SUNNY ISLAND 3.0M / 4.4M / 6.0H / 8.0H
SUNNY REMOTE CONTROL
SI30M-44M-60H-80H-BE-en-30 | Version 3.0ENGLISH
Legal ProvisionsSMA Solar Technology AG
Legal Provisions
The information contained in this document is the property of SMA Solar Technology AG. Publishing its content, either
partially or in full, requires the written permission of SMA Solar Technology AG. Any internal company copying of the
document for the purposes of evaluating the product or its correct implementation is allowed and does not require
permission.
SMA Warranty
You can download the current warranty conditions from the Internet at www.SMA-Solar.com.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. A lack of identification does not mean that a
product or symbol is not trademarked.
The BLUETOOTH
marks by SMA Solar Technology AG is under license.
®
Modbus
is a registered trademark of Schneider Electric and is licensed by the Modbus Organization, Inc.
QR Code is a registered trademark of DENSO WAVE INCORPORATED.
®
Phillips
Torx
and Pozidriv® are registered trademarks of Phillips Screw Company.
®
is a registered trademark of Acument Global Technologies, Inc.
®
word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of these
SMA Solar Technology AG1 Information on this Document
1 Information on this Document
1.1 Validity
This document is valid for the following device types:
• SI3.0M-11 (Sunny Island 3.0M) from firmware version 3.2
• SI4.4M-11 (Sunny Island 4.4M) from firmware version 3.2
• SI6.0H-11 (Sunny Island 6.0H) from firmware version 3.1
• SI8.0H-11 (Sunny Island 8.0H) from firmware version 3.1
• SRC-20 (Sunny Remote Control)
1.2 Target Group
This document is intended for qualified persons and operators. Only qualified persons are allowed to perform the
activities marked in this document with a warning symbol and the caption "Qualified person". Activities that may also be
performed by operators are not marked and may be performed by operators.
Operators
Operators must be given training on the following subjects by qualified persons:
• Training on the dangers involved when handling electrical devices
• Training on the operation of the Sunny Island
• Training on the safe handling of batteries
• Training on the secure disconnecting of the Sunny Island under fault conditions
• Training on how to secure a system against unintentional reactivation
• Training on the maintenance and cleaning of the Sunny Island inverter
• Knowledge of and compliance with this document and all safety information
Qualified persons
Only qualified persons are allowed to perform the activities marked in this document with a warning symbol and the
caption "Qualified person". Qualified persons must have the following skills:
• Training in how to deal with the dangers and risks associated with installing and using electrical devices and batteries
• Training in the installation and commissioning of electrical devices
• Knowledge of and adherence to the local standards and directives
• Knowledge of and compliance with the documentation of the Sunny Island inverter with all safety information
Operating ManualSI30M-44M-60H-80H-BE-en-307
1 Information on this DocumentSMA Solar Technology AG
'$1*(5
:$5 1,1*
&$87,21
/05*$&
1.3 Symbols
SymbolExplanation
Indicates a hazardous situation which, if not avoided, will result in death or serious
injury
Indicates a hazardous situation which, if not avoided, can result in death or serious
injury
Indicates a hazardous situation which, if not avoided, can result in minor or moderate
injury
Indicates a situation which, if not avoided, can result in property damage
Information advising that the following section contains activities that may only be
performed by qualified persons.
Content that is relevant for SMA Flexible Storage Systems.
Content that is relevant for off-grid systems.
Information that is important for a specific topic or goal, but is not safety-relevant
☐Indicates a requirement for meeting a specific goal
☑Desired result
✖A problem that might occur
1.4 Typographies
TypographyUseExample
bold• Display messages
• Parameters
•Connections
•Slots
• Elements to be selected or
entered
>• Connects several elements to be
selected
•Connect PE to AC2Gen/Grid.
• Select the parameter 235.01 GnAutoEna
and set to Off.
• Select 600# Direct Access > Select
Number.
1.5 Nomenclature
Complete designationDesignation in this document
Off-grid system, battery backup system, system for
increased self-consumption
Sunny Boy, Sunny Mini Central, Sunny TripowerPV Inverters
Menus are presented as follows: menu number, hash, and menu name (e.g., 150# Compact Meters).
Parameters are presented as follows: menu number, period, parameter number, and parameter name (e.g., 150.01
GdRmgTm). The term parameter includes parameters with configurable values as well as parameters for displaying
values.
8SI30M-44M-60H-80H-BE-en-30Operating Manual
System
SMA Solar Technology AG2 Safety
2 Safety
2.1 Intended Use
Sunny Island
The Sunny Island is a battery inverter which controls the electrical energy balance in an off-grid system, in a battery
backup system, or in a system for increased self-consumption. In a battery backup system, you can also use the
Sunny Island for increased self-consumption.
Use this product only in accordance with the information provided in the enclosed documentation and with the locally
applicable standards and directives. Any other application may cause personal injury or property damage. Any changes
to the electrical installation must be performed in accordance with the Sunny Island inverter installation manual.
The Sunny Island is not suitable for supplying life-sustaining medical devices. A power outage must not lead to personal
injury.
The Sunny Island uses batteries for the storage of energy. The battery room must be ventilated in accordance with the
requirements of the battery manufacturer and with the locally applicable standards and directives (see documentation of
the battery manufacturer).
Alterations to the product, e.g., modifications or conversions, are permitted only with the express written permission of
SMA Solar Technology AG. Unauthorized alterations will void guarantee and warranty claims and usually void the
operation permit. SMA Solar Technology AG shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as appropriate.
The enclosed documentation is an integral part of this product. Keep the documentation in a convenient place for future
reference and observe all instructions contained therein.
The type label must remain permanently attached to the product.
Sunny Remote Control
You can configure and control the system from a central location using the Sunny Remote Control display.
Only use the product in accordance with the information provided in the enclosed documentation. Alterations to the
product, e.g., modifications or conversions, are permitted only with the express written permission of
SMA Solar Technology AG. Unauthorized alterations will void guarantee and warranty claims and usually void the
operation permit. SMA Solar Technology AG shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as appropriate.
The enclosed documentation is an integral part of this product. Keep the documentation in a convenient place for future
reference and observe all instructions contained therein.
The type label must remain permanently attached to the product.
Operating ManualSI30M-44M-60H-80H-BE-en-309
2 SafetySMA Solar Technology AG
:$5 1,1*
2.2 Safety Information
This section contains safety information that must be observed at all times when working on or with the product.
To prevent personal injury and property damage and to ensure long-term operation of the product, read this section
carefully and observe all safety information at all times.
Danger to life from electric shocks due to live voltage and risk of injury from short-circuit currents
High voltages are present inside the Sunny Island. When the enclosure lid is removed, live components can be touched
which can result in death or serious injury due to electric shock. Short-circuit currents in the battery can cause heat
build-up and electric arcs. Burns or eye injuries due to flashes may result.
• When carrying out any work on the electrical installation, wear suitable personal protective equipment.
• Turn off or disconnect the following devices from voltage sources in the given order:
–Sunny Island
– In the distribution board the circuit breakers of the Sunny Island inverters and of the control and measurement
voltages
– Load-break switch of the battery
• Ensure that the system cannot be reconnected.
• Open the enclosure lid of the Sunny Island and ensure that no voltage is present.
• Ground and short-circuit the AC conductors outside the Sunny Island inverter.
• Cover or isolate any adjacent live components.
Danger to life from electric shock due to damaged Sunny Island
Operating a damaged Sunny Island can lead to hazardous situations that can result in death or serious injuries due to
electric shock.
• Only operate the Sunny Island when it is technically faultless and in an operationally safe state.
• Regularly check the Sunny Island for visible damage.
• Make sure that all external safety equipment is freely accessible at all times.
• Make sure that all safety equipment is in good working order.
Risk of crushing injuries due to movable generator parts
Moving parts in the generator can crush or sever body parts. A generator can be started automatically by the
Sunny Island.
• Only operate the generator with the safety equipment.
• Install, maintain, and operate the generator according to the manufacturer's specifications.
10SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG2 Safety
&$87,21
/05*$&
Risk of burns due to short-circuit currents on the disconnected Sunny Island
The capacitors at the DC connection input area store energy. After the battery is isolated from the Sunny Island, battery
voltage is still temporarily present at the DC terminal. A short circuit on the DC connection can lead to burns and may
damage the Sunny Island.
• Wait 15 minutes before performing any work at the DC connection or on the D C cables. This allows the capacitors
to discharge.
Risk of burns due to hot components
Some components of the Sunny Island can get very hot during operation. Touching these components can cause burns.
Heat build-up can cause burns.
• During operation, do not touch any parts other than the enclosure lid of the Sunny Island.
• When the Sunny Island is open, do not touch hot surfaces.
Destruction of the Sunny Island inverter due to electrostatic discharge (ESD)
By touching electronic components within the Sunny Island, you can damage or destroy the Sunny Island.
• Do not touch any electronic assemblies.
• Ground yourself before touching any connections.
Operating ManualSI30M-44M-60H-80H-BE-en-3011
2 SafetySMA Solar Technology AG
:$5 1,1*
&$87,21
2.3 Information for Handling Batteries
Danger to life due to explosive gases
Explosive gases may escape from the battery and cause an explosion. This can result in death or serious injury.
• Protect the battery environment from open flames, embers, or sparks.
• Install, operate, and maintain the battery in accordance with the manufacturer's specifications.
• Do not heat the battery above the temperature permitted or burn the battery.
• Ensure that the battery room is sufficiently ventilated.
Chemical burns and poisoning due to battery electrolyte
If handled inappropriately, battery electrolyte can cause irritation to the eyes, respiratory system, and skin, and it can
be toxic. This may result in blindness and serious chemical burns.
• Protect the battery enclosure against destruction.
• Do not open or deform the battery.
• Whenever working on the battery, wear suitable personal protective equipment such as rubber gloves, apron,
rubber boots, and goggles.
• Rinse acid splashes thoroughly with clear water and consult a doctor.
• Install, operate, maintain, and dispose of the battery according to the manufacturer's specifications.
Risk of injury due to short-circuit currents
Short-circuit currents in the battery can cause heat build-up and electric arcs. Burns or eye injuries due to flashes may
result.
• Remove watches, rings, and other metal objects.
• Use insulated tools.
• Do not place tools or metal parts on the battery.
Risk of burns due to hot battery components
Improper battery connection may result in excessively high transition resistances. Excessive transition resistances give
rise to localized heat build-up.
• Ensure that all pole connectors are connected with the connecting torque specified by the battery manufacturer.
• Ensure that all DC cables are connected with the connecting torque specified by the battery manufacturer.
12SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG2 Safety
/05*$&
Damage to the battery due to incorrect settings
Incorrect settings lead to premature aging of the battery. Settings of the parameters in the menu 220# Battery
influence the charging behavior of the Sunny Island.
• Check whether initial battery charging with special settings is required.
If initial charging is required, adjust the charging behavior of the Sunny Island for one-off initial charging.
• Ensure that the values for the battery as recommended by the battery manufacturer are set in the menus
222# Chargemode and 223# Protection (for the technical data of the battery, see the documentation provided
by the battery manufacturer). Note that the charging behavior names used by SMA Solar Technology AG and
the battery manufacturer may, in some cases, differ in meaning (for the charging behavior of the Sunny Island
inverter, see technical information "Battery Management"). Tip: For questions relating to the settings of the
Sunny Island, please contact the SMA Service Line.
Permanent damage to the battery due to improper handling
Improper set-up and maintenance of the battery can cause it to become permanently damaged. Logs can help to
determine the cause.
• Comply with all requirements of the battery manufacturer with regard to mounting location.
• Check and log the status of the battery before performing maintenance work:
• Check the battery for visible damage and log.
• Measure and log the fill level and acid density of FLA batteries.
• In the case of lead-acid batteries, measure and log the voltages of the individual cells.
• Perform and log the test routines required by the battery manufacturer.
Tip: Many battery manufacturers provide suitable logs.
Prior damage to batteries
Batteries may already have suffered damage due to production defects. Logs can help to determine the cause.
• Check and log the status of the battery before performing maintenance work.
Performance impairment of batteries
Transition resistances can impair the performance of the batteries.
• Ensure that the torques at the battery connections are correct each time that maintenance is performed.
Operating ManualSI30M-44M-60H-80H-BE-en-3013
3 Product DescriptionSMA Solar Technology AG
3 Product Description
3.1 Sunny Island
The Sunny Island is a battery inverter and controls the electrical energy balance in off-grid systems, in battery backup
systems, or in systems for increased self-consumption. In a battery backup system, you can also use the Sunny Island for
increased self-consumption.
Figure1: Design of the Sunny Island inverter
PositionDesignation
AVentilation grid
BType label
CControl panel
DEnclosure lid
The Sunny Island supplies AC loads in the system from a battery or charges the battery with the energy provided by AC
sources (e.g., PV inverter). AC sources supply loads and are used by the Sunny Island to recharge the battery.
14SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG3 Product Description
3.2 Control Panel of the Sunny Island Inverter
Figure2: Layout of the control panel
PositionSymbolDesignationStatusExplanation
AStart-stop button
TSS
‒By pressing the start-stop button, you can start or stop
the system. In display messages on the
Sunny Remote Control, the start-stop button is
referred to as TSS.
B"On" button‒Pressing the "On" button will switch the Sunny Island
on. The Sunny Island is in standby mode after being
switched on.
C"Off" button‒Pressing the "Off" button will switch the Sunny Island
off.
DInverter LEDnot glowingThe Sunny Island is switched off.
glowing greenThe Sunny Island is in operation.
glowing orangeThe Sunny Island is in standby mode.
glowing redThe Sunny Island switched off due to an error.
flashing quickly*
flashing
The Sunny Island is not configured.
The Sunny Island is in overnight shutdown.
slowly**
EGrid LEDnot glowingThere is no voltage present from the generator or the
utility grid.
glowing greenGenerator or utility grid is connected.
glowing orangeThe Sunny Island is synchronizing the stand-alone
grid with the generator or the utility grid.
glowing redError at the connection of the generator or the utility
grid.
FBattery LEDglowing greenThe state of charge is more than 50%.
glowing orangeThe state of charge is between 50% and 20%.
glowing redThe state of charge is less than 20%.
GStandby‒Position of the buttons for switching on and off
HAC operation‒Position of the button for starting and stopping
operation
* Flashing at intervals of 0.5 s to 1 s
** Flashing at intervals of 1.5 s to 2 s
Operating ManualSI30M-44M-60H-80H-BE-en-3015
3 Product DescriptionSMA Solar Technology AG
V
D
E
3.3 Type Label
The type label clearly identifies the product. The type label is located on the right-hand side of the enclosure. You will find
the following information on the type label:
• Address of SMA Solar Technology AG
• Device type (Model)
• Serial number (Serial No.)
• Device-specific characteristics
You will require the information on the type label to use the product safely and when seeking customer support from the
SMA Service Line.
Symbols on the type label
SymbolExplanation
Danger to life due to high voltages
The product operates at high voltages. All work on the product must be carried out by qualified
persons only.
Risk of burns due to hot surfaces
The product can get hot during operation. Avoid contact during operation. Allow the product to cool
down sufficiently before carrying out any work. Wear personal protective equipment such as safety
gloves.
Observe the documentation.
Observe all documentation supplied with the product.
AC
Alternating current
DC
Direct current
Transformer
The product has a transformer.
WEEE designation
Do not dispose of the product together with the household waste but in accordance with the locally
applicable disposal regulations for electronic waste.
CE marking
The product complies with the requirements of the applicable EU directives.
Protection class I
All electrical equipment is connected to the grounding conductor system of the product.
Degree of protection
The product is protected against interior dust deposits and splashing water from all angles.
Certified safety
The product is VDE-tested and complies with the requirements of the German Equipment and Product
Safety Act.
RCM tick
The product complies with the requirements of the applicable Australian EMC standards.
16SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG3 Product Description
3.4 Sunny Remote Control
You can configure and control the system from a central location using the Sunny Remote Control display.
Figure3: Layout of the Sunny Remote Control
PositionDesignationExplanation
ADisplayFour-line display displays operating data (e.g., operating state, display values) and
events, warnings, or errors on the Sunny Island inverter.
The display backlight is automatically deactivated after a short period of inactivity.
BButtonPressing the button will turn on the backlight, confirm parameters, or switch the level
within a menu. The return symbol "" in the display indicates when you can perform
an action by pressing the button.
Turning the button will switch on the backlight, change parameters, or navigate within a
menu level.
CSlot for the SD
memory card
‒
Service interface, SD memory card
The Sunny Remote Control has a slot for SD memory cards. The SD memory card stores data for system control and
facilitates service work. The SD memory card also allows you to update the firmware on the Sunny Island inverter.
The following data is stored on the SD memory card:
• Parameter settings
• Every minute, measurement data from the areas:
– Battery
– Sunny Island
– Generator
– Utility grid
–Stand-alone grid
• Events and errors
• Statistical values of the battery
The SD memory card must be formatted as FAT-16 or FAT-32.
Operating ManualSI30M-44M-60H-80H-BE-en-3017
4 Starting and Stopping the SystemSMA Solar Technology AG
4 Starting and Stopping the System
4.1 Switching on the Sunny Island
Requirements:
☐ The load-break switch in the DC cable must be closed.
☐ The Sunny Island must not have switched itself off (see Section9.6 "Charging the Battery After Automatic Shutdown
in Off-Grid Systems", page72).
Procedure:
• For systems with one Sunny Island, press the "On" button on the
Sunny Island.
• For systems with up to three Sunny Island inverters, press and hold
the "On" button on the master until an acoustic signal sounds.
• For multicluster systems, press and hold the "On" button on each
master until an acoustic signal sounds.
☑ The inverter LED on each Sunny Island inverter is glowing orange and the Sunny Island inverters are in standby.
4.2 Starting the System
Requirement:
☐ All Sunny Island inverters must be switched on.
Procedure:
• Press the start-stop button on the Sunny Island and hold it until an
acoustic signal sounds.
or
Press and hold the button on the Sunny Remote Control until an acoustic signal sounds.
☑The inverter LED on each Sunny Island is glowing green.
18SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG4 Starting and Stopping the System
4.3 Stopping the System
If you stop the system, the Sunny Island switches from operation into standby mode. In standby mode, the Sunny Island
discharges the battery due to its standby consumption. Tip: For longer shut-down periods, switch off the Sunny Island
(see Section4.4, page19).
Procedure
• Press and hold the start-stop button on the Sunny Island until the
inverter LED is glowing orange.
or
Press and hold the button on the Sunny Remote Control until the progress bar has run down.
☑ The inverter LED on each Sunny Island is glowing orange. The Sunny Island inverters are in standby.
4.4 Switching off the Sunny Island
Requirement:
☐ The system is stopped.
Procedure:
• Press and hold the "Off" button on the Sunny Island until an
acoustic signal sounds.
☑ The inverter LED is off on all Sunny Island inverters.
Operating ManualSI30M-44M-60H-80H-BE-en-3019
4 Starting and Stopping the SystemSMA Solar Technology AG
4.5 Tripping the Emergency Disconnection of the System
Effects of an emergency disconnection
Emergency disconnection triggers the uncontrolled shutdown of the system and unsaved data is lost.
• Only use emergency disconnection to avoid danger or consequential damages.
Procedure:
• Press and hold the "Off" button on the Sunny Island until an
acoustic signal sounds.
☑ The inverter LED is off on all Sunny Island inverters.
4.6 Setting Time-Controlled Inverter Operation in Off-Grid Systems
Example: Parameter settings for time-controlled inverter operation
You want to operate the Sunny Island in inverter operation every Sunday from 10:00 a.m. to 6:00 p.m., starting on
Sunday, January 8, 2012. To do this, set the Sunny Island as follows:
• Str.Date: 08.01.2012
• Start Time: 10:00:00
• Run Time: 08:00:00
• Repetition: Weekly
Requirement:
☐ The Sunny Remote Control must be in user mode (see Section5.3, page27).
Procedure:
1. Select the Inverter display page on the Sunny Remote Control and press the
button.
☑ The Sunny Remote Control switches to the Inverter setting page.
2. Set the time-controlled inverter operation:
• Select the Start Date parameter and set it to the desired start date.
• Select the Start Time parameter and set it to the desired start time.
• Select the Run Time parameter and set it to the desired run time.
• Select the Repetition parameter and set it to the desired repetition cycle.
3. To activate time-controlled inverter operation, select the Timed Start parameter and set it to Enable.
☑ Time-controlled inverter operation is activated. If the Sunny Island has started automatically under time-control and
you stop the Sunny Island, time-controlled inverter operation is deactivated automatically.
20SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG5 Operation of the Sunny Island Inverter With the Sunny Remote Control
5 Operation of the Sunny Island Inverter With the Sunny Remote Control
5.1 Display Modes
The Sunny Remote Control uses four display modes for the display. The Sunny Remote Control will switch to standard
mode if the button has not been used for over five minutes.
ModePage content
Standard mode
<home>
User mode
User
Installer mode
Installer
Expert mode
Expert
The parameters for devices that are not configured are hidden, e.g., the generator parameters are hidden for systems
without a generator. The parameters for multicluster systems are only available in expert mode.
• Message regarding operating states
• Display of energy flows
• Display of key parameters
In display messages on the Sunny Remote Control, <home> refers to the standard mode.
• Display of and access to key operating parameters
In display messages on the Sunny Remote Control, User refers to the user mode.
• Display of and access to configuration and operation parameters
The installer mode is protected with an installer password. In display messages on the
Sunny Remote Control, Installer refers to the installer mode.
• Display of and access to all parameters for the system configuration set in QCG
The expert mode can only be accessed via installer mode (see Section5.4.1, page29). In display
messages on the Sunny Remote Control, Expert refers to the expert mode.
Operating ManualSI30M-44M-60H-80H-BE-en-3021
5 Operation of the Sunny Island Inverter With the Sunny Remote ControlSMA Solar Technology AG
5.2 Standard Mode
5.2.1 Display of Operating States
The Sunny Remote Control displays the following operating states until the Sunny Island is started.
Figure4: Display of operating states (example Standby)
PositionDesignationExplanation
ABootThe Sunny Island is initializing.
ErrorThe Sunny Island is in error status.
LBM 1The Sunny Island is in battery protection mode 1.
LBM 2The Sunny Island is in battery protection mode 2.
LBM 3The Sunny Island is in battery protection mode 3.
RestartThe Sunny Island is performing a restart.
ShutdownThe Sunny Island is stopped.
Silent The Sunny Island is in energy saving mode.
StandbyThe Sunny Island is in standby mode or in time-controlled operation.
StartupThe Sunny Island is starting up.
5.2.2 Information Page in Systems for Increased Self-Consumption and
Battery Backup Systems
When the Sunny Island is started, the Sunny Remote Control provides information on the status of the system for increased
self-consumption.
Figure5: Energy flows and status messages of the Sunny Island
PositionSymbolDesignationExplanation
AWarning symbolSymbol for warnings and errors that do not affect the Sunny Island
operation.
If this symbol is flashing, acknowledge the error or warning
(see Section9.2, page42).
22SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG5 Operation of the Sunny Island Inverter With the Sunny Remote Control
PositionSymbolDesignationExplanation
BDevice assignmentThe Sunny Island connected to the Sunny Remote Control is the
master.
The Sunny Island connected to the Sunny Remote Control is slave 1.
The Sunny Island connected to the Sunny Remote Control is slave 2.
CSD memory cardSD memory card inserted.
Symbol
flashing
No
symbol
DMultifunction relay 1Multifunction relay 1 is deactivated.
EMultifunction relay 2Multifunction relay 2 is deactivated.
FBattery power and
state of charge
Ghh:mm:ssTimeSystem time
HPower and status of
the utility grid
The Sunny Island is accessing the SD memory card.
SD memory card not inserted.
Multifunction relay 1 is activated.
Multifunction relay 2 is activated.
The battery is being charged.
The battery is being discharged.
Battery power in kW, state of charge (SOC) in %
Power in kW
The utility grid voltage and frequency are within the configured limits.
The maximum reverse power in the utility grid has been exceeded.
5.2.3 Information Page in Off-Grid Systems
Figure6: Energy flows and status of the Sunny Island inverter (example)
PositionDesignation
AGraphical representation of the energy flows
BStatus of the stand-alone grid
CStatus of the Sunny Island inverter
DState of charge of the battery
EStatus of the generator
Operating ManualSI30M-44M-60H-80H-BE-en-3023
5 Operation of the Sunny Island Inverter With the Sunny Remote ControlSMA Solar Technology AG
Graphical representation of the energy flows
Figure7: Energy flow diagram in standard mode (example)
PositionSymbolDesignationExplanation
ABatteryBattery symbol
BDirection of energy flowThe battery is supplying the loads.
The battery is being charged.
CGeneratorGenerator symbol
DInternal transfer relayThe generator is disconnected from the stand-alone grid.
The stand-alone grid is synchronized with the generator.
The generator is supplying the loads and charging the battery.
EDirection of energy flowLoads are being supplied.
AC sources in the stand-alone grid are supplying more energy than
is being consumed by the stand-alone grid.
FLoads in the stand-alone
Symbol for loads in the stand-alone grid
grid
Status of the stand-alone grid
Figure8: Status of the stand-alone grid (example)
PositionDesignationExplanation
AOutput powerOutput power of the Sunny Island inverter in kW
BLoads in the stand-alone
Symbol for loads in the stand-alone grid
grid
24SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG5 Operation of the Sunny Island Inverter With the Sunny Remote Control
Status of the Sunny Island inverter
Figure9: Status of the Sunny Island inverter (example)
PositionSymbolDesignationExplanation
AWarning symbolSymbol for warnings and errors that do not affect the Sunny Island
operation.
If this symbol is flashing, acknowledge the error or warning
(see Section9.2, page42).
BDevice assignmentThe Sunny Island connected to the Sunny Remote Control is the
master.
The Sunny Island connected to the Sunny Remote Control is
slave 1.
The Sunny Island connected to the Sunny Remote Control is
slave 2.
CSD memory cardSD memory card inserted.
Symbol
The Sunny Island is accessing the SD memory card.
flashing
No
SD memory card not inserted.
symbol
DMultifunction relay 1Multifunction relay 1 is deactivated.
Multifunction relay 1 is activated.
EMultifunction relay 2Multifunction relay 2 is deactivated.
Multifunction relay 2 is activated.
Fhh:mm:ssTimeOff-grid system time
State of charge of the battery
Figure10: State of charge of the battery in standard mode (example)
PositionDesignationExplanation
ABatteryBattery symbol
BState of chargeState of charge of the battery in percent
Operating ManualSI30M-44M-60H-80H-BE-en-3025
5 Operation of the Sunny Island Inverter With the Sunny Remote ControlSMA Solar Technology AG
Status of the external energy source
Figure11: Status of the external energy source in standard mode (example)
PositionSymbolDesignationExplanation
AStatus of the generatorVoltage and frequency of the generator are within the thresholds
set.
The maximum reverse power in the generator has been exceeded.
Battery
Electricity generator was requested due to state of charge.
Cycle
Generator was requested via time control.
External
Generator was requested by an extension cluster.
Load
Generator was requested due to load.
Start
You have manually started the generator via
Sunny Remote Control or a generator was requested via the DigIn
input.
Time
You have started the generator for one hour via
Sunny Remote Control.
B‒Power of the generator or
Power in kW
the utility grid
CGeneratorGenerator symbol
DInternal transfer relayThe generator is disconnected from the stand-alone grid.
The stand-alone grid is synchronized with the generator.
The generator is supplying the loads and charging the battery.
26SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG5 Operation of the Sunny Island Inverter With the Sunny Remote Control
5.3 User Mode
5.3.1 Displaying Parameters and Operating and Setting the System
User mode displays all important information for the system sorted by category. User mode enables manual control of
the Sunny Island inverter or system devices, e.g., generator start.
User mode distinguishes between display pages and setting pages. Display pages show the parameters of a category.
Setting pages enable the operation and setting of the system.
Figure12: Layout of a page in user mode (example)
PositionDesignationSymbol or
message
APage typeInformation
BCategory−Category name (see Section12 "Directory of the Parameters in User
CPage and number
of pages
DReturn symbolOn display pages, this symbol means that setting pages are
EParameters‒Parameters with the current values
Procedure
1. Press the button to activate the display illumination of the Sunny Remote Control.
2. Turn the button to the right.
☑ The Sunny Remote Control switches from standard mode to
user mode.
‒Page and number of pages of the selected category
No symbolNo setting pages are available for this category.
Explanation
This symbol indicates display pages.
Set
This symbol indicates setting pages.
Mode", page83)
available for this category.
On setting pages, this symbol points to the selected parameter.
3. To scroll through the display pages, continue to turn the button to the right.
4. To go back to a previous page, turn the button to the left.
5. To select a setting page, scroll to the display page for the category of the desired setting (see Section12 "Directory
of the Parameters in User Mode", page83).
Example: Selecting the display page.
You want to restart the Sunny Island. This setting is in the Inverter category.
• Select display page Inverter (1/1).
Operating ManualSI30M-44M-60H-80H-BE-en-3027
5 Operation of the Sunny Island Inverter With the Sunny Remote ControlSMA Solar Technology AG
6. Press the button. The Sunny Remote Control displays the setting pages belonging to the display page.
Example: Selecting the setting page
You have selected the display page Inverter (1/1).
• Press the button.
☑ The setting page Inverter (1/2) appears.
7. To select the desired parameter, turn the button to the right until the return symbol appears to the right of the desired
parameter.
☑ You have selected the parameter.
8. To set the parameter, press the button and then turn it to the left or right.
9. Once you have set the required parameter, press the button. This saves the setting.
Example: The Sunny Island is to start in time-controlled operation weekly. For this, the repetition type
(Repetition) must be set to "Weekly".
• Access the setting page Inverter (1/2).
☑ The setting page Inverter (1/2) appears.
• Turn the button until the return symbol appears next to the parameter Repetition.
The Sunny Remote Control switches from setting page Inverter (1/2) to setting page Inverter (2/2).
• Press the button.
• Turn the button to the right until Weekly appears.
• Press the button. This saves the parameter.
☑ You have set the repetition type to Weekly in
time-controlled operation.
10. To exit the setting page, switch to the display page or the standard mode:
• Turn the button to the left until the return symbol appears in the first line.
• To return to the display page, turn the button to the left until <back> appears.
• To switch to standard mode, turn the button to the left until <home> appears.
• Press the button.
Tip: <back> and <home> also appear at the end of the list if the button is turned to the right.
28SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG5 Operation of the Sunny Island Inverter With the Sunny Remote Control
/05*$&
5.4 Installer Mode and Expert Mode
5.4.1 Switching to Installer Mode or Expert Mode
The installer mode is protected with an installer password. The installer password changes constantly and must be
recalculated every time. Expert mode can only be accessed via installer mode.
System failures due to entering incorrect parameter values
The system can become unstable and fail due to entering incorrect parameter values. All parameters which could affect
the operating safety of the system are protected by the installer password.
• Only a qualified person is permitted to set and adjust system parameters.
• Only give the installer password to qualified persons and operators.
Procedure
1. On the Sunny Remote Control, select the setting page Password (1/1) in user mode.
2. Calculate the checksum of the operating hours Runtime. This determines the installer password.
Example: Calculating the checksum
The operating hours Runtime is 1234 h. The checksum is the sum of all digits:
1 + 2 + 3 + 4 = 10
The checksum is 10.
3. Select the parameter Set and set the installer password calculated.
☑ The Sunny Remote Control is in installer mode.
4. To switch to expert mode, select the parameter 700.01 ActLev and set to Expert (see Section5.4.6 "Setting the
Parameters", page31).
5.4.2 Exiting Installer Mode or Expert Mode
If you do not press or turn the button on the Sunny Remote Control for five minutes, the Sunny Remote Control will switch
from installer or expert mode to standard mode automatically.
• Select the parameter 700.01 ActLev on the Sunny Remote Control and set to User (see Section5.4.6 "Setting the
Parameters", page31).
Operating ManualSI30M-44M-60H-80H-BE-en-3029
5 Operation of the Sunny Island Inverter With the Sunny Remote ControlSMA Solar Technology AG
5.4.3 Menus in Installer and Expert Mode
Figure13: Layout of the menu page in installer mode (example)
PositionDesignationExplanation
AMenu pathThe two previously selected menu levels
If you are in the top menu level, the display will show Installer in installer mode
and Expert in expert mode.
BReturn symbolReturn symbol for selecting a menu
CMenu‒
5.4.4 Parameter Page in Installer and Expert Mode
Figure14: Layout of the parameter page in installer mode (example)
PositionDesignationExplanation
AMenu number and parameter number‒
BMenu pathThe two previously selected menu levels
CReturn symbolReturn symbol for setting the parameter
If no return symbol is displayed, the parameter cannot be set.
DName of the parameter‒
EValue and unit of the parameter‒
5.4.5 Selecting Menus and Parameters
1. Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
2. Turn the button to the right until the return symbol appears to the right of the desired menu. The Sunny Remote Control
scrolls through the menu items on the display line by line.
3. Press the button. This accesses the sub-menu level.
☑ The Sunny Remote Control displays the sub-menu level. The selected menu level is shown in the first line.
4. Repeat steps 2 and 3 until the Sunny Remote Control displays the first parameter page.
5. Turn the button to the right until the Sunny Remote Control displays the desired parameter.
6. Set the parameter (see Section5.4.6, page31).
30SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG5 Operation of the Sunny Island Inverter With the Sunny Remote Control
7. To exit the parameter page, switch to the higher level or switch to standard mode:
• Turn the button to the left until the return symbol appears in the first line.
• To switch to a higher menu level, turn the button to the left until <back> appears.
• To switch to standard mode, turn the button to the left until <home> appears.
• Press the button.
Tip: <back> and <home> also appear at the end of the list if the button is turned to the right.
5.4.6 Setting the Parameters
1. Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
2. Select the desired parameter. You can only set the parameters for
which < Set > is shown in the second line in the display.
3. Press the button.
☑ The return symbol is flashing next to the value.
✖ Stop device to change the value? appears in the display.
The parameter can only be changed in standby mode.
• Stop the system (see Section4.3, page19).
✖ No permission to change the value appears in the display.
You are not allowed to change the parameter in installer mode.
• If you want to change the parameters for the battery, select the menu New Battery in the QCG
(see Section10.8 "Replacing the Battery", page78).
• For all other settings, select the menu New System in the QCG (see the Sunny Island inverter installation
manual).
4. To set the parameter, turn the button to the left or right.
5. Press the button.
☑ The Sunny Remote Control requests a confirmation of the set
parameter.
6. To confirm the value, turn the button to the right until Y is flashing and then press the button.
7. To discard the value, turn the button to the right until N is flashing and then press the button.
Operating ManualSI30M-44M-60H-80H-BE-en-3031
5 Operation of the Sunny Island Inverter With the Sunny Remote ControlSMA Solar Technology AG
5.4.7 Directly Accessing the Parameters
Any parameter can be accessed directly by entering a five-digit number. The five-digit number is composed as follows:
• The first three digits are the menu number.
• The last two digits are the parameter number.
Example: Five-digit number for direct parameter access.
The parameter 111.01 TotInvPwrAt allows you to display the complete active power of the Sunny Island inverters in
a cluster. The five-digit number for direct access is 11101.
Procedure:
1. Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
2. Select the parameter 600.02 Select Number and set the five-digit number.
☑ The parameter is displayed.
✖ The display shows Item not Found?
You cannot access the parameter in installer mode.
• Press the button and switch to expert mode (see Section5.4.1, page29).
The number set is incorrect.
• Press the button and enter the number again.
32SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG6 Data Storage and Firmware Update
6 Data Storage and Firmware Update
6.1 Inserting the SD Memory Card
Requirements:
☐ The SD memory card must be formatted as FAT-16 or FAT-32.
☐ The SD memory card must be used exclusively as a data medium for the system.
Procedure:
• Insert the SD memory card, with the slanted corner facing
upwards, into the SD memory card slot in the
Sunny Remote Control.
6.2 Saving and Loading Parameters
You can load and save the current parameter settings in two different parameter sets on the SD memory card. The two
parameter sets are distinguished by the Sunny Remote Control in Set1 and Set2. Each parameter set saves all settings.
This makes it possible to test the settings of a new parameter set without having to delete the old parameter set. Tip: As
soon as you have adjusted the system to your requirements, save the parameter settings to the SD memory card. After
saving, you can make further adjustments to the system. If the adjustment does not lead to the desired results, reload the
saved parameter set.
Requirement:
☐ The SD memory card must be inserted.
Procedure
1. Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
2. To save a parameter set, select the parameter 550.01 ParaSto and set the parameter:
ValueExplanation
Set1Save the settings in the first parameter set.
Set2Save the settings in the second parameter set.
3. Proceed as follows to load a parameter set:
• Switch to expert mode on the Sunny Remote Control (see Section5.4.1, page29).
• Select the parameter 550.02 ParaLod and set the parameter:
ValueExplanation
Set1Loads the settings from the first parameter set.
Set2Loads the settings from the second parameter set.
FactoryStarts the quick configuration guide.
Operating ManualSI30M-44M-60H-80H-BE-en-3033
6 Data Storage and Firmware UpdateSMA Solar Technology AG
6.3 Saving the Event History and Error History
Requirement:
☐ The SD memory card must be inserted.
Procedure:
1. Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
2. To save the event history, select the parameter 550.03 CardFunc and set to StoEvtHis.
3. To save the error history, select the parameter 550.03 CardFunc and set to StoFailHis.
4. To save the error history and the event history, select the parameter 550.03 CardFunc and set to StoHis.
6.4 Displaying the SD Memory Card Status Message
The Sunny Remote Control determines the SD memory card status (see Section13.3.1 "Inverter (310#)", page123).
1. Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
2. Select the parameter 312.11 CardStt and read off the value.
6.5 Removing the SD Memory Card
If the SD memory card is removed without preparation, the removal will cause data loss. Data loss affects the log data
of the last 15 minutes at most.
Procedure
1. Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
2. Select the parameter 550.03 CardFunc and set to ForcedWrite. Unsaved data will now be saved to the
SD memory card.
3. Remove the SD memory card.
6.6 Displaying the SD Memory Card Content
Figure15: Content of an SD memory card (example)
The files saved to the SD memory card depend on the configuration and on the system.
Explanation of the folders:
Folder nameExplanation
BATSTATFolder containing battery statistics for each month
The files are stored by year and month in sub-folders.
HISTORYFolder containing event and error histories
LOGGINGFolder containing the data logging, event and error histories for each day
The files are stored by year and month in sub-folders.
SIPARFolder containing the parameter lists
34SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG6 Data Storage and Firmware Update
Explanation of the files within the folders:
File nameExplanation
evthis.logEvent history
errhis.logError history
si010112.evtEvent and error histories for one day
The date (ddmmyy) is part of the file name.
si010112.logData logging for the day
The date (ddmmyy) is part of the file name.
sipar.lstCurrent parameter set
sipar1.lstParameter set 1
sipar2.lstParameter set 2
update.binSunny Island inverter firmware
batstat.txtStatistical values of the battery
These values are saved every night at 10:00 p.m.
batstat.smaStatistical values of the battery for evaluation by SMA Solar Technology AG
sim.ccfSystem information of the Sunny Island inverter
bootex.logFile generated by the operating system of the computer
This file is not generated by every operating system.
Structure of the files:
The files are CSV files, which means that the data is saved as ASCII text. The files are structured as follows:
• The first lines in the file are used for information. Information lines start and end with the character #.
• The data in the following lines is separated by semicolons.
• Decimal places are separated by periods.
• The date format is dd.mm.yyyy.
• The time format is hh:mm:ss.
• Some of the parameter values are saved with plain text numbers (see Section13 "Directory of the Parameters in
Installer Mode and Expert Mode", page90).
Requirements:
☐ A computer with installed spreadsheet software must be available.
☐ The spreadsheet software must be able to read CSV files.
Procedure
1. Insert the SD memory card into the card reader and display the content.
2. Start the spreadsheet software and import the required file. When importing, set the import filter in accordance with
the file structure (see spreadsheet software manual).
Operating ManualSI30M-44M-60H-80H-BE-en-3035
6 Data Storage and Firmware UpdateSMA Solar Technology AG
6.7 Firmware Update
6.7.1 Updating the Firmware Using an SD Memory Card
Automatic Sunny Island inverter start
If the Sunny Island was in operation before the firmware update, the Sunny Island restarts automatically upon
completion of the firmware update.
Requirements:
☐ The SD memory card must be formatted as FAT-16 or FAT-32.
☐ SD memory card with the current firmware in the main directory must be available.
☐ The SD memory card must be used exclusively as a data medium for the system.
☐ A computer must be able to read from and write to the SD memory card.
☐ The Sunny Remote Control must be connected to the master.
Procedure:
1. Insert the SD memory card into the SD memory card slot (see Section6.1, page33).
2. Wait until the message UPDATE AVAILABLE appears. This can take up to two minutes.
3. Confirm the question UPDATE AVAILABLE Start update now ? with YES.
☑ The Sunny Island switches to standby and updates the firmware.
6.7.2 Updating the Firmware Using Sunny Explorer
-
Automatic Sunny Island inverter start
If the Sunny Island was in operation before the firmware update, the Sunny Island restarts automatically upon
completion of the firmware update.
Using Sunny Explorer, transfer the firmware update to the SMA Speedwire data module Sunny Island. Then, the
SMA Speedwire data module Sunny Island automatically transfers the firmware update to the SD memory card in the
Sunny Remote Control. This transfer takes some time.
Requirements:
☐ The SMA Speedwire data module Sunny Island of the type SWDMSI-NR10 with firmware version 1.01.06.R or
higher must be installed in the system.
☐ A computer with Sunny Explorer and the current firmware must be available.
☐ The Sunny Remote Control must be connected to the master.
Procedure
1. Ensure that a writable SD memory card is inserted in the Sunny Remote Control and remains inserted throughout the
entire update.
2. Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
3. Set the parameter 250.32 UpdMode to Auto.
4. Set the parameter 250.33 UpdAutoTime to the desired firmware update time.
5. Transfer the firmware update from the computer to the Sunny Island using Sunny Explorer (see the Sunny Explorer
user manual).
6. Once the transfer is complete, close Sunny Explorer.
☑ Once the transfer to the SD memory card is complete, the Sunny Island updates automatically at the specified time.
The Sunny Island switches to standby mode and updates the firmware.
36SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG6 Data Storage and Firmware Update
6.7.3 Performing a Remote Update Using the Sunny Home Manager
Automatic Sunny Island inverter start
If the Sunny Island was in operation before the firmware update, the Sunny Island restarts automatically upon
completion of the firmware update.
The Sunny Home Manager can automatically make the current firmware available via Sunny Portal. For this, the
Sunny Home Manager first transfers the firmware update to the SMA Speedwire data module Sunny Island. Then,
the SMA Speedwire data module Sunny Island automatically transfers the firmware update to the SD memory card in
the Sunny Remote Control. This transfer takes some time.
Requirements:
☐ The Sunny Island must be registered in Sunny Portal.
☐ The SMA Speedwire data module Sunny Island of the type SWDMSI-NR10 must be installed in the system.
☐ The Sunny Home Manager must be integrated in the system.
☐ The Sunny Remote Control must be connected to the master.
Procedure
1. Ensure that a writable SD memory card is inserted in the Sunny Remote Control and remains inserted.
2. Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
3. Set the parameter 250.32 UpdMode to Auto.
4. Set the parameter 250.33 UpdAutoTime to the desired firmware update time.
5. Activate the automatic software update in the Sunny Home Manager (see user manual of the
Sunny Home Manager).
☑ Once the transfer to the SD memory card is complete, the Sunny Island updates automatically at the specified time.
The Sunny Island switches to standby mode and updates the firmware.
Operating ManualSI30M-44M-60H-80H-BE-en-3037
7 Manually Controlling the GeneratorSMA Solar Technology AG
:$5 1,1*
7 Manually Controlling the Generator
7.1 Starting the Generator with Sunny Remote Control
Requirements:
☐ The Sunny Island must be able to control the generator via a control cable.
☐ The Sunny Remote Control must be in standard mode or user mode.
Procedure
1. Select the Generator display page on the Sunny Remote Control and press the button (see Section5.3.1
"Displaying Parameters and Operating and Setting the System", page27).
2. To start the generator and run it permanently, select the parameter Mode and set to Start.
☑ The electricity generator starts and runs until you stop it again.
3. To start the generator and run it for one hour, select the parameter Mode and set to Run1h.
☑ The generator starts. If there is no generator request after one hour, the Sunny Island stops the generator.
7.2 Stopping the Generator with Sunny Remote Control
Risk of crushing injuries due to movable generator parts
Moving parts in the generator can crush or sever body parts. A generator can be started automatically by the
Sunny Island.
• Before performing work on the generator, permanently stop the generator and secure it against inadvertent
restarting.
• Carry out work on the generator in accordance with the manufacturer's specifications.
Requirements:
☐ The Sunny Island must be able to control the generator via a control cable.
☐ The Sunny Remote Control must be in standard mode or user mode.
Procedure
1. Select the Generator display page on the Sunny Remote Control and press the button (see Section5.3.1
"Displaying Parameters and Operating and Setting the System", page27).
2. Select the parameter Mode and set to Stop.
☑ The generator is stopped temporarily. The generator restarts when a generator request is issued in automatic
generator mode and the minimum stop time has elapsed.
3. To permanently stop the generator, deactivate the automatic generator mode:
• Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
• Select the parameter 235.01 GnAutoEna and set to Disable.
☑ The generator is permanently stopped.
7.3 Starting the Generator without Autostart Function
1. Start the generator (see manufacturer's manual).
2. Close the load-break switch between the generator and Sunny Island.
☑ After the warm-up period, the Sunny Island connects the stand-alone grid to the generator.
38SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG7 Manually Controlling the Generator
7.4 Stopping the Generator without Autostart Function
1. Stop the generator on the Sunny Remote Control (see Section7.2, page38). When you do this, the Sunny Island
disconnects the stand-alone grid from the generator.
2. Open the load-break switch between the generator and the Sunny Island.
3. Stop the generator (see manufacturer's manual).
☑ The generator is stopped. After the power-down time and the minimum stop time, you can use the generator again.
Operating ManualSI30M-44M-60H-80H-BE-en-3039
8 Disconnecting the Sunny Island from Voltage SourcesSMA Solar Technology AG
/05*$&
8 Disconnecting the Sunny Island from Voltage Sources
1. Switch the system off (see Section4.4, page19).
2. Disconnect the circuit breakers and the load-break switches in the sub-distributions and secure against reconnection.
3. Open the load-break switch in the DC cable and secure against reconnection.
4.
Destruction of the Sunny Island inverter due to electrostatic discharge (ESD)
By touching electronic components within the Sunny Island, you can damage or destroy the Sunny Island.
• Do not touch any electronic assemblies.
• Ground yourself before touching any connections.
5. Loosen all screws of the enclosure lid and remove the enclosure lid.
6. Ensure that the DC connection is disconnected from voltage sources.
7. Ensure that the connections AC1 Loads/SunnyBoys, AC2 Gen/Grid, and ExtVtg (position A) are disconnected from
voltage sources.
8. Ensure that the connections Relay1 and Relay2 (position A) are
disconnected from voltage sources.
9. Ground and short-circuit the AC power cables outside the Sunny Island.
10. Cover or isolate any adjacent live components.
40SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
9 Troubleshooting
9.1 Sunny Island Inverter Behavior Under Fault Conditions
Display of errors, warnings, and events
Pending warnings and errors are shown automatically on the display of the Sunny Remote Control until the cause of the
warning or error is no longer logged by the Sunny Island or has been acknowledged. Events are logged by the
Sunny Island. The following menus log warnings, errors and events:
• 410# Error active - display of currently pending warnings and errors
• 420# Error history - warning and error history
• 430# Event history - events history
• In systems for increased self-consumption and battery backup systems: 440# Error Grid - history of the last five utility
grid errors
Structure of display numbers
Each error and each event has a unique three-digit display number that is determined based on the parameter or
measurement value assignment. Events and errors use the same number range:
• 1xx - Sunny Island
• 2xx - Battery
• 3xx - Generator or utility grid
• 4xx - Generator
• 5xx - Utility grid
• 6xx - Relay
• 7xx - System
• 8xx - External devices and components
• 9xx - General
Meaning of abbreviations
F indicates an error, W a warning, and E an event.In the event of an error, the display shows whether the error has come or gone using ! for "Set" and C for "Clear".
Error Levels
The Sunny Island distinguishes between five different levels of errors, each requiring different user interaction.
LevelDesignationDisplay on the
Sunny Remote
Control
1Warning WarningWarning, the Sunny Island continues to run. Information in standard
Explanation
mode indicating that a warning has been generated.
2Malfunction 1MalfunctionMalfunction that is only detectable during operation. The Sunny Island
shuts down. Restart can be initiated immediately (e.g., via autostart).
3Malfunction 2MalfunctionMalfunction that is also detectable in standby mode. The Sunny Island
shuts down. Restart is blocked until the malfunction is no longer detected
by the Sunny Island.
Operating ManualSI30M-44M-60H-80H-BE-en-3041
9 TroubleshootingSMA Solar Technology AG
LevelDesignationDisplay on the
Sunny Remote
Control
4FailureFailureDevice failure, the Sunny Island switches off. Troubleshooting,
5Device defectDefectThe Sunny Island is defective and switches itself off. The Sunny Island
Explanation
acknowledgment of the error and manual restart necessary.
must be replaced.
Handling of pending errors upon activation
During the activation procedure, all pending errors are acknowledged without the error being logged in the list 420#
Error history. Errors which are still pending are entered again after activation. Errors which were detected by the Sunny Island before activation and are no longer detected after activation are shown in the list 420# Error history.
Autostart
The autostart function allows automatic restarts in the event of malfunctions. If the autostart function fails in the event of a
malfunction, the Sunny Island attempts to carry out the next autostart immediately. The number of autostarts is restricted.
If the Sunny Island is in operation without malfunctions for ten minutes, it resets the autostart counter.
When the maximum number of autostarts has been reached, the Sunny Island reacts as follows:
• The Sunny Island waits ten minutes.
• The autostart counter is reset.
• The Sunny Island attempts to perform an autostart.
• When the maximum number of autostarts has been reached, the Sunny Island waits again for ten minutes.
9.2 Acknowledging Errors
If a malfunction or failure occurs, the Sunny Island switches to standby mode. Once you have eliminated the cause of the
error, you can enable a restart of the Sunny Island inverter by acknowledging the error.
Procedure:
1. Eliminate the cause.
2. Press the button on the Sunny Remote Control. This acknowledges the error.
3. Start the system (see Section4.2, page18).
9.3 Logged Events
9.3.1 Sunny Island Category (1xx)
No.NameDescription
E101StandbyWaiting mode
E102StartupStartup process
E103RunOperation
E104RunExtGnOperation with a generator
E105RunExtGdOperation with the utility grid
E106RunGdFeedFeed-in grid operation
E108Silent Energy saving mode
E110ErrShutdownShutdown due to error
42SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
No.NameDescription
E115EmgChargeEmergency charging
E118AutoStartAutomatic start
E119ManStartManual start
E120ManStopManual stop
E121PwrSaveStartStart of energy saving mode
E122PwrSaveStopEnd of energy saving mode
E129Ext.StartExternal start
E130Ext.StopExternal stop
E131AfraStartAutomatic frequency synchronization control is activated.
E132AfraStopAutomatic frequency synchronization control is not activated.
E133SlfCsmpStartStart of increased self-consumption
E134SlfCsmpStopStop of increased self-consumption
E135SlfCsmpChrgOnly Battery is charged only when increased self-consumption is active
E136SLfCsmpBatMntFull or equalization charge with active increased self-consumption
E137SlfCsmpNormalSwitch back to increased self-consumption after completion of full or equalization charge
E138InvShutdownThe Sunny Island shuts down.
E140FedInOnSetpoint activated
E141FedInOffSetpoint deactivated
9.3.2 Battery Category (2xx)
No.NameDescription
E202BmsNewBat(Partial) reset of battery management due to new battery
E203BmsFloatBattery charge algorithm switches to float charge
E204BmsBoostBattery charge algorithm switches to boost charge
E205BmsFullBattery charge algorithm switches to full charge
E206BmsSilentSwitches to energy saving mode
E207BmsEqualBattery charge algorithm switches to equalization charge
E224BMS20PReCal20% recalibration being performed.
E501GdSocOnGrid request due to low battery state of charge
E502GdSocOffGrid release due to adequate battery state of charge
E503GdPwrOnGrid request due to power limit being exceeded
E504GdPwrOffGrid release due to power falling below the limit
E505GdManOnManual grid request
E506GdManOffManual grid release
E507GdFeedStartStart of grid feed-in to utility grid
E508GdFeedStopStop of grid feed-in to utility grid
9.3.5 Relay Category (6xx)
No.NameDescription
E601Rly1OffMultifunction relay 1 is deactivated.
E602Rly1OnMultifunction relay 1 is activated.
E603Rly1Slv1OffMultifunction relay 1 of slave 1 is deactivated.
E604Rly1Slv1OnMultifunction relay 1 of slave 1 is activated.
E605Rly1Slv2OffMultifunction relay 1 of slave 2 is deactivated.
E606Rly1Slv2OnMultifunction relay 1 of slave 2 is activated.
E609TransferOffInternal transfer relay is open.
E610TransferOnInternal transfer relay is closed.
E611TransferSlv1OffInternal transfer relay of slave 1 is open.
E612TransferSlv1OnInternal transfer relay of slave 1 is closed.
E613TransferSlv2OffInternal transfer relay of slave 2 is open.
E614TransferSlv2OnInternal transfer relay of slave 2 is closed.
E617Rly2OffMultifunction relay 2 is deactivated.
E618Rly2OnMultifunction relay 2 is activated.
E619Rly2Slv1OffMultifunction relay 2 of slave 1 is deactivated.
E620Rly2Slv1OnMultifunction relay 2 of slave 1 is activated.
E621Rly2Slv2OffMultifunction relay 2 of slave 2 is deactivated.
E622Rly2Slv2OnMultifunction relay 2 of slave 2 is activated.
E625DigInOffNo voltage at input DigIn (Low).
44SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
No.NameDescription
E626DigInOnVoltage at input DigIn (High).
E627DigInSlv1OffNo voltage at input DigIn (Low) at slave 1.
E628DigInSlv1OnVoltage at input DigIn (High) at slave 1.
E629DigInSlv2OffNo voltage at input DigIn (Low) at slave 2.
E630DigInSlv2OnVoltage at input DigIn (High) at slave 2.
9.3.6 System Category (7xx)
No.NameDescription
E705PwrOnDevice start
E706DateSetDate or time has been changed.
E707NewSysNew system configured in the QCG.
E708Fw1UpdatePart 1 of the firmware updated.
E709Fw2UpdatePart 2 of the firmware updated.
E710ClstUpdateCluster firmware updated.
E711CardInsertSD memory card inserted.
E712ParaUpdateParameter set has been loaded from SD memory card.
E715SRCOnSunny Remote Control is activated.
E716PvDisconDisconnection of inverters whose power is not controllable depending on the frequency
E718NoComMod1Communication interface 1 is incorrectly plugged or missing.
E719NoComMod2Communication interface 2 is incorrectly plugged or missing.
9.3.7 External Device and Component Category (8xx)
No.NameDescription
E807StartBoxMulticluster Box ready for operation.
E808StopBoxMulticluster Box disabled.
E824UpdFileCompleteFile for firmware update transferred.
E825UpdFileCrcOKFile for firmware update is OK.
E827UpdFileCrcNOKFile for firmware update is damaged.
E851Sic1DetectSunny Island Charger 1 has been detected.
E852Sic2DetectSunny Island Charger 2 has been detected.
E853Sic3DetectSunny Island Charger 3 has been detected.
E854Sic4DetectSunny Island Charger 4 has been detected.
Operating ManualSI30M-44M-60H-80H-BE-en-3045
9 TroubleshootingSMA Solar Technology AG
9.4 Logged Warning Messages and Error Messages
9.4.1 Sunny Island Category (1xx)
No.NameLevel CauseCorrective measures
F 109InvTmpHi3Temperature of the transformer in
the master is too high due to
overload or ambient temperature.
W 110InvTmpHiSlv11Temperature of the transformer in
slave 1 is too high due to overload
or ambient temperature.
W 111InvTmpHiSlv21Temperature of the transformer in
slave 2 is too high due to overload
or ambient temperature.
F 113InvTmpHi3Temperature of the heat sink in the
master is too high due to overload
or ambient temperature.
W 114InvTmpHiSlv11Temperature of the heat sink in
slave 1 is too high due to overload
or ambient temperature.
W 115InvTmpHiSlv21Temperature of the heat sink in
slave 2 is too high due to overload
or ambient temperature.
F 117AcCurLim2The power of the loads is too high
for the master.
W 118AcCurLimSlv11The power of the loads is too high
for slave 1.
W 119AcCurLimSlv21The power of the loads is too high
for slave 2.
• Ensure that the Sunny Island is
functional. For this, wait until the
Sunny Island has cooled down
and then restart it.
• Clean the fans (see Section10.7
"Cleaning the Fans", page77).
• Reduce the total power of the
loads, e.g., by staggering their use
over time.
• Ensure that the Sunny Island is
functional. For this, wait until the
Sunny Island has cooled down
and then restart it.
• Reduce the total power of the
loads, e.g., by staggering their use
over time.
• Ensure that the Sunny Island is
functional. For this, clean the fans
and restart the Sunny Island (see
Section10.7 "Cleaning the Fans",
page77).
•
Ensure that there are no short
circuits in the system and that the
power of the loads is not greater
than the power of the
Sunny Island inverter.
•
Use a star delta electronic circuit
to start three-phase loads with a
high start-up electricity demand
(e.g., engines).
•
Connect the loads with very high
power directly to the generator
whenever possible. Ensure that the
generator is not overloaded.
46SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
No.NameLevelCauseCorrective measures
F 121InvVtgHi3An overvoltage has occurred at
connection AC1 of the master.
W 122InvVtgHiSlv11An overvoltage has occurred at
connection AC1 of slave 1.
W 123InvVtgHiSlv21An overvoltage has occurred at
connection AC1 of slave 2.
F 129InvFrqHi3An overfrequency has occurred at
connection AC1 of the master.
W 130InvFrqHiSlv11An overfrequency has occurred at
connection AC1 of slave 1.
W 131InvFrqHiSlv21An overfrequency has occurred at
connection AC1 of slave 2.
•
Ensure that the Sunny Island is
functional. For this, disconnect all
AC sources and loads from the
Sunny Island and restart the
Sunny Island.
•
Find the cause of the overvoltage
through measurement and
step-by-step connection of the AC
sources and loads.
•
Ensure that the Sunny Island is
functional. For this, disconnect all
AC sources and loads from the
Sunny Island and restart the
Sunny Island.
•
Find the cause of the
overfrequency through
measurement and step-by-step
connection of the AC sources and
loads.
F 133InvFrqLo3An underfrequency has occurred
at connection AC1 of the master.
W 134InvFrqLoSlv11An underfrequency has occurred
at connection AC1 of slave 1.
W 135InvFrqLoSlv21An underfrequency has occurred
at connection AC1 of slave 2.
W 137Derate1The master has reduced the battery
charging current due to
overtemperature in the
Sunny Island.
W 138DerateSlv11Slave 1 has reduced the battery
charging current due to
overtemperature in the
Sunny Island.
W 139DerateSlv21Slave 2 has reduced the battery
charging current due to
overtemperature in the
Sunny Island.
•
Ensure that the Sunny Island is
functional. For this, disconnect all
AC sources and loads from the
Sunny Island and restart the
Sunny Island.
•
Find the cause of the
underfrequency through
measurement and step-by-step
connection of the AC sources and
loads.
• Clean the fans (see Section10.7
"Cleaning the Fans", page77).
• Reduce the total power of the
loads, e.g., by staggering their use
over time.
•
If the Sunny Island frequently
reduces its power, increase power
by replacing the Sunny Island
with a higher-powered version or
by installing additional
Sunny Island inverters.
Operating ManualSI30M-44M-60H-80H-BE-en-3047
9 TroubleshootingSMA Solar Technology AG
No.NameLevel CauseCorrective measures
F 141InvVtgLo2The voltage at connection AC1 of
the master is too low due to AC
sources in the system.
W 142InvVtgLoSlv11The voltage at connection AC1 of
slave 1 is too low due to AC
sources in the system.
W 143InvVtgLoSlv21The voltage at connection AC1 of
slave 2 is too low due to AC
sources in the system.
F 158VtgOnAC1Det2The master has measured an
undesired voltage at connection
AC1.
W 159VtgOnAC1DetSlv11Slave 1 has measured an
undesired voltage at connection
AC1.
W 160VtgOnAC1DetSlv21Slave 2 has measured an
undesired voltage at connection
AC1.
•
Ensure that the Sunny Island is
functional. For this, disconnect all
AC sources and loads from the
Sunny Island and restart the
Sunny Island.
•
Find the cause of the undervoltage
through measurement and
step-by-step connection of the AC
sources and loads.
A bypass switch may have bridged the
internal transfer relay.
• Ensure that the bypass switch is in
the position for operation with the
Sunny Island.
•
Ensure that the Sunny Island is
functional. For this, disconnect all
AC sources and loads from the
Sunny Island and restart the
Sunny Island.
A voltage source (e.g., generator) may
have been connected to the
connection AC1.
F 162OvrCurDet2Too much current is flowing
through the DC connection of the
master.
W 163OvrCurDetSlv11Too much current is flowing
through the DC connection of
slave 1.
W 164OvrCurDetSlv21Too much current is flowing
through the DC connection of
slave 2.
F 166Overload5min3The five minute overload capacity
of the master has been exceeded.
W 167Overload5minSlv11The five minute overload capacity
of slave 1 has been exceeded.
W 168Overload5minSlv21The five minute overload capacity
of slave 2 has been exceeded.
•
Disconnect voltage source from
connection AC1 and connect to
connection AC2 (see the
Sunny Island inverter installation
manual).
• Reduce the power of the loads.
48SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
No.NameLevelCauseCorrective measures
F 169Overload30min3The 30 minute overload capacity
of the master has been exceeded.
W 170Overload30minSlv11The 30 minute overload capacity
of slave 1 has been exceeded.
W 171Overload30minSlv21The 30 minute overload capacity
of slave 2 has been exceeded.
F 172Overload3The overload capacity of the
master has been exceeded.
W 173OverloadSlv11The overload capacity of slave 1
has been exceeded.
W 174OverloadSlv21The overload capacity of slave 2
has been exceeded.
F 175StopSlvError1A slave has disconnected• Contact the SMA Service Line.
F 176CurTrfSns4Internal current sensor is not
functioning correctly.
• Reduce the power of the loads.
9.4.2 Battery Category (2xx)
No.NameLevelCauseCorrective measures
F 201VBATMAX2Battery voltage at the master is
above the permissible
measurement range.
W 202VBATMAXSL11Battery voltage at slave 1 is
above the permissible
measurement range.
W 203VBATMAXSL21Battery voltage at slave 2 is
above the permissible
measurement range.
F 206BatTmpHi3The battery temperature is too
high.
• Check whether the value of the
parameter 120.02 BatVtg is above
65.0 V. If the value is above 65.0 V,
check the settings of the DC sources and
ensure that the battery capacity is
sufficient. When doing so, bear in mind
the technical data for the battery at the
DC connection (see the Sunny Island
inverter installation manual).
•
Ensure that the DC sources are correctly
connected and configured.
• Wait for the battery to cool down.
Tip: Protect the battery against
temperatures above 25°C. This helps
prevent premature aging of the battery.
•
Check whether the electrical resistance of
the battery temperature sensor is approx.
2,000 Ω at 20°C to 25°C. If the
resistance deviates strongly from this
value, replace the sensor.
Operating ManualSI30M-44M-60H-80H-BE-en-3049
9 TroubleshootingSMA Solar Technology AG
No.NameLevelCauseCorrective measures
F 208BatVtgHi3The battery voltage is greater
than the target charge voltage.
•
Ensure that all DC sources are correctly
configured.
•
Ensure that all SMA inverters are
configured to the country data set for
stand-alone grid operation.
W 209BatVtgWrnHi1The battery voltage is too high
and has not been generated by
the Sunny Island.
W 210BatVtgHiWarn1Battery voltage is temporarily
too high.
W 211BatTmpLoWarn1The battery temperature is too
low.
W 212BatTmpHiWarn1The battery temperature is too
high.
F 213BatVtgLow3Battery voltage is too low.•
•
Ensure that all DC sources are correctly
configured.
•
Ensure that all SMA inverters are
configured to the country data set for
stand-alone grid operation.
•
Ensure that all DC sources are correctly
configured.
•
Ensure that all SMA inverters are
configured to the country data set for
stand-alone grid operation.
• Ensure that the battery room is sufficiently
warm.
• Wait for the battery to cool down. Tip:
Protect the battery against temperatures
above 25°C. This helps prevent
premature aging of the battery.
Charge the battery in emergency charge
operation or using an external battery
charger (see Section9.6 "Charging the
Battery After Automatic Shutdown in
Off-Grid Systems", page72).
•
Ensure that DC loads are shed via a
load-shedding contactor when the
battery state of charge is low.
W 220BatSOH70Warn1Available battery capacity is
below 70%.
F 221InvalidBatType4External battery management
detected although no external
energy management has been
configured.
W 222CheckBat1The 20% recalibration resulted
in a jump of more than 10%.
50SI30M-44M-60H-80H-BE-en-30Operating Manual
•
Verify the plausibilit y of the error messag e
and replace the battery if necessary.
•
Start QCG and configure a new system
with external energy management
(e.g., system with lithium-ion battery).
• Check the battery.
SMA Solar Technology AG9 Troubleshooting
9.4.3 Generator or Utility Grid Category (3xx)
No.NameLevelCauseCorrective measures
W 309RlyProtect1Excessive current has been
applied to the internal
transfer relay of the master.
W 310RlyProtectSlv11Excessive current has been
applied to the internal
transfer relay of slave 1.
W 311RlyProtectSlv21Excessive current has been
applied to the internal
transfer relay of slave 2.
F 314ExtVtgLoss2The voltage and/or
frequency of the generator
or the utility grid are outside
the configured range.
• Reduce the total power of the loads, e.g.,
by staggering their use over time.
•
Connect the loads with very high power
directly to the generator whenever
possible or connect the utility grid. Ensure
that the generator is not overloaded.
•
In off-grid systems, ensure that the country
data sets of the SMA inverters are set to
stand-alone grid operation
(see the installation manuals of the SMA
inverters).
Corrective measures for a generator:
•
Adjust the thresholds for generator
frequency and/or voltage on the
Sunny Island (see the Sunny Island
inverter installation manual). Observe
and analyze the measured values
134.02 ExtVtg and 134.04 ExtFrq
during operation.
•
Adjust the generator voltage and/or
generator frequency.
Corrective measures in battery backup
systems:
• Contact the SMA Service Line, if required.
Operating ManualSI30M-44M-60H-80H-BE-en-3051
9 TroubleshootingSMA Solar Technology AG
No.NameLevelCauseCorrective measures
W 315ExtVtgLo1The voltage of the generator
or the utility grid at the
master is too low.
W 316ExtVtgLoSlv11The voltage of the generator
or the utility grid at slave 1 is
too low.
W 317ExtVtgLoSlv21The voltage of the generator
or the utility grid at slave 2 is
too low.
W 319ExtVtgHi1The voltage of the generator
or the utility grid at the
master is too high.
W 320ExtVtgHiSlv11The voltage of the generator
or the utility grid at slave 1 is
too high.
W 321ExtVtgHiSlv21The voltage of the generator
or the utility grid at slave 2 is
too high.
W 323ExtFrqLo1The frequency of the
generator or the utility grid at
the master is too low.
W 324ExtFrqLoSlv11The frequency of the
generator or the utility grid at
slave 1 is too low.
W 325ExtFrqLoSlv21The frequency of the
generator or the utility grid at
slave 2 is too low.
W 327ExtFrqHi1The frequency of the
generator or the utility grid at
the master is too high.
W 328ExtFrqHiSlv11The frequency of the
generator or the utility grid at
slave 1 is too high.
W 329ExtFrqHiSlv21The frequency of the
generator or the utility grid at
slave 2 is too high.
Corrective measures for a generator:
•
Adjust the thresholds for generator
voltage on the Sunny Island
(see the Sunny Island inverter installation
manual). Observe and analyze the
measured values 134.02 ExtVtg during
operation.
•
If possible, adjust the generator voltage.
Corrective measures in battery backup
systems:
• Contact the SMA Service Line, if required.
Corrective measures for a generator:
• The generator may be overloaded.
Reduce the total power of the loads by
staggering their use over time.
•
Adjust the thresholds for generator
frequency on the Sunny Island (see the
Sunny Island inverter installation
manual). Observe and analyze the
measured values 134.04 ExtFrq during
operation.
•
Adjust the frequency of the external
energy source.
Corrective measures for a utility grid:
• Contact the SMA Service Line, if required.
52SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
No.NameLevelCauseCorrective measures
W 331AntiIsl1Undesired stand-alone grid
is present at connection AC2
of the master.
W 332AntiIslSlv11Undesired stand-alone grid
is present at connection AC2
of slave 1.
W 333AntiIslSlv21Undesired stand-alone grid
is present at connection AC2
of slave 2.
W 335ExtVtgRdtErr1The voltage of the generator
or the utility grid at the
master is outside the
configured thresholds
(redundant measurement).
W 336ExtVtgRdtErrSlv11The voltage of the generator
or the utility grid at slave 1 is
outside the configured
thresholds (redundant
measurement).
W 337ExtVtgRdtErrSlv21The voltage of the generator
or the utility grid at slave 2 is
outside the configured
thresholds (redundant
measurement).
•
Ensure that the insulated wires at
connection AC2 are securely connected
and that the conductors in the terminals
are free of insulation.
Corrective measures for a generator:
This may be caused by a contactor between
the generator and the Sunny Island.
•
Control the contactor via a Sunny Island
inverter multifunction relay. Set the
parameter of the multifunction relay, e.g.,
241.01 Rly1Op, to AutoGn.
•
Set the parameter 234.20 GdAiSns to a
lower sensitivity.
Corrective measures for a utility grid:
• Contact the SMA Service Line.
Corrective measures for a generator:
•
Adjust the thresholds for generator
voltage on the Sunny Island
(see the Sunny Island inverter installation
manual). Observe and analyze the
measured values 134.02 ExtVtg during
operation.
•
If possible, adjust the generator voltage.
Corrective measures for a utility grid:
• Contact the SMA Service Line, if required.
W 339ExtVtgIncPro1Voltage increase protection•
W 340ExtVtgIncProSlv11
W 341ExtVtgIncProSlv21
Operating ManualSI30M-44M-60H-80H-BE-en-3053
Ensure that the conductor cross-section of
the AC cables is correctly sized.
9 TroubleshootingSMA Solar Technology AG
No.NameLevelCauseCorrective measures
W 343AcVtglim1The master disconnects from
the external energy source
because the voltage at
connection AC2 is too high
or the battery voltage too
low.
W 344AcVtglimSlv11Slave 1 disconnects from the
external energy source
because the voltage at
connection AC2 is too high
or the battery voltage too
low.
W 345AcVtglimSlv21Slave 2 disconnects from the
external energy source
because the voltage at
connection AC2 is too high
or the battery voltage too
low.
W 347ExtOverload1The master disconnects from
the utility grid due to line
conductor failure/overload
at connection AC2.
W 348ExtOverloadSlv11Slave 1 disconnects from the
utility grid due to line
conductor failure/overload
at connection AC2.
• Contact the SMA Service Line if required.
• Reduce the total power of the loads, e.g.,
by staggering their use over time.
•
Ensure that there is not a short circuit
present at connection AC2.
W 349ExtOverloadSlv21Slave 2 disconnects from the
utility grid due to line
conductor failure/overload
at connection AC2.
W 351ExtScirDet1There is a short circuit
present at connection AC2
of the master.
W 352ExtScirDetSlv11There is a short circuit
present at connection AC2
of slave 1.
W 353ExtScirDetSlv21There is a short circuit
present at connection AC2
of slave 2.
W 355PhsAngErr1Assignment of the line
conductors of the external
energy source to the AC2
connections of the
Sunny Island does not result
in a right-rotating magnetic
field.
•
Eliminate the short circuit.
•
Ensure that the master is connected to L1,
slave 1 to L2, and slave 2 to L3.
54SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
No.NameLevelCauseCorrective measures
F 365VAcExtPhsFail3The line conductors of the
measured AC voltage at
connections VExt and AC2
do not match.
F 366HotAcBus3When the tie switch is open,
AC voltage from an
unknown source is present at
connection AC2.
F 367ExtCtcNotOpen3Tie switch does not open.
• Ensure that the neutral conductor and line
conductor are correctly connected to
connection ExtVtg.
• Ensure that the neutral conductor and line
conductor are correctly connected to
connection AC2.
• Ensure that the connections ExtVtg and
AC2 are connected to the same line
conductor.
• Ensure that the triggering of the tie switch
is correct.
• Ensure that the tie switch is correctly
wired.
• Ensure that the triggering of the tie switch
is correct.
• Ensure that the tie switch is correctly
wired.
• Ensure that the feedback contact is
correctly connected.
F 368NRelNotOpen3Neutral conductor relay of
the master does not open.
W 369NRelNotOpenSlv11Neutral conductor relay of
slave 1 does not open.
W 370NRelNotOpenSlv21Neutral conductor relay of
slave 2 does not open.
W 372VtgFrqRatio1Disconnection from the utility
grid or generator due to
noncompliance with the
voltage-frequency ratio at
the master
W 373VtgFrqRatioSlv11Disconnection from the utility
grid or generator due to
noncompliance with the
voltage-frequency ratio at
slave 1
W 374VtgFrqRatioSlv21Disconnection from the utility
grid or generator due to
noncompliance with the
voltage-frequency ratio at
slave 2
• Contact the SMA Service Line.
• Contact the SMA Service Line if required.
Operating ManualSI30M-44M-60H-80H-BE-en-3055
9 TroubleshootingSMA Solar Technology AG
No.NameLevelCauseCorrective measures
F 376ExtCtcNotClose3Tie switch does not close.
• Ensure that the triggering of the tie switch
is correct.
• Ensure that the tie switch is correctly
wired.
• Ensure that the feedback contact is
correctly connected.
W 380VAcExtPhsFailS11The line conductors of the
W381 VAcExtPhsFailS21
measured AC voltage at
connections VExt and AC2
do not match.
• Ensure that the neutral conductor and line
conductor are correctly connected to the
connection ExtVtg.
• Ensure that the neutral conductor and line
conductor are correctly connected to
connection AC2.
• Ensure that the connections ExtVtg and
AC2 are connected to the same line
conductor.
W 383HotAcBusSlv11When the tie switch is open,
W 384HotAcBusSlv21
AC voltage from an
unknown source is present at
connection AC2.
• Ensure that the triggering of the tie switch
is correct.
• Ensure that the tie switch is correctly
wired.
9.4.4 Generator Category (4xx)
No.NameLevel CauseCorrective measures
W 401GnRevPwrProt1AC sources in the
system are driving the
generator. The reverse
power in the generator
has been exceeded for
too long.
• Adjust the generator request to the properties of the
AC sources in the system and the loads, e.g., for PV
inverters preferably request the generator at night.
•
If the generator can absorb reverse power, adjust
the settings for reverse power (see the Sunny Island
inverter installation manual).
56SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
No.NameLevel CauseCorrective measures
W 402GnFailLock1Connection of the
generator is locked as a
result of too many
interrupted start
processes.
• Ensure that the generator triggering is functioning,
the generator starts, and there is constant and stable
generator voltage present at connection AC2.
• To re-enable connection of the generator,
acknowledge the generator error (see Section9.2
"Acknowledging Errors", page42).
A warm-up time 234.12 GnWarmTm that is too short
may have been configured and hence the generator is
unable to supply valid voltage.
• Ensure that the generator warm-up time is configured
appropriately (see the Sunny Island inverter
installation manual).
9.4.5 Utility Grid Category (5xx)
No.NameLevelCauseCorrective measures
W 501GdRevPwrProt1AC sources in the stand-alone grid are
W 502GdRevPwrProtSL11
W 503GdRevPwrProtSL21
W 505GdCurNomExceed1The feed-in current of the master is greater
W 506GdCurNomExcSlv1 1The feed-in current of slave 1 is greater than
W 507GdCurNomExcSlv2 1The feed-in current of slave 2 is greater than
performing undesired feed-in to the utility
grid. The reverse power to the utility grid has
been exceeded for too long.
than 232.04 GdCurNom.
232.04 GdCurNom.
232.04 GdCurNom.
• Contact the SMA Service
Line, if required.
• Contact the SMA Service
Line, if required.
9.4.6 Relay Category (6xx)
No.NameLevelCauseCorrective measures
F 605TransfNotOpn4Internal transfer relay in the
master does not open.
W 606TransfNotOpnSL1 1Internal transfer relay in
slave 1 does not open.
W 607TransfNotOpnSL2 1Internal transfer relay in
slave 2 does not open.
A bypass switch may have bridged the internal
transfer relay.
• Ensure that the bypass switch is in the
position for operation with the
Sunny Island.
•
Ensure that the connections AC1 and
AC2 are not bridged.
Operating ManualSI30M-44M-60H-80H-BE-en-3057
9 TroubleshootingSMA Solar Technology AG
9.4.7 System Category (7xx)
No.NameLevelCauseCorrective measures
F 702RsDsp5Signal processor has performed a
reset.
F 703TimeOut2Time for performing a particular task
has been exceeded.
F 704Calib4The system has not calibrated.
W 705TimeOut1The watchdog of the signal processor
of the master has tripped.
F 706TimeOut4The watchdog of the signal processor
of the master has tripped several
times.
W 707TimeOutSlv11The watchdog of the signal processor
of slave 1 has tripped several times.
W 708TimeOutSlv21The watchdog of the signal processor
of slave 2 has tripped several times.
F 710AutoStrCnt4Autostart meter has expired several
times in succession.
• Contact the SMA Service Line.
• Contact the SMA Service Line if
required.
• Contact the SMA Service Line.
•
Read off the pending and logged
warnings and errors and eliminate
the causes.
• Ensure that the parameter 250.01 AutoStr is set to 3.
W 713TimeOut1The watchdog of the operation
control unit has tripped.
W 715MMCUpdFail1The update cannot be carried out.
The type or format of the SD memory
card is not supported.
F 716VBATMIN2The measured battery voltage of the
master is below the permissible
measurement range.
W 717VBATMINSL11The measured battery voltage of
slave 1 is below the permissible
measurement range.
W 718VBATMINSL21The measured battery voltage of
slave 2 is below the permissible
measurement range.
F 720InvTmpSns4The temperature sensor on the
transformer of the master is defective.
• Contact the SMA Service Line if
required.
• Copy the update file to an SD
memory card with maximum 2 GB
and with FAT-16 format.
• Disconnect the DC loads and
charge the battery.
The usable battery capacity may be too
small, e.g., due to aging. If a load with
high power connects, the battery
voltage collapses.
•
If DC loads are installed in the
system, install load shedding for
DC loads.
•
Ensure that all battery cells are
functional.
• Contact the SMA Service Line.
F 721InvTmpSns4The temperature sensor on the heat
sink of the master is defective.
58SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
No.NameLevelCauseCorrective measures
W 722BatTmpSnsShort1Short circuit of the battery
temperature sensor
W 723BatTmpSnsOpn1Cable break in battery temperature
sensor
W 724AutoStrCntSlv11Maximum number of autostarts for
slave 1 has been reached.
W 725AutoStrCntSlv21Maximum number of autostarts for
slave 2 has been reached.
F 731ClstConfig4Configuration of the cluster is
incorrect.
F 733MstrLoss4Communication to the master is
interrupted.
W 734Slv1Loss1Communication from the master to
slave 1 is interrupted.
W 735Slv2Loss1Communication from the master to
slave 2 is interrupted.
•
Ensure that the battery temperature
sensor is correctly connected
(see the Sunny Island inverter
installation manual).
• Contact the SMA Service Line.
•
Read off the pending and logged
warnings and errors and eliminate
the causes.
• Ensure that the parameter 250.01
AutoStr is set to 3.
•
Change the addresses of the
slaves in the cluster
(see Section9.7, page74)
•
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
•
Ensure that the communication bus
is equipped with a terminator at
both ends.
F 737BootUpdateFail4Updating of the boot loader failed.• Contact the SMA Service Line.
W 738GnSynLoss1Synchronization with the generator
not successful.
F 739SPICom3Internal device communication of the
master is disturbed.
W 740SPIComSlv11Internal device communication of
slave 1 is disturbed.
W 741SPIComSlv21Internal device communication of
slave 2 is disturbed.
• Ensure that the generator can be
started. The fuel level may be too
low.
•
Ensure that a constant and stable
voltage is present at connection
AC2.
•
Ensure that the thresholds for the
generator voltage are correctly
configured.
• Contact the SMA Service Line.
Operating ManualSI30M-44M-60H-80H-BE-en-3059
9 TroubleshootingSMA Solar Technology AG
No.NameLevelCauseCorrective measures
F 743CANCom3Internal device CAN communication
of the master is disturbed.
W 744CANComSlv11Internal device CAN communication
of slave 1 is disturbed.
W 745CANComSlv21Internal device CAN communication
of slave 2 is disturbed.
W 747InvTmpSnsSlv11Temperature sensor on the
transformer of slave 1 is defective.
W 748InvTmpSnsSlv21Temperature sensor on the
transformer of slave 2 is defective.
W 750InvTmpSnsSlv11Temperature sensor on the heat sink
of slave 1 is defective.
W 751InvTmpSnsSlv21Temperature sensor on the heat sink
of slave 2 is defective.
W 753DateInvalid1System time is invalid.• Select the parameter 250.02 Dt
•
Ensure that the terminators in the
communication bus are attached.
•
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
• Contact the SMA Service Line.
• Contact the SMA Service Line.
and set the date. Select the
parameter 250.03 Tm and set the
time.
F 754BoxCom2Communication with Multicluster Box
is interrupted.
W 755LoBatMod11Battery protection mode protects the
battery. Level 1 is active.
W 756LoBatMod21Battery protection mode protects the
battery. Level 2 is active.
W 757LoBatMod31Battery protection mode protects the
battery. Level 3 is active.
F 758McNoVtg2Voltage of the main cluster cannot be
measured at the master.
W 759McNoVtgSv11Voltage of the main cluster cannot be
measured at slave 1.
W 760McNoVtgSlv21Voltage of the main cluster cannot be
measured at slave 2.
•
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
•
Ensure that the communication bus
is equipped with a terminator at
both ends.
• Disconnect the loads, start the
generator, start the Sunny Island
and charge the battery.
• Ensure that all circuit breakers of
the Sunny Island inverters in the
Multicluster Box are closed.
•
Ensure that the cabling at
connection AC1 is correctly
installed.
60SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
No.NameLevelCauseCorrective measures
W 778DSPNoSlv11CAN communication with slave 1 is
faulty.
W 779DSPNoSlv21CAN communication with slave 2 is
faulty.
F 781SlvError4Error at a slave in the main cluster
causing system shutdown.
F 782AIVtgMonFail4Monitoring of the utility grid has
failed.
F 783CANCom2Synchronization in the cluster is
interrupted at the master.
W 784CANComSlv11Synchronization in the cluster is
interrupted at slave 1.
W 785CANComSlv21Synchronization in the cluster is
interrupted at slave 2.
•
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
•
Ensure that the communication bus
is equipped with a terminator at
both ends.
•
Read off the pending and logged
warnings and errors and eliminate
the causes.
• Contact the SMA Service Line.
•
Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
•
Ensure that the communication bus
is equipped with a terminator at
both ends.
F 787VcoreFail3Internal device voltage in the master
is outside the tolerance limits.
F 788VcoreFailSlv13Internal device voltage in slave 1 is
outside the tolerance limits.
F 789VcoreFailSlv23Internal device voltage in slave 2 is
outside the tolerance limits.
W 791RsDspSlv11Signal processor has performed a
W 792RsDspSlv21
W 793TimeOutDspSlv11Time for performing a particular task
W 794TimeOutDspSlv21
W 797AiVtgMonFailSlv1 1Monitoring of the utility grid has
W 798AiVtgMonFailSlv2 1
reset.
has been exceeded.
failed.
• Contact the SMA Service Line.
Operating ManualSI30M-44M-60H-80H-BE-en-3061
9 TroubleshootingSMA Solar Technology AG
9.4.8 External Device and Component Category (8xx)
No.NameLevelCauseCorrective measures
F 801Box4Plausibility check of the
contactors in the
Multicluster Box has failed.
W 805BoxNoGn1Operation with the generator
is not possible.
F 806BoxType4Configuration of the
Sunny Island inverters does
not match the Multicluster Box.
• Contact the SMA Service Line.
•
Reset the off-grid system. For this,
disconnect all loads, AC sources,
generator and DC sources. Open the
load-break switch of the BatFuse. Wait ten
minutes and restart the off-grid system.
Wait until all AC sources are feeding into
the stand-alone grid and all loads are
connected before connecting the
generator.
• Contact the SMA Service Line.
•
Check whether the value of the parameter
250.23 Box matches the
Multicluster Box. If the value does not
match, restart the QCG (see the
Sunny Island inverter installation manual).
• Contact the SMA Service Line.
W 807BoxGdVtg1Voltage of the external energy
source is not within the valid
thresholds for connection.
F 809BoxNoLod4Load-shedding contactor Q5
in the Multicluster Box is not
functioning correctly.
F 810Box15V415 V voltage supply in the
Multicluster Box is defective.
F 811Box24V424 V voltage supply in the
Multicluster Box is defective.
• Acknowledge the error (see Section9.2,
page42).
• Contact the SMA Service Line.
• Reset the off-grid system. For this,
disconnect the off-grid system and restart.
The configuration may be incorrect.
•
Start the QCG and reconfigure
multicluster operation (see the
Sunny Island inverter installation manual).
• Contact the SMA Service Line.
• Contact the SMA Service Line.
62SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
No.NameLevelCauseCorrective measures
W 815BoxQ51Contactor Q5 in the
Multicluster Box is not
functioning correctly.
F 816BoxQ72Contactor Q7 in the
Multicluster Box is not
functioning correctly.
F 817BoxQ94Contactor Q9 in the
Multicluster Box is not
functioning correctly.
F 818BoxPhsFail4One line conductor of a
Sunny Island inverter is
missing.
• Reset the off-grid system. For this,
disconnect the off-grid system and restart.
The configuration may be incorrect.
•
Start the QCG and reconfigure
multicluster operation (see the
Sunny Island inverter installation manual).
• Contact the SMA Service Line.
• Ensure that all circuit breakers of the
Sunny Island inverters in the
Multicluster Box are closed.
• Reset the off-grid system. For this,
disconnect the off-grid system and restart.
•
Search for the missing line conductor and
eliminate the error. For this, with loads
connected, measure the AC voltage
between each line conductor and
between the line conductors and the
neutral conductors. If an AC voltage
deviates from the nominal voltage by
±10%, the corresponding line conductor
is missing.
W 824BoxQ4Overload1Multicluster Box signals an
error at contactor Q4.
W 840eHZ1ComFail1Faulty communication with the
feed-in meter and purchased
electricity meter
W 841eHZ2ComFail1Faulty communication with the
PV production meter
W 842ComBoxFail1Faulty communication
between the Sunny Island and
the Meter Box.
W 843ComBoxWD1The Meter Box watchdog has
triggered.
W 844eHZ1ProtFail1Data protocol of the feed-in
and purchased electricity
meter is unknown.
W 845eHZ2ProtFail1Data protocol of the PV
production meter is unknown.
W 846eHzInFail1Optical probes have been
swapped.
• Contact the SMA Service Line.
• Ensure that the optical probe is correctly
mounted.
• Ensure that the optical probe is correctly
connected.
•
Ensure that the data cables are correctly
installed.
• Contact the SMA Service Line.
• Swap the optical probe connections.
Operating ManualSI30M-44M-60H-80H-BE-en-3063
9 TroubleshootingSMA Solar Technology AG
No.NameLevelCauseCorrective measures
W 847ComHMFaill1Faulty communication
between the Sunny Island and
Sunny Home Manager.
W 851Sic1BatShort1Connection of the battery to
the Sunny Island Charger 1 is
reverse poled or there is a
short circuit.
W 852Sic1BatVtgHi1Battery voltage at the
Sunny Island Charger 1 is too
high.
•
Ensure that the data cables are correctly
installed.
• Ensure that the parameter
250.06 ComBaud is set to 115k Bd.
•
Ensure that the battery is correctly
connected to the DC connection of the
Sunny Island Charger charge controller.
•
Disconnect the PV array from the
Sunny Island Charger and restart the
system. This will ensure that the PV array is
not short-circuited.
•
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.
•
Ensure that all DC sources and DC loads
are correctly configured and connected.
• Reset the system. For this, switch off the
system, wait ten minutes and restart.
W 853Sic1PvVtgHi1PV voltage at the Sunny Island
Charger 1 is too high.
W 854Sic1PvVtgLo1No PV voltage at the
Sunny Island Charger 1 or
there is a short circuit.
W 855Sic1TmpLo1Sunny Island Charger 1
reports: sensor error or device
temperature too low.
W 856Sic1TmpHI1Sunny Island Charger 1
reports: sensor error or device
temperature too high.
• Contact the SMA Service Line if required.
•
Set the Sunny Island Charger to the
operating mode "SMA operation"
(see the Sunny Island Charger charge
controller installation manual).
•
Set the Sunny Island Charger to the
operating mode "SMA operation"
(see the Sunny Island Charger charge
controller installation manual).
64SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
No.NameLevelCauseCorrective measures
W 857Sic1ComLoss1Last communication with the
Sunny Island Charger 1 was
more than 24 hours ago.
W 861Sic2BatShort1Connection of the battery to
the Sunny Island Charger 2 is
reverse poled or there is a
short circuit.
•
Ensure that undamaged CAT5e cables
are used for communication and that the
cables are plugged in correctly.
•
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.
•
Ensure that the communication interfaces
are correctly inserted in the Sunny Island.
•
Ensure that the battery is correctly
connected to the DC connection of the
Sunny Island Charger charge controller.
•
Disconnect the PV array from the
Sunny Island Charger and restart the
system. This will ensure that the PV array is
not short-circuited.
W 862Sic2BatVtgHi1Battery voltage at the
Sunny Island Charger 2 is too
high.
W 863Sic2PvVtgHi1PV voltage at the Sunny Island
Charger 2 is too high.
W 864Sic2PvVtgLo1No PV voltage at the
Sunny Island Charger 2 or
there is a short circuit.
W 865Sic2TmpLo1Sunny Island Charger 2
reports: sensor error or device
temperature too low.
•
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.
•
Ensure that all DC sources and DC loads
are correctly configured and connected.
• Reset the system. For this, switch off the
system, wait ten minutes and restart.
• Contact the SMA Service Line if required.
•
Set the Sunny Island Charger to the
operating mode "SMA operation"
(see the Sunny Island Charger charge
controller installation manual).
W 866Sic2TmpHI1Sunny Island Charger 2
reports: sensor error or device
temperature too high.
Operating ManualSI30M-44M-60H-80H-BE-en-3065
•
Set the Sunny Island Charger to the
operating mode "SMA operation"
(see the Sunny Island Charger charge
controller installation manual).
9 TroubleshootingSMA Solar Technology AG
No.NameLevelCauseCorrective measures
W 867Sic2ComLoss1Last communication with the
Sunny Island Charger 2 was
more than 24 hours ago.
W 871Sic2BatShort1Connection of the battery to
the Sunny Island Charger 2 is
reverse poled or there is a
short circuit.
•
Ensure that undamaged CAT5e cables
are used for communication and that the
cables are plugged in correctly.
•
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.
•
Ensure that the communication interfaces
are correctly inserted in the Sunny Island.
•
Ensure that the battery is correctly
connected to the DC connection of the
Sunny Island Charger charge controller.
•
Disconnect the PV array from the
Sunny Island Charger and restart the
system. This will ensure that the PV array is
not short-circuited.
W 872Sic3BatVtgHi1Battery voltage at the
Sunny Island Charger 3 is too
high.
W 873Sic3PvVtgHi1PV voltage at the Sunny Island
Charger 3 is too high.
W 874Sic3PvVtgLo1No PV voltage at the
Sunny Island Charger 3 or
there is a short circuit.
W 875Sic3TmpLo1Sunny Island Charger 3
reports: sensor error or device
temperature too low.
•
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.
•
Ensure that all DC sources and DC loads
are correctly configured and connected.
• Reset the system. For this, switch off the
system, wait ten minutes and restart.
• Contact the SMA Service Line if required.
•
Set the Sunny Island Charger to the
operating mode "SMA operation"
(see the Sunny Island Charger charge
controller installation manual).
W 876Sic3TmpHI1Sunny Island Charger 3
reports: sensor error or device
temperature too high.
66SI30M-44M-60H-80H-BE-en-30Operating Manual
•
Set the Sunny Island Charger to the
operating mode "SMA operation"
(see the Sunny Island Charger charge
controller installation manual).
SMA Solar Technology AG9 Troubleshooting
No.NameLevelCauseCorrective measures
W 877Sic3ComLoss1Last communication with the
Sunny Island Charger 3 was
more than 24 hours ago.
W 881Sic4BatShort1Connection of the battery to
the Sunny Island Charger 4 is
reverse poled or there is a
short circuit.
•
Ensure that undamaged CAT5e cables
are used for communication and that the
cables are plugged in correctly.
•
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.
•
Ensure that the communication interfaces
are correctly inserted in the Sunny Island.
•
Ensure that the battery is correctly
connected to the DC connection of the
Sunny Island Charger charge controller.
•
Disconnect the PV array from the
Sunny Island Charger and restart the
system. This will ensure that the PV array is
not short-circuited.
W 882Sic4BatVtgHi1Battery voltage at the
Sunny Island Charger 4 is too
high.
W 883Sic4PvVtgHi1PV voltage at the Sunny Island
Charger 4 is too high.
W 884Sic4PvVtgLo1No PV voltage at the
Sunny Island Charger 4 or
there is a short circuit.
W 885Sic4TmpLo1Sunny Island Charger 4
reports: sensor error or device
temperature too low.
•
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.
•
Ensure that all DC sources and DC loads
are correctly configured and connected.
• Reset the system. For this, switch off the
system, wait ten minutes and restart.
• Contact the SMA Service Line if required.
•
Set the Sunny Island Charger to the
operating mode "SMA operation"
(see the Sunny Island Charger charge
controller installation manual).
W 886Sic4TmpHI1Sunny Island Charger 4
reports: sensor error or device
temperature too high.
Operating ManualSI30M-44M-60H-80H-BE-en-3067
•
Set the Sunny Island Charger to the
operating mode "SMA operation"
(see the Sunny Island Charger charge
controller installation manual).
9 TroubleshootingSMA Solar Technology AG
No.NameLevelCauseCorrective measures
W 887Sic4ComLoss1Last communication with the
Sunny Island Charger 4 was
more than 24 hours ago.
W 890BoxMeas2Disturbance in voltage or
current measurement at the
measurement point of the
Multicluster Box for the master.
W 891BoxMeasSlv12Disturbance in voltage or
current measurement at the
measurement point of the
Multicluster Box for slave 1.
W 892BoxMeasSlv22Disturbance in voltage or
current measurement at the
measurement point of the
Multicluster Box for slave 2.
•
Ensure that undamaged CAT5e cables
are used for communication and that the
cables are plugged in correctly.
•
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.
•
Ensure that the communication interfaces
are correctly inserted in the Sunny Island.
•
Ensure that the control and measuring
cable between the Multicluster Box and
the corresponding Sunny Island of the
main cluster is correctly inserted. When
doing so, observe the correct sequence of
the Multicluster Box connections to the
Sunny Island inverters
(see the Sunny Island inverter installation
manual and the Multicluster Box
documentation).
9.4.9 General Category (9xx)
No.NameLevel Cause
F 905CalFail4Unable to read calibration data.
F 906CalFailSlv14Unable to read calibration data of slave 1.
F 907CalFailSlv24Unable to read calibration data of slave 2.
W 915TimeOut1An error has occurred in the program run sequence.
F 952ExtBMSTimeout3Time for communication with the external battery management has been
exceeded.
W 953WrnExtBMSTmOut1Time for communication with the external battery management has been
exceeded.
68SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
9.5 Frequently Asked Questions (FAQ)
9.5.1 Questions Regarding the Sunny Island
The Sunny Island does not switch off even though you have opened the load-break switch of the
BatFuse?
The Sunny Island may still be supplied from the AC side.
•
Switch off all AC sources and disconnect them from the Sunny Island.
The Sunny Island does not switch to energy saving mode?
Another function might have a higher priority than energy saving mode, e.g., equalization charge or full charge.
After automatic disconnection in battery protection mode, the Sunny Island can no longer be started?
•
Only charge the battery when the Sunny Island cannot be switched on (see Section9.6 "Charging the Battery
After Automatic Shutdown in Off-Grid Systems", page72).
• Switch off all loads.
• If there is a generator in the system, start the generator manually. When doing so, observe the warm-up time of
the generator. Five minutes without charge current can result in disconnection of the Sunny Island inverter.
• If sufficient power is available from the generator or the AC sources in the stand-alone grid, e.g., sufficient solar
irradiation for PV inverters, switch the Sunny Island on. AC sources in the stand-alone grid can only start feeding
in electric current once the Sunny Island has been started and is in operation.
9.5.2 Questions Regarding the Sunny Remote Control
The display of the Sunny Remote Control is dark and nothing is displayed?
The Sunny Island might not be switched on.
• Switch the Sunny Island on (see Section4.1, page18).
✖ The Sunny Island does not switch on?
•
Ensure that the fuse in the BatFuse is not defective.
The Sunny Remote Control might not be connected to the Sunny Island.
•
Ensure that the Sunny Remote Control is connected to the Sunny Island.
The RJ45 data cable may be damaged.
•
Replace the RJ45 data cable between the Sunny Remote Control and the Sunny Island.
Parameters cannot be changed?
The parameter might only be displayed in expert mode.
• Switch to expert mode on the Sunny Remote Control (see Section5.4.1, page29).
The parameter might only be changeable in standby mode or in the QCG.
• Observe the messages in the display (see Section5.4.6 "Setting the Parameters", page31).
The parameter may be hidden as it is not required in the configuration set for the system.
• Ensure that the configuration does not deactivate any functions which are required.
Operating ManualSI30M-44M-60H-80H-BE-en-3069
9 TroubleshootingSMA Solar Technology AG
"MMC/SD operation failed !" is shown in the display?
An action with the SD memory card has failed.
• Use a computer to ensure that the SD memory card is free of errors.
•
Ensure that the data cable between the Sunny Remote Control and the Sunny Island is undamaged and that the
plugs are firmly inserted into the pin connectors.
The display shows "WRONG FILE SYSTEM"?
The SD memory card is not formatted with the FAT-16 or FAT-32 file system.
9.5.3 Questions Regarding the Battery
A battery cell is defective?
•
Remove the defective battery cell from the battery system. This reduces the rated voltage of the battery by the
voltage of the battery cell.
•
In the QCG, set the current rated voltage of the battery under New Battery (see Section10.8 "Replacing the
Battery", page78).
The state of charge of the battery is not 100 percent after completion of a full charge?
The power requirements of the loads might have been so high before completion of the full charge that the battery
could not be charged 100 percent.
•If necessary, select the parameter 222.03 AptTmFul and set to a longer time period.
The battery discharges even though the generator is running?
The Sunny Island may not have connected to the generator.
• Eliminate the cause (see Section9.5.4 "Questions Regarding the Generator", page70).
The power of the loads might exceed the power of the generator.
What do you need to do after replacing a battery current sensor?
•
Calibrate the battery current sensor (see the Commissioning section in the Sunny Island inverter installation
manual).
9.5.4 Questions Regarding the Generator
The Sunny Island does not connect to the running generator?
A high output power of the Sunny Island inverter when the battery state of charge is low may lead to the
Sunny Island not being able to raise the AC voltage in the stand-alone grid to the AC voltage of the generator.
The Sunny Island cancels the synchronization.
• To charge the battery, reduce the power of the loads.
The generator voltage might not be within the thresholds for voltage and frequency.
• Check whether the symbol " " is displayed permanently in standard mode.
If the "" symbol is not displayed, ensure that the fuse is not defective or the circuit breaker is activated.
If the "" symbol is not displayed permanently, the generator voltage is sporadically outside the thresholds.
•
Set the thresholds for voltage and frequency of the generator voltage (see the Sunny Island inverter
installation manual).
If the "" symbol is displayed permanently, the Sunny Island is in the warm-up period or is blocked for
connection. Tip: Check whether the Sunny Remote Control displays the "" warning symbol in standard mode.
70SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
The Sunny Island only connects to the generator for a short time?
The generator may be overloaded.
• Select the parameter 234.03 GnCurNom and set it to 75% of the rated current of the generator.
• If possible, reduce the power of the loads.
The maximum permissible generator voltage may be set too low.
•
Select the parameter 234.02 GnVtgMax and set to the maximum generator voltage.
The minimum frequency for the generator voltage may be set too high.
•
Select the parameter 234.05 GnFrqMin and set to the minimum frequency of the generator voltage.
The permitted time 234.14 GnRvTm for reverse power might have been exceeded.
• Check whether warning W401 is registered in the menu 420# Error history. Tip: If a warning was registered,
the warning symbol "" is shown in the standard mode of the Sunny Remote Control.
• Select the 540.02 GnAck parameter and set to Ackn. This acknowledges the generator error.
The Sunny Island does not reconnect to the generator after a disconnection from the generator due
to noncompliance with the thresholds for voltage and frequency?
The Sunny Island is switched with a hysteresis, i.e., the thresholds for connection do not correspond to the thresholds
for disconnection.
• To unload the generator, disconnect unnecessary loads.
• Wait until the voltage and frequency have reached the nominal values.
9.5.5 Questions Regarding Multicluster Systems
Extension clusters remain in standby mode even though the main cluster is in inverter mode?
The data cable between the masters of the individual clusters might not be connected. The master of the main cluster
cannot forward the "Start" command to the masters of the extension clusters.
The multicluster system is not supplying full power?
An extension cluster or individual Sunny Island inverters of an extension cluster might have failed.
High levels of energy are transferred between the clusters in the multicluster system?
The state of charge of the batteries might differ temporarily. The off-grid system equalizes different states of charge
automatically.
The nominal frequencies and nominal voltages may be defined differently.
• Set the frequencies and voltages in the 210# Inverter Settings menu to the same values for all masters.
The battery capacities might differ significantly.
•
Distribute the battery capacities to the clusters as evenly as possible.
Individual battery cells of a battery might have failed.
•
Disconnect defective battery cells and set the new rated voltage and capacity (see Section10.8 "Replacing the
Battery", page78).
Operating ManualSI30M-44M-60H-80H-BE-en-3071
9 TroubleshootingSMA Solar Technology AG
:$5 1,1*
9.6 Charging the Battery After Automatic Shutdown in Off-Grid Systems
When a battery undergoes a deep discharge, the Sunny Island shuts down automatically and you cannot restart the
Sunny Island. In order to start the Sunny Island again after an automatic shutdown, you must charge the battery in
emergency charge mode.
In emergency charge mode, the Sunny Island does not form a separate stand-alone grid, and you can charge the battery
using a generator. Battery management is active in emergency charge mode and the Sunny Island charges the battery
in accordance with the parameter settings. In standby mode or in the QCG, you can adjust the parameters for the battery,
e.g., the battery nominal voltage, if a battery cell fails.
Restricted management functions in emergency charge mode
In emergency charge mode, the generator management is not active. The limits for voltage, current and frequency
are not monitored. Set the maximum current consumption of the Sunny Island inverter for charging the battery in
emergency charge mode. The Sunny Island does not record additional strain on the generator due to loads.
Requirement:
☐ The Sunny Remote Control must be connected to the master.
☐ The system must be an off-grid system.
☐ Lead-acid batteries must be connected.
Procedure
• Connect the generator to connection AC1.
• Charge the battery.
• Disconnect the generator from connection AC1.
• Start the off-grid system.
Connecting the generator to connection AC1
1.
Danger to life from electric shock due to high voltages
High voltages are present on the AC power cables and on the control cables. Touching live parts can result in death
or serious injury due to electric shock.
• Disconnect the Sunny Island from voltage sources (see Section8, page40).
2. If a generator is installed permanently in the off-grid system, bridge the connections AC1 and AC2.
3. If a mobile generator is used, connect the generator to connection AC1 (see the Sunny Island inverter installation
manual).
4. Close the Sunny Island (see Commissioning section in the Sunny Island inverter installation manual).
Charging the battery
1. Switch off all loads.
2. Connect or close all circuit breakers and fuse switch-disconnectors for energy sources.
3. Quickly connect the load-break switch of the BatFuse and close the BatFuse (see BatFuse installation manual).
4. Start the generator.
5. Switch the Sunny Island on (see Section4.1, page18).
72SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG9 Troubleshooting
:$5 1,1*
6. If the Sunny Remote Control displays <Init System>, press and hold the button.
☑ The Sunny Remote Control displays the QCG.
7. Select the menu Emerg Charge and press the button.
8. Confirm with Y.
☑ The Sunny Remote Control shows the ExtCurMax parameter.
9. Set the AC current of the connected generator and press the button.
10. Confirm the AC current with Y.
11. Turn the button to the right and confirm the message Emerg.
Charge Mode Start?
Interrupting the emergency charge mode
You can interrupt the emergency charge mode, e.g., to add diesel to a generator.
• Press and hold the button.
☑ Emergency charge mode is stopped.
• Press and hold the button.
☑ Emergency charge mode is in operation.
Disconnecting the generator from connection AC1
1. Switch the Sunny Island off (see Section4.4, page19).
2. Ensure that the generator is stopped permanently.
3.
Danger to life from electric shock due to high voltages
High voltages are present on the AC power cables and on the control cables. Touching live parts can result in death
or serious injury due to electric shock.
• Disconnect the Sunny Island from voltage sources (see Section8, page40).
4. If the connections AC1 and AC2 are bridged, remove the bridge.
5. If a mobile generator is used, disconnect the generator from connection AC1.
6. Close the Sunny Island (see Commissioning section in the Sunny Island inverter installation manual).
Starting the off-grid system
1. Connect or close all circuit breakers and fuse switch-disconnectors.
2. Start the off-grid system (see Section4.2, page18).
Operating ManualSI30M-44M-60H-80H-BE-en-3073
9 TroubleshootingSMA Solar Technology AG
9.7 Changing Slave Addresses in a Cluster
If you want to change slave addresses (e.g., after replacing a Sunny Island inverter), you can assign the slaves a new
address using the QCG. Only the address is changed, all other configurations remain as they were, e.g., assignment of
the clusters in a multicluster system. When replacing a master, you must reconfigure the cluster (see the quick reference
guide for the relevant system for configuring single-cluster operation or multicluster operation).
Requirements:
☐ All Sunny Island inverters must be switched off.
☐ A Sunny Remote Control is connected to the master only.
Procedure
1. Switch the slave on.
2. Switch the master on.
3. When the Sunny Remote Control shows <Init System>, press and hold the button on the Sunny Remote Control.
☑ An acoustic signal sounds three times and the QCG starts.
4. Select the NewClstCfg menu on the Sunny Remote Control and confirm with Y.
5. Select number of line conductors in the system:
• For a single-phase system, set 1Phs and press the button.
• For a three-phase system, set 3Phs and press the button.
6. Confirm the question Setup new cluster ? with Y.
7. Wait until the inverter LED of slave 1 is flashing and the Sunny Remote Control shows the message To identify
Slave1 press Tss on the Slv.
8. Press the start-stop button on slave 1.
☑ The QCG configures slave 1.
9. To configure slave 2, wait until the inverter LED of slave 2 is flashing and the Sunny Remote Control shows the
message To identify Slave2 press Tss on the Slv.
10. Press the start-stop button on slave 2.
☑ An acoustic signal sounds and the QCG configures slave 2.
11. Press the button on the Sunny Remote Control. This closes the QCG.
☑The Sunny Remote Control switches from display mode to standard mode.
74SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG10 Cleaning and Maintenance
:$5 1,1*
10 Cleaning and Maintenance
10.1 Cleaning and Checking the Sunny Island Inverter Enclosure
• If the enclosure is heavily soiled, use a soft brush to remove the soiling.
• If the enclosure is dusty, remove the dust with a dry soft cloth. Do not use any solvents, abrasives or corrosive liquids.
10.2 Cleaning the Sunny Remote Control
• Clean the Sunny Remote Control with a dry soft cloth. Do not use any solvents, abrasives or corrosive liquids.
10.3 Performing a Manual Equalization Charge in the Off-Grid System
After extended periods without charging (e.g., systems operated seasonally), perform a manual equalization charge at
the end or start of the season.
Requirement:
☐ The Sunny Remote Control must be in standard mode or user mode.
Procedure
1. Select the display page Battery on the Sunny Remote Control and press the button (see Section5.3.1 "Displaying
Parameters and Operating and Setting the System", page27).
2. Select the parameter Equalize and set to Start.
10.4 Checking the Function
• For the first six months after installation of new systems, check every week whether error messages have been
logged. This will reveal any hidden errors in the installation or configuration:
• Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
• Select the menu 420# Error history and check whether any error messages have been logged.
• If error messages have been logged, eliminate the cause (see Section9 "Troubleshooting", page41).
• Check every six months whether error messages have been logged:
• Switch to installer mode on the Sunny Remote Control (see Section5.4.1, page29).
• Select the menu 420# Error history and check whether any error messages have been logged.
• If error messages have been logged, eliminate the cause (see Section9.4 "Logged Warning Messages and Error
Messages", page46).
10.5 Checking the Connections
1.
Danger to life from electric shock due to live voltage
High voltages are present inside the Sunny Island. When the enclosure lid is removed, live components can be
touched which can result in death or serious injury due to electric shock.
• Disconnect the Sunny Island from voltage sources (see Section8, page40).
2. Ensure that the cables on the DC+ and DC‒ connections are securely fastened (torque: 12 Nm).
3. Ensure that the connections are free of corrosion.
4. Ensure that the cables in the AC1 and AC2 connections are securely fastened.
5. Close the Sunny Island (see the Sunny Island inverter installation manual).
6. Switch on all load-break switches and circuit breakers.
Operating ManualSI30M-44M-60H-80H-BE-en-3075
10 Cleaning and MaintenanceSMA Solar Technology AG
:$5 1,1*
:$5 1,1*
10.6 Checking and Maintaining the Battery
Chemical burns and poisoning due to battery electrolyte
If handled inappropriately, battery electrolyte can cause irritation to the eyes, respiratory system, and skin, and it can
be toxic. This may result in blindness and serious chemical burns.
• Protect the battery enclosure against destruction.
• Do not open or deform the battery.
• Do not throw batteries into fire. Batteries may explode in fire.
• Whenever working on the battery, wear suitable personal protective equipment such as rubber gloves, apron,
rubber boots, and goggles.
• Rinse acid splashes thoroughly with clear water and consult a doctor.
• Install, operate, maintain, and dispose of the battery according to the manufacturer's specifications.
Risk of injury due to short-circuit currents
Short-circuit currents in the battery can cause heat build-up and electric arcs. Burns or eye injuries due to flashes may
result.
• Remove watches, rings, and other metal objects.
• Use insulated tools.
• Do not place tools or metal parts on the battery.
Requirement:
☐ The Sunny Remote Control is in user mode.
Procedure
1. Check whether the current state of the battery corresponds with the expected state:
• Select the display page Battery on the Sunny Remote Control.
• Select the parameter Cycle and compare the value with the expected nominal energy throughputs.
• Select the parameter Health (SOH) and compare with the expected usable battery capacity.
If the current state of the battery does not correspond with the expected state, carry out the following steps:
• Ensure that the requirements for the ambient temperature of the battery are met (see documentation of the battery
manufacturer).
• Check and optimize the battery management settings.
• If you cannot determine the cause for the deviation, contact the SMA Service Line.
2. Stop the system and switch off the Sunny Island (see Section6, page33).
3. Open the load-break switch of the BatFuse and secure against reconnection.
4. Check and maintain the battery (see documentation of the battery manufacturer).
5. Quickly connect the load-break switch of the BatFuse and close the BatFuse (see BatFuse installation manual).
6. Start the system.
76SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG10 Cleaning and Maintenance
:$5 1,1*
10.7 Cleaning the Fans
If the Sunny Remote Control shows the warning W137 Derate exceptionally often, one of the fans is probably defective
or blocked.
Procedure
1.
Danger to life from electric shock due to live voltage
High voltages are present inside the Sunny Island. When the enclosure lid is removed, live components can be
touched which can result in death or serious injury due to electric shock.
• Disconnect the Sunny Island from voltage sources (see Section8, page40).
2. Wait for the fans to stop rotating.
3. Check whether the fan guard is dusty or badly clogged.
If the fan guard is dusty, clean it with a vacuum cleaner or a soft brush.
If the fan guard is heavily soiled, remove it and clean it:
• Use a screwdriver to push the two locking tabs at the right-hand
edge of the fan guard to the right and remove them from the
retainer.
• Carefully remove the fan guard.
• Clean the fan guard with a soft brush, a paint brush, a cloth or compressed air.
4. Check whether the fan is soiled.
If the fan is soiled, remove the fan:
• If a fan guard is fitted, remove the fan guard (see step 3).
• Push the front locking tabs of the fan backwards and the rear
locking tabs of the fan forwards.
• Slowly remove the fan from the Sunny Island.
Operating ManualSI30M-44M-60H-80H-BE-en-3077
10 Cleaning and MaintenanceSMA Solar Technology AG
/05*$&
:$5 1,1*
:$5 1,1*
• Release and remove the fan plug.
5.
Damage to the fan due to compressed air
• Clean the fan with a soft brush, a paint brush, or a damp cloth.
6. Insert the fan plug into the jack until it snaps into place.
7. Insert the fan into the Sunny Island until the fan audibly snaps into place.
8. Press the fan guard into the bracket until it audibly snaps into place.
10.8 Replacing the Battery
Risk of injury due to short-circuit currents
Short-circuit currents in the battery can cause heat build-up and electric arcs. Burns or eye injuries due to flashes may
result.
• Remove watches, rings, and other metal objects.
• Use insulated tools.
• Do not place tools or metal parts on the battery.
Danger to life due to incompatible lithium-ion battery
An incompatible lithium-ion battery can lead to a fire or an explosion. With incompatible lithium-ion batteries, it is not
ensured that the battery management is intrinsically safe and will protect the battery.
• Ensure that the battery complies with the locally applicable standards and directives and is intrinsically safe.
• Ensure that the lithium-ion batteries are approved for use with the Sunny Island.
The list of lithium-ion batteries approved for the Sunny Island is updated regularly (see the Technical Information
"List of Approved Lithium-Ion Batteries" at www.SMA-Solar.com).
• If no lithium-ion batteries approved for the Sunny Island can be used, use lead-acid batteries.
78SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG10 Cleaning and Maintenance
:$5 1,1*
/05*$&
Chemical burns and poisoning due to battery electrolyte
If handled inappropriately, battery electrolyte can cause irritation to the eyes, respiratory system, and skin, and it can
be toxic. This may result in blindness and serious chemical burns.
• Protect the battery enclosure against destruction.
• Do not open or deform the battery.
• Do not throw batteries into fire. Batteries may explode in fire.
• Whenever working on the battery, wear suitable personal protective equipment such as rubber gloves, apron,
rubber boots, and goggles.
• Rinse acid splashes thoroughly with clear water and consult a doctor.
• Install, operate, maintain, and dispose of the battery according to the manufacturer's specifications.
Damage to the battery due to incorrect settings
The battery parameters influence the charging behavior of the Sunny Island. The battery will be damaged by incorrect
settings of the parameters for battery type, nominal voltage and capacity.
• Ensure that the values recommended by the battery manufacturer are set for the battery (refer to the technical data
of the battery in the manufacturer documentation).
Procedure
1. Stop the system and switch off the Sunny Island (see Section6, page33).
2. Ensure that the battery is not grounded unintentionally.
If the battery is unintentionally grounded, identify the connection between the battery and ground potential and
remove the unintentional connection. This helps to prevent electric shock caused by malfunction of other system
devices.
3. Open the load-break switch of the BatFuse and secure against reconnection.
4. Remove the battery to be replaced (see battery manufacturer's instructions).
5. Mount and connect the new battery (see manuals of the battery manufacturer). The battery must comply with the
technical requirements of the Sunny Island inverter (refer to the Sunny Island inverter installation manual for technical
data of the DC connection).
6. Quickly connect the load-break switch of the BatFuse and close the BatFuse (see BatFuse installation manual).
7. Switch the Sunny Island on (see Section4.1, page18).
8. If the Sunny Remote Control displays <Init System>, press and hold the button until the Sunny Remote Control
displays the QCG.
9. Select the menu New Battery and press the button.
10. Confirm with Y.
11. Select the parameter BatTyp, set the battery type as follows and confirm with Y.
ValueExplanation
Operating ManualSI30M-44M-60H-80H-BE-en-3079
VRLALead-acid battery with immobilized electrolyte in AGM (Absorbent Glass Mat Separator) or
gel
FLALead-acid battery with liquid electrolyte
LiIon_Ext-BMSLithium-ion battery
10 Cleaning and MaintenanceSMA Solar Technology AG
12. Make the following settings for lead-acid batteries.
• Select the parameter BatVtgLst, set the battery voltage and confirm with Y.
• Select the parameter BatCpyNom, set the C10 capacity of the battery (see the Sunny Island inverter installation
manual for how to calculate the battery capacity) and confirm the battery capacity with Y.
13. Make the following settings for lithium-ion batteries.
• Select the parameter BatCpyNom, set the C10 capacity of the battery (see the Sunny Island inverter installation
manual for how to calculate the battery capacity) and confirm the battery capacity with Y.
14. Select the last page and confirm the question Setup New Battery with Y.
80SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG11 Decommissioning
:$5 1,1*
11 Decommissioning
11.1 Disassembling the Sunny Island
1.
Danger to life from electric shock due to live voltage
High voltages are present inside the Sunny Island. When the enclosure lid is removed, live components can be
touched which can result in death or serious injury due to electric shock.
• Disconnect the Sunny Island from voltage sources (see Section8, page40).
2. Remove all cables from the Sunny Island.
3. Close the Sunny Island.
4. Remove the ventilation grids laterally.
5. If the Sunny Island is protected against theft, loosen the security
screws.
6. Loosen the screws on both sides between the Sunny Island and the
wall mounting bracket using an Allen key (AF 5).
Operating ManualSI30M-44M-60H-80H-BE-en-3081
11 DecommissioningSMA Solar Technology AG
&$87,21
7.
Risk of injury due to the heavy weight of the Sunny Island inverter
• Keep in mind the weight of the Sunny Island inverter.
• With the SI3.0M-11 and SI4.4M-11, remove the Sunny Island
vertically upwards from the wall mounting bracket. To do this,
use the side recess grips. Keep the Sunny Island in a horizontal
position when moving it.
• With the SI6.0H-11 and SI8.0H-11, remove the Sunny Island
vertically upwards from the wall mounting bracket. To do this,
use the side recess grips or a steel rod (diameter: maximum
30 mm). Keep the Sunny Island in a horizontal position when
moving it.
11.2 Packaging the Sunny Island
1. Remove the cable glands from the Sunny Island.
2. Pack the Sunny Island and the cable glands. For this, use the original packaging or packaging that is suitable for the
weight and dimensions of the Sunny Island inverter (for the technical data, see the Sunny Island installation manual).
11.3 Disposing of the Sunny Island
• Dispose of the Sunny Island in accordance with the locally applicable disposal regulations for electronic waste.
82SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG12 Directory of the Parameters in User Mode
12 Directory of the Parameters in User Mode
12.1 Inverter Category
Display page
NameDescriptionValueExplanation
Tot.PowerTotal active power of the Sunny Island inverters
in kW
This parameter is hidden in multicluster systems.
MC.PowerTotal active power of the multicluster system in kW
This parameter is hidden in single systems and
single-cluster systems.
Timer mode Time-controlled operation of the Sunny Island in
off-grid systems
‒‒✓✓
‒‒✖✓
EnableThe Sunny Island is in
time-controlled operation.
DisableTime-controlled operation is
disabled.
✖✓
Setting pages
NameDescriptionValueExplanation
RestartRestart of the Sunny Island inverterYesInitiate restart.✖✓
NoDo not initiate a restart.
Str.DateStart date for time-controlled operation of the
Sunny Island in dd.mm.yy
In time-controlled operation, the Sunny Island
switches from standby mode to operation for the first
time on the start date.
‒‒✖✓
Start timeStart time for time-controlled operation, in hh:mm:ss‒‒✖✓
Run timeRun time for time-controlled operation
The Sunny Island switches to operation from the start
time for the configured run time.
RepetitionRepetition cycle for time-controlled operationSingleConfigures one-time
from the start date.
The start date determines the
weekday.
✖✓
operation.
EnableEnables time-controlled
operation.
Operating ManualSI30M-44M-60H-80H-BE-en-3083
12 Directory of the Parameters in User ModeSMA Solar Technology AG
12.2 Battery Category
Display pages
NameDescriptionValueExplanation
StateOfChargeCurrent battery state of charge in %‒‒✓✓
VoltageBattery voltage in V‒‒✓✓
PowerOutCurrent discharge power of the battery in kW ‒If the value is positive, the
battery is discharging. If the
value is negative, the battery
is charging.
ModeCurrent charging processBoostBoost charge is enabled.✓✓
Full Full charge is enabled.
FloatFloat charge is enabled.
EqualizeEqualization charge is
enabled.
Silent The Sunny Island has
switched to energy saving
mode.
Remain timeRemaining time of current charging process
in hh:mm:ss
Next equalRemaining time until next equalization charge
in days
Health (SOH)Ratio of currently usable capacity to nominal
capacity, in %
CycleNominal energy throughputs of the battery
A nominal energy throughput is the calculated
result of one full charge and discharge of the
battery.
‒‒✓✓
‒‒✓✓
‒‒✓✓
‒‒✓✓
✓✓
Setting page
NameDescriptionValueExplanation
EqualizeManual equalization chargeStartStarts the equalization
charge.
StopStops the equalization
charge.
IdleRemains idle until the
requirements for an
equalization charge are met.
84SI30M-44M-60H-80H-BE-en-30Operating Manual
✓✓
SMA Solar Technology AG12 Directory of the Parameters in User Mode
12.3 Generator Category
Display pages
The Sunny Remote Control displays these pages whenever a generator has been connected and configured.
NameDescriptionValueExplanation
PowerActive power of the generator in kW‒‒✖✓
VoltageGenerator voltage‒‒✖✓
FrequencyFrequency of generator voltage‒‒✖✓
Request bySource for generator requestNoneGenerator has not been requested.✖✓
BatElectricity generator was requested
due to state of charge.
LodGenerator was requested due to
load.
TimGenerator requested due to time.
Run1hGenerator manually requested for
one hour.
StartGenerator was started manually.
ExtSrcReqGenerator was requested
externally.
Run TimeCurrent run time of the generator
in hh:mm:ss
EnergyEnergy supplied by the generator since
the last start in kWh
No.OfStartsNumber of generator starts‒‒✖✓
Op.HoursTotal operating hours of the generator‒‒✖✓
Tot.EnergyTotal energy supplied by the generator
in kWh
‒‒✖✓
‒‒✖✓
‒‒✖✓
Setting page
The Sunny Remote Control displays these pages whenever a generator has been connected and configured.
StartStarts the generator.
Run1hStarts the generator for one hour.
ErrorError confirmation for generator errorAckn.Acknowledges the error.✖✓
Operating ManualSI30M-44M-60H-80H-BE-en-3085
12 Directory of the Parameters in User ModeSMA Solar Technology AG
12.4 Grid Category
Display page
The Sunny Remote Control displays these pages in a battery backup system.
NameDescription
PowerActive power of utility grid in kW✓✖
VoltageVoltage of utility grid in V✓✖
FrequencyFrequency of the utility grid, in Hz✓✖
Setting page
The Sunny Remote Control displays these pages in a battery backup system.
NameDescriptionValueExplanation
ModeManual connection to the
utility grid
AutoEnables automatic connection to the utility grid.✓✖
StopDisconnects the Sunny Island from the utility grid.
StartConnects the Sunny Island to the utility grid.
12.5 SI Charger Category
Display page
The Sunny Remote Control only shows this page if at least one Sunny Island Charger is used in the off-grid system.
NameDescription
Tot.PowerTotal active power of all Sunny Island Charger charge controllers in kW✖✓
Tot.EnergyTotal energy of all Sunny Island Charger charge controllers in kWh✖✓
Day Energy Current daily energy of all Sunny Island Charger charge controllers in kWh✖✓
12.6 Self Cnsmptn Category
Display pages
The Sunny Remote Control displays these pages if the PV generation in a system for increased self-consumption is
transferred to the Sunny Island.
NameDescription
IncPowerCurrent increased self-consumption in kW✓✖
IncTodayToday's increased self-consumption in kWh✓✖
IncEnergyTotal increased self-consumption in kWh✓✖
EnergyTotal self-consumption in kWh✓✖
86SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG12 Directory of the Parameters in User Mode
12.7 Grid Cnsmptn Category
Display page
The Sunny Remote Control displays these pages in a system for increased self-consumption.
NameDescription
PowerPower currently consumed in kW✓✖
EnergyEnergy drawn from the utility grid in kWh✓✖
12.8 Grid Feed Category
Display page
The Sunny Remote Control displays these pages in a system for increased self-consumption.
NameDescription
PowerCurrent feed-in power in kW✓✖
EnergyEnergy fed in in kWh✓✖
12.9 Loads Category
Display page
The Sunny Remote Control displays these pages if the PV generation in a system for increased self-consumption is
transferred to the Sunny Island.
NameDescription
PowerCurrent power of the loads in kW✓✖
EnergyPower consumed by the loads in kWh✓✖
ConStateReserved for future applications✓✖
12.10 PV System Category
Display page
The Sunny Remote Control displays these pages if the PV generation in a system for increased self-consumption is
transferred to the Sunny Island.
NameDescription
PowerCurrent power of the PV system in kW✓✖
EnergyPower fed in by the PV system in kWh✓✖
ConStateReserved for future applications✓✖
Operating ManualSI30M-44M-60H-80H-BE-en-3087
12 Directory of the Parameters in User ModeSMA Solar Technology AG
12.11 System Category
Display page
NameDescriptionValueExplanation
TypeConfiguration of the system1Phase1Single-phase system with one
Sunny Island
1Phase2Single-phase system with two
Sunny Island inverters
1Phase3Single-phase system with three
Sunny Island inverters
3PhaseThree-phase system
MC-BoxMulticluster system
Box TypeType of connected Multicluster Box
This parameter is only shown in multicluster
systems.
DeviceType of cluster
This parameter is only shown in multicluster
systems.
MC-Box-6Multicluster Box 6✖✓
MC-Box-12 Multicluster Box 12
MC-Box-36 Multicluster Box 36
MainClstSunny Remote Control is
connected to the main cluster.
ExtnClstThe Sunny Remote Control is
connected to the extension cluster.
12.12 Time Category
✓✓
✖✓
Display page
NameDescription
DateDate in dd.mm.yyyy✓✓
TimeTime in hh:mm:ss✓✓
Setting page
NameDescriptionExplanation
DateDate in dd.mm.yyyySet the date.✓✓
TimeTime in hh:mm:ssSet the time.✓✓
12.13 Identity Category
Display page
NameDescription
Serial No.Serial number✓✓
FirmwareFirmware version✓✓
88SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG12 Directory of the Parameters in User Mode
12.14 Password Category
Display page
NameDescriptionValueExplanation
LevelCurrent password levelUserSunny Remote Control is in user mode.✓✓
Setting page
NameDescription
SetEnter the installer password.✓✓
RuntimeDisplays the operating hours✓✓
Operating ManualSI30M-44M-60H-80H-BE-en-3089
13 Directory of the Parameters in Installer Mode and Expert ModeSMA Solar Technology AG
13 Directory of the Parameters in Installer Mode and Expert Mode
13.1 Display Values
13.1.1 Inverter (110#)
111# Total
No.NameDescription
111.01 TotInvPwrAtTotal active power of Sunny Island inverters in a cluster in kW.✓✓
111.02 TotInvCurTotal current of Sunny Island inverters in a cluster in A✓✓
111.03 TotInvPwrRtTotal reactive power of Sunny Island inverters in a cluster in kVAr (expert mode)✓✓
111.05 TotLodPwrTotal current active power of the loads in a cluster in kW✓✓
111.06 TotMccLodPwr Total current active power of the loads in a multicluster system in kW✖✓
112# Device
No.NameDescriptionValue
(plain text no.)
112.01 InvOpSttOperating state of the Sunny Island
inverter
112.02 InvPwrAtActive power of the Sunny Island
inverter in kW
112.03 InvVtgVoltage of the Sunny Island inverter
in V
112.04 InvCurCurrent of the Sunny Island inverter
in A
112.05 InvFrqVoltage frequency of the Sunny Island
inverter in Hz
Init (1)Initialization✓✓
Startup (2)Switch from standby
Standby (3)Standby
Run (4)Operation
I-Loop (5)Current-controlled
Error (6)Error status
‒‒✓✓
‒‒✓✓
‒‒✓✓
‒‒✓✓
Explanation
to operation
generator operation
112.06 InvPwrRtReactive power of the Sunny Island
inverter in kVAr (expert mode)
112.07 Rly1SttStatus of multifunction relay 1OffMultifunction relay is
90SI30M-44M-60H-80H-BE-en-30Operating Manual
‒‒✓✓
✓✓
deactivated.
OnMultifunction relay is
activated.
SMA Solar Technology AG13 Directory of the Parameters in Installer Mode and Expert Mode
No.NameDescriptionValue
(plain text no.)
112.08 Rly2SttState of multifunction relay 2OffMultifunction relay is
OnMultifunction relay is
112.12 TrfTmpTemperature of the transformer in °C
(expert mode)
The temperature of the transformer is
displayed in the master of a cluster.
112.13 HsTmpTemperature of the heat sink in the
Sunny Island in °C (expert mode)
The temperature of the heat sink is
displayed in the master of a cluster.
‒‒✓✓
‒‒✓✓
Explanation
✓✓
deactivated.
activated.
113# Slave1
No.NameDescriptionValueExplanation
113.01 InvOpSttSlv1 Operating state of slave 1Init (1)Initialization✓✓
Startup (2)Switch from standby to
operation
Standby (3)Standby
Run (4)Operation
I-Loop (5)Current-controlled generator
operation
Error (6)Error status
113.02 InvPwrAtSlv1 Active power of slave 1 in kW‒‒✓✓
113.03 InvVtgSlv1Voltage of slave 1 in V‒‒✓✓
113.04 InvCurSlv1Current of slave 1 in A‒‒✓✓
113.05 InvPwrRtSlv1Reactive power of slave 1
in kVAr (expert mode)
113.06 Rly1SttSlv1Status of multifunction relay 1 in
slave 1
113.07 Rly2SttSlv1Status of multifunction relay 2 in
slave 1
‒‒✓✓
OffMultifunction relay is
deactivated.
OnMultifunction relay is
activated.
OffMultifunction relay is
deactivated.
OnMultifunction relay is
activated.
✓✓
✓✓
113.09 TrfTmpSlv1Temperature of the transformer
in slave 1 in °C (expert mode)
113.10 HsTmpSlv1Temperature of the heat sink in
slave 1 in °C (expert mode)
Operating ManualSI30M-44M-60H-80H-BE-en-3091
‒‒✓✓
‒‒✓✓
13 Directory of the Parameters in Installer Mode and Expert ModeSMA Solar Technology AG
114# Slave2
No.NameDescriptionValueExplanation
114.01 InvOpSttSlv2 Operating state of slave 2Init (1)Initialization✓✓
Startup (2)Switch from standby to
operation
Standby (3)Standby
Run (4)Operation
I-Loop (5)Current-controlled generator
operation
Error (6)Error status
114.02 InvPwrAtSlv2 Active power of slave 2 in kW‒‒✓✓
114.03 InvVtgSlv2Voltage of slave 2 in V‒‒✓✓
114.04 InvCurSlv2Current of slave 2 in A‒‒✓✓
114.05 InvPwrRtSlv2Reactive power of slave 2
in kVAr (expert mode)
114.06 Rly1SttSlv2State of multifunction relay 1 in
slave 2
114.07 Rly2SttSlv2State of multifunction relay 2 in
slave 2
114.09 TrfTmpSlv2Temperature of the transformer
in slave 2 in °C (expert mode)
114.10 HsTmpSlv2Temperature of the heat sink in
slave 2 in °C (expert mode)
‒‒✓✓
OffMultifunction relay is
deactivated.
OnMultifunction relay is
activated.
OffMultifunction relay is
deactivated.
OnMultifunction relay is
activated.
‒‒✓✓
‒‒✓✓
13.1.2 Battery (120#)
No.NameDescriptionValue (plain
text no.)
✓✓
✓✓
Explanation
120.01 BatSocState of charge of the battery (SOC)
based on the nominal battery capacity
in %
120.02 BatVtgBattery voltage in V‒‒✓✓
120.03 BatChrgVtgCharging voltage setpoint in V‒‒✓✓
120.04 AptTmRmgRemaining absorption time upon
completion of the active charging
process 120.05 BatChrgOp
in hh:mm:ss
92SI30M-44M-60H-80H-BE-en-30Operating Manual
0% to 100%‒✓✓
‒‒✓✓
SMA Solar Technology AG13 Directory of the Parameters in Installer Mode and Expert Mode
120.06 TotBatCurTotal battery current of the cluster in A‒‒✓✓
120.07 BatTmpBattery temperature in °C‒‒✓✓
120.08 RmgTmFulRemaining time until next full charge in
days
120.09 RmgTmEquRemaining time until next equalization
charge in days
120.10 AptPhsStatus of the absorption phaseOff (1)Absorption phase
‒‒✓✓
‒‒✓✓
On (2)Absorption phase is
Explanation
active
✓✓
not active
active
120.11 BatSocErrEstimated error of the state of charge
(SOC) in % (expert mode)
120.12 BatCpyThrpCntNominal energy throughputs of the
battery
A nominal energy throughput is the
calculated result of one full charge and
discharge of the battery.
‒‒✓✓
‒‒✓✓
13.1.3 External (130#)
131# Total
No.NameDescription
131.01 TotExtPwrAtTotal active power of external energy source in kW✓✓
131.02 TotExtCurTotal current of external energy source in A✓✓
131.03 TotExtPwrRtTotal reactive power of the external energy source in kVAr✓✓
Operating ManualSI30M-44M-60H-80H-BE-en-3093
13 Directory of the Parameters in Installer Mode and Expert ModeSMA Solar Technology AG
132# Grid State
No.NameDescriptionValue (plain
text no.)
132.01 GdSttStatus of the
management for the
operation on the utility
grid (expert mode)
Off (1)Grid operation is disabled.✓✓
Init (2)Utility grid has been detected.
Detect (3)Grid monitoring started.
Wait (4)Waiting until the stand-alone grid is
RunVExt (5)The stand-alone grid is synchronized
Feed (6)Grid feed-in into the utility grid is
Silent (7)The Sunny Island is in energy saving
SiStr (8)The Sunny Island is switching to energy
SiStp (9)The Sunny Island is leaving energy
Error (10)An error occurred when connecting.
Explanation
synchronized with the utility grid.
with and connected to the utility grid.
possible.
mode.
saving mode.
saving mode.
Reinit (11)Utility grid has been re-detected.
132.02 GdRmgTmRemaining time of grid
monitoring in hh:mm:ss
‒‒✓✓
133# Gen State
No.NameDescriptionValue (plain
text no.)
133.01 GnDmdSrcSource for generator
request
None (1)No request✖✓
Bat (2)State-of-charge-dependent request
Lod (3)Load-dependent request
Tim (4)Time-controlled request
Run1h (5)Requested for 1 hour
Start (6)Manually started
ExtSrcReq (7)External generator request
Explanation
94SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG13 Directory of the Parameters in Installer Mode and Expert Mode
No.NameDescriptionValue (plain
text no.)
133.02 GnSttStatus of the generator
management
133.03 GnRmgTmRemaining minimum run
time of the generator
in hh:mm:ss
Off (1)Deactivated generator operation✖✓
Init (2)Detecting generator
Ready (3)Waiting for request (ready)
Warm (4)Warming up
Connect (5)Connecting
Run (6)Operation
Retry (7)Restarting
Disconnect (8)Split
Cool (9)Cooling down
Lock (10)Locked after operation
Fail (11)Error
FailLock (12)Locked after error
Reinit (13)Re-detection of the generator
‒‒✖✓
Explanation
133.04 GnRnSttStatus of generator
feedback (expert mode)
Off (1)Off✖✓
On (2)On✖✓
134# Device
No.NameDescription
134.01 ExtPwrAtActive power of external energy source in kW✖✓
134.02 ExtVtgVoltage of external energy source in V✖✓
134.03 ExtCurCurrent of external energy source in A✖✓
134.04 ExtFrqFrequency of external energy source in Hz✖✓
134.05 ExtPwrRtReactive power of external energy source in kVAr (expert mode)✖✓
134.07 ExtLkRmgTmMinimum stop time in hh:mm:ss✖✓
135# Slave1
No.NameDescription
135.01 ExtPwrAtSlv1 Active power of external energy source at slave 1 in kW✖✓
135.02 ExtVtgSlv1Voltage of external energy source at slave 1 in V✖✓
135.03 ExtCurSlv1Current of external energy source at slave 1 in A✖✓
135.04 ExtPwrRtSlv1Reactive power of external energy source at slave 1 in kVAr (expert mode)✖✓
Operating ManualSI30M-44M-60H-80H-BE-en-3095
13 Directory of the Parameters in Installer Mode and Expert ModeSMA Solar Technology AG
136# Slave2
No.NameDescription
136.01 ExtPwrAtSlv2 Active power of external energy source at slave 2 in kW✖✓
136.02 ExtVtgSlv2Voltage of external energy source at slave 2 in V✖✓
136.03 ExtCurSlv2Current of external energy source at slave 2 in A✖✓
136.04 ExtPwrRtSlv2Reactive power of external energy source at slave 2 in kVAr (expert mode)✖✓
13.1.4 Charge Controller (140#)
141# SIC50 Total
No.NameDescription
141.01 TotSicEgyCntInTotal energy of all Sunny Island Charger charge controllers in kWh✖✓
141.02 TSicDyEgyCntInTotal daily energy of all Sunny Island Charger charge controllers in kWh✖✓
141.03 TotSicPvPwrTotal PV power of all Sunny Island Charger charge controllers in W✖✓
141.04 TotSicBatCurTotal battery current of all Sunny Island Charger charge controllers in A✖✓
142# SIC50 1
No.NameDescription
142.01 Sic1EgyCntInTotal energy of Sunny Island Charger charge controller 1 in kWh✖✓
142.02 Sic1TdyEgyCntInDaily energy of Sunny Island Charger charge controller 1 in kWh✖✓
142.03 Sic1PvPwrPV power of Sunny Island Charger charge controller 1 in W✖✓
142.04 Sic1PvVtgPV voltage of Sunny Island Charger charge controller 1 in V✖✓
142.05 Sic1BatVtgBattery voltage of Sunny Island Charger charge controller 1 in V
(expert mode)
142.06 Sic1BatCurBattery current of Sunny Island Charger charge controller 1 in A
(expert mode)
142.07 Sic1HsTmpHeat sink temperature of Sunny Island Charger charge controller 1 in °C
(expert mode)
✖✓
✖✓
✖✓
143# SIC50 2
No.NameDescription
143.01 Sic2EgyCntInTotal energy of Sunny Island Charger charge controller 2 in kWh✖✓
143.02 Sic2TdyEgyCntInDaily energy of Sunny Island Charger charge controller 2 in kWh✖✓
143.03 Sic2PvPwrPV power of Sunny Island Charger charge controller 2 in W✖✓
143.04 Sic2PvVtgPV voltage of Sunny Island Charger charge controller 2 in V✖✓
143.05 Sic2BatVtgBattery voltage of Sunny Island Charger charge controller 2 in V
(expert mode)
143.06 Sic2BatCurBattery current of Sunny Island Charger charge controller 2 in A
(expert mode)
143.07 Sic2HsTmpHeat sink temperature of Sunny Island Charger charge controller 2 in °C
(expert mode)
96SI30M-44M-60H-80H-BE-en-30Operating Manual
✖✓
✖✓
✖✓
SMA Solar Technology AG13 Directory of the Parameters in Installer Mode and Expert Mode
144# SIC50 3
No.NameDescription
144.01 Sic3EgyCntInTotal energy of Sunny Island Charger charge controller 3 in kWh✖✓
144.02 Sic3TdyEgyCntInDaily energy of Sunny Island Charger charge controller 3 in kWh✖✓
144.03 Sic3PvPwrPV power of Sunny Island Charger charge controller 3 in W✖✓
144.04 Sic3PvVtgPV voltage of Sunny Island Charger charge controller 3 in V✖✓
144.05 Sic3BatVtgBattery voltage of Sunny Island Charger charge controller 3 in V
(expert mode)
144.06 Sic3BatCurBattery current of Sunny Island Charger charge controller 3 in A
(expert mode)
144.07 Sic3HsTmpHeat sink temperature of Sunny Island Charger charge controller 3 in °C
(expert mode)
✖✓
✖✓
✖✓
145# SIC50 4
No.NameDescription
145.01 Sic4EgyCntInTotal energy of Sunny Island Charger charge controller 4 in kWh✖✓
145.02 Sic4TdyEgyCntInDaily energy of Sunny Island Charger charge controller 4 in kWh✖✓
145.03 Sic4PvPwrPV power of Sunny Island Charger charge controller 4 in W✖✓
145.04 Sic4PvVtgPV voltage of Sunny Island Charger charge controller 4 in V✖✓
145.05 Sic4BatVtgBattery voltage of Sunny Island Charger charge controller 4 in V
(expert mode)
145.06 Sic4BatCurBattery current of Sunny Island Charger charge controller 4 in A
(expert mode)
145.07 Sic4HsTmpHeat sink temperature of Sunny Island Charger charge controller 4 in °C
(expert mode)
✖✓
✖✓
✖✓
13.1.5 Compact (150#)
The menu 150# Compact displays multiple parameters from the following areas at a glance:
• Battery
• AC measured values of the Sunny Island inverter
• Electric generator or utility grid
• Status of the Sunny Island inverter
Battery (Bat)
Figure16: Overview of the menu Meters Compact for the battery
Operating ManualSI30M-44M-60H-80H-BE-en-3097
13 Directory of the Parameters in Installer Mode and Expert ModeSMA Solar Technology AG
PositionDescriptionParameters
AState of charge of the battery (SOC) in %120.01 BatSoc✓✓
BEstimated error of the state of charge in %120.11 BatSocErr✓✓
CBattery temperature in °C120.07 BatTmp✓✓
DSetpoint of the charge voltage in V120.03 BatChrgVtg✓✓
EBattery voltage in V120.02 BatVtg✓✓
FTotal battery current of the cluster in A120.06 TotBatCur✓✓
AC measured values of the Sunny Island inverter (Inv)
Figure17: Overview of the menu Meters Compact for the AC measured values of the Sunny Island inverter
PositionDescriptionParameters
AVoltage of the Sunny Island inverter in V112.03 InvVtg✓✓
BVoltage frequency of the Sunny Island inverter in Hz112.05 InvFrq✓✓
CReactive power of the inverter in kVAr112.06 InvPwrRt✓✓
DActive power of the inverter in kW112.02 InvPwrAt✓✓
Generator or utility grid (Ext)
Figure18: Overview of the menu Meters Compact for the generator or the battery backup grid
PositionDescriptionParameters
AVoltage of generator or utility grid in V134.02 ExtVtg✓✓
BFrequency of generator or utility grid in Hz134.04 ExtFrq✓✓
CReactive power of generator or utility grid in kVAr134.05 ExtPwrRt✓✓
DActive power of generator or utility grid in kW134.01 ExtPwrAt✓✓
98SI30M-44M-60H-80H-BE-en-30Operating Manual
SMA Solar Technology AG13 Directory of the Parameters in Installer Mode and Expert Mode
Status of the Sunny Island inverter (OpStt)
Figure19: Overview of the menu Meters Compact for the status of the Sunny Island inverter
161.04 SlfCsmpIncPwrIncreased self-consumption in kW✓✖
161.05 GdCsmpPwrAtPower drawn from the utility grid in kW✓✖
161.06 GdFeedPwrAtFeed-in power into the utility grid in kW✓✖
162# Energy
No.NameDescription
162.01 TotLodEgyCntTotal consumption in kWh✓✖
162.02 SlfCsmpIncEgyTotal increased self-consumption in kWh✓✖
162.03 SlfCsmpIncTdyToday's increased self-consumption in kWh✓✖
162.04 SlfCsmpEgyTotal self-consumption in kWh✓✖
162.05 GdCsmpEgyMtr Meter reading purchased electricity in kWh✓✖
162.06 GdCsmpEgyTdy Today's purchased electricity in kWh✓✖
162.07 GdFeedEgyMtrMeter reading grid feed-in in kWh✓✖
162.08 PvEgyMtrMeter reading PV production meter in kWh✓✖
162.09 GdFeedEgyTdyToday's grid feed-in in kWh✓✖
Operating ManualSI30M-44M-60H-80H-BE-en-3099
13 Directory of the Parameters in Installer Mode and Expert ModeSMA Solar Technology AG
163# State
No.NameDescriptionValueExplanation
163.01 BatMntSttStatus of the full charge or
equalization charge
If full charge or
equalization charge with
PV energy has not ended
after 24 hours,
163.01 BatMntStt
automatically switches to
On.
163.02 SlfCsmpSOCAreaCurrent range of the state
of charge of the battery
In systems for increased
self-consumption and in
battery backup systems,
this parameter shows the
range in which the state of
charge of the battery
currently is.
OnFull charge or equalization
charge active, energy is
drawn from the utility grid
WaitIf sufficient PV energy is
available, full charge or
equalization charge active
OffNo full charge or
equalization charge active
PeakShaveSOCRange for prevention of
derating losses
SlfCsmpSOCRange for increased
self-consumption
PVResSOCRange for maintaining the
state of charge of the
battery
BUResSOCRange for the battery
backup system function
BatResSOCRange for protection
against deep discharge
✓✖
✓✖
163.03 SlfCsmpSOCLimThreshold of the current
day of the state of charge
of the battery for increased
self-consumption in %
(expert mode)
The battery can be used for
increased self-consumption
up to the displayed
threshold.
ProtResSOCRange for protection in the
event of deep discharge
5% to 90%‒✓✖
100SI30M-44M-60H-80H-BE-en-30Operating Manual
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.