Slant/Fin GAS Modular Boilers, HOT WATER Modular Boilers, Caravan GGHT-3500E Application Manual

Page 1
®
HOT WATER/GAS Modular Boilers
APPLICATION GUIDE
CONTENTS
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Ratings and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .3,4
Recommended Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Optional factory supply and return headers . . . . . . . . . . . . . .6
Boiler room design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Boiler room air supply requirements . . . . . . . . . . . . . . . . . . . .7
Typical layouts for gas-fired systems . . . . . . . . . . . . . . . . . . .8
Venting a gas-fired system . . . . . . . . . . . . . . . . . . . . . . . . .9,10
Gas piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-12
CODES AND STANDARDS
All Caravan installations must comply to local codes or, in the absence of local codes, to the National Fuel Gas Code, ANSI, Z223.1-latest edition.
In addition where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Codes for controls and safety devices for automatically fired boilers, No. CSD-1. The installation must also conform to the additional requirements of Slant/Fin Instruction Book publication no. GG-100-40 latest edition.
All electrical wiring is to be done in accordance with the National Electrical Code ANSI/NFPA No. 70-latest edition and all local electri­cal codes. The unit must be electrically grounded if an external power source is used.
In Canada, the installation must be in accordance with standards CGA B149.1 and B149.2, installation codes for gas burning appliances and equipment and/or local codes. All electrical connections are to be made in accordance with Standard C.S.A. C22.1 Canadian Electrical Code Part 1 and/or local codes.
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13,14
Field wiring at modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
SC-3 system wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
SC-3 ladder wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
SC-9 space heating wiring . . . . . . . . . . . . . . . . . . . . . . . . . .18
SC-9 space heating ladder wiring . . . . . . . . . . . . . . . . . . . . .19
SC-9 space and domestic hot water wiring . . . . . . . . . . . . .20
SC-9 space and domestic hot water ladder wiring . . . . . . . .21
Caravan warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Request for Caravan rating plate . . . . . . . . . . . . . . . . . . .23,24
INTRODUCTION OF FRESH WATER
Introduction of excessive amounts of fresh water into a system can cause scaling and leave deposits in the boiler and the surrounding pipes. This will lead to inefficient boiler operation and breakdown. Fresh water will enter the system as a result of hidden leaks such as may occur in underground piping. Relief valves should be piped to a location that shows visible signs of relief.
Process applications that use fresh water, require the use of heat exchangers. Any process application that results in introduction of fresh water into a boiler can cause scaling with deposits forming in the boiler and surrounding piping. This will damage the boiler. Introduction of fresh water from leaks will cause similar damage.
In some areas it may be necessary to use a feed water treatment to control the corrosive makeup of the feed water. Check with the local authority, to determine if the feed water will need a conditioning treatment before being supplied to the boiler.
y state and local codes require inter
Man gas boilers
w
Ne
GGT and GGHT Caravan Modules - MEA 283-93-E Vol. II Slant/Fin vent damper NYS approval No. 8859
Pennsylvania:
Caravan boilers are approved in Pennsylvania by PA Cert. 174-BT-S
Please specify if necessar
.
LOCAL
ork City:
Y
CODE
mittent ignition de
y.
O
APPR
ALS
V
vices f
or
Publication No. CG-10-HWG
inted in the U
Pr
www.slantfin.com
.A. 1104
.S
Page 2
Page 3
INTRODUCTION
This Caravan application manual is intended to simplify the selection and application of Slant/Fin modular systems for a variety of space heating and domestic hot water requirements. It applies to gas-fired, hot water applications only. Where intermittent pilot, vent damper or an wholesaler
y additional information is required, contact your local
, Slant/Fin sales representative, or the Slant/Fin factory.
Faster, easier installation
B.
- modules are completely f
actory assembled, including individual jackets to save on-site labor. Optional easy to install return and supply headers with flexible quick connect fittings are available for hot water systems.
C. Safety - each module contains an individual high limit control
and a dual combination gas valve. ASME relief valve is provided
Due to design flexibility of a Caravan modular boiler system, BTU
separately for mounting directly on each module.
input capacities are unlimited.
A. Boiler room design, size and flexibility - since Caravan
. Fast domestic hot water recovery
D
heat exchanger of the positive circulating type.
avan offers an external
- Car
modules have the burner and controls mounted to the front, they can be installed with minimum clearances as per codes, thus
ving a significant amount of floor space.
sa
Table 1: Gas Caravan ratings and dimension/hot water model—GGT Series (100 psi maximum working pressure)
Consists of
Module
Model
Number
Model No.
No.of
Htg.
Mod.
GGT-400E 2 GG-200EC 400 332 1866 280 9.9 14.2 820 1915⁄16 571⁄2 7 831⁄32 151⁄16 121⁄16 4'4" 2" GGT-500E 2 GG-250EC 500 402 2333 350 12.0 16.4 950 235⁄16 595⁄8 8 1011⁄32 187⁄16 811⁄16 4'8" 2" GGT-600E 2 GG-300EC 600 480 2780 417 14.3 18.4 1080 2611⁄16 595⁄8 8 121⁄32 2113⁄16 55⁄16 4'11" 2" GGHT-750E 2 GG-375HEC 750 608 3520 529 18.1 20.6 1230 301⁄16 595⁄8 10 1323⁄32 253⁄16 115⁄16 5'2" 2" GGHT-800E 2 GG-399HEC 798 654 3786 569 19.5 20.6 1230 301⁄16 625⁄8 10 1323⁄32 253⁄16 115⁄16 5'2" 2" GGT-900E 3 GG-300EC 900 720 4173 626 21.5 27.6 1590 2611⁄16 595⁄8 8 121⁄32 2113⁄16 55⁄16 7'7" 2" GGHT-1125E 3 GG-375HEC 1125 912 5286 793 27.2 30.9 1830 301⁄16 595⁄8 10 1323⁄32 253⁄16 115⁄16 7'10" 2" GGHT-1200E 3 GG-399HEC 1197 981 5686 853 29.3 30.9 1830 301⁄16 625⁄8 10 1323⁄32 253⁄16 115⁄16 7'10" 3" GGT-1200E 4 GG-300EC 1200 960 5560 834 28.7 36.8 2140 2611⁄16 595⁄8 8121⁄32 2113⁄16 55⁄16 10'3" 3" GGHT-1500E 4 GG-375HEC 1500 1216 7046 1057 36.3 41.2 2440 301⁄16 595⁄8 10 1323⁄32 253⁄16 115⁄16 10'6" 3" GGT-1500E 5 GG-300EC 1500 1200 6950 1043 35.9 46.0 2675 2611⁄16 595⁄8 8121⁄32 2113⁄16 55⁄16 12'11" 3" GGHT-1600E 4 GG-399HEC 1596 1308 7580 1137 39.0 41.2 2440 301⁄16 625⁄8 10 1323⁄32 253⁄16 115⁄16 10'6" 3" GGHT-1875E 5 GG-375HEC 1875 1520 8806 1321 45.4 51.5 3050 301⁄16 595⁄8 10 1323⁄32 253⁄16 115⁄16 13'2" 3" GGHT-2000E 5 GG-399HEC 1995 1635 9473 1421 48.8 51.5 3050 301⁄16 625⁄8 10 1323⁄32 253⁄16 115⁄16 13'2" 3" GGHT-2250E 6 GG-375HEC 2250 1824 10573 1586 54.4 61.8 3660 301⁄16 595⁄8 10 1323⁄32 253⁄16 115⁄16 15'10" 3" GGHT-2400E 6 GG-399HEC 2394 1962 11373 1706 58.6 61.8 3660 301⁄16 625⁄8 10 1323⁄32 253⁄16 115⁄16 15'10" 3" GGHT-2625E 7 GG-375HEC 2625 2128 12333 1850 63.5 72.1 4270 301⁄16 595⁄8 10 1323⁄32 253⁄16 115⁄16 18'6" 3" GGHT-2800E 7 GG-399HEC 2793 2289 13266 1990 68.3 72.1 4270 301⁄16 625⁄8 10 1323⁄32 253⁄16 115⁄16 18'6" 3" GGHT-3000E 8 GG-375HEC 3000 2432 14093 2115 72.6 82.4 4880 301⁄16 595⁄8 10 1323⁄32 253⁄16 115⁄16 21'2" 3" GGHT-3200E 8 GG-399HEC 3192 2616 15160 2275 78.1 82.4 4880 301⁄16 625⁄8 10 1323⁄32 253⁄16 115⁄16 21'2" 3" GGHT-3375E 9 GG-375HEC 3375 2736 15860 2379 81.7 92.7 5490 301⁄16 595⁄8 10 1323⁄32 253⁄16 115⁄16 23'10" 3" GGHT-3600E 9 GG-399HEC 3591 2943 17060 2559 87.9 92.7 5490 301⁄16 625⁄8 10 1323⁄32 253⁄16 115⁄16 23'10" 3" GGHT-3750E 10 GG-375HEC 3750 3040 17620 2643 90.8 103.0 6100 30 GGHT-4000E 10 GG-399HEC 3990 3270 18953 2843 97.6 103.0 6100 301⁄16 625⁄8 10 1323⁄32 253⁄16 115⁄16 26'6" 3"
I=B=R Ratings
(MBH)
Gross
Input
Output
EDR
Water‡
(Sq.Ft.)
I=B=R
Net
Output†
Boiler
Horse-
power
Water
Content
(gal.)
Ship
Wt.
Draft
Jkt.
Hood
Width
Ht.
1
16 595⁄8 10 1323⁄32 253⁄16 115⁄16 26'6" 3"
Flue
Collar
Draft Hood
Ht. D§
Header
to
Header
Space Btwn. Mods.
Length
with
Header
Header
Size‡‡
83% Efficiency Modules
-700E 2 GG-350HEC 700 581 3368 505 17.3 20.6 1230 30
GGHT
-1050E 3 GG-350HEC 1050 872 5052 758 26 30.9 1830 30
GGHT
-1400E 4 GG-350HEC 1400 1162 6736 1010 34.7 41.2 2440 30
GGHT
-1750E 5 GG-350HEC 1750 1453 8420 1263 43.4 51.5 3050 30
GGHT
-2100E 6 GG-350HEC 2100 1743 10104 1516 52 61.8 3660 30
GGHT
-2450E 7 GG-350HEC 2450 2034 11788 1768 60.7 72.1 4270 30
GGHT
-2800E 8 GG-350HEC 2800 2324 13472 2021 69.4 82.4 4880 30
GGHT
-3150E 9 GG-350HEC 3150 2615 15157 2273 78.1 82.4 5490 30
GGHT
-3500E 10 GG-350HEC 3500 2905 16841 2526 86.7 92.7 6100 30
GGHT
1
16 671⁄8 9
1
16 671⁄8 9
1
16 671⁄8 9
1
16 671⁄8 9
1
16 671⁄8 9
1
16 671⁄8 9
1
16 671⁄8 9
1
16 671⁄8 9
1
16 671⁄8 9
23
13
32 253⁄16 115⁄16 5'2"
23
13
32 253⁄16 115⁄16 7'10"
23
13
32 253⁄16 115⁄16 10'6"
23
13
32 253⁄16 115⁄16 13'2"
23
13
32 253⁄16 115⁄16 15'10"
23
13
32 253⁄16 115⁄16 15'10"
23
13
32 253⁄16 115⁄16 21'2"
23
13
32 253⁄16 115⁄16 23'10"
23
13
32 253⁄16 115⁄16 26'6"
Min.
2" 2" 3" 3" 3" 3" 3" 3" 3"
LARGER SIZES,
FOR
Specify gas b
*
Net r
be consulted before selecting a boiler for installation having unusual piping and/or pick-up requirements. Ratings must be reduced by 4% at 2,000 ft. elevation and an additional 4% f
y name, "Natural" or "Propane".
atings are based on piping and pic
USE MUL
or every additional 1,000 ft. elevation over 2,000 ft.
TIPLES OF
k-up allo
THE ABO
ance of 1.15. Slant/Fin should
w
VE.
atings in square feet based on emission rate of 150 Btuh/sq. ft.
Net r
er to figures 1 and 8.
Ref
§ ‡‡All factory supplied headers use 3" system connections.
Modules in e
Note: For higher capacities, specify correct combination of standard Caravan
xcess of 10 should be piped in par
modules shown.
Headers sho
wn are optional.
allel in two or more batteries.
3
Page 4
Figure 1:
Gas Caravan dimensions and typical piping/hot water models
Design Data Max. ASME Working Pressure: 100 psi Power Requirements: 120 volts, 60 HZ, .34 amps per module
4
Page 5
RECOMMENDED PIPING
Figure 2. Recommended boiler piping for variable circulation
Figure 3. Supply and return piping locations
Figure 4. Instantaneous tankless coil—
two temperature with recirculation
Figure 5. Storage tank from tankless coil with recirculation
5
Page 6
EQUIPMENT INCLUDED GGT SERIES — Hot Water Models
One per module unless otherwise noted
Pre-assembled heat exchangers with built-in air separators
• and insulated jac Base.
• Flue collector.
• Gas burners, gas orifices and manifold assembly.
• Combination gas valve including manual shut-off pressure
• regulator.
• Pilot adjustment and automatic pilot-thermocouple safety.
• Hi-limit control.
• System pressure and temperature gauge (unmounted, one per system).
ket.
Module pressure and temperature gauge (unmounted).
• Module pressure relief valve (ASME) (unmounted). Specify
• 30, 50 or 100 psi. Control header (unmounted, one per system).
• Draft hoods (unmounted).
OPTIONAL EQUIPMENT
• Hot water supply and return header assemblies.
• Control panel with automatic lead lag.
• Spark ignition system.
• Vent dampers.
• External DHW heat exchanger.
Figure 6. Gas Caravan—optional header assembly for all models GGT hot water Caravan systems
*Building piping must be rigidly secured so it cannot
e where connected to headers
v
mo
NOTE: Shown reverse return (Preferred). For direct return, header assembly piping connections may be made at the same end of the boiler bank, not as sho
Some governing agencies do not allow compression type couplings. Consult your local code requirements.
.
wn.
6
Page 7
BOILER ROOM DESIGN
avan modular boiler systems allow better utilization of floor
Car space and per modules are hand truckable, fit through doorways and often may be installed around an existing inoperative boiler. They can be grouped in heating module batteries of single, multiple or angular rows. Gas-fired boiler systems consisting of 11 or more modules should be piped in parallel in two or more batteries. Illustrated on the following page are typical boiler room layouts and dimensional data on the size requirements of gas-fired hot water boilers.
mit future expansion with minimum cost. Caravan
BOILER ROOM AIR SUPPLY
o ensure safe, efficient operation, the modular boiler system must
T be supplied with sufficient air to suppor replacing air entering draft dampers or draft hoods and ventilating the boiler room or areas. For additional information, not listed below, see ANSI,Z223.1, section 5.3.3.
INSTALLATION IN ENCLOSED BOILER ROOM REQUIRES TWO UNOBSTRUCTED OPENINGS FOR PASSAGE OF AIR INT
O THE BOILER ROOM:
t complete combustion,
Figure 7: Correct location of combustion-air supply ducts
1.
2.
3.
4.
IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT, THE AREA OF FREE OPENINGS MUST BE APPROPRIATELY INCREASED TO ACCOMMODATE THE ADDITIONAL LOAD.
wn horizontally from outdoors DIRECTLY
Air dra through an outside wall;
the floor (below burner air inlet) and one louvered opening near the ceiling (above the highest draft regulator), each opening with a minimum FREE air passage area of system input.
Air drawn horizontally through HORIZONTAL DUCTS;
one opening near the floor (below burner inlet) and one opening near the ceiling (above the highest draft regulator), each opening with a minimum FREE air passage area of system input.
Air drawn VERTICALLY from outdoors; one opening at the floor and one opening at the ceiling, each opening with a minimum FREE air passage area of
1 square inch per 4000 BTUH of total system input.
Air drawn from inside the building; one opening near
the floor (below burner inlet) and one opening near the ceiling (above the highest draft regulator), each opening with a minimum FREE air passage area of
1 square inch per 1000 BTUH of total system input.
1 square inch per 4000 BTUH of total
1 square inch per 2000 BTUH of total
one louvered opening near
UNLESS PROPERLY CONTROLLED, AVOID THE USE OF FORCED VENTILATION, SINCE IT CAN CREATE AN UNDESIRABLE PRESSURE DIFFERENTIAL BETWEEN BOILER ROOM AND AIR SOURCE.
7
Page 8
Figure 8. Typical layouts for gas-fired systems
8
Page 9
VENTING A GAS-FIRED SYSTEM
A boiler v comb Caravan: a draft hood for each module, a breeching manifold and a chimney.
Draft Hood
The draft hood is part of each boiler module, although shipped in a separate carton. It compensates for excessive draft that can be caused by the venturi effect of winds passing over the top of the chim­ney. The dimensional relationships between the draft hood, the boiler and surface on which the boiler is mounted, are critical. These factors are all interdependent in allowing the draft hood to function without moving parts. Attempts to alter these dimensions can result in unsafe oper Note: When mounting the modules on a r the platf on all sides.
Breeching
Breeching is a term used to describe a manifold(s) that connects individual boiler modules to a chimney. Breeching is usually construct­ed of sheet metal having a smooth interior surface with all joints made tight against leakage. Pitch breeching up toward chimney. Horizontal breeching size should be maintained for the total length. Any transi­tions should be made after 4 modules. Connection should be made at a 45° angle in the direction of the chimney. See figure 10.
Table 2. Breeching dimensions for gas-fired systems
Based on single row of modules with no elbows. * Height measured from top of draft hood to top of chimney. NOTE: For conditions other than those shown, consult factory, or
enting system provides an escape path for the products of
ustion. There are three major components for venting a gas-fired
ating conditions.
aised platform, be certain
orm extends past the edge of the modules at least 3 inches
GGT and GGHT series: hot water boilers.
Consists of Chimney Height*
Model No.
GGT-400E 2 GG-200EC 9" 9" 8" 8" GGT-500E 2 GG-250EC 10" 9" 9" 8" GGT-600E 2 GG-300EC 12" 10" 10" 9" GGHT-700E 2 GG-350HEC 12" 12" 10" 10" GGHT-750E 2 GG-375HEC 12" 12" 12" 10" GGHT-800E 2 GG-399HEC 12" 12" 12" 10" GGT-900E 3 GG-300EC 14" 12" 12" 12" GGHT-1050E 3 GG-350HEC 14" 14" 14" 12" GGHT-1125E 3 GG-375HEC 14" 14" 14" 12" GGHT-1200E 3 GG-399HEC 16" 14" 14" 12" GGT-1200E 4 GG-300EC 16" 14" 14" 12"
-1400E
GGHT GGHT-1500E 4 GG-375HEC 16" 16" 16" 14" GGT-1500E 5 GG-300EC 16" 16" 16" 14"
-1600E 4 GG-399HEC 18" 16" 16" 14"
GGHT GGHT-1750E 5 GG-350HEC 18" 18" 16" 14" GGHT-1875E 5 GG-375HEC 18" 18" 18" 16" GGHT-2000E 5 GG-399HEC 20" 18" 18" 16" GGHT-2100E 6 GG-350HEC 20" 18" 18" 16” GGHT-2250E 6 GG-375HEC 20" 20" 18" 16"
-2400E
GGHT GGHT-2450E 7 GG-350HEC 20" 20" 20" 18" GGHT-2625E 7 GG-375HEC 22" 20" 20" 18"
-2800E
GGHT GGHT-2800E 8 GG-350HEC 22" 22” 20” 18”
-3000E
GGHT GGHT-3150E 9 GG-350HEC 24" 22" 22" 20" GGHT-3200E 8 GG-399HEC 24" 22" 22" 20"
-3375E
GGHT GGHT-3500E 10 GG-350HEC 24" 24" 22” 20" GGHT-3600E 9 GG-399HEC 26" 24" 24" 20" GGHT-3750E 10 GG-375HEC 26" 24" 24" 22"
-4000E 10 GG-399HEC 26" 26" 24" 22"
GGHT
National Fuel Gas Code NFP
No. of
Modules
4 GG-350HEC 16" 16" 16" 14"
6
7 GG-399HEC 22" 22" 20" 18"
8
9 GG-375HEC 24" 24" 22" 20"
Module
No.
GG-399HEC
GG-375HEC
A 54
20
Feet25Feet30Feet50Feet
20" 20" 18"
20"
22" 20"
22"
24"
Run breeching as high as clear
ertical rise of individual boiler vents. Note that this does not alter
v
ance permits to obtain maximum
chimney height (the height from hood skirt to chimney top). The portion of chimney height rising directly above each hood is most effective in preventing spillage. When the boiler room is in unheated space, insulate vent pipe and breeching to maintain flue gas temper­ature and good chimney operation.
It is not permitted to lower draft hood skirt height to achieve pitch, or to compensate for low ceilings
breeching, a dr are locally specified and w
For some combinations of low chimneys, ceilings and long
.
aft inducer may be needed. Inducers when required
arrantied. The breeching should extend
into, but not beyond, the chimney liner.
Chimney
Caravan gas-fired modular boilers operate efficiently with masonry or prefabricated chimneys as well as with “Type B” or double-walled metal vent pipe. This latter type of chimney construction is generally the least expensive. Chimney height is usually governed by the building height and the size of the boilers (see Table 1). However, the chimney should be high enough to minimize the effects of turbulent winds and pressure common near roof-top obstruction. A vent cap should be used where permitted for additional protection against adverse wind conditions and precipitation. The National Board of Fire Underwriters recommend that the chimney should extend at least 3 feet above the roof and be 2 feet higher than any obstruction within 10 feet.
Sizing Horizontal Breeching Connectors and Chimneys for Gas­Fired Systems
Horizontal breeching connectors shall be constant sized.The chimney and the horizontal breeching connector are sized using Table 2. When there are multiple banks of boilers, the horizontal breeching connector for each bank is sized using Table 2. To size the common horizontal breeching connector, add up the total input and refer to Table 2 to size.
The minimum chimney opening will be equal to the size of the largest horizontal breeching section connected to it.
Horizontal Breeching Connector Length
The MAXIMUM length of the horizontal breeching connector length between the chimney and the closest boiler shall
NOT be longer than 12 inches per inch of horizontal breeching connector diameter, i.e. if the horizontal breeching connector is 16" D., the
MAXIMUM length
from the chimney to the first boiler would be 16" x 12" or 192 inches.
MINIMUM length shall be 12 inches regardless of the horizontal
The breeching connector diameter
. See figure 9.
9
Page 10
Connector Rise: Connector rise is the length of the pipe connecting the top of the draft hood to the system breeching above. The diameter of this pipe varies depending upon BTU input, chimney height and the length of the connector. Fig.9 (Dim. “B”) shows the location of this pipe in a typical appli­cation. Table 2a depicts the proper diameter (Dim. “C”) of the connector rise depending upon its total length (top of the dr
ve).
abo
Vent Connector Diameters (20’ chimney*)
Model
Flue Outlet
Size
3' High
aft hoods to the breeching
Connector
2' High
1' High
Figure 9. Connector rise
GG-200C
7” 7” 7” 8” GG-250C 8” 8” 8” 10” GG-300C 8” 8” 10” 10” GG-350H 9” 9” 10” 12” GG-375-HC 10” 10” 10” 12” GG-399-HC 10” 10” 12” 12”
Based on single row of modules with no elbows.
TE: For conditions other than those shown, consult factory, or National Fuel
NO
Gas Code NFP
A 54
Figure 10. Suggested venting system constructions
10
Page 11
GAS PIPING
This section contains sizing and construction recommendations
or fuel supply piping to Caravan gas-fired modular boiler
f systems. Gas-fired equipment must conform not only to codes of local regulator may be imposed by the utility or gas supplier. Therefore, the following information should be considered only as a guideline.
Figure 11 illustrates a typical gas supply line installation. It consists of a main between the utility’s meter box and the boiler system, a main shut-off valve sediment trap, gas header pipe and drip legs on individual boilers.
y agencies, but also to additional specifications that
Individual gas lines to individual boiler modules should be
3
4" diameter. Size of gas main and header pipes depends on volume of gas required and acceptable pressure drop between meter and modules’ gas regulator valves. Minimum pressure required at each valve is 5 inches of water column for natural gas and 11 inches for propane gas, measured while all boilers and other gas-fired equipment on the same meter are firing. Small variations in gas flow can be compensated for by adjusting gas regulator valves. However, final pressure of gas header must vary no more than + 0.3 in. of water column.
Table 3: Gas consumption rate
hot water boilers only
Gas
Model No.
GGT-400E 400 GGT-500E 500 GGT-600E 600 GGHT-700E 700 GGHT-750E 750 GGHT-800E 798 GGT-900E 900 GGHT-1050E 1050 GGHT-1125E 1125 GGHT-1200E 1197 GGT-1200E 1200 GGHT-1400E 1400 GGHT-1500E 1500 GGT-1500E 1500 GGHT-1600E 1596 GGHT-1750E 1750 GGHT-1875E 1875 GGHT-2000E 1995 GGHT-2100E 2100 GGHT-2250E 2250 GGHT-2400E 2394 GGHT-2450E 2450 GGHT-2625E 2625 GGHT-2800E 2793 GGHT-2800E 2800 GGHT-3000E 3000 GGHT-3150E 3150 GGHT-3200E 3192 GGHT-3375E 3375 GGHT-3500E 3500 GGHT-3600E 3591 GGHT-3750E 3750 GGHT-4000E 3990
Consumption In CFH
Gas Main Sizing
To determine the correct pipe diameter for the gas main serving a specific Caravan system, proceed as follows: a. Follow the building plans, find total length of straight pipe between supply from gas
meter and boiler gas header.
b. Using data in Table 4, calculate equivalent linear length of screw pipe fittings used in
fabrications of main. Add this to figure from step (a) to obtain equivalent total length.
c. Find Caravan gas consumption in cubic feet per hour from Table 3 in hot water
systems.
d. Multiply the system total hourly gas consumption by flow correction value from
Table 5. e. Locate system’s total equivalent pipe length in right column of Table 6. f. Move vertically to the system’s corrected flow rate calculated in step (c). If this value
falls between two of those listed, select larger value. g. From this point move horizontally to the left column and read suggested pipe
diameter for gas main.
Table 4: Equivalent linear length in feet of standard iron pipe fittings for natural gas
Pipe
Size
Inches Standard
Elbow Valve
Medium
Sweep
Long
Sweep Gate Globe Angle
Return
Bend
Side
Outlet
Tee
1/2 0.84 0.52 0.41 0.031 2.50 1.12 1.25 1.66
3/4 1.17 0.73 0.57 0.044 3.50 1.84 1.75 2.33
1 1.57 0.98 0.77 0.057 4.68 2.11 2.34 3.11
1-1/4
2.19
1.37
1.07
0.082 6.54 2.94 3.27 4.35
1-1/2 2.63 1.64 1.29 0.098 7.84 3.52 3.92 5.21
2 3
3.55
5.72
2.23
3.59
1.74 1.320 10.60 4.77 5.30 7.05
2.81
2.130
17.08
7.69
8.84 11.40
ypical gas suppl
Figure 11.
T
y line installation
11
Page 12
able 5. Characteristics of various fuel gases
T
Type
of Gas
al 1000 Btu 1.00
Natur
Heating
Valve*†
Flow
Correction
Factor
Propane 2500 Btu 1.10
* per cubic f † Consult fuel supplier for actual BTU value.
Table 6. Gas main sizing guide
Iron Pipe
oot
Nominal
Size
Inches
Internal
Diameter
Inches
10 20 30 40 50 60 70
Equivalent
Length of Pipe, Feet
1/4 .364 32 22 18 15 14 12 11 3/8 .493 72 49 40 34 30 27 25 1/2 .622 132 92 73 63 56 50 46 3/4 .824 278 190 152 130 115 105 96
1 1.049 520 350 285 245 215 195 180 1 1/4 1.380 1,050 730 590 500 440 400 370 1 1/2 1.610 1,600 1,100 890 760 670 610 560
2 2.067 3,050 2,100 1,650 1,450 1,270 1,150 1,050 2 1/2 2.469 4,800 3,300 2,700 2,300 2,000 1,850 1,700
3 3.068 8,500 5,900 4,700 4,100 3,600 3,250 3,000
4 4.026 17,500 12,000 9,700 8,300 7,400 6,800 6,200
80 90 100 125 150 175 200
1/4 .364 11 10 9 8 8 7 6 3/8 .493 23 22 21 18 17 15 14 1/2 .622 43 40 38 34 31 28 26 3/4 .824 90 84 79 72 64 59 55
1 1.049 170 160 150 130 120 110 100 1 1/4 1.380 350 320 305 275 250 225 210 1 1/2 1.610 530 490 460 410 380 350 320
2 2.067 990 930 870 780 710 650 610 2 1/2 2.469 1,600 1,500 1,400 1,250 1,130 1,050 980
3 3.068 2,800 2,600 2,500 2,200 2,000 1,850 1,700
4 4.026 5,800 5,400 5,100 4,500 4,100 3,800 3,500
Maximum capacity of pipe in cubic feet of gas per hour for gas pres­sures of 0.5 psig or less and a pressure drop of 0.3 inch water column (based on a 0.60 specific gravity gas).
12
Page 13
CONTROLS
THE BOILER STAGING CONCEPT
The heart of the Caravan boiler plant is a temperature-actuated control system that automatically stages only those boiler modules needed to meet the heating demand in a given period,
y conserving fuel.
thereb
In a staging control system, each stage ordinarily activates one boiler module. With appropriate wiring, multiple modules can be
rouped within a stage.
g
During a fluctuation in heating requirements, a large central boiler cycles on and off to match heat output to building demand. A staged modular boiler system, on the other hand, will energize only as many modules as the system load requires. Only one stage cycles at a time. The other stages remain off or operate continuously, thereby performing at peak efficiency. For example, in a 10 module boiler system, with the heating load at 61% of capacity efficiency se "off cycles on and off, resulting in lower efficiency.
Over-sizing is a major factor in poor system efficiency. Most of the time a single central boiler is oversized. Historical data shows that many single central boilers are considerably oversized even at the outdoor temperature for which they were designed. Modular boiler systems are not oversized by more than a portion of one module, regardless of the load.
The Caravan control system automatically compensates for seasonal temperature changes. It energizes more or fewer modules depending on changes of outside temperature, system water temperature, or both. Modules save energy by operating in long cycles at full-rated output and maximum efficiency.
, six of the modules operate continuously at peak
. Fractional heating requirements are supplied by the
venth "cycling" module, while the remaining three modules are
." This is in contrast to a single large central boiler that simply
CONTROL SYSTEM SELECTION
Slant/Fin offers two controls to step fire a hot water Caravan sys­tem. The SC-3 and SC-9 controls fulfill a wide range of applica­tions. They control the boiler system and are not intended to be the sole building temperature control. They do not replace zoning the system or the thermostats that control these zones.
SC-3 Control
The SC-3 control allo Generally each stage controls 1 module. However, it is possible to
e more than 1 module activ
v
ha
Standard programmable features include: system activation or de-activ supply w temper outdoor temperature and indoor design temperatures.
The vie outdoor air temper target supply water temperature and running time for each stage.
ation based on outdoor temper
ater temper
ature; adjustable delay between stages; adjustable
w men
ws up to 3 stages in a Car
ated with each stage.
ature;
adjustable design target supply water
ature;
u on the control includes error messages
ature, actual supply water temperature,
avan system.
um target
minim
, actual
This control can be programmed as follows:
1. Outdoor reset: The supply water temperature is automatically adjusted up or do temperature. The control automatically controls the
umber of modules required to maintain required supply
n water temperature. Setpoint temperature: The control can be programmed
2. to maintain a set supply water temperature. The control automatically controls the number of modules activated to maintain the setpoint temperature.
SC-9 Control
The SC-9 control allows up to 9 stages of operation for space heating, domestic water or combination, in a Caravan system. Generally each stage controls 1 module. However, it is possible to have more than one module activated with each stage.
Standard programmable features include: system activation or de-activation based on outdoor temperature; minimum target supply water temperature; adjustable design target supply water temperature; adjustable delay between stages; adjustable outdoor and indoor design temperatures; delay to allow combustion air damper to open; ability to provide equal run time rotation of boiler modules; fixed lead of a module when Caravan system activates; first on/last off or first on/first off for modules; control of primary circulator and periodic exercising of primary circulator when system is inactive.
The view menu on the control includes error messages, actual outdoor air temperature, actual supply water temperature, target water temperature, running time for each stage and the difference between supply water and return water temperatures.
The SC-9 can be programmed as follows:
1. Outdoor reset: The supply water temperature is automatically increased as outdoor temperature decreases and decreased as outdoor temperature increases. The control activates only the number of stages required to maintain the required supply water temperature.
Setpoint temperature: The control maintains a set supply
2. water temperature. The control activates only the number of stages required to maintain the setpoint temperature. Setpoint temperature may be used for a Caravan system that is dedicated f
3.
Domestic hot water: The domestic hot water controls override the SC-9 control for only those modules used to heat the domestic hot w
ater are isolated from space heating system until
hot w demand f not used for domestic hot water heating remain under control of SC-9 control.
Slant/Fin off external tankless heaters as options for use with the SC-9 control.
or domestic hot water is satisfied. The modules
or use as v
ater
ers domestic hot w
wn based on outdoor
olume w
The modules f
.
ater heating.
or domestic
ater control packages and
13
Page 14
BILL OF MATERIALS FOR SC SERIES CONTROLLERS
Material List for SC-3
• SC-3 modular boiler control (part# 435-084) 1 Outdoor sensor (part # 339-070)
• 1 Universal sensor to be used as supply water sensor (part # 339-071)
• 1 Plastic tie strap
Material List for SC-9
• 1 SC-9 modular boiler control (part # 435-085)
• 1 Outdoor sensor (part # 339-070)
• 2 Universal sensors (part # 339-071)
- 1 to be used as supply water sensor
- 1 can be used as return water sensor
• 2 Plastic tie straps
Other Options
• Immersion well for supply water sensor: to be installed in control header supplied with Caravan
• High Limit (manual reset) and Immersion Well: to be installed in control header supplied with Caravan
• Low Water Cut-Off (manual reset): to be installed in modular boiler headers above modules cast iron heat exchanger
• Domestic Hot Water Control Packages: components include EMV valve; setpoint aquastat L6006A with immersion well. This is to be used with external heat exchanger such as Caravan BP series brazed plate heat exchangers.
Circulators, switches, wiring and other relays are provided by contractor.
include:
14
Page 15
FIELD WIRING AT MODULES
15
Page 16
SC-3 SYSTEM WIRING DIAGRAM
16
Page 17
SC-3 LADDER WIRING DIAGRAM
17
Page 18
SC-9 SPACE HEATING WIRING DIAGRAM
18
Page 19
SC-9 SPACE HEATING LADDER WIRING DIAGRAM
19
Page 20
SC-9 SPACE AND DOMESTIC HOT WATER WIRING DIAGRAM
20
Page 21
SC-9 SPACE AND DOMESTIC HOT WATER LADDER WIRING DIAGRAM
21
Page 22
Slant/Fin
Limited Five-Year Warranty
for Caravan Modular and Individual Commercial Application
Cast-iron Hot Water Boilers in Space Heating Applications.
WARRANTY INCLUDES: FIRST YEAR:
warranty service procedure, for a period of one year after or
iginal installation, of all parts found to be defectively
manufactured.
W
ARRANTY INCLUDES:
SECOND THROUGH FIFTH YEAR:
for the second through fifth year after original installation, of cast iron heat exchanger found to be defectively manufac­tured, at no cost for the replacement part. The repaired or exchanged part will be warranted for only the unexpired portion of the original warranty.
This warranty extends only to boilers in space heating applications. See “Additional Warranty Terms” section for more details.
Warranty extends only to boilers which have been properly installed, operated and maintained in accordance with Slant/Fin installation instructions and all applicable codes. Warranty applies only if the boiler has remained at all times in the location at which it was originally installed. Slant/Fin makes no express warranties other than the warranties contained herein.
WARRANTY EXCLUDES:
All labor charges incurred by any person in connection with the examination, removal, and repair of parts claimed to be defective and the installation of replacement parts.
Repair or replacement in accordance with
Repair or replacement
AFTER FIRST YEAR, WARRANTY EXCLUDES:
All boiler components other than a cast-iron heat exchanger, such as, sheet metal base, jacket, insulation, combustion chamber, tankless heater exhaust and air inlet piping, burner enclosure, mixing elbow, gas and air orifice, blower assem­bly, air filter and electrical and mechanical components furnished to Slant/Fin by other manufacturers, such as pumps, relays, controls, gauges, etc.
PROCEDURE FOR WARRANTY SERVICE:
or warranty service, provide the person who installed your
F Slant/Fin boiler with the following information: boiler model number and serial number (from the boiler rating plate) and the date of installation. That person will notify the Slant/Fin wholesaler from whom the boiler was purchased.
Part(s) claimed to be defective must be returned through trade channels and replacement part(s) will, if warranty conditions are met, be provided by Slant/Fin through the wholesaler.
If there are any questions about the coverage of this warranty, please contact Slant/Fin at the address shown below.
LIMITATIONS ON IMPLIED WARRANTIES AND DAMAGES:
Slant/Fin assumes no liability for damages or unsatisfactory performance of any kind which is a result of improper installation.
The part claimed to be defective shall be returned to Slant/Fin. The cost of shipment to Slant/Fin is borne by the consumer.
Damage caused by water that contains excessive lime, calcium, or other contaminants.
Boilers operated with combustion air that may be contaminated by chemicals or improper fuel additives.
Improper b maintenance procedures.
NOTE:
application that causes significant quantities of fresh make up water to enter the system is not permitted. Such applications can be met with a heat exchanger that will maintain the boilers in a closed system.
urner adjustments, control settings or
Boilers are to be used in closed systems
y
An
.
Technical Service Department
Slant/Fin Corporation, 100 Forest Drive at East Hills, Greenvale, N. Y. 11548 • (516) 484-2600
Slant/Fin's sole obligation in the event of a breach of any implied w warranties of merchantability and fitness for a particular pur warranties are limited in duration to the period of time after the date of or
This warranty does not cover claims for incidental or consequential damages resulting from a breach of any express or implied warranty or any other reason.
Some states do not allo warranty lasts or the exclusion or limitation of incidental or consequential damages. So the above limitation or e
THIS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
arranty (including, but not limited to, implied
pose) is limited to repair or replacement, and all such
.
e
iginal installation as stated abo
w limitations on how long an implied
xclusion ma
y not apply to y
WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS
ou.
v
22
Page 23
CARAVAN SYSTEM RATING PLATE
System rating plate format for Caravan modular boiler system.
System rating plates are available upon request using the form on the back cover.
Page 24
REQUEST FOR CARAVAN SYSTEM RATING PLATE
Each individual Caravan module is shipped with a rating plate bearing the model, serial number, capacities and certifications for that module. A modular boiler system is a single boiler. To meet local requirements, a system rating plate will be issued b pro
vide the information indicated on this page.
y Slant/Fin upon request. Just
Slant/Fin Tech
Service
FAX THIS REQUEST TO: 516-484-6958
PHONE: 516-484-2600
Requested by:
Mail to:
PLEASE USE CARE TO MAKE SURE THE PROPER SYSTEM MODEL IS INDICATED
Type of System:
Phone:
Phone:
NOTE:
INDICATE ACCURATELY
Some model numbers are similar, such as GGT-600 and GGT-600E etc.
COMPLETE WITH LETTER SUFFIX.
INCLUDE ALL LETTERS AND ZEROS, ENTER ALL
USE A SEPARATE FORM FOR EACH SYSTEM
Gas
Oil
Water
Steam
BE ACCURATE!
Natural Gas
Propane
Dual Fuel
Required
Required
INFORMATION ASKED FOR!
INDICATE SYSTEM MODEL NUMBER BELOW:
INDICATE SERIAL NUMBERS OF INDIVIDUAL MODULES (Please write legibly)
System serial number assigned Done by
DO NO
FOR
WRITE BELOW THIS LINE
T
SLANT/FIN USE ONL
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600
F
AX:
Y
(516) 484-5921
Canada:
Slant/Fin
TD/L
L
TEE
, Mississauga, Ontar
www.slantfin.com
io
Loading...