INSTALLATIONINSTRUCTIONSFOR
CONCEALEDCLOSETANDURINALFLUSHOMETERS
ConcealedClosetFlushometer—
1-1/2”ExposedBackSpud
ConcealedClosetFlushometer—
1-1/2”ExposedTopSpud
ConcealedClosetFlushometer—
1-1/2”BackSpud
ConcealedUrinalFlushometer—
BackSpud
ConcealedUrinalFlushometer—
Model 140
Model 195
ExposedTopSpud
LIMITEDWARRANTY
THEREARENOWARRANTIESWHICHEXTENDBEYONDTHEDESCRIPTIONONTHEFACEHEREOF.INNOEVENTISSLOAN
VALVECOMPANYRESPONSIBLEFORANYCONSEQUENTIALDAMAGESOFANYMEASUREWHATSOEVER.
PRIOR TO INSTALLATION
Check to make certain that the “L” dimension shown on the ushometer
package is correct for your application. Determine the “L” dimension for
your application by using the following formula:
“L” dimension = Wall Thickness (To Nearest Whole Inch) + 2-3/4”
Prior to installing a concealed ushometer, perform the following functions
as illustrated in the Rough-in Diagrams on Pages 2 and 3.
piping, if required.
IMPORTANT:
INSTALL ALL PLUMBING IN ACCORDANCE WITH
APPLICABLE CODES AND REGULATIONS.
• WATERSUPPLYLINESMUSTBESIZEDTOPROVIDEAN
ADEQUATEVOLUMEOFWATERFOREACHFIXTURE.
• FLUSHALLWATERLINESPRIORTOMAKING
CONNECTIONS.
TOTHEVALVEISDETERMINEDBYTHETYPEOFFIXTURE
SELECTED.
THE MINIMUM PRESSURE REQUIRED
requirements.
!!! IMPORTANT !!!
WITHTHEEXCEPTIONOFCONTROL
STOP INLET, DO NOT USE PIPE THREAD
SEALANTORPLUMBINGGREASEONVALVE
COMPONENTS OR COUPLINGS!
TOOLSREQUIREDFORINSTALLATION
Page 2
ROUGH-IN
MODEL 140
MODEL 142
MODELS 143/144
MODEL 153
MODEL 152
MODEL 154
!!! IMPORTANT !!!
WITHTHEEXCEPTIONOFTHECONTROL
STOP INLET, DO NOT USE PIPE THREAD
SEALANT OR PLUMBING GREASE ON
VALVECOMPONENTSORCOUPLINGS.
NOTE:WaterClosetValveswith
“-2.4” Model
DesignationDeliver2.4gpf(9.0Lpf)
THIS PRODUCT CONTAINS MECHANICAL AND/OR
ELECTRICAL COMPONENTS THAT ARE SUBjECT TO
NORMAL WEAR. THESE COMPONENTS SHOULD BE
CHECKEDONAREGULARBASISANDREPLACEDAS
NEEDEDTOMAINTAINTHEVALVE’SPERFORMANCE.
2
!!! IMPORTANT !!!
Page 3
ROUGH-IN (CONTINUED)
MODEL 190
NOTE:Requires1”I.P.S.(25mmDN)SUPPLY
MODEL 192
NOTE:Requires1”I.P.S.(25mmDN)SUPPLY
MODEL 195
MODEL 197
1-INSTALLOPTIONALSWEATSOLDERADAPTER(ONLYIFYOURSUPPLYPIPEDOES
NOTHAVEAMALETHREAD)ANDINSTALLCONTROLSTOP
®
A
water supply pipe until end
of pipe rests against shoulder
NOTE
B
supply line with the outlet
positioned as required.
®
3
Page 4
2-INSTALLVACUUMBREAKERFLUSHCONNECTION
A
3-MOUNTACTUATORASSEMBLYTOWALL
A
B
C
IMPORTANT: WHEN CUTTING SCORED
PIPETOFIT,LEAVEAMINIMUM
OF1-1/4”(32mm)OFSCORINGTO
ENSURE PROPER ENGAGEMENT WITH
COMPRESSION COUPLINGS.
4-INSTALLFLUSHOMETER
A
B
!!! IMPORTANT !!!
USE A SLOAN A-50 “SUPER-WRENCH™”, SLOAN A-109
PLIER WRENCH OR SMOOTH jAWED SPUD WRENCH
TO SECURE ALL COUPLINGS. THIS WILL ELIMINATE
DAMAGETOCHROMEORSPECIALFINISHTHAT
NORMALLYOCCURSWHENSLIP-jOINTPLIERS,PIPE
WRENCHES OR OTHER “TOOTHED” TOOLS ARE USED.
Use a wrench to tighten the following couplings in the order shown.
C
Coupling
D
(1) (2)
(3) (4) and
(5).
NOTE
2
3
4
5
1
Page 5
5-FLUSHOUTSUPPLYLINEANDADjUSTCONTROLSTOP
A
CLOCKWISE
SLOANFLUSHOMETERSAREENGINEEREDFORQUIET
OPERATION.EXCESSIVEWATERFLOWCREATESNOISE,
WHILETOOLITTLEWATERFLOWMAYNOTSATISFYTHE
NEEDSOFTHEFIXTURE.PROPERADjUSTMENTISMADE
B
ush line of any debris or sediment.
WHENTHEPLUMBINGFIXTUREISCLEANSEDAFTER
EACHFLUSHWITHOUTSPLASHINGWATEROUTFROM
THELIPANDAQUIETFLUSHINGCYCLEISACHIEVED.
NEVEROPENCONTROLSTOPTOWHERETHEFLOW
FROMTHEVALVEEXCEEDSTHEFLOWCAPABILITY
OFTHEFIXTURE.INTHEEVENTOFAVALVEFAILURE,
C
THEFIXTUREMUSTBEABLETOACCOMMODATEA
CONTINUOUSFLOWFROMTHEVALVE.
D
rate required for proper cleansing
NEVEROPENTHECONTROLSTOPTO
WHERETHEFLOWFROMTHEVALVEEXCEEDS
THEFLOWCAPABILITYOFTHEFIXTURE.INTHE
EVENTOFAVALVEFAILURE,THEFIXTUREMUST
BE ABLE TO ACCOMMODATE A CONTINUOUS
COUNTERCLOCKWISE ONE
FULL
TROUBLESHOOTING GUIDE
1. Flushometerdoesnotfunction(noush).
2. Volumeofwaterisnotsufcienttosiphonxture.
inside a Closet ushometer, or Low Consumption assembly inside a higher
IMPORTANT—LAWSANDREGULATIONSPROHIBITTHE
USEOFHIGHERFLUSHINGVOLUMESTHANLISTEDON
FIXTUREORFLUSHOMETER.
3. Flushometerclosesoffimmediately.
ForRegalFlushometers—
4. Lengthofushistooshort(ShortFlush).
ForRegalFlushometers—
ForRegalFlushometers—
5. Lengthofushistoolong(LongFlush)orcontinuous.
ForRoyalFlushometers—
ForRegalFlushometers—
NOTE:SIZEOFTHEORIFICEINTHEBYPASSISOFUTMOST
IMPORTANCEFORTHEPROPERMETERINGOFWATER
INTOTHEUPPERCHAMBEROFTHEFLUSHOMETER.DO
NOTENLARGEORDAMAGETHISORIFICE.REPLACEINSIDE
PARTSKITIFCLEANINGDOESNOTCORRECTPROBLEM.
are problems that must be discussed with the building engineer.
6. Chatteringnoiseisheardduringush.
ForRegalFlushometers—
7. LeakingatHandleorPushButtonAssembly.
NOTE:TheB-39SealwilleasilyslideontotheB-40Bushingif
itiswet.
Whenfurtherassistanceisrequired,pleasecontactyour
localSloanRepresentativeorSloanTechnicalSupportat:
orvisitusonlineat:www.sloanvalve.com
!!! IMPORTANT !!!
!!! IMPORTANT !!!
FLOWFROMTHEVALVE.
1-888-SLOAN-14 (1-888-756-2614)
Page 6
CARE AND CLEANING
PARTS LIST
2
MODEL 152
MODEL 142
MODEL 153
22
22
MODEL 195 MODEL 197
3
MODEL 143
MODEL 144
MODEL 154
23
Item Part Description
No. No.
®
®
, Para-o®®
®
MODEL 140
MODEL 150
MODEL 190 MODEL 192
NOTE:
SLOANHEADQUARTERS•10500SEYMOURAVENUE•FRANKLINPARK,IL60131