voltageU
Minimum DC voltageU
Start voltage, adjustable U
Maximum input currentI
PV
DC nom
DC min
PV Start
PV max
max
8,250 W
700 V
333 V … 500 V
350 V
330 V
400 V
25 A
Number of MPP trackers1
Maximum number of parallel strings4
Voltage ripple of input voltageU
pp
<10%
Internal consumption during operation< 10 W
* The maximum open circuit voltage, which can occur at a cell temperature of -10 °C, may not exceed the maximum input voltage.
AC Output
AC nominal power at 230 V AC, 50 HzP
Maximum AC apparent powerS
Nominal AC currentI
Maximum output currentI
AC nom
AC max
AC nom
AC max
Maximum fuse protection50 A
Harmonic distortion of output current at
voltage < 2 %,
AC T
HD
K
IAC
AC power > 0.5 AC nominal power
Nominal AC voltageU
AC voltage rangeU
AC grid frequencyf
Operating range at AC grid frequencyf
AC nom
AC
AC nom
AC
50 Hz: 45.5 Hz … 54.5 Hz
60 Hz: 55.5 Hz … 64.5 Hz
Power factor at nominal AC powercos ϕ1
Supply phases1
Connection phases1
Overvoltage category as per
AUS/NZS 60950.1:2003
Overvoltage category as per EN 50178:1998III
Test voltage (DC)2.15 kV
Surge testing voltage4 kV
8,000 W
8,000 VA
35 A
35 A
< 3 %
220 V / 230 V / 240 V
180 V … 260 V
50 Hz / 60 Hz
II
Installation GuideSMC6-8TL-IEN10104081
Page 82
Technical DataSMA Solar Technology AG
Surge testing voltage with serial interface6 kV
Internal consumption in night mode0.25 W
Mechanical data
Width x height x depth468 mm x 613 mm x 242 mm
Weight33 kg
Climatic Conditions
Extended temperature range *− 25 °C … +60 °C
Extended humidity range *0 % … 100 %
Extended air pressure range *79.5 kPa … 106 kPa
Temperature range **− 25 °C … +70 °C
Operation temperature range− 25 °C … +60 °C
Maximum operating altitude above mean sea
3,000 m
level
* according to DIN EN 50178:1998-04, installation type C, class 4K4H
** according to DIN EN 50178:1998-04, transport type E, class 2K3
Features
TopologyTransformerless
Cooling conceptOptiCool
Fan connectionDesigned for safe disconnection
All-pole DC switch-disconnectorElectronic Solar Switch,
DC plug system SUNCLIX
DC overvoltage protectionThermally monitored varistors
Personal protection (R
Pole confusion protectionShort circuit diode
AC short circuit protectionCurrent control
All-pole AC disconnection unitAutomatic disconnection device
Electrical servic e life in the event of a short circuit,
A minimum of 50 switching operations
with a nominal current of 35 A
Maximum switching current35 A
Maximum switching voltage800 V
Maximum PV power12 kW
Protection rating when pluggedIP65
Protection rating when unpluggedIP21
Efficiency
Peak efficiencyη
European efficiencyη
Installation GuideSMC6-8TL-IEN10104083
max
euro
98 %
97.7 %
Page 84
AccessoriesSMA Solar Technology AG
12 Accessories
You will find the corresponding accessories and replacement parts for your product In the following
overview. If required, you can order these from SMA Solar Technology AG or your dealer.
DescriptionBrief descriptionSMA order number
SMA Power Balancer
plug
SMA Power Balancer
Ycable
Electronic Solar Switch ESS handle replacement partESS-HANDLE:04
Air grillsAir grill set "right and left" as spare part45-7202
Replacement varistorsSet of thermally monitored varistors (2 pcs.)
Insertion tool for
replacing the varistors
RS485 upgrade kitRS485 interface485PB-SMC-NR
Bluetooth upgrade kitBluetooth communication interfaceBTPBINV-NR
SUNCLIX DC plug
connectors
Upgrade kit to retrofit a Sunny Mini Central
Equipped with an SMA Power Balancer to
SMA Power Balancer Connector System
Connecting cable (2 x 2 m) for SMA Power
Balancer connector system
including insertion tool
Installation tool for varistorsSB-TVWZ
Field connectors for conductor cross sections
2.5 mm² … 6 mm²
PBL-SMC-10-NR
PBL-YCABLE-10
MSWR-TV 7
SUNCLIX-FC6-SET
84SMC6-8TL-IEN101040Installation Guide
Page 85
SMA Solar Technology AGContact
13 Contact
If you have technical problems concerning our products, contact the SMA Serviceline We require the
following information in order to provide you with the necessary assistance:
The information contained in this document is the property of SMA Solar Technology AG. Publishing its content, either partially or
in full, requires the written permission of SMA Solar Technology AG. Any internal company copying of the document for the
purposes of evaluating the product or its correct implementation is allowed and does not require permission.
Exclusion of liability
The general terms and conditions of delivery of SMA Solar Technology AG shall apply.
The content of these documents is continually checked and amended, where necessary. However, discrepancies cannot be
excluded. No guarantee is made for the completeness of these documents. The latest version is available online at www.SMA.de
or from the usual sales channels.
Guarantee or liability claims for damages of any kind are excluded if they are caused by one or more of the following:
• Damages during transportation
• Improper or inappropriate use of the product
• Operating the product in an unintended environment
• Operating the product whilst ignoring relevant, statutory safety regulations in the deployment location
• Ignoring safety warnings and instructions contained in all documents relevant to the product
• Operating the product under incorrect safety or protection conditions
• Altering the product or supplied software without authority
• The product malfunctions due to operating attached or neighboring devices beyond statutory limit values
• In case of unforeseen calamity or force majeure
The use of supplied software produced by SMA Solar Technology AG is subject to the following conditions:
• SMA Solar Technology AG rejects any liability for direct or indirect damages arising from the use of software developed by
SMA Solar Technology AG. This also applies to the provision or non-provision of support activities.
• Supplied software not developed by SMA Solar Technology AG is subject to the respective licensing and liability agreements
of the manufacturer.
SMA Factory Warranty
The current guarantee conditions come enclosed with your device. These are also available online at www.SMA.de and can be
downloaded or are available on paper from the usual sales channels if required.
Trademarks
All trademarks are recognized even if these are not marked separately. Missing designations do not mean that a product or brand
is not a registered trademark.
The Bluetooth
Solar Technology AG is under license.