or by any means, electronic, mechanical, photographic, magnetic or otherwise, without the prior
written permission of SMA America,LLC.
SMA America,LLC doesn’t make representations, express or implied, with respect to this
do cum ent ati on o r an y of the equip men t an d/o r so ftw are it m ay d escribe, including (with no limitation)
any implied warranties of utility, merchantability, or fitness for any particular purpose. All such
warranties are expressly disclaimed. Neither SMA America,LLC nor its distributors or dealers shall
be liable for any indirect, incidental, or consequential damage under any circumstances.
(The exclusion of implied warranties may not apply in all cases under some statutes, and thus the
above exclusion may not apply.)
Specifications are subject to change without notice. Every attempt has been made to make this
document complete, accurate and up-to-date. Readers are cautioned, however, that
SMAAmerica,LLC reserves the right to make changes without notice and shall not be responsible for
any damage, including indirect, incidental or consequential damage, caused by reliance on the
material presented, including, but not limited to, omissions, typographical errors, arithmetical errors or
listing errors in the content material.
All trademarks are recognized even if these are not marked separately. Missing designations do not
mean that a product or brand is not a registered trademark.
SMA America, LLC
3801 N. Havana Street
Denver, CO 80239 U.S.A.
Installation ManualSI_TDBOX-IA-eng-IUS1222113
Important Safety InstructionsSMA America, LLC
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the following product:
• Smartformer for Sunny Island
This manual must be followed during installation and maintenance.
The product is designed and tested according to international safety requirements, but as with all
electrical and electronic equipment, certain precautions must be observed when installing and/or
operating the product. To reduce the risk of personal injury and to ensure the safe installation and
operation of the product, you must carefully read and follow all instructions, cautions and warnings
in this manual.
Warnings in this document
A warning describes a hazard to equipment or personnel. It calls attention to a procedure or practice,
which, if not correctly performed or adhered to, could result in damage to or destruction of part or all
of the SMA equipment and/or other equipment connected to the SMA equipment, or in personal
injury.
SymbolDescription
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
NOTICE is used to address practices not related to personal injury.
4SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLCImportant Safety Instructions
Other Symbols in this document
In addition to the safety and hazard symbols described on the previous pages, the following symbols
are also used in this manual:
SymbolDescription
Indicates information that is important for a specific topic or objective, but is not
safety-relevant.
☐Indicates a requirement for meeting a specific goal.
☑Desired result
✖A problem that could occur
Markings on this product
The following symbols are used as product markings with the following meanings.
SymbolDescription
Warning regarding dangerous voltage
The product works with high voltages. All work on the product must only be
performed as described in the documentation of the product.
Risk of Fire
Improper installation of the product may cause a fire.
Beware of hot surface
The product can become hot during operation. Do not touch the product during
operation.
Observe the operating instructions
Read the documentation of the product before working on it. Follow all safety
precautions and instructions as described in the documentation.
UL1741 is the standard applied by Underwriters Laboratories to the product to
certify that it meets the requirements of the NationalElectricalCode
Installation ManualSI_TDBOX-IA-eng-IUS1222115
®
.
General WarningsSMA America, LLC
General Warnings
General Warnings
All electri cal installations m ust be done in accordance with the local and NationalElectrical Code
ANSI/NFPA 70 or the Canadian Electrical Code® CSAC22.1. This document does not and is not
intended to replace any local, state, provincial, federal or national laws, regulation or codes
applicable to the installation and use of the product, including without limitation applicable
electrical safety codes. All installations must conform with the laws, regulations, codes and
standards applicable in the jurisdiction of installation. SMA assumes no responsibility for the
compliance or noncompliance with such laws or codes in connection with the installation of the
product.
The product contains no user-serviceable parts. For all repair and maintenance, always return the
unit to an authorized SMA Service Center.
Before installing or using the product, read all of the instructions, cautions, and warnings in this
manual.
Before connecting the product to the electrical utility grid, contact the local utility company. This
connection must be made only by qualified personnel.
Wiring of the product must be made by qualified personnel only.
This document applies to device type SI-TD-BOX, hardware version 1.0 and higher.
Target Group
This document is for skilled workers. Only qualified personnel are allowed to perform the tasks set
forth in this document (see Section 2.2 "Qualification of Skilled Workers", page 13).
Typography
TypographyUsageExample
"light"• Terminals
• Spring clamp terminals
•Screw terminals
bold• Switch settings that you
should select
• Connect the L conductor of the AC 1
terminal of the Sunny Island to the
lower spring clamp terminal in
connecting terminal plate
"Sunny Island AC1 L".
• To have the connected loads supplied
by the Sunny Island, set the bypass
switch to ION.
Nomenclature
The following nomenclature is used in this document:
Complete designationDesignation in this document
SMA Solar Technology America, LLCSMA
Smartformer for Sunny Island"Smartformer" or "product"
Sunny BoyPV inverter
Abbreviations
AbbreviationDesignationExplanation
ACAlternating Current‒
DCDirect Current‒
PEProtective Earth‒
PVPhotovoltaics‒
Installation ManualSI_TDBOX-IA-eng-IUS12221111
2 SafetySMA America, LLC
SMARTFORMER
Loads
Generator
PV inverter
Battery
PV array
Power
distribution grid
Sunny Island
2Safety
2.1 Intended Use
Figure 1: Principle of a simple Sunny Island system with Smartformer
The Smartformer for Sunny Island is a pre-wired AC distribution board with an autotransformer,
bypass switch, load-shedding contactor, overload protection, and miniature circuit-breakers.
Mounting requirements:
The Smartformer is only suitable for indoor use. Do not mount the Smartformer outdoors.
• Do not mount the Smartformer on flammable construction materials.
• Do not mount the Smartformer near highly flammable materials.
• Do not mount the Smartformer in potentially explosive atmospheres.
12SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC2 Safety
Electrical connection requirements:
The Smartformer must only be used with the following Sunny Island inverters:
• Sunny Island 4548‑US / 6048‑US
• Sunny Island 5048-US with labeling "Smartformer compatible" on the original packaging
Sunny Island 5048-US inverters without labeling "Smartformer compatible" on the original
packaging require an additional fuse outside of the Smartformer for Sunny Island (see
Section6.3 "Selecting Cables", page 36).
The Smartformer may be used with the following PV inverters by SMA:
• Sunny Boy 2000HF-US / 2500HF-US / 3000HF-US
• Sunny Boy 3000-US / 3800-US / 4000-US
• Sunny Boy 5000-US / 6000-US
• In off-grid systems: Sunny Boy 7000-US / 8000-US
A generator or the power distribution grid may be connected to the Smartformer. The generator or
the power distribution grid may supply the Sunny Island system with 120 V on 1 line conductor or
with 240 V on 2 line conductors. A generator and the power distribution grid may only be connected
to the Smartformer at the same time if used with an external automatic transfer switch.
General terms of use:
Only use the Smartformer in accordance with the information provided in the enclosed
documentation. Any other use can result in personal injury or property damage.
The enclosed documentation is an integral part of this product.
• Read and adhere to the documentation.
• Keep the documentation in a convenient place for future reference.
Do not operate the Smartformer if it has technical defects.
For safety reasons, it is forbidden to modify the product or install components that are not explicitly
recommended or distributed by SMA.
2.2 Qualification of Skilled Workers
The tasks described in this document are intended for skilled workers only. Skilled workers must have
the following skills:
• Knowledge about the functional principle and operation of off-grid systems and backup systems
• Knowledge of how to deal with the dangers and risks associated with installing and using
electrical devices
• Knowledge of the installation and commissioning of electrical devices
• Knowledge of all applicable standards and guidelines
• Knowledge of and adherence to this document and all safety precautions
Installation ManualSI_TDBOX-IA-eng-IUS12221113
2 SafetySMA America, LLC
2.3 Safety Precautions
Danger to life due to electric shock
High volt ages that can result in electr ic shocks are present in t he live components of the Smartformer.
• Disconnect the Smartformer from the power supply before performing any work on the
Smartformer (see Section 10).
• Always use a contact hazard protection cover when operating the Smartformer.
• Work on the Smartformer may only be performed by a skilled worker.
• Do not touch live components of the Smartformer or other components of the Sunny Island
system.
Risk of injury due to moving parts
A generator can be started automatically by the Sunny Island. Moving parts in the generator can
crush or sever body parts.
• Only operate the generator with safety equipment provided by the manufacturer.
• Install, maintain, and operate the generator according to the manufacturer's specifications.
Risk of injury due to hot components
Components inside the Smartformer may become hot during operation. This may result in burns to
the body.
• Always use a contact hazard protection cover when operating the Smartformer.
• Allow the Smartformer to cool down before removing the contact hazard protection cover.
Property damage due to moisture and dust intrusion
The Smartformer corresponds to the NEMA 1 degree of protection when it is closed and is only
suitable for indoor installation. The intrusion of dust and moisture into the interior can damage the
Smartformer.
• Protect the Smartformer against moisture and dust.
• After working on the Smartformer, mount the contact hazard protection cover and close the
Smartformer.
• While the Smartformer is open, protect it against dust and water.
14SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC3 Scope of Delivery
3Scope of Delivery
Check the delivery for completeness and any externally visible damage. Contact your specialty
retailer if the delivery is incomplete or you find any damage.
Figure 2: Components included in delivery
PositionQuantityDescription
A1Smartformer
B4Anchorage bracket, sealing ring, and hexagon head screw M6x8
C4Hexagon socket screw M8x12
D28Phillips screw PZ 2
E12-pole miniature circuit-breaker 25 A
F1Upper flange plate
G1 Lower flange plate
H1Installation manual technical description*
* Information about the circuitry of the Smartformer in the Sunny Island can be found in the technical description.
Installation ManualSI_TDBOX-IA-eng-IUS12221115
4 Product DescriptionSMA America, LLC
4Product Description
4.1 Smartformer for Sunny Island
The Smartformer for Sunny Island is a pre-wired AC distribution board with an autotransformer,
bypass switch, load-shedding contactor, overload protection, and miniature circuit-breakers.
Figure 3: Structure of the Smartformer
PositionDescription
ADoor handles
BFlange plate
CVentilation slots
DType label
ERear wall of enclosure with 8 drill holes
The Smartformer is the AC distribution board in a Sunny Island system with 1 Sunny Island. The
Smartformer provides the terminals for all components in the Sunny Island system. The Smartformer
expands the scope of functions of the Sunny Island with the autotransformer, bypass switch, loadshedding contactor, overload protection, and miniature circuit-breakers.
16SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC4 Product Description
Symbols on the Smartformer
SymbolDescriptionExplanation
Spring clamp terminals Some of the terminals of the Smartformer are
executed as spring clamp terminals.
Always connect a conductor to a spring
clamp terminal as described in this document
(see Section 6.5 "Connecting Insulated
Conductors to Spring Clamp
Terminals", page 39).
4.2 Autotransformer
The autotransformer enables the following functions in a Sunny Island:
• Integration of PV inverters with an AC output voltage of 240 V
• Supply of AC loads with 120 V or 240 V
The autotransformer converts the input voltage according to the load requirements, operating in the
step-up and step-down operating modes.
•Step-up:
The Sunny Island makes an AC input voltage of 120 V available. The autotransformer converts
this AC input voltage into an AC output voltage of 240 V. The loads use one AC output with
120 V or both AC outputs with 240 V. A different load on the two 120 V outputs is
compensated by the Smartformer through power transmission.
•Step-down:
The PV inverter makes an AC input voltage of 240 V available. The autotransformer converts
this AC input voltage into an AC output voltage 120 V. The Sunny Island uses this voltage to
load the battery.
Unlike in other transformers, the input circuit and the output circuit of the autotransformer are not
galvanically isolated.
Installation ManualSI_TDBOX-IA-eng-IUS12221117
4 Product DescriptionSMA America, LLC
4.3 Bypass Switch
The bypass switch is a manual automatic transfer switch that makes it possible to directly supply the
loads through the generator or power distribution grid. By directly supplying the loads through the
generator or power distribution grid, the Smartformer bypasses the terminals of the PV plant and
Sunny Island. In this way, the Smartformer simplifies maintenance work and repairs.
Figure 4: Overview of the bypass switch
PositionDescriptionExplanation
ASwitch position "ION"The Sunny Island supplies the loads and, in
doing so, integrates the generator or power
distribution grid, along with the PV plant.
BSwitch position "O OFF"The loads are not supplied with voltage.
CSwitch position "II ON"Generators or power distribution grids supply
the loads directly.
4.4 Load-Shedding Contactor
The load-shedding contactor is an automatic switch-off device used to protect the battery from deep
discharge.
When a predefined charge status limit of the battery is reached, the Sunny Island triggers the loadshedding contactor. The load-shedding contactor disconnects the loads from the Sunny Island system.
By doing so, the Sunny Island prevents deep battery discharge.
18SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC4 Product Description
4.5 Miniature Circuit-Breaker
The miniature circuit-breakers protect the connected conductors against destruction due to
overheating. Each of the miniature circuit-breakers can be manually activated or can be tripped
automatically.
To be able to trip automatically, each miniature circuit-breaker monitors the electric current in the
connected conductors. When the current becomes too high, the miniature circuit-breaker interrupts the
flow of current and thus prevents overheating of the conductors.
Figure 5: Overview of the miniature circuit-breakers
PositionDescriptionExplanation
AUpper switch positionThe miniature circuit-breaker is closed.
BLower switch positionThe miniature circuit-breaker is open.
Installation ManualSI_TDBOX-IA-eng-IUS12221119
4 Product DescriptionSMA America, LLC
4.6 Overload Protection
The overload protection protects the autotransformer against damage from overheating or a short
circuit. The overload protection identifies overheating or a short circuit by monitoring the currents in
the autotransformer. If currents become too high, the overload protection is tripped with a predefined
time delay. The time delay prevents tripping of the overload protection during brief switch-on current
peaks.
Figure 6: Overview of the overload protection
PositionDescriptionExplanation
ASwitch position "1"The overload protection is in its normal operating state.
Current is flowing through the primary side and the secondary
side of the autotransformer.
BSwitch position "0"The overload protection has been tripped. The current flow is
interrupted on the secondary side of the transformer.
20SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC4 Product Description
4.7 Type Label
The type label provides a unique identification of the Smartformer. The type label is on the right-hand
side of the enclosure.
Figure 7: Layout of the type label
PositionDescriptionExplanation
AModelDevice type
BSerial No.Serial number of the Smartformer
CDate of manufacture–
DDevice-specific characteristics‒
Installation ManualSI_TDBOX-IA-eng-IUS12221121
5 MountingSMA America, LLC
5Mounting
5.1 Selecting the Mounting Location
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
• Do not mount the Smartformer on flammable construction materials.
• Do not mount the Smartformer near highly flammable materials.
• Do not mount the Smartformer in potentially explosive atmospheres.
Danger to life due to electric shock
Penetrating moisture may result in voltage being applied to parts of the mounting location.
• Do not mount the Smartformer outdoors.
Destruction of the Smartformer due to direct solar irradiation
Direct solar irradiation can damage the paintwork on the Smartformer enclosure and lead to
enclosure corrosion.
• Ensure that the Smartformer is not exposed to direct solar irradiation.
Requirements for the mounting location:
☐ A firm surface must be available for mounting, such as a masonry wall, studs, or posts. In living
areas, make sure that the surface is no t ma de o f pl ast erb oar d or similar. The Smartformer makes
noises when in use, which can be regarded as a nuisance.
☐ The mounting location must be suitable for the weight and dimensions of the Smartformer
(see Section 14 "Technical Data", page 64).
☐ The mounting location is clear and has safe access at all times without any additional aids being
necessary (such as scaffolding or lifting platforms). Non-fulfillment of these criteria may restrict
servicing.
☐ The ambient conditions are met (see Section 14 "Technical Data", page 64). This ensures
optimal operation of the Smartformer.
☐ The mounting location must not be exposed to direct solar irradiation.
22SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC5 Mounting
Observe minimum clearances:
Figure 8: Minimum clearances
Destruction of the Smartformer due to insufficient heat dissipation
The Smartformer can overheat if there is insufficient heat dissipation. Frequent overheating can
destroy the Smartformer in the long term.
• Maintain the minimum clearance to walls and adjacent devices or objects. As a result,
sufficient heat dissipation is ensured.
• If the Smartformer is installed together with other electrical devices in areas with high ambient
temperatures, increase the distances between the Smartformer and the other electrical devices
and provide a sufficient fresh-air supply. This prevents the Smartformerfrom drawing in the
exhaust air from adjacent devices.
• Make sure that there is a distance of at least 391⁄2 in. (1 000 mm) between the door of the
Smartformer and any obstacle in front of it. This makes it easier to open the door of the
Smartformer.
Installation ManualSI_TDBOX-IA-eng-IUS12221123
5 MountingSMA America, LLC
Selecting the positions of the anchorage brackets on the enclosure rear wall:
Before mounting the anchorage brackets, select 1 of the following 3 options for positioning the
anchorage brackets. This determines the position of the 4 drill holes.
Figure 9: Dimensions with outer drill holes and vertical position of anchorage brackets
Figure 10: Dimensions with inner drill holes and vertical position of anchorage brackets
24SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC5 Mounting
Figure 11: Dimensions with outer drill holes and horizontal position of anchorage brackets
• When mounting the Smartformer on a wooden wall, ensure that the distance between the
middle of one stud and the middle of the next stud equals the horizontal distance between the
drill holes.
Observe permitted mounting position:
Figure 12: Permitted mounting position and prohibited mounting position
• Mount the Smartformer in the permitted mounting position.
• Position the upper enclosure side horizontally. Tip: Use a spirit level.
Installation ManualSI_TDBOX-IA-eng-IUS12221125
5 MountingSMA America, LLC
5.2 Mounting the Anchorage Brackets on the Enclosure Rear Wall
Risk of injury due to falling Smartformer
Due to its heavy weight, the Smartformer can crush or break bones if it falls.
• When mounting, take into account the weight of the Smartformer, which is 132
• Make sure that the Smartformer does not tilt or move out of position during mounting.
1. Place the Smartformer on a firm substructure and
open the enclosure door using the door handles.
2. Disassemble the contact hazard protection cover (see Section 9.1).
3. 2 position anchorage brackets on the upper drill
holes in the enclosure rear wall. When doing so,
ke ep t he a nchor age bra cke ts i n the c hos en p osi tion
and align the metal bars of the anchorage bracket
with the enclosure door.
1
⁄2lbs. (60 kg).
4. Screw on both anchorage brackets:
• Insert the hexagon socket screw with the sealing
ring through the drill hole from the inside and
into the thread of the anchorage bracket.
26SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC5 Mounting
• Tighten the hexagon socket screw
(torque: 88 in-lbs. (10 Nm)).
Use a torque wrench with an attachment for
hexagon socket screws 3⁄16in. (5 mm).
5. Turn the Smartformer by 180°.
6. 2 position anchorage brackets on the upper drill
holes in the enclosure rear wall. When doing so,
ke ep t he a nchor age bra cke ts i n the c hos en p osi tion
and align the metal bars of the anchorage bracket
with the enclosure door.
7. Screw on both anchorage brackets.
• Insert the hexagon socket screw with the sealing
ring through the drill hole from the inside and
into the thread of the anchorage bracket.
• Tighten the hexagon socket screw
(torque: 88 in-lbs. (10 Nm)).
Use a torque wrench with an attachment for
hexagon socket screws
Installation ManualSI_TDBOX-IA-eng-IUS12221127
3
⁄16in. (5 mm).
5 MountingSMA America, LLC
5.3 Mounting the Smartformer on a Masonry Wall
Additional required mounting material (not included in the scope of delivery):
☐ 4 screws that are suitable for the mounting substructure and the weight of the Smartformer
(minimum diameter:5⁄16 in. (8 mm), minimum length: 11⁄2in. (40 mm)).
☐ 4 screw anchors that are suitable for the mounting substructure and the size of the screws.
Requirements:
☐ The mounting location must be defined.
☐ The 4 anchorage brackets must be mounted on the enclosure rear wall.
1. Mark the positions of the 4 drill holes on the wall. Adhere to the dimensions of the Smartformer
with the mounted anchorage brackets (see Section 5.1 "Selecting the Mounting
Location", page 22).
2. Ensure that there are no electric lines or other supply lines in the wall behind the marked
positions.
3. Drill the holes. Ensure that the diameter of each drill hole matches the diameter of the screw
anchor.
4. Insert 4 screw anchors into the drill holes.
5. Screw the screws into the wall. Allow the screw heads to protrude at least
3
/8 in. (10 mm) from
the wall.
28SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC5 Mounting
6.
Risk of injury due to falling Smartformer
Due to its heavy weight, the Smartformer can crush or break bones if it falls.
• Hang the Smartformer onto the screws and
carefully slide it into the guides of the
anchorage brackets. When doing so, note
that the weight of the Smartformer is
1
132
⁄2lbs. (60 kg) and make sure that the
Smartformer does not tilt or slip out of place
during mounting.
7. Ti ght en t he scr ews in t he wal l fi rml y. Use a to rqu e wren ch w ith a suitable attachment and adhere
to the maximum torque specified for the screws used.
5.4 Mounting the Smartformer on a Wooden Wall
Additional required mounting material (not included in the scope of delivery):
☐ 4 screws that are suitable for the mounting substructure and the weight of the Smartformer
(minimum diameter:
Requirements:
☐ The mounting location must be defined.
☐ The 4 anchorage brackets must be mounted on the enclosure rear wall.
☐ The 4 anchorage brackets must be positioned so that each drill hole can be drilled into a stud.
5
⁄16 in. (8 mm), minimum length: 11⁄2in. (40 mm)).
1. Mark the positions of the 4 drill holes on the wall. Adhere to the dimensions of the Smartformer
with the mounted anchorage brackets (see Section 5.1 "Selecting the Mounting
Location", page 22).
2. Ensure that there are no electric lines or other supply lines in the wall behind the marked
positions.
3. Drill the holes. The diameter of each drill hole must be approx. 1 mm smaller than the diameter
of the screws used.
4. Screw the screws into the wall. Allow the screw heads to protrude at least
3
/8 in. (10 mm) from
the wall.
Installation ManualSI_TDBOX-IA-eng-IUS12221129
5 MountingSMA America, LLC
5.
Risk of injury due to falling Smartformer
Due to its heavy weight, the Smartformer can crush or break bones if it falls.
• Hang the Smartformer onto the screws and
carefully slide it into the guides of the
anchorage brackets. When doing so, note
that the weight of the Smartformer is
1
132
⁄2lbs. (60 kg) and make sure that the
Smartformer does not tilt or slip out of place
during mounting.
6. Ti ght en t he scr ews in t he wal l fi rml y. Use a to rqu e wren ch w ith a suitable attachment and adhere
to the maximum torque specified for the screws used.
30SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC6 Electrical Connection
6Electrical Connection
6.1 Safety during Electrical Connection
Danger to life due to electric shock
High volt ages that can result in electr ic shocks are present in t he live components of the Smartformer.
• Disconnect the Smartformer from the power supply before performing any work on the
Smartformer (see Section 10).
• Always use a contact hazard protection cover when operating the Smartformer.
• Work on the Smartformer may only be performed by a skilled worker.
• Do not touch live components of the Smartformer or other components of the Sunny Island
system.
Risk of lethal electric shock due to faulty grounding
There may be only 1 conducting connection between N and PE in the entire Sunny Island system.
Any further connections disturb the fault current detection and can lead to electric shock.
• Establish 1 connection between N and PE in the AC main distribution unit. Observe the
National Electrical Code
apply.
• Make sure that there are no other connections between N and PE in the entire Sunny Island
system.
®
, ANSI/NFPA 70 and all local standards and regulations that may
Destruction of the Smartformer due to cables coming loose
The insulated conductors can become detached from the terminals due to their heavy weight,
thereby damaging or destroying the Smartformer.
• Use cable conduits to insert the cables into the Smartformer.
• Use the cable clamps within the Smartformer to clamp the cables.
Installation ManualSI_TDBOX-IA-eng-IUS12221131
6 Electrical ConnectionSMA America, LLC
6.2 Overview of the Connection Area
6.2.1 View from Below
Figure 13: Flange plate with knockouts on the bottom of the Smartformer
PositionDescriptionSuitable conduit for connection (diameter)
3
AKnockouts
⁄4 in. (19 mm)
BKnockouts1 in. (25 mm)
1
CKnockouts1
⁄4in. (32 mm)
6.2.2 View from Above
Figure 14: Flange plate with knockouts on the upper side of the Smartformer
PositionDescriptionSuitable conduit for connection (diameter)
AKnockouts
3
⁄4 in. (19 mm)
BKnockouts1 in. (25 mm)
1
CKnockouts1
32SI_TDBOX-IA-eng-IUS122211Installation Manual
⁄4in. (32 mm)
SMA America, LLC6 Electrical Connection
6.2.3 Interior View
Figure 15: Electrical connection area of the Smartformer
PositionDescriptionColorExplanation
ACable clamps‒For clamping the cables when cables
are inserted via the upper flange plate.
BConnecting terminal blocks
"Relay2: C", "Relay2: NC" with
spring clamp terminals
CConnecting terminal blocks
"Grounding" with spring clamp
terminals
BlackFor connecting the Sunny Island to the
load-shedding contactor in the
Smartformer
Yellow/
green
For connecting PE of the AC
sub-distribution for the loads, the
PV plant, the Sunny Island, and the
generator or the power distribution grid
and for grounding the protection against
contact
Installation ManualSI_TDBOX-IA-eng-IUS12221133
6 Electrical ConnectionSMA America, LLC
PositionDescriptionColorExplanation
DConnecting terminal
blocks"Load L1", "Load L2"
Black/red For connecting L1 and L2 of the AC
sub-distribution for the loads
with spring clamp terminals
EConnecting terminal blocks
"Neutral N" with spring clamp
terminals
GrayFor connecting N of the AC sub-
distribution for the loads, the PV plant,
the Sunny Island, and the generator or
the power distribution grid
FConnecting terminal blocks
"Sunny Island AC2 L"with
BlackFor connecting L of the AC 2 terminal of
Sunny Island
spring clamp terminals
GConnecting terminal blocks
"Sunny Island AC1 L"with
BlackFor connecting L of the AC 1 terminal of
Sunny Island
spring clamp terminals
H2-pole miniature circuit-breaker
"F6"and "F7" with screw
terminals
Black/red For connecting L or L1 and L2 of the
generator or for connecting L1 and L2 of
the power distribution grid
"Grid or Generator L/L1",
"Grid or Generator L2"
I2-pole miniature circuit-breaker
Black/red For connecting L1 and L2 of the PV plant
"F4" and "F5" with screw
terminals "Sunny Boy L1",
"Sunny Boy L2"
K2-pole miniature circuit-breaker
‒See Section 4.5
"F2" and "F3"
L1-pole miniature circuit-breaker
See Section 4.5
"F1"
MBypass switch‒See Section 4.3
NOverload protection‒See Section 4.6
OContact hazard protection
cover*
* The contact hazard protection cover is shown as semi-transparent.
"F7"When the bypass switch is set to "II ON", "F7" protects the
ATSAutomatic Transfer
circuit-breaker
circuit-breaker
circuit-breaker
Switch
When the bypass switch is set to "ION", "F2" and "F3"
protect the loads.
"F4" and "F5" protect the PV inverters.
When the bypass switch is set to "II ON", "F6" protects the
loads and the generator.
When the bypass switch is set to "ION", "F6" protects the
AC 2 output of the Sunny Island.
loads and the generator.
Automatic transfer switch: not included in scope of delivery
Installation ManualSI_TDBOX-IA-eng-IUS12221135
6 Electrical ConnectionSMA America, LLC
6.3 Selecting Cables
Cable requirements:
☐ Conductor material: copper
☐ Conductor structure: solid wire, coarse stranded wire, or fine stranded wire
☐ The cable must be approved for 167°F (75°C).
☐Maximum wire size: 4AWG
Minimum wire sizes
Components for connectionMinimum wire size
Loads6 AWG
PV plant with miniature circuit-breaker 25 A10 AWG
PV plant with miniature circuit-breaker 50 A6 AWG
Generator or power distribution grid6 AWG
Sunny Island: AC 1 terminal4 AWG*
Sunny Island: AC 2 terminal6 AWG
* Valid for Sunny Island 4548-US / 6048-US an d for Sunny I sland 5048-US with labeling "Smartformer compatible" on the
original packaging
• Make sure that the general cable requirements are adhered to.
• Make sure that minimum and maximum wire sizes are adhered to.
If you connect a Sunny Island 5048-US without labeling "Smartformer compatible" on the original
packaging, observe the following procedure:
• Select a wire size of 6 AWG for the AC 1 connection cable of the Sunny Island.
• Fuse the AC 1 connection cable of the Sunny Island outside of the Smartformer. Use a 60 A
miniature circuit-breaker, for example.
• In order to avoid excessive tripping of the 60 A miniature circuit-breaker, limit the rated power
of the loads to 5.8 kW.
36SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC6 Electrical Connection
6.4 Inserting the Cables
Insert each cable into the Smartformer according to the following procedure.
Risk of injury due to cable fire
Hot fluids that arise during a cable fire can emerge from the open knockouts in the bottom flange
plate.
• Make sure that all knockouts that have be opened for introducing cables are in use.
• Close unused knockouts with a suitable material.
1. Open the Smartformer using the two door handles.
2. Disassemble the contact hazard protection cover (see Section 9.1).
3. Select the conduit that matches the external diameter of the chosen cable (see Section 6.2.1
or Section 6.2.2). Take the National Electrical Code
applicable standards and regulations into consideration.
4. Select the flange plate for inserting the cable:
• To introduce the cable from below into the Smartformer, select the lower flange plate.
• To introduce the cable from above into the Smartformer, select the upper flange plate.
5. Select the knockout that matches the conduit (see Section 6.2.1 and Section 6.2.2).
6. Open the selected knockout using a hammer and
screwdriver. Tip: Open all knockouts for the upper
or lower flange plate before reinserting the flange
plates.
®
, ANSI/NFPA 70, and all locally
7.
Destruction of the thread if flange plate is mounted multiple times
When they are being screwed in, the PZ 2 screws cut a thread into the Smartformer enclosure.
Screwing them in more than once destroys this thread. This means that the flange plates are no
long screwed tight.
• Make sure that all required knockouts have been opened before the flange plate is
mounted.
• The flange plates must not be screwed to the enclosure more than once.
Installation ManualSI_TDBOX-IA-eng-IUS12221137
6 Electrical ConnectionSMA America, LLC
8. Insert the flange plates into the Smartformer:
• Hold the lower flange plate against the
Smartformer enclosure and tighten the
14 PZ 2 screws (torque: 25 in-lbs. (2.8 Nm)).
Use a torque wrench with a PZ 2 attachment or
another suitable cross-head screwdriver
attachment.
• Hold the upper flange plate against the
Smartformer enclosure and tighten the
14 PZ 2 screws (torque: 25 in-lbs. (2.8 Nm)).
Use a torque wrench with a PZ 2 attachment
or another suitable cross-head screwdriver
attachment.
9. Install the cable conduit between the Smartformer
and the components being connected.
10. Attach the conduit on the inside of the Smartformer
with a counter nut.
11. If a metal cable conduit is used, ground the cable conduit according to the locally applicable
standards and regulations. Tip: You can use a vacant terminal of the "Grounding" connecting
terminal plate to ground the conduit.
12. Insert the cable of the components being connected through the cable conduit into the
Smartformer.
13. If the cable is being introduced into the Smartformer from above, attach the cable with a cable
tie to one of the cable clamps. Use a cable length that reaches to the specified terminal.
14. Make sure that all opened knockouts are closed again.
38SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC6 Electrical Connection
6.5 Connecting Insulated Conductors to Spring Clamp Terminals
Some of the terminals of the Smartformer are executed as spring clamp terminals. Always use the
following procedure when connecting an insulated conductor to a spring clamp terminal. A different
procedure applies for connecting the insulated conductors on the load-shedding contactor
(see Section 6.10 "Connecting the Load-Shedding Contactor", page 44).
Required tools:
☐ Screwdriver (maximum blade width: 5.5 mm)
1. Insert the cable (see Section 6.4).
2. Remove the coating.
3. Shorten insulated conductors by at least
corroded conductor material.
4. Strip the insulation of the insulated conductors by 3⁄4 in. (19 mm).
5. Route the insulated conductors to the connecting terminal plate provided.
6. Connect the conductors to the spring clamp terminals. Note that there is 1 possible procedure
for a conductor with a bootlace ferrule and 1 possible procedure for a conductor made of
coarse stranded wire or solid wire:
• To connect a conductor with a bootlace ferrule,
a conductor made of coarse stranded wire or
solid wire, or a conductor made of fine stranded
wire, push a screwdriver into the terminal
contact of the spring clamp terminal and insert
the conductor into the terminal up to the limit
position.
3
⁄8in. (10 mm). This removes any damaged or
• To connect a conductor with a bootlace ferrule
or a conductor made of coarse stranded wire or
solid wire, push the conductor into the terminal
up to the limit position.
Installation ManualSI_TDBOX-IA-eng-IUS12221139
6 Electrical ConnectionSMA America, LLC
6.6 Connecting Loads
There are two ways to connect loads.
• AC main distribution unit:
In a backup system, some of the loads can be connected to the AC main distribution unit.
Th e ge ner ato r or th e po wer distr ibu tio n gr id dir ect ly s upp lie s all loads connected to the AC main
distribution unit. These loads are not integrated into the Sunny Island system.
• AC sub-distribution:
In a st and -al one gri d, a ll loa ds a re c onn ect ed t o th e AC sub -di stribution behind the Smartformer.
The Smartformer and the Sunny Island supply the loads connected to the AC sub-distribution
behind the Smartformer.
This section describes the connection of the AC sub-distribution for the loads to the Smartformer.
Connecting loads to the AC sub-distribution
The power requirement of the loads should be designed in accordance with the nominal power
of the Sunny Island.
• To minimize the transmission losses, connect frequently used loads or loads with a high
power consumption to the "Load L1" terminal block via the AC sub-distribution. The
requirement of the loads should not exceed a nominal current of 32 A at "Load L1".
• If the Sunny Island with power distribution grid or generator is the only power supply, all
loads connected to terminal block "Load L2" are supplied via the autotransformer, which
is fused with 32 A.
• The continual requirement of the loads should not exceed a nominal current of 28 A at
"Load L2".
1. Connect the PE conductor to a vacant spring clamp terminal of a "Grounding" connecting
terminal plate (see Section 6.5).
2. Connect the N conductor to a vacant spring clamp terminal of a "Neutral N" connecting
terminal plate (see Section 6.5).
3. Connect the L1 conductor to the lower spring clamp terminal of the "Load L1" connecting
terminal plate (see Section 6.5).
4. Connect the L2 conductor to the lower spring clamp terminal of the "Load L2" connecting
terminal plate (see Section 6.5).
40SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC6 Electrical Connection
6.7 Connecting the PV Plant
Danger to life due to fire in incorrectly connected PV inverter
An excessive current load can overheat the AC connection of the PV inverter and cause a cable fire.
• Protect the AC output of each PV inverter according to the maximum permissible AC electrical
current strength (see the PV inverter installation manual).
• If 1 PV inverter is connected to the Sunny Island system, protect the PV inverter with miniature
circuit-breakers "F4" and "F5" of the Smartformer.
• If several PV inverters are connected to the Sunny Island system, install the AC sub-distribution
for the PV plant according to the locally applicable standards and regulations, and protect
the PV inverters individually.
• When selecting the wire size, consult the PV inverter installation manual and adhere to the
locally applicable standards and regulations.
PV inverterRated current Replace the miniature
circuit-breaker?
Sunny Boy 2000HF-US / 2500HF-US / 3000HF-US 25 AYes: see Section 12.2
Sunny Boy 3000-US / 3800-US / 4000-US25 AYes: see Section 12.2
Sunny Boy 5000-US / 6000-US50 ANo*
In stand-alone grids:
Sunny Boy 7000-US /8000-US
*The "F4" and "F5" miniature circuit-breakers of the Smartformer are preinstalled with 50 A on delivery.
50 ANo*
1. Make sure that each PV inverter is protected in the Smartformer or in the AC sub-distribution of
the PV plant according to its rated current (see the PV inverter installation manual).
2. Connect the PE conductor to a vacant spring clamp terminal of a "Grounding" connecting
terminal plate (see Section 6.5).
3. Connect the N conductor to a vacant spring clamp terminal of a "Neutral N" connecting
terminal plate (see Section 6.5).
4. Shorten insulated conductors L1 and L2 and strip the insulation by
Installation ManualSI_TDBOX-IA-eng-IUS12221141
3
⁄8in. (10 mm).
6 Electrical ConnectionSMA America, LLC
5. Connect the L1 conductor to the lower
screw terminal "Sunny Boy L1" of the miniature
circuit-breaker "F4" and tighten screw
(torque: 25 in-lbs. (2.8 Nm)). Use a torque wrench
with a PZ 2 attachment or another suitable
cross-head screwdriver attachment.
6. Connect the L2 conductor to the lower
screw terminal "Sunny Boy L2" of the miniature
circuit-breaker "F5" and tighten screw
(torque: 25 in-lbs. (2.8 Nm)). Use a torque wrench
with a PZ 2 attachment or another suitable
cross-head screwdriver attachment.
6.8 Connecting the Generator or Power Distribution Grid
When connecting to the power distribution grid, proceed as described below for the generator.
1. Connect the PE conductor to a vacant spring clamp terminal of a "Grounding" connecting
terminal plate (see Section 6.5).
2. Connect the N conductor to a vacant spring clamp terminal of a "Neutral N" connecting
terminal plate (see Section 6.5).
3. To connect a single-phase generator, connect conductor L of the generator.
• Strip the insulation of insulated conductor L by
• Connect the L conductor to the lower screw
terminal "Grid or Generator L/L1" of the
miniature circuit-breaker "F6" and tighten screw
(torque: 25 in-lbs. (2.8 Nm)). Use a torque
wrench with a PZ 2 attachment or another
suitable cross-head screwdriver attachment.
3
⁄8in. (10 mm).
42SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC6 Electrical Connection
4.
Destruction of the generator due to uneven power reduction
If the connected loads are supplied by the Sunny Island, the Smartformer only transfers the
power provided by the split-phase generator via L1. This uneven power reduction may destroy
the generator.
• Make sure that the split-phase generator being used is approved for uneven power
reduction (see manufacturer's documentation for the generator).
or
• Connect 1-phase generator.
or
• Also install 1 Smartformer or an autotransformer.
5. To connect a split-phase generator, connect conductors L1 and L2 of the generator:
• Strip the insulation of insulated conductors L1 and L2 by
3
⁄8in. (10 mm).
• Connect the L1 conductor to the lower screw
terminal "Grid or Generator L/L1" of miniature
circuit-breaker "F6" and tighten screw
(torque: 25 in-lbs. (2.8 Nm)). Use a torque
wrench with a PZ 2 attachment or another
suitable cross-head screwdriver attachment.
• Connect the L2 conductor to the lower screw
terminal "Grid or Generator L2" of the miniature
circuit-breaker "F7" and tighten screw
(torque: 25 in-lbs. (2.8 Nm)). Use a torque
wrench with a PZ 2 attachment or another
suitable cross-head screwdriver attachment.
6.9 Connecting the Sunny Island
1. Connect each of the PE conductors to a vacant spring clamp terminal of a "Grounding"
connecting terminal plate (see Section 6.5).
2. Connect each of the N conductors to a vacant spring clamp terminal of a "Neutral N"
connecting terminal plate (see Section 6.5).
3. Connect the L conductor of the AC 1 terminal of the Sunny Island to the lower spring clamp
terminal of the "Sunny Island AC1 L" connecting terminal plate (see Section 6.5).
4. Connect the L conductor of the AC 2 terminal of the Sunny Island to the lower spring clamp
terminal of the "Sunny Island AC2 L" connecting terminal plate (see Section 6.5).
Installation ManualSI_TDBOX-IA-eng-IUS12221143
6 Electrical ConnectionSMA America, LLC
6.10 Connecting the Load-Shedding Contactor
Cable requirements:
☐ Conductor material: copper
☐ Minimum wire size: 18 AWG
☐ Maximum wire size: 14 AWG
☐ The cable must be approved for 167°F (75°C).
☐ The cable must be approved for AC 120 V.
Selecting a wire size:
• Choose the dimension of the wire size according to the maximum electrical current strength
which occurs at the terminals of the Smartformer (maximum electrical current strength: AC 3 A).
Overview:
Figure 17: Connecting the load-shedding contactor to the Sunny Island
Required tools:
☐ Screwdriver (maximum blade width: 2.5 mm)
1. Insert 2 insulated conductors into the Sunny Island and route to the terminal of the
multi-function relay 2 (see technical description of the Sunny Island).
2. Connect both insulated conductors to the 3-pin terminal supplied with the Sunny Island.
Use the contacts "C" and "NC" and label the insulated conductors accordingly.
4. Insert the terminal into the "Relay 2" connection in the Sunny Island.
5. Introduce both insulated conductors into the Smartformer (see Section 6.4).
6. Shorten both insulated conductors and strip the insulation by
44SI_TDBOX-IA-eng-IUS122211Installation Manual
3
⁄8in. (10 mm).
SMA America, LLC6 Electrical Connection
7. Connect the NC conductor to the lower spring clamp terminal of the "Relay2: NC"
connecting terminal plate. Note that there is 1 possible procedure for a conductor with a
bootlace ferrule and 1 possible procedure for a conductor made of coarse stranded wire or
solid wire:
• To connect a conductor with a bootlace ferrule,
a conductor made of coarse stranded wire or
solid wire, or a conductor made of fine stranded
wire, push a screwdriver into the terminal
contact of the spring clamp terminal and insert
the conductor into the terminal up to the limit
position.
• To connect a conductor with a bootlace ferrule
or a conductor made of coarse stranded wire or
solid wire, push the conductor into the terminal
up to the limit position.
8. Connect the C conductor to the lower spring clamp terminal of the "Relay2: C"
connecting terminal plate. Proceed as described in step 7.
Installation ManualSI_TDBOX-IA-eng-IUS12221145
7 CommissioningSMA America, LLC
7Commissioning
Requirements:
☐ The Smartformer must be mounted properly.
☐ All conduits must be correctly installed and attached.
☐ All lines must be connected correctly.
☐ The contact hazard protection cover must be mounted.
☐ All knockouts in the flange plates must be closed.
☐ The bypass switch must be set to O OFF.
☐ The overload protection must be set to 0.
☐ The switches of the miniature circuit-breakers "F1" to "F7" must be in the lower position.
☐ The generator must be switched off.
☐ There must be no connection to the power distribution grid.
1. Start the Sunny Island (see technical description of the Sunny Island).
2. Start the PV inverters (see the PV inverter installation manual).
☑ The PV inverters check the grid conditions.
3. Set the PV inverters to stand-alone operation (see the PV inverter installation manual).
4. Set the overload protection to 1.
46SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC7 Commissioning
5. Mo ve t he swi tch es o f mini atu re cir cui t-bre ake rs " F4"
and "F5" to the upper position.
6. Check whether the PV plant feeds into the Sunny Island system.
If the PV plant does not feed into the Sunny Island system, check the installation of the
Smartformer:
• Check the connection of the Sunny Island to the Smartformer (see Section 6.9).
• Check the connection of the PV plant to the Smartformer (see Section 6.7).
7. Set the bypass switch to ION.
8. Mo ve t he swi tch es o f mini atu re cir cui t-bre ake rs " F2"
and "F3" to the upper position.
9. Check whether the loads are being supplied with voltage.
If the loads are not being supplied with voltage, check the connection of the loads to the
Smartformer (see Section 6.6).
Installation ManualSI_TDBOX-IA-eng-IUS12221147
7 CommissioningSMA America, LLC
10. Set the bypass switch to II ON.
11. Check whether the bypass switch interrupts the supply to the loads.
If the loads continue to be supplied with voltage, check the connection of the loads to the
Smartformer (see Section 6.6).
12. Start the generator or connect the power distribution grid.
13 . Mov e the s witch es o f mini atu re c irc uit-b rea kers " F6"
and "F7" to the upper position.
14. Check whether the generator or the power distribution grid is supplying the loads with voltage.
If the loads are not being supplied with voltage, check the connection of the generator or the
power distribution grid to the Smartformer (see Section 6.8).
15. Set the bypass switch to ION.
☑ The Sunny Island synchronizes with the
generator or the power distribution grid and
takes over supply of the loads.
48SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC7 Commissioning
16. Move the switch of miniature circuit-breaker "F1" to
the upper position.
17. If the load-shedding contactor is connected, set the parameter "241.02 Rly2Op" on the
Sunny Island to Off(see technical description of the Sunny Island). This triggers the
load-shedding contactor of the Smartformer.
18. Check whether the load-shedding contactor interrupts the supply of the loads.
If the load-shedding contactor does not interrupt the supply of the loads, check the connection
of the load-shedding contactor to the Sunny Island (see Section 6.10 "Connecting the LoadShedding Contactor", page 44).
19. If the load-shedding contactor is connected, set the parameter "241.02 Rly2Op" on the
Sunny Island to AutoLodExt (see technical description of the Sunny Island). This is used to set
the desired function of the load-shedding contactor.
Installation ManualSI_TDBOX-IA-eng-IUS12221149
8 Setting the Operating Mode via the Bypass SwitchSMA America, LLC
8Setting the Operating Mode via the Bypass Switch
• To have the connected loads supplied by the
Sunny Island, set the bypass switch to ION.
• To have the connected loads supplied only by the
generator or power distribution grid, set the bypass
switch to II ON.
• To switch off the supply of the loads, set the bypass
switch to OOFF.
50SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC9 Mounting and Disassembling the Contact Hazard Protection Cover
9Mounting and Disassembling the Contact Hazard
Protection Cover
Danger to life due to electric shock
High volt ages that can result in electr ic shocks are present in t he live components of the Smartformer.
• Disconnect the Smartformer from the power supply before performing any work on the
Smartformer (see Section 10).
• Always use a contact hazard protection cover when operating the Smartformer.
• Work on the Smartformer may only be performed by a skilled worker.
• Do not touch live components of the Smartformer or other components of the Sunny Island
system.
Risk of burns due to hot components
Components inside the Smartformer may become hot during operation.
• Always use a contact hazard protection cover when operating the Smartformer.
• Allow the Smartformer to cool down before removing the contact hazard protection cover.
Installation ManualSI_TDBOX-IA-eng-IUS12221151
9 Mounting and Disassembling the Contact Hazard Protection CoverSMA America, LLC
9.1 Disassembling the Contact Hazard Protection Cover
1. Disconnect the Smartformer from the power supply (see Section 10).
2. Ensure that the Smartformer has cooled down.
3. Relea se th e fa stenin g screw of th e gr ound ing cable.
Keep the fastening screw, split lock washer, and
contact washer safe.
4. Release 6 fastening screws of the contact hazard
protection cover.
5. Pull the right side of the contact hazard protection
cover forwards and, with the cover at an angle,
remove the contact hazard protection cover in a
straight movement forwards out of the Smartformer.
Do not touch any components or terminals in doing
so.
6. Secure the terminal lug of the grounding cable with adhesive tape to the bottom right of the
Smartformer enclosure wall.
52SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC9 Mounting and Disassembling the Contact Hazard Protection Cover
9.2 Mounting the Contact Hazard Protection Cover
1. Ensure that the Smartformer is disconnected from the power supply (see Section 10).
2. Position the left side of the contact hazard
protection cover against the right-hand side of the
Smartformer and, with the cover at an angle to the
left, push back the contact hazard protection cover
in a straight movement. Do not touch any
components or terminals in doing so.
3. Lower the right-hand side of the contact hazard protection cover towards the back.
☑ Contact hazard protection cover is in place in
the Smartformer.
Installation ManualSI_TDBOX-IA-eng-IUS12221153
9 Mounting and Disassembling the Contact Hazard Protection CoverSMA America, LLC
4. Align the contact hazard protection cover with the
6 spacers. The mounting openings of the contact
hazard protection cover must be positioned directly
above the inner threads of the spacers.
5. Tighten the 6 fastening screws of the contact
hazard protection cover (torque: 45 in-lbs. (5 Nm).
Use a torque wrench with an attachment for
hexagon-socket screws
3
⁄16 in. (5 mm).
6. Mount the split lock washer, terminal lug, and
contact washer onto the screw and tighten
(torque: 45 in-lbs. (5 Nm)). Use a torque wrench
with an attachment for hexagon-socket screws
3
⁄16 in. (5 mm).
54SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC10 Disconnecting the Smartformer from the Power Supply
10 Disconnecting the Smartformer from the Power
Supply
1. Switch off the loads.
2. Set the bypass switch to OOFF.
3. Set the overload protection to 0.
4. Move the switch of miniature circuit-breakers "F1"
to "F7" to the lower position.
5. If there is a PV array, switch off the PV array and ensure that it cannot be reconnected
(see the PV array manual).
6. If there is a power distribution grid, switch off the power supply from the power distribution grid
and ensure that it cannot be reconnected. Follow the instructions from the local grid operator.
7. Disconnect the PV inverter from the power supply (see PV inverter manual).
Installation ManualSI_TDBOX-IA-eng-IUS12221155
10 Disconnecting the Smartformer from the Power SupplySMA America, LLC
8.
Risk of lethal electric shock due to unnoticed start of the Sunny Island
The Sunny Island can start on its own from standby.
• Disconnect the Sunny Island from the power supply (see technical description of the
Sunny Island).
9. Ensure that the Sunny Island system with the Smartformer cannot be reconnected.
10. Ascertain that the Sunny Island system and the Smartformer are dead.
11. Ground and short circuit the Sunny Island system at the connection of the generator or the
power distribution grid.
12. Cover or shield any adjacent live components.
56SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC11 Cleaning
11 Cleaning
Cleaning the enclosure
1. Check the Smartformer enclosure for externally visible damage.
If the Smartformer enclosure exhibits externally visible damage, perform the following
measures:
• Take the Smartformer out of service (see Section 13 "Decommissioning", page 62).
• Contact the SMA Service Line.
2. Remove coarse dirt contamination from the outside of the enclosure with a soft brush or similar
tool.
3.
Damage to Smartformer due to moisture penetration
Moisture penetration can cause short circuits and damage to the Smartformer.
• Use a moist cloth to remove dust from the outside of the enclosure. Do not use solvents,
abrasives, or other corrosive substances.
Cleaning the ventilation slots
• If the ventilation slots of the Smartformer are dusty, clean them with a soft brush, hand brush,
or similar tool.
Installation ManualSI_TDBOX-IA-eng-IUS12221157
12 TroubleshootingSMA America, LLC
12 Troubleshooting
12.1 Activating Overload Protection
The overload protection of the Smartformer was tripped. Activate the overload protection using the
following procedure.
1. Switch the overload protection to 0.
2. Switch the overload protection to 1.
☑ The overload protection stays set to 1 and the connected loads are supplied with voltage.
✖ What if the overload protection jumps back to a position between 0 and 1?
Possible cause of fault: The temperature in the autotransformer is still too high.
• Wait at least 10 minutes.
• Switch the overload protection to 0.
• Switch the overload protection to 1.
Possible cause of fault: Too many loads are connected via "Load L2".
• Switch off individual loads.
• Connect more loads via "Load L1".
58SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC12 Troubleshooting
12.2 Replacing Miniature Circuit-Breakers "F4" and "F5"
Danger to life due to electric shock
High volt ages that can result in electr ic shocks are present in t he live components of the Smartformer.
• Disconnect the Smartformer from the power supply before performing any work on the
Smartformer (see Section 10).
• Always use a contact hazard protection cover when operating the Smartformer.
• Work on the Smartformer may only be performed by a skilled worker.
• Do not touch live components of the Smartformer or other components of the
Sunny Island system.
1. Release the upper screw terminals of miniature
circuit-breakers "F4" and "F5" and remove the
conductors. Use a PZ 2 screwdriver or a suitable
cross-head screwdriver.
2. Release the lower screw terminals of miniature
circuit-breakers "F4" and "F5" and remove the
conductors. Use a PZ 2 screwdriver or a suitable
cross-head screwdriver.
Installation ManualSI_TDBOX-IA-eng-IUS12221159
12 TroubleshootingSMA America, LLC
3. Use a screwdriver to release the locking lever of
each miniature circuit-breaker and lift the miniature
circuit-breaker off the top-hat rail.
4. Ensure that the fuse rating of the new miniature circuit-breaker matches the maximum feed
current of the PV plant of 25 A or 50 A.
5. Ensure that the miniature circuit-breaker is certified according to the specified UL standard and
adheres to the specified tripping characteristic (see Section 14 "Technical Data", page 64).
6. Position the new miniature circuit-breaker at the top
edge of the top-hat rail and press against the lower
edge of the top-hat rail until the locking lever
engages.
7. Insert the upper conductor into the upper screw
terminal and tighten screws (torque: 25 in-lbs.
(2.8 Nm)). Use a torque wrench with a
PZ 2 attachment or another suitable cross-head
screwdriver attachment.
60SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC12 Troubleshooting
8. Insert the lower conductor into the lower screw
terminal and tighten screws (torque: 25 in-lbs.
(2.8 Nm)). Use a torque wrench with a
PZ 2 attachment or another suitable cross-head
screwdriver attachment.
Installation ManualSI_TDBOX-IA-eng-IUS12221161
13 DecommissioningSMA America, LLC
13 Decommissioning
13.1 Disassembling the Smartformer
Danger to life due to electric shock
High voltages that can result in electric shocks are present in the conductive components of the
Smartformer.
• Disconnect the Smartformer from the power supply before performing any work on the
Smartformer (see Section 10).
• Work on the Smartformer may only be performed by a skilled worker.
• Do not touch live components of the Smartformer or other components of the Sunny Island
system.
Risk of injury due to falling Smartformer
Due to its heavy weight, the Smartformer can crush or break bones if it falls.
• When disassembling, take into account the weight of the Smartformer, which is 132
(60 kg).
• Make sure that the Smartformer does not tilt or move out of position during disassembly.
1
⁄2lbs.
1. Disconnect the Smartformer from the power supply (see Section 10).
2. Wait for at least 1 hour, until the Smartformer has cooled down.
3. Open the enclosure door using the door handles.
4. Disassemble the contact hazard protection cover (see Section 9.1).
5. Release insulated conductors from all spring clamp
terminals of the Smartformer. Insert a screwdriver
into the terminal contact of the spring clamp
terminal and pull the insulated conductor out of the
spring clamp terminal.
62SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC13 Decommissioning
6. Release insulated conductors from the screw terminals of the miniature circuit-breakers "F4",
"F5", "F6" and "F7".
7. Remove all connection cables from the Smartformer.
8. Loosen 4 screws in the wall.
9. Take the Smartformer off the wall and set it down.
10. Unscrew 4 screws from the wall.
11. Release screws of the 4 anchorage brackets on the Smartformer and remove anchorage
brackets.
12. Mount the contact hazard protection cover (see Section 9.2).
13. Close the enclosure door using the door handles.
13.2 Storing the Smartformer
• Store the Smartformer in a dry place where the ambient temperature is always between
− 13°F ( − 25°C) and +140°F (+60°C).
• Store the Smartformer in closed packaging.
13.3 Packaging the Smartformer
• Package the Smartformer and the 4 anchorage brackets. Use the original packaging for this or
packaging suitable for the weight and dimensions of the Smartformer (see Section 14
"Technical Data", page 64).
13.4 Disposing of the Smartformer
• Dispose of the Smartformer in accordance with the locally applicable disposal regulations for
electronic waste.
or
• Send the Smartformer to SMA at your own expense (see Section 16 "Contact", page 71).
When doing so, label the packaging with the information "FOR DISPOSAL".
Installation ManualSI_TDBOX-IA-eng-IUS12221163
14 Technical DataSMA America, LLC
14 Technical Data
General data
Number of phases1-phase / split phase
Nominal power of the transformer*
AC power of the transformer for 30 minutes*4.4 kVA
AC power of the transformer for 1 minute*8.8 kVA
Typical self-consumption in no-load operation19 W
Maximum self-consumption in no-load operation23.3 W
Maximum efficiency99.0%
CEC efficiency98.8%
CertificationUL
Permissible grounding systemsTN
Width x height x depth24 in. x 24 in. x 9
(610 mm x 610 mm x 235 mm)
Weight132
Width x height x depth of packaging27
(690 mm x 700 mm x 320 mm)
* Power that the transformer can transfer from one line conductor to the other line conductor.
3.4 kVA
1
⁄4in.
1
⁄2lbs. (60 kg)
1
⁄4in. x 275⁄8in. x 125⁄8in.
64SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC14 Technical Data
86
88
90
92
94
96
98
SI-TD-BOX
0.4
1.0
0.80.20.6
Output power / Rated power
0.0
Efficency [%]
Efficiency curve
Figure 18: Efficiency curve of Smartformer
Ambient conditions
Ambient temperature − 25°C … 50°C
( − 13°F … 122°F)
Maximum value for relative humidity, noncondensing
Protection classNEMA 1
Enclosure degree of protectionIP20
Contact hazard protection cover degree of
protection
Overvoltage category3
EMC environmentFCC Part 15
Installation ManualSI_TDBOX-IA-eng-IUS12221165
100%
IP10
14 Technical DataSMA America, LLC
Possible conduits for connection
Top with diameter 3⁄4 in. (19 mm)2
Top with diameter 1 in. (25 mm)2
1
Top with diameter 1
Bottom with diameter
⁄4in. (32 mm)2
3
⁄4 in. (19 mm)5
Top with diameter 1 in. (25 mm)3
1
Bottom with diameter 1
⁄4in. (32 mm)3
Miniature circuit-breakers in use
Designation in Smartformer Nominal
AC current
Tripping
characteristics
CertificationVersion
Miniature circuit-breaker "F1"3 AZUL 4891-pole
Miniature circuit-breaker "F2"40 AKUL 4892-pole
Miniature circuit-breaker "F3"40AKUL489
Miniature circuit-breaker "F4"25A/50AZUL4892-pole
Miniature circuit-breaker "F5"25A/50AZUL489
Miniature circuit-breaker "F6"60 AKUL 4892-pole
Miniature circuit-breaker "F7"60AKUL489
AC 1 terminal of Sunny Island
Number of devices1 Sunny Island
Nominal AC voltage120 V
Rated power7.2 kW
AC power at 104°F (40°C)6.7 kW
AC power at 122°F (50°C)6.0 kW
AC current at rated power60 A
AC current at 104°F (40°C)55.7 A
AC current at 122°F (50°C)49.6 A
Number of phases1-phase
Connection typeSpring clamp terminal
Wire size*
* Valid for Sunny Island 4548-US / 6048-US an d for Sunny I sland 5048-US with labeling "Smartformer compatible" on the
Miniature circuit-breakers used in Smartformer"F4" and "F5"
* Nominal current of miniature circuit-breakers "F4" and "F5"
6 kW
10 AWG
Load connection: General data
Nominal AC voltage120 V / 240 V
Rated grid voltage between L1 and N120 V
AC voltage range between L1 and N102 V … 132 V
Rated grid voltage between L2 and N120 V
AC voltage range between L2 and N102 V … 132 V
Rated grid voltage between L1 and L2240 V
AC voltage range between L1 and L2204 V … 264 V
Nominal frequency60 Hz
Frequency range55 Hz … 65 Hz
Connection typeSpring clamp terminal
Maximum wire size4 AWG
Minimum wire size6 AWG
Fuse typeMiniature circuit-breaker
68SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC14 Technical Data
Load connection: If bypass switch is set to "ION"
Rated power7.2 kW
Rated power between L1 and L26.7 kW
Rated power between L1 and N3.8 kW
Rated power between L2 and N3.4 kW
AC current to L1 at rated power32 A
AC current to L2 at rated power28 A
AC power between L1 and L2 at 104°F (40°C)6.6 kW
AC power between L1 and N at 104°F (40°C)3.3 kW
AC power between L2 and N at 104°F (40°C)3.3 kW
AC current to L1 at 104°F (40°C)27.7 A
AC current to L2 at 104°F (40°C)27.7 A
AC power between L1 and L2 at 122°F (50°C)5.8 kW
AC power between L1 and N at 122°F (50°C)3.0 kW
AC power between L2 and N at 122°F (50°C)2.9 kW
AC current to L1 at 122°F (50°C)25.3 A
AC current to L2 at 122°F (50°C)24.3 A
Miniature circuit-breakers used in the Smartformer for
fusing
"F2" and "F3"
Load connection: If bypass switch is set to "II ON"
Rated power11.5 kW
AC power at 104°F (40°C)10 kW
AC power at 122°F (50°C)9.1 kW
AC current at rated power2 x 48 A
AC current at 104°F (40°C)2 x 41.6 A
AC current at 122°F (50°C)2 x 37.9 A
Miniature circuit-breakers used in the Smartformer for
fusing
Installation ManualSI_TDBOX-IA-eng-IUS12221169
"F6" and "F7"
15 Compliance InformationSMA America, LLC
15 Compliance Information
FCC Compliance
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause
undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class A & B digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However, there is no guarantee
that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following
measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and the receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
• Consult the dealer or an experienced radio/TV technician for help.
The user is cautioned that changes or modifications not expressly approved by SMA America, LLC
could void the user’s authority to operate this equipment.
70SI_TDBOX-IA-eng-IUS122211Installation Manual
SMA America, LLC16 Contact
16 Contact
If you encounter technical problems with our products, contact the SMA Service Line. We require the
following information in order to provide you with the necessary assistance:
• Serial number of the Smartformer
• Sunny Island type, serial number and firmware version
• PV inverter serial number and type
• Wind energy inverter serial number and type
• Type and rated capacity of the connected battery
If a generator is connected:
–Type
–Power
– Maximum current
• Type and power consumption of the connected loads
SMA Solar Technology America, LLC
6020 West Oaks Blvd, Ste 300
Rocklin, CA 95765
Tel. +1 916 625 0870
Tel. +1 877-MY SMA TECH
Tel. +1 877 697 6283 (Toll free, available for USA, Canada and Puerto Rico)
Fax +1 916 625 0871
Service@SMA-America.com
www.SMA-America.com
Installation ManualSI_TDBOX-IA-eng-IUS12221171
XXX4."4PMBSDPN
4."4PMBS5FDIOPMPHZ
4.""NFSJDB--$
XXX4.""NFSJDBDPN
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.